GRUNDFOS DATA BOOKLET
Grundfos Direct Sensors™Vortex flow sensors
Ta
ble
of c
on
ten
ts
2
Grundfos Direct Sensors™
1. Vortex flow sensors 3Introduction 3
2. Vortex flow sensor, industry (VFI) 4VFI general data 4VFI 0.3-6 DN 18, technical data 6VFI 0.6-12 DN 25, technical data 7VFI 1.3-25 DN 32, technical data 8VFI 2-40 DN 40, technical data 9VFI 3.2-64 DN 50, technical data 10VFI 5.2-104 DN 65, technical data 11VFI 8-160 DN 80, technical data 12VFI 12-240 DN 100, technical data 13
3. Vortex flow sensor, standard 14VFS general data 14VFS 1-20, technical data 16VFS 2-40, technical data 17VFS 5-100, technical data 18VFS 10-200, technical data 19VFS 20-400, technical data 20VFS 1-12 QT, technical data 21VFS 1-15 QT, technical data 22VFS 2-40 QT, technical data 23VFS 5-100 QT, technical data 24VFS 10-200 QT, technical data 25
4. Product range 26VFI sensor 26VFS sensor 27Sensor selection 27
5. Accessories 28Sensor interface, type SI 001 PSU 28Sensor interface, type SI 010 CNV 28
6. Appendix 29Installation of VFI sensor 29Minimum flow rate 30Pressure drop curves 31
7. Further product documentation 32WebCAPS 32WinCAPS 33
Vo
rte
x f
low
se
ns
ors
Grundfos Direct Sensors™ 1
1. Vortex flow sensors
IntroductionThis data booklet comprises an overview of the
Grundfos vortex flow sensor range and related products.
Fig. 1 Grundfos vortex flow sensors
The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos group.
The Grundfos vortex flow sensor is an integrated flow and temperature measurement system designed and validated for harsh aqueous environments. The flow measurement is based on the vortex principle. The system elements include a flow pipe with an integrated bluff body and a differential pressure detector.
Fig. 1 Bluff body inside a vortex flow sensor
When a bluff body is placed in a flow inside a pipe, a series of vortices will be generated periodically on each side of the bluff body. These vortices propagate down stream giving rise to periodic pressure variations, which can be detected by the differential pressure detector. The frequency of the pressure variations is proportional to the volume flow through the pipe.
Fig. 2 Operating principle
The bluff body is designed to optimise the pulse strength of the pressure variations at the position of the differential pressure detector. The bluff body is an integrated part of the injection moulded flow pipe, or supplied as a composite insert solution.
Flow ranges are determined by the pipe diameter and the signal processing parameters. The differential pressure detector key elements are a bulk micromachined silicon chip and a microprocessor-based signal-conditioning circuit, both on the same PCB. The conditioning circuit converts the pressure reading to a signal proportional to the flow through the pipe.
The electronics are protected by an IP44 composite housing.
The chip has a square membrane, which deflects due to pressure. Strain gauges are incorporated in a Wheatstone bridge configuration on stress intensive positions on the membrane. The pressure and temperature sensitive area (the membrane region) is coated on both sides by an extremely corrosion and diffusion resistive thin film (Silicoat®). The coating provides direct environmental robustness of the chip. The separation of the media and media-free zones is provided by O-ring sealing.
TM
04
73
62
16
10
, T
M0
5 4
73
9 2
41
2 &
TM
05
47
46
24
12
TM
04
92
36
37
10
TM
04
71
55
16
10
PipeBluff body
Flow direction
3
Vo
rtex
flow
se
ns
or, in
du
stry
(VF
I)
4
Grundfos Direct Sensors™2
2. Vortex flow sensor, industry (VFI)
VFI general data
Vortex flow sensor, industry
Fig. 3 VFI sensor
Technical overview The VFI is the industrial version of the Grundfos vortex flowmeter range. The VFI is based on the principle of vortex shedding behind a bluff body. The VFI has no moving parts and is built into a stainless steel pipe. The rugged design allows the VFI to be used in a wide range of applications as a cost-effective and accurate flow sensor.The flow sensors are supplied with flanges or with threaded ends for use with union nuts.
Fig. 4 Bluff body in a VFI sensor
Applications• Water treatment and distribution
• light chemical industry
• water management
• pool and water resorts
• heating
• air-conditioning
• cooling towers
• condensing units
• solar collectors.
Features• Flow range from 0.3 to 240 m3/h
• based on the vortex principle
• compact and well-proven design
• approved for drinking water
• wide temperature range.
Benefits• No moving parts
• compatible with wet, aggressive media
• cost-effective and robust design
• system solution with Grundfos pumps.
Approvals• WRAS
• KTW
• ACS
• NSF 61.
Markings
Electrical connections
Fig. 5 Electrical connections
Power supply: 12.5 - 30 V (screened cable)
Type: Loop-powered, 2-wire
TM
04
73
62
22
10
TM
04
92
28
37
10
CE c, CSA, us C-Tick
TM
04
71
56
16
10
PIN 1 2 3 4
Wire colour Brown White Blue Black
Output 4-20 mA
+ -
���
1
3
4
2
Vo
rte
x f
low
se
ns
or,
in
du
str
y (
VF
I)
Grundfos Direct Sensors™ 2
Type key
Type designation VFI -··0.3-6 m -1 -C -M 5.000 X -FG6 -SG -30 F -A··1
Product group:VFI: Vortex flow sensor, industry
Range:0.3-6
Unit:m: m3/h
Generation:1: 1st generation
Electrical output type:C: 4-20 mA, 2-wire
Sensor connector or cable type and cable connector in sensor end:M: M12x1, female straight, screened 4-wire cable
Cable length5.000= 5 m
Cable connector opposite sensor:X: Open-ended
Sealing material and class:First letter:E: EPDM (drinking-water approved)F: FKM (for use in oily media)Second letter:G: Gel-filledThird letter:6: IP67
Material:B: BrassC: CompositeG: Cast ironQ: Stainless steel flow pipe with composite insert (QT)S: Stainless steel
Dimension of mechanical connection:30: DIN PN25/40 DN18/25/32, ANSI B16.5 Class 300 - 1¼"
Mechanical connection type:F: Flange
Packaging:A: Set with pre-assembled components1: 1 piece
5
Vo
rtex
flow
se
ns
or, in
du
stry
(VF
I)
6
Grundfos Direct Sensors™2
VFI 0.3-6 DN 18, technical data
Vortex flow sensor, industry, 0.3 - 6 m³/h
Fig. 6 VFI 0.3-6 sensor
Dimensions
Fig. 7 Dimensions VFI sensor with flanges
Flanges are compatible with DN 25/32 flanges sizes.
Fig. 8 Dimensions VFI sensor with thread
The VFI sensor with threaded ends must be mounted with union nuts.
Specifications
*Reference condition:
- Liquids at 20 °C, 1013 mbar, ρ = 998 kg/m3, v = 1 x 10-6 m2/s
Sensor output signals
Fig. 9 Flow response
TM
04
71
42
17
10
/ T
M0
4 4
25
0 1
71
0T
M0
4 7
15
4 1
61
0
Flange material
FlangeA
[mm]B
[mm]C
[mm]D
[mm]Weight
[kg]
Cast iron DN 25/32 (PN 40)
200 18 120 1404.38
Stainless steel 4.44
TM
04
71
53
16
10
MaterialThread
sizeA
[mm]B
[mm]C
[mm]Weight
[kg]
Stainless steel G1 1/4" 200 18 120 1.39
Flow
Measuring range 0.3 - 6 m³/h*
Accuracy (±1σ), 0 - 100 °C
± 1.5 % FS*
Response time < 1 s
Resolution 0.0075 m³/h
Media and environment
Liquid types See appendix Minimum flow rate
Liquid max. pressure 28 barLiquid temperature (operation) -30 - 120 °C, non-freezing
Liquid temperature -30 - 120 °C, non-freezing
Ambient air temperature (operation)
–25 - 60 °C
Ambient air temperature –55 - 70 °C
Storage temperature –55 - 70 °C
Humidity 0 - 95 % RH, non-condensing
System burst pressure 60 bar
Electrical data
Power supply 12.5 - 30 VDC (± 5 %)
Output signals - cut off
4-20 mA21 mA
Power consumption Max. 660 mW
Load impedance
Max. 60 Ω at 12.5 VDCMax. 100 Ω at 13.3 VDCMax. 600 Ω at 24 VDCMax. 900 Ω at 30 VDC
Sensor materials
Measurement element Silicon-based MEMS sensor
Packing material EPDM or FKM rubber
Sensor housing Stainless steel 1.4404
Flow pipe Stainless steel 1.4408
Bluff body Stainless steel 1.4401
Wetted materialsCorrosion-resistant coating
EPDM or FKM rubberStainless steel 1.4401/04/08
Environmental standards
Enclosure class IP67
Temperature cycling IEC 68-2-14
Vibration (non-destructive) 20-2000 Hz, 10G, 4h
Electromagnetic compatibility EN 61326-1
TM
04
75
34
12
10
21 mA
4 mA
Qmin Qmax
Signal cut off
Vo
rte
x f
low
se
ns
or,
in
du
str
y (
VF
I)
Grundfos Direct Sensors™ 2
VFI 0.6-12 DN 25, technical data
Vortex flow sensor, industry, 0.6 - 12 m³/h
Fig. 10 VFI 0.6-12 sensor
Dimensions
Fig. 11 Dimensions VFI sensor with flanges
Flanges are compatible with DN 25/32 flanges sizes.
