P LY CABLE IND.LTD. aluminium & copper cable manufacture
Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd
Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj
Web: www.polycables.com.bd
Customer Power Grid Company of Bangladesh Limited (PGCB) Name of Project Lot-2: Design, Supply, Erection, Testing & Commissioning of
132kV Transmission Lines and substations on Turnkey Basis Contract No. PSEEIP/ADB/PGCB/SS dated 18.09.2014 Contractor ABB India Limited Supplier POLY CABLE INDUSTRIES LIMITED PO No. 3191772893 dated 16.09.2015 Title 4x1.5mm2 (CU/XLPE/SWA/FRLS-PVC) Drawing No. 01
DRUM DIMENSION
WOODEN DRUM d1 d2 d3 L1+BOLT L2
Φ 10 1000 mm 500 mm 75 mm 690 mm 600 mm
Ød3
Ød2
Ød1
L2
L1
FIGURE 01: 4x1.5mm2 (CU/XLPE/SWA/FRLS-PVC)
STEEL WIRE ARMOUR
PVC INNER SHEATH
TAPE BINDER XLPE INSULATION
COPPER CONDUCTOR
TAPE BINDER
FRLS-PVC OUTER SHEATH
P LY CABLE IND.LTD. aluminium & copper cable manufacture
Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd
Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj
Web: www.polycables.com.bd
TECHNICAL PARTICULARS FOR
4Cx1.5mm² CU/XLPE/PVC/SWA/FRLS-PVC Specification: IEC 60502 Part–1; Rated Voltage: Uo /U: 600/1000V
Guaranteed Technical Particulars of Control Cable: Plain Annealed Stranded Circular Copper Conductor, XLPE Insulated, Non Hygroscopic Polypropylene Filler & Tapes Bedding, PVC Extruded Inner Sheath, Galvanizing Steel Round Wire Armored, Non Hygroscopic Tapes Bedding & Overall FRLS-PVC Sheathed Cables
SL.# Description Unit Standard particulars Guaranteed Technical Particulars
01 CONDUCTOR: i) Number of Core ii) Cross Sectional area iii) No/Diameter of each wire iv) Conductor Diameter
No
4
4
mm² 1.5 1.5 No/mm 7/0.52 7/0.52
mm 1.56 1.56 02 MAXIMUM DC RESISTANCE OF 20º C Ω/km 12.10 12.10 03 INSULATION:
i) Martial ii) Nominal thickness iii) Minimum thickness iv) Insulated core diameter (approx) v) Core Identification
XLPE
XLPE
mm 0.70 0.70 mm 0.53 0.53 mm 3.0 3.0 --- Red, Yellow, Blue, Natural Red, Yellow, Blue, Natural
04 DIAMETER OF LAID UP CORE mm 7.25 7.25 05 TAPES BEDDING:
i) Material -
Non Hygroscopic Material
Non Hygroscopic Material
06 INNER SHEATH i) Martial ii) Nominal thickness iii) Diameter over inner sheath iv) Colour
PVC
PVC
mm 0.80 0.80 mm 9.10 9.10
Black Black 07 ARMOURING:
i) Material ii) Approx .No/wire diameter iii) Diameter over Armoring (approx)
Galvanizing Round Wire
Galvanizing Round Wire
No/mm 35± 3/0.80 35± 3/0.80 mm 10.70 10.70
08 TAPES BEDDING: i) Material
-
Non Hygroscopic Material
Non Hygroscopic Material
09 OUTER SHEATH: i) Martial ii) Nominal thickness iii) Minimum thickness iv) Colour
-
FRLS-PVC
FRLS-PVC
mm 1.80 1.80 mm 1.24 1.24
- Black Black 10 COMPLETED CABLE:
i) Approx. Overall Diameter ii) Approx Weight iii) Standard Packing Length iv) Drum Type v) Gross Weight ± 5%
mm
14.90
14.90±2.0
Kg/km - 385 - 1000 1000±5% - Wooden Wooden
Kg - 455±5% 11 MAXIMUM CONDUCTOR TEMP °C 90 90 12 EMBOSSING OR PRINTING - Printing & Meter Marking per Meter 13 TEST VOLTAGE kV 3.5 3.5 14 CURRENT RATING:
i) At 30°C in ground ii) At 35°C in air
Amps Amps
30 23
15 SHROT CIRCUIT CURRENT: i) For 1 sec
kA
0.213
Engr. Anamul Kabir Engr. Mohammad Ali Manager Deputy General Manager
P LY CABLE IND.LTD. aluminium & copper cable manufacture
Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd
Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj
Web: www.polycables.com.bd
Customer Power Grid Company of Bangladesh Limited (PGCB) Name of Project Lot-2: Design, Supply, Erection, Testing & Commissioning of
