Page 1 of 25
Government of India
Bhabha Atomic Research Centre
Nuclear Recycle Board
Tender Document
for
“MANUFACTURING, TESTING & SUPPLY OF 1100V GRADE LT POWER CABLE
FOR NRB, BARC, TARAPUR”
.
Nuclear Recycle Board, BARC, Mumbai - 400094
Page 2 of 25
Index
Sr. No. Description
1 Section A : Tendering and Contract conditions
2
Section B :
Technical Specifications for design, manufacturing, testing and delivery
of 1100V grade LT Power Cable.
3
Section C : Format for submission of tender;
Part- I: (Technical Bid)
Annexure I: Technical format for submission of tender.
Annexure II: Schedule of deviation
Annexure III: Vendor evaluation Form
Annexure IV: Typical QAP for Power cable
Annexure V : Proof of ability of the bidder
Part – II: (Price Bid)
A. Price & Quantities Schedule
B. Manufacturing & Delivery Schedule
Page 3 of 25
Section - A
TENDERING AND CONTRACT CONDITIONS
CONTENTS
Clause No. Details
1 Introduction
2 Location
3 Copies of bids, specifications and drawings
4 Delivery & Execution
5 Information to be included with the proposal
6 Price
7 Deviation from tender specifications
8 Packing shipment & transport
9 Testing, quality surveillance, progress reports and training
10 Guarantee
11 Validity of offers
12 Pre-qualification Criteria
13 Tender Submission requirement
Page 4 of 25
TENDERING AND CONTRACT CONDITIONS
1. INTRODUCTION
This specification covers the design, manufacturing, testing at manufacturer's works and safe
delivery at site, the following cables as specified herein under:
i) 1.1 kV grade, aluminium conductor, XLPE insulated, FRLS PVC ST-2 inner sheathed, GI wire
armored and FRLS PVC ST-2 outer sheathed power cable (A2XWY).
ii) 1.1 kV grade copper conductor, XLPE insulated, FRLS PVC ST-2 inner sheathed, GI wire
armored and FRLS PVC ST-2 outer sheathed Power Cable (2XWY)
The above cables shall be supplied at INRP Stores, BARC, Tarapur as per technical specifications.
2. LOCATION
The site of NRB, BARC, Tarapur, Boisar, Palghar (Dist.), herein referred to as “site”, is located in
the state of Maharashtra.
3. COPIES OF BIDS, SPECIFICATION AND DRAWING
The bidder shall on-line submit the bid together with all supporting information and technical
details.
4. DELIVERY & EXECUTION
The supplier shall submit his plans giving detailed time schedule of work in the form of PERT/ CPM
network covering the various phases involved in the work e.g. procurement of materials, inspection
and testing etc.
The cables specified in this document shall be delivered within 08 months from the date of P.O
5. INFORMATION TO BE INCLUDED WITH THE PROPOSAL
a) The offer without technical literatures, complete technical details (Section-C) of all components
and sub-systems, make, model number, manufacturer, operating instructions, calibration
procedures, circuit diagrams, all drawings and descriptions with troubleshooting, check list,
maintenance tips, technical data sheet with relevant drawings, will be treated as incomplete and
are liable to be rejected.
b) Contractor evaluation Performa
c) Proof of ability (Manufacturing & testing facility, past supplies made and their feedback)
d) Schedule of deviation
e) List of qualified man power and machinery
6. PRICE
Bidders are hereby advised to quote against the offer in compliance with the specification given here
in with deviations separately. Bidders are requested to quote as per the format provided with the
tender.
7. DEVIATION FROM TENDER SPECIFICATIONS
Page 5 of 25
The bidder shall preferably quote for the item, strictly in accordance with the specifications. Should
he require offering deviations in any way from the specification, the deviations shall be clearly and
distinctly listed in his offer.
8. PACKING SHIPMENT & TRANSPORT
8.1 Delivery of materials at site shall be responsibility of the supplier. The supplied items shall be
packed and protected as not to suffer any deterioration, damage or breakage during shipment and
storage in tropical climate.
8.2 The supplier should, at his responsibility check and ascertain the existing rail/road limitation for
transport of the materials from works to site, unloading of materials at site, transport to store, joint
inspection of material by department and supplier, safe storage and prevention during storage. It is
the responsibility of the supplier to insure all the material during transit.
