1 Modified_103007 GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED POWER-DISTRIBUTION SYSTEMS WITH ADJUSTABLE-SPEED DRIVES

Transcript of GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED...

Page 1: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

1

Modified_103007

GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED

POWER-DISTRIBUTION SYSTEMS WITH

ADJUSTABLE-SPEED DRIVES

Page 2: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

2

Modified_103007

TWO BASIC PROBLEMS

1.  Prevent nuisance or false trips because of noise on loads or feeders without an ASD.

2.  Reliably detect a ground fault on an ASD-driven motor load.

Page 3: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

3

Modified_103007

SOME BACKGROUND

Page 4: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

4

Modified_103007

SENSING GROUND FAULTS on a grounded electrical system

THE BEST WAY TO DETECT A GROUND FAULT: •  CURRENT SENSING

- usually with a zero-sequence core-balance current transformer (CT or ZSCT) - permits selective coordination and ease of finding a fault

Page 5: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

5

Modified_103007

Q: What is a Core-Balance Zero-Sequence CT?

Answer: Any window-type current transformer is a core-balance zero-sequence CT when all current-carrying conductors are passed through the CT window. Specialized CT’s for low-level fault detection are available (EFCT-x, SE-CS30-x).

Page 6: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

6

Modified_103007

LIMITING PHYSICAL FACTORS

LOW-LEVEL GROUND-FAULT DETECTION: PHYSICAL LIMITING FACTORS

1.) System Capacitance

2.) Unbalanced 1-Phase Loads

3.) Current-Sensor Limitations

4.) Harmonic Components

1, 2, & 4 result in current flowing to earth in an unfaulted system. 3 can result in incorrect indication of a ground fault.

Page 7: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

7

Modified_103007

SYSTEM CAPACITANCE

All electrical systems have phase-to-ground capacitance •  distributed throughout the system •  modeled here as “lumped” values in a simple single-load system

Capacitor—Noun: A device used to store an electric charge, consisting of one or more pairs of conductors separated by an insulator.

Page 8: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

8

Modified_103007

CHARGING CURRENT

Definition of charging current: The current that flows when one phase of an ungrounded system is shorted to ground

1 2

Note: A core-balance CT at “1” will measure charging current A core-balance CT at “2” will measure zero

Page 9: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

9

Modified_103007

CHARGING CURRENT & SYMPATHETIC OPERATION

A core-balance CT on an unfaulted feeder will detect its feeder’s charging current when a ground fault occurs on another feeder. •  To avoid sympathetic tripping (alarming), protection must be set above the charging current level •  Protection level can be set below charging current if sympathetic tripping (alarming) is acceptable •  Charging current does not flow to the system neutral

A4

A4 READS IZ

Page 10: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

10

Modified_103007

CAPACITANCE UNBALANCE

51G

Balanced Phase-to-Ground Capacitance: Xa=Xb=Xc •  Phase capacitive currents are equal •  Core-balance CT reads zero.

Unbalanced Phase-to-Ground Capacitance: Xa≠Xb≠Xc •  Phase capacitive currents are not equal •  Core-balance CT reads a finite value

Page 11: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

11

Modified_103007

VOLTAGE UNBALANCE

Voltage Unbalance, Van≠Vbn≠Vcn: •  May be the result of unbalanced single-phase utility loads

Voltage unbalance combined with capacitance unbalance forces capacitive current unbalance resulting in steady-state zero-sequence current.

These affects are usually small, but may affect low-level earth-fault current detection

Page 12: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

12

Modified_103007

UNBALANCED LOAD CURRENTS

Do unbalanced load currents cause ground-fault trips?

No. If there is no leakage to ground, unbalanced load currents add to zero, therefore no core-balance CT output.

Ia + Ib + Ic = 0 Balanced or Unbalanced

51G

Page 13: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

13

Modified_103007

CURRENT TRANSFORMERS

Practical Current-Transformer Considerations: •  Excitation Current

•  minimum primary current that will give an output. •  can require specialized ZSCT.