Fig. 12 Dimensions VFI sensor with thread
The VFI sensor with threaded ends must be mounted with union nuts.
Specifications
*Reference condition:
- Liquids at 20 °C, 1013 mbar, ρ = 998 kg/m3, v = 1 x 10-6 m2/s
Sensor output signals
Fig. 13 Flow response
TM
04
71
43
17
10
/ T
M0
4 4
25
1 1
71
0T
M0
4 7
15
4 1
61
0
Flange material
Flange size
A[mm]
B[mm]
C[mm]
D[mm]
Weight[kg]
Cast iron DN 25/32 (PN 40)
200 18 124 1404.52
Stainless steel 4.58
TM
04
71
53
16
10
MaterialThread
sizeA
[mm]B
[mm]C
[mm]Weight
[kg]
Stainless steel G1 1/4" 200 18 124 1.53
Flow
Measuring range 0.6 - 12 m³/h*
Accuracy (±1σ), 0 - 100 °C
± 1.5 % FS*
Response time < 1 s
Resolution 0.015 m³/h
Media and environment
Liquid types See appendix Minimum flow rate
Liquid max. pressure 28 barLiquid temperature (operation) -30 - 120 °C, non-freezing
Liquid temperature -30 - 120 °C, non-freezing
Ambient air temperature (operation)
–25 - 60 °C
Ambient air temperature –55 - 70 °C
Storage temperature –55 - 70 °C
Humidity 0 - 95 % RH, non-condensing
System burst pressure 60 bar
Electrical data
Power supply 12.5 - 30 VDC (± 5 %)
Output signals - cut off
4 - 20 mA21 mA
Power consumption Max. 660 mW
Load impedance
Max. 60 Ω at 12.5 VDCMax. 100 Ω at 13.3 VDCMax. 600 Ω at 24 VDCMax. 900 Ω at 30 VDC
Sensor materials
Measurement element Silicon-based MEMS sensor
Packing material EPDM or FKM rubber
Sensor housing Stainless steel 1.4404
Flow pipe Stainless steel 1.4408
Bluff body Stainless steel 1.4401
Wetted materialsCorrosion-resistant coating
EPDM or FKM rubberStainless steel 1.4401/04/08
Environmental standards
Enclosure class IP67
Temperature cycling IEC 68-2-14
Vibration (non-destructive) 20-2000 Hz, 10G, 4h
Electromagnetic compatibility EN 61326-1
TM
04
75
34
12
10
21 mA
4 mA
Qmin Qmax
Signal cut off
7
Vo
rtex
flow
se
ns
or, in
du
stry
(VF
I)
8
Grundfos Direct Sensors™2
VFI 1.3-25 DN 32, technical data
Vortex flow sensor, industry, 1.3 - 25 m³/h
Fig. 14 VFI 1.3-25 sensor
Dimensions
Fig. 15 Dimensions VFI sensor with flanges
Flanges are compatible with DN 25/32 flanges sizes.
Fig. 16 Dimensions VFI sensor with thread
The VFI sensor with threaded ends must be mounted with union nuts.
Specifications
*Reference condition:
- Liquids at 20 °C, 1013 mbar, ρ = 998 kg/m3, v = 1 x 10-6 m2/s
Sensor output signals
Fig. 17 Flow response
TM
04
71
44
17
10
/ T
M0
4 4
25
2 1
71
0T
M0
4 7
15
4 1
61
0
Flange material
Flange size
A[mm]
B[mm]
C[mm]
D[mm]
Weight[kg]
Cast iron DN 25/32 (PN 40)
200 18 128 1404.47
Stainless steel 4.53
TM
04
71
53
16
10
MatreialThread
sizeA
[mm]B
[mm]C
[mm]Weight
[kg]
Stainless steel G 1 1/2" 200 19 128 1.31
Flow
Measuring range 1.3 - 25 m³/h*
Accuracy (±1σ), 0 - 100 °C
± 1.5 % FS*
Response time < 1 s
Resolution 0.03125 m³/h
Media and environment
Liquid types See appendix Minimum flow rate
Liquid max. pressure 28 barLiquid temperature (operation) -30 - 120 °C, non-freezing
Liquid temperature -30 - 120 °C, non-freezing
Ambient air temperature (operation)
–25 - 60 °C
Ambient air temperature –55 - 70 °C
Storage temperature –55 - 70 °C
Humidity 0 - 95 % RH, non-condensing
System burst pressure 60 bar
Electrical data
Power supply 12.5 - 30 VDC (± 5 %)
Output signals - cut off
4 - 20 mA21 mA
Power consumption Max. 660 mW
Load impedance
Max. 60 Ω at 12.5 VDCMax. 100 Ω at 13.3 VDCMax. 600 Ω at 24 VDCMax. 900 Ω at 30 VDC
Sensor materials
Measurement element Silicon-based MEMS sensor
Packing material EPDM or FKM rubber
Sensor housing Stainless steel 1.4404
Flow pipe stainless steel 1.4408
Bluff body stainless steel 1.4401
Wetted materialsCorrosion-resistant coating
EPDM or FKM rubberStainless steel 1.4401/04/08
Environmental standards
Enclosure class IP67
Temperature cycling IEC 68-2-14
Vibration (non-destructive) 20-2000 Hz, 10G, 4h
Electromagnetic compatibility EN 61326-1
TM
04
75
34
12
10
21 mA
4 mA
Qmin Qmax
Signal cut off
Vo
rte
x f
low
se
ns
or,
in
du
str
y (
VF
I)
Grundfos Direct Sensors™ 2
VFI 2-40 DN 40, technical data
Vortex flow sensor, industry, 2 - 40 m³/h
Fig. 18 VFI 2 - 40 sensor
Dimensions
Fig. 19 Dimensions VFI sensor with flanges
Flanges are compatible with DN 40 flanges sizes.
Specifications
*Reference condition:
- Liquids at 20 °C, 1013 mbar, ρ = 998 kg/m3, v = 1 x 10-6 m2/s
Sensor output signals
Fig. 20 Flow response
TM
04
71
45
17
10
TM
04
71
54
16
10
Flange material
Flange size
A[mm]
B[mm]
C[mm]
D[mm]
Weight[kg]
Cast iron DN 40 (PN 40)
200 18 131 1505.58
Stainless steel 6.45
Flow
Measuring range 2 - 40 m³/h*
Accuracy (±1σ), 0 - 100 °C
± 1.5 % FS*
Response time < 1 s
Resolution 0.05 m³/h
Media and environment
Liquid types See appendix Minimum flow rate
Liquid max. pressure 28 barLiquid temperature (operation) -30-120 °C, non-freezing
Liquid temperature -30-120 °C, non-freezing
Ambient air temperature (operation)
–25 - 60 °C
Ambient air temperature –55 - 70 °C
Storage temperature –55 - 70 °C
Humidity 0 - 95 % RH, non-condensing
System burst pressure 60 bar
Electrical data
Power supply 12.5 - 30 VDC (± 5 %)
Output signals - cut off
4 - 20 mA21 mA
Power consumption Max. 660 mW
Load impedance
Max. 60 Ω at 12.5 VDCMax. 100 Ω at 13.3 VDCMax. 600 Ω at 24 VDCMax. 900 Ω at 30 VDC
Sensor materials
Measurement element Silicon-based MEMS sensor
Packing material EPDM or FKM rubber
Sensor housing Stainless steel 1.4404
Flow pipe Stainless steel 1.4408
Bluff body Stainless steel 1.4401
Wetted materialsCorrosion-resistant coating
EPDM or FKM rubberStainless steel 1.4401/04/08
Environmental standards
Enclosure class IP67
Temperature cycling IEC 68-2-14
Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h
Electromagnetic compatibility EN 61326-1
TM
04
75
34
12
10
21 mA
4 mA
Qmin Qmax
Signal cut off
9
Vo
rtex
flow
se
ns
or, in
du
stry
(VF
I)
10
Grundfos Direct Sensors™2
VFI 3.2-64 DN 50, technical data
Vortex flow sensor, industry, 3.2 - 64 m³/h
Fig. 21 VFI 3.2 - 64 sensor
Dimensions
Fig. 22 Dimensions VFI sensor with flanges
Flanges are compatible with DN 50 flanges sizes.