132kV Transmission Lines and substations on Turnkey Basis Contract No. PSEEIP/ADB/PGCB/SS dated 18.09.2014 Contractor ABB India Limited Supplier POLY CABLE INDUSTRIES LIMITED PO No. 3191772893 dated 16.09.2015 Title 7x1.5mm2 (CU/XLPE/SWA/FRLS-PVC) Drawing No. 02
DRUM DIMENSION
WOODEN DRUM d1 d2 d3 L1+BOLT L2
Φ 12 1200 mm 675 mm 75 mm 950 mm 850 mm
Ød3
Ød2
Ød1
L2
L1
FIGURE 02: 7x1.5mm2 (CU/XLPE/SWA/FRLS-PVC)
STEEL WIRE ARMOUR
PVC INNER SHEATH
TAPE BINDER XLPE INSULATION COPPER CONDUCTOR
TAPE BINDER
FRLS-PVC OUTER SHEATH
P LY CABLE IND.LTD. aluminium & copper cable manufacture
Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd
Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj
Web: www.polycables.com.bd
TECHNICAL PARTICULARS FOR
7Cx1.5mm² CU/XLPE/PVC/SWA/FRLS-PVC Specification: IEC 60502 Part–1; Rated Voltage: Uo /U: 600/1000V
Guaranteed Technical Particulars of Control Cable: Plain Annealed Stranded Circular Copper Conductor, XLPE Insulated, Non Hygroscopic Polypropylene Tapes Bedding, PVC Extruded Inner Sheath, Galvanizing Steel Round Wire Armored, Non Hygroscopic Tapes Bedding & Overall FRLS-PVC Sheathed Cables
SL.# Description Unit Standard particulars Guaranteed Technical Particulars
01 CONDUCTOR: i) Number of Core ii) Cross Sectional area iii) No/Diameter of each wire iv) Conductor Diameter
No
7
7
mm² 1.5 1.5 No/mm 7/0.52 7/0.52
mm 1.56 1.56 02 MAXIMUM DC RESISTANCE OF 20º C Ω/km 12.10 12.10 03 INSULATION:
i) Martial ii) Nominal thickness iii) Minimum thickness iv) Insulated core diameter (approx) v) Core Identification
XLPE
XLPE
mm 0.70 0.70 mm 0.53 0.53 mm 3.0 3.0 --- Natural with Core Number Natural with Core Number
04 DIAMETER OF LAID UP CORE mm 9.0 9.0 05 TAPES BEDDING:
i) Material -
Non Hygroscopic Material
Non Hygroscopic Material
06 INNER SHEATH i) Martial ii) Nominal thickness iii) Diameter over inner sheath iv) Colour
PVC
PVC
mm 0.80 0.80 mm 10.8 10.8
Black Black 07 ARMOURING:
i) Material ii) Approx .No/wire diameter iii) Diameter over Armoring (approx)
Galvanizing Round Wire
Galvanizing Round Wire
No/mm 27± 3/1.25 27± 3/1.25 mm 13.3 13.3
08 TAPES BEDDING: i) Material
-
Non Hygroscopic Material
Non Hygroscopic Material
09 OUTER SHEATH: i) Martial ii) Nominal thickness iii) Minimum thickness iv) Colour
-
FRLS-PVC
FRLS-PVC
mm 1.80 1.80 mm 1.24 1.24
- Black Black 10 COMPLETED CABLE:
i) Approx. Overall Diameter ii) Approx Weight iii) Standard Packing Length iv) Drum Type v) Gross Weight ± 5%
mm
17.50
17.50±2.0
Kg/km - 588 - 1000 1000±5% - Wooden Wooden
Kg - 698±5% 11 MAXIMUM CONDUCTOR TEMP °C 90 90 12 EMBOSSING OR PRINTING - Printing & Meter Marking per Meter 13 TEST VOLTAGE kV 3.5 3.5 14 CURRENT RATING:
i) At 30°C in ground ii) At 35°C in air
Amps Amps
18 13
15 SHROT CIRCUIT CURRENT: i) For 1 sec
kA
0.213
Engr. Anamul Kabir Engr. Mohammad Ali Manager Deputy General Manager
P LY CABLE IND.LTD. aluminium & copper cable manufacture
Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd
Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj
Web: www.polycables.com.bd
Customer Power Grid Company of Bangladesh Limited (PGCB) Name of Project Lot-2: Design, Supply, Erection, Testing & Commissioning of
132kV Transmission Lines and substations on Turnkey Basis Contract No. PSEEIP/ADB/PGCB/SS dated 18.09.2014 Contractor ABB India Limited Supplier POLY CABLE INDUSTRIES LIMITED PO No. 3191772893 dated 16.09.2015 Title 14x1.5mm2 (CU/XLPE/STA/FRLS-PVC) Drawing No. 03
DRUM DIMENSION
WOODEN DRUM d1 d2 d3 L1+BOLT L2