•  Saturation •  output current not proportional to large primary current (high-level fault)

•  Local Saturation

•  output with no zero-sequence current •  surge currents and poor conductor placement •  correct with proper conductor location and flux conditioner

Page 14: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

14

Modified_103007

HARMONIC FREQUENCIES

•  Often result from use of Adjustable-Speed Drives and Solid-State Starters •  ASD’s build waveforms in a series of steps. Each step includes harmonic frequencies.

Phase Conductor

Earth

XC fC21XCπ

=

Capacitive impedance (XC) decreases at higher frequencies •  Current per volt increases at higher frequencies •  The affect of capacitive and voltage unbalance are greater at higher frequencies…current flowing to ground, with no fault present

Where C=capacitance f=frequency

Page 15: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

15

Modified_103007

Building a Sine Wave

DC Voltage is switched on and off

Resulting AC current is a “noisy” sine wave.

A real example

Page 16: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

16

Modified_103007

TRIPLEN HARMONICS: A Special Case

In 3-phase systems third-order harmonics are in-phase •  their values add; they do not cancel

+ +

= Can cause nuisance ground-fault tripping

Example: Fundamental & 3rd harmonic

Page 17: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

17

Modified_103007

Harmonic Currents

Harmonic currents can flow to earth through system capacitance and cause nuisance earth-fault tripping

Solution: •  set ground-fault pickup level above harmonic current “background” level, or •  filter the harmonics with a protective device that responds only to the fundamental frequency

Triplen harmonics are detected by core-balance current transformers because they don’t cancel

Page 18: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

18

Modified_103007

Required Filter Characteristics

Filtering Requirements: •  Respond to the fundamental frequency to detect true zero-sequence ground-fault current •  Do not respond to dc-offset caused by starting motors •  Do not respond to harmonic-frequency components

∑−

=⎟⎠

⎞⎜⎝

⎛ π×=

1m

0n mn2sin)n(I

m2Ip

The Discrete Fourier Transform has these characteristics

Page 19: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

19

Modified_103007

Example of 50-Hz Fundamental with 150-Hz Component

-2

-1.5

-1

-0.5

0

0.5

1

1.5

2

0 4 8 12 16 20

Time (ms)

Ampe

res

50 Hz Component 150 HzComponent EF Current Waveform Samples

Sampler is set to take a known number of samples per 50 Hz cycle (here 20 samples/cycle)

150 Hz

2-component Signal

50 Hz

Sample

Page 20: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

20

Modified_103007

DFT Measures the Desired Frequency

SampleNumber

(n)

50 HzComp.

If (n)

150 HzComp.

SampledValue

I(n)If (n)sin(2*pi*n/20) I(n)sin(2*pi*n/20)

0 0.000 0.000 0.000 0.000 0.0001 0.437 0.381 0.818 0.135 0.2532 0.831 0.448 1.280 0.489 0.7523 1.144 0.146 1.290 0.926 1.0434 1.345 -0.277 1.068 1.279 1.0165 1.414 -0.471 0.943 1.414 0.9436 1.345 -0.277 1.068 1.279 1.0167 1.144 0.146 1.290 0.926 1.0438 0.831 0.448 1.280 0.489 0.7529 0.437 0.381 0.818 0.135 0.25310 0.000 0.000 0.000 0.000 0.00011 -0.437 -0.381 -0.818 0.135 0.25312 -0.831 -0.448 -1.280 0.489 0.75213 -1.144 -0.146 -1.290 0.926 1.04314 -1.345 0.277 -1.068 1.279 1.01615 -1.414 0.471 -0.943 1.414 0.94316 -1.345 0.277 -1.068 1.279 1.01617 -1.144 -0.146 -1.290 0.926 1.04318 -0.831 -0.448 -1.280 0.489 0.75219 -0.437 -0.381 -0.818 0.135 0.253

14.142 14.142

DFT of 50 Hz component = 14.142

DFT of signal = 14.142

The result for the multiple-frequency signal is the same as the result for the 50 Hz component Only one cycle is required to calculate earth-fault current, and is updated every sample

Page 21: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

21

Modified_103007

A SOLUTION FOR AVOIDING FALSE TRIPS IN HARMONIC-RICH SYSTEMS

Use a ground-fault protection device incorporating sampling technology and DFT processing for: •  DC-offset filtering •  Harmonic filtering •  Speed - one cycle maximum detection time

Examples are: SE-701, SE-704, SE-330, MPU-32, MPS, FPU-32, FPS

Page 22: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

22

Modified_103007

What about detecting a ground fault in a VFD circuit when the VFD is operating outside of 50-60 Hz? Another filtering algorithm is necessary; Peak Detection.