Specifications
*Reference condition:
- Liquids at 20 °C, 1013 mbar, ρ = 998 kg/m3, v = 1 x 10-6 m2/s
Sensor output signals
Fig. 23 Flow response
TM
04
71
46
17
10
TM
04
71
54
16
10
Flange material
Flange size
A[mm]
B[mm]
C[mm]
D[mm]
Weight[kg]
Cast iron DN 50 (PN 40)
200 22 138 1656.94
Stainless steel 5.94
Flow
Measuring range 3.2 - 64 m³/h*
Accuracy (±1σ), 0 - 100 °C
± 1.5 % FS*
Response time < 1 s
Resolution 0.08 m³/h
Media and environment
Liquid types See appendix Minimum flow rate
Liquid max. pressure 28 barLiquid temperature (operation) -30 - 120 °C, non-freezing
Liquid temperature -30 - 120 °C, non-freezing
Ambient air temperature (operation)
–25 - 60 °C
Ambient air temperature –55 - 70 °C
Storage temperature –55 - 70 °C
Humidity 0 - 95 % RH, non-condensing
System burst pressure 60 bar
Electrical data
Power supply 12.5 - 30 VDC (± 5 %)
Output signals - cut off
4 - 20 mA21 mA
Power consumption Max. 660 mW
Load impedance
Max. 60 Ω at 12.5 VDCMax. 100 Ω at 13.3 VDCMax. 600 Ω at 24 VDCMax. 900 Ω at 30 VDC
Sensor materials
Measurement element Silicon-based MEMS sensor
Packing material EPDM or FKM rubber
Sensor housing Stainless steel 1.4404
Flow pipe Stainless steel 1.4408
Bluff body Stainless steel 1.4401
Wetted materialsCorrosion-resistant coating
EPDM or FKM rubberStainless steel 1.4401/04/08
Environmental standards
Enclosure class IP67
Temperature cycling IEC 68-2-14
Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h
Electromagnetic compatibility EN 61326-1
TM
04
75
34
12
10
21 mA
4 mA
Qmin Qmax
Signal cut off
Vo
rte
x f
low
se
ns
or,
in
du
str
y (
VF
I)
Grundfos Direct Sensors™ 2
VFI 5.2-104 DN 65, technical data
Vortex flow sensor, industry, 5.2 - 104 m³/h
Fig. 24 VFI 5.2 - 104 sensor
Dimensions
Fig. 25 Dimensions VFI sensor with flanges
Flanges are compatible with DN 65 flanges sizes.
Specifications
*Reference condition:
- Liquids at 20 °C, 1013 mbar, ρ = 998 kg/m3, v = 1 x 10-6 m2/s
Sensor output signals
Fig. 26 Flow response
TM
04
71
47
17
10
TM
04
71
54
16
10
Flange material
Flange size
A[mm]
B[mm]
C[mm]
D[mm]
Weight[kg]
Cast iron DN 65 (PN 40)
200 25 145 1859.31
Stainless steel 9.9
Flow
Measuring range 5.2 - 104 m³/h*
Accuracy (±1σ), 0 - 100 °C
± 1.5 % FS*
Response time < 1 s
Resolution 0.13 m³/h
Media and environment
Liquid types See appendix Minimum flow rate
Liquid max. pressure 28 barLiquid temperature (operation) -30 - 120 °C, non-freezing
Liquid temperature -30 - 120 °C, non-freezing
Ambient air temperature (operation)
–25 - 60 °C
Ambient air temperature –55 - 70 °C
Storage temperature –55 - 70 °C
Humidity 0 - 95 % RH, non-condensing
System burst pressure 60 bar
Electrical data
Power supply 12.5 - 30 VDC (± 5 %)
Output signals - cut off
4 - 20 mA21 mA
Power consumption Max. 660 mW
Load impedance
Max. 60 Ω at 12.5 VDCMax. 100 Ω at 13.3 VDCMax. 600 Ω at 24 VDCMax. 900 Ω at 30 VDC
Sensor materials
Measurement element Silicon-based MEMS sensor
Packing material EPDM or FKM rubber
Sensor housing Stainless steel 1.4404
Flow pipe Stainless steel 1.4408
Bluff body Stainless steel 1.4401
Wetted materialsCorrosion-resistant coating
EPDM or FKM rubberStainless steel 1.4401/04/08
Environmental standards
Enclosure class IP67
Temperature cycling IEC 68-2-14
Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h
Electromagnetic compatibility EN 61326-1
TM
04
75
34
12
10
21 mA
4 mA
Qmin Qmax
Signal cut off
11
Vo
rtex
flow
se
ns
or, in
du
stry
(VF
I)
12
Grundfos Direct Sensors™2
VFI 8-160 DN 80, technical data
Vortex flow sensor, industry, 8 - 160 m³/h
Fig. 27 VFI 8 - 160 sensor
Dimensions
Fig. 28 Dimensions VFI sensor with flanges
Flanges are compatible with DN 80 flanges sizes.
Specifications
*Reference condition:
- Liquids at 20 °C, 1013 mbar, ρ = 998 kg/m3, v = 1 x 10-6 m2/s
Sensor output signals
Fig. 29 Flow response
TM
04
71
48
17
10
TM
04
71
54
16
10
Flange material
Flange size
A[mm]
B[mm]
C[mm]
D[mm]
Weight[kg]
Cast iron DN80 (PN40)
200 25 152 23511,51
Stainless steel 16
Flow
Measuring range 8 - 160 m³/h*
Accuracy (±1σ), 0 - 100 °C
± 1.5 % FS*
Response time < 1 s
Resolution 0.2 m³/h
Media and environment
Liquid types See appendix Minimum flow rate
Liquid max. pressure 28 barLiquid temperature (operation) -30 - 120 °C, non-freezing
Liquid temperature -30 - 120 °C, non-freezing
Ambient air temperature (operation)
–25 - 60 °C
Ambient air temperature –55 - 70 °C
Storage temperature –55 - 70 °C
Humidity 0 - 95 % RH, non-condensing
System burst pressure 60 bar
Electrical data
Power supply 12.5 - 30 VDC (± 5 %)
Output signals - cut off
4 - 20 mA21 mA
Power consumption Max. 660 mW
Load impedance
Max. 60 Ω at 12.5 VDCMax. 100 Ω at 13.3 VDCMax. 600 Ω at 24 VDCMax. 900 Ω at 30 VDC
Sensor materials
Measurement element Silicon-based MEMS sensor
Packing material EPDM or FKM rubber
Sensor housing Stainless steel 1.4404
Flow pipe Stainless steel 1.4408
Bluff body Stainless steel 1.4401
Wetted materialsCorrosion-resistant coating
EPDM or FKM rubberStainless steel 1.4401/04/08
Environmental standards
Enclosure class IP67
Temperature cycling IEC 68-2-14
Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h
Electromagnetic compatibility EN 61326-1
TM
04
75
34
12
10
21 mA
4 mA
Qmin Qmax
Signal cut off
Vo
rte
x f
low
se
ns
or,
in
du
str
y (
VF
I)
Grundfos Direct Sensors™ 2
VFI 12-240 DN 100, technical data
Vortex flow sensor, industry, 12 - 240 m³/h
Fig. 30 VFI 12 - 240 sensor
Dimensions
Fig. 31 Dimensions VFI sensor with flanges
Flanges are compatible with DN 100 flanges sizes.
Specifications
*Reference condition:
- Liquids at 20 °C, 1013 mbar, ρ = 998 kg/m3, v = 1 x 10-6 m2/s
Sensor output signals
Fig. 32 Flow response
TM
04
71
49
17
10
TM
04
71
54
16
10
Flange material
Flange size
A[mm]
B[mm]
C[mm]
D[mm]
Weight[kg]
Cast iron DN 100 (PN 16)
250 25 163 22013.56
Stainless steel 14.00
Flow
Measuring range 12 - 240 m³/h*
Accuracy (±1σ), 0 - 100 °C
± 1.5 % FS*
Response time < 1 s
Resolution 0.30 m³/h
Media and environment
Liquid types See appendix Minimum flow rate
Liquid max. pressure 16 barLiquid temperature (operation) -30 - 120 °C, non-freezing
Liquid temperature -30 - 120 °C, non-freezing
Ambient air temperature (operation)
–25 - 60 °C
Ambient air temperature –55 - 70 °C
Storage temperature –55 - 70 °C
Humidity 0 - 95 % RH, non-condensing
System burst pressure 60 bar
Electrical data
Power supply 12.5 - 30 VDC (± 5 %)
Output signals - cut off
4 - 20 mA21 mA
Power consumption Max. 660 mW
Load impedance
Max. 60 Ω at 12.5 VDCMax. 100 Ω at 13.3 VDCMax. 600 Ω at 24 VDCMax. 900 Ω at 30 VDC
Sensor materials
Measurement element Silicon-based MEMS sensor
Packing material EPDM or FKM rubber
Sensor housing Stainless steel 1.4404
Flow pipe Stainless steel 1.4408
Bluff body Stainless steel 1.4401
Wetted materialsCorrosion-resistant coating
EPDM or FKM rubberStainless steel 1.4401/04/08
Environmental standards
Enclosure class IP67
Temperature cycling IEC 68-2-14
Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h
Electromagnetic compatibility EN 61326-1
TM
04
75
34
12
10
21 mA
4 mA
Qmin Qmax
Signal cut off
13
Vo
rtex
flow
se
ns
or, s
tan
da
rd
14
Grundfos Direct Sensors™3
3. Vortex flow sensor, standard
VFS general data
Vortex flow sensor, standard
Fig. 33 VFS and VFS QT Sensors
Technical overview Grundfos Direct Sensors™, type VFS, is a series of combined flow- and temperature sensors (two-in-one) based on the principle of vortex shedding behind a bluff body. The VFS sensors are designed for high-volume production and are fully compatible with wet, aggressive media. The VFS sensor utilises MEMS sensing technology in combination with a novel packaging concept using corrosion-resistant coating on the MEMS sensor element. This makes the VFS sensor very robust and ideal for high-volume OEM applications.
Applications• Thermal management in solar heating systems
• industrial process flow control
• flow rate detection for pump controls
• monitoring of pumps, valves and filters
• temperature control
• domestic hot-water systems
• heat metering indication (solar heat pumps).
Features• Flow ranges: 1-12, 1-15, 1.3-20, 2-40, 5-100,
10-200 and 20-400 l/min.
