Lighting Protection Level I Lighting Protection Level II Lighting Protection Level III Lighting Protection Level IV Type 1, Type 2, Type 3 Follow the right direction ... step by step ... SPD SELECTION GUIDE Surge Protection Device

Transcript of HAKEL přepěťová ochrana - SPD SELECTION GUIDE · Step 1 (object selection) Step 2 (selection of...

Page 1: HAKEL přepěťová ochrana - SPD SELECTION GUIDE · Step 1 (object selection) Step 2 (selection of SPD T1) Lightning arrester Type 1 HS50-50/3+0 Art. No. 10 090 Lightning arrester

HAKEL spol. s r.o. Bratří Štefanů 980500 03 Hradec KrálovéČeská republika

tel.: +420 494 942 300fax: +420 494 942 303e-mail: [email protected]

Lighting Protection Level ILighting Protection Level IILighting Protection Level III

Lighting Protection Level IV

Type 1, Type 2, Type 3

Buildings with considerable level of protection LPL I ( Iimp = 100 kA)

Hospitals Banks

Transmission point for GSM,BTS

Water stations

Power plants Aerodrome control tower

Buildings with danger of explosion

Bigger industrial buildings

Buildings with particular importance

TNC

1 1+0

HS50-50

SubstationSwitchboard (kWh)Main switchboard

5 metres cable or decoupling element

PI-L (16-120 A )

3 3+0HS50-50/3+0

SubstationSwitchboard (kWh)Main switchboard

SPC25/3+0

Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

TNS

1

1+1

HS50-50/1+1 SubstationSwitchboard (kWh)Main switchboard

5 metres cable or decoupling element

PI-L (16-120 A )

2+0

HS50-50/2+0

3

3+1

SPC25/3+1Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

4+0

SPC25/4+0

LIGHTNING PROTECTION LEVEL I

Classification of typical objects

System No.of phases

Circuit Type 1-at boundaries of LPZ 0-1 (lightning arrester)

CoordinationT1 and T2

SPD type Installation < 5 m

Step 1(object selection)

Step 2(selection of SPD T1)

Lightning arrester Type 1

HS50-50/3+0 Art. No. 10 090

Lightning arrester Type 1 + Type 2

SPC25/4+0 Art. No. 10 651

EBB

EBB

LIGHTNING PROTECTION LEVEL I

Type 3 - at boundaries of LPZ 2-3 (surge arrester) SPD + EMI filter Additional SPD

SPD type Installation SPD type Installation

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1DSM

Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.PI-3k(16-120A)

Pk2

ZS-1I

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1POutlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.

PDU

PI-3k(16-120A)

PK2

ZS-1DSM

Type 2 - at boundaries of LPZ 1-2(surge arrester)

CoordinationT2 a T3

SPD type Installation < 5 m

100 %(property protection)

Step 4(selection of SPD T3)

Step 3(selection of SPD T2)

PIII-275/3+0 Art. No. 24 001

Surge arrester Type 3

PI-k8 Art. No. 30 080

Surge arrester Type 2

ZS-1P Art. No. 32 006

PIIIM-275/3+1 Art. No. 27 022

PI-3k120 Art. No. 30 307

EQUIPMENT

EQUIPMENT

PIIIM-275Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIII-275/3+0

PIII-275/3+0

If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIII-275/1+1Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIIIM-275/1+1

PIII-275/3+1If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIIIM-275/3+1

the queen of power the queen of power

Follow the right direction ... step by step ...

SPD SELECTION GUIDE

HAKEL spol. s r.o.Bratri Stefanu 980500 03 Hradec KraloveCzech Republic

tel.: +420 494 942 300fax: +420 494 942 303e-mail: [email protected]

H-SV-21-09-2016-EN-sales

SurgeProtection

Device

Selection guideSelection guide

Page 2: HAKEL přepěťová ochrana - SPD SELECTION GUIDE · Step 1 (object selection) Step 2 (selection of SPD T1) Lightning arrester Type 1 HS50-50/3+0 Art. No. 10 090 Lightning arrester

HAKEL spol. s r.o. Bratří Štefanů 980500 03 Hradec KrálovéČeská republika

tel.: +420 494 942 300fax: +420 494 942 303e-mail: [email protected]

Lighting Protection Level ILighting Protection Level IILighting Protection Level III

Lighting Protection Level IV

Type 1, Type 2, Type 3

Buildings with considerable level of protection LPL I ( Iimp = 100 kA)