Φ 12 1200 mm 675 mm 75 mm 950 mm 850 mm
Ød3
Ød2
Ød1
L2
L1
FIGURE 03: 14x1.5mm2 (CU/XLPE/STA/FRLS-PVC)
STEEL TAPE ARMOUR
PVC INNER SHEATH
TAPE BINDER XLPE INSULATION
COPPER CONDUCTOR
FRLS-PVC OUTER SHEATH
P LY CABLE IND.LTD. aluminium & copper cable manufacture
Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd
Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj
Web: www.polycables.com.bd
TECHNICAL PARTICULARS FOR
14Cx1.5mm² CU/XLPE/PVC/STA/FRLS-PVC Specification: IEC 60502 Part–1; Rated Voltage: Uo /U: 600/1000V
Guaranteed Technical Particulars of Control Cable: Plain Annealed Stranded Circular Copper Conductor, XLPE Insulated, Non Hygroscopic Polypropylene Tapes Bedding, PVC Extruded Inner Sheath, Galvanizing Steel Tape Armored & Overall FRLS-PVC Sheathed Cables
SL.# Description Unit Standard particulars Guaranteed Technical Particulars
01 CONDUCTOR: i) Number of Core ii) Cross Sectional area iii) No/Diameter of each wire iv) Conductor Diameter
No
14
14
mm² 1.5 1.5 No/mm 7/0.52 7/0.52
mm 1.56 1.56 02 MAXIMUM DC RESISTANCE OF 20º C Ω/km 12.10 12.10 03 INSULATION:
i) Martial ii) Nominal thickness iii) Minimum thickness iv) Insulated core diameter (approx) v) Core Identification
XLPE
XLPE
mm 0.70 0.70 mm 0.53 0.53 mm 3.0 3.0 --- Natural with Core Number Natural with Core Number
04 DIAMETER OF LAID UP CORE mm 13.2 13.2 05 TAPES BEDDING:
i) Material -
Non Hygroscopic Material
Non Hygroscopic Material
06 INNER SHEATH i) Martial ii) Nominal thickness iii) Diameter over inner sheath iv) Colour
PVC
PVC
mm 0.80 0.80 mm 15.0 15.0
Black Black 07 ARMOURING:
i) Material ii) Approx .No/Tape Thickness iii) Diameter over Armoring (approx)
Galvanizing Steel Tape
Galvanizing Steel Tape
No/mm 2 / 0.2±0.05 2 / 0.2±0.05 mm 15.6 15.6
08 OUTER SHEATH: i) Martial ii) Nominal thickness iii) Minimum thickness iv) Colour
-
FRLS-PVC
FRLS-PVC
mm 1.80 1.80 mm 1.24 1.24
- Black Black 09 COMPLETED CABLE:
i) Approx. Overall Diameter ii) Approx Weight iii) Standard Packing Length iv) Drum Type v) Gross Weight ± 5%
mm
19.20
19.20±2.0
Kg/km - 568 - 500 500±5% - Wooden Wooden
Kg - 395±5% 10 MAXIMUM CONDUCTOR TEMP °C 90 90 11 EMBOSSING OR PRINTING - Printing & Meter Marking per Meter 12 TEST VOLTAGE kV 3.5 3.5 13 CURRENT RATING:
i) At 30°C in ground ii) At 35°C in air
Amps Amps
12 9
14 SHROT CIRCUIT CURRENT: i) For 1 sec
kA
0.213
Engr. Anamul Kabir Engr. Mohammad Ali Manager Deputy General Manager
P LY CABLE IND.LTD. aluminium & copper cable manufacture
Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd
Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj
Web: www.polycables.com.bd
Customer Power Grid Company of Bangladesh Limited (PGCB) Name of Project Lot-2: Design, Supply, Erection, Testing & Commissioning of
132kV Transmission Lines and substations on Turnkey Basis Contract No. PSEEIP/ADB/PGCB/SS dated 18.09.2014 Contractor ABB India Limited Supplier POLY CABLE INDUSTRIES LIMITED PO No. 3191772893 dated 16.09.2015 Title 19x1.5mm2 (CU/XLPE/STA/FRLS-PVC) Drawing No. 04
DRUM DIMENSION
WOODEN DRUM d1 d2 d3 L1+BOLT L2
Φ 12 1200 mm 675 mm 75 mm 950 mm 850 mm
Ød3
Ød2
Ød1
L2
L1
FIGURE 04: 19x1.5mm2 (CU/XLPE/STA/FRLS-PVC)
STEEL TAPE ARMOUR
PVC INNER SHEATH TAPE BINDER XLPE INSULATION
COPPER CONDUCTOR
FRLS-PVC OUTER SHEATH
P LY CABLE IND.LTD. aluminium & copper cable manufacture
Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd
Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj
Web: www.polycables.com.bd
TECHNICAL PARTICULARS FOR