• designed to operate in glycol mixture
• based on vortex shedding
• voltage output (ratiometric, ideal for use with microprocessor and PLC)
• compact and robust design
• approved for drinking water: WRAS, KTW, W270, ACS
• SiliCoat® technology.
Benefits• No moving parts
• flow- and temperature sensor in one package (two-in-one sensor)
• quick temperature response (direct media contact)
• compatible with wet, aggressive media
• cost-effective and robust construction.
Type key
For more information. see http://www.grundfos.com/directsensors.
Electrical connections
Fig. 34 Electrical connections
Power supply requirements
• 5 VDC ±5%
• max. 10 mV ripple, 50 Hz
• min. output current 10 mA
• separated from hazardous live circuitry by double or reinforced insulation
• power limitation: 150 VA; current limitation: 8 A.
Directives
The Grundfos Vortex flow sensors are in conformity with these Council directives on the approximation of the laws of the EC member states:
• Low Voltage Directive (2006/95/EC)
– Standards used: EN 61010-1:2001
• EMC Directive (2004/108/EC)
– Standards used: EN 61326-1:2006 and 61326-2-3:2006
The Grundfos Vortex flow sensors fall under Article 3, §3 of PED Directive 97/23/EEC and are therefore not required to be CE-marked according to this directive.
TM
05
47
45
24
12
96xxxxxx - XX - XXXX XXXXX
Product number
Version
Production year and week
Consecutive number
TM
04
71
56
16
10
Pin configuration Colour
1 Temperature signal (0.5 to 3.5 V relative to pin 3) Yellow
2 Flow signal (0.5 to 3.5 V relative to pin 3) White
3 GND (0 V), PELV Green
4 Power supply (+ 5 V DC) Brown
V
V
4321
PE
Temperature signal
Flow signal
Electrical connector
Pin No
Pipe system
Vo
rte
x f
low
se
ns
or,
sta
nd
ard
Grundfos Direct Sensors™ 3
VFS Sensors
Fig. 35 VFS family
VFS flow sensors consist of a composite flow pipe and a sensor with cable.
The VFS are available in 1-20, 2-40, 5-100, 10-200, 20-400 l/min versions.
VFS QT sensors
Fig. 36 VFS QT family
VFS QT flow sensors consist of a composite insert, a stainless steel outer pipe and a sensor with cable.
The VFS QT are availiable in 1-12, 1-15, 2-40, 5-100, 10-200 l/min versions.
Sensor and cable connection
Fig. 37 Sensor and cableT
M0
5 4
74
4 2
51
2T
M0
5 4
74
3 2
51
2
TM
05
47
49
25
12
15
Vo
rtex
flow
se
ns
or, s
tan
da
rd
16
Grundfos Direct Sensors™3
VFS 1-20, technical data
Vortex flow sensor, standard, 1-20 l/min
Fig. 38 VFS 1-20 sensor
Dimensions
Fig. 39 Dimensional sketches of sensing element
Fig. 40 Dimensional sketch of flow pipe
Sensor output signals
Fig. 41 Flow response
Fig. 42 Temperature response
Specifications
TM
05
47
51
25
12
TM
05
46
69
25
12
TM
03
82
05
08
07
TM
03
82
06
08
07
Flow (l/min)
Flo
w o
utp
ut
sig
na
l (V
)
TM
03
81
49
06
07
Flow
Measuring range:In water (0 - 100 °C)Tyfocor LS (30 - 100 °C)
1.3 - 20 l/min1.3 - 20 l/min
Accuracy:In water (±1σ), (0 - 100 °C)Tyfocor LS (±1σ), (0 - 100 °C)
±1.5 % FS± 5 % FS (typical ±3% FS)
Response time (63.2 %) < 1s
Resolution 0.1 l/min
Temperature
Measuring range 0 - 100 °C
Accuracy (±1σ), 25 - 80 °C ±1 °C
Accuracy (±1σ), 0 - 100 °C ±2 °C
Response time (63.2 % at 50 % FS flow)
250 ms
Resolution 0.35 °C
Media and environment
Media typesThe sensor is compatible with liquids
(kinematic viscosity ≤ 2 mm2/s)
Media temperature (operation)Water: 0 - 100 °C
Tyfocor LS: 30 - 100 °C
Media temperature (peak)–25 °C, non-freezing
120 °C for 5 minutes, up to 3 weeks in sensor lifetime
Ambient air temperature (operation)
–25 - 60 °C
Ambient air temperature (peak) –55 - 90 °C
Humidity 0 - 95 % (relative), non-condensing
System burst pressure > 16 bar
Electrical data
Power supply5 V DC (± 5 %). Grounding of the sensor
supply is recommended (PELV)
Output signals Ratiometric
Flow signal 0.35 - 3.5 V (Zero at 0.35 V)
Temperature signal 0.5 - 3.5 V
Power consumption < 50 mW
Load impedance > 10 kΩ
Sensor materials
Sensing element Silicon-based MEMS sensor
Seal (sensor to housing) EPDM rubber
Housing Composites (PPS, PA66)
Flow pipe PPA 40-GF
Wetted materialsCorrosion-resistant coating, EPDM,
PPS, PPA 40-GF
Environmental standards
Enclosure class IP44 (Not overmoulded IP20)
Temperature cycling IEC 68-2-14
Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h
Electromagnetic compatibility EN 61326-1
Dimensions
Sensing element 47 x 40 x 20 mm, see drawing
Flow pipe 82 x 39 x 25 mm
Temperature (°C)
Tem
pe
ratu
re o
utp
ut
sig
na
l (V
)
Vo
rte
x f
low
se
ns
or,
sta
nd
ard
Grundfos Direct Sensors™ 3
VFS 2-40, technical data
Vortex flow sensor, standard, 2-40 l/min
Fig. 43 VFS 2-40 sensor
Dimensions
Fig. 44 Dimensional sketches of sensing element
Fig. 45 Dimensional sketch of flow pipe
Sensor output signals
Fig. 46 Flow response
Fig. 47 Temperature response
Specifications
TM
05
47
49
25
12
TM
05
46
69
25
12
TM
03
82
04
08
07
TM
03
82
16
08
07
Flow (l/min)
Flo
w o
utp
ut
sig
na
l (V
)
TM
03
81
49
06
07
Flow
Measuring range:In water (0 - 100 °C)Tyfocor LS (30 - 100 °C)
2 - 40 l/min 2 - 40 l/min
Accuracy:In water (±1σ), (0 - 100 °C)Tyfocor LS (±1σ), (0 - 100 °C)
±1.5 % FS± 5 % FS (typical ±3% FS)
Response time (63.2 %) < 1 s
Resolution 0.2 l/min
Temperature
Measuring range 0 - 100 °C
Accuracy (±1σ), 25 - 80°C ±1 °C
Accuracy (±1σ), 0 - 100°C ±2 °C
Response time (63.2 % at 50 % FS flow)
250 ms
Resolution 0.35 °C
Media and environment
Media typesThe sensor is compatible with liquids
(kinematic viscosity ≤ 2 mm2/s)
Media temperature (operation)Water: 0 - 100 °C
Tyfocor LS: 30 - 100 °C
Media temperature (peak)–25 °C, non-freezing
120 °C for 5 minutes, up to 3 weeks in sensor lifetime
Ambient air temperature (operation)
–25 - 60 °C
Ambient air temperature (peak)
–55 - 90 °C
Humidity 0 - 95 % (relative), non-condensing
System burst pressure > 16 bar
Electrical data
Power supply5 V DC (± 5 %). Grounding of the sensor
supply is required (PELV)
Output signals Ratiometric
Flow signal 0.5 - 3.5 V (Zero at 0.35 V)
Temperature signal 0.5 - 3.5 V
Power consumption < 50 mW
Load impedance > 10 kΩ
Sensor materials
Sensing element Silicon-based MEMS sensor
Seal (sensor to housing) EPDM rubber
Housing Composites (PPS, PA66)
Flow pipe PPA 40-GF
Wetted materialsCorrosion-resistant coating, EPDM, PPS,
PPA 40-GF
Environmental standards
Enclosure class IP44 (Non overmoulded IP20)
Temperature cycling IEC 68-2-14
Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h
Electromagnetic compatibility EN 61326-1
Dimensions
Sensing element 47 x 40 x 20 mm, see drawing
Flow pipe 88 x 39 x 25 mm
Temperature (°C)
Tem
pe
ratu
re o
utp
ut
sig
na
l (V
)
17
Vo
rtex
flow
se
ns
or, s
tan
da
rd
18
Grundfos Direct Sensors™3
VFS 5-100, technical data
Vortex flow sensor, standard, 5-100 l/min
Fig. 48 VFS 5-100 sensor
Dimensions
Fig. 49 Dimensional sketches of sensing element
Fig. 50 Dimensional sketch of flow pipe
Sensor output signals
Fig. 51 Flow response
Fig. 52 Temperature response
