18
P LY CABLE IND.LTD. aluminium & copper cable manufacture Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected] , Web : www.polycables.com.bd Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj Web: www.polycables.com.bd Customer Power Grid Company of Bangladesh Limited (PGCB) Name of Project Lot-2: Design, Supply, Erection, Testing & Commissioning of 132kV Transmission Lines and substations on Turnkey Basis Contract No. PSEEIP/ADB/PGCB/SS dated 18.09.2014 Contractor ABB India Limited Supplier POLY CABLE INDUSTRIES LIMITED PO No. 3191772893 dated 16.09.2015 Title 4x1.5mm 2 (CU/XLPE/SWA/FRLS-PVC) Drawing No. 01 DRUM DIMENSION WOODEN DRUM d1 d2 d3 L1+BOLT L2 Φ 10 1000 mm 500 mm 75 mm 690 mm 600 mm Ød3 Ød2 Ød1 L2 L1 FIGURE 01: 4x1.5mm 2 (CU/XLPE/SWA/FRLS-PVC) STEEL WIRE ARMOUR PVC INNER SHEATH TAPE BINDER XLPE INSULATION COPPER CONDUCTOR TAPE BINDER FRLS-PVC OUTER SHEATH

description

GTP for ABB India Limited

Transcript of GTP for ABB India Limited

Page 1: GTP for ABB India Limited

P LY CABLE IND.LTD. aluminium & copper cable manufacture

Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd

Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj

Web: www.polycables.com.bd

Customer Power Grid Company of Bangladesh Limited (PGCB) Name of Project Lot-2: Design, Supply, Erection, Testing & Commissioning of

132kV Transmission Lines and substations on Turnkey Basis Contract No. PSEEIP/ADB/PGCB/SS dated 18.09.2014 Contractor ABB India Limited Supplier POLY CABLE INDUSTRIES LIMITED PO No. 3191772893 dated 16.09.2015 Title 4x1.5mm2 (CU/XLPE/SWA/FRLS-PVC) Drawing No. 01

DRUM DIMENSION

WOODEN DRUM d1 d2 d3 L1+BOLT L2

Φ 10 1000 mm 500 mm 75 mm 690 mm 600 mm

Ød3

Ød2

Ød1

L2

L1

FIGURE 01: 4x1.5mm2 (CU/XLPE/SWA/FRLS-PVC)

STEEL WIRE ARMOUR

PVC INNER SHEATH

TAPE BINDER XLPE INSULATION

COPPER CONDUCTOR

TAPE BINDER

FRLS-PVC OUTER SHEATH

Page 2: GTP for ABB India Limited

P LY CABLE IND.LTD. aluminium & copper cable manufacture

Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd

Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj

Web: www.polycables.com.bd

TECHNICAL PARTICULARS FOR

4Cx1.5mm² CU/XLPE/PVC/SWA/FRLS-PVC Specification: IEC 60502 Part–1; Rated Voltage: Uo /U: 600/1000V

Guaranteed Technical Particulars of Control Cable: Plain Annealed Stranded Circular Copper Conductor, XLPE Insulated, Non Hygroscopic Polypropylene Filler & Tapes Bedding, PVC Extruded Inner Sheath, Galvanizing Steel Round Wire Armored, Non Hygroscopic Tapes Bedding & Overall FRLS-PVC Sheathed Cables

SL.# Description Unit Standard particulars Guaranteed Technical Particulars

01 CONDUCTOR: i) Number of Core ii) Cross Sectional area iii) No/Diameter of each wire iv) Conductor Diameter

No

4

4

mm² 1.5 1.5 No/mm 7/0.52 7/0.52

mm 1.56 1.56 02 MAXIMUM DC RESISTANCE OF 20º C Ω/km 12.10 12.10 03 INSULATION:

i) Martial ii) Nominal thickness iii) Minimum thickness iv) Insulated core diameter (approx) v) Core Identification

XLPE

XLPE

mm 0.70 0.70 mm 0.53 0.53 mm 3.0 3.0 --- Red, Yellow, Blue, Natural Red, Yellow, Blue, Natural

04 DIAMETER OF LAID UP CORE mm 7.25 7.25 05 TAPES BEDDING:

i) Material -

Non Hygroscopic Material

Non Hygroscopic Material

06 INNER SHEATH i) Martial ii) Nominal thickness iii) Diameter over inner sheath iv) Colour

PVC

PVC

mm 0.80 0.80 mm 9.10 9.10

Black Black 07 ARMOURING:

i) Material ii) Approx .No/wire diameter iii) Diameter over Armoring (approx)

