Group 8 hvdc

39
Simulation of VSC HVDC Transmission System and Fault Analysis DEPARTMENT OF EEE, NATIONAL INSTITUTE OF TECHNOLOGY TIRUCHIRAPPALLI-620015

Transcript of Group 8 hvdc

Page 1: Group  8 hvdc

Simulation of VSC HVDC Transmission System and Fault

Analysis

DEPARTMENT OF EEE,

NATIONAL INSTITUTE OF TECHNOLOGY

TIRUCHIRAPPALLI -620015

Page 2: Group  8 hvdc

Project MembersAaron Saldanha 107111002

Akam Singh Patel 107111011

Mahesh Bolavakar 107111026

John D. Cheerotha 107111038

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 2

Page 3: Group  8 hvdc

Project Aim

Simulation of VSC based HVDC line in MATLAB / SIMULINK

Simulation and Analysis of various DC Fault Condition

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 3

Page 4: Group  8 hvdc

This project aims at the implementation of VSC based HVDC systems, which will help bidirectional power flow along with stable operation of the system during disturbances like Faults.

A PWM control system has been designed for the sending-end of the HVDC link.

The control strategy is studied and corresponding performance is observed in MATLAB/ SIMULINK.

The simulation results verify that the PWM controller has good transient and steady state performance.

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 4

Page 5: Group  8 hvdc

What is HVDC …?

1. A high-voltage, direct current (HVDC) electric power transmission system uses direct current for the bulk transmission of electrical power, in contrast with the more common alternating current (AC) systems.

2. For long-distance transmission, HVDC systems may be less expensive and suffer lower electrical losses.

3. For underwater power cables, HVDC avoids the heavy currents required to charge and discharge the cable capacitance each cycle.

4. For shorter distances, the higher cost of DC conversion equipment compared to an AC system may still be warranted, due to other benefits of direct current links.

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 5

Page 6: Group  8 hvdc

Types of HVDC ConvertersLine Commutated Converter (LCC)

− Current Sourced Converter

− Thyristor based Technology

Voltage Sourced Converter (VSC)

− Self Commutated Converter

− Transistor (IGBT, GTO etc.) based Technology

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 6

Page 7: Group  8 hvdc

LCC v/s VSC

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 7

Page 8: Group  8 hvdc

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 8

Page 9: Group  8 hvdc

Why VSC over LCC….?LCC VSC

Use semiconductors which can

turn on by control action

Use semiconductors which can

turn on or off by control action

Requires stronger AC systems Operates into weaker AC

systems

Requires additional equipment

for “Black” start capability

“Black” start capability

Generates harmonic distortion,

AC & DC harmonic filters

required

Insignificant level of harmonic

generation, hence no filters

required

Coarser reactive power control Finer reactive power control

Large site area, dominated by

harmonic filters

Compact site area, 50 – 60% of

LCC site area

Power is reversed by changing

polarity of the converters

Power is reversed by changing

direction of current flow

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 9

Page 10: Group  8 hvdc

What is VSC HVDC System…?VSC-HVDC is a new dc transmission system technology. It is based on the voltage source converter, where the valves are built by IGBTs and PWM is used to create the desired voltage waveform. With PWM, it is possible to create any waveform (up to a certain limit set by the switching frequency), any phase angle and magnitude of the fundamental component. Changes in waveform, phase angle and magnitude can be made by changing the PWM pattern, which can be done almost instantaneously. Thus, the voltage source converter can be considered as a controllable voltage source.

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 10

Page 11: Group  8 hvdc

Components of VSC - HVDC

a. Physical Structure

b. Converters

c. Transformer

d. Phase Reactors

e. AC Filters

f. DC Capacitors

g. DC Cables

h. IGBT Valves

i. AC Grid

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 11

Page 12: Group  8 hvdc

Layout of Project

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 12

Page 13: Group  8 hvdc

HVDC allows power transmission between unsynchronized AC transmission systems.

Since the power flow through an HVDC link can be controlled independently of the phase angle between source and load, it can stabilize a network against disturbances due to rapid changes in power.

HVDC also allows transfer of power between grid systems running at different frequencies, such as 50 Hz and 60 Hz. This improves the stability and economy of each grid, by allowing exchange of power between incompatible networks.

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 13

Page 14: Group  8 hvdc

HVDC can transfer power between separate AC networks. HVDC power flow between separate AC systems can be automatically controlled to support either network during transient conditions, but without the risk that a major power system collapse in one network will lead to a collapse in the second.

HVDC improves on system controllability, with at least one HVDC link embedded in an AC grid in the deregulated environment, the controllability feature is particularly useful where control of energy trading is needed.

