GridBee®
THM Removal Systems
The EPA Stage 2 Disinfectants and Disinfection Byproducts rule with locational maximums for TTHM (80 ug/l) has resulted in compliance pressure for many cities. Mixing alone may not lower the THM concentration enough to comply. For these systems, Medora Corporation has developed an effective and economical floating spray nozzle system for THM removal in tanks and clearwells.
THMs enter the tankwhile it is �lling.
Floating Spray Nozzle THM RemovalSystem picks up the new water as fast as it comes in, and treats it throughthe spray nozzles. The entire tank is mixed thoroughly. The system can be left on year-round, at full speed or reduced speed, to prevent ice damagein cold climates.
Headspace:Two feet minimumoperating height; four feet duringinstallation.
Blower pushes air into tank.
Spray nozzles
THMs
THMs
THMs
THMs
THMs
THMs
THMs THMs THMs THMsTHMs
THMs
THMs
THMs THMsTHMs THMs THMs
THMs THMs
THMs
THMsTHMs
THMs
THMs
THMs
THMs
THMs
THMsTHMs
THMs THMs THMs
THMs
THMs
THMs THMs
THMs
THMsTHMs
THMs
THMs
THMs
THMs
THMs
THMs
THMs THMs
THMs
THMs
THMs
THMs
THMs
THMs
THMs
THMs
THMs
THMs
THMsTHMs
THMsTHMs THMs
THMs
Floating Spray Nozzle THM Removal System
Features and Benefits of the Floating Spray Nozzle THM Removal System• Four machine sizes, 3 hp, 5 hp, 10 hp, and 15 hp provide for scalable systems for clearwells and tanks from
10,000 to 100,000,000 gallons, and tank flow rates up to 100,000,000 gallons per day• There are no significant friction or lifting losses, so 98% of the energy consumed by the pump is converted to
stripping TTHM at the nozzle assembly, compared to less-efficient fixed-ceiling nozzle designs• Patented long-life nozzle and intake treat all incoming water, minimize THM formation downstream• Nozzle angle assures no damage to tank coatings• Ventilation blowers for headspace included with all systems• All models fit through a 24" x 24" or larger hatch opening, eliminating the need to install a new larger hatch
or special lifting equipment• No infrastructure piping is required, and no modifications to the tank or clearwell other than small access
openings for electrical cable and the headspace air ventilation• Factory installation is available for entire system except the wiring by the local electrician• Small-footprint units are easily movable and removable for any future interior tank work• If the TTHM problem changes, this equipment is portable and can easily be moved to another area of town
or sold to another water district• Low-maintenance, long-life design• Two year parts and labor warranty; factory maintenance plans available• Full-scale pilot studies can be provided, with purchase options
Medora Corporation's potable water products are certified to NSF/ANSI Standard 61, and NSF/ANSI 372 for lead-free content. Learn more at www.medoraco.com/std61.
Medora Corporation3225 Hwy 22 • Dickinson, ND 58601
Ph +1 866 437 8076 • www.medoraco.comTHMremoval_20150318 • © 2015 Medora Corporation
Model SN3 Model SN5 Model SN10 Model SN15
Unique Features
Flow through nozzles, MGD 0.25 MGD 0.33 MGD 0.66 MGD 1.0 MGDPossible reduction of TTHM, each
pass through nozzles35% to 70% 35% to 70% 35% to 70% 35% to 70%
Spray pump horsepower and motor electrical options
3HP/230V/1PH/1.15 S.F.3HP/230V/3PH/1.15 S.F.3HP/460V/3PH/1.15 S.F.
5HP/230V/1PH/1.15 S.F.5HP/230V/3PH/1.15 S.F.5HP/460V/3PH/1.15 S.F.
10HP/230V/3PH/1.15 S.F.10HP/460V/3PH/1.15 S.F.
15HP/230V/3PH/1.15 S.F.15HP/460V/3PH/1.15 S.F.
Dimensions
Unit Weight
Hatch size required
Head space required
Water depth required
Machine Diameter
Ventilation Blower (included)
Ventilation Blower horsepowerand motor electrical options
Ventilation blower mounting
Low Energy Tank mixing system
Installation Consdiderations
Electrical requirementsfor the owner to provide
If have power source limitationsa VFD may be recommended
A power source, conduit and NEMA combination starter / disconnect per electrical code to each pump motor, each blower and each low energy mixer as listed in the THM system proposal
Variable frequency drive (VFD) may be desired to providea conversion from
230V/1ph power source to a 230-‐460V/3PH power source
Variable frequency drive (VFD) may be desired to providea conversion from
115V/1ph power source to a 230V/3PH power source or 230V/1ph power source to a 230-‐460V/3PH power source
Little or no infrastructure changes needed, no need to drain the tank, no need for diver(s), factory installation available, tank owner to provide electrical service and connections
GS-‐series submersible mixer(s) may be included in a THM system proposal for mixing due to tank inflow rate, for low energy mixing when the THM system is off, or for ice considerations
Pre-‐designed • Pre-‐packaged • Portable • Reliable • Long Life • No need for diver(s) or to drain the tank • Fits through most standard size hatches Full written specifications available upon request.
Working dimension: 8 ft diameter x 5 ft tall, plus draft hose Working dimension: 10 ft diameter x 6 ft tall, plus draft hose
Typically on top of the tank or clearwell
2HP/230V/1PH/1.15 S.F.2HP/230V/3PH/1.15 S.F.2HP/460V/3PH/1.15 S.F.
Approx. 8 feet Approx. 10 feet
Approx. 60 inches
Approx. 300 lbs Approx. 500 lbs
Minimum 18 inches clear unobstructed diameter Minimum 24 inches clear unobstructed diameter
Minimum 18 inches working height, Minimum 4 feet temporarily during installation
Minimum 24 inches working height, Minimum 4 feet temporarily during installation
2HP/230V/1PH/1.15 S.F.2HP/230V/3PH/1.15 S.F.2HP/460V/3PH/1.15 S.F.
750 CFM 750 CFM per blower (Multiple blowers may be required)
Approx. 54 inches
Specifications
Locally Represented By:
GridBee®
are brands of Medora Corporationand
Photos