Galvanizing Round Wire

Galvanizing Round Wire

No/mm 35± 3/0.80 35± 3/0.80 mm 10.70 10.70

08 TAPES BEDDING: i) Material

-

Non Hygroscopic Material

Non Hygroscopic Material

09 OUTER SHEATH: i) Martial ii) Nominal thickness iii) Minimum thickness iv) Colour

-

FRLS-PVC

FRLS-PVC

mm 1.80 1.80 mm 1.24 1.24

- Black Black 10 COMPLETED CABLE:

i) Approx. Overall Diameter ii) Approx Weight iii) Standard Packing Length iv) Drum Type v) Gross Weight ± 5%

mm

14.90

14.90±2.0

Kg/km - 385 - 1000 1000±5% - Wooden Wooden

Kg - 455±5% 11 MAXIMUM CONDUCTOR TEMP °C 90 90 12 EMBOSSING OR PRINTING - Printing & Meter Marking per Meter 13 TEST VOLTAGE kV 3.5 3.5 14 CURRENT RATING:

i) At 30°C in ground ii) At 35°C in air

Amps Amps

30 23

15 SHROT CIRCUIT CURRENT: i) For 1 sec

kA

0.213

Engr. Anamul Kabir Engr. Mohammad Ali Manager Deputy General Manager

Page 3: GTP for ABB India Limited

P LY CABLE IND.LTD. aluminium & copper cable manufacture

Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd

Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj

Web: www.polycables.com.bd

Customer Power Grid Company of Bangladesh Limited (PGCB) Name of Project Lot-2: Design, Supply, Erection, Testing & Commissioning of

132kV Transmission Lines and substations on Turnkey Basis Contract No. PSEEIP/ADB/PGCB/SS dated 18.09.2014 Contractor ABB India Limited Supplier POLY CABLE INDUSTRIES LIMITED PO No. 3191772893 dated 16.09.2015 Title 7x1.5mm2 (CU/XLPE/SWA/FRLS-PVC) Drawing No. 02

DRUM DIMENSION

WOODEN DRUM d1 d2 d3 L1+BOLT L2

Φ 12 1200 mm 675 mm 75 mm 950 mm 850 mm

Ød3

Ød2

Ød1

L2

L1

FIGURE 02: 7x1.5mm2 (CU/XLPE/SWA/FRLS-PVC)

STEEL WIRE ARMOUR

PVC INNER SHEATH

TAPE BINDER XLPE INSULATION COPPER CONDUCTOR

TAPE BINDER

FRLS-PVC OUTER SHEATH

Page 4: GTP for ABB India Limited

P LY CABLE IND.LTD. aluminium & copper cable manufacture

Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd

Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj

Web: www.polycables.com.bd

TECHNICAL PARTICULARS FOR

7Cx1.5mm² CU/XLPE/PVC/SWA/FRLS-PVC Specification: IEC 60502 Part–1; Rated Voltage: Uo /U: 600/1000V

Guaranteed Technical Particulars of Control Cable: Plain Annealed Stranded Circular Copper Conductor, XLPE Insulated, Non Hygroscopic Polypropylene Tapes Bedding, PVC Extruded Inner Sheath, Galvanizing Steel Round Wire Armored, Non Hygroscopic Tapes Bedding & Overall FRLS-PVC Sheathed Cables

SL.# Description Unit Standard particulars Guaranteed Technical Particulars

01 CONDUCTOR: i) Number of Core ii) Cross Sectional area iii) No/Diameter of each wire iv) Conductor Diameter

No

7

7

mm² 1.5 1.5 No/mm 7/0.52 7/0.52

mm 1.56 1.56 02 MAXIMUM DC RESISTANCE OF 20º C Ω/km 12.10 12.10 03 INSULATION:

i) Martial ii) Nominal thickness iii) Minimum thickness iv) Insulated core diameter (approx) v) Core Identification

XLPE

XLPE

mm 0.70 0.70 mm 0.53 0.53 mm 3.0 3.0 --- Natural with Core Number Natural with Core Number

04 DIAMETER OF LAID UP CORE mm 9.0 9.0 05 TAPES BEDDING:

i) Material -

Non Hygroscopic Material

Non Hygroscopic Material

06 INNER SHEATH i) Martial ii) Nominal thickness iii) Diameter over inner sheath iv) Colour

PVC

PVC

mm 0.80 0.80 mm 10.8 10.8

Black Black 07 ARMOURING:

i) Material ii) Approx .No/wire diameter iii) Diameter over Armoring (approx)

Galvanizing Round Wire

Galvanizing Round Wire

No/mm 27± 3/1.25 27± 3/1.25 mm 13.3 13.3

08 TAPES BEDDING: i) Material

-

Non Hygroscopic Material

Non Hygroscopic Material

09 OUTER SHEATH: i) Martial ii) Nominal thickness iii) Minimum thickness iv) Colour

-

FRLS-PVC

FRLS-PVC

mm 1.80 1.80 mm 1.24 1.24

- Black Black 10 COMPLETED CABLE:

i) Approx. Overall Diameter ii) Approx Weight iii) Standard Packing Length iv) Drum Type v) Gross Weight ± 5%

mm

17.50

17.50±2.0

Kg/km - 588 - 1000 1000±5% - Wooden Wooden

Kg - 698±5% 11 MAXIMUM CONDUCTOR TEMP °C 90 90 12 EMBOSSING OR PRINTING - Printing & Meter Marking per Meter 13 TEST VOLTAGE kV 3.5 3.5 14 CURRENT RATING:

i) At 30°C in ground ii) At 35°C in air

Amps Amps

18 13

15 SHROT CIRCUIT CURRENT: i) For 1 sec

kA

0.213

Engr. Anamul Kabir Engr. Mohammad Ali Manager Deputy General Manager

Page 5: GTP for ABB India Limited

P LY CABLE IND.LTD. aluminium & copper cable manufacture

Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd

Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj

Web: www.polycables.com.bd

Customer Power Grid Company of Bangladesh Limited (PGCB) Name of Project Lot-2: Design, Supply, Erection, Testing & Commissioning of