Hospitals Banks

Transmission point for GSM,BTS

Water stations

Power plants Aerodrome control tower

Buildings with danger of explosion

Bigger industrial buildings

Buildings with particular importance

TNC

1 1+0

HS50-50

SubstationSwitchboard (kWh)Main switchboard

5 metres cable or decoupling element

PI-L (16-120 A )

3 3+0HS50-50/3+0

SubstationSwitchboard (kWh)Main switchboard

SPC25/3+0

Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

TNS

1

1+1

HS50-50/1+1 SubstationSwitchboard (kWh)Main switchboard

5 metres cable or decoupling element

PI-L (16-120 A )

2+0

HS50-50/2+0

3

3+1

SPC25/3+1Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

4+0

SPC25/4+0

LIGHTNING PROTECTION LEVEL I

Classification of typical objects

System No.of phases

Circuit Type 1-at boundaries of LPZ 0-1 (lightning arrester)

CoordinationT1 and T2

SPD type Installation < 5 m

Step 1(object selection)

Step 2(selection of SPD T1)

Lightning arrester Type 1

HS50-50/3+0 Art. No. 10 090

Lightning arrester Type 1 + Type 2

SPC25/4+0 Art. No. 10 651

EBB

EBB

LIGHTNING PROTECTION LEVEL I

Type 3 - at boundaries of LPZ 2-3 (surge arrester) SPD + EMI filter Additional SPD

SPD type Installation SPD type Installation

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1DSM

Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.PI-3k(16-120A)

Pk2

ZS-1I

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1POutlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.

PDU

PI-3k(16-120A)

PK2

ZS-1DSM

Type 2 - at boundaries of LPZ 1-2(surge arrester)

CoordinationT2 a T3

SPD type Installation < 5 m

100 %(property protection)

Step 4(selection of SPD T3)

Step 3(selection of SPD T2)

PIII-275/3+0 Art. No. 24 001

Surge arrester Type 3

PI-k8 Art. No. 30 080

Surge arrester Type 2

ZS-1P Art. No. 32 006

PIIIM-275/3+1 Art. No. 27 022

PI-3k120 Art. No. 30 307

EQUIPMENT

EQUIPMENT

PIIIM-275Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIII-275/3+0

PIII-275/3+0

If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIII-275/1+1Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIIIM-275/1+1

PIII-275/3+1If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIIIM-275/3+1

the queen of power the queen of power

SPD SELECTION GUIDE

HAKEL spol. s r.o.Bratri Stefanu 980500 03 Hradec KraloveCzech Republic

tel.: +420 494 942 300fax: +420 494 942 303e-mail: [email protected]

H-SV-21-09-2016-EN-sales

SurgeProtection

Device

Selection guideSelection guide

Page 3: HAKEL přepěťová ochrana - SPD SELECTION GUIDE · Step 1 (object selection) Step 2 (selection of SPD T1) Lightning arrester Type 1 HS50-50/3+0 Art. No. 10 090 Lightning arrester

HAKEL spol. s r.o. Bratří Štefanů 980500 03 Hradec KrálovéČeská republika

tel.: +420 494 942 300fax: +420 494 942 303e-mail: [email protected]

Lighting Protection Level ILighting Protection Level IILighting Protection Level III

Lighting Protection Level IV

Type 1, Type 2, Type 3

Buildings with considerable level of protection LPL I ( Iimp = 100 kA)

Hospitals Banks

Transmission point for GSM,BTS

Water stations

Power plants Aerodrome control tower

Buildings with danger of explosion

Bigger industrial buildings

Buildings with particular importance

TNC

1 1+0

HS50-50

SubstationSwitchboard (kWh)Main switchboard

5 metres cable or decoupling element

PI-L (16-120 A )

3 3+0HS50-50/3+0

SubstationSwitchboard (kWh)Main switchboard

SPC25/3+0

Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

TNS

1

1+1

HS50-50/1+1 SubstationSwitchboard (kWh)Main switchboard

5 metres cable or decoupling element

PI-L (16-120 A )

2+0

HS50-50/2+0

3

3+1

SPC25/3+1Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

4+0

SPC25/4+0

LIGHTNING PROTECTION LEVEL I

Classification of typical objects

System No.of phases

Circuit Type 1-at boundaries of LPZ 0-1 (lightning arrester)

CoordinationT1 and T2

SPD type Installation < 5 m

Step 1(object selection)

Step 2(selection of SPD T1)

Lightning arrester Type 1

HS50-50/3+0 Art. No. 10 090

Lightning arrester Type 1 + Type 2

SPC25/4+0 Art. No. 10 651

EBB

EBB

LIGHTNING PROTECTION LEVEL I

Type 3 - at boundaries of LPZ 2-3 (surge arrester) SPD + EMI filter Additional SPD

SPD type Installation SPD type Installation

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1DSM

Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.PI-3k(16-120A)

Pk2

ZS-1I

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1POutlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.