8.3 The supplier shall note that shipment shall be in accordance with the given instructions. Each
package shall be limited to size and weight that are permissible under the existing rail and road
limitations.
8.4 The supplier shall not ship the material without the prior approval of the purchaser's inspector and
subsequent written instruction to do so.
9. TESTING, QUALITY SURVEILLANCE, PROGRESS REPORTS & TRAINING
9.1 The supplier shall give at least 15 days advance notice prior to the commencement of pre-dispatch
testing so that the purchaser's representative can plan to witness the tests. The cables shall be tested
for Type and Routine tests as per latest IS-7098 (part-I) / IS-1554 in presence of representative of
the purchaser at the manufacturer's works.
9.2 Four copies of test reports (in CDs) and one hard copy shall be submitted after receiving the approval
of a preliminary copy from the purchaser.
9.3 Waiving of quality surveillance or acceptance of material or equipment by the quality surveyor shall
not relieve the supplier from the responsibility of furnishing material and workmanship in
accordance with this tender document.
10. GUARANTEE
10.1 All the equipment supplied under this contract shall be guaranteed for satisfactory performance and
against manufacturing and material defects for a period of 12 months from the date of
commissioning or 18 months from the date of delivery.
10.2 Materials damaged in transit or during guarantee period shall be replaced immediately and such
replacement shall also be governed by similar guarantee.
11. VALIDITY OF OFFERS
The quoted prices shall be valid for 120 days from the date of opening the tender.
12. PRE-QUALIFICATION CRITERIA
12.1 Bidder shall have minimum 5 years manufacturing experience for the tendered cables and should
furnish satisfactory feedback reports for the materials supplied by him to reputed clients. In case of
a dealer, an authorization from the OEM shall be submitted.
12.2 Bidder shall have full-fledged extrusion and curing facility for XLPE insulated cables to be offered.
Page 6 of 25
12.3 Bidder shall have IS0-9001/9002 certification for design, manufacturing, QA&QC for the tendered
items.
12.4 Bidder shall have adequate and standardized in-house manufacturing and testing facilities, duly
calibrated/certified from reputed institutions/laboratories, for undertaking the work under this
tender.
12.5 Bidder shall furnish type test reports duly certified from reputed institutions/laboratories like CPRI/
ERDA, for material similar to that covered under the scope of this tender.
12.6 Following documents (self-attested) shall be submitted along with the quotation : -
a) Duly filled up technical data sheet and annexure-I to III of Section-D
b) List of past supplies made
c) Performance feedback report from users
d) Quality Assurance (QA) plan for the tendered item(s)
f) Latest solvency certificate from any scheduled bank for a minimum value of 40% of the
estimated cost.
g) List of plant & machinery and other infrastructure facilities to complete the work in time.
h) Details of manpower.
i) Performance certificates.
j) Proof of average annual turnover of not less than Rs. 5 crores during last three years.
k) Profit and loss statement of last five years confirming that loss has not been incurred for more
than two years in the period of last five years.
Note: Original documents shall be produced for verifications, if required.
13 No end user certificate shall be provided by the purchaser for the tendered work.
14 TENDER SUBMISSION REQUIREMENT
14.1 The tender submission shall show compliance to the specifications and shall include a full set of
descriptive and technical literature on the equipment and system proposed. Necessary catalogues
shall be enclosed. In case Xerox copy of catalogue is submitted, the supplier shall be required to
submit original copy whenever asked by BARC.
14.2 A detailed description of acceptance test procedures and checklist.
Note: The cables shall be supplied on non-returnable steel drums of suitable size, packed and
marked.
Page 7 of 25
SECTION-B
TECHNICAL SPECIFICATIONS FOR DESIGN, MANUFACTURING, TESTING AND
DELIVERY OF 1100V GRADE LT POWER CABLES FOR NRB, BARC, TARAPUR.
Page 8 of 25
TECHNICAL SPECIFICATIONS OF DESIGN, MANUFACTURING, TESTING AND
DELIVERY OF 1100V GRADE LT POWER CABLE
1. SCOPE
This specification covers the design, manufacturing, testing at manufacturer's works and safe delivery
of power cables at NRB, BARC Tarapur store. 2. PROJECT DATA:
The cables specified herewith are required at the following sites for DAE Project.