132kV Transmission Lines and substations on Turnkey Basis Contract No. PSEEIP/ADB/PGCB/SS dated 18.09.2014 Contractor ABB India Limited Supplier POLY CABLE INDUSTRIES LIMITED PO No. 3191772893 dated 16.09.2015 Title 14x1.5mm2 (CU/XLPE/STA/FRLS-PVC) Drawing No. 03

DRUM DIMENSION

WOODEN DRUM d1 d2 d3 L1+BOLT L2

Φ 12 1200 mm 675 mm 75 mm 950 mm 850 mm

Ød3

Ød2

Ød1

L2

L1

FIGURE 03: 14x1.5mm2 (CU/XLPE/STA/FRLS-PVC)

STEEL TAPE ARMOUR

PVC INNER SHEATH

TAPE BINDER XLPE INSULATION

COPPER CONDUCTOR

FRLS-PVC OUTER SHEATH

Page 6: GTP for ABB India Limited

P LY CABLE IND.LTD. aluminium & copper cable manufacture

Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd

Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj

Web: www.polycables.com.bd

TECHNICAL PARTICULARS FOR

14Cx1.5mm² CU/XLPE/PVC/STA/FRLS-PVC Specification: IEC 60502 Part–1; Rated Voltage: Uo /U: 600/1000V

Guaranteed Technical Particulars of Control Cable: Plain Annealed Stranded Circular Copper Conductor, XLPE Insulated, Non Hygroscopic Polypropylene Tapes Bedding, PVC Extruded Inner Sheath, Galvanizing Steel Tape Armored & Overall FRLS-PVC Sheathed Cables

SL.# Description Unit Standard particulars Guaranteed Technical Particulars

01 CONDUCTOR: i) Number of Core ii) Cross Sectional area iii) No/Diameter of each wire iv) Conductor Diameter

No

14

14

mm² 1.5 1.5 No/mm 7/0.52 7/0.52

mm 1.56 1.56 02 MAXIMUM DC RESISTANCE OF 20º C Ω/km 12.10 12.10 03 INSULATION:

i) Martial ii) Nominal thickness iii) Minimum thickness iv) Insulated core diameter (approx) v) Core Identification

XLPE

XLPE

mm 0.70 0.70 mm 0.53 0.53 mm 3.0 3.0 --- Natural with Core Number Natural with Core Number

04 DIAMETER OF LAID UP CORE mm 13.2 13.2 05 TAPES BEDDING:

i) Material -

Non Hygroscopic Material

Non Hygroscopic Material

06 INNER SHEATH i) Martial ii) Nominal thickness iii) Diameter over inner sheath iv) Colour

PVC

PVC

mm 0.80 0.80 mm 15.0 15.0

Black Black 07 ARMOURING:

i) Material ii) Approx .No/Tape Thickness iii) Diameter over Armoring (approx)

Galvanizing Steel Tape

Galvanizing Steel Tape

No/mm 2 / 0.2±0.05 2 / 0.2±0.05 mm 15.6 15.6

08 OUTER SHEATH: i) Martial ii) Nominal thickness iii) Minimum thickness iv) Colour

-

FRLS-PVC

FRLS-PVC

mm 1.80 1.80 mm 1.24 1.24

- Black Black 09 COMPLETED CABLE:

i) Approx. Overall Diameter ii) Approx Weight iii) Standard Packing Length iv) Drum Type v) Gross Weight ± 5%

mm

19.20

19.20±2.0

Kg/km - 568 - 500 500±5% - Wooden Wooden

Kg - 395±5% 10 MAXIMUM CONDUCTOR TEMP °C 90 90 11 EMBOSSING OR PRINTING - Printing & Meter Marking per Meter 12 TEST VOLTAGE kV 3.5 3.5 13 CURRENT RATING:

i) At 30°C in ground ii) At 35°C in air

Amps Amps

12 9

14 SHROT CIRCUIT CURRENT: i) For 1 sec

kA

0.213

Engr. Anamul Kabir Engr. Mohammad Ali Manager Deputy General Manager

Page 7: GTP for ABB India Limited

P LY CABLE IND.LTD. aluminium & copper cable manufacture

Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd

Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj

Web: www.polycables.com.bd

Customer Power Grid Company of Bangladesh Limited (PGCB) Name of Project Lot-2: Design, Supply, Erection, Testing & Commissioning of

132kV Transmission Lines and substations on Turnkey Basis Contract No. PSEEIP/ADB/PGCB/SS dated 18.09.2014 Contractor ABB India Limited Supplier POLY CABLE INDUSTRIES LIMITED PO No. 3191772893 dated 16.09.2015 Title 19x1.5mm2 (CU/XLPE/STA/FRLS-PVC) Drawing No. 04