Page 23: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

23

Modified_103007

THE TROUBLE WITH VFD BUILT-IN GROUND-FAULT PROTECTION

MANY LOW-VOLTAGE DRIVES HAVE A FIXED (Non-Adjustable) GROUND-FAULT PROTECTION LEVEL. •  Often presumes a solidly grounded system •  Often a large percentage (eg: 50%) of rated current •  Often not compatible with a high-resistance grounded system

THESE DRIVES REQUIRE SUPPLEMENTAL GROUND-FAULT PROTECTION

Page 24: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

24

Modified_103007

Why is Inability to Detect a GF in an ASD System a Problem?

Page 25: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

25

Modified_103007

Why is Inability to Detect a GF in an ASD System a Problem?

Page 26: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

26

Modified_103007

What Happened Here?

The System: •  Low-voltage •  Variable-speed drive •  5-A neutral-grounding resistor (NGR)

Some type of fault occurred with The Result: •  Melted copper and steel •  Luckily, no fire

Ground was obviously involved

But the ground fault was not detected!

Page 27: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

27

Modified_103007

What Happened Here?

The System: •  Low-voltage •  Variable-speed drive •  5-A neutral-grounding resistor (NGR)

Could the damage be the direct result of the ground fault? No. P = I2R and IGF ≤ 5 A. Furthermore, for 5 A to flow, the fault impedance R must = 0 Ω (so P=0). As fault impedance rises, current decreases and power dissipation at the fault is small.

0

200

400

600

0 10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190

200

Wat

ts

Fault Impedance (Ohms)

Fault Power Dissipation 600-Vll, 5-A NGR

Page 28: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

28

Modified_103007

What Happened Here? A Theory

A phase-to-winding connection became disconnected in the terminal box, but electrical continuity was maintained by (hi-impedance) contact with the grounded terminal-box cover.

VFD

Motor

Iθ = Imotor + 5 A, max

IGF = 5 A max

And the ground fault was not detected

51G > 5 A

This fault wouldn’t cause an overcurrent trip

Page 29: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

29

Modified_103007

THE CHALLENGE IN VFD GROUND-FAULT PROTECTION

CHALLENGE: RELIABLY DETECT A LOW-LEVEL GROUND FAULT ACROSS VFD

OPERATING-FREQUENCY RANGE WITHOUT NUISANCE TRIPS.

WE DID SOME TESTING; …and invented a new product

BIG QUESTION—WHERE TO PUT THE CT? LINE SIDE? LOAD SIDE?

Page 30: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

30

Modified_103007

Littelfuse Startco R&D Lab VFD Ground-Fault Test Setup

We set up a system with an NGR-grounded three-phase supply to a VFD feeding a motor, with a controlled ground fault, protection relays, and instrumentation

Page 31: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

31

Modified_103007

Littelfuse Startco R&D Lab VFD Ground-Fault Test Setup

Page 32: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

32

Modified_103007

Littelfuse Startco R&D Lab VFD Ground-Fault Test Setup

Analog outputs from three SE-701’s were recorded. EFCT-1 Current Transformers were input devices.

Page 33: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

33

Modified_103007

Littelfuse Startco R&D Lab VFD Ground-Fault Test Setup

An adjustable “decade box” was used to simulate a ground fault at various system locations. Digital RMS meters and a power analyzer were used to confirm SE-701 Ground Fault Monitor readings.