2.1 NRB Facilities, Tarapur
2.2 The site conditions are as follows:-
2.2.1 Max. Ambient temperature: : 50C
2.2.2 Relative humidity : 97 %
2.2.3 Climatic conditions : Tropically highly humid, heavy rainfall, conducive to rust &
fungus growth, besides being close to Arabian Sea Coast, the
environment is laden with salt spray. The cables shall be
capable of continuous operation at their rated current without
exceeding the specified temperature rise limits while
operating in above conditions.
2.3 Power supply : 415V, 3 phase, 4 wire, grounded system.
2.4 System grounding : Solidly grounded
2.5 System fault level : 35 MVA (50 kA) symmetrical
3. STANDARDS
The cables covered by this specification unless otherwise stated be designed in accordance with the
latest editions/ amendments of the following standards:
S. N. Standard Description of Standard
1 IS 7098 -1988 (Part I) Specification for XLPE insulated PVC sheathed cables.
2 IS 8130-1984 Specification for conductors for insulated electric cables
and flexible cords.
3 IS 8139 Conductor for Electrical cables
4 IS 2182 – 1965 Specification for copper conductors in insulated cables and
chords.
5 IS 5831-1984 Specification for PVC Specification for PVC insulation and sheath of electric
cables.
6 IS-6380-1984 Elastomeric insulation and sheath of electric cables (1984)
7 IS 1554 (Part-I)-1988 Specification for PVC insulated heavy duty electric cable
8 IS 694-1990 Specification for PVC insulated cables for voltages up to
and including 1100V.
9 IS 3961-1968 Specification for Recommended current ratings for cables
10 IS 3975-1988 Specification for mild steel wires, strips and tapes for
armouring cables.
11 IEC332 - 1 Specification for Flammability Test
12 IEC754 - 1 Specification for Acid Gas Generation Test.
13 ASTM-D 2863 Specification for Oxygen Index Test. BICC Handbook
Chap. No.6
Specification for Temperature Index Test.
14 ASTM-D 2843 Specification for Smoke Density Test.
Page 9 of 25
15 ISO-9001/2.
The cable manufacturing company should have been
qualified.
4. SPECIFICATIONS FOR XLPE INSULATED POWER CABLES
Power cable of 1.1 kV grade, multi-stranded Aluminium/ Copper conductor, XLPE insulated, FRLS
PVC type ST2 inner sheathed, GI round wire Armoured, and FRLS PVC ST2 outer sheathed, as per
IS 7098 ( part - 1) 1988.
4.1 REQUIREMENT
S.N. Description of cable Qty.
1.
1.1 kV grade Power cable (A2XWY) of size 3.5C x 400 Sq.mm,
Aluminium conductor, XLPE insulated, FRLS PVC type ST2
inner sheathed, GI round wire Armoured, and FRLS PVC ST2
outer sheathed, as per IS 7098 ( part - 1) 1988.
8000m
2.
1.1kV grade Power cable (2XWY) of size 4C x 10 Sq.mm,
copper conductor, XLPE insulated, FRLS PVC type ST2 inner
sheathed, GI round wire Armoured, and FRLS PVC ST2 outer
sheathed, as per IS 7098 ( part - 1) 1988.
5000m
4.2 DESIGN AND CONSTRUCTION PARTICULARS 4.2.1 Construction
LT cable shall conform to 1100 V Grade stranded & round annealed plain Copper conductor /
Aluminium H2/H4 grade conductors, XLPE insulated, core suitably laid up, inner and outer sheath of
extruded FRLS PVC type ST2 in black colour & GI round wire. The cables shall conform to IS 7098
(part -1) 1988. Adequate insulation shall be provided for the cables to operate continuously at the
specified voltage with a high degree of safety and reliability throughout the life of the cable.
4.2.2 Copper Conductor
The copper conductor shall be of 99.9% electrolytic grade copper & shall be stranded, shaped/
circular in section; smooth, uniform in quality and free from scale, inequalities, spills, splits and other
defects. The conductors shall conform to appropriate dimensions and resistance given in IS 8130
(Part I): 1984. The base metal shall be Electrolytic Grade copper having a minimum purity of 99.9%
(silver being counted as copper) as per IS 2182 - 1965.
4.2.3 Aluminum Conductor
The Aluminium conductor shall be of electrical purity, electrolytic grade H2/H4 aluminium and shall
be stranded shaped/circular in section; smooth, uniform in quality and free from scale, inequalities,
spills, splits and other defects. The conductors shall conform to appropriate dimensions and
resistance given in IS 8130 (Part I): 1984.