DRUM DIMENSION

WOODEN DRUM d1 d2 d3 L1+BOLT L2

Φ 12 1200 mm 675 mm 75 mm 950 mm 850 mm

Ød3

Ød2

Ød1

L2

L1

FIGURE 04: 19x1.5mm2 (CU/XLPE/STA/FRLS-PVC)

STEEL TAPE ARMOUR

PVC INNER SHEATH TAPE BINDER XLPE INSULATION

COPPER CONDUCTOR

FRLS-PVC OUTER SHEATH

Page 8: GTP for ABB India Limited

P LY CABLE IND.LTD. aluminium & copper cable manufacture

Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd

Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj

Web: www.polycables.com.bd

TECHNICAL PARTICULARS FOR

19Cx1.5mm² CU/XLPE/PVC/STA/FRLS-PVC Specification: IEC 60502 Part–1; Rated Voltage: Uo /U: 600/1000V

Guaranteed Technical Particulars of Control Cable: Plain Annealed Stranded Circular Copper Conductor, XLPE Insulated, Non Hygroscopic Polypropylene Tapes Bedding, PVC Extruded Inner Sheath, Galvanizing Steel Tape Armored & Overall FRLS-PVC Sheathed Cables

SL.# Description Unit Standard particulars Guaranteed Technical Particulars

01 CONDUCTOR: i) Number of Core ii) Cross Sectional area iii) No/Diameter of each wire iv) Conductor Diameter

No

19

19

mm² 1.5 1.5 No/mm 7/0.52 7/0.52

mm 1.56 1.56 02 MAXIMUM DC RESISTANCE OF 20º C Ω/km 12.10 12.10 03 INSULATION:

i) Martial ii) Nominal thickness iii) Minimum thickness iv) Insulated core diameter (approx) v) Core Identification

XLPE

XLPE

mm 0.70 0.70 mm 0.53 0.53 mm 3.0 3.0 --- Natural with Core Number Natural with Core Number

04 DIAMETER OF LAID UP CORE mm 15.0 15.0 05 TAPES BEDDING:

i) Material -

Non Hygroscopic Material

Non Hygroscopic Material

06 INNER SHEATH i) Martial ii) Nominal thickness iii) Diameter over inner sheath iv) Colour

PVC

PVC

mm 0.80 0.80 mm 16.8 16.8

Black Black 07 ARMOURING:

i) Material ii) Approx .No/Tape Thickness iii) Diameter over Armoring (approx)

Galvanizing Steel Tape

Galvanizing Steel Tape

No/mm 2 / 0.2±0.05 2 / 0.2±0.05 mm 17.4 17.4

08 OUTER SHEATH: i) Martial ii) Nominal thickness iii) Minimum thickness iv) Colour

-

FRLS-PVC

FRLS-PVC

mm 1.80 1.80 mm 1.24 1.24

- Black Black 09 COMPLETED CABLE:

i) Approx. Overall Diameter ii) Approx Weight iii) Standard Packing Length iv) Drum Type v) Gross Weight ± 5%

mm

21.00

21.00±2.0

Kg/km - 695 - 500 500±5% - Wooden Wooden

Kg - 458±5% 10 MAXIMUM CONDUCTOR TEMP °C 90 90 11 EMBOSSING OR PRINTING - Printing & Meter Marking per Meter 12 TEST VOLTAGE kV 3.5 3.5 13 CURRENT RATING:

i) At 30°C in ground ii) At 35°C in air

Amps Amps

11 8

14 SHROT CIRCUIT CURRENT: i) For 1 sec

kA

0.213

Engr. Anamul Kabir Engr. Mohammad Ali Manager Deputy General Manager

Page 9: GTP for ABB India Limited

P LY CABLE IND.LTD. aluminium & copper cable manufacture

Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd

Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj

Web: www.polycables.com.bd

Customer Power Grid Company of Bangladesh Limited (PGCB) Name of Project Lot-2: Design, Supply, Erection, Testing & Commissioning of

132kV Transmission Lines and substations on Turnkey Basis Contract No. PSEEIP/ADB/PGCB/SS dated 18.09.2014 Contractor ABB India Limited Supplier POLY CABLE INDUSTRIES LIMITED PO No. 3191772893 dated 16.09.2015 Title 24x1.5mm2 (CU/XLPE/STA/FRLS-PVC) Drawing No. 05

DRUM DIMENSION

WOODEN DRUM d1 d2 d3 L1+BOLT L2

Φ 12 1200 mm 675 mm 75 mm 950 mm 850 mm

Ød3

Ød2

Ød1

L2

L1

FIGURE 05: 24x1.5mm2 (CU/XLPE/STA/FRLS-PVC)

STEEL TAPE ARMOUR

PVC INNER SHEATH

TAPE BINDER XLPE INSULATION

COPPER CONDUCTOR

FRLS-PVC OUTER SHEATH

Page 10: GTP for ABB India Limited

P LY CABLE IND.LTD. aluminium & copper cable manufacture

Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd

Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj

Web: www.polycables.com.bd

TECHNICAL PARTICULARS FOR

24Cx1.5mm² CU/XLPE/PVC/STA/FRLS-PVC Specification: IEC 60502 Part–1; Rated Voltage: Uo /U: 600/1000V