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 14

Page 15: Group  8 hvdc

Part 1 : Three Phase Sinusoidal PWM Rectifier

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 15

Page 16: Group  8 hvdc

Supply Voltage data Output of Three Phase Source (Vp-ground) =325kV (AC)

Output of Three Phase Source (Vp line to line) = 3X (Vp-ground)

=563kV (AC)

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 16

Page 17: Group  8 hvdc

Supply Voltage (Phase Voltage)

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 17

Page 18: Group  8 hvdc

Three Phase Rectifier Unit

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 18

Page 19: Group  8 hvdc

Calculations for RectifierInput voltage to the Rectifier (Vp - AC) = 325kV (AC)

Vout = (3 3 × Vp)/π

= 1.654*Vin

= 537.5kV (DC)

This is the Theoretical value.

Output voltage of the Rectifier (Vdc) = 503kV (DC)

This is the Experimental Value.

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 19

Page 20: Group  8 hvdc

Output of Rectifier (SIMULINK)

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 20

Page 21: Group  8 hvdc

VDC (approx. 500kV)

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 21

Page 22: Group  8 hvdc

IDC (approx. 4.325kA)

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 22

Page 23: Group  8 hvdc

PDC (approx. 2175MW)

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 23

Page 24: Group  8 hvdc

Pulse Sequence Generation

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 24

Page 25: Group  8 hvdc

Part 2: Three Phase Inverter

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 25

Page 26: Group  8 hvdc

Calculations for InverterInput voltage to the Inverter (Vdc) = 537.5kV

Peak value of output line voltage = 1.10266*Vdc

= (4 × Vp × cos(π/6))/π

= 592.6kV (AC Line-Line)

= 592.6kV/√3

= 342.13kV (AC Line-Ground)

This is the Theoretical value.

Output voltage of the Inverter = 580kV (AC Line-Line)

= 334.8kV (AC Line-Ground)

This is the Experimental Value .

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 26

Page 27: Group  8 hvdc

Output of Inverter

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 27

Page 28: Group  8 hvdc

Three Phase AC output

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 28

Page 29: Group  8 hvdc

Line-Line AC (approx. 580kV)

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 29

Page 30: Group  8 hvdc

Line-Ground AC (approx. 320kV)

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 30

Page 31: Group  8 hvdc

AC Filter cum Load

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 31

Page 32: Group  8 hvdc

DC Faults

The DC Link in subjected to fault at t=0.2 at the mid point of the link.

1) Short Duration Faults . Time Period ≤0.2s

2) Medium Duration Faults. Time Period 0.2 ≤ 0.6s

3) Long Duration Faults . Time Period ≈ 1s

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 32

Page 33: Group  8 hvdc

a) Short Duration Fault

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 33

Page 34: Group  8 hvdc

b) Medium Duration Fault

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 34

Page 35: Group  8 hvdc

c) Long Duration Fault

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 35

Page 36: Group  8 hvdc

AdvantagesA long distance point to point HVDC transmission scheme generally has lower overall investment cost and lower losses than an equivalent AC transmission scheme.

HVDC conversion equipment at the terminal stations is costly, but the total DC transmission line costs over long distances are lower than AC line of the same distance.

HVDC requires less conductor per unit distance than an AC line, as there is no need to support three phases and there is no skin effect.

HVDC transmission losses are quoted as about 3.5% per 1,000 km, which is less than typical AC transmission losses.

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 36

Page 37: Group  8 hvdc

Applicationsa) Endpoint-to-endpoint long-haul bulk power transmission, usually to connect a remote generating

plant to the main grid.

b) Increasing the capacity of an existing power grid in situations where additional wires are difficult or expensive to install.

c) Power transmission and stabilization between unsynchronized AC networks, with the extreme example being an ability to transfer power between countries that use AC at different frequencies. Since such transfer can occur in either direction, it increases the stability of both networks by allowing them to draw on each other in emergencies and failures.

d) Stabilizing a predominantly AC power-grid, without increasing fault levels.

e) Integration of renewable resources such as wind into the main transmission grid. HVDC overhead lines for onshore wind integration projects and HVDC cables for offshore projects have been proposed in North America and Europe for both technical and economic reasons. DC grids with multiple voltage-source converters (VSCs) are one of the technical solutions for pooling offshore wind energy and transmitting it to load centers located far away onshore.

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 37

Page 38: Group  8 hvdc

Conclusion

This project work dealt with the theoretical concepts of the PWM controller scheme implemented in the simulation of VSC based HVDC system with fault analysis.

The controller has been developed and then implemented in MATLAB in order to trigger the VSC. The model used in MATLAB/SIMULINK consists of 6-pulse IGBT VSC based HVDC system. The performance of the system under normal condition and under different types of faults is comprehensively analyzed.

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 38

Page 39: Group  8 hvdc

Thank You…!!

GROUP 8 ,B.TECH. FINAL YR. , NIT TRICHY 39