PDU

PI-3k(16-120A)

PK2

ZS-1DSM

Type 2 - at boundaries of LPZ 1-2(surge arrester)

CoordinationT2 a T3

SPD type Installation < 5 m

100 %(property protection)

Step 4(selection of SPD T3)

Step 3(selection of SPD T2)

PIII-275/3+0 Art. No. 24 001

Surge arrester Type 3

PI-k8 Art. No. 30 080

Surge arrester Type 2

ZS-1P Art. No. 32 006

PIIIM-275/3+1 Art. No. 27 022

PI-3k120 Art. No. 30 307

EQUIPMENT

EQUIPMENT

PIIIM-275Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIII-275/3+0

PIII-275/3+0

If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIII-275/1+1Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIIIM-275/1+1

PIII-275/3+1If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIIIM-275/3+1

the queen of power the queen of power

SPD SELECTION GUIDE

HAKEL spol. s r.o.Bratri Stefanu 980500 03 Hradec KraloveCzech Republic

tel.: +420 494 942 300fax: +420 494 942 303e-mail: [email protected]

H-SV-21-09-2016-EN-sales

SurgeProtection

Device

Selection guideSelection guide

Page 4: HAKEL přepěťová ochrana - SPD SELECTION GUIDE · Step 1 (object selection) Step 2 (selection of SPD T1) Lightning arrester Type 1 HS50-50/3+0 Art. No. 10 090 Lightning arrester

Buildings with considerable level of protection LPL II ( Iimp = 75 kA)

Industrial buildings

Administrative buildings

Schools

Supermarkets

Cathedrals

Objects connected by buried cable.

TNC

1 1+0

HS50-50

SubstationSwitchboard (kWh)Main switchboard

5 metres cable or decoupling element

PI-L (16-120 A )

3 3+0HS50-50/3+0

SubstationSwitchboard (kWh)Main switchboard

SPC25/3+0

Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

TNS

1

1+1

HS50-50/1+1 SubstationSwitchboard (kWh)Main switchboard

5 metres cable or decoupling element

PI-L (16-120 A )

2+0

HS50-50/2+0

3

3+1

SPC25/3+1Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

4+0

SPC25/4+0

LIGHTNING PROTECTION LEVEL IILIGHTNING PROTECTION LEVEL II

Classification of typical objects

System No.of phases

Circuit Type 1-at boundaries of LPZ 0-1 (lightning arrester)

CoordinationT1 and T2

SPD type Installation < 5 m

Step 1(object selection)

Step 2(selection of SPD T1)

Type 3 - at boundaries of LPZ 2-3 (surge arrester) SPD + EMI filter Additional SPD

SPD type Installation SPD type Installation

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1DSM

Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.PI-3k(16-120A)

Pk2

ZS-1I

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1POutlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.

PDU

PI-3k(16-120A)

PK2

ZS-1DSM

Type 2 - at boundaries of LPZ 1-2(surge arrester)

CoordinationT2 a T3

SPD type Installation < 5 m

100 %(property protection)

Step 4(selection of SPD T3)

Step 3(selection of SPD T2)

Lightning and surge arrester Type 1 + Type 2

SPC25/3+0 Art. No. 10 736

PIII-275/3+0 Art. No. 24 001

Surge arrester Type 3

PI-k8 Art. No. 30 080

Surge arrester Type 2

ZS-1P Art. No. 32 006

PI-3k120 Art. No. 30 307

PIIIM-275/3+1 Art. No. 27 022Lightning arrester Type 1 + Type 2

SPC25/4+0 Art. No. 10 651

EBB

EBB

EQUIPMENT

EQUIPMENT

PIIIM-275Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIII-275/3+0

PIII-275/3+0

If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIII-275/1+1Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIIIM-275/1+1

PIII-275/1+1If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIIIM-275/3+1

PIIIM-275Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIII-275/3+0

PIII-275/3+0

If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIII-275/1+1Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIIIM-275/1+1

PIII-275/1+1If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIIIM-275/3+1

Buildings with considerable level of protection LPL III and IV ( Iimp = 50 kA)

LPL IIIApartment houses

Small administartive buildings

Family houses

Agricultural structures

LPL IVBuildings and halls without occurrence of persons and internal equipment

Objects with the main back-up fuse up to 63A connected by buried cable.

TNC

1 1+0

SPC25

Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

3 3+0PIV12.5/3+0

Main switchboard5 metres cable or

decoupling elementPI-L (16-120 A )

SPC25/3+0

Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

TNS

1

1+1

SPC25/1+1Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

2+0

SPC25/2+0

3

3+1

SPC12,5/3+1

Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

4+0

PIV12,5/4+0

Main switchboard5 metres cable or

decoupling elementPI-L (16-120 A)

LIGHTNING PROTECTION LEVEL III a IVLIGHTNING PROTECTION LEVEL III a IV

Classification of typical objects

System No.of phases

Circuit Type 1-at boundaries of LPZ 0-1 (lightning arrester)

CoordinationT1 and T2

SPD type Installation < 5 m

Step 1(object selection)

Step 2(selection of SPD T1)

Type 3 - at boundaries of LPZ 2-3 (surge arrester) SPD + EMI filter Additional SPD

SPD type Installation SPD type Installation

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1DSM

Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.PI-3k(16-120A)

Pk2

ZS-1I

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1POutlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.

PDU

PI-3k(16-120A)

PK2

ZS-1DSM

Type 2 - at boundaries of LPZ 1-2(surge arrester)

CoordinationT2 a T3

SPD type Installation < 5 m

100 %(property protection)

Step 4(selection of SPD T3)

Step 3(selection of SPD T2)

Lightning arrester Type 1

PIV 12,5-275/3+0 Art. No. 10 152

PIII-275/3+0 Art. No. 24 001

Surge arrester Type 3

PI-k8 Art. No. 30 080

Surge arrester Type 2

ZS-1P Art. No. 32 006

PI-3k120 Art. No. 30 307

PIIIM-275/3+1 Art. No. 27 022Lightning arrester Type 1

PIV 12,5-275/4+0 Art. No. 10 195

EQUIPMENT

EQUIPMENT

EBB

EBB

the queen of powerthe queen of power the queen of power the queen of power

Selection guide Selection guideSelection guide Selection guide

Page 5: HAKEL přepěťová ochrana - SPD SELECTION GUIDE · Step 1 (object selection) Step 2 (selection of SPD T1) Lightning arrester Type 1 HS50-50/3+0 Art. No. 10 090 Lightning arrester

Buildings with considerable level of protection LPL II ( Iimp = 75 kA)

Industrial buildings

Administrative buildings

Schools

Supermarkets

Cathedrals

Objects connected by buried cable.

TNC

1 1+0

HS50-50

SubstationSwitchboard (kWh)Main switchboard

5 metres cable or decoupling element

PI-L (16-120 A )

3 3+0HS50-50/3+0

SubstationSwitchboard (kWh)Main switchboard

SPC25/3+0

Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

TNS

1

1+1

HS50-50/1+1 SubstationSwitchboard (kWh)Main switchboard

5 metres cable or decoupling element

PI-L (16-120 A )

2+0

HS50-50/2+0

3

3+1

SPC25/3+1Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

4+0

SPC25/4+0

LIGHTNING PROTECTION LEVEL IILIGHTNING PROTECTION LEVEL II

Classification of typical objects

System No.of phases

Circuit Type 1-at boundaries of LPZ 0-1 (lightning arrester)

CoordinationT1 and T2

SPD type Installation < 5 m

Step 1(object selection)

Step 2(selection of SPD T1)

Type 3 - at boundaries of LPZ 2-3 (surge arrester) SPD + EMI filter Additional SPD

SPD type Installation SPD type Installation

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1DSM

Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.PI-3k(16-120A)

Pk2

ZS-1I

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1POutlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.

