GRX-IRPS-WH InfraredTransmitter/Receiver Pair(Class 2 Device)
Specifications• Operating voltage: Low-voltage Class 2 (PELV) 12
V~ from GRX-12VDC plug-in power supply(ordered separately). One GRX-12VDC can supplypower to five sensor transmitter/receiver pairs.
• Transmitter and receiver have reverse polarity andshort-circuit protection.
• Receiver includes an LED indicator that assists insensor alignment during installation and sensoroperating status.
• Each GRX-AV or OMX-AV interface (ordered sep-arately) can accommodate up to fivetransmitter/receiver pairs for five different move-able walls.
• 32-104°F (0 - 40°C). Relative humidity less than90% non-condensing.
• Surface mount indoors only.
Installation InstructionsPlease Read
DescriptionInfrared transmitter/receiver pair automatically coor-dinates lighting preset functions in areas with parti-tions (example: partitioned meeting rooms and ball-rooms). Sensors may be used with any GRAFIKEye 3000 or 4000 systems as well as GRAFIK EyeCentralized Lighting Control Systems.• Automatically combines lighting preset functions
when partition is open creating one large space.• Lighting preset functions become independent as
partition is closed creating several smallerspaces.
Sensors require additional Lutron interface (GRX-AVor OMX-AV) and power supply (GRX-12VDC) forproper operation.
Important Notes1. Read all instructions carefully before starting
installation.2. This device must be installed by a qualified
electrician.3. Install in accordance with the National Electric
Code® and all applicable local regulations.4. Turn power OFF at the control panel before
installing the device. Do not connect high-volt-age power to low voltage terminals. Improperwiring can result in personal injury or damage tothe device or to other equipment.
GRX-IRPS-WH
®
Side View
Standard single-gang U.S. wallbox mountedfacedown and flush with ceiling surface (typicalof two).
8 ft. (243 mm) maximum)
1.5 in. (38.1 mm)
GRX-IRPS-WHReceiver
GRX-IRPS-WHTransmitter
Partition
Ceiling
Dimensions and MountingReceiver and transmitter surface mount in 1-gang U.S. wallboxes 3.5 in. (89 mm) deep mounted face-down from the ceiling. Indoors only.• The sensors must be mounted in a position where the partition separates the transmitter and receiver
when the partition is closed.• Transmitter and receiver may be located no more than 8 ft. (2430 mm) apart.• Adjustable mounting brackets allow easy alignment during installation.• Wires feed through the back of the transmitter/receiver.
LUTRON LUTRON
1 2 3 4 5 6 7 8
MUX LINK INPUTS OUTPUTS
CO
M +V
MU
X
PR
OG
RA
MS
WIT
CH
CO
M
CO
M
C 1 2 3 4 5 1 2 3 4 5 C1 2 3 4
MU
X
MUX LINK INPUTS OUTPUTSC 1 2 3 4 5 1 2 3 4 5 C1 2 3 4
0 = ON; 1 = OFF
1 2 3 4
0 0 0 00 0 0 10 0 1 00 0 1 1
1 2 3 4
1 1 0 01 1 0 11 1 1 01 1 1 1
1 2 3 4
1 0 0 01 0 0 11 0 1 01 0 1 1
1 2 3 4
0 1 0 00 1 0 10 1 1 00 1 1 1
ADDRESS
1234
ADDRESS
13141516
ADDRESS
9101112
ADDRESS
5678
DIP SWITCH SETTINGS (1-4)
DIP SWITCH SETTINGS (5-8)
TYPE DIP SETTINGCONFIGURATION
ADDRESS
CONFIG.
TYPE
1 2 3 4 5 6 7 8
ON
OFF
GRX-AVINTERFACE CONTROL
SELV(CLASS 2:USA)COOPERSBURG, PA 18036
4S CONTROL SCENES 1-4, MAINTAIN OUTPUTS 5 ON 6 ONSCENES 5-8, MAINTAIN OUTPUTS 5 OFF 6 ON
7 ON 8 ON SCENES 9-12, MAINTAIN OUTPUTS 5 ON 6 OFFSCENES 13-16, MAINTAIN OUTPUTS 5 OFF 6 OFF
4S CONTROL SCENES 1-4, MOMENTARY OUTPUTS 5 ON 6 ONSCENES 5-8, MOMENTARY OUTPUTS 5 OFF 6 ON
7 ON 8 OFF SCENES 9-12, MOMENTARY OUTPUTS 5 ON 6 OFFSCENES 13-16, MOMENTARY OUTPUTS 5 OFF 6 OFF
4Q CONTROL SEQUENCE 1-4, MAINTAIN INPUTS 5 OFF 6 ONSEQUENCE 1-4, MOMENTARY INPUTS 5 ON 6 ON
7 OFF 8 OFF SEQUENCE 5-16, MAINTAIN INPUTS 6 OFF 6 OFFSEQUENCE 5-16, MOMENTARY INPUTS 6 ON 6 OFF
4PS CONTROL PARTITION STATUS, MOMENTARY INPUTS 5 ON 6 ON7 OFF 8 ON PARTITION STATUS, MAINTAINED INPUTS 5 OFF 6 ON
SPECIAL OCCUPANCY SENSOR - SCENE 1 & OFF 5 ON 6 OFFCONTROL OCCUPANCY SENSOR - OFF ONLY 5 OFF 6 OFF7 OFF 8 ON
SELV (CLASS 2:USA)
R
R
System Diagram
GRX-IRPS ReceiverGRX-IRPS Transmitter
Room A Room B
Partition
GRX-12VDC
Wallstations Wallstations
GRX/OMX-AV
Class 2/PELV Control Link
Ceiling
2 GRX-IRPS-WH Infrared Transmitter/Receiver Pair
Top View
Single gang wallbox(typical of two)
Wallbox mountingline of center
WiringWARNING: Always turn off the power to the control panel before doing any work. Failure to do so
can result in serious personal injury and damage to equipment.