Guaranteed Technical Particulars of Control Cable: Plain Annealed Stranded Circular Copper Conductor, XLPE Insulated, Non Hygroscopic Polypropylene Tapes Bedding, PVC Extruded Inner Sheath, Galvanizing Steel Tape Armored & Overall FRLS-PVC Sheathed Cables

SL.# Description Unit Standard particulars Guaranteed Technical Particulars

01 CONDUCTOR: i) Number of Core ii) Cross Sectional area iii) No/Diameter of each wire iv) Conductor Diameter

No

24

24

mm² 1.5 1.5 No/mm 7/0.52 7/0.52

mm 1.56 1.56 02 MAXIMUM DC RESISTANCE OF 20º C Ω/km 12.10 12.10 03 INSULATION:

i) Martial ii) Nominal thickness iii) Minimum thickness iv) Insulated core diameter (approx) v) Core Identification

XLPE

XLPE

mm 0.70 0.70 mm 0.53 0.53 mm 3.0 3.0 --- Natural with Core Number Natural with Core Number

04 DIAMETER OF LAID UP CORE mm 18.0 18.0 05 TAPES BEDDING:

i) Material -

Non Hygroscopic Material

Non Hygroscopic Material

06 INNER SHEATH i) Martial ii) Nominal thickness iii) Diameter over inner sheath iv) Colour

PVC

PVC

mm 0.80 0.80 mm 19.8 19.8

Black Black 07 ARMOURING:

i) Material ii) Approx .No/Tape Thickness iii) Diameter over Armoring (approx)

Galvanizing Steel Tape

Galvanizing Steel Tape

No/mm 2 / 0.2±0.05 2 / 0.2±0.05 mm 20.4 20.4

08 OUTER SHEATH: i) Martial ii) Nominal thickness iii) Minimum thickness iv) Colour

-

FRLS-PVC

FRLS-PVC

mm 1.80 1.80 mm 1.24 1.24

- Black Black 09 COMPLETED CABLE:

i) Approx. Overall Diameter ii) Approx Weight iii) Standard Packing Length iv) Drum Type v) Gross Weight ± 5%

mm

24.00

24.00±2.0

Kg/km - 848 - 500 500±5% - Wooden Wooden

Kg - 535±5% 10 MAXIMUM CONDUCTOR TEMP °C 90 90 11 EMBOSSING OR PRINTING - Printing & Meter Marking per Meter 12 TEST VOLTAGE kV 3.5 3.5 13 CURRENT RATING:

i) At 30°C in ground ii) At 35°C in air

Amps Amps

10 8

14 SHROT CIRCUIT CURRENT: i) For 1 sec

kA

0.213

Engr. Anamul Kabir Engr. Mohammad Ali Manager Deputy General Manager

Page 11: GTP for ABB India Limited

P LY CABLE IND.LTD. aluminium & copper cable manufacture

Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd

Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj

Web: www.polycables.com.bd

Customer Power Grid Company of Bangladesh Limited (PGCB) Name of Project Lot-2: Design, Supply, Erection, Testing & Commissioning of

132kV Transmission Lines and substations on Turnkey Basis Contract No. PSEEIP/ADB/PGCB/SS dated 18.09.2014 Contractor ABB India Limited Supplier POLY CABLE INDUSTRIES LIMITED PO No. 3191772893 dated 16.09.2015 Title 2x6mm2 (CU/XLPE/SWA/FRLS-PVC) Drawing No. 06

DRUM DIMENSION

WOODEN DRUM d1 d2 d3 L1+BOLT L2

Φ 10 1000 mm 500 mm 75 mm 690 mm 600 mm

Ød3

Ød2

Ød1

L2

L1

FIGURE 06: 2x6.0mm2 (CU/XLPE/SWA/FRLS-PVC)

STEEL WIRE ARMOUR

PVC INNER COVERING XLPE INSULATION

COPPER CONDUCTOR

TAPE BINDER

FRLS-PVC OUTER SHEATH

Page 12: GTP for ABB India Limited

P LY CABLE IND.LTD. aluminium & copper cable manufacture

Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd

Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj

Web: www.polycables.com.bd

TECHNICAL PARTICULARS FOR 2Cx6mm² CU/XLPE/PVC/SWA/FRLS-PVC

Specification: IEC 60502 Part–1; Rated Voltage: Uo /U: 600/1000V Guaranteed Technical Particulars of Control Cable: Plain Annealed Stranded Circular Copper Conductor, XLPE Insulated, , PVC Extruded Inner Sheath, Galvanizing Steel Round Wire Armored, Non Hygroscopic Tapes Bedding & Overall FRLS-PVC Sheathed Cables