Specifications
TM
05
47
48
25
12
TM
05
46
69
25
12
TM
03
82
19
08
07
TM
03
82
17
08
07
2xISO 228/1-G 1A
Flow (l/min)
Flo
w o
utp
ut
sig
na
l (V
)
TM
03
81
49
06
07
Flow
Measuring range:In water (0 - 100 °C)Tyfocor LS (30 - 100 °C)
5 - 100 l/min5 - 100 l/min
Accuracy:In water (±1σ), (0 - 100 °C)Tyfocor LS (±1σ), (0 - 100 °C)
±1.5 % FS± 5 % FS (typical ±3% FS)
Response time (63.2 %) < 1 s
Resolution 0.5 l/min
Temperature
Measuring range 0 - 100 °C
Accuracy (±1σ), 25 - 80 °C ±1 °C
Accuracy (±1σ), 0 - 100 °C ±2 °C
Response time (63.2 % at 50 % FS flow)
250 ms
Resolution 0.35 °C
Media and environment
Media typesThe sensor is compatible with liquids
(kinematic viscosity ≤ 2 mm2/s)
Media temperature (operation)Water: 0 - 100 °C
Tyfocor LS: 30 - 100 °C
Media temperature (peak)–25 °C, non-freezing
120 °C for 5 minutes, up to 3 weeks in sensor lifetime
Ambient air temperature (operation)
–25 - 60 °C
Ambient air temperature (peak)
–55 - 90 °C
Humidity 0 - 95 % (relative), non-condensing
System burst pressure > 16 bar
Electrical data
Power supply5 V DC (±5 %). Grounding of the sensor
supply is required (PELV)
Output signals Ratiometric
Flow signal 0.5 - 3.5 V (Zero at 0.35 V)
Temperature signal 0.5 - 3.5 V
Power consumption < 50 mW
Load impedance > 10 kΩ
Sensor materials
Sensing element Silicon-based MEMS sensor
Seal (sensor to housing) EPDM rubber
Housing Composites (PPS, PA66)
Flow pipe PPA 40-GF
Wetted materialsCorrosion-resistant coating, EPDM, PPS,
PPA 40-GF
Environmental standards
Enclosure class IP44 (Non overmoulded IP20)
Temperature cycling IEC 68-2-14
Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h
Electromagnetic compatibility EN 61326-1
Dimensions
Sensing element 47 x 40 x 20 mm, see drawing
Flow pipe 129 x 37 x 32 mm
Temperature (°C)
Tem
pe
ratu
re o
utp
ut
sig
na
l (V
)
Vo
rte
x f
low
se
ns
or,
sta
nd
ard
Grundfos Direct Sensors™ 3
VFS 10-200, technical data
Vortex flow sensor, standard, 10-200 l/min
Fig. 53 VFS 10-200 sensor
Dimensions
Fig. 54 Dimensional sketches of sensing element
Fig. 55 Dimensional sketch of flow pipe
Sensor output signals
Fig. 56 Flow response
Fig. 57 Temperature response
SpecificationsTM
05
47
47
25
12
TM
05
46
69
25
12
TM
03
82
04
08
07
TM
03
82
16
08
07
2xISO 228/1-G 1¼ A
Flow (l/min)
Flo
w o
utp
ut
sig
na
l (V
)
TM
03
81
49
06
07
Flow
Measuring range:In water (0 - 100 °C)Tyfocor LS (30 - 100 °C)
10 - 200 l/min10 - 200 l/min
Accuracy:In water (±1σ), (0 - 100 °C)Tyfocor LS (±1σ), (0 - 100 °C)
±1.5 % FS± 5 % FS (typical ±3% FS)
Response time (63.2 %) < 1.0 s
Resolution 1.0 l/min
Temperature
Measuring range 0 - 100 °C
Accuracy (± 1σ), 25 - 80 °C ± 1 °C
Accuracy (± 1σ), 0 - 100 °C ± 2 °C
Response time (63.2 %) 250 ms
Resolution 0.35 °C
Media and environment
Media typesThe sensor is compatible with liquids
(kinematic viscosity ≤ 2 mm2/s)
Media temperature (operation)Water: 0 - 100 °C
Tyfocor LS: 30 - 100 °C
Media temperature (peak)–25 °C, non-freezing
120 °C for 5 minutes, up to 3 weeks in sensor lifetime
Ambient air temperature (operation)
–25 - 60 °C
Ambient air temperature (peak) –55 - 90 °C
Humidity 0 - 95 % RH, non-condensing
System burst pressure > 16 bar
Electrical data
Power supply5 VDC (± 5 %). Grounding of the sensor
supply is required (PELV)
Output signals Ratiometric
Flow signal 0.5 - 3.5 V (Zero at 0.35 V)
Temperature signal 0.5 - 3.5 V
Power consumption < 50 mW
Load impedance > 10 kΩ
Sensor materials
Sensing element Silicon-based MEMS sensor
Seal (sensor to housing) EPDM rubber
Housing Composites (PPS, PA66)
Flow pipe PPA 40-GF
Wetted materialsCorrosion-resistant coating, EPDM, PPS,
PPA 40-GF
Environmental standards
Enclosure class IP44 (Non overmoulded IP20)
Temperature cycling IEC 68-2-14
Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h
Electromagnetic compatibility EN 61326-1
Dimensions
Sensing element 47 x 40 x 20 mm, see drawings
Flow pipe 137 x 45 x 41 mm
Temperature (°C)Tem
pe
ratu
re o
utp
ut
sig
na
l (V
)
19
Vo
rtex
flow
se
ns
or, s
tan
da
rd
20
Grundfos Direct Sensors™3
VFS 20-400, technical data
Vortex flow sensor, standard, 20-400 l/min
Fig. 58 VFS 20-400 sensor
Dimensions
Fig. 59 Dimensional sketches of sensing element
Fig. 60 Dimensional sketch of flow pipe
Sensor output signals
Fig. 61 Flow response
Fig. 62 Temperature response
SpecificationsTM
05
47
46
25
12
TM
05
46
69
25
12
TM
04
29
54
33
08
TM
03
82
18
08
07
2xISO 228/1-G 1½
Flow (l/min)
Flo
w o
utp
ut
sig
na
l (V
)
100 200 300 400
TM
03
81
49
06
07
Flow
Measuring range:In water (0 - 100 °C)Tyfocor LS (30 - 100 °C)
20 - 400 l/min20 - 400 l/min
Accuracy:In water (±1σ), (0 - 100 °C)Tyfocor LS (±1σ), (0 - 100 °C)
±1.5 % FS± 5 % FS (typical ±3% FS)
Response time (63.2 %) < 1.0 s
Resolution 2.0 l/min
Temperature
Measuring range 0 - 100 °C
Accuracy (± 1σ), 25 - 80 °C ± 1 °C
Accuracy (± 1σ), 0 - 100 °C ± 2 °C
Response time (63.2 % at 50 % FS flow)
250 ms
Resolution 0.35 °C
Media and environment
Media typesThe sensor is compatible with liquids
(kinematic viscosity ≤ 2 mm2/s)
Media temperature (operation)Water: 0 - 100 °C
Tyfocor LS: 30 - 100 °C
Media temperature (peak)–25 °C, non-freezing
120 °C for 5 minutes, up to 3 weeks in sensor lifetime
Ambient air temperature (operation)
–25 - 60 °C
Ambient air temperature (peak) –55 - 90 °C
Humidity 0 - 95 % RH, non-condensing
System burst pressure > 16 bar
Electrical data
Power supply5 VDC (± 5 %). Grounding of the sensor
supply is required (PELV)
Output signals Ratiometric
Flow signal 0.5 - 3.5 V (Zero at 0.35 V)
Temperature signal 0.5 - 3.5 V
Power consumption < 50 mW
Load impedance > 10 kΩ
Sensor materials
Sensing element Silicon-based MEMS sensor
Seal (sensor to housing) EPDM rubber
Housing Composites (PPS, PA66)
Flow pipe PPA 40-GF
Wetted materialsCorrosion-resistant coating, EPDM, PPS,
PPA 40-GF
Environmental standards
Enclosure class IP44 (Non-overmoulded IP20)
Temperature cycling IEC 68-2-14
Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h
Electromagnetic compatibility EN 61326-1
Dimensions
Sensing element 47 x 40 x 20 mm, see drawings
Flow pipe 180 x 54 x 48 mm
Temperature (°C)Tem
pe
ratu
re o
utp
ut
sig
na
l (V
)
Vo
rte
x f
low
se
ns
or,
sta
nd
ard
Grundfos Direct Sensors™ 3
VFS 1-12 QT, technical data
Vortex flow sensor, standard, 1-12 l/min
Fig. 63 VFS 1-12 sensor
Dimensions
Fig. 64 Dimensional sketches of VFS QT
Sensor output signals
Fig. 65 Flow response
Fig. 66 Temperature response
Specifications
TM
05
47
42
25
12
TM
00
5 4
67
1 2
51
2T
M0
05
46
70
25
12
TM
03
24
65
21
08
0 1 2 3 4 5 6 7 8 9 10 11 12
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
Flow (l/min)
Flo
w o
utp
ut
sig
na
l (V
)
TM
03
81
49
06
07
Flow
Measuring range:In water (0 - 100 °C)Tyfocor LS (30 - 100 °C)
1 - 12 l/min1 - 12 l/min
Accuracy:In water (±1σ), (0 - 100 °C) Tyfocor LS (±1σ), (0 - 100 °C)
± 1.5 % FS± 5.0 % FS (typical 3%)
Response time (63.2 %) < 3 sec.
Resolution 0.06 l/min
Temperature
Measuring range 0 - 100 °C
Accuracy (±1σ), 25 - 80 °C ± 1 °C
Accuracy (±1σ), 0 - 100 °C ± 2 °C
Response time (63.2 % at 50 % FS flow)
250 ms
Resolution 0.35 °C
Media and environment
Media typesThe sensor is compatible with liquids
(kinematic viscosity ≤ 4 mm2/s)
Media temperature (operation)Water: 0 - 100 °C
Tyfocor LS: 30 - 100 °C
Media temperature (peak)–25 °C, non-freezing
120 °C for 5 minutes, up to 3 weeks in sensor lifetime
Ambient air temperature (operation)
–25 - 60 °C
Ambient air temperature (peak) –55 - 90 °C
Humidity 0 - 95 % (relative), non-condensing
System burst pressure > 16 bar
Electrical data
Power supply5 V DC (± 5 %). Grounding of the sensor
supply is required (PELV)
Output signals Ratiometric
Flow signal 0.5 - 3.5 V (Zero at 0.25 V)
Temperature signal 0.5 - 3.5 V
Power consumption < 50 mW
Load impedance > 10 kΩ
Sensor materials
Sensing element Silicon-based MEMS sensor
Seal (sensor to housing) EPDM rubber
Housing Composites (PPS, PA66)
Vortex tube 1.4408
Insert PPA 40 GF
Wetted materialsCorrosion-resistant coating
EPDM, PPS, PPA 40-GF, 1.4408
Environmental standards
Enclosure class IP44 (Non overmoulded IP20)
Temperature cycling IEC 68-2-14
Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h
Electromagnetic compatibility EN 61326-1
Dimensions
Sensing element 47 x 40 x 20 mm, see drawing
Vortex tube 110 x 29.8 x 31.5 mm
Insert 63.9 x 16 x 15.4 mm
Temperature (°C)
Tem
pe
ratu
re o
utp
ut
sig
na
l (V
)
21
Vo
rtex
flow
se
ns
or, s
tan
da
rd
22
Grundfos Direct Sensors™3
VFS 1-15 QT, technical data
Vortex flow sensor, standard, 1-15 l/min
Fig. 67 VFS 1-15 sensor
Dimensions
Fig. 68 Dimensional sketches of VFS QT
Sensor output signals
Fig. 69 Flow response
Fig. 70 Temperature response
Specifications
TM
05
47
42
25
12
TM
00
5 4
67
1 2
51
2T
M0
05
46
70
25
12
TM
05 3
706
16
12
0 5 10
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
15Flow (l/min)
Flo
w o
utp
ut
sig
na
l (V
)
TM
03
81
49
06
07
Flow
Measuring range:In water (0 - 100 °C)Tyfocor LS (30 - 100 °C)
1 - 15 l/min1 - 15 l/min
Accuracy:In water (±1σ), (0 - 100 °C) Tyfocor LS (±1σ), (0 - 100 °C)
± 1.5 % FS± 5.0 % FS (typical 3%)
Response time (63.2 %) < 1 sec.
Resolution 0.075 l/min
Temperature
Measuring range 0 - 100 °C
Accuracy (±1σ), 25 - 80 °C ± 1 °C
Accuracy (±1σ), 0 - 100 °C ± 2 °C
Response time (63.2 % at 50 % FS flow)
250 ms
Resolution 0.35 °C
Media and environment
Media typesThe sensor is compatible with liquids
(kinematic viscosity ≤ 2 mm2/s)
Media temperature (operation)Water: 0 - 100 °C
Tyfocor LS: 30 - 100 °C
Media temperature (peak)–25 °C, non-freezing
120 °C for 5 minutes, up to 3 weeks in sensor lifetime
Ambient air temperature (operation)
–25 - 60 °C
Ambient air temperature (peak) –55 - 90 °C
Humidity 0 - 95 % (relative), non-condensing
System burst pressure > 16 bar
Electrical data
Power supply5 V DC (± 5 %). Grounding of the sensor
supply is required (PELV)
Output signals Ratiometric
Flow signal 0.5 - 3.5 V (Zero at 0.25 V)
Temperature signal 0.5 - 3.5 V
Power consumption < 50 mW
Load impedance > 10 kΩ
Sensor materials
Sensing element Silicon-based MEMS sensor
Seal (sensor to housing) EPDM rubber
Housing Composites (PPS, PA66)
Vortex tube 1.4408
Insert PPA 40 GF
Wetted materialsCorrosion-resistant coating
EPDM, PPS, PPA 40-GF, 1.4408
Environmental standards
Enclosure class IP44 (Non overmoulded IP20)
Temperature cycling IEC 68-2-14
Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h
Electromagnetic compatibility EN 61326-1
Dimensions
Sensing element 47 x 40 x 20 mm, see drawing
Vortex tube 110 x 29.8 x 31.5 mm
Insert 63.9 x 16 x 15.4 mm
Temperature (°C)
Tem
pe
ratu
re o
utp
ut
sig
na
l (V
)
Vo
rte
x f
low
se
ns
or,
sta
nd
ard
Grundfos Direct Sensors™ 3
VFS 2-40 QT, technical data
Vortex flow sensor, standard, 2-40 l/min
Fig. 71 VFS 2-40 sensor
Dimensions
Fig. 72 Dimensional sketches of VFS QT
Sensor output signals
Fig. 73 Flow response
Fig. 74 Temperature response
Specifications
TM
05
47
41
25
12
TM
00
5 4
67
1 2
51
2T
M0
05
46
70
25
12
TM
03
82
16
08
07
Flow (l/min)
Flo
w o
utp
ut
sig
na
l (V
)
TM
03
81
49
06
07
Flow
Measuring range:In water (0 - 100 °C)Tyfocor LS (30 - 100 °C)
2 - 40 l/min
Accuracy:In water (±1σ), (0 - 100 °C) Tyfocor LS (±1σ), (0 - 100 °C)
± 1.5 % FS± 5.0 % FS (typical 3%)
Response time (63.2 %) < 1 sec.
Resolution 0.2 l/min
Temperature
Measuring range 0 - 100 °C
Accuracy (±1σ), 25 - 80 °C ±1 °C
Accuracy (±1σ), 0 - 100 °C ±2 °C
Response time (63.2 % at 50 % FS flow)
250 ms
Resolution 0.35 °C
Media and environment
Media typesThe sensor is compatible with liquids
(kinematic viscosity ≤ 2 mm²/s).
Media temperature (operation)Water: 0 - 100 °C
Tyfocor LS: 30 - 100 °C
Media temperature (peak)–25 °C, non-freezing
120 °C for 5 minutes, up to 3 weeks in sensor lifetime
Ambient air temperature (operation)
–25 - 60 °C
Ambient air temperature (peak) –55 - 90 °C
Humidity 0 - 95 % (relative), non-condensing
System burst pressure > 16 bar
Electrical data
Power supply5 V DC (±5 %). Grounding of the sensor
supply is required (PELV)
Output signals Ratiometric
Flow signal 0.5 - 3.5 V (zero at 0.35 V)
Temperature signal 0.5 - 3.5 V
Power consumption < 50 mW
Load impedance > 10 kΩ
Sensor materials
Sensing element Silicon-based MEMS sensor
Seal (sensor to housing) EPDM rubber
Housing Composites (PPS, PA66)
Vortex tube 1.4408
Insert PPA 40 GF
Wetted materialsCorrosion-resistant coating, EPDM,
PPS, PPA 40-GF, 1.4408
Environmental standards
Enclosure class IP44 (Non overmoulded IP20)
Temperature cycling IEC 68-2-14
Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h
Electromagnetic compatibility EN 61326-1
Dimensions
Sensing element 47 x 40 x 20 mm, see drawing
Vortex tube 110 x 29.8 x 31.5 mm
Insert 63.9 x 16 x 15.4 mm
Temperature (°C)Tem
pe
ratu
re o
utp
ut
sig
na
l (V
)
23
Vo
rtex
flow
se
ns
or, s
tan
da
rd
24
Grundfos Direct Sensors™3
VFS 5-100 QT, technical data
Vortex flow sensor, standard, 5-100 l/min
Fig. 75 VFS 5-100 sensor
Dimensions
Fig. 76 Dimensional sketches of VFS QT
Sensor output signals
Fig. 77 Flow response
Fig. 78 Temperature response
Specifications
TM
05
47
40
25
12
TM
00
5 4
67
2 2
51
2T
M0
3 8
21
7 0
80
7T
M0
3 8
14
9 0
60
7
Flow (l/min)
Flo
w o
utp
ut
sig
na
l (V
)
Temperature (°C)Tem
pe
ratu
re o
utp
ut
sig
na
l (V
)
Flow
Measuring range:In water (0 - 100 °C)Tyfocor LS (30 - 100 °C)
5 - 100 l/min
Accuracy:In water (±1σ), (0 - 100 °C) Tyfocor LS (±1σ), (0 - 100 °C)
± 1.5 % FS± 5.0 % FS (typical 3%)
Response time (63.2 %) < 1 s
Resolution 0.5 l/min
Temperature
Measuring range 0 - 100 °C
Accuracy (±1σ), 25 - 80 °C ±1 °C
Accuracy (±1σ), 0 - 100 °C ±2 °C
Response time (63.2 % at 50 % FS flow)
250 ms
Resolution 0.35 °C
Media and environment
Media typesThe sensor is compatible with liquids
(kinematic viscosity ≤ 2 mm2/s)
Media temperature (operation)Water: 0 - 100 °C
Tyfocor LS: 30 - 100 °C
Media temperature (peak)–25 °C, non-freezing
120 °C for 5 minutes, up to 3 weeks in sensor lifetime
Ambient air temperature (operation)
–25 - 60 °C
Ambient air temperature (peak) –55 - 90 °C
Humidity 0 - 95 % (relative), non-condensing
System burst pressure > 16 bar
Electrical data
Power supply5 V DC (±5 %). Grounding of the sensor
supply is required (PELV)
Output signals Ratiometric
Flow signal 0.5 - 3.5 V (Zero at 0.35 V)
Temperature signal 0.5 - 3.5 V
Power consumption < 50 mW
Load impedance > 10 kΩ
Sensor materials
Sensing element Silicon-based MEMS sensor
Seal (sensor to housing) EPDM rubber
Vortex tube 1.4408
Insert PPA 40-GF
Wetted materialsCorrosion-resistant coating, EPDM,
PPS, PPA 40-GF, 1.4408
Environmental standards
Enclosure class IP44 (Non overmoulded IP20)
Temperature cycling IEC 68-2-14
Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h
Electromagnetic compatibility EN 61326-1
Dimensions
Sensing element 47 x 40 x 20 mm, see drawing
Vortex tube 129 x 37 x 32 mm
Insert 99.2 x 23.4x 21.9 mm
Vo
rte
x f
low
se
ns
or,
sta
nd
ard
Grundfos Direct Sensors™ 3
VFS 10-200 QT, technical data
Vortex flow sensor, standard, 10-200 l/min
Fig. 79 VFS 10-200 sensor
Dimensions
Fig. 80 Dimensional sketches of VFS QT
Sensor output signals
Fig. 81 Flow response
Fig. 82 Temperature response
Specifications
TM
05
47
39
25
12
TM
00
5 4
67
3 2
51
2T
M0
3 8
21
8 0
80
7T
M0
3 8
14
9 0
60
7
Flow (l/min)
Flo
w o
utp
ut
sig
na
l (V
)
Temperature (°C)Tem
pe
ratu
re o
utp
ut
sig
na
l (V
)
Flow
Measuring range:In water (0 - 100 °C)Tyfocor LS (30 - 100 °C)
10 - 200 l/min
Accuracy:In water (±1σ), (0 - 100 °C) Tyfocor LS (±1σ), (0 - 100 °C)
± 1.5 % FS± 5.0 % FS (typical 3%)
Response time (63.2 %) < 1.0 s
Resolution 1.0 l/min
Temperature
Measuring range 0 - 100 °C
Accuracy (± 1σ), 25 - 80 °C ± 1 °C
Accuracy (± 1σ), 0 - 100 °C ± 2 °C
Response time (63.2 % at 50 % FS flow)
250 ms
Resolution 0.35 °C
Media and environment
Media typesThe sensor is compatible with liquids
(kinematic viscosity ≤ 2 mm2/s)
Media temperature (operation)Water: 0 - 100 °C
Tyfocor LS: 30 - 100 °C
Media temperature (peak)–25 °C, non-freezing
120 °C for 5 minutes, up to 3 weeks in sensor lifetime
Ambient air temperature (operation)
–25 - 60 °C
Ambient air temperature (peak) –55 - 90 °C
Humidity 0 - 95 % RH, non-condensing
System burst pressure > 16 bar
Electrical data
Power supply5 VDC (± 5 %). Grounding of the sensor
supply is required (PELV)
Output signals Ratiometric
Flow signal 0.5 - 3.5 V (Zero at 0.35 V)
Temperature signal 0.5 - 3.5 V
Power consumption < 50 mW
Load impedance > 10 kΩ
Sensor materials
Sensing element Silicon-based MEMS sensor
Seal (sensor to housing) EPDM rubber
Vortex tube 1.4408
Insert PPA 40-GF
Wetted materialsCorrosion-resistant coating, EPDM,
PPS, PPA 40-GF, 1.4408
Environmental standards
Enclosure class IP44 (Non overmoulded IP20)
Temperature cycling IEC 68-2-14
Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h
Electromagnetic compatibility EN 61326-1
Dimensions
Sensing element 47 x 40 x 20 mm, see drawings
Vortex tube 137 x 45 x 41 mm
Insert 104.2 x 30.4 x 28.9 mm
25
Pro
du
ct ra
ng
e
26
Grundfos Direct Sensors™4
4. Product range
VFI sensorScope of delivery:
• Sensor tube with sensor
• flanges (only for flange versions)
• union nuts (for threaded versions)
• 5 m cable with M12 connection in one end
• quick guide.
Complete product Flow rangePipe size
O-ring Connection typeProduct numberEPDM FKM
Cast iron flange
Stainless steel flange
Thread
VFI-··0.3-6m-1-C-M5.000X-FG6-SG-30F-A··1
0.3-6 m3/h DN 18
97686127
VFI-··0.3-6m-1-C-M5.000X-FG6-SG-30F-A··1 97686128
VFI-··0.3-6m-1-C-M5.000X-EG6-SS-30F-A··1 97688293
VFI-··0.3-6m-1-C-M5.000X-FG6-SS-30F-A··1 97688294
VFI- 0.3-6m-1-C-M5.000X-EG6-SS-07P-A 1 97688334
VFI-··0.3-6m-1-C-M5.000X-FG6-SS-07P-A··1 97688342
VFI-·0.6-12m-1-C-M5.000X-EG6-SG-30F-A··1
0.6-12 m3/h DN 25
97686129
VFI-·0.6-12m-1-C-M5.000X-FG6-SG-30F-A··1 97686130
VFI-·0.6-12m-1-C-M5.000X-EG6-SS-30F-A··1 97688295
VFI-·0.6-12m-1-C-M5.000X-FG6-SS-30F-A··1 97688296
VFI-·0.6-12m-1-C-M5.000X-EG6-SS-07P-A··1 97688335
VFI-·0.6-12m-1-C-M5.000X-FG6-SS-07P-A··1 97688343
VFI-·1.3-25m-1-C-M5.000X-EG6-SG-30F-A··1
1.3-25 m3/h DN 32
97686141
VFI-·1.3-25m-1-C-M5.000X-FG6-SG-30F-A··1 97686142
VFI-·1.3-25m-1-C-M5.000X-EG6-SS-30F-A··1 97688297
VFI-·1.3-25m-1-C-M5.000X-FG6-SG-30F-A··1 97688298
VFI-·1.3-25m-1-C-M5.000X-EG6-SS-09P-A··1 97688336
VFI-·1.3-25m-1-C-M5.000X-FG6-SS-09P-A··1 97688344
VFI-···2-40m-1-C-M5.000X-EG6-SG-31F-A··1
2-40 m3/h DN 40
97686143
VFI-···2-40m-1-C-M5.000X-FG6-SG-31F-A··1 97686144
VFI-···2-40m-1-C-M5.000X-EG6-SS-31F-A··1 97688299
VFI-···2-40m-1-C-M5.000X-FG6-SS-31F-A··1 97688300
VFI-·3.2-64m-1-C-M5.000X-EG6-SG-32F-A··1
2-64 m3/h DN 50
97686145
VFI-·3.2-64m-1-C-M5.000X-FG6-SG-32F-A··1 97686146
VFI-·3.2-64m-1-C-M5.000X-EG6-SS-32F-A··1 97688301
VFI-·3.2-64m-1-C-M5.000X-FG6-SS-32F-A··1 97688302
VFI-5.2-104m-1-C-M5.000X-EG6-SG-33F-A··1
5.2-104 m3/h DN 65
97686147
VFI-5.2-104m-1-C-M5.000X-FG6-SG-33F-A··1 97686148
VFI-5.2-104m-1-C-M5.000X-EG6-SS-33F-A··1 97688303
VFI-5.2-104m-1-C-M5.000X-FG6-SS-33F-A··1 97688304
VFI-··8-160m-1-C-M5.000X-EG6-SG-35F-A··1
8-160 m3/h DN 80
97686149
VFI-··8-160m-1-C-M5.000X-FG6-SG-35F-A··1 97686150
VFI-··8-160m-1-C-M5.000X-EG6-SS-35F-A··1 97688305
VFI-··8-160m-1-C-M5.000X-FG6-SS-35F-A··1 97688306
VFI-·12-240m-1-C-M5.000X-EG6-SG-37F-A··1
12-240 m3/h DN 100
97686151
VFI-·12-240m-1-C-M5.000X-FG6-SG-37F-A··1 97686152
VFI-·12-240m-1-C-M5.000X-EG6-SS-37F-A··1 97688308
VFI-·12-240m-1-C-M5.000X-FG6-SS-37F-A··1 97688309
Pro
du
ct
ran
ge
Grundfos Direct Sensors™ 4
VFS sensor
Sensor selectionGrundfos offers a wide range of custom-built variants of the VFS sensorthat can be customized to meet individual requirements.
Due to the large variation of VFS sensors, all VFS sensors cannot be listed in one table. Therefore, the tables below give a point of selection to choose from. Be aware that not all combinations are possible. Therefore, if you have any questions regarding selection, please contact Grundfos Sensors.
Example of a type key:
VFS -·20-400L-1-D-C1.200E-·G4-CS-25P-W··1
1. Product group
2. Product range and units:
3. Generation:
4. Electrical output type:
5. Cable and connectors:
– Middle letters: 1.200 is cable length in m
– First and last letters: Cable connector
6. Sealing material and enclosure class
– Material:The first letter represents the flow pipe, the second represents the mechanical connection part.