1. Turn power OFF.2. Strip insulation from wires so 3/8" (10 mm) bare wire is exposed.3. Gently squeeze the sides of the GRX-IRPS cover and remove to expose the sensor mounting bracket.
Unsnap the plastic faceplate.4. Connect wiring as shown in the Wiring Diagram (next page). Confirm all connections.5. Attach the device to the ceiling-mounted wallbox - Do not fully tighten the screws6. Plug in the GRX-12VDC to apply power to the transmitter and receiver. Note: Do not restore power to
the control panel until after the installation of the system is complete.7. Verify that the Transmitter and Receiver are properly aligned (the movable partition must be OPEN to
allow the beam to travel from the Transmitter to the Receiver). A Green LED should be lit on theTransmitter to indicate that it is properly powered and transmitting. Adjust the horizontal and verticalalignment of the units until they are aligned.Receiver LED(s) lit:— Amber. Indicates that a strong signal is being received.— Amber and Red. Receiver is partially misaligned, improper functionality may occur.— Red. Receiver is misaligned, improper functionality will occur.— No LED. Receiver is completely misaligned and no signal is being received.
8. Close and re-open the movable partition to verify that the LEDs on the receiver turn OFF when thepartition is closed and ON when the partition is re-opened.
9. Tighten all screws and verify that the Amber LED on the receiver is still on.10. Snap the faceplate onto the unit.11. Snap the cover over the sensor.12. Restore power to the control panel.
GRX-IRPS-WH Infrared Transmitter/Receiver Pair 3
Internet: www.lutron.comE-mail: [email protected]
WORLD HEADQUARTERSLutron Electronics Co. Inc.,TOLL FREE: 1.800.523.9466(U.S.A., Canada, portions ofCaribbean)Tel: 1.610.282.3800Fax: 1.610.282.3090
GREAT BRITAINLutron EA Ltd.,Tel: +44.207.702.0657Fax: +44.207.480.6899
GERMANYLutron Electronics GmbHTel: +49.309.710.4590Fax: +49.309.710.4591
JAPAN SALES OFFICELutron Asuka CorporationTel: +813.5405.7333Fax: +813.5405.7496
HONG KONG SALES OFFICELutron GL (Hong Kong)Tel: +852.2104.7733Fax: +852.2104.7633
SINGAPORELutron GL (Singapore)Tel: +65.220.4666Fax: +65.220.4333
LIMITED WARRANTYLutron will, at its option, repair or replace any unit that is defective in mate-rials or manufacture within one year after purchase. For warranty service,return unit to place of purchase or mail to Lutron at 7200 Suter Rd.,Coopersburg, PA 18036-1299, postage pre-paid.This warranty is in lieu of all other express warranties, and the implied war-ranty of merchantability is limited to one year from purchase. This warrantydoes not cover the cost of installation, removal, or reinstallation, or damageresulting from misuse, abuse, or improper or incorrect repair, or damagefrom improper wiring or installation. This warranty does not cover incidentalor consequential damages. Lutron’s liability on any claim for damages aris-ing out of or in connection with the manufacture, sale, installation, delivery,or use of the unit shall never exceed the purchase price of the unit.This warranty gives you specific legal rights, and you may also have otherrights which vary from state to state. Some states do not allow limitations onhow long an implied warranty lasts, so the above limitation may not apply toyou. Some states do not allow the exclusion or limitation of incidental orconsequential damages, so the above limitation or exclusion may not applyto you.This product may be covered under one or more of the following U.S.patents: 4,803,380; 4,835,343; 4,924,349 and corresponding foreignpatents.Lutron and Nova T and design are registered trademarks of Lutron Electron-ics Co., Inc.National Electric Code is a registered trademark of the National FireProtection Association, Inc., Quincy, Massachusetts.© 2005 Lutron Electronics Co., Inc.
Lutron Electronics Co., Inc.Made and printed in U.S.A.P/N 040-XXX 4/05
3OUTPUTS
C 5421 3INPUTS
21 4 5 C
GRX-AV* or OMX-AV(ordered separately)
Twist-onConnector
Black Wire withWhite Trace (+)
Solid Black Wire (-)
6 ft. (1829 mm)Cable
GRX-12VDC12V Power Supply(ordered separately)
RECEIVER
SINGLE-GANGBACKBOX
BLU
E
BR
OW
N
BLA
CK
BLU
E
BR
OW
N
TRANSMITTER
* GRX-AV is programmed for partition mode. Set input closuresfor maintained inputs (refer to GRX-AV installation instructions).
Note: Drawing represents a single partition. GRX-AV/OMX-AV will accomodate up to five sets of sensors (five parti-tions). A single GRX-12VDC will power up to five GRX-IRPS sensors.
SINGLE-GANGBACKBOX
Wiring Diagram