19Cx1.5mm² CU/XLPE/PVC/STA/FRLS-PVC Specification: IEC 60502 Part–1; Rated Voltage: Uo /U: 600/1000V
Guaranteed Technical Particulars of Control Cable: Plain Annealed Stranded Circular Copper Conductor, XLPE Insulated, Non Hygroscopic Polypropylene Tapes Bedding, PVC Extruded Inner Sheath, Galvanizing Steel Tape Armored & Overall FRLS-PVC Sheathed Cables
SL.# Description Unit Standard particulars Guaranteed Technical Particulars
01 CONDUCTOR: i) Number of Core ii) Cross Sectional area iii) No/Diameter of each wire iv) Conductor Diameter
No
19
19
mm² 1.5 1.5 No/mm 7/0.52 7/0.52
mm 1.56 1.56 02 MAXIMUM DC RESISTANCE OF 20º C Ω/km 12.10 12.10 03 INSULATION:
i) Martial ii) Nominal thickness iii) Minimum thickness iv) Insulated core diameter (approx) v) Core Identification
XLPE
XLPE
mm 0.70 0.70 mm 0.53 0.53 mm 3.0 3.0 --- Natural with Core Number Natural with Core Number
04 DIAMETER OF LAID UP CORE mm 15.0 15.0 05 TAPES BEDDING:
i) Material -
Non Hygroscopic Material
Non Hygroscopic Material
06 INNER SHEATH i) Martial ii) Nominal thickness iii) Diameter over inner sheath iv) Colour
PVC
PVC
mm 0.80 0.80 mm 16.8 16.8
Black Black 07 ARMOURING:
i) Material ii) Approx .No/Tape Thickness iii) Diameter over Armoring (approx)
Galvanizing Steel Tape
Galvanizing Steel Tape
No/mm 2 / 0.2±0.05 2 / 0.2±0.05 mm 17.4 17.4
08 OUTER SHEATH: i) Martial ii) Nominal thickness iii) Minimum thickness iv) Colour
-
FRLS-PVC
FRLS-PVC
mm 1.80 1.80 mm 1.24 1.24
- Black Black 09 COMPLETED CABLE:
i) Approx. Overall Diameter ii) Approx Weight iii) Standard Packing Length iv) Drum Type v) Gross Weight ± 5%
mm
21.00
21.00±2.0
Kg/km - 695 - 500 500±5% - Wooden Wooden
Kg - 458±5% 10 MAXIMUM CONDUCTOR TEMP °C 90 90 11 EMBOSSING OR PRINTING - Printing & Meter Marking per Meter 12 TEST VOLTAGE kV 3.5 3.5 13 CURRENT RATING:
i) At 30°C in ground ii) At 35°C in air
Amps Amps
11 8
14 SHROT CIRCUIT CURRENT: i) For 1 sec
kA
0.213
Engr. Anamul Kabir Engr. Mohammad Ali Manager Deputy General Manager
P LY CABLE IND.LTD. aluminium & copper cable manufacture
Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd
Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj
Web: www.polycables.com.bd
Customer Power Grid Company of Bangladesh Limited (PGCB) Name of Project Lot-2: Design, Supply, Erection, Testing & Commissioning of
132kV Transmission Lines and substations on Turnkey Basis Contract No. PSEEIP/ADB/PGCB/SS dated 18.09.2014 Contractor ABB India Limited Supplier POLY CABLE INDUSTRIES LIMITED PO No. 3191772893 dated 16.09.2015 Title 24x1.5mm2 (CU/XLPE/STA/FRLS-PVC) Drawing No. 05
DRUM DIMENSION
WOODEN DRUM d1 d2 d3 L1+BOLT L2
Φ 12 1200 mm 675 mm 75 mm 950 mm 850 mm
Ød3
Ød2
Ød1
L2
L1
FIGURE 05: 24x1.5mm2 (CU/XLPE/STA/FRLS-PVC)
STEEL TAPE ARMOUR
PVC INNER SHEATH
TAPE BINDER XLPE INSULATION
COPPER CONDUCTOR
FRLS-PVC OUTER SHEATH
P LY CABLE IND.LTD. aluminium & copper cable manufacture
Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd
Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj
Web: www.polycables.com.bd
TECHNICAL PARTICULARS FOR
24Cx1.5mm² CU/XLPE/PVC/STA/FRLS-PVC Specification: IEC 60502 Part–1; Rated Voltage: Uo /U: 600/1000V
Guaranteed Technical Particulars of Control Cable: Plain Annealed Stranded Circular Copper Conductor, XLPE Insulated, Non Hygroscopic Polypropylene Tapes Bedding, PVC Extruded Inner Sheath, Galvanizing Steel Tape Armored & Overall FRLS-PVC Sheathed Cables
SL.# Description Unit Standard particulars Guaranteed Technical Particulars
01 CONDUCTOR: i) Number of Core ii) Cross Sectional area iii) No/Diameter of each wire iv) Conductor Diameter
No
24
24
mm² 1.5 1.5 No/mm 7/0.52 7/0.52
mm 1.56 1.56 02 MAXIMUM DC RESISTANCE OF 20º C Ω/km 12.10 12.10 03 INSULATION:
i) Martial ii) Nominal thickness iii) Minimum thickness iv) Insulated core diameter (approx) v) Core Identification
XLPE
XLPE
mm 0.70 0.70 mm 0.53 0.53 mm 3.0 3.0 --- Natural with Core Number Natural with Core Number
04 DIAMETER OF LAID UP CORE mm 18.0 18.0 05 TAPES BEDDING:
i) Material -
Non Hygroscopic Material
Non Hygroscopic Material
06 INNER SHEATH i) Martial ii) Nominal thickness iii) Diameter over inner sheath iv) Colour
PVC
PVC
mm 0.80 0.80 mm 19.8 19.8
Black Black 07 ARMOURING:
i) Material ii) Approx .No/Tape Thickness iii) Diameter over Armoring (approx)
Galvanizing Steel Tape
Galvanizing Steel Tape
No/mm 2 / 0.2±0.05 2 / 0.2±0.05 mm 20.4 20.4
08 OUTER SHEATH: i) Martial ii) Nominal thickness iii) Minimum thickness iv) Colour
-
FRLS-PVC
FRLS-PVC
mm 1.80 1.80 mm 1.24 1.24
- Black Black 09 COMPLETED CABLE:
i) Approx. Overall Diameter ii) Approx Weight iii) Standard Packing Length iv) Drum Type v) Gross Weight ± 5%
mm
24.00
24.00±2.0
Kg/km - 848 - 500 500±5% - Wooden Wooden
Kg - 535±5% 10 MAXIMUM CONDUCTOR TEMP °C 90 90 11 EMBOSSING OR PRINTING - Printing & Meter Marking per Meter 12 TEST VOLTAGE kV 3.5 3.5 13 CURRENT RATING:
i) At 30°C in ground ii) At 35°C in air
Amps Amps
10 8
14 SHROT CIRCUIT CURRENT: i) For 1 sec
kA
0.213
Engr. Anamul Kabir Engr. Mohammad Ali Manager Deputy General Manager
P LY CABLE IND.LTD. aluminium & copper cable manufacture
Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd
Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj
Web: www.polycables.com.bd
Customer Power Grid Company of Bangladesh Limited (PGCB) Name of Project Lot-2: Design, Supply, Erection, Testing & Commissioning of
132kV Transmission Lines and substations on Turnkey Basis Contract No. PSEEIP/ADB/PGCB/SS dated 18.09.2014 Contractor ABB India Limited Supplier POLY CABLE INDUSTRIES LIMITED PO No. 3191772893 dated 16.09.2015 Title 2x6mm2 (CU/XLPE/SWA/FRLS-PVC) Drawing No. 06
DRUM DIMENSION
WOODEN DRUM d1 d2 d3 L1+BOLT L2
Φ 10 1000 mm 500 mm 75 mm 690 mm 600 mm
Ød3
Ød2
Ød1
L2
L1
FIGURE 06: 2x6.0mm2 (CU/XLPE/SWA/FRLS-PVC)
STEEL WIRE ARMOUR
PVC INNER COVERING XLPE INSULATION
COPPER CONDUCTOR
TAPE BINDER
FRLS-PVC OUTER SHEATH
P LY CABLE IND.LTD. aluminium & copper cable manufacture
Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd
Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj
Web: www.polycables.com.bd
TECHNICAL PARTICULARS FOR 2Cx6mm² CU/XLPE/PVC/SWA/FRLS-PVC
Specification: IEC 60502 Part–1; Rated Voltage: Uo /U: 600/1000V Guaranteed Technical Particulars of Control Cable: Plain Annealed Stranded Circular Copper Conductor, XLPE Insulated, , PVC Extruded Inner Sheath, Galvanizing Steel Round Wire Armored, Non Hygroscopic Tapes Bedding & Overall FRLS-PVC Sheathed Cables
SL.# Description Unit Standard particulars Guaranteed Technical Particulars
01 CONDUCTOR: i) Number of Core ii) Cross Sectional area iii) No/Diameter of each wire iv) Conductor Diameter
No
2
2
mm² 6 6 No/mm 7/1.05 7/1.05
mm 3.15 3.15 02 MAXIMUM DC RESISTANCE OF 20º C Ω/km 3.08 3.08 03 INSULATION:
i) Martial ii) Nominal thickness iii) Minimum thickness iv) Insulated core diameter (approx) v) Core Identification
XLPE
XLPE
mm 0.70 0.70 mm 0.53 0.53 mm 4.6 4.6 --- Red, Natural Red, Natural
04 DIAMETER OF LAID UP CORE mm 9.20 9.20 05 INNER SHEATH
i) Martial ii) Nominal thickness iii) Diameter over inner sheath iv) Colour
PVC
PVC
mm 0.80 0.80 mm 10.8 10.8
Black Black 06 ARMOURING:
i) Material ii) Approx .No/wire diameter iii) Diameter over Armoring (approx)
Galvanizing Round Wire
Galvanizing Round Wire
No/mm 27± 3/1.25 27± 3/1.25 mm 13.3 13.3
07 TAPES BEDDING: i) Material
-
Non Hygroscopic Material
Non Hygroscopic Material
08 OUTER SHEATH: i) Martial ii) Nominal thickness iii) Minimum thickness iv) Colour
-
FRLS-PVC
FRLS-PVC
mm 1.80 1.80 mm 1.24 1.24
- Black Black 09 COMPLETED CABLE:
i) Approx. Overall Diameter ii) Approx Weight iii) Standard Packing Length iv) Drum Type v) Gross Weight ± 5%
mm
17.50
17.50±2.0
Kg/km - 630 - 1000 1000±5% - Wooden Wooden
Kg - 700±5% 10 MAXIMUM CONDUCTOR TEMP °C 90 90 11 EMBOSSING OR PRINTING - Printing & Meter Marking per Meter 12 TEST VOLTAGE kV 3.5 3.5 13 CURRENT RATING:
i) At 30°C in ground ii) At 35°C in air
Amps Amps
74 62
14 SHROT CIRCUIT CURRENT: i) For 1 sec
kA
0.852
Engr. Anamul Kabir Engr. Mohammad Ali Manager Deputy General Manager
P LY CABLE IND.LTD. aluminium & copper cable manufacture
Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd
Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj
Web: www.polycables.com.bd
Customer Power Grid Company of Bangladesh Limited (PGCB) Name of Project Lot-2: Design, Supply, Erection, Testing & Commissioning of
132kV Transmission Lines and substations on Turnkey Basis Contract No. PSEEIP/ADB/PGCB/SS dated 18.09.2014 Contractor ABB India Limited Supplier POLY CABLE INDUSTRIES LIMITED PO No. 3191772893 dated 16.09.2015 Title 4x16mm2 (CU/XLPE/STA/FRLS-PVC) Drawing No. 07
DRUM DIMENSION
WOODEN DRUM d1 d2 d3 L1+BOLT L2
Φ 12 1200 mm 675 mm 75 mm 950 mm 850 mm
Ød3
Ød2
Ød1
L2
L1
FIGURE 07: 4x16mm2 (CU/XLPE/STA/FRLS-PVC)
STEEL TAPE ARMOUR
PVC INNER SHEATH TAPE BINDER XLPE INSULATION
COPPER CONDUCTOR
FRLS-PVC OUTER SHEATH
P LY CABLE IND.LTD. aluminium & copper cable manufacture
Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd
Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj
Web: www.polycables.com.bd
TECHNICAL PARTICULARS FOR
4Cx16mm² CU/XLPE/PVC/STA/FRLS-PVC Specification: IEC 60502 Part–1; Rated Voltage: Uo /U: 600/1000V
Guaranteed Technical Particulars of Power Cable: Plain Annealed Stranded Circular Copper Conductor, XLPE Insulated, Non Hygroscopic Polypropylene Filler & Tapes Bedding, PVC Extruded Inner Sheath, Galvanizing Steel Tape Armored & Overall FRLS-PVC Sheathed Cables
SL.# Description Unit Standard particulars Guaranteed Technical Particulars
01 CONDUCTOR: i) Number of Core ii) Cross Sectional area iii) No/Diameter of each wire iv) Conductor Diameter
No
4
4
mm² 16 16 No/mm 7/1.71 7/1.71
mm 5.13 5.13 02 MAXIMUM DC RESISTANCE OF 20º C Ω/km 1.15 1.15 03 INSULATION:
i) Martial ii) Nominal thickness iii) Minimum thickness iv) Insulated core diameter (approx) v) Core Identification
XLPE
XLPE
mm 0.70 0.70 mm 0.53 0.53 mm 6.6 6.6 --- Red, Yellow, Blue, Natural Red, Yellow, Blue, Natural
04 DIAMETER OF LAID UP CORE mm 15.95 15.95 05 TAPES BEDDING:
i) Material -
Non Hygroscopic Material
Non Hygroscopic Material
06 INNER SHEATH i) Martial ii) Nominal thickness iii) Diameter over inner sheath iv) Colour
PVC
PVC
mm 0.80 0.80 mm 17.75 17.75
Black Black 07 ARMOURING:
i) Material ii) Approx .No/Tape Thickness iii) Diameter over Armoring (approx)
Galvanizing Steel Tape
Galvanizing Steel Tape
No/mm 2 / 0.2±0.05 2 / 0.2±0.05 mm 18.35 18.35
08 OUTER SHEATH: i) Martial ii) Nominal thickness iii) Minimum thickness iv) Colour
-
FRLS-PVC
FRLS-PVC
mm 1.80 1.80 mm 1.24 1.24
- Black Black 09 COMPLETED CABLE:
i) Approx. Overall Diameter ii) Approx Weight iii) Standard Packing Length iv) Drum Type v) Gross Weight ± 5%
mm
22.00
22.00±2.0
Kg/km - 1030 - 500 500±5% - Wooden Wooden
Kg - 625±5% 10 MAXIMUM CONDUCTOR TEMP °C 90 90 11 EMBOSSING OR PRINTING - Printing & Meter Marking per Meter 12 TEST VOLTAGE kV 3.5 3.5 13 CURRENT RATING:
i) At 30°C in ground ii) At 35°C in air
Amps Amps
110 98
14 SHROT CIRCUIT CURRENT: i) For 1 sec
kA
2.272
Engr. Anamul Kabir Engr. Mohammad Ali Manager Deputy General Manager
P LY CABLE IND.LTD. aluminium & copper cable manufacture
Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd
Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj
Web: www.polycables.com.bd
Customer Power Grid Company of Bangladesh Limited (PGCB) Name of Project Lot-2: Design, Supply, Erection, Testing & Commissioning of
132kV Transmission Lines and substations on Turnkey Basis Contract No. PSEEIP/ADB/PGCB/SS dated 18.09.2014 Contractor ABB India Limited Supplier POLY CABLE INDUSTRIES LIMITED PO No. 3191772893 dated 16.09.2015 Title 4x120mm2 (CU/XLPE/STA/FRLS-PVC) Drawing No. 08
DRUM DIMENSION
WOODEN DRUM d1 d2 d3 L1+BOLT L2
Φ 22 2200 mm 1400 mm 110 mm 1390 mm 1250 mm
Ød3
Ød2
Ød1
L2
L1
FIGURE 08: 4x120mm2 (CU/XLPE/STA/FRLS-PVC)
STEEL TAPE ARMOUR
PVC INNER COVERING
TAPE BINDER XLPE INSULATION
COPPER CONDUCTOR
FRLS-PVC OUTER SHEATH
P LY CABLE IND.LTD. aluminium & copper cable manufacture
Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd
Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj
Web: www.polycables.com.bd
TECHNICAL PARTICULARS FOR
4Cx120mm² CU/XLPE/PVC/STA/FRLS-PVC Specification: IEC 60502 Part–1; Rated Voltage: Uo /U: 600/1000V
Guaranteed Technical Particulars of Power Cable: Plain Annealed Stranded Sector Shaped Copper Conductor, XLPE Insulated, Non Hygroscopic Polypropylene Filler & Tapes Bedding, PVC Extruded Inner Sheath, Galvanizing Steel Tape Armored & Overall FRLS-PVC Sheathed Cables
SL.# Description Unit Standard particulars Guaranteed Technical Particulars
01 CONDUCTOR: i) Number of Core ii) Cross Sectional area iii) No/Diameter of each wire iv) Conductor Diameter
No
4
4
mm² 120 120 No/mm 39/2.03 39/2.03
mm 12.38 12.38 02 MAXIMUM DC RESISTANCE OF 20º C Ω/km 0.153 0.153 03 INSULATION:
i) Martial ii) Nominal thickness iii) Minimum thickness iv) Insulated core diameter (approx) v) Core Identification
XLPE
XLPE
mm 1.20 1.20 mm 0.98 0.98 mm 14.80 14.80 --- Red, Yellow, Blue, Natural Red, Yellow, Blue, Natural
04 DIAMETER OF LAID UP CORE mm 35.80 35.80 05 TAPES BEDDING:
i) Material -
Non Hygroscopic Material
Non Hygroscopic Material
06 INNER SHEATH i) Martial ii) Nominal thickness iii) Diameter over inner sheath iv) Colour
PVC
PVC
mm 1.40 1.40 mm 39.40 39.40
Black Black 07 ARMOURING:
i) Material ii) Approx .No/Tape Thickness iii) Diameter over Armoring (approx)
Galvanizing Steel Tape
Galvanizing Steel Tape
No/mm 2 / 0.3±0.05 2 / 0.3±0.05 mm 40.10 40.10
08 OUTER SHEATH: i) Martial ii) Nominal thickness iii) Minimum thickness iv) Colour
-
FRLS-PVC
FRLS-PVC
mm 2.40 2.40 mm 1.72 1.72
- Black Black 09 COMPLETED CABLE:
i) Approx. Overall Diameter ii) Approx Weight iii) Standard Packing Length iv) Drum Type v) Gross Weight ± 5%
mm
44.90
44.90±2.5
Kg/km - 5885 - 500 500±5% - Wooden Wooden
Kg - 3420±5% 10 MAXIMUM CONDUCTOR TEMP °C 90 90 11 EMBOSSING OR PRINTING - Printing & Meter Marking per Meter 12 TEST VOLTAGE kV 3.5 3.5 13 CURRENT RATING:
i) At 30°C in ground ii) At 35°C in air
Amps Amps
295 305
14 SHROT CIRCUIT CURRENT: i) For 1 sec
kA
17.04
Engr. Anamul Kabir Engr. Mohammad Ali Manager Deputy General Manager
P LY CABLE IND.LTD. aluminium & copper cable manufacture
Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd
Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj
Web: www.polycables.com.bd
Customer Power Grid Company of Bangladesh Limited (PGCB) Name of Project Lot-2: Design, Supply, Erection, Testing & Commissioning of
132kV Transmission Lines and substations on Turnkey Basis Contract No. PSEEIP/ADB/PGCB/SS dated 18.09.2014 Contractor ABB India Limited Supplier POLY CABLE INDUSTRIES LIMITED PO No. 3191772893 dated 16.09.2015 Title 4x4mm2 (CU/XLPE/SWA/FRLS-PVC) Drawing No. 09
DRUM DIMENSION
WOODEN DRUM d1 d2 d3 L1+BOLT L2
Φ 12 1200 mm 675 mm 75 mm 950 mm 850 mm
Ød3
Ød2
Ød1
L2
L1
FIGURE 09: 4x4mm2 (CU/XLPE/SWA/FRLS-PVC)
STEEL WIRE ARMOUR
PVC INNER SHEATH
TAPE BINDER XLPE INSULATION
COPPER CONDUCTOR
TAPE BINDER
FRLS-PVC OUTER SHEATH
P LY CABLE IND.LTD. aluminium & copper cable manufacture
Sena Kalyan Bhaban, Floor # 9, Suite # 902 195, Motijheel C/A, Dhaka-1000, Bangladesh Tel: (+8802) 712 1493, 712 0862,712 1956, Fax: (8802) 955 6431 Email: [email protected], Web : www.polycables.com.bd
Registered Office : 16/1 Bonogram, Lane Wari, Dhaka-1203, Bangladesh Factory : Bhitikandi, Bhober Char, Gozaria, Munshigonj
Web: www.polycables.com.bd
TECHNICAL PARTICULARS FOR 4Cx4mm² CU/XLPE/PVC/SWA/FRLS-PVC
Specification: IEC 60502 Part–1; Rated Voltage: Uo /U: 600/1000V Guaranteed Technical Particulars of Control Cable: Plain Annealed Stranded Circular Copper Conductor, XLPE Insulated, Non Hygroscopic Polypropylene Filler & Tapes Bedding, PVC Extruded Inner Sheath, Galvanizing Steel Round Wire Armored, Non Hygroscopic Tapes Bedding & Overall FRLS-PVC Sheathed Cables
SL.# Description Unit Standard particulars Guaranteed Technical Particulars
01 CONDUCTOR: i) Number of Core ii) Cross Sectional area iii) No/Diameter of each wire iv) Conductor Diameter
No
4
4
mm² 4 4 No/mm 7/0.85 7/0.85
mm 2.55 2.55 02 MAXIMUM DC RESISTANCE OF 20º C Ω/km 4.61 4.61 03 INSULATION:
i) Martial ii) Nominal thickness iii) Minimum thickness iv) Insulated core diameter (approx) v) Core Identification
XLPE
XLPE
mm 0.70 0.70 mm 0.53 0.53 mm 4.0 4.0 --- Red, Yellow, Blue, Natural Red, Yellow, Blue, Natural
04 DIAMETER OF LAID UP CORE mm 9.70 9.70 05 TAPES BEDDING:
i) Material -
Non Hygroscopic Material
Non Hygroscopic Material
06 INNER SHEATH i) Martial ii) Nominal thickness iii) Diameter over inner sheath iv) Colour
PVC
PVC
mm 0.80 0.80 mm 11.50 11.50
Black Black 07 ARMOURING:
i) Material ii) Approx .No/wire diameter iii) Diameter over Armoring (approx)
Galvanizing Round Wire
Galvanizing Round Wire
No/mm 29± 3/1.25 29± 3/1.25 mm 14.0 14.0
08 TAPES BEDDING: i) Material
-
Non Hygroscopic Material
Non Hygroscopic Material
09 OUTER SHEATH: i) Martial ii) Nominal thickness iii) Minimum thickness iv) Colour
-
FRLS-PVC
FRLS-PVC
mm 1.80 1.80 mm 1.24 1.24
- Black Black 10 COMPLETED CABLE:
i) Approx. Overall Diameter ii) Approx Weight iii) Standard Packing Length iv) Drum Type v) Gross Weight ± 5%
mm
18.20
18.20±2.0
Kg/km - 675 - 1000 1000±5% - Wooden Wooden
Kg - 785±5% 11 MAXIMUM CONDUCTOR TEMP °C 90 90 12 EMBOSSING OR PRINTING - Printing & Meter Marking per Meter 13 TEST VOLTAGE kV 3.5 3.5 14 CURRENT RATING:
i) At 30°C in ground ii) At 35°C in air
Amps Amps
48 41
15 SHROT CIRCUIT CURRENT: i) For 1 sec
kA
0.568
Engr. Anamul Kabir Engr. Mohammad Ali Manager Deputy General Manager