4.2.4 Insulation
The insulating material for power cables shall be extruded cross linked polyethylene (XLPE)
compound as per IS-7098(Part-I)-1988. The minimum thickness of insulation shall not be less than
Page 10 of 25
the values specified in Table-2 of IS-7098 (Part-I)-1988. No negative tolerance shall be applicable for
the thickness.
The cores shall be identified by the following colour schedule:
4, 3 &1/2 core : Red, yellow, blue and black, reduced neutral core being black
4.2.5 Inner Sheath
The inner sheath material as applicable shall be extruded FRLS PVC ST-2, compatible with thermal
rating of insulation conforming to IS-6380-1984. The sheath shall have adequate thickness,
mechanical strength and elasticity.
4.2.6 Armoring
The armoring arranged over the inner sheath shall consist of one layer of GI round wire. The armor
wire being put on the cable shall conform to IS 3975-1988 for all requirements. The direction of lay
of armor shall be opposite to that of the cores.
4.2.7 Outer Sheath
Extruded outer sheath shall be provided over the armoring. The material used for sheathing shall be
FRLS PVC sheath, Type ST-2 base compound conforming to IS 1554/ IS 5831 for power cable. The
colour of the outer sheath shall be black. The thickness of outer sheath shall be in accordance with the
IS 1554 (Part-I)-1988.
4.3 Tests of LT power cables.
All the tests specified below shall be carried out in accordance with relevant Indian Standards by the
manufacturer in the presence of purchaser's representative. If the cable fails to pass the test
specified, the purchaser shall have the option to reject it.
4.3.1 Acceptance test
4.3.2 Annealing test – for Cu.
4.3.3 Tensile & wrapping test for Al.
4.3.4 Tensile test for Cu.
4.3.5 Conductor resistance.
4.3.6 Full physical dimension measurements for insulation, sheath & armour.
4.3.7 Tensile/elongation for insulation & sheath.
4.3.8 Volume resistivity at room temperature & at 90 o
C.
4.3.9 Hot set test for XLPE.
4.3.10 HV test.
4.4 Special test (FRLS test)
4.4.1 Oxygen index test
4.4.2 Temperature index test
4.4.3 Smoke density test
4.4.4 HCL gas generation test
4.4.5 Flammability test
4.4.6 Swedish chimney test.
Page 11 of 25
4.5 Routine test (On each drum)
4.5.1 Conductor resistance test.
4.5.2 HV test.
4.5.3 IR test.
4.6 Type test
4.6.1 Ageing test.
4.6.2 Shrinkage test.
4.6.3 Hot deformation test on insulation/sheath.
4.6.4 Heat shock test.
4.6.5 Loss of mass.
4.6.6 Thermal stability.
4.6.7 Water absorption test for XLPE.
4.6.8 Test on armored wires:-
- Dimension measurement.
- Tensile strength test.
- Elongation test.
- Winding test.
- Mass of zinc coating.
- Uniformity of zinc coating
4.6.9 Anti-rodent test
4.7 Test requirement of FRLS inner & outer sheath
The inner and outer sheath of cables shall meet the following test requirements related to flame
retardance, low smoke emission, low acid and toxic gas emission. The BIDDERs shall have proper
test apparatus to conduct all the relevant tests as per the applicable Standards mentioned herein.
4.7.1 Oxygen Index and Temperature index test
The critical oxygen index value shall be minimum 29 when tested at 27+2ºC as per ASTM-D-2863
and the temperature index value shall be minimum 250ºC at oxygen index of 21 when tested as per
NES 715.
4.7.2 Flammability test
i. Cables shall pass test under fire conditions as per IS-10810- Part-53.
ii. Cables shall also pass tests as per IS-10810 Part- 61 & Part-62.
Flammability shall be as per IEC 332-1 and IS 694: 1990.
4.7.3 Smoke Generation test
The cables shall satisfy the tests conducted to evaluate the percentage obscuration by smoke in an
optical system placed in the path of the smoke. The maximum smoke density rating shall not be
more than 60% when tested as per ASTM-D-2843.
4.7.4 Acid Gas Generation test
The hydrochloric acid generation when tested as per IEC 754-1 shall be less than 20% by weight.
Page 12 of 25
4.8 Resistance to Ultra Violet Radiation
This test shall be carried out as per DIN 53387. The retention values of tensile strength and ultimate
elongation after the tests shall be minimum 60% of tensile strength and ultimate elongation before
test.