Page 34: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

34

Modified_103007

Sample 1: No Ground Fault VFD Phase-Voltage Spectrum: 30 Hz No Filter

VL-G

fC21XCπ

=

Earth

XC

Phase

Page 35: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

35

Modified_103007

Sample 1: No Ground Fault VFD Phase-Voltage Spectrum: 30 Hz 500-Hz Low-Pass Filter

VL-G

Page 36: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

36

Modified_103007

Sample 2: System with a Ground Fault VFD Ground-Fault Spectrum: 60 Hz, 0.3 A No Filter

VL-G

IL-G

IN-G

VN-G

Page 37: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

37

Modified_103007

60 Hz Sample with 500-Hz Low-Pass Filter

VL-G

IL-G

IN-G

VN-G

Sample 2: System with a Ground Fault VFD Ground-Fault Spectrum: 60 Hz, 0.3 A 500-Hz Low-Pass Filter

Page 38: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

38

Modified_103007

Sample 3: System with a Ground Fault VFD Ground-Fault Spectrum: 10 Hz, 1 A No Filter

VL-G

IL-G

IN-G

VN-G

Page 39: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

39

Modified_103007

VL-G

IL-G

IN-G

VN-G

10 Hz Sample with 500-Hz Low-Pass Filter

Sample 3: System with a Ground Fault VFD Ground-Fault Spectrum: 10 Hz, 1 A 500-Hz Low-Pass Filter

Page 40: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

40

Modified_103007

SE-70x Monitors Have a Filter-Selector Switch

SE-701 top view

Page 41: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

41

Modified_103007

SE-70x Filter Characteristics

Frequency (Hz)

Filte

r Out

put

SE-70X Frequency ResponseVariable Frequency ⎯ Peak Detection

10 20 30 40 50 6070 100 200 300 400500 700 10000

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1.1

1.2

Frequency (Hz)

Filte

r Out

put

SE-70X Frequency ResponseFixed Frequency ⎯ 50/60 Hz DFT

10 20 30 40 50 60 7080 100 200 300 400 5000

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1.1

1.2

Peak-Detection Filter (labeled as Variable Frequency)

DFT Filter (labeled as Fixed Frequency)

Page 42: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

42

Modified_103007

What about CT Location?

A Littelfuse Startco Ground-Fault Monitor can be installed upstream of the drive.

REALLY??

Page 43: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

43

Modified_103007

Yes. Really.

A VFD DOES NOT ISOLATE THE LOAD FROM THE SUPPLY

Drive Frequency (Hz)

Fault Current (mA) (No Filter)

NGR Current (mA)

SE-701 Filter Selection

Upstream SE-701

Downstream SE-701

NGR SE-701

60 316 326 DFT 251 251 243 50 364 375 DFT 260 260 260 40 513 537 DFT 270 270 270 30 735 760 DFT 330 330 300 25 910 945 DFT 340 340 318

Page 44: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

44

Modified_103007

Yes. Really.

A VFD DOES NOT ISOLATE THE LOAD FROM THE SUPPLY Drive Frequency (Hz)

Fault Current (mA) (No Filter)

NGR Current (mA)

SE-701 Filter Selection

Upstream SE-701

Downstream SE-701

NGR SE-701

60 280 295 Peak 264 268 263

50 299 317 Peak 268 265 253

40 353 371 Peak 268 268 258

30 432 453 Peak 260 260 270

20 670 700 Peak 325 312 312

10 1000 1030 Peak 400 400 380

Page 45: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

45

Modified_103007

A VFD Does Not Isolate the Load from the Supply

~ M

Page 46: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

46

Modified_103007

Ground-Fault Pickup Setting Guide

Drive Output Frequency

Nor

mal

ized

Res

pons

eSE-701 Frequency Response

SVX9000 Drive

10 15 20 25 30 35 40 45 50 55 600.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

From the chart, multiply the desired pickup at a frequency by the Normalized Response Value.

Page 47: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

47

Modified_103007

What About a DC-Bus Fault?

Can an AC-sensing relay detect a DC fault?

