HAGER AutomationProducts

32
Automation & Control p.2 switch disconnectors p.3 contactors p.4 latching relays p.5-6 electromechanical time switches p.7 digital time switches p.8 twilight switches p.9 delay timmers p.10 time lag switches p.11 pushbuttons p.12 pushbuttons and indicator lights p.13 transformers, bells and buzzers p.14 analogue voltmeters and ammeters - digital voltmeters and ammeters p.15 selector switches for voltmeters and ammeters current transformers (C.T.) p.16 kilowatt hour meter and hours counter

description

hffghf

Transcript of HAGER AutomationProducts

Page 1: HAGER AutomationProducts

Automation & Controlp.2 switch disconnectors

p.3 contactors

p.4 latching relays

p.5-6 electromechanical time switches

p.7 digital time switches

p.8 twilight switches

p.9 delay timmers

p.10 time lag switches

p.11 pushbuttons

p.12 pushbuttons and indicator lights

p.13 transformers, bells and buzzers

p.14 analogue voltmeters and ammeters

- digital voltmeters and ammeters

p.15 selector switches for voltmeters and ammeters

current transformers (C.T.)

p.16 kilowatt hour meter and hours counter

Page 2: HAGER AutomationProducts

2

SB499S

switch disconnectors

descriptionfor use as a switch disconnectorin all types of circuit. Complieswith: BSEN 60 947-3

BS 5419 -1977

technical dataAC 22 duty specification: BS 5419-1977

In : 25, 32Ashrouded cable clamps, connection capacity:10 mm2 – rigid conductor.6 mm2 – flexible conductor.

In : 40, 63, 80Acable clamps, connection capacity:25mm2 – rigid conductor.16mm2 – flexible conductor.

In : 100Acable clamps, connection capacity:50 mm2 – rigid conductor.35 mm2 – flexible conductor.All switches have a green / redmechanical indication giving a positive contact indication:

- version with pilot light for 25-32A SP/DP switches.

optionhandle link pin

designation characteristics width in I pack cat.

17.5mm qty. ref.

single pole 1 x 25A 250V~ 1 12 SB116S

1 x 32A 250V~ 1 12 SB132S

1 x 63A 250V~ 1 12 SB163S

1 x 80A 250V~ 1 12 SB177S

1 x 100A 250V~ 1 12 SB197S

double pole 2 x 32A 400V~ 1 12 SB232S

2 x 40A 400V~ 2 6 SB240S

2 x 63A 400V~ 2 6 SB263S

2 x 80A 400V~ 2 1 SB280S

2 x 100A 400V~ 2 1 SB299S

triple pole 3 x 25A 400V~ 2 6 SB316S

3 x 32A 400V~ 2 6 SB332S

3 x 40A 400V~ 3 4 SB340S

3 x 63A 400V~ 3 4 SB363S

3 x 80A 400V~ 3 1 SB380S

3 x 100A 400V~ 3 1 SB399S

3 x 125A 400V~ * 1 JK125S

3 x 160A 400V~ * 1 JK160S

3 x 200A 400V~ * 1 JK200S

four pole 4 x 25A 400V~ 2 6 SB416S

with indicator 4 x 32A 400V~ 2 6 SB432S

4 x 40A 400V~ 4 3 SB440S

4 x 63A 400V~ 4 3 SB463S

4 x 80A 400V~ 4 1 SB480S

4 x 100A 400V~ 4 1 SB499S

* please consult us

SB116S

SB240S

SB399S

JK200S

Page 3: HAGER AutomationProducts

3

contactors

descriptioncontactors for the remoteswitching and control of powercircuits (20A-63A AC1)

technical datathe choice of contactor dependsupon a number of parameters,e.g.– the nature of the supply.– the power it is switching.– the characteristics of the load.– the control voltage required.

All contactors ratings are forAC1 loads only – if the load dif-fers from AC1 the contactor mayneed de-rating. Derating information can be obtainedfrom Hager Engineers at thenearest Regional Centre.

The use of LZ060 (heat dissipation inserts) between allcontactors installed or betweencontactors and adjacent devicesis recommended.

optionscontact choice– normally open (NO)– normally closed (NC)

LZ060 heat dissipation inserts.

ES237 and ES238 low noise version available.

auxiliary20A contactors will accept auxiliary, EP071 contact.

• for technical information see page 19

designation type coil power width in I pack cat.circuit AC1 17.5mm qty. ref.

2 NO 230V 50 Hz 20A - 250V~ 1 12 ES220

40A - 400V~ 3 4 ES240

63A - 400V~ 3 4 ES263

3 NO 230V 50 Hz 20A - 400V~ 2 6 ES320

40A - 400V~ 3 4 ES340

63A - 400V~ 3 4 ES365auxiliary contact 1 NC (10A)

4 NO 230V 50 Hz 20A - 400V~ 2 6 ES420

40A - 400V~ 3 4 ES440

63A - 400V~ 3 4 ES463

auxiliary for 20A contactors 2A - 250V~ 1/2 1 EP071

heat dissipation insert 1/2 10 LZ060

ES463

ES320

ES230

Page 4: HAGER AutomationProducts

4

latching relays

descriptionlatching relays - operate whenimpulsed by a signal voltage. The impulse can be provided via a pushbutton or switch. The firstpulse operates the relay andlatches it into its set (opposite)state, the next operation of thepushbutton returns the relay intoits reset (original) state.

auxiliary contacts (EP070, EP071) are available for remotesignalling applications and canbe easily combined with thelatching relays.connection: 10mm2 flexible

6mm2 rigid

• for technical information see page 20

designation type coil power width in I pack cat.circuit 17.5mm qty. ref.

latching relays 1 NO 230V 50 Hz 16A - 250V~ 1 12 EP510

24V 50 Hz 16A - 250V~ 1 12 EP513

2 NO 230V 50 Hz 16A - 250V~ 1 12 EP520

24V 50 Hz 16A - 250V~ 1 12 EP524

1 NC + 1 NO 230V 50 Hz 16A - 250V~ 1 12 EP515

24V 50 Hz 16A - 250V~ 1 12 EP518

12V 50 Hz 16A - 250V~ 1 12 EP519

2 NC + 2 NO 230V 50 Hz 16A - 250V~ 2 6 EP525

24V 50 Hz 16A - 250V~ 2 6 EP528

12V 50 Hz 16A - 250V~ 2 6 EP529

4 NO 230V 50 Hz 16A - 400V~ 2 6 EP540

24V 50 Hz 16A - 400V~ 2 6 EP541

designation voltage power width in I pack cat.circuit 17.5mm qty. ref.

auxiliary contact 2A - 250V~ 1/2 1 EP071

EP510

EP541

EP071

Page 5: HAGER AutomationProducts

5

electromechanical time switches

description:electromechanical time switches1 channel for daily or weeklyprogramming.to control lighting, heating,household appliances, shop win-dows etc.- to improve comfort and saveenergy.Applications: domesticcommercial premises

Din rail mounting technical data:- programming by captivesegments.manual override:on 1 module devices:- automatic- permanent ONon 3 and 5 modules devices:- automatic- permanent ON

- permanent OFFminimum switching time:- 15 min for daily versions- 2 hours for weekly version- 15 min and 2 hours on thedaily + weekly version

connection capacity:1 to 4 mm2

complies with EN 60730

designation characteristics width in I pack cat.17.5mm qty ref.