4.9 Water Absorption
Outer sheathes shall be subjected to tests for water absorption as per IS-10810. When additional
characteristics are required, the tests shall be as applicable or as agreed to between Purchaser and
Vendor before the placement of order.
The purchaser at his option may waive all or any of the type tests provided type test certificate
carried out on essentially identical cable are furnished by the manufacturer.
5 Guarantee against defects
The cable shall be guaranteed against any type of defects and for trouble free operation
conforming to this specification for a period of at least 12 months from the date of
commissioning or 18 months from the date of dispatch from the supplier's works whichever is
earlier. The following performance characteristics of cables shall be guaranteed at the maximum
continuous rating when operating under the specified operating conditions:
Voltage drop
Maximum current rating
Operating conductor Resistance at 20 ºC
FRLS properties
6 SEQUENTIAL LENGTH MARKING
Length of the cable shall be sequentially marked on every metre length of the cable to be supplied by
the contractor as follows:
Name of manufacturer:
Name of the project: NRB, Tarapur
Configuration of the cable: viz. Core & Sq. mm, A2XWY/2XWY/YWY / YY as applicable
Year of manufacturing:
7 PACKING AND MARKING
The single length of cable shall be minimum 500 metres.
The cable shall be wound on non-returnable steel drums of suitable size, packed and marked. The
packing shall be such that it can withstand rough handling during transport and shall ensure that no
damage will be caused to the cable during transit. The markings done on the drums shall have the
following information:-
i) Trade mark or trade name, if any.
ii) Name of the manufacturer.
iii) Nominal sectional area of the conductor of the cable.
iv) Number of cores
v) Voltage grade and type of the cable.
vi) Length of the cable on the drum.
vii) Direction of rotation of the drum (an arrow).
Page 13 of 25
viii) Type of cable.
The cut-ends of the cable shall be sealed by means of non-hygroscopic sealing materials. Each end of
the cable shall be firmly and properly secured to the drum.
8 Quantity Tolerance:
The quantity tolerance of all cables shall be ±5%.
Page 14 of 25
SECTION - C
FORMAT FOR SUBMISSION OF TENDER FOR PART- I (TECHNICAL BID)
ANNEXURE-I (TECHNICAL DATA FORMAT)
1. TECHNICAL PARTICULARS OF LT CABLE:
The bidder shall furnish the technical particulars below for the cables quoted without which the
offer shall be considered as incomplete. Specific details shal l be furnished avoiding general
statement like as per standards etc.
Sr.
No. Description
3.5Cx400 Sq. mm
(A2XWY) 4Cx10Sq. mm (2XWY)
1 Name of manufacturer
1.1 Trade name or type of
cable
1.2 Rated voltage
1.3 Voltage grade
1.4
Suitable for
earthed/unearthed
system
1.5 Number of cores
1.6 Nominal area of the
conductor in sq.mm
1.7 Conductor material,
purity and grade
1.8 Tensile strength of
wires in kg./sq.cm
1.9 Circular conductor or
shaped conductor?
1.10 Circular conductor
a. Diameter of the wires
in mm.
i Number of wires
ii Overall diameter
iii
Resistance of the
conductor/km at 20
deg. C and maximum
allowable resistance at
20 deg. C
Page 15 of 25
iv Rated current in amps.
at 45 dg. C ambient
v Weight in kg/km
vi Shaped Conductor
b. Diameter of the wires
in mm.
i Number of wires used
ii Tolerance on number
of wires given above
iii
Resistance of the
conductor/KM at 20
ºC and maximum
allowable resistance at
20 dg. C
iv Rated current in amps.
at 45ºC ambient
v
vi Weight in Kg/km
Conductor temp.
corresponding to
maximum continuous
current
1.11
Maximum short circuit
current withstanding
capacity for the cables for
1 second
1.12
Max. temperature of the
cable conductor under
short circuit condition
1.13
Max. let through
energy the cable can
withstand
1.14
Impedance/Ian. (in ohms)
of cable at 85°C
conductor temperature
1.15
Voltage
drop/ampere/mtr.
length of the cables
1.16 Loss tangent at normal
frequency
1.17 Dielectric constant at
normal frequency
1.18
Material of insulation and
type as per latest IS 7098
P-1 for XLPE & IS 5831
for PVC.