PDU

PI-3k(16-120A)

PK2

ZS-1DSM

Type 2 - at boundaries of LPZ 1-2(surge arrester)

CoordinationT2 a T3

SPD type Installation < 5 m

100 %(property protection)

Step 4(selection of SPD T3)

Step 3(selection of SPD T2)

Lightning and surge arrester Type 1 + Type 2

SPC25/3+0 Art. No. 10 736

PIII-275/3+0 Art. No. 24 001

Surge arrester Type 3

PI-k8 Art. No. 30 080

Surge arrester Type 2

ZS-1P Art. No. 32 006

PI-3k120 Art. No. 30 307

PIIIM-275/3+1 Art. No. 27 022Lightning arrester Type 1 + Type 2

SPC25/4+0 Art. No. 10 651

EBB

EBB

EQUIPMENT

EQUIPMENT

PIIIM-275Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIII-275/3+0

PIII-275/3+0

If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIII-275/1+1Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIIIM-275/1+1

PIII-275/1+1If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIIIM-275/3+1

PIIIM-275Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIII-275/3+0

PIII-275/3+0

If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIII-275/1+1Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIIIM-275/1+1

PIII-275/1+1If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIIIM-275/3+1

Buildings with considerable level of protection LPL III and IV ( Iimp = 50 kA)

LPL IIIApartment houses

Small administartive buildings

Family houses

Agricultural structures

LPL IVBuildings and halls without occurrence of persons and internal equipment

Objects with the main back-up fuse up to 63A connected by buried cable.

TNC

1 1+0

SPC25

Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

3 3+0PIV12.5/3+0

Main switchboard5 metres cable or

decoupling elementPI-L (16-120 A )

SPC25/3+0

Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

TNS

1

1+1

SPC25/1+1Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

2+0

SPC25/2+0

3

3+1

SPC12,5/3+1

Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

4+0

PIV12,5/4+0

Main switchboard5 metres cable or

decoupling elementPI-L (16-120 A)

LIGHTNING PROTECTION LEVEL III a IVLIGHTNING PROTECTION LEVEL III a IV

Classification of typical objects

System No.of phases

Circuit Type 1-at boundaries of LPZ 0-1 (lightning arrester)

CoordinationT1 and T2

SPD type Installation < 5 m

Step 1(object selection)

Step 2(selection of SPD T1)

Type 3 - at boundaries of LPZ 2-3 (surge arrester) SPD + EMI filter Additional SPD

SPD type Installation SPD type Installation

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1DSM

Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.PI-3k(16-120A)

Pk2

ZS-1I

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1POutlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.

PDU

PI-3k(16-120A)

PK2

ZS-1DSM

Type 2 - at boundaries of LPZ 1-2(surge arrester)

CoordinationT2 a T3

SPD type Installation < 5 m

100 %(property protection)

Step 4(selection of SPD T3)

Step 3(selection of SPD T2)

Lightning arrester Type 1

PIV 12,5-275/3+0 Art. No. 10 152

PIII-275/3+0 Art. No. 24 001

Surge arrester Type 3

PI-k8 Art. No. 30 080

Surge arrester Type 2

ZS-1P Art. No. 32 006

PI-3k120 Art. No. 30 307

PIIIM-275/3+1 Art. No. 27 022Lightning arrester Type 1

PIV 12,5-275/4+0 Art. No. 10 195

EQUIPMENT

EQUIPMENT

EBB

EBB

the queen of powerthe queen of power the queen of power the queen of power

Selection guide Selection guideSelection guide Selection guide

Page 6: HAKEL přepěťová ochrana - SPD SELECTION GUIDE · Step 1 (object selection) Step 2 (selection of SPD T1) Lightning arrester Type 1 HS50-50/3+0 Art. No. 10 090 Lightning arrester

Buildings with considerable level of protection LPL II ( Iimp = 75 kA)

Industrial buildings

Administrative buildings

Schools

Supermarkets

Cathedrals

Objects connected by buried cable.

TNC

1 1+0

HS50-50

SubstationSwitchboard (kWh)Main switchboard

5 metres cable or decoupling element

PI-L (16-120 A )

3 3+0HS50-50/3+0

SubstationSwitchboard (kWh)Main switchboard

SPC25/3+0

Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

TNS

1

1+1

HS50-50/1+1 SubstationSwitchboard (kWh)Main switchboard

5 metres cable or decoupling element

PI-L (16-120 A )

2+0

HS50-50/2+0

3

3+1

SPC25/3+1Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

4+0

SPC25/4+0

LIGHTNING PROTECTION LEVEL IILIGHTNING PROTECTION LEVEL II

Classification of typical objects

System No.of phases

Circuit Type 1-at boundaries of LPZ 0-1 (lightning arrester)

CoordinationT1 and T2

SPD type Installation < 5 m

Step 1(object selection)

Step 2(selection of SPD T1)

Type 3 - at boundaries of LPZ 2-3 (surge arrester) SPD + EMI filter Additional SPD

SPD type Installation SPD type Installation

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1DSM

Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.PI-3k(16-120A)

Pk2

ZS-1I

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1POutlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.

PDU

PI-3k(16-120A)

PK2

ZS-1DSM

Type 2 - at boundaries of LPZ 1-2(surge arrester)

CoordinationT2 a T3

SPD type Installation < 5 m

100 %(property protection)

Step 4(selection of SPD T3)

Step 3(selection of SPD T2)

Lightning and surge arrester Type 1 + Type 2

SPC25/3+0 Art. No. 10 736

PIII-275/3+0 Art. No. 24 001

Surge arrester Type 3

PI-k8 Art. No. 30 080

Surge arrester Type 2

ZS-1P Art. No. 32 006

PI-3k120 Art. No. 30 307

PIIIM-275/3+1 Art. No. 27 022Lightning arrester Type 1 + Type 2

SPC25/4+0 Art. No. 10 651

EBB

EBB

EQUIPMENT

EQUIPMENT

PIIIM-275Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIII-275/3+0

PIII-275/3+0

If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIII-275/1+1Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIIIM-275/1+1

PIII-275/1+1If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIIIM-275/3+1

PIIIM-275Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIII-275/3+0

PIII-275/3+0

If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIII-275/1+1Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIIIM-275/1+1

PIII-275/1+1If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIIIM-275/3+1

Buildings with considerable level of protection LPL III and IV ( Iimp = 50 kA)

LPL IIIApartment houses

Small administartive buildings

Family houses

Agricultural structures

LPL IVBuildings and halls without occurrence of persons and internal equipment

Objects with the main back-up fuse up to 63A connected by buried cable.

TNC

1 1+0

SPC25

Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

3 3+0PIV12.5/3+0

Main switchboard5 metres cable or

decoupling elementPI-L (16-120 A )

SPC25/3+0

Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

TNS

1

1+1

SPC25/1+1Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

2+0

SPC25/2+0

3

3+1

SPC12,5/3+1

Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

4+0

PIV12,5/4+0

Main switchboard5 metres cable or

decoupling elementPI-L (16-120 A)

LIGHTNING PROTECTION LEVEL III a IVLIGHTNING PROTECTION LEVEL III a IV

Classification of typical objects

System No.of phases

Circuit Type 1-at boundaries of LPZ 0-1 (lightning arrester)

CoordinationT1 and T2

SPD type Installation < 5 m

Step 1(object selection)

Step 2(selection of SPD T1)

Type 3 - at boundaries of LPZ 2-3 (surge arrester) SPD + EMI filter Additional SPD

SPD type Installation SPD type Installation

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1DSM

Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.PI-3k(16-120A)

Pk2

ZS-1I

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1POutlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.

PDU

PI-3k(16-120A)

PK2

ZS-1DSM

Type 2 - at boundaries of LPZ 1-2(surge arrester)

CoordinationT2 a T3

SPD type Installation < 5 m

100 %(property protection)

Step 4(selection of SPD T3)

Step 3(selection of SPD T2)

Lightning arrester Type 1

PIV 12,5-275/3+0 Art. No. 10 152

PIII-275/3+0 Art. No. 24 001

Surge arrester Type 3

PI-k8 Art. No. 30 080

Surge arrester Type 2

ZS-1P Art. No. 32 006

PI-3k120 Art. No. 30 307

PIIIM-275/3+1 Art. No. 27 022Lightning arrester Type 1

PIV 12,5-275/4+0 Art. No. 10 195

EQUIPMENT

EQUIPMENT

EBB

EBB

the queen of powerthe queen of power the queen of power the queen of power

Selection guide Selection guideSelection guide Selection guide

Page 7: HAKEL přepěťová ochrana - SPD SELECTION GUIDE · Step 1 (object selection) Step 2 (selection of SPD T1) Lightning arrester Type 1 HS50-50/3+0 Art. No. 10 090 Lightning arrester

Buildings with considerable level of protection LPL II ( Iimp = 75 kA)

Industrial buildings

Administrative buildings

Schools

Supermarkets

Cathedrals

Objects connected by buried cable.

TNC

1 1+0

HS50-50

SubstationSwitchboard (kWh)Main switchboard

5 metres cable or decoupling element

PI-L (16-120 A )

3 3+0HS50-50/3+0

SubstationSwitchboard (kWh)Main switchboard

SPC25/3+0

Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

TNS

1

1+1

HS50-50/1+1 SubstationSwitchboard (kWh)Main switchboard

5 metres cable or decoupling element

PI-L (16-120 A )

2+0

HS50-50/2+0

3

3+1

SPC25/3+1Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

4+0

SPC25/4+0

LIGHTNING PROTECTION LEVEL IILIGHTNING PROTECTION LEVEL II

Classification of typical objects

System No.of phases

Circuit Type 1-at boundaries of LPZ 0-1 (lightning arrester)

CoordinationT1 and T2

SPD type Installation < 5 m

Step 1(object selection)

Step 2(selection of SPD T1)

Type 3 - at boundaries of LPZ 2-3 (surge arrester) SPD + EMI filter Additional SPD

SPD type Installation SPD type Installation

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1DSM

Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.PI-3k(16-120A)

Pk2

ZS-1I

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1POutlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.

PDU

PI-3k(16-120A)

PK2

ZS-1DSM

Type 2 - at boundaries of LPZ 1-2(surge arrester)

CoordinationT2 a T3

SPD type Installation < 5 m

100 %(property protection)

Step 4(selection of SPD T3)

Step 3(selection of SPD T2)

Lightning and surge arrester Type 1 + Type 2

SPC25/3+0 Art. No. 10 736

PIII-275/3+0 Art. No. 24 001

Surge arrester Type 3

PI-k8 Art. No. 30 080

Surge arrester Type 2

ZS-1P Art. No. 32 006

PI-3k120 Art. No. 30 307

PIIIM-275/3+1 Art. No. 27 022Lightning arrester Type 1 + Type 2

SPC25/4+0 Art. No. 10 651

EBB

EBB

EQUIPMENT

EQUIPMENT

PIIIM-275Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIII-275/3+0

PIII-275/3+0

If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIII-275/1+1Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIIIM-275/1+1

PIII-275/1+1If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIIIM-275/3+1

PIIIM-275Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIII-275/3+0

PIII-275/3+0

If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIII-275/1+1Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIIIM-275/1+1

PIII-275/1+1If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIIIM-275/3+1

Buildings with considerable level of protection LPL III and IV ( Iimp = 50 kA)

LPL IIIApartment houses

Small administartive buildings

Family houses

Agricultural structures

LPL IVBuildings and halls without occurrence of persons and internal equipment

Objects with the main back-up fuse up to 63A connected by buried cable.

TNC

1 1+0

SPC25

Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

3 3+0PIV12.5/3+0

Main switchboard5 metres cable or

decoupling elementPI-L (16-120 A )

SPC25/3+0

Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

TNS

1

1+1

SPC25/1+1Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

2+0

SPC25/2+0

3

3+1

SPC12,5/3+1

Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

4+0

PIV12,5/4+0

Main switchboard5 metres cable or

decoupling elementPI-L (16-120 A)

LIGHTNING PROTECTION LEVEL III a IVLIGHTNING PROTECTION LEVEL III a IV

Classification of typical objects

System No.of phases

Circuit Type 1-at boundaries of LPZ 0-1 (lightning arrester)

CoordinationT1 and T2

SPD type Installation < 5 m

Step 1(object selection)

Step 2(selection of SPD T1)

Type 3 - at boundaries of LPZ 2-3 (surge arrester) SPD + EMI filter Additional SPD

SPD type Installation SPD type Installation

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1DSM

Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.PI-3k(16-120A)

Pk2

ZS-1I

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1POutlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.

PDU

PI-3k(16-120A)

PK2

ZS-1DSM

Type 2 - at boundaries of LPZ 1-2(surge arrester)

CoordinationT2 a T3

SPD type Installation < 5 m

100 %(property protection)

Step 4(selection of SPD T3)

Step 3(selection of SPD T2)

Lightning arrester Type 1

PIV 12,5-275/3+0 Art. No. 10 152

PIII-275/3+0 Art. No. 24 001

Surge arrester Type 3

PI-k8 Art. No. 30 080

Surge arrester Type 2

ZS-1P Art. No. 32 006

PI-3k120 Art. No. 30 307

PIIIM-275/3+1 Art. No. 27 022Lightning arrester Type 1

PIV 12,5-275/4+0 Art. No. 10 195

EQUIPMENT

EQUIPMENT

EBB

EBB

the queen of powerthe queen of power the queen of power the queen of power

Selection guide Selection guideSelection guide Selection guide

Page 8: HAKEL přepěťová ochrana - SPD SELECTION GUIDE · Step 1 (object selection) Step 2 (selection of SPD T1) Lightning arrester Type 1 HS50-50/3+0 Art. No. 10 090 Lightning arrester

HAKEL spol. s r.o. Bratří Štefanů 980500 03 Hradec KrálovéČeská republika

tel.: +420 494 942 300fax: +420 494 942 303e-mail: [email protected]

Lighting Protection Level ILighting Protection Level IILighting Protection Level III

Lighting Protection Level IV

Type 1, Type 2, Type 3

Buildings with considerable level of protection LPL I ( Iimp = 100 kA)

Hospitals Banks

Transmission point for GSM,BTS

Water stations

Power plants Aerodrome control tower

Buildings with danger of explosion

Bigger industrial buildings

Buildings with particular importance

TNC

1 1+0

HS50-50

SubstationSwitchboard (kWh)Main switchboard

5 metres cable or decoupling element

PI-L (16-120 A )

3 3+0HS50-50/3+0

SubstationSwitchboard (kWh)Main switchboard

SPC25/3+0

Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

TNS

1

1+1

HS50-50/1+1 SubstationSwitchboard (kWh)Main switchboard

5 metres cable or decoupling element

PI-L (16-120 A )

2+0

HS50-50/2+0

3

3+1

SPC25/3+1Main switchboardCoordination of SPC with SPU doesn‘t require separation by longer cable or by decoupling element. (The installation of SPD T2 is necessary, if the length is > 30 m from T1)

4+0

SPC25/4+0

LIGHTNING PROTECTION LEVEL I

Classification of typical objects

System No.of phases

Circuit Type 1-at boundaries of LPZ 0-1 (lightning arrester)

CoordinationT1 and T2

SPD type Installation < 5 m

Step 1(object selection)

Step 2(selection of SPD T1)

Lightning arrester Type 1

HS50-50/3+0 Art. No. 10 090

Lightning arrester Type 1 + Type 2

SPC25/4+0 Art. No. 10 651

EBB

EBB

LIGHTNING PROTECTION LEVEL I

Type 3 - at boundaries of LPZ 2-3 (surge arrester) SPD + EMI filter Additional SPD

SPD type Installation SPD type Installation

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1DSM

Outlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.PI-3k(16-120A)

Pk2

ZS-1I

PI-k(8-150A)

To the switchboard, which is closest to the protected equipment

(In case of electronic control protection, the installation is directly to the appliance)

ZS-1POutlet circuits which are longer than 20 m. Flush-mounted sockets and cable ducts. It is recommended to install SPD into the outlet circuit to every fourth socket or to the point of supply. The installation eliminates induced overvoltage which is enducing into the object‘s service cables.

PDU

PI-3k(16-120A)

PK2

ZS-1DSM

Type 2 - at boundaries of LPZ 1-2(surge arrester)

CoordinationT2 a T3

SPD type Installation < 5 m

100 %(property protection)

Step 4(selection of SPD T3)

Step 3(selection of SPD T2)

PIII-275/3+0 Art. No. 24 001

Surge arrester Type 3

PI-k8 Art. No. 30 080

Surge arrester Type 2

ZS-1P Art. No. 32 006

PIIIM-275/3+1 Art. No. 27 022

PI-3k120 Art. No. 30 307

EQUIPMENT

EQUIPMENT

PIIIM-275Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIII-275/3+0

PIII-275/3+0

If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIII-275/1+1Subsidiary switchboard, Switchboards on every floor of the object orin every control panel

5 meters of cable or decoupling element

PI-L(16-120 A)

(Decoupling elements(PI-L) are installed for coordination of T2 and T3. These protect

SPD T3 against destruction. If there is a distance between

T2 and T3 < 5 m, it is necessary to use decoupling elements. The

recommended connection is in series, hence is required to know the nominal voltage of

existing conductor.

PIIIM-275/1+1

PIII-275/3+1If the distance from T1 is > 30 m, then it is necessary to install SPD T2

PIIIM-275/3+1