1 channel voltage supply: 230V50/60Hz

daily dial output:without battery reserve 1M devices= 1N/O 1 1 EH010

16A - 250V AC1

3M devices = 1 3 1 EH110changeover16A - 250V AC1

1 channel voltage supply: 230V50/60Hz

daily dial output:with battery reserve 1M devices = 1NO 1 1 EH011

16A - 250V AC1

reserve: 3M devices = 1 3 1 EH111200 hours after being changeoverconnected for 120 hours 16A - 250V AC1

1 channel voltage supply: 230V50/60Hz

weekly dial output: with battery reserve 1 changeover 3 1 EH171

16A - 250V AC1reserve:200 hours after being connected for 120 hours

1 channel voltage supply: 230V50/60Hz

daily + weekly dial outputwith battery reserve 1 changeover 5 1 EH191

16A - 250V AC1reserve:200 hours after being connected for 120 hours

EH 111

EH 011

Page 6: HAGER AutomationProducts

6

electromechanical time switches

description:for daily or weekly programming.1 channel for the control oflighting, heating, householdappliances, shop windows etc...to improve comfort and saveenergy.application: domestic commer-cial premises.

technical data:- suitable for surface, flush ordin rail mounting- programming by captive seg-ments- manual override with automaticreturn to programme- operating reserve: 200h afterbeing connected for 120h- output: voltage freechangeover contact 16A/250V

daily version:programming in steps of 10minutes.- minimum time between 2switching intervals: 20minutes

weekly version:programming in steps of onehour.- minimum time between 2switching intervals: 2 hours- switching accuracy: 10 mincomplies with EN60730

designation characteristics pack cat.qty ref.

1 channel daily cycle supply: 230V 50/60Hz

without battery reserve 1 EH710

with battery reserve 1 EH711

Economy version (1 NO contact) 1 EH712

1 channel weekly cycle supply: 230V 50/60Hz

without battery reserve 1 EH770

with battery reserve 1 EH771

1 channel daily cycle supply: 48V DC 110 to 230V 50/60Hz

without battery reserve 1 EH715

with battery reserve 1 EH716

11

56

EH 711

EH 771

Page 7: HAGER AutomationProducts

7

digital time switches

description:for the control of lighting, schoolbells (EG171), pumps, heating,household appliances, shop win-dows etc...

- to improve comfort and saveenergy

applications: domestic, schools,colleges and commercialpremises

technical data:1, 2 or 4 channel :- programming in 1 minuteincrements- easy programming- display and control of theprogram- possibility to override the output (permanent or temporary)- operating reserve:lithium battery total of threeyears.

- output: changeover contacts16A -250V AC1- sealable front cover

connection capacity:1 to 4 mm2

complies with EN 60730

designation characteristics width in I pack cat.

17.5mm qty. ref

1 channel daily cycle 5 adjustable pre-recor- 1 1 EG010

-ded programs: 6 com-

-mutations per day

230V 50/60 Hz

1 channel daily cycle capacity: 20 program 3 1 EG110

steps. 230V 50/60Hz

2 channel daily cycle capacity: 20 program 3 1 EG210

steps to be divided

between the 2 channels

110/230V 50/60 Hz

1 channel weekly cycle capacity: 20 program 1 1 EG071

steps. 230V 50/60 Hz

1 channel weekly cycle capacity: 20 program 3 1 EG170

steps. 230V 50/60Hz

1 channel weekly cycle capacity: 20 program 3 1 EG172

steps. 12V AC/DC

1 channel weekly cycle capacity: 20 program 3 1 EG171

pulsed output steps. 230V 50/60Hz

pulsed output adjustable

from 1 sec. to 99 mins.

2 channel weekly cycle capacity: 20 program 3 1 EG270

steps to be divided be-

-tween the 2 channels

110/230V 50/60Hz

4 channel weekly cycle capacity: 84 program 5 1 EG470

steps to be divided

between the 4 channels

230V 50/60Hz

EG 210

EG 071

Page 8: HAGER AutomationProducts

8

description:The light sensitive switch con-trols light systems according todaylight level:- the user sets the switchinglevel- the photo cell measures theexternal light level.

applications: domestic and com-mercial premises

technical data:supply: 230V +10%-15% 50Hz1 changeover contact 16A 250Vselection switch:5 to 100 lux50 to 2000 lux4 position override switch allow-ing:-auto: normal operation mode- on: permanently switched-on- off: permanently switched-off-test: setting mode for easy

adjustmenta light indicator when installingshows the status “on” of thecontact

complies with EN 60730

designation characteristics width in I cat.

17.5mm ref

twilight switch 3 EE100

with surface cell

twilight switch 3 EE101

with flush cell

programmable twilight daily cycle / electromech. switch 5 EE110

switch with flush cell

programmable twilight weekly cycle / electronical program 3 EE170

switch with flush cell

flush cell IP54 for EE100, 101,110 & 170 EE002

surface cell IP54 for EE100, 101,110 & 170 EE003

twilight switches

EE 170

EE 110

EE 002

Page 9: HAGER AutomationProducts

9

delay timers

descriptionto provide all types of automaticcontrol i.e. lighting, ventilation,watering, machine pre-heating,automatic door and visual audible indication, cycle controletc.

applicationsfor timing and automation indomestic and commercial premises. The input signal canbe via various switching devices (pushbutton, latching switch, timeclock etc.) and the timedoutput used to control the appli-cation.

technical datavoltage range:12 & 24 to 48V DC12 & 24 to 230V ACadjustable:time delay from 0.1s to 10hrs.Led indicator complies with EN 60669-2-1terminal capacity:6mm2 max rigid1.5mm - 10mm2 flexible

• for technical information see page 25 - 26

designation characteristics width in I pack cat.17.5mm qty. ref.

delay on 1 c/o contact 1 1 EZ00110A / 230V~ ACtime delay T: 0.1s to 10hr

adjustable time on 1 c/o contact 1 1 EZ00310A / 230V~ ACtime delay T: 0.1s to 10hr

delay off 1 c/o contact 1 1 EZ00210A / 230V~ ACtime delay T: 0.1s to 10hr

symmetrical flasher 1 c/o contact 1 1 EZ00510A / 230V~ ACtime delay T: 0.1s to 10hr

timer 1 c/o contact 1 1 EZ00410A / 230V~ ACtime delay T: 0.1s to 10hr

multifunction 1 c/o contact 1 1 EZ0066 individual functions 10A - 230V~ AC including: time delay T. 0.1s. to 10hdelay ondelay offtimersee page 28 for moreinformation

EZ001

EZ002

Page 10: HAGER AutomationProducts

10

time lag switches

descriptionto provide control of lighting circuits with automatic switch-offafter a pre-set time(e.g.: staircase, corridors).command signal via impulse

technical data– time delay setting by rotating

thumbwheel dial on frontof device.