SL.# Description Unit Standard particulars Guaranteed Technical Particulars

01 CONDUCTOR: i) Number of Core ii) Cross Sectional area iii) No/Diameter of each wire iv) Conductor Diameter

No

2

2

mm² 6 6 No/mm 7/1.05 7/1.05

mm 3.15 3.15 02 MAXIMUM DC RESISTANCE OF 20º C Ω/km 3.08 3.08 03 INSULATION:

i) Martial ii) Nominal thickness iii) Minimum thickness iv) Insulated core diameter (approx) v) Core Identification

XLPE

XLPE

mm 0.70 0.70 mm 0.53 0.53 mm 4.6 4.6 --- Red, Natural Red, Natural

04 DIAMETER OF LAID UP CORE mm 9.20 9.20 05 INNER SHEATH

i) Martial ii) Nominal thickness iii) Diameter over inner sheath iv) Colour

PVC

PVC

mm 0.80 0.80 mm 10.8 10.8

Black Black 06 ARMOURING:

i) Material ii) Approx .No/wire diameter iii) Diameter over Armoring (approx)

Galvanizing Round Wire

Galvanizing Round Wire

No/mm 27± 3/1.25 27± 3/1.25 mm 13.3 13.3

07 TAPES BEDDING: i) Material

-

Non Hygroscopic Material

Non Hygroscopic Material

08 OUTER SHEATH: i) Martial ii) Nominal thickness iii) Minimum thickness iv) Colour

-

FRLS-PVC

FRLS-PVC

mm 1.80 1.80 mm 1.24 1.24

- Black Black 09 COMPLETED CABLE:

i) Approx. Overall Diameter ii) Approx Weight iii) Standard Packing Length iv) Drum Type v) Gross Weight ± 5%

mm

17.50

17.50±2.0

Kg/km - 630 - 1000 1000±5% - Wooden Wooden

Kg - 700±5% 10 MAXIMUM CONDUCTOR TEMP °C 90 90 11 EMBOSSING OR PRINTING - Printing & Meter Marking per Meter 12 TEST VOLTAGE kV 3.5 3.5 13 CURRENT RATING:

i) At 30°C in ground ii) At 35°C in air

Amps Amps

74 62

14 SHROT CIRCUIT CURRENT: i) For 1 sec

kA

0.852

Engr. Anamul Kabir Engr. Mohammad Ali Manager Deputy General Manager

Page 13: GTP for ABB India Limited

P LY CABLE IND.LTD. aluminium & copper cable manufacture

Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd

Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj

Web: www.polycables.com.bd

Customer Power Grid Company of Bangladesh Limited (PGCB) Name of Project Lot-2: Design, Supply, Erection, Testing & Commissioning of

132kV Transmission Lines and substations on Turnkey Basis Contract No. PSEEIP/ADB/PGCB/SS dated 18.09.2014 Contractor ABB India Limited Supplier POLY CABLE INDUSTRIES LIMITED PO No. 3191772893 dated 16.09.2015 Title 4x16mm2 (CU/XLPE/STA/FRLS-PVC) Drawing No. 07

DRUM DIMENSION

WOODEN DRUM d1 d2 d3 L1+BOLT L2

Φ 12 1200 mm 675 mm 75 mm 950 mm 850 mm

Ød3

Ød2

Ød1

L2

L1

FIGURE 07: 4x16mm2 (CU/XLPE/STA/FRLS-PVC)

STEEL TAPE ARMOUR

PVC INNER SHEATH TAPE BINDER XLPE INSULATION

COPPER CONDUCTOR

FRLS-PVC OUTER SHEATH

Page 14: GTP for ABB India Limited

P LY CABLE IND.LTD. aluminium & copper cable manufacture

Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd

Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj

Web: www.polycables.com.bd

TECHNICAL PARTICULARS FOR

4Cx16mm² CU/XLPE/PVC/STA/FRLS-PVC Specification: IEC 60502 Part–1; Rated Voltage: Uo /U: 600/1000V

Guaranteed Technical Particulars of Power Cable: Plain Annealed Stranded Circular Copper Conductor, XLPE Insulated, Non Hygroscopic Polypropylene Filler & Tapes Bedding, PVC Extruded Inner Sheath, Galvanizing Steel Tape Armored & Overall FRLS-PVC Sheathed Cables

SL.# Description Unit Standard particulars Guaranteed Technical Particulars

01 CONDUCTOR: i) Number of Core ii) Cross Sectional area iii) No/Diameter of each wire iv) Conductor Diameter

No

4

4

mm² 16 16 No/mm 7/1.71 7/1.71

mm 5.13 5.13 02 MAXIMUM DC RESISTANCE OF 20º C Ω/km 1.15 1.15 03 INSULATION:

i) Martial ii) Nominal thickness iii) Minimum thickness iv) Insulated core diameter (approx) v) Core Identification

XLPE

XLPE

mm 0.70 0.70 mm 0.53 0.53 mm 6.6 6.6 --- Red, Yellow, Blue, Natural Red, Yellow, Blue, Natural

04 DIAMETER OF LAID UP CORE mm 15.95 15.95 05 TAPES BEDDING:

i) Material -

Non Hygroscopic Material

Non Hygroscopic Material

06 INNER SHEATH i) Martial ii) Nominal thickness iii) Diameter over inner sheath iv) Colour

PVC

PVC

mm 0.80 0.80 mm 17.75 17.75

Black Black 07 ARMOURING:

i) Material ii) Approx .No/Tape Thickness iii) Diameter over Armoring (approx)