7. Dimension of mechanical connection
8. Mechanical connection type
9. Packaging
1 2 3 4 5 6 7 8 9 10
VFS 20 - 400 L 1 D C1.200E G4 CS 25 P W··1
Product range Range of unit
20-400 L: litres/min.
Code Generation
1 1st generation
2 2nd generation
3 3rd generation
Code Output
B 0-10 V
C 4-20 mA, 2 wires
D 0.5-3.5 V
E 0.5-4.5 V
F 2 x 0-10 V
G 4-20 mA, 3 wires
Code Cable connector description
B FCI 90312-004LF/77138-101
C CKM 42010107/42010311, tin plated
D AMP 103648-3/104479-9
E Molex 51004-0400/50011-8000
F AMP 172167-1/0-170365-1
G Tyco Val-U-Lok 794954-4/794958-2, gold plated
J JST XHP-4/SXH-001T-P0.6
L Lumberg 3510-04 K02
N Lumberg 3510-04 K03
PMolex 43025-0400/43030-0005, 43030-001/ Cembre 1910M16
Q Molex 43025-0400/43030-0006
R Molex 51004-0400/50011-8000/ Cembre 1900M12
X Open ended
Code Sealing description
E EPDM (drinking water approved)
F FPM (for use in oily media)
G Gel-filled
Code Enclosure class
2 IP20
4 IP44
5 IP55
6 IP67
Code Material description
B Brass
C Composite
G Cast iron
Q Stainless steel flow pipe with composite insert (QT)
S Stainless steel
Code Dimension Code Dimension
03 G ½" 17 7/16"
04 G ¾" 19 18.75mm
05 G1" 21 21.5mm
06 6mm 24 1/8 - 27
07 G 1¼" 25 3/4 - 14
08 8mm 26 1 - 11.5
09 G 1½" 27 1 ¼ - 11.5
10 G 1½" 51 f1" - G ¾
11 G 2½" 52 f1¼" - G 1
12 G 3" 63 G ½ with ventilation opening
13 G4"
Code Description
B BSPT (ISO 7/1)
C Compression
F Flange
G Flange and BSPP (ISO 228/1)
K Clips
M NPSM
N NPT
P BSPP (ISO 228/1)
S Sweat
T Tube
U UNF
Code Description of packaging
A Set with pre-assembled components
P Spare parts set
S Set
V Service set
W Blister pack, standard Grundfos cardboard
N Blister pack, white cardboard
1 1 piece
10 Bulk 10
25 Bulk 25
50 Bulk 50
100 Bulk 100
500 Bulk 500
27
Ac
ce
ss
orie
s
28
Grundfos Direct Sensors™5
5. Accessories
Sensor interface, type SI 001 PSUSI 001 PSU from Grundfos Direct Sensors™ is an external power supply for Grundfos sensors and other transmitters with 24 VDC supply voltage.
The power supply is to be used where the distance between the transmitter and the controller exceeds 30 m.
Fig. 83 Sensor interface, SI 001 PSU
Specification:
• Voltage range: 110-400 VAC
• frequency range: 50-60 Hz
• ambient temperature: -20 to +50°C
• enclosure class: IP54.
Sensor interface, type SI 010 CNVSI 010 CNV from Grundfos Direct Sensors™ is an external power supply, signal amplifier and signal converter for Grundfos sensors.
SI 010 CNV has built-in precision resistors enabling the transmitter to give 4-20 mA, 1-5 V and 2-10 V output signals.
SI 010 CNV should be used in applications where sensors from the standard product range are used, but the controller requires a 4-20 mA input signal.
Fig. 84 Sensor interface, SI 010 CNV
Specification:
• Voltage range: 115-230 VAC± 10% or 24 VDC
• frequency range: 50-60 Hz
• power consumption: Max. 2.5 W
• ambient temperature: -20 to +50°C
• enclosure class: IP20.
TM
04
41
94
08
09
Part Product No.
Sensor interface, SI 001 PSU 96915820
TM
04
48
82
22
09
Part Product No.
Sensor interface, SI 010 CNV 96983684
Ap
pe
nd
ix
Grundfos Direct Sensors™ 6
6. Appendix
Installation of VFI sensor
TM
05
23
06
48
11
min. 10 x D 1 min. 5 x D 1
D
0 bar
min. 20 x D 1 -0,05 bar (0.725 PSI)
D
-30 to 120 °C (-22 to 248 °F)
-25 to 60 °C(-13 to 140 °F)
Max. 28 bar(406 PSI) IP67
29
Ap
pe
nd
ix
30
Grundfos Direct Sensors™6
Minimum flow rate
Minimum flow rate as a function of the kinematic viscosity
The minimum detectable flow rate (Qmin.) for the VFI sensors depends on the kinematic viscosity of the liquid. The chart below shows Qmin as a function of the kinematic viscosity.
*Reference condition:
- Liquids at 20 °C, 1013 mbar, ρ = 998 kg/m3, v = 1 x 10-6 m2/s.
TM
04
80
01
27
10
0.1 1 100.4
0.9
1.3
1.8
2.2
2.63.13.54.0
9
13
18
22
26313539
4.5
44
88
132
176
220
GPM
Kinematic Viscosity [cSt]
DN100
DN80
DN65
DN50
DN40
DN32
DN25
DN18
*
Ap
pe
nd
ix
Grundfos Direct Sensors™ 6
Pressure drop curves
Reference condition:
- Liquids at 20 °C, 1013 mbar, ρ = 998 kg/m3, v = 1 x 10-6 m2/s.
TM
04
93
90
43
10
00.30.3 0.4 0.6 0.8 11 1.2 1.5 2 3 4 5 6 8 1010 12 15 20 30 40 50 60 80 100100 150 200 300Q [m³/h]
0.01
0.02
0.03
0.04
0.050.06
0.08
0.10.1
0.2
0.3
0.4
0.50.6
0.8
1.001.00
2.00
3.00
4.00
5.006.00
[psi]p
1010 20 30 40 50 60 80 100100 200 300 400 Q [US GPM]
DN100
DN18
DN25
DN32
DN40 DN50DN65
DN80
31
Fu
rthe
r pro
du
ct d
oc
um
en
tatio
n
32
Grundfos Direct Sensors™7
7. Further product documentation
WebCAPSWebCAPS is a Web-based Computer Aided Product Selection program available on www.grundfos.com.
WebCAPS contains detailed information on more than 185,000 Grundfos products in more than 20 languages.
In WebCAPS, all information is divided into 6 sections:
• Catalogue
• Literature
• Service
• Sizing
• Replacement
• CAD drawings.
Catalogue
This section is based on fields of application and pump types, and contains
• technical data• curves (QH, Eta, P1, P2, etc.) which can be adapted to the
density and viscosity of the pumped liquid and show the number of pumps in operation
• product photos• dimensional drawings• wiring diagrams• quotation texts, etc.
Literature
In this section you can access all the latest documents of a given pump, such as
• data booklets• installation and operating instructions• service documentation, such as Service kit catalogue and
Service kit instructions• quick guides• product brochures.
Service
This section contains an easy-to-use interactive service catalogue. Here you can find and identify service parts of both
existing and discontinued Grundfos pumps.Furthermore, this section contains service videos showing you
how to replace service parts.
Fu
rth
er
pro
du
ct
do
cu
me
nta
tio
n
Grundfos Direct Sensors™ 7
WinCAPS
Fig. 85 WinCAPS CD-ROM
WinCAPS is a Windows-based Computer Aided Product Selection program containing detailed information on more than 185,000 Grundfos products in more than 20 languages.
The program contains the same features and functions as WebCAPS, but is an ideal solution if no Internet connection is available.
WinCAPS is available on CD-ROM and updated once a year.
Sizing
This section is based on different fields of application and installation examples, and gives easy step-by-step instructions in
how to• select the most suitable and efficient pump for your installation• carry out advanced calculations based on energy
consumption, payback periods, load profiles, life cycle costs, etc.
• analyse your selected pump via the built-in life cycle cost tool• determine the flow velocity in wastewater applications, etc.
Replacement
In this section you find a guide to selecting and comparing replacement data of an installed pump in order to replace the
pump with a more efficient Grundfos pump. The section contains replacement data of a wide range of pumps
produced by other manufacturers than Grundfos.
Based on an easy step-by-step guide, you can compare Grundfos pumps with the one you have installed on your site.
When you have specified the installed pump, the guide will suggest a number of Grundfos pumps which can improve both
comfort and efficiency.
CAD drawings
In this section it is possible to download 2-dimensional (2D) and 3-dimensional (3D) CAD drawings of most Grundfos pumps.
These formats are available in WebCAPS:
2-dimensional drawings:• .dxf, wireframe drawings• .dwg, wireframe drawings.
3-dimensional drawings:• .dwg, wireframe drawings (without surfaces)• .stp, solid drawings (with surfaces)• .eprt, E-drawings.
0 1
33
GRUNDFOS A/S . DK-8850 Bjerringbro . DenmarkTelephone: +45 87 50 14 00www.grundfos.com
The name Grundfos, the Grundfos logo, and the payoff Be–Think–Innovate are registrated trademarks owned by Grundfos Management A/S or Grundfos A/S, Denmark. All rights reserved worldwide.
Being responsible is our foundationThinking ahead makes it possible
Innovation is the essence
97790189 0912 GBRepl.