EM002 switch off notice add-on blockincorporating pre-warning ofswitch-off improves the safetyfor users / pre-warning ofswitch-off at the end of thetime delay,light intensity reduction by 50%for a period of 24 sec. prior tofinal switch off.use only on incandescentlighting circuits.

EM001 time lag switchfor lighting circuits (medium orhigh daily use)characteristic: compact designequipped with a 2 position dialpermanent/timed lightingimplementation facility.

note: this range is only suitablefor use with pushbuttons,not switches.

• for technical characteristics,see page 27

designation characteristics width in I pack cat.17.5 mm qty. ref.

time lag switch voltage rating: 1 6 EM001230V; - 50/60 Hzrestart facility

24 sec. to 12 min. 2 function switch:– permanent– timed

output: 1 changeover contact16 A - 230V; AC 110A - 2300W - incandescent10A - 2300W - halogen 230V10A - 2300W - on compact fluorescent

Note: Heat dissipation insert (LZ060) recommended between switch off notice & timer

Add-on block voltage rating: 2 1 EM002pre-warning 230V; - 50/60 Hzswitch off notice restart facility

pre-warning of switch-offby decrease of outputvoltage (50% for 24 sec.)

switch off notice: 24 secsoutput power:1000W - incandescent1000W - halogenEM002

EM001

Page 11: HAGER AutomationProducts

11

pushbuttons

description

pushbuttonsto actuate loads either directly orvia contactors etc.

technical datamodular pushbuttons– without light with grey button, red/greenoptional

– with lightwith red, green button (amber,blue, colourless, red, green lens-es on option).delivered with neon lamp 240V~, E 10 cap.

optionspushbuttons can be fitted with 12, 24, 48, 60V lamps (see below).

shrouded cable clamp type, connection capacity:10mm2 rigid conductor.6mm2 flexible conductor.

designation characteristics width in I pack cat.17.5mm qty. ref.

pushbuttons 16A – 250V~without indicator light

contacts: 1 NO 1 12 SV021

contacts: 2 NO 1 12 SV022

contacts: 3 NO 1 12 SV025

contacts: 1 NC 1 12 SV023

contacts: 2 NC 1 12 SV024

contacts: 1 NO + 1 NC 1 12 SV120

contacts: 1NO + 1 NC 1 12 SV031

contacts: 2 changeover 1 12 SV026

pushbuttons with indicator light

contacts: 1NO green 1 12 SV124

contacts: 2 NO red 1 12 SV062

contacts: 1 NC red 1 12 SV123

contacts: 2 NC green 1 12 SV064

SV025

SV031

SV062

Page 12: HAGER AutomationProducts

12

pushbuttons

indicator lights

modular indicator lightsavailable with red, green, amber,blue, colourless lensdelivered with neon lamp230V~, E10 cap

optionsindicator lights can be fitted with12, 24, 48, 60V lamps (seebelow)

shrouded cable clamp type, connection capacity:10mm2 rigid conductor.6mm2 flexib le conductor.

designation characteristics width in I pack cat.17.5mm qty. ref.

indicator lights 230V~ with light green 1 12 SV121

red 1 12 SV122

orange 1 12 SV126

clear 1 12 SV127

blue 1 12 SV128

designation characteristics width in I pack cat.17.5mm qty. ref.

pushbuttons 16A – 250V~without indicator lightcontacts: 1 NO 1 12 SV041

contacts: 2 NO 1 12 SV042

contacts: 3 NO 1 12 SV047

contacts: 4 NO 1 12 SV048

contacts: 1 NO + 1 NC 1 12 SV045

contacts: 2 changeover 1 12 SV046

with indicator lightcontacts: 1 NO green 1 12 SV071

contacts: 2 NO green 1 12 SV072

SV072

SV121 SV127 SV126SV122 SV128

Page 13: HAGER AutomationProducts

13

transformers, bells and buzzers

descriptionProvide extra safety low voltage8, 12, 24V~.

technical datasecondary voltages: 8V, 12V, 24V~bell transformers are short-circuit protected.bells/buzzers:max. continuous duty≤ 30 minutes.connection capacities: 6 mm2

cable clamp typeoutput:bells: 85 dBAbuzzers: 78 dBA

When a bell transformer isinstalled in an enclosure withmains voltage equipment, 230Vcable should be used on thesecondary side of the trans-former or extra low voltage cableshould be sheathed within theenclosure.

note: the transformers have ahigher no load voltage.The stated voltages correspond to the voltages on nominalload.

∆ for technical information see page 29

designation characteristics width in I pack cat.17.5mm qty. ref.

safety transformers 16VA 50/60 Hz 4 3 ST313

230V/12-24V~ 25VA 50/60 Hz 4 3 ST31250Hz

40VA 50/60 HZ 4 1 ST314

60VA 50/60 Hz 6 2 ST315

bell transformers 230V/8V~ 50/60 Hz 2 6 ST3014VA - 8-12V : 0.33A

230V/8-12V~ 50/60 Hz 2 6 ST3038VA - 8V : 1A

12V : 0.67A

230V/8-12V~ 50/60 Hz 3 4 ST30516VA - 8V : 2A

12V : 1.33A24V : 0.67A

bells 8/12V~ 1 12 SU2124VA - 0.35A

230V~ 1 12 SU2136.5VA - 0.03A

buzzers 8/12V~ 1 12 SU2144VA - 0.35A

230V~ 1 12 SU2156.5VA - 0.03A

ST313

ST301

SU212

SU214

Page 14: HAGER AutomationProducts

14

digital voltmetersSM501for domestic and commercialinstallations

three phase: use of avoltmeter selector switch SK602

digital ammetersSM151, SM401, SM601SM151: direct readingSM401, SM601: reading via acurrent transformer (see below)

• for detailed characteristics,see page 31

designation characteristics width in I pack cat.17.5 mm qty. ref.

digital voltmeters voltage rating:220/230V ; 50/60 Hzaccuracy: ± 1%consumption: 4 VA

scale: 0 - 500V

4 1 SM501

digital ammeters voltage rating:220/230V ; 50/60 Hzaccuracy: ± 1%consumption: 4 VA

–reading via CT 150/5A scale: 0 - 150A 4 1 SM151(SR150)

–reading via CT 400/5A scale: 0 - 400A 4 1 SM401(SR400)

–reading via CT 600/5A scale: 0 - 600A 4 1 SM601(SR600)

SM501

SM401

analogue voltmeters, ammeters

designation characteristics width in I pack cat.17.5 mm qty. ref.

voltmeter

3 1 SM500

ammeter accuracy: 2% or via a current transformer (CT) (page 33)

0 - 50A 1 SM050

0 - 100A 1 SM100

0 - 150A 1 SM150

0 - 250A 1 SM250

0 - 400A 1 SM400

0 - 600A 1 SM600

accuracy: 2%consumption: 2.5 VA0 - 500V

SM500

SM050

analogue voltmetersfor domestic and commercialinstallations

single phase:direct connectionthree phase: use of avoltmeter selector switchSK602 see page 64

frequency: 50 Hzconnection capacity:rigid conductor 10mm2

flexible conductor 6mm2

analogue ammetersfor domestic and commercialinstallations

direct reading:SM005: 0 - 5ASM015: 0 - 15ASM030: 0 - 30A

indirect reading via currenttransformers: 50-100-150-50-400-600A

• for detailed characteristics, `see page 31

digital voltmeters, ammeters

Page 15: HAGER AutomationProducts

15

selector switches for voltmeters and ammeters

descriptionFor use with voltmeters andammeters.

applicationscomplies with IEC 947-3BSEN 60947-3.

terminal capacity 2.5mm2

isolating voltage 500Vacnominal current 10-20A

connecting capacityrigid conductor 1.5 to 10mm2

flexible conductor 1 to 6mm2

designation characteristics width in I pack cat.17.5mm qty. ref.

voltmeter selector 20A 400Vac 3 1 SK6023P&N3 readings between phases3 readings between phase & neutralnull position (no reading)

ammeter selector 20A 400Vac 3 1 SK6034 positionsuse in 3P&Nreading by phasenull position (no reading)should be used with current transformer (CT)see page 111

lockable rotary switch 10A 400Vac 3 1 SK6064 positions

SK602

SK603

SK606

current transformers (C.T.)

current transformers are used tofeed analogue and digitalammeters

Their current on secondarycircuit (0 - 5A) is proportionalto the current on primary circuitclass: 1

can be mounted on copper baror on cable

can be mounted on DIN rail withadaptors

∆ for detailed characteristics,see page 31

current transformers

(CT) ratio:

50/5 1 SR050

100/5 1 SR100

150/5 1 SR150

200/5 1 SR200

250/5 1 SR250

300/5 1 SR300

400/5 1 SR400

600/5 1 SR600

SR300

Page 16: HAGER AutomationProducts

16

kilowatt hour meters and hours counter

descriptionkilowatt hour meters measurethe active energy used in anelectrical installation. The rangeincludes metres with pulsed outputs for remote indication orlinking into an energy management system. KwH meters can be used forlocal metering of installations or monitoring individual machines.The single phase meter offers 3 options:– total counter (non resettable)– resettable counter (shows

energy used since last reset)– watt meter (displays power as

it is used)

technical data2 types– for single phase (direct

reading)– for three phase (via a CT)

displaysthree phase - 6 digit roller typesingle phase - LCD

pulsed LED - 1 pulse = 1 Wh

optionssingle phase – without pulsed output

three phase– without pulsed output

single phase– with pulsed output

three phase– with pulsed output

• for technical information see page 32

designation characteristics width in I pack cat.17.5mm qty. ref.

kilowatt hour meter without pulsed output 7 1 EC010single phasevoltage 230V - 50Hzdirect connection In = 75mA - 90A with pulsed output 7 1 EC011

1 pulse = 1 Wh

kilowatt hour meter without pulsed output 7 1 EC030three phasevoltage 3 x 230/400V 50-60 Hzconnection via a currenttransformer (In/5A) with pulsed output 7 1 EC031ratio of 50/5 - 100/5200/5 - 300/5 - 400/5500/5 - 600/5 - 800/5 1 pulse = 1 Whsee page 34 for CT

hours counter

descriptionto measure the total operatingtime of any circuit/loadnon resettable

application example– total time of plant running– connection in parallel withcontactor coil– recording of lighting hours forrelamping purposes

designation characteristics width in I pack cat.17.5mm qty. ref.

kilowhours counter voltage ratings: 2 1 EC100230V - 50 Hz

EC010

EC100

Page 17: HAGER AutomationProducts

technical information

p.18 choice of contactors

p.19-20 contactors and relays

p.21 latching relays- technical

p.22 technical data - analogue time switches

p.23 technical data 72 X 72mm

p.24 technical data - digital time switches

p.25-26 delay timers

p.27 time lag switches

p.28 technical data - twilight switches

p.29 transformers

p.30 voltmeters, ammeters and hours counters

p.31 voltmeters, ammeters and current transformers

p.32 kWh meters

Page 18: HAGER AutomationProducts

18

choice of contactors

requirements of useinfluence of working temperature:derating factor between 40°C and 50°C : 0.9example: heating with convectorthe maximum load of ES220 is 4.4kW for 50,000 operations and for

a temperature <40°C.between 40°C and 50°C, the load is 4.4 x 0.9 i.e. 3.96kWclose fitting:it is necessary to put a heat dissipation insert (reference LZ060)between each contactor.

heatingthe choice of the contactor depends on the mechanical resistance(number of operations) and on the electrical heating load i.e. resistive elements, infra-red element, convectors.

choice of contactorsthe choice of contactor is dependant upon many parameters i.e. operating voltage, size of contacts, number of operations, ambient temperature, type of load supplied etc.

type of loadloads are categorised into various AC ratings, (AC1, AC2, AC3 etc.)and the higher the AC rating the more inductive the load becomes.All Hager contactor ratings are given at AC1, therefore they must bede-rated if used on other types of AC load.

heat dissipation insertsthe ambient temperature around a contactor can affect its lifeexpectancy, therefore, we strongly recommend that heat dissipationinserts (LZ060) are fitted between all contactors and adjacentdevices.

please consult your Local Regional Office, if you require helpselecting a suitable contactor.

single phase three phase

motors (AC3)single phase 230V three phase 400V three phase 400V

single phase with three phase choice of contactor accordingcapacitor (AC3 cat.) to control diagram230V 400V 2 wires 3 wires

1.1 ES220

maximum 2.2 ES240

load 4 ES320 - ES420

in kW 7.5 ES340 - ES345 - ES440

15 ES365 - ES463

* on three phase configuration the maximum load per phase corresponds to the values states divided by 3.

example:function of a heating installation 200 days/annum, 100 operations per day (1 opening + 1 closing = 2 operations)mechanical life = 10 yearstotal number of operations: 200 x 100 x 10 = 200,000in that case select an ES240 to control a load of 4.4 kW(single phase 230V)

U R R

L1 U

V

M

L2

L1 U

W

M

L3

L2 V

R

R

R

U

U

U

number of operations 50,000 100,000 150,000 200,000 300,000 single phase 230V three phase*400V

4.4 4.4 3.9 3.5 2.9 ES220 - ES230

7.8 5.9 5 4.4 3.7 ES240

maximum 12 8.8 7.7 6.6 5.9 ES263

load* 12 10.5 8.5 6.5 5.8 ES320 - ES430

in kW 23.2 17.7 15 13.1 10.8 ES340

35 26.3 23 19.7 5.8 ES463

Page 19: HAGER AutomationProducts

19

contactors and relays

technical characteristics

auxiliary contacts auxiliary contacts are available for the range of relays and 20A contactors.

20A relays and contactors with manual override1. permanently on2. automatic3. permanently off

I

Auto

0

1

2

3

control voltage start and maintainedconsumption

12V DC 0.5W

24V DC 1.5W

12V AC 1VA

24V ac 2VA

contactors

ES320 ES240 ES263

ES220 ES340 ES365ES420 ES463

ES440command voltage V 230 230 230 230

frequency % +10/ -15 for all

productsHz 50

starting consumption VA 15 20 50 50

maintained consumption VA 5 5 7 7

max perm.current AC1 A 20 20 40 63

insulation voltage V 250 400 400 400

mech. endurance 1,000,000

working temperature °C -10/ +50 for

all products

storage temperature °C -40/ +80

connectioncontrol flexible mm2 0.5 to 4 0.5 to 4 1 to 2.5 1 to 2.5

rigid mm2 1 to 6 1 to 6 1.5 to 4 1.5 to 4

power flexible mm2 1 to 6 1 to 6

rigid mm2 1.5to10 1.5to10 4to25 4to25

note: (a) power consumption of EN145 and EN146

Page 20: HAGER AutomationProducts

20

contactors and relays

incandescent lamps

tungsten filament and halogen 230 V : 40 W60 W75 W100 W150 W200 W300 W500 W1000 W

45302418129531

503528211410642

100756545332516105

1201059065453523147

halogen 12 or 24V with transformer electronic: 20 W50 W75 W100 W150 W

702819149

8040262013

16080524026

240120786039

fluorescent tubes

single with starter non compensated : 15 W18 W30 W36 W58 W

2925252414

5042353020

11080706040

1501301109060

single with starter in parallel :15 W18 W30 W36 W58 W

C max.25 112 UF25 112 UF20 90 UF20 90 UF15 67 UF

C max.30 135 UF30 135 UF25 112 UF25 112 UF17 76 UF

C max.45 202 UF45 202 UF40 180 UF40 180 UF22 99 UF

C max.60 270 UF60 270 UF55 247 UF55 247 UF40 180 UF

double with starter compensated : 2 x 18 W 2,7 UF2 x 20 W 2,7 UF2 x 36 W 3,4 UF2 x 40 W 3,4 UF2 x 58 W 5,3 UF2 x 65 W 5,3 UF

404022221212

454526261313

909050502323

1401401001005050

single with electronic ballast : 18 W36 W58 W

302615

353017

603225

804530

double with electronic ballast : 2 x 18 W2 x 36 W2 x 58 W

15138

17159

301612

402215

compact fluorescent with electromagnetic bal-last, without compensation :

7 W10 W18 W26 W

50454025

55504227

100906550

1301159080

compact fluorescent with electronic supplyincorporated:

11 W15 W20 W23 W

80605040

85635242

1101007060

150130110100

discharge lamps

high pressure mercury without compensation : 50 W80 W125 W250 W400 W

119731

1210832

362719107

5038261410

high pressure mercury with parralled compensation :50 W80 W125 W250 W400 W

C max.9 63 UF7 49 UF5 50 UF3 54 UF1 25 UF

C max.10 70 UF8 56 UF6 60 UF3 54 UF2 50 UF

C max.25 175 UF21 147 UF14 140 UF7 126 UF4 100 UF

C max.30 210 UF25 175 UF17 170 UF9 162 UF6 150 UF

mixed : 100 W160 W250 W400 W

9631

10742

2219118

33271511

high pressure sodium vapour or metal halidewithout compensation:

70 W150 W250 W400 W

9531

10642

201064

3015106

high pressure sodium vapour or metal halide withcompensation: 70 W

150 W250 W400 W

C max.5 60 UF3 54 UF1 32 UF1 /

C max.6 72 UF3 54 UF2 64 UF1 50 UF

C max.15 180 UF9 162 UF5 160 UF3 150 UF

C max.20 240 UF16 198 UF7 224 UF5 250 UF

type 16 A 20 A 40 A 63 A

connector selectionthe table below indicates the number of lamps that can be connected to each pole of the contactor on 230V 50Hz circuits.

Page 21: HAGER AutomationProducts

21

latching relays - technical

technical characteristics

latching relays auxiliaries

EP510 EP513 EP519 EP525 EP528 EP529 EP071EP515 EP518 EP540 EP541EP520 EP524

voltage 230V 24V 12V 230V 24V 12V

start consumption 16VA 30VA

contact rating 16A 250V~* 2A 250V~AC1

electrical endurance 100,000 operations –AC1 - 16A

mechanical endurance 500,000 operations –

current in open position 8 mA –

max duration of 1 h –voltage supply to coil

min duration of 0.1 s –current supply to coil

working temperature -10 to +50°C -1 to +50°C

stocking temperature -40 to +80°C -40 to +80°C

connectionscoilflexible 0.5 to 4mm2 0.5 to 4mm2

rigid 1 to 6mm2 1 to 6mm2

powerflexible 1 to 6mm2

rigid 1.5 to 10mm2

*400V~ for the EP540 and EP541.

auxiliary contacts (EP071)The range of latching relays have been designed for use with an auxiliarycontact. The devices simpl clip on the side of the relay.

Page 22: HAGER AutomationProducts

EH010 EH011 EH110 EH111 EH171 EH191width in 17.5mm 1 1 3 3 3 5version daily weekly daily +weeklyelectricalcharacteristicsvoltage supply 230V +10/ -10%

50/60HZconsumption 0.5VAoutput 1NO 1NO 1 changeover 1 changeover 1 changeover 1 changeoverswitching capacityAC1 16A / 250Vinductive load 4A / 250V(cos phi = 0.6)incandescent 900Wlampscharacteristicstechnology Quartzdial 24 hours 7 days 24 hours and

7 daysmin. switching 15 min 2 hours 15 min and

2 hoursmax. number of 96 84 96 / 84switchingaccuracy +/- 1 sec per daysupply failure 200 hours 200 hours 200 hours 200 hoursreservereached in 120 hours 120 hours 120 hours 120 hoursmanual override auto / on / offEnvironmentprotection degree IP20working -100C to temperature +450Cstorage -100C to temperature + 500Cconnection 0.5 to 4 mm2

22

technical data - analogue time switches

PhN

3 4 5 621

M

EH110 Electrical connections

EH010EH011

21

43

Ph

N

EH010, EH011 electrical connections

Simple time setting and programming using dual direction dial

Programming by captive segments

Page 23: HAGER AutomationProducts

23

technical data - 72 x 72 mm

M

PhN

3 4 521

53

EH710 electrical connection

3 4 5

Very easy programmingwith dual direction dial

3 4 5

manual override

EH710 EH711 EH770 EH771 EH712 EH715 EH716dimensions(mm) 72x72x48

electrical characteristicsvoltage supply 230V +10/-15% 110 to 240V AC 50/60 Hz

50/60Hz 48V DC +10% / -15%

consumption 0.5VAoutput: 1 changeover 1 N/O 1 changeover switching capacity:AC1 16A / 250Vinductive load cos phi= 0.6 3A / 250Vincandescent lighting 1000 W

characteristicstechnology Quartzdial 24h 24h 7 days 7 days 24h 24h 24hswitching dial 10min 10min 1 hour 1 hour 10 min 10min 10minminimum switching 20min 20min 2 hours 2 hours 20 min 20min 20minworking accuracy + / - 1 sec per daysupply failure reserve - 200h - 200h - - 200hreached in 120h 120h 120hmanual switch temporary ON or OFFenvironementworking temperature -10 to + 500Cstorage temperature -20 to +600Cconnection capacity 1 to 6 mm2

Page 24: HAGER AutomationProducts

24

EG 170

3 4 5 621

LN

1 2 3 4 5 6 7

4

5

1

6 7 8 9

3

2

enter

reseton

off

progautomanu

OFF

LN

65

21

43

EG 010

1 2 3

OFF

P

- +

6

7

4

3

1

5

2

technical data - digital time switches

3 4 5 621

LN

EG 470

14 15

7 8 9

18 19

A

A,B

,C,D

C

11 12 13

B

10

D

16 17

OFF

20

Electrical connections:

EG 010

EG 170

EG 470

Display:

1. Time2. Output contact (ON or OFF)3. Program selected

Buttons:

4. To select the program to apply5. To scroll program steps6. Reset7. + and -: change time settings

Display:

1. Time2. Circuit status (ON or OFF)3. Day of the week (1 = Monday, 2 =Tuesday...)

Buttons:

4. Mode selector: to select one of thefollowing modes:- time setting- programming- running mode- manual override

5. “1” to “7”: selection of the days6 “on/off”: chooses whether the cir-cuit is on or off7. “+” and “-”: changes settings8 ”enter”: to confirm selection9.”reset”

EG010 EG110 EG210 EG071 EG170 EG171 EG172 EG270 EG470width in 17.5 mm 1 3 3 1 3 3 (pulsed) 3 3 5version daily weeklyelectrical characteristicsvoltage supply 230V +15 / -15% 110/230V 230V +15 / -15% 12V AC 110/230V 230V

50Hz 50/60Hz 50Hz 50Hz 50/60Hz+ 15 / -15%12V DC 50 Hz+ 15/-15%

consumption 1VA 20VAoutput changeover contactswitching capacityAC1 16A / 250Vinductive load 3A / 250Vcos phi = 0.6incandescent lamps 1000Wcharacteristicsaccuracy + / - 1 sec per daysupply failure reserve Lithium battery total of three yearsmanual override permanent permanent ON/OFF permanent permanent ON/OFF

ON/OFF temporary ON/OFF ON/OFF temporary ON/OFFenvironmentprotection degree IP20working temperature -100C to + 500Cstorage temperature -100C to + 500Cconnection 0.5 to 4 mm2

Page 25: HAGER AutomationProducts

25

delay timers

Ph / +N / -

In

18

18

16

15

15

A1/B1

A2

A3/B1

16

Ph / +N / -

18

18

16

15

15 B1

A1

A2

In

A3

16

technical specifications

functional characteristicsEZ001, EZ003, EZ005, EZ006 functions D,E,F) EZ002, EZ004, EZ006 (functions A,B,C)

Cd: command.O: output.T: time delay.

indicator light (for versions with NO contact).ONOFF

product EZ001, EZ002, EZ003, EZ004, EZ005, EZ006.

electrical characteristics

supply voltage 24-28 Vdc (+10% - 15%) terminals A1 & A224-230 Vac (+10% - 15%) terminals A1 & A212 Vac & dc (+10% -10%) terminals A3 & A2

output 1 volt free C/O contact

life expectancymax load AC1 10A / 230V~ 50,000 cyclesincandescent 450W~ 100,000 cyclesfluorescent non comp. 600W~ 50,000 cyclesinductive load 0.6pf 5A / 230V~ 100,000 cycles

min powerAC 100mA at 230VDC 100mA at 12V

galvanic isolation 2kV

standard / norm EN60669-2-1

functional characteristics

timer range 0.1s - 10 hours

min. command periodAC 50msDC 30ms

operating temperatureworking -20oC to +50oCstorage -40oC to +50oC

connection capacityflexible 1 - 6 mm2

rigid 1.5 - 10 mm2

each time delay bracket is divided into 4 ranges

time delay brackets 1s to 1h 0.1min to 10h 0.1s to 10min 0.2min to 20h

ranges 1s to 10s 0.1min to 1min 0.1s to 1s 0.2min to 2min0.1min to 1min 1min to 10min 1s to 10s 2min to 20min1min to 10min 0.1h to 1h 0.1min to 1min 0.2h to 2h0.1h to 1h 1h to 10h 1min to 10min 2h to 20h

environmentworking temperature: -10°C to +60°C.storage temperature: -20°C to +70°C

Page 26: HAGER AutomationProducts

26

delay timers

T

Command (B1)

output (15,18)

LED

T

Command (B1)

output (15,18)

LED

delay onEZ001 & EZ006 function D

delay offEZ002 & EZ006 function C

T

Command (B1)

output (15,18)

LED

T

Command (B1)

output (15,18)

LED

delay offEZ003 & EZ006 function E

impulse timerEZ004 & EZ006 function A

T TT T T

Command (B1)

output (15,18)

LED

T

Command (B1)

output (15-10)

LED

symmetrical timerEZ005 & EZ006 function F

multifunction timerEZ004 & EZ006 function A

multifunction timer - 8 individual functionsA = timer.B = delay off (output relay opens either at end of command or

after set time period - which ever is shorter).C = delay off.D = delay on.E = delay on (output relay closes either at end of command or

after set time period - which ever is shorter).F = Symmetrical timer.

on selection - contact permanently closedoff selection - contact permanently open

output relay open - with no command

output relay open - with command signal running

output relay closed - with command signal running

output relay closed - with command signal removed

output relay closed (EZ005)

Page 27: HAGER AutomationProducts

27

time lag switches

technical specifications

electrical connections

1 3

42

EM001

NPh

24 stime period

EM 001 EM 002

pre warning

secondaryimpulse

inputimpulse

working diagram

I3

I2

I1

I = (I1 + I2 + I3)

1 3

42

EM001

1 3

42

EM001

NPh

1 3

42

7

8

EM001EM 002

NPh

7

8

EM 002

1 3

42

EM001

NPh

cat. ref. EM001 EM002

Electrical characteristics

supply voltage 230V +10 - 15% 230V +10 - 15%50/60 Hz 50/60 Hz

consumption 0.5 VA 0.5 W permanent8 W max.

Breaking capacity

AC1 16A 230V~ 4A 230V~incandescent 2300W 1000Whalogen 230V 2300W 1000Wfero magnetic transformer 1600W -parallel compensated cap 112µF -fluorescent series 3000W -electronic transformer 3600W -compact fluorescent 2300W -

Functional characteristics

time delay 24s to 12 min 24smax. current in rest position 50 mA -

environment

working temperature –15 to +55ºC –15 to +55ºCstorage temperature –25 to +70ºC –25 to +70ºC

connection

flexible (mm2) 0.75 to 4 1 to 6rigid (mm2) 1 to 6 1.5 to 10connection EM001/EM002 2 wires 1.5 2 wires 1.5

Page 28: HAGER AutomationProducts

28

technical data - twilight switches

NL

13302133722330123801

EE 100EE 100

Wiring Diagram

note: * delivered with a 1 m cable (2 x 0.75mm2)** 8 predefined programs

cells EE002 EE003type flush mounting surface mountingdimension (mm) 89x48x32 25x25x20 hole O 25mmconnection cable 1 m 2x0.75mm2 0.75 to 4 mm2

protection class IP54 IP54working and storage temperature -300C to +600C -300C to +600C

EE100 EE101 EE110 EE170width in 17.5 mm 3 3 5 3electrical characteristicsvoltage supply 230V +10 / -15% frequency 50Hzconsumption 1.5 VA maximumoutput 1 voltage free changeover contactsmaximum switching capacityAC1 16A / 250Vincandescent lamps 2000W230V halogen lamps 1000Wfluorescent lamps, non compensated 1000Wfluorescent lamps, compensated 200Wfluorescent lamps compensated in series 1000Wduo fluorescent lamps 1000Wfunctional characteristicslighting level: 2 ranges 5 to 100 lux and 50 to 2000 luxON and OFF delay 15 to 60 secondsmounting of cell surface flush* surface surfaceprogrammable no no yes yestechnology electromechanical digitalcycle 24h 7 days**program setting 15 min. 1 min.accuracy +/- 6 min/year +/- 6 min./yearoperating reserve accu lithium battery

200h after beeing total of 3 year ofconnected for 120h supply failure

environmentworking temperature -300C to + 600C (cell) -100C to + 500C (modular device) storage temperature -200C to + 600Cconnectionmaximum length between cell and modular 50 meterscapacity mm2 (modular device) 0.5 to 4 0.5 to 4 0.5 to 4 0.5 to 4capacity mm2 (cell) 0.75 to 4 0.75 to 4 0.75 to 4

Page 29: HAGER AutomationProducts

29

transformers

24 V230 V

U1

U2

U3

safety transformersThese transformers are designed to ensure personal safety, their primary winding are electrically separated from their secondary windings and they are intended to feed safety extra low voltage circuits U ≤ 50V. A thermal overload, in the primary windings,ensures that if a short circuit or an overload occurs in the output itwill not damage the device.

bell transformersBell transformers are similar to safety transformers but the secondary voltages do not exceed 24 volts, they are also similarlyprotected against short circuits and overloads, by thermal protectionin the primary winding.

compliance with the standardsThe bell and safety transformers conform with EN 60742 (BS 3535).

technical specification

reference ST301 ST303 ST305 ST312 ST313 ST314 ST315

nominal power 4VA 8VA 16VA 25VA 16VA 40VA 60VA

designation bell bell bell safety safety safety safety

primary voltage 230 volts 230 volts 230 volts 230 volts 230 volts 230 volts 230 volts

U2 12 volts 8 volts 8 volts 12 volts 12 volts 12 volts 12 voltsIn = 0.33A In = 1A In = 2A In = 2.08A In = 1.33A In = 3.33A In = 5.25A

secondary voltageU3 12 volts 12 volts 12 volts 24 volts 24 volts 24 volts 24 volts

In = 0.5A In = 0.67A In = 1.33A In = 1.04A In = 0.67A In = 1.67A In = 2.63A

no load U2 12 volts 15 volts 12.4 volts 14 volts 15.5 volts 13.7 volts 13.6 voltssecondary voltage

U3 18 volts 21.8 volts 18.5 volts 29 volts 29.7 volts 26.5 volts 27 volts

galvanic isolation 4kV 4kV 4kV 4kV 4kV 4kV 4kV

max functional temperature 35°C 35°C 35°C 35°C 35°C 35°C 35°C

overload and S/C protection thermal cut out in the primary winding

number of products that can be operated simultaneously by a transformer

transformer reference ST301 ST303 ST305 ST312 ST313 ST314 ST315

8V 12V 8V 12V 8V 12V 12V 24V 12V 24V 12V 24V 12V 24V

power 4 4 8 8 16 16 25 25 16 16 40 40 63 63

bell SU212 8/12V 1 1 3 2 5 3 - - - - - - - -

buzzer SU214 8/12V 1 1 3 2 5 3 - - - - - - - -

relays ER124 12V - - - - - - 4 - 2 - 7 - 8 -

ER139 12V - - - - - - 2 - 1 - 3 - 4 -

ER123 24V - - - - - - - 2 - 2 - 7 - 8

ER138 24V - - - - - - - 2 - 1 - 3 - 4

contactors ES224 24V - - - - - - - 5 - 3 - 11 - 12

ES424 24V - - - - - - - 3 - 2 - 7 - 8

latching relays EP519 12V - - - - - 2 3 - 2 - 4 - 4 -

EP529 12V - - - - - 1 2 - 1 - 3 - 3 -

EP513 24V - - - - - - - 2 - 2 - 3 - 3

EP518 24V - - - - - - - 2 - 2 - 3 - 3

EP525 24V - - - - - - - 2 - 2 - 3 - 3

EP528 24V - - - - - - - 2 - 1 - 3 - 3

EP541 24V - - - - - - - 2 - 1 - 3 - 3

Page 30: HAGER AutomationProducts

30

voltmeters, ammeters and hours counters

R

S

T

N

0

SK 603

L1

L2

L3

11 9

4 10 2

3

2 4 1412SM 151/SM 401

RSTN

0L1L2

L2L3

L3L1

SK 602

L1

L2

L3

3 1

12 2 4 12 1410 6 2SM 501

2 4 12 14SM 020

230 V~0/20 A

2 4 12 14

230 V~/5 A

SM 151/SM 401/SM 6012 4 12 14

SM 501

230 V~0/500 V~

A1

A2

00005 20

EC 100

digital voltmeter and ammeter

technical specificationselectrical characteristics– working voltage: 220/230V~ 50/60Hz– consumption: 4VA

environment– working T°: -5 to +40°C– storage T°: -30°C to +75°C

connection

– connection capacity: flexible: 6mm2

rigid: 10mm2

overload withstand of ammeters- 2 x In continuous- 10 x In for 5 secondsthese values are to allow for starting currents

electrical connectionelectrical connection

hours countertechnical specifications

electrical characteristics– working voltage: 230V~

electrical connection– connection in parallel on the command of the receiver

(contactor coil)

electrical connection

application diagrams

range of voltmeters

cat. ref. scale input resolution accuracyresistance ±1 digit

SM625 0-999V 3.3 MOhm 1V 1%

range of ammeterscat. ref. scale volt resolution accuracy

drop ± digit

SM626 0-99.9A 120 mV 0.01A 1%

SM627 0-99.9/5A 120 mV 0.1A 1%

SM628 0-400/5A 120 mV 1A 1%

Page 31: HAGER AutomationProducts

31

voltmeters, ammeters and current transformers

R

ST

N

0L1L2

L2L3

L3L1

SK 602

L1

L2

L3

3 1

12 10 6 2SM 500

1000200 400

500

V

300

0

SK 603

L1

L2

L3

R

S

T

N

11 9

4 10 2

3

SM 050

0 50

A

analogue voltmeter and ammeter

technical specificationselectrical characteristics– direct reading voltmeter: 300V and 500V for 50/60Hz– direct reading ammeter: 10A, 20A, 30A– ammeter with CT: CT/5A– consumption: voltmeter: 1.5VA/ammeter: 0.3VA– isolating voltage: 2kV

environment– working T°: 20°C ± 10°C class = 2– working T°: -10°C to +50°C class > 2– storage T°: -30°C to +75°C

connection capacity– flexible: 1 to 6mm2

– rigid: 1.5 to 10mm2

electrical connectionelectrical connection

voltmeters range

current transformers (CT)technical specificationselectrical characteristics– primary current: 50 to 400A (depend. on model) secondary current: 5A– frequency: 40/60Hz

56 28

84

46

56

84

42

60

46

107

77

64

range of CT’sSR671: 50/5A - SR673: 80/5ASR672: 60/5A - SR674: 100/5A

SR675: 150/5A - SR677: 250/5ASR676: 200/5A

SR678: 300/5ASR679: 400/5A

voltmeters range

cat. ref. scale reading

SM630 0-300V direct

SM650 0-500V direct

cat. ref. scale reading

SM615 0-10A direct

SM620 0-20A direct

SM640 0-30A direct

SM610 see below via CT/5A

measurement scale for SM610

SM659 0-5A

SM661 0-50A

SM662 0-60A

SM663 0-80A

SM664 0-100A

SM665 0-150A

SM666 0-200A

SM667 0-250A

SM668 0-300A

SM669 0-400A

Page 32: HAGER AutomationProducts

32

kWh meters

technical specifications EC031electrical characteristics– working voltage: 3 x 230/400V -20% +15%– frequency: 50/60Hz– In: 5A– Imax: 6A– current transformer ratio:

50/5 - 100/5 - 200/5 - 300/5 - 400/5 - 500/5 - 600/5 - 800/5 – CT ratio selector, not accessible when front plate in place B.– to get direct reading in kWh the selector must be adjusted to the

corresponding value of chosen.functional characteristics– size: 7 modules (122.5mm)– direct reading on display: unit = 1 kWh– accuracy: class 2 (acc. to IEC 1036)– power level indicator: 16 impulses per kWh A.environment– working temperature: -10°C to +45°C– storage temperature: -25°C to +70°Cconnection capacity– max: 6mm2

electrical connection1. supply 2. loadIt is important to ensure correct termination and that the polarity of the conductors passingthrough the torroid is constant to achieve accurate recording of the cumulative current consumption in all three phases.warning:– never connect the secondaries of CTs to earth – never make a common connection on the meters (+)

incoming terminals.impulse transmitter (EC031 only)– output optocoupler– conformity DIN 43864– 1 pulse = 1kWh– pulse duration: 100ms ±10%– internal between 2 pulse ≥ 30ms– insulation: 2kV– external supply: 27V ... max.

– operating current:– – closed output: 10 to 27mA– open output: 0 to 2mA

connection capacity– max: 6mm2

technical specifications EC010-EC011direct connection– supply : 230V -20 +15%– frequency: 50Hz.– working current: 75 mA to 90A– wattmeter measure: 10 to 18,000 W– the counters comply with IEC 1036– accuracy: class 2 (±2% from 1.5A to 90A)– power level indicator: illum. in excess of 1W– direct reading on displays, unit:

energy 1 kWhinstant consumption 1W

– working temperature: -10°C to +60°C– storage temperature: -25°C to +70°Cconnection capacity– power clamps 25mm2 max– impulse transmitter: max 6mm2 for a connection with flexible cableelectrical connection1. supply 2. loadimpulse transmitter (EC011)– output an optocoupler complying with DIN 43– 1 pulse = 1 Wh– interval between 2 impulses ≥ 30ms– insulation: 2kV– external supply: Ue ≤ 27V dc

Re (kΩ) ≥ Ue (V) /27– operating current:– closed output: ≤ 27mA

1(mA) = Ue (V) / Re (kΩ)– open output: ≤ 2mA by 27V

L2

S1 S2

P2

L3

L1

S1 S2

P2

S1 S2

P2

ED

3+

4-

5+

6-

7+

8-

9L1

10L2

11L3 N

N

12

B

A

1 2

50

100

200

300400

500

600

800

000001 kWh

kWh

CL?

E

ED

C

B

A

1 2