Galvanizing Steel Tape

Galvanizing Steel Tape

No/mm 2 / 0.2±0.05 2 / 0.2±0.05 mm 18.35 18.35

08 OUTER SHEATH: i) Martial ii) Nominal thickness iii) Minimum thickness iv) Colour

-

FRLS-PVC

FRLS-PVC

mm 1.80 1.80 mm 1.24 1.24

- Black Black 09 COMPLETED CABLE:

i) Approx. Overall Diameter ii) Approx Weight iii) Standard Packing Length iv) Drum Type v) Gross Weight ± 5%

mm

22.00

22.00±2.0

Kg/km - 1030 - 500 500±5% - Wooden Wooden

Kg - 625±5% 10 MAXIMUM CONDUCTOR TEMP °C 90 90 11 EMBOSSING OR PRINTING - Printing & Meter Marking per Meter 12 TEST VOLTAGE kV 3.5 3.5 13 CURRENT RATING:

i) At 30°C in ground ii) At 35°C in air

Amps Amps

110 98

14 SHROT CIRCUIT CURRENT: i) For 1 sec

kA

2.272

Engr. Anamul Kabir Engr. Mohammad Ali Manager Deputy General Manager

Page 15: GTP for ABB India Limited

P LY CABLE IND.LTD. aluminium & copper cable manufacture

Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd

Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj

Web: www.polycables.com.bd

Customer Power Grid Company of Bangladesh Limited (PGCB) Name of Project Lot-2: Design, Supply, Erection, Testing & Commissioning of

132kV Transmission Lines and substations on Turnkey Basis Contract No. PSEEIP/ADB/PGCB/SS dated 18.09.2014 Contractor ABB India Limited Supplier POLY CABLE INDUSTRIES LIMITED PO No. 3191772893 dated 16.09.2015 Title 4x120mm2 (CU/XLPE/STA/FRLS-PVC) Drawing No. 08

DRUM DIMENSION

WOODEN DRUM d1 d2 d3 L1+BOLT L2

Φ 22 2200 mm 1400 mm 110 mm 1390 mm 1250 mm

Ød3

Ød2

Ød1

L2

L1

FIGURE 08: 4x120mm2 (CU/XLPE/STA/FRLS-PVC)

STEEL TAPE ARMOUR

PVC INNER COVERING

TAPE BINDER XLPE INSULATION

COPPER CONDUCTOR

FRLS-PVC OUTER SHEATH

Page 16: GTP for ABB India Limited

P LY CABLE IND.LTD. aluminium & copper cable manufacture

Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd

Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj

Web: www.polycables.com.bd

TECHNICAL PARTICULARS FOR

4Cx120mm² CU/XLPE/PVC/STA/FRLS-PVC Specification: IEC 60502 Part–1; Rated Voltage: Uo /U: 600/1000V

Guaranteed Technical Particulars of Power Cable: Plain Annealed Stranded Sector Shaped Copper Conductor, XLPE Insulated, Non Hygroscopic Polypropylene Filler & Tapes Bedding, PVC Extruded Inner Sheath, Galvanizing Steel Tape Armored & Overall FRLS-PVC Sheathed Cables

SL.# Description Unit Standard particulars Guaranteed Technical Particulars

01 CONDUCTOR: i) Number of Core ii) Cross Sectional area iii) No/Diameter of each wire iv) Conductor Diameter

No

4

4

mm² 120 120 No/mm 39/2.03 39/2.03

mm 12.38 12.38 02 MAXIMUM DC RESISTANCE OF 20º C Ω/km 0.153 0.153 03 INSULATION:

i) Martial ii) Nominal thickness iii) Minimum thickness iv) Insulated core diameter (approx) v) Core Identification

XLPE

XLPE

mm 1.20 1.20 mm 0.98 0.98 mm 14.80 14.80 --- Red, Yellow, Blue, Natural Red, Yellow, Blue, Natural

04 DIAMETER OF LAID UP CORE mm 35.80 35.80 05 TAPES BEDDING:

i) Material -

Non Hygroscopic Material

Non Hygroscopic Material

06 INNER SHEATH i) Martial ii) Nominal thickness iii) Diameter over inner sheath iv) Colour

PVC

PVC

mm 1.40 1.40 mm 39.40 39.40

Black Black 07 ARMOURING:

i) Material ii) Approx .No/Tape Thickness iii) Diameter over Armoring (approx)

Galvanizing Steel Tape

Galvanizing Steel Tape

No/mm 2 / 0.3±0.05 2 / 0.3±0.05 mm 40.10 40.10

08 OUTER SHEATH: i) Martial ii) Nominal thickness iii) Minimum thickness iv) Colour

-

FRLS-PVC

FRLS-PVC

mm 2.40 2.40 mm 1.72 1.72

- Black Black 09 COMPLETED CABLE:

i) Approx. Overall Diameter ii) Approx Weight iii) Standard Packing Length iv) Drum Type v) Gross Weight ± 5%

mm

44.90

44.90±2.5

Kg/km - 5885 - 500 500±5% - Wooden Wooden

Kg - 3420±5% 10 MAXIMUM CONDUCTOR TEMP °C 90 90 11 EMBOSSING OR PRINTING - Printing & Meter Marking per Meter 12 TEST VOLTAGE kV 3.5 3.5 13 CURRENT RATING:

i) At 30°C in ground ii) At 35°C in air

Amps Amps

295 305

14 SHROT CIRCUIT CURRENT: i) For 1 sec

kA

17.04

Engr. Anamul Kabir Engr. Mohammad Ali Manager Deputy General Manager

Page 17: GTP for ABB India Limited

P LY CABLE IND.LTD. aluminium & copper cable manufacture

Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd

Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj

Web: www.polycables.com.bd

Customer Power Grid Company of Bangladesh Limited (PGCB) Name of Project Lot-2: Design, Supply, Erection, Testing & Commissioning of

132kV Transmission Lines and substations on Turnkey Basis Contract No. PSEEIP/ADB/PGCB/SS dated 18.09.2014 Contractor ABB India Limited Supplier POLY CABLE INDUSTRIES LIMITED PO No. 3191772893 dated 16.09.2015 Title 4x4mm2 (CU/XLPE/SWA/FRLS-PVC) Drawing No. 09

DRUM DIMENSION

WOODEN DRUM d1 d2 d3 L1+BOLT L2

Φ 12 1200 mm 675 mm 75 mm 950 mm 850 mm

Ød3

Ød2

Ød1

L2

L1

FIGURE 09: 4x4mm2 (CU/XLPE/SWA/FRLS-PVC)

STEEL WIRE ARMOUR

PVC INNER SHEATH

TAPE BINDER XLPE INSULATION

COPPER CONDUCTOR

TAPE BINDER

FRLS-PVC OUTER SHEATH

Page 18: GTP for ABB India Limited

P LY CABLE IND.LTD. aluminium & copper cable manufacture

Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd

Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj

Web: www.polycables.com.bd

TECHNICAL PARTICULARS FOR 4Cx4mm² CU/XLPE/PVC/SWA/FRLS-PVC

Specification: IEC 60502 Part–1; Rated Voltage: Uo /U: 600/1000V Guaranteed Technical Particulars of Control Cable: Plain Annealed Stranded Circular Copper Conductor, XLPE Insulated, Non Hygroscopic Polypropylene Filler & Tapes Bedding, PVC Extruded Inner Sheath, Galvanizing Steel Round Wire Armored, Non Hygroscopic Tapes Bedding & Overall FRLS-PVC Sheathed Cables

SL.# Description Unit Standard particulars Guaranteed Technical Particulars

01 CONDUCTOR: i) Number of Core ii) Cross Sectional area iii) No/Diameter of each wire iv) Conductor Diameter

No

4

4

mm² 4 4 No/mm 7/0.85 7/0.85

mm 2.55 2.55 02 MAXIMUM DC RESISTANCE OF 20º C Ω/km 4.61 4.61 03 INSULATION:

i) Martial ii) Nominal thickness iii) Minimum thickness iv) Insulated core diameter (approx) v) Core Identification

XLPE

XLPE

mm 0.70 0.70 mm 0.53 0.53 mm 4.0 4.0 --- Red, Yellow, Blue, Natural Red, Yellow, Blue, Natural

04 DIAMETER OF LAID UP CORE mm 9.70 9.70 05 TAPES BEDDING:

i) Material -

Non Hygroscopic Material

Non Hygroscopic Material

06 INNER SHEATH i) Martial ii) Nominal thickness iii) Diameter over inner sheath iv) Colour

PVC

PVC

mm 0.80 0.80 mm 11.50 11.50

Black Black 07 ARMOURING:

i) Material ii) Approx .No/wire diameter iii) Diameter over Armoring (approx)

Galvanizing Round Wire

Galvanizing Round Wire

No/mm 29± 3/1.25 29± 3/1.25 mm 14.0 14.0

08 TAPES BEDDING: i) Material

-

Non Hygroscopic Material

Non Hygroscopic Material

09 OUTER SHEATH: i) Martial ii) Nominal thickness iii) Minimum thickness iv) Colour

-

FRLS-PVC

FRLS-PVC

mm 1.80 1.80 mm 1.24 1.24

- Black Black 10 COMPLETED CABLE:

i) Approx. Overall Diameter ii) Approx Weight iii) Standard Packing Length iv) Drum Type v) Gross Weight ± 5%

mm

18.20

18.20±2.0

Kg/km - 675 - 1000 1000±5% - Wooden Wooden

Kg - 785±5% 11 MAXIMUM CONDUCTOR TEMP °C 90 90 12 EMBOSSING OR PRINTING - Printing & Meter Marking per Meter 13 TEST VOLTAGE kV 3.5 3.5 14 CURRENT RATING:

i) At 30°C in ground ii) At 35°C in air

Amps Amps

48 41

15 SHROT CIRCUIT CURRENT: i) For 1 sec

kA

0.568