1.19 Thickness of insulation
between conductor
1.2
Thickness of insulation
between conductors and
sheath
1.21 Tolerance on thickness of
insulation
Page 16 of 25
1.22
No negative tolerance
on insulation
thickness-Acceptable/
Not acceptable
1.23 Insulation resistance in
ohm-m.
1.24 Minimum thickness of
inner sheath
1.25
Material of inner sheath
and type as per IS 5831 &
IS 7098 P-1
1.26 Details of armouring
1.27 Type of armour
i Size of wire
ii Thickness of zinc coating
over wire
iii
Short circuit current
capacity of armouring
wire
iv Material of outer sheath
and type
1.28 Minimum thickness of
outer sheath
1.29 Tolerance on thickness of
inner and outer sheath
1.30 Overall diameter of the
finished cable
1.31 Weight of the cable in
kg./km
1.32 FRLS Properties
1.33 Oxygen index
i Temperature index
ii Smoke density
iii Amount of acid gas
generated (%)
iv Fire resistance in terms of
un-burnt cable length (%)
v
Tests (Pl mention tests &
also additional test
provided if any)
1.34 Routine test
i Type test
ii Acceptance Test
iii Test on FRLS Sheath
Page 17 of 25
1.35
Whether color scheme
used for the identification
of cores
1.36 De-rating factor for
grouping of cables
1.37 When laid in trench
and technical galleries
I
When laid
underground (directly
buried)
Ii When laid in air on
cable trays
Iii
Operating factor for
various ambient (air &
ground) temperature
1.38
De-rating factor under
high temperature
condition, group rating
factors etc.
1.39
Any special too
required for jointing &
end termination of
cable
1.40
Recommended
minimum bending
radius during
installation
1.41
Safe pulling force,
when pulled by pulling
eye
1.42 Length of the cable in a
drum
1.43 Type of Drum offered and
its dimensions
1.44 Total weight of a drum
complete with cable
1.45
Whether the cables are lSI
marked (if yes, please
attach certificate)
1.46
Whether the cables are
type tested for temperature
rise, impulse voltage at
CPRI/ ERDA (If yes,
please attach certificate)
1.47
Whether the cables are
covered under ISO
9001&9002 certification
(If yes, please attach
certificate)
Page 18 of 25
2. Following documents shall be furnished along with the tender:
2.1 Technical particulars of all the cables as given above.
2.2 Cross section of all cables.
2.3 QAP of cables.
2.4 Test report(s) of past supplies for similar items.
2.5 Past supplies and their feedback reports.
2.6 CPRI/ ERDA type test certificates etc.
Page 19 of 25
Annexure - II
Schedule of deviation
All deviations from this specification including the general conditions of contract shall be set out by
the tenderer clause by clause in this schedule. Compliance with this specification is taken for granted
in the absence of mention of any departure from any of the clauses of this specification in this
schedule.
Sr. No. Section Clause No. Deviation
1.
2.
3.
Date:
Place:
(Signature of bidder)
Page 20 of 25
Annexure III
Vendor Evaluation Proforma
(To be filled in and submitted along with the tender.)
Ref: Tender Enquiry No. ________________ Date :
Equipment :
Quotation No. :
1. Vendor details
1.1 Name :
1.2 Address (Office) :
Address (Works) :
1.3 Telephone :
1.4 Telex :
1.5 E-mail :
1.6 Contact person :
2. Registration details with
2.1 S. S. I. :
2.2 Directorate of Industries :
2.3 Others (please specify) :
3. Organizational details
3.1 State/Central undertaking :
3.2 Public/Private Ltd. :
3.3 Partnership :
3.4 Proprietary :
3.5 Top Management (Qualification & position) :
3.6 Date of inception :
4. Performance of past 3 years with profit & loss and as anticipated for the Current year.
4.1 Year :
4.2 Capital :
(Authorized/Working)
4.3 Turnover :
Page 21 of 25
4.4 Profit/Loss :
(Do not enclose balance sheet, Annual report etc.)
4.5 Give a list of items on the regular production program with annual production rates for each item
5. Proof of ability
Give name and address of the parties to whom 1100V grade LT Power Cable of the type covered by
this tender were supplied in the last 5 years.