Page 48: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

48

Modified_103007

How a VFD Makes DC from AC: Start with Full-Wave Rectification

Show four waveforms. 1-phase 60-hz sine, 3-phase 60-hz sine, rectified 1 and 3-phase sine

Single-Phase Sine Wave On Average, the value is 0

Full-Wave Rectified Singe-Phase Sine Wave

On Average, the value is +ve

Page 49: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

49

Modified_103007

How a VFD Makes DC from AC: Start with Full-Wave Rectification, 3θ

Three-Phase Sine Waves On Average, the value is 0

Full-Wave Rectified Three-Phase Sine Waves

On Average, the value is +ve

Page 50: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

50

Modified_103007

DC from AC

DC

AC Ripple

Page 51: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

51

Modified_103007

VFD Negative DC-Bus Fault, 500 mA

VL-G

IL-G

IN-G

VN-G

All of the measurements show the 180-Hz ripple.

Page 52: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

52

Modified_103007

DC Fault Spectrum Analysis

Page 53: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

53

Modified_103007

DC Fault Spectrum Analysis

180 Hz and Harmonics

Page 54: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

54

Modified_103007

ONE SOLUTION FOR TWO PROBLEMS

51G

LOAD 1

LOAD 2

FEEDER 1

FEEDER 2

VFD

51G

SE-701

SE-701

Page 55: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

55

Modified_103007

SOLUTIONS FOR GROUND-FAULT DETECTION in an HRG SYSTEM with ASD’s RUNNING NEAR LINE FREQUENCY

For non-ASD circuits, use a detection device with a narrow band-pass filter

For ASD circuits, use a detection device with a low-pass filter

Frequency (Hz)

Filte

r Out

put

SE-70X Frequency ResponseVariable Frequency ⎯ Peak Detection

10 20 30 40 50 6070 100 200 300 400500 700 10000

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1.1

1.2

Frequency (Hz)

Filte

r Out

put

SE-70X Frequency ResponseFixed Frequency ⎯ 50/60 Hz DFT

10 20 30 40 50 60 7080 100 200 300 400 5000

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1.1

1.2

Page 56: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

56

Modified_103007

SOME ASD’S ARE USED AT VERY LOW SPEEDS…<20 Hz

Frequency (Hz)

Filte

r Out

put

SE-70X Frequency ResponseFixed Frequency ⎯ 50/60 Hz DFT

10 20 30 40 50 60 7080 100 200 300 400 5000

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1.1

1.2

Frequency (Hz)

Filte

r Out

put

SE-70X Frequency ResponseVariable Frequency ⎯ Peak Detection

10 20 30 40 50 6070 100 200 300 400500 700 10000

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1.1

1.2

Page 57: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

57

Modified_103007

SOMETIMES A CONVENTIONAL GROUND-FAULT RELAY WON’T DO

SOMETIMES ACCURATE DC-to-60 Hz MEASUREMENT IS NECESSARY

SOMETIMES ACCURATE HIGH-FREQUENCY MEASUREMENT IS NECESSARY

Page 58: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

58

Modified_103007

SE-70x Filter Characteristics

Frequency (Hz)

Filte

r Out

put

SE-70X Frequency ResponseVariable Frequency ⎯ Peak Detection

10 20 30 40 50 6070 100 200 300 400500 700 10000

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1.1

1.2

Frequency (Hz)Fi

lter O

utpu

t

SE-70X Frequency ResponseFixed Frequency ⎯ 50/60 Hz DFT

10 20 30 40 50 60 7080 100 200 300 400 5000

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1.1

1.2

Peak-Detection Filter (labeled as Variable Frequency)

DFT Filter (labeled as Fixed Frequency)

400 Hz 1000 Hz 90 Hz

Page 59: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

59

Modified_103007

Introducing the EL731

EL731 AC/DC SENSITIVE EARTH-LEAKAGE RELAY

Page 60: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

60

Modified_103007

THERE IS A NEW APPROACH TO WIDE-BAND CURRENT MEAUSUREMENT

AC/DC EARTH-LEAKAGE RELAY

THE EL731 accurately measures ground-fault current in the frequency range of 0 to 6 kHz

•  using ‘conventional’ CT’s

Page 61: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

61

Modified_103007

Benefit #1

§  Provides low frequency to high frequency protection capability with one relay—0 to 6 kHz

Frequency (Hz)

Nor

mal

ized

Res

pons

e

SE-731 Frequency Response

10 20 30 50 70 100 200 300 500 1000 2000 5000 10000 200000

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1.1

CT1CT2

EL731 Frequency Response

Page 62: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

62

Modified_103007

AC/DC EARTH-LEAKAGE RELAY

EFCT-SERIES

CURRENT TRANSFORMER #1 •  CT1 MEASURES 0 TO 100 Hz • 0 Hz = DC •  CT1 IS A STANDARD SENSITIVE EARTH-FAULT CT AND A DCCT •  USED ALONE OR WITH CT2 •  30 T0 5,000 mA SETTING RANGE

Page 63: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

63

Modified_103007

AC/DC EARTH-LEAKAGE RELAY

CURRENT TRANSFORMER #2 •  CT2 MEASURES 20 TO 6,000 Hz •  A STANDARD SENSITIVE EARTH-FAULT CT •  USED ALONE OR WITH CT1 •  30 T0 5,000 mA SETTING RANGE

EFCT-SERIES

Page 64: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

64

Modified_103007

CT1 AND CT2 •  USE ONE OR BOTH •  COMBINED 0 TO 6,000 HZ FREQUENCY RESPONSE

Page 65: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

65

Modified_103007

Benefit #2

§  EFCT series CT used on previous applications can be re-used.

§  Upgrade SE-701 applications.

Page 66: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

66

Modified_103007

Benefit #3

§  Separate Alarm and Trip relay outputs

§  3 programmable Form-C relays

§  Early detection of alarm conditions allows prevention of extended downtime.

Page 67: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

67

Modified_103007

DC Applications

Page 68: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

68

Modified_103007

DC Application

§  Must be grounded DC supply.

Page 69: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

69

Modified_103007

Benefit # 4

§  Feature: Ability to detect DC faults with a CT §  Benefit provides ability to locate the fault on a

grounded-DC system. §  Improves upon previous DC ground-fault

detection methods that would only tell you the system had a fault and possibly which bus was faulted. (SE-601)

Page 70: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

70

Modified_103007

But Wait There’s more

§  A fan cooled motor operated at low speed draws less air over the windings. Less cooling equates to higher winding temperature.

Page 71: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

71

Modified_103007

Feature and Benefit #5

§  The only ground-fault relay on the market with temperature protection.

§  RTD or PTC Thermistor input for temperature measurement and protection. –  Allows measurement of motor, load or drive

temperature. Many drives operate motors at lower speed (less cooling) but most do not offer temperature protection.

Page 72: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

72

Modified_103007

Features and Benefits #6 and #7

§  Communications module available to send info to data network.

§  Flash upgradeable via optional communication adapter. Allows field modification of firmware if ever required.

Page 73: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

73

Modified_103007

Feature and Benefit #8

§  Password Protection §  1st of our ground-fault relays with this feature.

Page 74: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

74

Modified_103007

Features and Benefits #9 and #10

§  Metering on the door. 2-Line OLED display §  Panel-mount adapter not required for door

mounting. §  No PMA-55 or PMA-60 required.

§  Optionally available surface-mount adapter

Page 75: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

75

Modified_103007

Accessories

Page 76: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

76

Modified_103007

EL731 Benefits Reviewed

1.  Full Frequency Coverage 2.  Re-use existing EFCT series CT 3.  Detection and fault location on DC systems 4.  Separate Trip and Alarm Setpoints 5.  Overtemperature Protection 6.  Communications Capable GF relay 7.  Firmware Upgradeable 8.  Password Protected 9.  Panel Mount Ready; optional surface mounting 10.  Metering

Page 77: GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED …/media/protection-relays/presentations/littelfuse... · Harmonic currents can flow to earth through system capacitance and cause

77

Modified_103007

Ground-Fault Protection for VFD’s on High-Resistance-Grounded Systems

SE-701 Ground-Fault Monitor Pickup: 50 mA to ?? A

SE-704 Earth-Leakage Monitor

Pickup: 10 mA to 5 A

Frequency Response: 32 to 86 Hz, 20 to 420 Hz

Frequency Response: 0 to 90 Hz,

20 to 90 Hz, 20 to 3,000 Hz, 190 to 6,000 Hz,

0 to 6,000 Hz

EL731 AC/DC Sensitive Earth-Leakage Relay

Pickup: 30 mA to 5 A