List of supplies made in Nuclear Plants if any
6. Details of facilities
6.1 Floor space
6.2 Key departments (Attached Separately)
6.3 List of man power, machines/ equipment, test and calibrating standards etc. available. (Attached
Separately)
6.4 Quality control facilities. (Attached Separately)
6.5 Drawing facilities Men power available (Attached Separately)
6.6 List all inspection and test facilities available to carry out the different tests/inspections specified in
this tender specification:
7. Documentation:
7.1 Reference standards (Specific to this tender) : Available /Not Available
7.2 Drawing detailed availability : Verification (Yes/No)
Retention (Yes/No)
7.3 Test certificate for procured materials : Verification (Yes/No)
Retention (Yes/No)
7.4 Availability of inward inspection records to customer for : Verification (Yes/No)
Retention (Yes/No)
7.5 Availability of process inspection records to customer for : Verification (Yes/No)
Retention (Yes/No)
7.6 Availability of final inspection records to customer for : Verification (Yes/No)
Retention (Yes/No)
Page 22 of 25
Annexure - IV
Typical Quality Assurance Plan for XLPE cables
Sr.No. Stage &
Activity Characteristics
Quantum of
check
Scope of
Inspection
1 Acceptance
Tests Annealing test for Cu
As per IS 7098
PT-1 P W
Tensile & wrapping test for Al " " "
Tensile test for Cu " " "
Conductor resistance " " "
Full physical dimension
measurements for insulation,
sheath & armor
" " "
Tensile/elongation for
insulation & sheath " " "
Volume resistivity at room
temperature & at 90 o C
" " "
Hot set test for XLPE " " "
HV test. " " "
2 Routine Test Conductor resistance 100% drums " "
HV test 100% drums " "
IR test 100% drums " "
3 Type test Ageing test
1 Sample per
Lot P R
Shrinkage test. As per IS P W
Hot deformation test on
insulation/sheath. " " "
Heat shock test. " " "
Loss of mass. " " "
Thermal stability. " " "
Water absorption test for
XLPE. " " "
Test on armored wires:-
- Dimension
measurement. " " "
- Tensile strength test. " " "
- Elongation test. " " "
- Winding test. " " "
- Mass of zinc coating. " " "
- Uniformity of zinc
coating " " "
Anti-rodent test " " "
4 FRLS tests Flame retardance test 1 Sample per
Lot P W
Oxygen & temperature index
test " " "
Page 23 of 25
Flammability test " " "
Smoke generation test " " "
Acid gas generation test " " "
5
Resistance to ultra violet
radiation " " "
6 Water absorption test " " R
Legends: P- Performed by manufacturer, R- Review by BARC, W- Witness by BARC
Page 24 of 25
Annexure - 5
Proof of ability of the bidder
Use one form for each work carried out
1. Name of work :
2. Name of firm for which project was done :
3. Address for reference :
4. Value of total work : Rs.
5. Date of commencement :
6. Date of completion :
7. Has the work been completed and final payment received :
Yes ____________ No__________
8. Was there any arbitration :
Yes ____________ No__________
Date:
Place:
(Signature of bidder)
Page 25 of 25
PART-II
(PRICE –BID)
The bidder shall quote for design, manufacture, testing, delivery at site for following on a firm lump
sum basis, conforming to the requirements of this specification.
A. PRICE & QUANTITIES SCHEDULE:
Sr.
No. Description
Qty.
(Mtr)
Rate
(Rs. per Mtr) Total Price
(Rs.) Design, manufacturing, Testing & safe
delivery of following cables :
1. 1.1 kV grade Power cable (A2XWY)
of size 3.5C x 400 Sq.mm,
Aluminium conductor, XLPE
insulated, FRLS PVC type ST2 inner
sheathed, GI round wire Armoured,
and FRLS PVC ST2 outer sheathed,
as per IS 7098 ( part - 1) 1988.
8000m
2. 1.1kV grade Power cable (2XWY) of
size 4C x 10 Sq.mm, copper
conductor, XLPE insulated, FRLS
PVC type ST2 inner sheathed, GI
round wire Armoured, and FRLS
PVC ST2 outer sheathed, as per IS
7098 ( part - 1) 1988.
5000m
Sub Total (Rs.) Excise Duty Packing & Forwarding (if any) VAT Freight charges Grand Total (Rs.)
B. MANUFACTURING & DELIVERY SCHEDULE
We agree to carry out the work in accordance with the following schedule:
1. Period required for starting manufacture after placement of purchase order:
2. Period required for inspection & testing at site:
(Signature of the Bidder)
Date:
Place: