gloucester township board of education anna a. mullen - Amazon S3
Transcript of gloucester township board of education anna a. mullen - Amazon S3
GLOUCESTER TOWNSHIP BOARD OF EDUCATION
ANNA A. MULLEN MIDDLE SCHOOL
1400 SICKLERVILLE ROAD SICKLERVILLE, NJ 08081
FACILITY ENERGY REPORT
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 1 of 31
TABLE OF CONTENTS
I. HISTORIC ENERGY CONSUMPTION/COST ................................................................. 2
II. FACILITY DESCRIPTION ................................................................................................ 9
III. MAJOR EQUIPMENT LIST ............................................................................................ 11
IV. ENERGY CONSERVATION MEASURES ..................................................................... 12
V. ADDITIONAL RECOMMENDATIONS ......................................................................... 31
Appendix A – ECM Cost & Savings Breakdown
Appendix B – New Jersey Smart Start® Program Incentives
Appendix C – Portfolio Manager “Statement of Energy Performance”
Appendix D – Major Equipment List
Appendix E – Investment Grade Lighting Audit
Appendix F – Renewable / Distributed Energy Measures Calculations
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 2 of 31
I. HISTORIC ENERGY CONSUMPTION/COST The energy usage for the facility has been tabulated and plotted in graph form as depicted within this section. Each energy source has been identified and monthly consumption and cost noted per the information provided by the Owner. Electric Utility Provider: Atlantic City Electric Electric Utility Rate Structure: Monthly General Service & Annual General Service Third Party Supplier: South Jersey Energy Co. Natural Gas Utility Provider: South Jersey Gas Utility Rate Structure: Firm Transportation Third Party Supplier: Hess The electric usage profile represents the actual electrical usage for the facility. The electric utility measures consumption in kilowatt-hours (KWH) and maximum demand in kilowatts (KW). One KWH usage is equivalent to 1000 watts running for one hour. One KW of electric demand is equivalent to 1000 watts running at any given time. The basic usage charges are shown as generation service and delivery charges along with several non-utility generation charges. Rates used in this report reflect the historical data received for the facility. The gas usage profile within each facility report shows the actual natural gas energy usage for the facility. The gas utility measures consumption in cubic feet x 100 (CCF), and converts the quantity into Therms of energy. One Therm is equivalent to 100,000 BTUs of energy.
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 3 of 31
Table 1 Electricity Billing Data
Utility Provider: Atlantic City ElectricRate: Monthly General Service (MGS) / Annual General Service (AGS)
Meter No: 105763483 / 36135500Account # 1139 5589 9944 / 1139 5589 9969
Third Party Utility Provider: South Jersey EnergyTPS Meter / Acct No: 113955899944
MONTH OF USE CONSUMPTION KWH TOTAL BILL
Jan-11 158,047 $23,650
Feb-11 139,055 $21,093
Mar-11 144,905 $36,503
Apr-11 154,030 $23,352
May-11 171,407 $23,452
Jun-11 225,958 $45,830
Jul-11 225,249 $29,696
Aug-11 212,164 $27,858
Sep-11 191,096 $26,119
Oct-11 193,560 $26,189
Nov-11 116,334 $16,217
Dec-11 134,240 $18,983
Totals 2,066,045 572 Max $318,941
AVERAGE DEMAND 430.2 KW average
AVERAGE RATE $0.154 $/kWh
353
349
531
ELECTRIC USAGE SUMMARY
DEMAND KW
335
347
393
351
572
418
416
551
546
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 4 of 31
Figure 1
Electricity
Usage
Profile
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 5 of 31
Table 4 Natural Gas Billing Data
Utility Provider: South Jersey GasRate: Firm Transportation
Meter No: 517372Account Number 2 19 41 0099 0 0
Third Party Utility Provider: Hess CorporationTPS Account No:
MONTH OF USECONSUMPTION
(THERMS)TOTAL BILL
Jan-11 23,306 $21,270
Feb-11 16,685 $15,303
Mar-11 11,605 $10,904
Apr-11 9,284 $8,991
May-11 1,499 $2,035
Jun-11 879 $1,583
Jul-11 633 $1,405
Aug-11 622 $1,315
Sep-11 614 $1,313
Oct-11 1,870 $2,399
Nov-11 6,308 $6,016
Dec-11 10,793 $9,901
TOTALS 84,099 $82,435
AVERAGE RATE: $0.98 $/THERM
446596/447054
NATURAL GAS USAGE SUMMARY
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 6 of 31
Figure 2
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 7 of 31
Nat
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 8 of 31
ural Gas Usage Profile
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 9 of 31
II. FACILITY DESCRIPTION
The Ann A. Mullen Middle School is located on 1400 Sicklerville Road in Sicklerville, New Jersey. The 173,342 SF school was built in 1995 with an addition in 2002. The building is a single story facility comprised of classrooms, multi-purpose room, cafeteria, kitchen, media center, mechanical room and offices.
Occupancy Profile
The typical hours of operation for the Middle School are Monday through Friday between 8:00 am and 2:30 pm. Anna A. Mullen School employs approximately 87 people, with student enrollment estimated at 1,180.
Building Envelope
Exterior walls for the Elementary School are masonry brick faced with a concrete block construction. The windows throughout the school are in good condition and appear to be maintained. Typical windows are double pane, operable, ¼” coated glass with aluminum frames. The roof is a flat, built up with gravel overlay.
HVAC Systems
The Anna Mullen Middle School is mostly conditioned by a 4-pipe system of unit ventilators with hot water and chilled water coils. The chilled water system consists of a 320 Ton Centrifugal Chiller paired with an Imeco cooling tower. There are two 50 horsepower condenser water pumps rated at 1,760 gallons per minute and 78 feet of head pressure. There are also two sets of pumps circulating chilled water through the unit ventilator systems; Two 60 horsepower chilled water pumps for the existing building and two 20 horsepower pumps for the 2002 addition.
The remainder of the classrooms on the interior of the building and are conditioned by a variety of packaged rooftop units. There are five Lennox (Epic) packaged DX cooling and gas furnaces that have capacities ranging from 5 to 10 tons serving teacher’s lounge, boys & girls locker rooms and the music rooms. Additionally, there is a McQuay remote condensing unit attached to a McQuay outdoor air handling unit with a rated cooling capacity of 16 tons. This Mcquay system also has a reznor outdoor duct heater connection which provides heating to the shop areas in which these units serve.
Heating Hot Water is generated by a single boiler plant fitted with three H.B. Smith cast iron sectional boilers. Two of the boilers are older Model 28A series and the last boiler is a newer Model 28A series. These boilers are natural gas fired rated at 3,563 MBH and 1,166 MBH respectively, and the older boilers are fit with Cyclonetic Burners and the new wing boiler is fit with a Power Flame Burner. The primary hot water pumps are two 20 horsepower Taco pumps rated at 450 gallons per minute and 115 feet of head pressure. With the 2002 addition, two more 7.5 horsepower in-line pumps were added rated at 90 gallons per minute and 90 feet of head pressure.
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 10 of 31
Exhaust System
Air is exhausted from the toilet rooms through the roof exhausters.
HVAC System Controls
The building has a control system that monitors the boilers and pneumatic thermostats and control valves in the unit ventilators. Supplemental cooling systems are controlled by individual thermostat. The new 2002 addition and more recently, the cafeteria and gymnasium have been converted over to electronic controls instead of pneumatics. All controls are tied into a full BMS system which can be controlled remotely.
Domestic Hot Water
Domestic hot water is provided by a single Bradford and White 300 MBH gas fired heater with an integrated 100 gallon storage tank. Domestic hot water is circulated via a small horsepower pump.
Lighting
Refer to the Investment Grade lighting Audit Appendix for a detailed list of the lighting throughout the facility and estimated operating hours per space.
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 11 of 31
III. MAJOR EQUIPMENT LIST
The equipment list contains major energy consuming equipment that through implementation of energy conservation measures could yield substantial energy savings. The list shows the major equipment in the facility and all pertinent information utilized in energy savings calculations. An approximate age was assigned to the equipment in some cases if a manufactures date was not shown on the equipment’s nameplate. The ASHRAE service life for the equipment along with the remaining useful life is also shown in the Appendix.
Refer to the Major Equipment List Appendix for this facility.
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 12 of 31
IV. ENERGY CONSERVATION MEASURES Energy Conservation Measures are developed specifically for this facility. The energy savings and calculations are highly dependent on the information received from the site survey and interviews with operations personnel. The assumptions and calculations should be reviewed by the owner to ensure accurate representation of this facility. The following ECMs were analyzed:
Table 1 ECM Financial Summary
ECM #1 General Lighting Upgrade $33,413 $15,143 2.2 579.8%
ECM #2Gym/Café & Other Lighting
Upgrades$18,680 $4,081 4.6 227.7%
ECM #3 Lighting Controls Upgrade $31,210 $5,157 6.1 147.9%
ECM #4 Rooftop Unit Replacements $93,887 $5,648 16.6 -9.8%
ECM #5NEMA Premium Motor
Replacements$73,930 $20,174 3.7 445.8%
ECM #6 DDC System Expansion $412,000 $17,137 24.0 -37.6%
REM #1 438.51 KW PV System $2,548,057 $186,994 13.6 10.1%
Notes:
NET INSTALLATION
COSTA
RENEWABLE ENERGY MEASURES (REM's)
ECM NO.
DESCRIPTIONNET
INSTALLATION COST
ANNUAL
SAVINGSB
ANNUAL SAVINGS
SIMPLE PAYBACK
(Yrs)
SIMPLE LIFETIME
ROI
A. Cost takes into consideration applicable NJ Smart StartTM incentives.B. Savings takes into consideration applicable maintenance savings.
ECM NO.
DESCRIPTIONSIMPLE
PAYBACK (Yrs)
SIMPLE LIFETIME
ROI
ENERGY CONSERVATION MEASURES (ECM's)
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 13 of 31
Table 2 ECM Energy Summary
ECM #1 General Lighting Upgrade 40.0 98,330 0
ECM #2Gym/Café & Other Lighting
Upgrades10 26,498 0
ECM #3 Lighting Controls Upgrade 0.0 33,488 0
ECM #4 Rooftop Unit Replacements 18.3 36,675 0
ECM #5NEMA Premium Motor
Replacements38.1 131,002 0
ECM #6 DDC System Expansion 0.0 82,077 4,588
REM #1 438.51 KW PV System 438.5 541,878 0
ECM NO.
DESCRIPTION
ANNUAL UTILITY REDUCTION
ECM NO.
DESCRIPTION
ANNUAL UTILITY REDUCTION
RENEWABLE ENERGY MEASURES (REM's)
NATURAL GAS (THERMS)
ELECTRIC DEMAND
(KW)
NATURAL GAS (THERMS)
ELECTRIC CONSUMPTION
(KWH)
ENERGY CONSERVATION MEASURES (ECM's)
ELECTRIC DEMAND
(KW)
ELECTRIC CONSUMPTION
(KWH)
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 14 of 31
Table 3 Facility Project Summary
Design / Construction Extras is shown as an additional cost for the facility project summary. This cost is included to estimate the costs associated with construction management fees for a larger combined project.
General Lighting Upgrade $15,143 $48,603 $15,190 $33,413 2.2
Gym/Café & Other Lighting Upgrades
$4,081 $26,080 $7,400 $18,680 4.6
Lighting Controls Upgrade $5,157 $34,000 $2,790 $31,210 6.1
Rooftop Unit Replacements
$5,648 $97,750 $3,863 $93,887 16.6
NEMA Premium Motor Replacements
$20,174 $75,570 $1,640 $73,930 3.7
DDC System Expansion $17,137 $412,000 $0 $412,000 24.0
Design / Construction Extras (15%)
$0 $42,300 $0 $42,300
Total Project $50,203 $324,303 $30,883 $293,420 6
Note: ECM's with the strike-through font are not included in the ESIP.
SIMPLE PAYBACK
ENERGY CONSERVATION
MEASURES
ANNUAL ENERGY
SAVINGS ($)
PROJECT COST ($)
SMART START
INCENTIVES
CUSTOMER COST
ENERGY SAVINGS IMPROVEMENT PROGRAM - POTENTIAL PROJECT
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 15 of 31
ECM #1: Lighting Upgrade – General Description: The majority of the interior lighting throughout Ann Mullen Middle School is provided with fluorescent fixtures with older generation, 700 series and 741/ECO 32W T8 lamps and electronic ballasts. Although these T8 lamps are considered fairly efficient, further energy savings can be achieved by replacing the existing T8 lamps with new generation, 800 series 28W T8 lamps without compromising light output. CE recommends, re-lamping all of the fixtures with 28W T8 lamps and in some cases removing a lamp from the fixture due to excessive foot candle levels in specific areas. This ECM includes re-lamping of the existing fluorescent fixtures with 800 series, 28W T8 lamps. The ECM also includes retrofit of all older fluorescent fixtures with T8 or T5 fluorescent fixtures with electronic ballasts in the building. The new, energy efficient T8 fixtures will provide adequate lighting and will save on electrical costs due to better performance of the lamp and ballasts. The ECM also includes replacement of any incandescent lamps with compact fluorescent lamps. Compact fluorescent lamps (CFL’s) were designed to be direct replacements for the standard incandescent lamps which are common to table lamps, spot lights, hi-hats, bathroom vanity lighting, etc. The light output of the CFL has been designed to resemble the incandescent lamp. The color rendering index (CRI) of the CFL is much higher than standard fluorescent lighting, and therefore provides a much “truer” light. The CFL is available in a myriad of shapes and sizes depending on the specific application. Typical replacements are: a 13-Watt CFL for a 60-Watt incandescent lamp, an 18-Watt CFL for a 75-Watt incandescent lamp, and a 26-Watt CFL for a 100-Watt incandescent lamp. The CFL is also available for a number of “brightness colors” that is indicated by the Kelvin rating. A 2700K CFL is the “warmest” color available and is closest in color to the incandescent lamp. CFL’s are also available in 3000K, 3500K, and 4100K. The 4100K would be the “brightest” or “coolest” output. A CFL can be chosen to screw right into your existing fixtures, or hardwired into your existing fixtures. Where the existing fixture is controlled by a dimmer switch, the CFL bulb must be compatible with a dimmer switch. In some locations the bulb replacement will need to be tested to make sure the larger base of the CFL will fit into the existing fixture. The energy usage of an incandescent compared to a compact fluorescent approximately 3 to 4 times greater. In addition to the energy savings, compact fluorescent fixtures burn-hours are 8 to 15 times longer than incandescent fixtures ranging from 6,000 to 15,000 burn-hours compared to incandescent fixtures ranging from 750 to 1000 burn-hours. However, the maintenance savings due to reduced lamp replacement is offset by the higher cost of the CFL’s compared to the incandescent lamps. Energy Savings Calculations: The Investment Grade Lighting Audit Appendix outlines the hours of operation, proposed retrofits, costs, savings, and payback periods for each set of fixtures in the each building.
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 16 of 31
Energy Savings Summary:
Installation Cost ($): $48,603
NJ Smart Start Equipment Incentive ($): $15,190
Net Installation Cost ($): $33,413
Maintenance Savings ($/Yr): $0
Energy Savings ($/Yr): $15,143
Total Yearly Savings ($/Yr): $15,143
Estimated ECM Lifetime (Yr): 15
Simple Payback 2.2
Simple Lifetime ROI 579.8%
Simple Lifetime Maintenance Savings $0
Simple Lifetime Savings $227,145
Internal Rate of Return (IRR) 45%
Net Present Value (NPV) $147,363.15
ECM #1 - ENERGY SAVINGS SUMMARY
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 17 of 31
ECM #2: Lighting Upgrade – Gymnasium/Cafeteria & Other Description: The gymnasium, cafeteria, lobby, stage, and hallway at Ann Mullen Middle School are currently lit via 400 watt and 250 watt Metal Halide HID fixtures. The space would be better served with a more efficient, fluorescent lighting system. CE recommends upgrading the lighting to an energy-efficient T5 high output system that includes new three and six lamp, 54 watt high output fixtures. This measure replaces all the HID, 400 and 250 watt HID MH fixtures with a well-designed T5 high output (HO) system. T5 High output fixtures with reflectors and wire guards will be required in order to meet the mandated 50 foot-candle average within the spaces. Energy Savings Calculations: A detailed Investment Grade Lighting Audit can be found in Investment Grade Lighting Audit Appendix that outlines the proposed retrofits, costs, savings, and payback periods. Energy Savings Summary:
Installation Cost ($): $26,080
NJ Smart Start Equipment Incentive ($): $7,400
Net Installation Cost ($): $18,680
Maintenance Savings ($/Yr): $0
Energy Savings ($/Yr): $4,081
Total Yearly Savings ($/Yr): $4,081
Estimated ECM Lifetime (Yr): 15
Simple Payback 4.6
Simple Lifetime ROI 227.7%
Simple Lifetime Maintenance Savings $0
Simple Lifetime Savings $61,215
Internal Rate of Return (IRR) 21%
Net Present Value (NPV) $30,038.71
ECM #2 - ENERGY SAVINGS SUMMARY
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 18 of 31
ECM #3: Lighting Controls Upgrade – Occupancy Sensors Description: Some of the lights in the Ann Mullen Middle School are left on unnecessarily. In many cases the lights are left on because of the inconvenience to manually switch lights off when a room is left or on when a room is first occupied. This is common in rooms that are occupied for only short periods and only a few times per day. In some instances lights are left on due to the misconception that it is better to keep the lights on rather than to continuously switch lights on and off. Although increased switching reduces lamp life, the energy savings outweigh the lamp replacement costs. The payback timeframe for when to turn the lights off is approximately two minutes. If the lights are expected to be off for at least a two minute interval, then it pays to shut them off.
Lighting controls come in many forms. Sometimes an additional switch is adequate to provide reduced lighting levels when full light output is not needed. Occupancy sensors detect motion and will switch the lights on when the room is occupied. Occupancy sensors can either be mounted in place of a current wall switch, or on the ceiling to cover large areas. The U.S. Department of Energy sponsored a study to analyze energy savings achieved through various types of building system controls. The referenced savings is based on the “Advanced Sensors and Controls for Building Applications: Market Assessment and Potential R&D Pathways,” document posted for public use April 2005. The study has found that commercial buildings have the potential to achieve significant energy savings through the use of building controls. The average energy savings are as follows based on the report:
Occupancy Sensors for Lighting Control 20% - 28% energy savings.
Savings resulting from the implementation of this ECM for energy management controls are estimated to be 20% of the total light energy controlled by occupancy sensors (The majority of the savings is expected to be after school hours when rooms are left with lights on) This ECM includes installation of ceiling or switch mount sensors for individual offices, classrooms, large bathrooms, and Media Centers. Sensors shall be manufactured by Sensorswitch, Watt Stopper or equivalent. The Investment Grade Lighting Audit Appendix of this report includes the summary of lighting controls implemented in this ECM and outlines the proposed controls, costs, savings, and payback periods. The calculations adjust the lighting power usage by the applicable percent savings for each area that includes lighting controls. Energy Savings Calculations:
kWh/YrEnergyLightControlledSavings%SavingsEnergy
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 19 of 31
kWh
$CostElecAvekWhSavingsEnergySavings.
Rebates and Incentives:
From the NJ Smart Start® Program Incentives Appendix, the installation of a lighting control device warrants the following incentive: SmartStartIncentive
#Wallmountsensors $20persensor#Ceilingmountsensors $35persensor
Energy Savings Summary:
Installation Cost ($): $34,000
NJ Smart Start Equipment Incentive ($): $2,790
Net Installation Cost ($): $31,210
Maintenance Savings ($/Yr): $0
Energy Savings ($/Yr): $5,157
Total Yearly Savings ($/Yr): $5,157
Estimated ECM Lifetime (Yr): 15
Simple Payback 6.1
Simple Lifetime ROI 147.9%
Simple Lifetime Maintenance Savings $0
Simple Lifetime Savings $77,355
Internal Rate of Return (IRR) 14%
Net Present Value (NPV) $30,353.93
ECM #3 - ENERGY SAVINGS SUMMARY
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 20 of 31
ECM #4: Replace Split System Units with High Efficiency Units
Description:
The teacher’s lounge, boy’s and girl’s locker rooms, tech labs and music rooms are cooled by packaged rooftop units and split systems at Anna A. Mullen Middle School. These units capacities range from 5 tons to 16 tons. Please refer to the Major Equipment List Appendix for further information about these units.
These units are in average condition though the current units in operation are not high efficiency units. These units are approximately seventeen years old and have surpassed their ASHRAE service life of fifteen years.
These units can be replaced with new higher efficiency units. New packaged rooftop units and split system units provide higher full load and part load efficiencies due to advances in inverter motor technologies, heat exchangers and higher efficiency refrigerants such as R410A which would be used in place of R22 that is currently used in the units. This ECM includes one-for-one replacement of the older packaged and split system units with new higher efficiency systems which include new evaporator coils and refrigerant lines. It is recommended to fully evaluate the capacity needed for all new systems prior to moving forward with this ECM. A summary of the unit replacements for this ECM can be found in the table below:
The manufacturers used as the basis for the calculation is Trane. The unit pricing and install cost were estimated based on current rates quotes and labor rates. The payback may change based on actual unit pricing and install costs if the ECM is implemented. Energy Savings Calculations: Cooling Energy Savings:
ECM INPUTS SERVICE FORNUMBER OF UNITS
COOLING CAPACITY,
BTU/HR
TOTAL CAPACITY,
TONSREPLACE UNIT WITH
SS CU - 2 1 192,000 16.0 Trane TTA180
RTU RTU - 1 1 120,000 10.0 Trane YHC120
RTU RTU - 2 , 3 2 78,000 13.0 Trane YHC072
RTU RTU - 4 , 5 2 60,000 10.0 Trane YHC060
Total 6 588,000 49.0
IMPLEMENTATION SUMMARY
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 21 of 31
Seasonal energy consumption of the air conditioners at the cooling mode is calculated with the equation below:
EnergySavings, kWh CoolingCapacity,BTUHr
1SEER
1SEER
OperationHours
1000 WkWh
DemandSavings, kWEnergySavings kWhHoursofCooling
CoolingCostSavings EnergySavings, kWh CostofElectricity$
kWh
Project Cost, Incentives and Maintenance Savings From the NJ Smart Start® Program appendix, the rebate are $92 per ton for units below 5.4 tons & $73 per ton for units ranging from 5.4 tons to 11.25 tons.. Summary of cost, savings and payback for this ECM is below.
ECM INPUTS
COOLING CAPACITY,
BTU/Hr
ANNUAL COOLING
HOURS
EXISTING UNITS
EER/SEER
SPLIT UNITS EER/SEER
# OF UNITS
ENERGY SAVINGS
kWh
DEMAND SAVINGS
kW
SS 192,000 2,000 9 EER 13 EER 1 13,128 6.6
RTU 120,000 2,000 9 EER 12.5 EER 1 7,467 3.7
RTU 78,000 2,000 9.5 EER 12.6 EER 2 8,080 4.0
RTU 60,000 2,000 10 SEER 15 SEER 2 8,000 4.0
Total 6 36,675 18.3
ENERGY SAVINGS CALCULATIONS
ECM INPUTSINSTALLED
COST# OF
UNITSTOTAL COST
REBATES NET COSTENERGY SAVING
PAY BACK YEARS
SS $22,750 1 $22,750 $1,264 $21,486 $2,022 10.6
RTU $17,500 1 $17,500 $730 $16,770 $1,150 14.6
RTU $32,500 2 $32,500 $949 $31,551 $1,244 25.4
RTU $25,000 2 $25,000 $920 $24,080 $1,232 19.5
Total $97,750 6 $97,750 $3,863 $93,887 $5,648 16.6
COST & SAVINGS SUMMARY
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 22 of 31
Energy Savings Summary:
Installation Cost ($): $97,750
NJ Smart Start Equipment Incentive ($): $3,863
Net Installation Cost ($): $93,887
Maintenance Savings ($/Yr): $0
Energy Savings ($/Yr): $5,648
Total Yearly Savings ($/Yr): $5,648
Estimated ECM Lifetime (Yr): 15
Simple Payback 16.6
Simple Lifetime ROI -9.8%
Simple Lifetime Maintenance Savings $0
Simple Lifetime Savings $84,719
Internal Rate of Return (IRR) -1%
Net Present Value (NPV) ($26,462.01)
ECM #4 - ENERGY SAVINGS SUMMARY
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 23 of 31
ECM #5: Install NEMA Premium® Efficiency Motors Description: The improved efficiency of the NEMA Premium® efficient motors is primarily due to better designs with use of better materials to reduce losses. Surprisingly, the electricity used to power a motor represents 95 % of its total lifetime operating cost. Because many motors operate continuously 24 hours a day, even small increases in efficiency can yield substantial energy and dollar savings. The electric motors driving the hot and cold water pumps are candidates for replacing with premium efficiency motors. These standard efficiency motors run considerable amount of time over a year. This energy conservation measure replaces existing inefficient electric motors with NEMA Premium® efficiency motors. NEMA Premium® is the most efficient motor designation in the marketplace today.
Energy Savings Calculations:
Electricusage, kWhHP LF 0.746 HoursofOperation
MotorEfficiency
where, HP MotorNameplateHorsepowerRating
EQMTID
FUNCTIONMOTOR
HPHOURS OF
OPERATIONEXISTING
EFFICIENCY
NEMA PREMIUM
EFFICIENCYCHWP-1 Chilled Water Pump 60 1,460 91.7% 95.0%CHWP-2 Chilled Water Pump 60 1,460 91.7% 95.0%CWP-1 Condenser Water Pump 50 1,460 91.7% 94.5%CWP-2 Condenser Water Pump 50 1,460 91.7% 94.5%P-1A Hot Water Pumps 20 3,732 88.5% 93.0%P-1B Hot Water Pumps 20 3,732 88.5% 93.0%SP-1 Inline Secondary HW P 7.5 3,732 84.0% 91.7%SP-2 Inline Secondary HW P 7.5 3,732 84.0% 91.7%P-3A Inline Secondary CHW 20 3,732 87.5% 9100.0%P-3B Inline Secondary CHW 20 3,732 87.5% 9100.0%
IMPLEMENTATION SUMMARY
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 24 of 31
LF LoadFactor MotorEfficiency MotorNameplateEfficiency
ProposedExisting UsageElectricUsageElectrickWhSavings,UsageElectric
ElectricUsageSavings, kWh ElectricUsage ElectricUsage
Electriccostsavings ElectricUsageSavings ElectricRate$
kWh
The calculations were carried out and the results are tabulated in the table below:
Equipment Cost and Incentives
Below is a summary of SmartStart Building® incentives for premium efficiency motors:
EQMTID
MOTOR HP
LOAD FACTOR
EXISTING EFFICIENCY
NEMA PREMIUM
EFFICIENCY
POWER SAVINGS
kW
ENERGY SAVINGS
kWH
COST SAVINGS
CHWP-1 60 90% 91.7% 95.0% 1.53 2,240 $345CHWP-2 60 90% 91.7% 95.0% 1.53 2,240 $345CWP-1 50 90% 91.7% 94.5% 1.08 1,592 $245CWP-2 50 90% 91.7% 94.5% 1.08 1,592 $245P-1A 20 90% 88.5% 93.0% 0.73 2,755 $424P-1B 20 90% 88.5% 93.0% 0.73 2,755 $424SP-1 7.5 90% 84.0% 91.7% 0.50 1,889 $291SP-2 7.5 90% 84.0% 91.7% 0.50 1,889 $291P-3A 20 90% 87.5% 9100.0% 15.20 57,026 $8,782P-3B 20 90% 87.5% 9100.0% 15.20 57,026 $8,782
TOTAL 38.1 131,002 $20,174
PREMIUM EFFICIENCY MOTOR CALCULATIONS
HORSE POWER
NJ SMART START
INCENTIVE7.5 $9015 $11520 $12525 $13030 $15040 $18050 $22060 $260
INCENTIVES
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 25 of 31
The following table outlines the summary of motor replacement costs and incentives:
Energy Savings Summary:
EQMTID
MOTOR POWER
HP
INSTALLED COST
SMART START
INCENTIVENET COST
TOTAL SAVINGS
SIMPLE PAYBACK
CHWP-1 60 $14,721 $260 $14,461 $345 41.9CHWP-2 60 $14,721 $260 $14,461 $345 41.9CWP-1 50 $11,177 $220 $10,957 $245 44.7CWP-2 50 $11,177 $220 $10,957 $245 44.7P-1A 20 $4,635 $125 $4,510 $424 10.6P-1B 20 $4,635 $125 $4,510 $424 10.6SP-1 7.5 $1,971 $90 $1,881 $291 6.5SP-2 7.5 $1,971 $90 $1,881 $291 6.5P-3A 20 $5,281 $125 $5,156 $8,782 0.6P-3B 20 $5,281 $125 $5,156 $8,782 0.6
TOTAL Totals: $75,570 $1,640 $73,930 $20,174 3.7
MOTOR REPLACEMENT SUMMARY
Installation Cost ($): $75,570
NJ Smart Start Equipment Incentive ($): $1,640
Net Installation Cost ($): $73,930
Maintenance Savings ($/Yr): $0
Energy Savings ($/Yr): $20,174
Total Yearly Savings ($/Yr): $20,174
Estimated ECM Lifetime (Yr): 20
Simple Payback 3.7
Simple Lifetime ROI 445.8%
Simple Lifetime Maintenance Savings $0
Simple Lifetime Savings $403,487
Internal Rate of Return (IRR) 27%
Net Present Value (NPV) $226,213.16
ECM #5 - ENERGY SAVINGS SUMMARY
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 26 of 31
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 27 of 31
ECM #6: Digital Energy Management System (DDC EMS) Description:
The unit ventilators in the original sections are controlled locally via central pneumatic control systems. The remainder of the HVAC systems throughout the school is controlled via electronic thermostats within rooms which are connected to a BMS system for that area. Also the cafeteria and gymnasium were recently converted from pneumatic controls to electronic controls.
Concord Engineering recommends installing a DDC system throughout the school to control the entire HVAC systems including the unit ventilators in the classrooms, indoor air handling units, rooftop units and roof exhaust fans. The system will include new temperature sensors and new local thermostats with limited over-ride capability, a front end computer and main controller. The system will also include central controls for lighting. With the communication between the control devices and the front end computer interface, the facility manager will be able to take advantage of scheduling for occupied and unoccupied periods based on the actual occupancy of each space in the facility. Due to the fact that the building may have diverse hours of occupancy, including evening and weekend activities, having supervisory control over all of the equipment makes sense. The DDC system will also aid in the response time to service / maintenance issues when the facility is not under normal maintenance supervision, i.e. after-hours. The new DDC system has the potential to provide significant savings by controlling the HVAC systems as a whole and provide operating schedules and features such as space averaging, night set-back, temperature override control, etc. The U.S. Department of Energy sponsored a study to analyze energy savings achieved through various types of building system controls. The referenced savings is based on the “Advanced Sensors and Controls for Building Applications: Market Assessment and Potential R&D Pathways,” document posted for public use April 2005. The study has found that commercial buildings have the potential to achieve significant energy savings through the use of building controls. The average energy savings are as follows based on the referenced report:
Energy Management and Control System Savings: 5%-15%. Savings resulting from the implementation of this ECM for energy management controls are estimated to be 10% of the electricity and 10% for the natural gas utility in this building.
The basis for the DDC system expansion is the Automated Logic Energy Management System or similar. Energy Savings Calculations:
Energy savings for each utility is calculated with the equation below.
EnergySavings Utility CurrentEnergyConsumption EstimatedSavings,%
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 28 of 31
Following table summarizes energy savings for this facility via implementation of an Energy Management System:
Demand savings due to implementation of this ECM is minimal. The cost of a full DDC system with new field devices, controllers, computer, software, programming, etc. is approximately $3.75 per SF in accordance with recent Contractor pricing for systems of this magnitude. Savings from the implementation of this ECM will be from the reduced energy consumption currently used by the HVAC system by proper control of schedule and temperatures via the DDC system.
ECM INPUTS EXISTING PROPOSED SAVINGS
ECM INPUTSExisting Controls w/ Local Thermostats
DDC Controls
Existing Nat Gas Usage (Therms)
45,884 -
Existing Electricity Usage (kWh)
820,770 -
Energy Savings, Nat Gas - 10%
Energy Savings, Electricity - 10%
Gas Cost ($/Therm) $0.98 $0.98
Electricity Cost ($/kWh) $0.154 $0.154
ECM RESULTS EXISTING PROPOSED SAVINGS
Nat Gas Usage (Therms) 45,884 41,296 4,588
Electricity Usage (kWh) 820,770 738,693 82,077
Nat Gas Cost ($) $44,966 $40,470 $4,497
Electricity Cost ($) $126,399 $113,759 $12,640
Energy Cost ($) $171,365 $154,229 $17,137
COMMENTS:
DDC ENERGY MANAGEMENT SYSYEM CALCULATIONS
ENERGY SAVINGS CALCULATIONS
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 29 of 31
Cost of complete DDC System = ($3.75/SF x 109,742 SF) = $412,000 Currently, there are no prequalified NJ SmartSmart Incentives for installation of the DDC system. Energy Savings Summary:
Installation Cost ($): $412,000
NJ Smart Start Equipment Incentive ($): $0
Net Installation Cost ($): $412,000
Maintenance Savings ($/Yr): $0
Energy Savings ($/Yr): $17,137
Total Yearly Savings ($/Yr): $17,137
Estimated ECM Lifetime (Yr): 15
Simple Payback 24.0
Simple Lifetime ROI -37.6%
Simple Lifetime Maintenance Savings 0
Simple Lifetime Savings $257,055
Internal Rate of Return (IRR) -5%
Net Present Value (NPV) ($207,419.61)
ECM #6 - ENERGY SAVINGS SUMMARY
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 30 of 31
REM #1: 438.51 kW Solar System Description: The Ann A. Mullen Middle School has available roof and parking lot space that could accommodate a significant amount of solar generation. Based on the available areas a 438.51 kilowatt solar array could be installed, assuming the existing roof structure is capable of supporting an array. The array will produce approximately 541,878 kilowatt-hours annually that will reduce the overall electric usage of the facility by 26.23%. Energy Savings Calculations: See Renewable / Distributed Energy Measures Calculations Appendix for detailed financial summary and proposed solar layout areas. Financial results in table below are based on 100% financing of the system over a fifteen year period. Energy Savings Summary:
System Size (KWDC): 438.51
Electric Generation (KWH/Yr): 541,878
Installation Cost ($): $2,548,057
SREC Revenue ($/Yr): $103,545
Energy Savings ($/Yr): $83,449
Total Yearly Savings ($/Yr): $186,994
ECM Analysis Period (Yr): 15
Simple Payback (Yrs): 13.6
Analysis Period Electric Savings ($): $1,552,065
Analysis Period SREC Revenue ($): $1,499,967
Net Present Value (NPV) ($633,743.88)
REM #1 - ENERGY SAVINGS SUMMARY
Gloucester Township BOE – Ann A. Mullen Middle School Energy Audit
Concord Engineering Group, Inc. 9C12010 August 2, 2012– FINAL Page 31 of 31
V. ADDITIONAL RECOMMENDATIONS The following recommendations include no cost/low cost measures, Operation & Maintenance (O&M) items, and water conservation measures with attractive paybacks. These measures are not eligible for the Smart Start Buildings incentives from the office of Clean Energy but save energy none the less.
A. Chemically clean the condenser and evaporator coils periodically to optimize efficiency. Poorly maintained heat transfer surfaces can reduce efficiency 5-10%.
B. Maintain all weather stripping on windows and doors.
C. Clean all light fixtures to maximize light output.
D. Provide more frequent air filter changes to decrease overall system power usage and maintain better IAQ.
E. Turn off computers when not in use. Ensure computers are not running in screen saver mode which saves the monitor screen not energy.
F. Ensure outside air dampers are functioning properly and only open during occupied mode.
Appendix Energy Audit
Concord Engineering Group, Inc.
APPENDIX A
APPENDIX A1 of 1
LIFETIME ENERGY SAVINGS
LIFETIME MAINTENANCE
SAVINGSLIFETIME ROI SIMPLE PAYBACK
INTERNAL RATE OF RETURN (IRR)
NET PRESENT VALUE (NPV)
MATERIAL LABORREBATES,
INCENTIVES
NET INSTALLATION
COSTENERGY MAINT. / SREC TOTAL (Yearly Saving * ECM Lifetime)
(Yearly Maint Svaing * ECM Lifetime)
(Lifetime Savings - Net Cost) / (Net Cost)
(Net cost / Yearly Savings)
($) ($) ($) ($) ($/Yr) ($/Yr) ($/Yr) (Yr) ($) ($) (%) (Yr) ($) ($)
ECM #1 General Lighting Upgrade $48,603 $0 $15,190 $33,413 $15,143 $0 $15,143 15 $227,145 $0 579.8% 2.2 45.15% $147,363.15
ECM #2 Gym/Café & Other Lighting Upgrades $26,080 $0 $7,400 $18,680 $4,081 $0 $4,081 15 $61,215 $0 227.7% 4.6 20.52% $30,038.71
ECM #3 Lighting Controls Upgrade $34,000 $0 $2,790 $31,210 $5,157 $0 $5,157 15 $77,355 $0 147.9% 6.1 14.30% $30,353.93
ECM #4 Rooftop Unit Replacements $62,250 $35,500 $3,863 $93,887 $5,648 $0 $5,648 15 $84,719 $0 -9.8% 16.6 -1.26% ($26,462.01)
ECM #5 NEMA Premium Motor Replacements $75,570 $0 $1,640 $73,930 $20,174 $0 $20,174 20 $403,487 $0 445.8% 3.7 27.06% $226,213.16
ECM #6 DDC System Expansion $412,000 $0 $0 $412,000 $17,137 $0 $17,137 15 $257,055 $0 -37.6% 24.0 -5.39% ($207,419.61)
REM #1 438.51 KW PV System $2,548,057 $0 $0 $2,548,057 $83,449 $103,545 $186,994 15 $2,804,906 $1,553,168 10.1% 13.6 1.23% ($315,738.01)
Notes: 1) The variable Cn in the formulas for Internal Rate of Return and Net Present Value stands for the cash flow during each period.2) The variable DR in the NPV equation stands for Discount Rate3) For NPV and IRR calculations: From n=0 to N periods where N is the lifetime of ECM and Cn is the cash flow during each period .
REM RENEWABLE ENERGY AND FINANCIAL COSTS AND SAVINGS SUMMARY
ECM COST & SAVINGS BREAKDOWN
CONCORD ENGINEERING GROUP
Gloucester Township BOE - Anna A. Mullen Middle School
INSTALLATION COST YEARLY SAVINGS
ECM LIFETIMEDESCRIPTIONECM NO.
ECM ENERGY AND FINANCIAL COSTS AND SAVINGS SUMMARY
Appendix Energy Audit
Concord Engineering Group, Inc.
APPENDIX B
Appendix B Page 1 of 4
Concord Engineering Group, Inc. 520 BURNT MILL ROAD VOORHEES, NEW JERSEY 08043 PHONE: (856) 427-0200 FAX: (856) 427-6508
SmartStart Building Incentives The NJ SmartStart Buildings Program offers financial incentives on a wide variety of building system equipment. The incentives were developed to help offset the initial cost of energy-efficient equipment. The following tables show the current available incentives as of February 15, 2011:
Electric Chillers Water-Cooled Chillers $12 - $170 per ton
Air-Cooled Chillers $8 - $52 per ton
Energy Efficiency must comply with ASHRAE 90.1-2007
Gas Cooling Gas Absorption Chillers $185 - $400 per ton
Gas Engine-Driven Chillers Calculated through custom measure
path)
Desiccant Systems $1.00 per cfm – gas or electric
Electric Unitary HVAC Unitary AC and Split Systems $73 - $92 per ton
Air-to-Air Heat Pumps $73 - $92 per ton Water-Source Heat Pumps $81 per ton
Packaged Terminal AC & HP $65 per ton Central DX AC Systems $40- $72 per ton
Dual Enthalpy Economizer Controls $250 Occupancy Controlled Thermostat
(Hospitality & Institutional Facility) $75 per thermostat
Energy Efficiency must comply with ASHRAE 90.1-2007
Gas Heating
Gas Fired Boilers < 300 MBH $300 per unit
Gas Fired Boilers ≥ 300 - 1500 MBH $1.75 per MBH
Gas Fired Boilers ≥1500 - ≤ 4000 MBH $1.00 per MBH
Gas Fired Boilers > 4000 MBH (Calculated through Custom Measure
Path)
Gas Furnaces $300 - $400 per unit, AFUE ≥ 92%
Appendix B Page 2 of 4
Ground Source Heat Pumps
Closed Loop $450 per ton, EER ≥ 16 $600 per ton, EER ≥ 18 $750 per ton, EER ≥ 20
Energy Efficiency must comply with ASHRAE 90.1-2007
Variable Frequency Drives Variable Air Volume $65 - $155 per hp
Chilled-Water Pumps $60 per VFD rated hp
Compressors $5,250 to $12,500 per drive
Cooling Towers ≥ 10 hp $60 per VFD rated hp
Natural Gas Water Heating
Gas Water Heaters ≤ 50 gallons, 0.67 energy factor or better
$50 per unit
Gas-Fired Water Heaters > 50 gallons $1.00 - $2.00 per MBH
Gas-Fired Booster Water Heaters $17 - $35 per MBH
Gas Fired Tankless Water Heaters $300 per unit
Prescriptive Lighting Retro fit of T12 to T-5 or T-8 Lamps
w/Electronic Ballast in Existing Facilities
$10 per fixture (1-4 lamps)
Replacement of T12 with new T-5 or T-8 Lamps w/Electronic Ballast in
Existing Facilities $25 per fixture (1-4 lamps)
Replacement of incandescent with screw-in PAR 38 or PAR 30 (CFL)
bulb $7 per bulb
T-8 reduced Wattage (28w/25w 4’, 1-4 lamps)
Lamp & ballast replacement $10 per fixture
Hard-Wired Compact Fluorescent $25 - $30 per fixture
Metal Halide w/Pulse Start Including Parking Lot
$25 per fixture
T-5 and T-8 High Bay Fixtures $16 - $200 per fixture
HID ≥ 100w Retrofit with induction lamp, power coupler and generator
(must be 30% less watts/fixture than HID system)
$50 per fixture
HID ≥ 100w Replacement with new HID ≥ 100w
$70 per fixture
Appendix B Page 3 of 4
Prescriptive Lighting - LED
LED New Exit Sign Fixture Existing Facility < 75 kw Existing Facility > 75 kw
$20 per fixture $10 per fixture
LED Display Case Lighting $30 per display case
LED Shelf-Mtd. Display & Task Lights $15 per linear foot
LED Portable Desk Lamp $20 per fixture
LED Wall-wash Lights $30 per fixture
LED Recessed Down Lights $35 per fixture LED Outdoor Pole/Arm-Mounted Area
and Roadway Luminaries $175 per fixture
LED Outdoor Pole/Arm-Mounted Decorative Luminaries
$175 per fixture
LED Outdoor Wall-Mounted Area Luminaries
$100 per fixture
LED Parking Garage Luminaries $100 per fixture
LED Track or Mono-Point Directional Lighting Fixtures
$50 per fixture
LED High-Bay and Low-Bay Fixtures for Commercial & Industrial Bldgs.
$150 per fixture
LED High-Bay-Aisle Lighting $150 per fixture
LED Bollard Fixtures $50 per fixture
LED Linear Panels (2x2 Troffers only) $100 per fixture
LED Fuel Pump Canopy $100 per fixture
LED Refrigerator/Freezer case lighting replacement of fluorescent in medium
and low temperature display case
$42 per 5 foot $65 per 6 foot
Appendix B Page 4 of 4
Lighting Controls – Occupancy Sensors
Wall Mounted $20 per control Remote Mounted $35 per control
Daylight Dimmers $25 per fixture
Occupancy Controlled hi-low Fluorescent Controls
$25 per fixture controlled
Lighting Controls – HID or Fluorescent Hi-Bay Controls Occupancy hi-low $75 per fixture controlled Daylight Dimming $75 per fixture controlled
Daylight Dimming - office $50 per fixture controlled
Premium Motors Three-Phase Motors $45 - $700 per motor
Fractional HP Motors Electronic Communicated Motors (replacing shaded pole motors in
refrigerator/freezer cases)
$40 per electronic communicated motor
Other Equipment Incentives
Performance Lighting
$1.00 per watt per SF below program incentive threshold, currently 5% more energy efficient than ASHRAE 90.1-
2007 for New Construction and Complete Renovation
Custom Electric and Gas Equipment Incentives
not prescriptive
Custom Measures
$0.16 KWh and $1.60/Therm of 1st year savings, or a buy down to a 1 year
payback on estimated savings. Minimum required savings of 75,000 KWh or 1,500 Therms and a IRR of at
least 10%. Multi Measures Bonus 15%
Appendix Energy Audit
Concord Engineering Group, Inc.
APPENDIX C
OMB No. 2060-0347
STATEMENT OF ENERGY PERFORMANCE2-Ann A. Mullen Middle School
Building ID: 3100642 For 12-month Period Ending: December 31, 20111
Date SEP becomes ineligible: N/A Date SEP Generated: July 03, 2012
Facility2-Ann A. Mullen Middle School1400 Sicklerville RoadSicklerville, NJ 08081
Facility OwnerGloucester Township Public Schools17 Erial Road Blackwood, NJ 08012
Primary Contact for this FacilityJohn Bilodeau17 Erial Road Blackwood, NJ 08012
Year Built: 2002Gross Floor Area (ft2): 173,342
Energy Performance Rating2 (1-100) 15
Site Energy Use Summary3
Electricity - Grid Purchase(kBtu) 7,049,346 Natural Gas (kBtu)4 8,409,800 Total Energy (kBtu) 15,459,146
Energy Intensity4 Site (kBtu/ft2/yr) 89 Source (kBtu/ft2/yr) 187 Emissions (based on site energy use) Greenhouse Gas Emissions (MtCO2e/year) 1,446 Electric Distribution Utility Atlantic City Electric Co [Pepco Holdings Inc] National Median Comparison National Median Site EUI 63 National Median Source EUI 131 % Difference from National Median Source EUI 42% Building Type K-12
School
Stamp of Certifying Professional
Based on the conditions observed at thetime of my visit to this building, I certify that
the information contained within thisstatement is accurate.
Meets Industry Standards5 for Indoor EnvironmentalConditions:Ventilation for Acceptable Indoor Air Quality N/A Acceptable Thermal Environmental Conditions N/A Adequate Illumination N/A
Certifying ProfessionalMichael Fischette520 South Burnt Mill Road Voorhees, NJ 08043
Notes: 1. Application for the ENERGY STAR must be submitted to EPA within 4 months of the Period Ending date. Award of the ENERGY STAR is not final until approval is received from EPA.2. The EPA Energy Performance Rating is based on total source energy. A rating of 75 is the minimum to be eligible for the ENERGY STAR.3. Values represent energy consumption, annualized to a 12-month period.4. Values represent energy intensity, annualized to a 12-month period.5. Based on Meeting ASHRAE Standard 62 for ventilation for acceptable indoor air quality, ASHRAE Standard 55 for thermal comfort, and IESNA Lighting Handbook for lighting quality.
The government estimates the average time needed to fill out this form is 6 hours (includes the time for entering energy data, Licensed Professional facility inspection, and notarizing the SEP) andwelcomes suggestions for reducing this level of effort. Send comments (referencing OMB control number) to the Director, Collection Strategies Division, U.S., EPA (2822T), 1200 Pennsylvania Ave.,NW, Washington, D.C. 20460.
EPA Form 5900-16
ENERGY STAR®
Data Checklistfor Commercial Buildings
In order for a building to qualify for the ENERGY STAR, a Professional Engineer (PE) or a Registered Architect (RA) must validate the accuracy of the data underlyingthe building's energy performance rating. This checklist is designed to provide an at-a-glance summary of a property's physical and operating characteristics, as well asits total energy consumption, to assist the PE or RA in double-checking the information that the building owner or operator has entered into Portfolio Manager.
Please complete and sign this checklist and include it with the stamped, signed Statement of Energy Performance.NOTE: You must check each box to indicate that each value is correct, OR include a note.
CRITERION VALUE AS ENTERED INPORTFOLIO MANAGER VERIFICATION QUESTIONS NOTES
Building Name 2-Ann A. Mullen Middle
School Is this the official building name to be displayed inthe ENERGY STAR Registry of LabeledBuildings?
Type K-12 School Is this an accurate description of the space inquestion?
Location 1400 Sicklerville Road,Sicklerville, NJ 08081
Is this address accurate and complete? Correctweather normalization requires an accurate zipcode.
Single Structure Single Facility
Does this SEP represent a single structure? SEPscannot be submitted for multiple-buildingcampuses (with the exception of a hospital, k-12school, hotel and senior care facility) nor can theybe submitted as representing only a portion of abuilding.
2-Ann A. Mullen (K-12 School)
CRITERION VALUE AS ENTERED INPORTFOLIO MANAGER VERIFICATION QUESTIONS NOTES
Gross Floor Area 173,342 Sq. Ft.
Does this square footage include all supportingfunctions such as kitchens and break rooms usedby staff, storage areas, administrative areas,elevators, stairwells, atria, vent shafts, etc. Alsonote that existing atriums should only include thebase floor area that it occupies. Interstitial(plenum) space between floors should not beincluded in the total. Finally gross floor area is notthe same as leasable space. Leasable space is asubset of gross floor area.
Open Weekends? No
Is this building normally open at all on theweekends? This includes activities beyond thework conducted by maintenance, cleaning, andsecurity personnel. Weekend activity could includeany time when the space is used for classes,performances or other school or communityactivities. If the building is open on the weekend aspart of the standard schedule during one or moreseasons, the building should select ?yes? for openweekends. The ?yes? response should applywhether the building is open for one or both of theweekend days.
Number of PCs 200 Is this the number of personal computers in theK12 School?
Number of walk-inrefrigeration/freezer
units 2
Is this the total number of commercial walk-in typefreezers and coolers? These units are typicallyfound in storage and receiving areas.
Presence ofcooking facilities Yes
Does this school have a dedicated space in whichfood is prepared and served to students? If theschool has space in which food for students is onlykept warm and/or served to students, or has only agalley that is used by teachers and staff then theanswer is "no".
Percent Cooled 100 % Is this the percentage of the total floor space withinthe facility that is served by mechanical coolingequipment?
Percent Heated 100 % Is this the percentage of the total floor space withinthe facility that is served by mechanical heatingequipment?
Months 10(Optional) Is this school in operation for at least 8 months ofthe year?
Page 1 of 4
High School? No
Is this building a high school (teaching grades 10,11, and/or 12)? If the building teaches to highschool students at all, the user should check 'yes'to 'high school'. For example, if the school teachesto grades K-12 (elementary/middle and highschool), the user should check 'yes' to 'highschool'.
Page 2 of 4
ENERGY STAR®
Data Checklistfor Commercial Buildings
Energy ConsumptionPower Generation Plant or Distribution Utility: Atlantic City Electric Co [Pepco Holdings Inc]
Fuel Type: Electricity
Meter: Electric (kWh (thousand Watt-hours))Space(s): Entire Facility
Generation Method: Grid Purchase
Start Date End Date Energy Use (kWh (thousand Watt-hours))
12/01/2011 12/31/2011 134,240.00
11/01/2011 11/30/2011 116,334.00
10/01/2011 10/31/2011 193,560.00
09/01/2011 09/30/2011 191,096.00
08/01/2011 08/31/2011 212,164.00
07/01/2011 07/31/2011 225,249.00
06/01/2011 06/30/2011 225,958.00
05/01/2011 05/31/2011 171,407.00
04/01/2011 04/30/2011 154,030.00
03/01/2011 03/31/2011 144,905.00
02/01/2011 02/28/2011 139,055.00
01/01/2011 01/31/2011 158,047.00
Electric Consumption (kWh (thousand Watt-hours)) 2,066,045.00
Electric Consumption (kBtu (thousand Btu)) 7,049,345.54
Total Electricity (Grid Purchase) Consumption (kBtu (thousand Btu)) 7,049,345.54
Is this the total Electricity (Grid Purchase) consumption at this building including allElectricity meters?
Fuel Type: Natural Gas
Meter: Gas (therms)Space(s): Entire Facility
Start Date End Date Energy Use (therms)
12/01/2011 12/31/2011 10,793.00
11/01/2011 11/30/2011 6,308.00
10/01/2011 10/31/2011 1,870.00
09/01/2011 09/30/2011 614.00
08/01/2011 08/31/2011 622.00
07/01/2011 07/31/2011 633.00
06/01/2011 06/30/2011 879.00
05/01/2011 05/31/2011 1,499.00
04/01/2011 04/30/2011 9,284.00
03/01/2011 03/31/2011 11,605.00
Page 3 of 4
02/01/2011 02/28/2011 16,685.00
01/01/2011 01/31/2011 23,306.00
Gas Consumption (therms) 84,098.00
Gas Consumption (kBtu (thousand Btu)) 8,409,800.00
Total Natural Gas Consumption (kBtu (thousand Btu)) 8,409,800.00
Is this the total Natural Gas consumption at this building including all Natural Gas meters?
Additional FuelsDo the fuel consumption totals shown above represent the total energy use of this building?Please confirm there are no additional fuels (district energy, generator fuel oil) used in this facility.
On-Site Solar and Wind EnergyDo the fuel consumption totals shown above include all on-site solar and/or wind power located atyour facility? Please confirm that no on-site solar or wind installations have been omitted from thislist. All on-site systems must be reported.
Certifying Professional (When applying for the ENERGY STAR, the Certifying Professional must be the same PE or RA that signed and stamped the SEP.)
Name: _____________________________________________ Date: _____________
Signature: ______________________________________ Signature is required when applying for the ENERGY STAR.
Page 4 of 4
FOR YOUR RECORDS ONLY. DO NOT SUBMIT TO EPA.
Please keep this Facility Summary for your own records; do not submit it to EPA. Only the Statement of Energy Performance(SEP), Data Checklist and Letter of Agreement need to be submitted to EPA when applying for the ENERGY STAR.
Facility2-Ann A. Mullen Middle School1400 Sicklerville RoadSicklerville, NJ 08081
Facility OwnerGloucester Township Public Schools17 Erial Road Blackwood, NJ 08012
Primary Contact for this FacilityJohn Bilodeau17 Erial Road Blackwood, NJ 08012
General Information2-Ann A. Mullen Middle School
Gross Floor Area Excluding Parking: (ft2) 173,342 Year Built 2002 For 12-month Evaluation Period Ending Date: December 31, 2011
Facility Space Use Summary2-Ann A. Mullen
Space Type K-12 School
Gross Floor Area (ft2) 173,342
Open Weekends? No
Number of PCs 200
Number of walk-in refrigeration/freezerunits 2
Presence of cooking facilities Yes
Percent Cooled 100
Percent Heated 100
Months o 10
High School? No
School District o N/A
Energy Performance ComparisonEvaluation Periods Comparisons
Performance Metrics Current(Ending Date 12/31/2011)
Baseline(Ending Date 12/31/2011) Rating of 75 Target National Median
Energy Performance Rating 15 15 75 N/A 50
Energy Intensity
Site (kBtu/ft2) 89 89 49 N/A 63
Source (kBtu/ft2) 187 187 103 N/A 131
Energy Cost
$/year N/A N/A N/A N/A N/A
$/ft2/year N/A N/A N/A N/A N/A
Greenhouse Gas Emissions
MtCO2e/year 1,446 1,446 796 N/A 1,018
kgCO2e/ft2/year 8 8 4 N/A 6
More than 50% of your building is defined as K-12 School. Please note that your rating accounts for all of the spaces listed. The National Median column presentsenergy performance data your building would have if your building had a median rating of 50. Notes:o - This attribute is optional.d - A default value has been supplied by Portfolio Manager.
20112-Ann A. Mullen Middle School1400 Sicklerville RoadSicklerville, NJ 08081
Portfolio Manager Building ID: 3100642
The energy use of this building has been measured and compared to other similar buildings using theEnvironmental Protection Agency’s (EPA’s) Energy Performance Scale of 1–100, with 1 being the least energyefficient and 100 the most energy efficient. For more information, visit energystar.gov/benchmark.
This building’sscore
15
100
Most Efficient
This building uses 187 kBtu per square foot per year.*
*Based on source energy intensity for the 12 month period ending December 2011
Date of certification
Date Generated: 07/03/2012
Statement ofEnergy Performance
1
Least Efficient
50
Median
Buildings with a score of75 or higher may qualifyfor EPA’s ENERGY STAR.
I certify that the information contained within this statement is accurate and in accordance with U.S.Environmental Protection Agency’s measurement standards, found at energystar.gov
Appendix Energy Audit
Concord Engineering Group, Inc.
APPENDIX D
Appendix D
Page 1 of 8
AC UnitsTag CU-1 RTU-1 RTU-2,3
Unit TypeRefrigeration
Condensing UnitRooftop Unit Rooftop Unit
Qty 1 1 2
Location Rooftop Roof Roof
Area Served Kitchen Teachers LoungBoys/Girls Locker
Room
Manufacturer Russell Lennox Lennox
Model # MLD400L44 GCS16-1353-270-7G GCS24-813-130-1G
Serial # M95 02175-011 - 5695G 01285
Cooling Type DX, R404A DX, R-22 DX, R-22
Cooling Capacity (Tons) - 10 Tons 6.5 Tons
Cooling Efficiency (SEER/EER)
- 9 EER 9.5 EER
Heating Type N/A Gas Fired HX Gas Fired HX
Heating Input (MBH) N/A 270 MBH 130 MBH
Efficiency N/A 80% 80%
Fuel N/A Nat Gas Nat Gas
Approx Age 17 17 17
ASHRAE Service Life 15 15 15
Remaining Life (2) (2) (2)
Comments
Note:
MAJOR EQUIPMENT LISTConcord Engineering Group
Ann A. Mullen Middle School
"N/A" = Not Applicable. "-" = Info Not Available
Appendix D
Page 2 of 8
AC UnitsTag
Unit Type
Qty
Location
Area Served
Manufacturer
Model #
Serial #
Cooling Type
Cooling Capacity (Tons)
Cooling Efficiency (SEER/EER)
Heating Type
Heating Input (MBH)
Efficiency
Fuel
Approx Age
ASHRAE Service Life
Remaining Life
Comments
Note:
"N/A" = Not Applicable. "-" = Info Not Available
CU-2 AHU-1 RTU-4,5Air Cooled Condensing
UnitOutdoor Air Handler Rooftop Unit
1 1 2
Roof Roof Roof
Tech Labs Tech Lab B43Vocal Music B-34/Inst
Music B-35
McQuay McQuay Lennox
ALP016C RDS 708BY GCS24-653-130-1G
55G8504002 35F01393 03 5695C 03581
DX, R-22McQuay Air Cooled
CondenserDX, R-22
16 Tons 2000-8000 CFM 5 Tons
9 EER - 10 SEER
N/A Reznor Duct Heater Gas Fired HX
N/A No Tag 130 MBH
N/A 80% 80%
N/A Nat Gas Nat Gas
17 17 17
15 15 15
(2) (2) (2)
Appendix D
Page 3 of 8
BoilersTag
Unit TypeCast Iron Sectional
BoilersCast Iron Sectional
Boilers
Qty 2 1
Location Mechanical Room Mechanical Room
Area Served Hot Water LoopHot Water Loop New
Wing
Manufacturer H.B. Smith H.B. Smith
Model # Series 28A-14 Series 28A-S/W-5
Serial # N95-220 N2002-1416
Input Capacity (Btu/Hr) - -
Rated Output Capacity (Btu/Hr)
3,563 1,166
Approx. Efficiency % 75.0% 80.0%
Fuel Nat Gas Nat Gas
Approx Age 17 10
ASHRAE Service Life 35 35 35
Remaining Life 18 25 35
Comments Cyclonetic Burner: JB2G-15-RM7895C-L20-UL
Power Flame Boiler: JR50A-15
Note:
MAJOR EQUIPMENT LIST
Concord Engineering Group
Ann A. Mullen Middle School
"N/A" = Not Applicable. "-" = Info Not Available
Appendix D
Page 4 of 8
Cooling TowerTag CH-1
Unit Type Water Chiller
Qty 1
Location Mechanical Room
Area Served Chilled Water Loop
Manufacturer Trane
Model # CVHE320
Serial # L02K19805
Refrigerant R-123
Cooling Capacity (Tons) 320 Tons
Cooling Efficiency (KW/Ton)
0.54375
Volts / Phase / Hz 460/3/60
Fuel R-123
Chilled Water GPM / ΔT - / 10°ΔT
Condenser Water GPM / ΔT
1760 GPM / 10°ΔT
Approx Age 10
ASHRAE Service Life 20
Remaining Life 10
Comments
Note:
MAJOR EQUIPMENT LISTConcord Engineering Group
Ann A. Mullen Middle School
"N/A" = Not Applicable. "-" = Info Not Available
Appendix D
Page 5 of 8
Cooling TowerTag
Unit Type Cooling Tower
Qty 1
Location Outside Mech Room
Area Served Condenser Water Loop
Manufacturer Imeco
Model # IMC1218590-1-40
Serial # 6661-1
Rated Flow GPM -
EWT / LWT -
Motor HP 40 HP
Electrical 460/3/60
Approx Age 17
ASHRAE Service Life 20
Remaining Life 3
Comments
Note:
MAJOR EQUIPMENT LIST
Concord Engineering Group
Ann A. Mullen Middle School
"N/A" = Not Applicable. "-" = Info Not Available
Appendix D
Page 6 of 8
Domestic Water HeatersTag
Unit TypeGas Fired Hot Water
Heater
Qty 2
Location Mechanical Room
Area Served Domestic Loop
Manufacturer Bradford White
Model # D100L3003NA
Serial # FG12190387
Size (Gallons) 100 Gallons
Input Capacity (MBH/KW)
300 MBH
Recovery (Gal/Hr) 290.0 GPH
Efficiency % 80%
Fuel Nat Gas
Approx Age 3
ASHRAE Service Life 12
Remaining Life 9
Comments
Note:
MAJOR EQUIPMENT LIST
Concord Engineering Group
Ann A. Mullen Middle School
"N/A" = Not Applicable. "-" = Info Not Available
Appendix D
Page 7 of 8
PumpsTag P-1A,1B CHWP-1,2 CWP-1,2
Unit Type Hot Water Pumps Chilled Water PumpsCondenser Water
Pumps
Qty 2 2 2
Location Mechanical Room Mechanical Room Mechanical Room
Area Served Hot Water Loop Chilled Water Loop Condenser Water Loop
Manufacturer Taco Taco Taco
Model # FE3013E2J1G2L0A - FE6013E2N1G2LOA
Serial # 158692 - 58892
Horse Power 20 HP 60 HP 50 HP
Flow459 GPM @ 115
FTHD-
1760 GPM @ 78 FTHD
Motor Info Baldor Baldor Baldor
Electrical Power 230/460/3/60 230/460/3/60 230/460/3/60
RPM 1760 RPM 1760 RPM 1760 RPM
Motor Efficiency % 88.5% 91.7% 91.7%
Approx Age 17 17 17
ASHRAE Service Life 20 20 20
Remaining Life 3 3 3
Comments
Note:
MAJOR EQUIPMENT LISTConcord Engineering Group
Ann A. Mullen Middle School
"N/A" = Not Applicable. "-" = Info Not Available
Appendix D
Page 8 of 8
PumpsTag
Unit Type
Qty
Location
Area Served
Manufacturer
Model #
Serial #
Horse Power
Flow
Motor Info
Electrical Power
RPM
Motor Efficiency %
Approx Age
ASHRAE Service Life
Remaining Life
Comments
Note:
"N/A" = Not Applicable. "-" = Info Not Available
SP-1,2 P-3A,3BInline Secondary Hot
Water PumpsInline Secondary
Chilled Water Pumps
2 2
Mechanical Room Mechanical Room
Hot Water Loop New Addition
Chilled Water Loop New Addition
Bell & Gossett Bell & Gossett
80 Series -
CP3062 01 A30 -
7.5 HP 20 HP
90 GPM @ 90 FTHD278 GPM @ 127
FTHD
Marathon Electric US Electric Motors
208-230/460/3/60 208-230/460/3/60
1745 RPM 3485 RPM
84.0% 87.5%
10 10
20 20
10 10
Appendix Energy Audit
Concord Engineering Group, Inc.
APPENDIX E
CEG Project #:
Facility Name:
Address:
City, State, Zip
Fixture Reference #
LocationAverage
Burn Hours
DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Work Description Equipment DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Energy Savings,
kW
Energy Savings,
kWh
Energy Savings, $
Control Ref #
Controls DescriptionQty of
Controls
Hour Reduction
%
Energy Savings,
kWh
Energy Savings, $
31 Storage A11 6002-Lamp T8 F032 4100k
1x4 Pendant Mount Prismatic Lens
2 55 8 0.44 264 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 8 0.34 202 0.10 62 $10 0 No New Controls 0 0.0% 0 $0
3 Nurse A14 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 6 0.65 1,685 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 6 0.50 1,310 0.14 374 $58 0 No New Controls 0 0.0% 0 $0
33 Nurse Waiting A13 2600
2-Lamp T8 F032 4100k 1x4 Side Wall Mount Prismatic Lens Vanity
Fixture
2 55 3 0.17 429 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 3 0.13 328 0.04 101 $16 0 No New Controls 0 0.0% 0 $0
33 Nurse Toilet A15 1200
2-Lamp T8 F032 4100k 1x4 Side Wall Mount Prismatic Lens Vanity
Fixture
2 55 1 0.06 66 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 1 0.04 50 0.01 16 $2 5
Dual Technology Occupancy Sensor - Switch
Mnt.1 20.0% 10 $2
10 Nurse Storage A12 6002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 1 0.06 33 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 1 0.04 25 0.01 8 $1 0 No New Controls 0 0.0% 0 $0
3Nurse Exam Room
A102600
4-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 2 0.22 562 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 2 0.17 437 0.05 125 $19 5Dual Technology
Occupancy Sensor - Switch Mnt.
1 20.0% 87 $13
3 Nurse Office A9 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 2 0.22 562 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 2 0.17 437 0.05 125 $19 5Dual Technology
Occupancy Sensor - Switch Mnt.
1 20.0% 87 $13
5 Work Room A16 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 4 0.33 863
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 4 0.17 437 0.16 426 $66 0 No New Controls 0 0.0% 0 $0
32 Work Room A16 2600 2 Lamp 17W CFL High Hat 2 34 1 0.03 88 Existing to Remain 0 2 34 0 0.03 88 0.00 0 $0 0 No New Controls 0 0.0% 0 $0
10 Storage A8 6002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 3 0.17 99 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 3 0.13 76 0.04 23 $4 0 No New Controls 0 0.0% 0 $0
5 Mail Room A17 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 2 0.17 432
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 2 0.08 218 0.08 213 $33 5Dual Technology
Occupancy Sensor - Switch Mnt.
1 20.0% 44 $7
32 Office Corridor A21 3000 2 Lamp 17W CFL High Hat 2 34 5 0.17 510 Existing to Remain 0 2 34 0 0.17 510 0.00 0 $0 0 No New Controls 0 0.0% 0 $0
7 Conference Room A7 26003-Lamp T8 FO32 4100K 2x4 Recessed Parabolic
Lens3 83 3 0.25 647
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 3 0.13 328 0.12 320 $49 4Dual Technology
Occupancy Sensor - Remote Mnt.
0.5 20.0% 66 $10
32 Conference Room A7 2600 2 Lamp 17W CFL High Hat 2 34 6 0.20 530 Existing to Remain 0 2 34 0 0.20 530 0.00 0 $0 4Dual Technology
Occupancy Sensor - Remote Mnt.
0.5 20.0% 106 $16
7 Principal A6 26003-Lamp T8 FO32 4100K 2x4 Recessed Parabolic
Lens3 83 4 0.33 863
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 4 0.17 437 0.16 426 $66 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 87 $13
3 Vice Principal 1 A20 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 2 0.22 562 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 2 0.17 437 0.05 125 $19 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 87 $13
3 Vice Principal 2 A22 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 2 0.22 562 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 2 0.17 437 0.05 125 $19 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 87 $13
10 Secret Closet A23 6002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 1 0.06 33 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 1 0.04 25 0.01 8 $1 0 No New Controls 0 0.0% 0 $0
3 Public Waiting A5 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 8 0.86 2,246 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 8 0.67 1,747 0.19 499 $77 0 No New Controls 0 0.0% 0 $0
3 Student Waiting A24 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 6 0.65 1,685 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 6 0.50 1,310 0.14 374 $58 0 No New Controls 0 0.0% 0 $0
9C12010
Ann Mullen Middle School
Sicklerville , NJ 08081
Proposed Lighting Controls
1400 Sicklerville Road
Retrofit Energy SavingsExisting Fixtures Proposed Fixtures Retrofit
Appendix E - Lighting Audit - Anna Mullen Middle School.xlsx Page 1
Fixture Reference #
LocationAverage
Burn Hours
DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Work Description Equipment DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Energy Savings,
kW
Energy Savings,
kWh
Energy Savings, $
Control Ref #
Controls DescriptionQty of
Controls
Hour Reduction
%
Energy Savings,
kWh
Energy Savings, $
Proposed Lighting ControlsRetrofit Energy SavingsExisting Fixtures Proposed Fixtures Retrofit
8 Corridor A3 3000
2-Lamp T8 FBO32 4100K U Tube
2x2 Recessed Prismatic Lens
2 55 13 0.72 2,145 Re-lampSylvania Lamp
FBO30/841XP/6//SS/ECO2 49 13 0.64 1,911 0.08 234 $36 0 No New Controls 0 0.0% 0 $0
32 Lobby A2 3000 2 Lamp 17W CFL High Hat 2 34 12 0.41 1,224 Existing to Remain 0 2 34 0 0.41 1,224 0.00 0 $0 0 No New Controls 0 0.0% 0 $0
8 Guidance Secretary C2 2600
2-Lamp T8 FBO32 4100K U Tube
2x2 Recessed Prismatic Lens
2 55 7 0.39 1,001 Re-lampSylvania Lamp
FBO30/841XP/6//SS/ECO2 49 7 0.34 892 0.04 109 $17 0 No New Controls 0 0.0% 0 $0
3 Office C2 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 2 0.22 562 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 2 0.17 437 0.05 125 $19 5Dual Technology
Occupancy Sensor - Switch Mnt.
1 20.0% 87 $13
3 Office C8 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 2 0.22 562 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 2 0.17 437 0.05 125 $19 5Dual Technology
Occupancy Sensor - Switch Mnt.
1 20.0% 87 $13
3 Office C7 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 2 0.22 562 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 2 0.17 437 0.05 125 $19 5Dual Technology
Occupancy Sensor - Switch Mnt.
1 20.0% 87 $13
3 Test C8 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 2 0.22 562 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 2 0.17 437 0.05 125 $19 5Dual Technology
Occupancy Sensor - Switch Mnt.
1 20.0% 87 $13
7 Conf C4 26003-Lamp T8 FO32 4100K 2x4 Recessed Parabolic
Lens3 83 4 0.33 863
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 4 0.17 437 0.16 426 $66 4Dual Technology
Occupancy Sensor - Remote Mnt.
0.5 20.0% 87 $13
32 Conf C4 2600 2 Lamp 17W CFL High Hat 2 34 2 0.07 177 Existing to Remain 0 2 34 0 0.07 177 0.00 0 $0 4Dual Technology
Occupancy Sensor - Remote Mnt.
0.5 20.0% 35 $5
3 Records/Storage C3 6004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 2 0.22 130 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 2 0.17 101 0.05 29 $4 0 No New Controls 0 0.0% 0 $0
33 Toilet A18 1200
2-Lamp T8 F032 4100k 1x4 Side Wall Mount Prismatic Lens Vanity
Fixture
2 55 1 0.06 66 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 1 0.04 50 0.01 16 $2 5
Dual Technology Occupancy Sensor - Switch
Mnt.1 20.0% 10 $2
33 Toilet A19 1200
2-Lamp T8 F032 4100k 1x4 Side Wall Mount Prismatic Lens Vanity
Fixture
2 55 1 0.06 66 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 1 0.04 50 0.01 16 $2 5
Dual Technology Occupancy Sensor - Switch
Mnt.1 20.0% 10 $2
8 Boys Toilet C18 1200
2-Lamp T8 FBO32 4100K U Tube
2x2 Recessed Prismatic Lens
2 55 3 0.17 198 Re-lampSylvania Lamp
FBO30/841XP/6//SS/ECO2 49 3 0.15 176 0.02 22 $3 0 No New Controls 0 0.0% 0 $0
3 Boys Toilet C18 12004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 1 0.11 130 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 1 0.08 101 0.02 29 $4 0 No New Controls 0 0.0% 0 $0
8 Girls Toilet C20 1200
2-Lamp T8 FBO32 4100K U Tube
2x2 Recessed Prismatic Lens
2 55 3 0.17 198 Re-lampSylvania Lamp
FBO30/841XP/6//SS/ECO2 49 3 0.15 176 0.02 22 $3 0 No New Controls 0 0.0% 0 $0
3 Girls Toilet C20 12004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 1 0.11 130 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 1 0.08 101 0.02 29 $4 0 No New Controls 0 0.0% 0 $0
31 Janitor Closet C19 6002-Lamp T8 F032 4100k
1x4 Pendant Mount Prismatic Lens
2 55 1 0.06 33 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 1 0.04 25 0.01 8 $1 0 No New Controls 0 0.0% 0 $0
3Girls Locker Office
A312600
4-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 3 0.32 842 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 3 0.25 655 0.07 187 $29 5Dual Technology
Occupancy Sensor - Switch Mnt.
1 20.0% 131 $20
31 Gym Storage A27 6002-Lamp T8 F032 4100k
1x4 Pendant Mount Prismatic Lens
2 55 4 0.22 132 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 4 0.17 101 0.05 31 $5 0 No New Controls 0 0.0% 0 $0
31Girls Locker Room
A322600
2-Lamp T8 F032 4100k 1x4 Pendant Mount
Prismatic Lens2 55 26 1.43 3,718 Re-lamp
Sylvania LampFO28/841/SS/ECO
2 42 26 1.09 2,839 0.34 879 $135 0 No New Controls 0 0.0% 0 $0
31Girls Locker Storage
A36600
2-Lamp T8 F032 4100k 1x4 Pendant Mount
Prismatic Lens2 55 2 0.11 66 Re-lamp
Sylvania LampFO28/841/SS/ECO
2 42 2 0.08 50 0.03 16 $2 0 No New Controls 0 0.0% 0 $0
Appendix E - Lighting Audit - Anna Mullen Middle School.xlsx Page 2
Fixture Reference #
LocationAverage
Burn Hours
DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Work Description Equipment DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Energy Savings,
kW
Energy Savings,
kWh
Energy Savings, $
Control Ref #
Controls DescriptionQty of
Controls
Hour Reduction
%
Energy Savings,
kWh
Energy Savings, $
Proposed Lighting ControlsRetrofit Energy SavingsExisting Fixtures Proposed Fixtures Retrofit
10Girls Locker Toilet/
Shower A35/331200
2-Lamp T8 FO32 4100K 1x4 Surface Mount
Prismatic Wrap2 55 5 0.28 330 Re-lamp
Sylvania LampFO28/841/SS/ECO
2 42 5 0.21 252 0.07 78 $12 0 No New Controls 0 0.0% 0 $0
3Boys Locker Office
A422600
4-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 3 0.32 842 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 3 0.25 655 0.07 187 $29 5Dual Technology
Occupancy Sensor - Switch Mnt.
1 20.0% 131 $20
31 Gym Storage A46 6002-Lamp T8 F032 4100k
1x4 Pendant Mount Prismatic Lens
2 55 4 0.22 132 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 4 0.17 101 0.05 31 $5 0 No New Controls 0 0.0% 0 $0
31Boys Locker Room
A412600
2-Lamp T8 F032 4100k 1x4 Pendant Mount
Prismatic Lens2 55 26 1.43 3,718 Re-lamp
Sylvania LampFO28/841/SS/ECO
2 42 26 1.09 2,839 0.34 879 $135 0 No New Controls 0 0.0% 0 $0
31Boys Locker Storage
A37600
2-Lamp T8 F032 4100k 1x4 Pendant Mount
Prismatic Lens2 55 2 0.11 66 Re-lamp
Sylvania LampFO28/841/SS/ECO
2 42 2 0.08 50 0.03 16 $2 0 No New Controls 0 0.0% 0 $0
10Boys Locker Toilet/
Shower A40/381200
2-Lamp T8 FO32 4100K 1x4 Surface Mount
Prismatic Wrap2 55 5 0.28 330 Re-lamp
Sylvania LampFO28/841/SS/ECO
2 42 5 0.21 252 0.07 78 $12 0 No New Controls 0 0.0% 0 $0
3 Classroom C9 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom C10 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom C11 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom C12 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom C13 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom C14 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom C15 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom C16 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom C17 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
8 Corridor C1 3000
2-Lamp T8 FBO32 4100K U Tube
2x2 Recessed Prismatic Lens
2 55 12 0.66 1,980 Re-lampSylvania Lamp
FBO30/841XP/6//SS/ECO2 49 12 0.59 1,764 0.07 216 $33 0 No New Controls 0 0.0% 0 $0
31 Boys Toilet D8 12002-Lamp T8 F032 4100k
1x4 Pendant Mount Prismatic Lens
2 55 3 0.17 198 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 3 0.13 151 0.04 47 $7 0 No New Controls 0 0.0% 0 $0
33 Boys Toilet D8 1200
2-Lamp T8 F032 4100k 1x4 Side Wall Mount Prismatic Lens Vanity
Fixture
2 55 2 0.11 132 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 2 0.08 101 0.03 31 $5 0 No New Controls 0 0.0% 0 $0
32 Boys Toilet D8 1200 2 Lamp 17W CFL High Hat 2 34 2 0.07 82 Existing to Remain 0 2 34 0 0.07 82 0.00 0 $0 0 No New Controls 0 0.0% 0 $0
31 Girls Toilet D9 12002-Lamp T8 F032 4100k
1x4 Pendant Mount Prismatic Lens
2 55 3 0.17 198 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 3 0.13 151 0.04 47 $7 0 No New Controls 0 0.0% 0 $0
33 Girls Toilet D9 1200
2-Lamp T8 F032 4100k 1x4 Side Wall Mount Prismatic Lens Vanity
Fixture
2 55 2 0.11 132 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 2 0.08 101 0.03 31 $5 0 No New Controls 0 0.0% 0 $0
Appendix E - Lighting Audit - Anna Mullen Middle School.xlsx Page 3
Fixture Reference #
LocationAverage
Burn Hours
DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Work Description Equipment DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Energy Savings,
kW
Energy Savings,
kWh
Energy Savings, $
Control Ref #
Controls DescriptionQty of
Controls
Hour Reduction
%
Energy Savings,
kWh
Energy Savings, $
Proposed Lighting ControlsRetrofit Energy SavingsExisting Fixtures Proposed Fixtures Retrofit
32 Girls Toilet D9 1200 2 Lamp 17W CFL High Hat 2 34 2 0.07 82 Existing to Remain 0 2 34 0 0.07 82 0.00 0 $0 0 No New Controls 0 0.0% 0 $0
8 Corridor D2 3000
2-Lamp T8 FBO32 4100K U Tube
2x2 Recessed Prismatic Lens
2 55 6 0.33 990 Re-lampSylvania Lamp
FBO30/841XP/6//SS/ECO2 49 6 0.29 882 0.04 108 $17 0 No New Controls 0 0.0% 0 $0
30 Janitor D7 6002-Lamp T8 F032 4100k 1x4 Pendant Mount No
Lens2 55 1 0.06 33 Re-lamp
Sylvania LampFO28/841/SS/ECO
2 42 1 0.04 25 0.01 8 $1 0 No New Controls 0 0.0% 0 $0
8 Corridor D1 3000
2-Lamp T8 FBO32 4100K U Tube
2x2 Recessed Prismatic Lens
2 55 14 0.77 2,310 Re-lampSylvania Lamp
FBO30/841XP/6//SS/ECO2 49 14 0.69 2,058 0.08 252 $39 0 No New Controls 0 0.0% 0 $0
3 Classroom D3 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom D4 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom D30 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom D32 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom D33 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom D31 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 SGI D5 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 6 0.65 1,685 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 6 0.50 1,310 0.14 374 $58 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 262 $40
3 SGI D6 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 6 0.65 1,685 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 6 0.50 1,310 0.14 374 $58 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 262 $40
40 Media Center D16 26002-Lamp T8 F032 4100k
1x4 Pendant Mount Parabolic Lens
2 55 119 6.55 17,017 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 119 5.00 12,995 1.55 4,022 $619 0 No New Controls 0 0.0% 0 $0
36 Media Center D16 26001-Lamp T8 F032 4100k Recessed Parabolic Lens
1 30 10 0.30 780 Re-lampSylvania Lamp
FO28/841/SS/ECO1 25 10 0.25 650 0.05 130 $20 0 No New Controls 0 0.0% 0 $0
5 Office D17 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 4 0.33 863
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 4 0.17 437 0.16 426 $66 5Dual Technology
Occupancy Sensor - Switch Mnt.
1 20.0% 87 $13
7 Conf D18 26003-Lamp T8 FO32 4100K 2x4 Recessed Parabolic
Lens3 83 4 0.33 863
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 4 0.17 437 0.16 426 $66 5Dual Technology
Occupancy Sensor - Switch Mnt.
0.5 20.0% 87 $13
32 Conf D18 2600 2 Lamp 17W CFL High Hat 2 34 6 0.20 530 Existing to Remain 0 2 34 0 0.20 530 0.00 0 $0 5Dual Technology
Occupancy Sensor - Switch Mnt.
0.5 20.0% 106 $16
10AVA Store Workroom
D19600
2-Lamp T8 FO32 4100K 1x4 Surface Mount
Prismatic Wrap2 55 13 0.72 429 Re-lamp
Sylvania LampFO28/841/SS/ECO
2 42 13 0.55 328 0.17 101 $16 0 No New Controls 0 0.0% 0 $0
7 Computer lab D15 26003-Lamp T8 FO32 4100K 2x4 Recessed Parabolic
Lens3 83 12 1.00 2,590
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 12 0.50 1,310 0.49 1,279 $197 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 262 $40
8 Corridor C21 3000
2-Lamp T8 FBO32 4100K U Tube
2x2 Recessed Prismatic Lens
2 55 17 0.94 2,805 Re-lampSylvania Lamp
FBO30/841XP/6//SS/ECO2 49 17 0.83 2,499 0.10 306 $47 0 No New Controls 0 0.0% 0 $0
32 Intersection C21 D1 3000 2 Lamp 17W CFL High Hat 2 34 12 0.41 1,224 Existing to Remain 0 2 34 0 0.41 1,224 0.00 0 $0 0 No New Controls 0 0.0% 0 $0
Appendix E - Lighting Audit - Anna Mullen Middle School.xlsx Page 4
Fixture Reference #
LocationAverage
Burn Hours
DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Work Description Equipment DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Energy Savings,
kW
Energy Savings,
kWh
Energy Savings, $
Control Ref #
Controls DescriptionQty of
Controls
Hour Reduction
%
Energy Savings,
kWh
Energy Savings, $
Proposed Lighting ControlsRetrofit Energy SavingsExisting Fixtures Proposed Fixtures Retrofit
8 Corridor D22 3000
2-Lamp T8 FBO32 4100K U Tube
2x2 Recessed Prismatic Lens
2 55 14 0.77 2,310 Re-lampSylvania Lamp
FBO30/841XP/6//SS/ECO2 49 14 0.69 2,058 0.08 252 $39 0 No New Controls 0 0.0% 0 $0
7Teachers Planning
Center D202600
3-Lamp T8 FO32 4100K 2x4 Recessed Parabolic
Lens3 83 10 0.83 2,158
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 10 0.42 1,092 0.41 1,066 $164 0 No New Controls 0 0.0% 0 $0
10 D21 6002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 2 0.11 66 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 2 0.08 50 0.03 16 $2 0 No New Controls 0 0.0% 0 $0
33 Toilet D11 1200
2-Lamp T8 F032 4100k 1x4 Side Wall Mount Prismatic Lens Vanity
Fixture
2 55 1 0.06 66 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 1 0.04 50 0.01 16 $2 0 No New Controls 0 0.0% 0 $0
33 Toilet D13 1200
2-Lamp T8 F032 4100k 1x4 Side Wall Mount Prismatic Lens Vanity
Fixture
2 55 1 0.06 66 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 1 0.04 50 0.01 16 $2 0 No New Controls 0 0.0% 0 $0
32 Closet D12 600 2 Lamp 17W CFL High Hat 2 34 1 0.03 20 Existing to Remain 0 2 34 0 0.03 20 0.00 0 $0 0 No New Controls 0 0.0% 0 $0
3Spec Ed Classroom
D142600
4-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Home Econ Lab C24 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 16 1.73 4,493 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 16 1.34 3,494 0.38 998 $154 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 699 $108
5Science Classroom
C252600
3-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 16 1.33 3,453
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 16 0.67 1,747 0.66 1,706 $263 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 349 $54
3 Prep C26 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 6 0.65 1,685 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 6 0.50 1,310 0.14 374 $58 5Dual Technology
Occupancy Sensor - Switch Mnt.
1 20.0% 262 $40
5Science Classroom
C272600
3-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 16 1.33 3,453
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 16 0.67 1,747 0.66 1,706 $263 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 349 $54
3 Classroom C28 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom C29 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
5 Art Classroom C30 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 16 1.33 3,453
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 16 0.67 1,747 0.66 1,706 $263 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 349 $54
3 Storage C31 6004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 4 0.43 259 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 4 0.34 202 0.10 58 $9 0 No New Controls 0 0.0% 0 $0
3 Kiln C32 6004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 2 0.22 130 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 2 0.17 101 0.05 29 $4 0 No New Controls 0 0.0% 0 $0
5 Art Classroom C33 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 16 1.33 3,453
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 16 0.67 1,747 0.66 1,706 $263 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 349 $54
3 Classroom C34 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom C35 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
10 Stprage C22 6002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 2 0.11 66 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 2 0.08 50 0.03 16 $2 0 No New Controls 0 0.0% 0 $0
10 SGI C23 26002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 4 0.22 572 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 4 0.17 437 0.05 135 $21 0 No New Controls 0 0.0% 0 $0
Appendix E - Lighting Audit - Anna Mullen Middle School.xlsx Page 5
Fixture Reference #
LocationAverage
Burn Hours
DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Work Description Equipment DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Energy Savings,
kW
Energy Savings,
kWh
Energy Savings, $
Control Ref #
Controls DescriptionQty of
Controls
Hour Reduction
%
Energy Savings,
kWh
Energy Savings, $
Proposed Lighting ControlsRetrofit Energy SavingsExisting Fixtures Proposed Fixtures Retrofit
8 Corridor C52 3000
2-Lamp T8 FBO32 4100K U Tube
2x2 Recessed Prismatic Lens
2 55 54 2.97 8,910 Re-lampSylvania Lamp
FBO30/841XP/6//SS/ECO2 49 54 2.65 7,938 0.32 972 $150 0 No New Controls 0 0.0% 0 $0
41 Corridor C52 30002-Lamp T8 F17 4100K 2x2 Recessed Prismatic
Lens 2 55 1 0.06 165 Existing to Remain 0 2 55 0 0.06 165 0.00 0 $0 0 No New Controls 0 0.0% 0 $0
8 Corridor B3 3000
2-Lamp T8 FBO32 4100K U Tube
2x2 Recessed Prismatic Lens
2 55 11 0.61 1,815 Re-lampSylvania Lamp
FBO30/841XP/6//SS/ECO2 49 11 0.54 1,617 0.07 198 $30 0 No New Controls 0 0.0% 0 $0
5 School Store B4 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 8 0.66 1,726
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 8 0.34 874 0.33 853 $131 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 175 $27
31 Storage B5 6002-Lamp T8 F032 4100k
1x4 Pendant Mount Prismatic Lens
2 55 6 0.33 198 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 6 0.25 151 0.08 47 $7 0 No New Controls 0 0.0% 0 $0
33 Womens Toilet B6 1200
2-Lamp T8 F032 4100k 1x4 Side Wall Mount Prismatic Lens Vanity
Fixture
2 55 1 0.06 66 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 1 0.04 50 0.01 16 $2 0 No New Controls 0 0.0% 0 $0
33 Mens Toilet B7 1200
2-Lamp T8 F032 4100k 1x4 Side Wall Mount Prismatic Lens Vanity
Fixture
2 55 1 0.06 66 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 1 0.04 50 0.01 16 $2 0 No New Controls 0 0.0% 0 $0
10 Janitor Storage B8 6002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 2 0.11 66 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 2 0.08 50 0.03 16 $2 0 No New Controls 0 0.0% 0 $0
3 Dining Staff B11 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 10 1.08 2,808 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 10 0.84 2,184 0.24 624 $96 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 437 $67
3 Kitchen B12 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 24 2.59 6,739 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 24 2.02 5,242 0.58 1,498 $231 0 No New Controls 0 0.0% 0 $0
10 Kitchen B12 26002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 2 0.11 286 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 2 0.08 218 0.03 68 $10 0 No New Controls 0 0.0% 0 $0
3 Kitchen Office B13 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 2 0.22 562 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 2 0.17 437 0.05 125 $19 5Dual Technology
Occupancy Sensor - Switch Mnt.
1 20.0% 87 $13
10 Storage B14 6002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 1 0.06 33 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 1 0.04 25 0.01 8 $1 0 No New Controls 0 0.0% 0 $0
10 Dish Washer B15 26002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 5 0.28 715 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 5 0.21 546 0.07 169 $26 0 No New Controls 0 0.0% 0 $0
10 Kitchen Hallway 26002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 5 0.28 715 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 5 0.21 546 0.07 169 $26 0 No New Controls 0 0.0% 0 $0
10 Storage B16 6002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 8 0.44 264 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 8 0.34 202 0.10 62 $10 0 No New Controls 0 0.0% 0 $0
10 Lockers B17 12002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 2 0.11 132 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 2 0.08 101 0.03 31 $5 0 No New Controls 0 0.0% 0 $0
33 Toilet B18 1200
2-Lamp T8 F032 4100k 1x4 Side Wall Mount Prismatic Lens Vanity
Fixture
2 55 1 0.06 66 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 1 0.04 50 0.01 16 $2 5
Dual Technology Occupancy Sensor - Switch
Mnt.1 20.0% 10 $2
10Kitchen Jan Storage
B19600
2-Lamp T8 FO32 4100K 1x4 Surface Mount
Prismatic Wrap2 55 1 0.06 33 Re-lamp
Sylvania LampFO28/841/SS/ECO
2 42 1 0.04 25 0.01 8 $1 0 No New Controls 0 0.0% 0 $0
31 Stage B28 26002-Lamp T8 F032 4100k
1x4 Pendant Mount Prismatic Lens
2 55 2 0.11 286 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 2 0.08 218 0.03 68 $10 0 No New Controls 0 0.0% 0 $0
17 Stage B28 2600100W Incandescent Screw-
in Medium Base Lamp1 90 2 0.18 468 Re-Lamp
Sylvania Product #29708
Supermini Twist 11 Watt CFL Medium Base
1 13 2 0.03 68 0.15 400 $62 0 No New Controls 0 0.0% 0 $0
Appendix E - Lighting Audit - Anna Mullen Middle School.xlsx Page 6
Fixture Reference #
LocationAverage
Burn Hours
DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Work Description Equipment DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Energy Savings,
kW
Energy Savings,
kWh
Energy Savings, $
Control Ref #
Controls DescriptionQty of
Controls
Hour Reduction
%
Energy Savings,
kWh
Energy Savings, $
Proposed Lighting ControlsRetrofit Energy SavingsExisting Fixtures Proposed Fixtures Retrofit
10 Stair B32 26002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 2 0.11 286 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 2 0.08 218 0.03 68 $10 0 No New Controls 0 0.0% 0 $0
10 HC Lift B33 26002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 2 0.11 286 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 2 0.08 218 0.03 68 $10 0 No New Controls 0 0.0% 0 $0
5 Storage B26 6003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 2 0.17 100
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 2 0.08 50 0.08 49 $8 0 No New Controls 0 0.0% 0 $0
5 Storage B27 6003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 2 0.17 100
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 2 0.08 50 0.08 49 $8 0 No New Controls 0 0.0% 0 $0
5 Storage B30 6003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 2 0.17 100
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 2 0.08 50 0.08 49 $8 0 No New Controls 0 0.0% 0 $0
5 Storage B29 6003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 2 0.17 100
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 2 0.08 50 0.08 49 $8 0 No New Controls 0 0.0% 0 $0
5Music Work Room
B25600
3-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 4 0.33 199
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 4 0.17 101 0.16 98 $15 5Dual Technology
Occupancy Sensor - Switch Mnt.
1 20.0% 20 $3
5 Music Storage B31 6003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 4 0.33 199
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 4 0.17 101 0.16 98 $15 0 No New Controls 0 0.0% 0 $0
8 Hallway 3000
2-Lamp T8 FBO32 4100K U Tube
2x2 Recessed Prismatic Lens
2 55 4 0.22 660 Re-lampSylvania Lamp
FBO30/841XP/6//SS/ECO2 49 4 0.20 588 0.02 72 $11 0 No New Controls 0 0.0% 0 $0
3 Vocal Music B35 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 18 1.94 5,054 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 18 1.51 3,931 0.43 1,123 $173 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 786 $121
3Instrumental Music
B342600
4-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 18 1.94 5,054 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 18 1.51 3,931 0.43 1,123 $173 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 786 $121
10 Elec B21 6002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 4 0.22 132 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 4 0.17 101 0.05 31 $5 0 No New Controls 0 0.0% 0 $0
31 Mechanical Room B20 6002-Lamp T8 F032 4100k
1x4 Pendant Mount Prismatic Lens
2 55 24 1.32 792 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 24 1.01 605 0.31 187 $29 0 No New Controls 0 0.0% 0 $0
5 Office B22 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 2 0.17 432
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 2 0.08 218 0.08 213 $33 5Dual Technology
Occupancy Sensor - Switch Mnt.
1 20.0% 44 $7
32 Closet B24 600 2 Lamp 17W CFL High Hat 2 34 1 0.03 20 Existing to Remain 0 2 34 0 0.03 20 0.00 0 $0 0 No New Controls 0 0.0% 0 $0
33 Toilet B23 1200
2-Lamp T8 F032 4100k 1x4 Side Wall Mount Prismatic Lens Vanity
Fixture
2 55 1 0.06 66 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 1 0.04 50 0.01 16 $2 0 No New Controls 0 0.0% 0 $0
8 Corridor B1 3000
2-Lamp T8 FBO32 4100K U Tube
2x2 Recessed Prismatic Lens
2 55 10 0.55 1,650 Re-lampSylvania Lamp
FBO30/841XP/6//SS/ECO2 49 10 0.49 1,470 0.06 180 $28 0 No New Controls 0 0.0% 0 $0
31 Tech Lab B43 26002-Lamp T8 F032 4100k
1x4 Pendant Mount Prismatic Lens
2 55 42 2.31 6,006 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 42 1.76 4,586 0.55 1,420 $219 0 No New Controls 0 0.0% 0 $0
10 Tech Lab B43 26002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 2 0.11 286 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 2 0.08 218 0.03 68 $10 0 No New Controls 0 0.0% 0 $0
10 Storage B44 6002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 3 0.17 99 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 3 0.13 76 0.04 23 $4 0 No New Controls 0 0.0% 0 $0
5 Library B42 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 3 0.25 647
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 3 0.13 328 0.12 320 $49 5Dual Technology
Occupancy Sensor - Switch Mnt.
1 20.0% 66 $10
Appendix E - Lighting Audit - Anna Mullen Middle School.xlsx Page 7
Fixture Reference #
LocationAverage
Burn Hours
DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Work Description Equipment DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Energy Savings,
kW
Energy Savings,
kWh
Energy Savings, $
Control Ref #
Controls DescriptionQty of
Controls
Hour Reduction
%
Energy Savings,
kWh
Energy Savings, $
Proposed Lighting ControlsRetrofit Energy SavingsExisting Fixtures Proposed Fixtures Retrofit
31 Comm Tech B40 26002-Lamp T8 F032 4100k
1x4 Pendant Mount Prismatic Lens
2 55 40 2.20 5,720 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 40 1.68 4,368 0.52 1,352 $208 4
Dual Technology Occupancy Sensor -
Remote Mnt.0.5 20.0% 874 $135
10 Comm Tech B40 26002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 2 0.11 286 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 2 0.08 218 0.03 68 $10 4
Dual Technology Occupancy Sensor -
Remote Mnt.0.5 20.0% 44 $7
5 Copy Center B41 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 3 0.25 647
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 3 0.13 328 0.12 320 $49 5Dual Technology
Occupancy Sensor - Switch Mnt.
1 20.0% 66 $10
5 Video Studio B39 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 4 0.33 863
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 4 0.17 437 0.16 426 $66 5Dual Technology
Occupancy Sensor - Switch Mnt.
1 20.0% 87 $13
31 Modeling Design B37 26002-Lamp T8 F032 4100k
1x4 Pendant Mount Prismatic Lens
2 55 42 2.31 6,006 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 42 1.76 4,586 0.55 1,420 $219 4
Dual Technology Occupancy Sensor -
Remote Mnt.0.5 20.0% 917 $141
10 Modeling Design B37 26002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 2 0.11 286 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 2 0.08 218 0.03 68 $10 4
Dual Technology Occupancy Sensor -
Remote Mnt.0.5 20.0% 44 $7
10 Storage B38 6002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 3 0.17 99 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 3 0.13 76 0.04 23 $4 0 No New Controls 0 0.0% 0 $0
5 Library B36 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 3 0.25 647
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 3 0.13 328 0.12 320 $49 5Dual Technology
Occupancy Sensor - Switch Mnt.
1 20.0% 66 $10
7 Teachers Room 03 26003-Lamp T8 FO32 4100K 2x4 Recessed Parabolic
Lens3 83 5 0.42 1,079
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 5 0.21 546 0.21 533 $82 0 No New Controls 0 0.0% 0 $0
5 Office 04 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 3 0.25 647
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 3 0.13 328 0.12 320 $49 0 No New Controls 0 0.0% 0 $0
5 Passage 08 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 1 0.08 216
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 1 0.04 109 0.04 107 $16 0 No New Controls 0 0.0% 0 $0
5 Office 07 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 2 0.17 432
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 2 0.08 218 0.08 213 $33 0 No New Controls 0 0.0% 0 $0
5 Office 06 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 2 0.17 432
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 2 0.08 218 0.08 213 $33 0 No New Controls 0 0.0% 0 $0
5 Conf 05 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 3 0.25 647
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 3 0.13 328 0.12 320 $49 0 No New Controls 0 0.0% 0 $0
5 Assistant Principal 09 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 2 0.17 432
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 2 0.08 218 0.08 213 $33 0 No New Controls 0 0.0% 0 $0
5 Sect 10 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 2 0.17 432
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 2 0.08 218 0.08 213 $33 0 No New Controls 0 0.0% 0 $0
5 Spec Ed 11 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 6 0.50 1,295
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 6 0.25 655 0.25 640 $98 0 No New Controls 0 0.0% 0 $0
5 SGI 12 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 6 0.50 1,295
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 6 0.25 655 0.25 640 $98 0 No New Controls 0 0.0% 0 $0
5 Classroom 13 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 9 0.75 1,942
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 9 0.38 983 0.37 959 $148 0 No New Controls 0 0.0% 0 $0
41 Corridor New Wing 30002-Lamp T8 F17 4100K 2x2 Recessed Prismatic
Lens 2 55 10 0.55 1,650 Existing to Remain 0 2 55 0 0.55 1,650 0.00 0 $0 0 No New Controls 0 0.0% 0 $0
5 Office 17 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 2 0.17 432
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 2 0.08 218 0.08 213 $33 0 No New Controls 0 0.0% 0 $0
Appendix E - Lighting Audit - Anna Mullen Middle School.xlsx Page 8
Fixture Reference #
LocationAverage
Burn Hours
DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Work Description Equipment DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Energy Savings,
kW
Energy Savings,
kWh
Energy Savings, $
Control Ref #
Controls DescriptionQty of
Controls
Hour Reduction
%
Energy Savings,
kWh
Energy Savings, $
Proposed Lighting ControlsRetrofit Energy SavingsExisting Fixtures Proposed Fixtures Retrofit
5 Girls 16 12003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 2 0.17 199
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 2 0.08 101 0.08 98 $15 0 No New Controls 0 0.0% 0 $0
5 Male 14 12003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 1 0.08 100
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 1 0.04 50 0.04 49 $8 0 No New Controls 0 0.0% 0 $0
5 Womens 13 12003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 1 0.08 100
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 1 0.04 50 0.04 49 $8 0 No New Controls 0 0.0% 0 $0
41Corridor New Wing
Rear Exit3000
2-Lamp T8 F17 4100K 2x2 Recessed Prismatic
Lens 2 55 1 0.06 165 Existing to Remain 0 2 55 0 0.06 165 0.00 0 $0 0 No New Controls 0 0.0% 0 $0
5 Classroom 18 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 9 0.75 1,942
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 9 0.38 983 0.37 959 $148 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 197 $30
5 Classroom 19 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 9 0.75 1,942
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 9 0.38 983 0.37 959 $148 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 197 $30
5 Classroom 20 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 9 0.75 1,942
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 9 0.38 983 0.37 959 $148 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 197 $30
5 SGI 21 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 6 0.50 1,295
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 6 0.25 655 0.25 640 $98 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 131 $20
5 Storage 22 6003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 1 0.08 50
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 1 0.04 25 0.04 25 $4 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 5 $1
5 Classroom 23 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 9 0.75 1,942
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 9 0.38 983 0.37 959 $148 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 197 $30
5 Classroom 24 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 6 0.50 1,295
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 6 0.25 655 0.25 640 $98 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 131 $20
5 Classroom 25 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 9 0.75 1,942
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 9 0.38 983 0.37 959 $148 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 197 $30
5 Classroom 26 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 9 0.75 1,942
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 9 0.38 983 0.37 959 $148 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 197 $30
5 Life Science 27 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 12 1.00 2,590
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 12 0.50 1,310 0.49 1,279 $197 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 262 $40
5 Classroom 28 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 9 0.75 1,942
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 9 0.38 983 0.37 959 $148 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 197 $30
5 SGI 29 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 6 0.50 1,295
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 6 0.25 655 0.25 640 $98 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 131 $20
5 Classroom 30 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 9 0.75 1,942
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 9 0.38 983 0.37 959 $148 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 197 $30
5 Classroom 31 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 9 0.75 1,942
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 9 0.38 983 0.37 959 $148 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 197 $30
5 Classroom 32 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 9 0.75 1,942
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 9 0.38 983 0.37 959 $148 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 197 $30
5 Classroom 34 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 9 0.75 1,942
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 9 0.38 983 0.37 959 $148 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 197 $30
5 Classroom 35 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 9 0.75 1,942
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 9 0.38 983 0.37 959 $148 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 197 $30
Appendix E - Lighting Audit - Anna Mullen Middle School.xlsx Page 9
Fixture Reference #
LocationAverage
Burn Hours
DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Work Description Equipment DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Energy Savings,
kW
Energy Savings,
kWh
Energy Savings, $
Control Ref #
Controls DescriptionQty of
Controls
Hour Reduction
%
Energy Savings,
kWh
Energy Savings, $
Proposed Lighting ControlsRetrofit Energy SavingsExisting Fixtures Proposed Fixtures Retrofit
5 Classroom 36 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 9 0.75 1,942
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 9 0.38 983 0.37 959 $148 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 197 $30
5 Classroom 37 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 9 0.75 1,942
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 9 0.38 983 0.37 959 $148 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 197 $30
5 Classroom 38 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 6 0.50 1,295
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 6 0.25 655 0.25 640 $98 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 131 $20
5 Girls 39 12003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 4 0.33 398
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 4 0.17 202 0.16 197 $30 0 No New Controls 0 0.0% 0 $0
30 Janitor 40 6002-Lamp T8 F032 4100k 1x4 Pendant Mount No
Lens2 55 2 0.11 66 Re-lamp
Sylvania LampFO28/841/SS/ECO
2 42 2 0.08 50 0.03 16 $2 0 No New Controls 0 0.0% 0 $0
5 Boys 41 12003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 3 0.25 299
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 3 0.13 151 0.12 148 $23 0 No New Controls 0 0.0% 0 $0
7 Computer 44 26003-Lamp T8 FO32 4100K 2x4 Recessed Parabolic
Lens3 83 12 1.00 2,590
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 12 0.50 1,310 0.49 1,279 $197 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 262 $40
7 Computer 45 26003-Lamp T8 FO32 4100K 2x4 Recessed Parabolic
Lens3 83 12 1.00 2,590
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 12 0.50 1,310 0.49 1,279 $197 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 262 $40
5 SGI 46 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 6 0.50 1,295
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 6 0.25 655 0.25 640 $98 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 131 $20
5 Spec ed 47 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 6 0.50 1,295
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 6 0.25 655 0.25 640 $98 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 131 $20
5 Classroom 48 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 9 0.75 1,942
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 9 0.38 983 0.37 959 $148 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 197 $30
5 Classroom 49 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 9 0.75 1,942
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 9 0.38 983 0.37 959 $148 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 197 $30
5 Classroom 50 26003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 9 0.75 1,942
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 9 0.38 983 0.37 959 $148 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 197 $30
41 Corridor 33 30002-Lamp T8 F17 4100K 2x2 Recessed Prismatic
Lens 2 55 62 3.41 10,230 Existing to Remain 0 2 55 0 3.41 10,230 0.00 0 $0 0 No New Controls 0 0.0% 0 $0
31 Janitor C37 6002-Lamp T8 F032 4100k
1x4 Pendant Mount Prismatic Lens
2 55 1 0.06 33 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 1 0.04 25 0.01 8 $1 0 No New Controls 0 0.0% 0 $0
32 Boys Toilet C38 1200 2 Lamp 17W CFL High Hat 2 34 5 0.17 204 Existing to Remain 0 2 34 0 0.17 204 0.00 0 $0 0 No New Controls 0 0.0% 0 $0
33 Boys Toilet C38 1200
2-Lamp T8 F032 4100k 1x4 Side Wall Mount Prismatic Lens Vanity
Fixture
2 55 2 0.11 132 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 2 0.08 101 0.03 31 $5 0 No New Controls 0 0.0% 0 $0
10 Boys Toilet C38 12002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 2 0.11 132 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 2 0.08 101 0.03 31 $5 0 No New Controls 0 0.0% 0 $0
32 Girls Toilet C39 1200 2 Lamp 17W CFL High Hat 2 34 2 0.07 82 Existing to Remain 0 2 34 0 0.07 82 0.00 0 $0 0 No New Controls 0 0.0% 0 $0
33 Girls Toilet C39 1200
2-Lamp T8 F032 4100k 1x4 Side Wall Mount Prismatic Lens Vanity
Fixture
2 55 2 0.11 132 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 2 0.08 101 0.03 31 $5 0 No New Controls 0 0.0% 0 $0
10 Girls Toilet C39 12002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 3 0.17 198 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 3 0.13 151 0.04 47 $7 0 No New Controls 0 0.0% 0 $0
Appendix E - Lighting Audit - Anna Mullen Middle School.xlsx Page 10
Fixture Reference #
LocationAverage
Burn Hours
DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Work Description Equipment DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Energy Savings,
kW
Energy Savings,
kWh
Energy Savings, $
Control Ref #
Controls DescriptionQty of
Controls
Hour Reduction
%
Energy Savings,
kWh
Energy Savings, $
Proposed Lighting ControlsRetrofit Energy SavingsExisting Fixtures Proposed Fixtures Retrofit
3 Classroom C40 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom C41 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom C42 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom C43 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom C44 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom C45 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom C46 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom C47 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom C48 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
7 Classroom C49 26003-Lamp T8 FO32 4100K 2x4 Recessed Parabolic
Lens3 83 16 1.33 3,453
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 16 0.67 1,747 0.66 1,706 $263 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 349 $54
10 Storage C50 6002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 3 0.17 99 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 3 0.13 76 0.04 23 $4 0 No New Controls 0 0.0% 0 $0
10 Storage C51 6002-Lamp T8 FO32 4100K
1x4 Surface Mount Prismatic Wrap
2 55 2 0.11 66 Re-lampSylvania Lamp
FO28/841/SS/ECO2 42 2 0.08 50 0.03 16 $2 0 No New Controls 0 0.0% 0 $0
8 Corridor C36 3000
2-Lamp T8 FBO32 4100K U Tube
2x2 Recessed Prismatic Lens
2 55 21 1.16 3,465 Re-lampSylvania Lamp
FBO30/841XP/6//SS/ECO2 49 21 1.03 3,087 0.13 378 $58 0 No New Controls 0 0.0% 0 $0
32 Girls Toilet D23 1200 2 Lamp 17W CFL High Hat 2 34 2 0.07 82 Existing to Remain 0 2 34 0 0.07 82 0.00 0 $0 0 No New Controls 0 0.0% 0 $0
8 Girls Toilet D23 1200
2-Lamp T8 FBO32 4100K U Tube
2x2 Recessed Prismatic Lens
2 55 3 0.17 198 Re-lampSylvania Lamp
FBO30/841XP/6//SS/ECO2 49 3 0.15 176 0.02 22 $3 0 No New Controls 0 0.0% 0 $0
5 Girls Toilet D23 12003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 1 0.08 100
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 1 0.04 50 0.04 49 $8 0 No New Controls 0 0.0% 0 $0
32 Boys Toilet D24 1200 2 Lamp 17W CFL High Hat 2 34 2 0.07 82 Existing to Remain 0 2 34 0 0.07 82 0.00 0 $0 0 No New Controls 0 0.0% 0 $0
8 Boys Toilet D24 1200
2-Lamp T8 FBO32 4100K U Tube
2x2 Recessed Prismatic Lens
2 55 2 0.11 132 Re-lampSylvania Lamp
FBO30/841XP/6//SS/ECO2 49 2 0.10 118 0.01 14 $2 0 No New Controls 0 0.0% 0 $0
5 Boys Toilet D24 12003-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens3 83 1 0.08 100
Relamp, De-lamp center Lamp, & Defeat Socket
Sylvania LampFO28/841/SS/ECO
2 42 1 0.04 50 0.04 49 $8 0 No New Controls 0 0.0% 0 $0
30 Janitor D25 6002-Lamp T8 F032 4100k 1x4 Pendant Mount No
Lens2 55 1 0.06 33 Re-lamp
Sylvania LampFO28/841/SS/ECO
2 42 1 0.04 25 0.01 8 $1 0 No New Controls 0 0.0% 0 $0
3 SGI D26 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 6 0.65 1,685 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 6 0.50 1,310 0.14 374 $58 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 262 $40
Appendix E - Lighting Audit - Anna Mullen Middle School.xlsx Page 11
Fixture Reference #
LocationAverage
Burn Hours
DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Work Description Equipment DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Energy Savings,
kW
Energy Savings,
kWh
Energy Savings, $
Control Ref #
Controls DescriptionQty of
Controls
Hour Reduction
%
Energy Savings,
kWh
Energy Savings, $
Proposed Lighting ControlsRetrofit Energy SavingsExisting Fixtures Proposed Fixtures Retrofit
3 SGI D27 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 6 0.65 1,685 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 6 0.50 1,310 0.14 374 $58 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 262 $40
3 Classroom D34 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom D36 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom D37 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom D35 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom D28 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
3 Classroom D29 26004-Lamp T8 FO32 4100K 2x4 Recessed Prismatic
Lens4 108 12 1.30 3,370 Re-lamp
Sylvania LampFO28/841/SS/ECO
4 84 12 1.01 2,621 0.29 749 $115 4Dual Technology
Occupancy Sensor - Remote Mnt.
1 20.0% 524 $81
TOTAL 1,850 144.1 357,872 1,715 104.1 259,542 40.0 98,330 $15,143 107 33,488 $5,157
Appendix E - Lighting Audit - Anna Mullen Middle School.xlsx Page 12
CEG Project #:
Facility Name:
Address:
City, State, Zip
Fixture Reference #
LocationAverage
Burn Hours
DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Work Description Equipment DescriptionLamps per
FixtureWatts per
FixtureQty of
FixturesTotal kW
Usage kWh/Yr
Energy Savings,
kW
Energy Savings,
kWh
Energy Savings, $
Control Ref #
Controls DescriptionQty of
Controls
Hour Reduction
%
Energy Savings,
kWh
Energy Savings, $
28 Lobby A2 3000400W MH Pendant
Prismatic Lens1 465 4 1.86 5,580 New Fixture
2x4 54w T5HO 6 Lamp w/Reflecter & Wire Guard
6 354 4 1.42 4,248 0.44 1,332 $205 0 No New Controls 0 0.0% 0 $0
28 Gymnasium A25 2600400W MH Pendant
Prismatic Lens1 465 48 22.32 58,032 New Fixture
2x4 54w T5HO 6 Lamp w/Reflecter & Wire Guard
6 354 48 16.99 44,179 5.33 13,853 $2,133 0 No New Controls 0 0.0% 0 $0
28 Intersection C21 D1 3000400W MH Pendant
Prismatic Lens1 465 2 0.93 2,790 New Fixture
2x4 54w T5HO 6 Lamp w/Reflecter & Wire Guard
6 354 2 0.71 2,124 0.22 666 $103 0 No New Controls 0 0.0% 0 $0
29 Cafetorium 2600 250W MH Recess Prismatic 1 295 30 8.85 23,010 New Fixture2x4 54w T5HO 3 Lamp
w/Reflecter & Wire Guard3 177 30 5.31 13,806 3.54 9,204 $1,417 0 No New Controls 0 0.0% 0 $0
28 Stage B28 2600400W MH Pendant
Prismatic Lens1 465 5 2.33 6,045 New Fixture
2x4 54w T5HO 6 Lamp w/Reflecter & Wire Guard
6 354 5 1.77 4,602 0.56 1,443 $222 0 No New Controls 0 0.0% 0 $0
TOTAL 89 36.3 95,457 89 26.2 68,959 10.1 26,498 $4,081 0 0 $0
Retrofit Energy Savings Proposed Lighting Controls
9C12010
Ann Mullen Middle School
1400 Sicklerville Road
Sicklerville , NJ 08081
Existing Fixtures Proposed Fixtures Retrofit
Appendix E - Lighting Audit - Anna Mullen Middle School.xlsx Page 13
Appendix Energy Audit
Concord Engineering Group, Inc.
APPENDIX F
Appendix FPage 1 of 2
Location Description
Area (Sq FT) Panel Qty
Panel Sq Ft
Panel Total Sq
FtTotal KWDC
Total Annual kWh
Total KWAC
Panel Weight
(41.9 lbs) W/SQFT
Anna A. Mullen Middle School
38000SHARP
NU-U235F21866 17.5 32,731 438.51 541,878 355.2 78,185 13.40
.= Proposed PV Layout
Notes:
1. Estimated kWH based on the National Renewable Energy Laboratory PVWatts Version 1 Calculator Program.
Appendix FPage 2 of 2
Project Name: LGEA Solar PV Project - Anna A. Mullen Middle School
Location: Blackwood, NJDescription: Photovoltaic System 100% Financing - 15 year
Simple Payback Analysis
Total Construction Cost $2,548,057Annual kWh Production 541,878
Annual Energy Cost Reduction $83,449Average Annual SREC Revenue $103,545
Simple Payback: Years
Life Cycle Cost AnalysisAnalysis Period (years): 15 Financing %: 100%
Discount Rate: 3% Maintenance Escalation Rate: 3.0%Average Energy Cost ($/kWh) $0.154 Energy Cost Escalation Rate: 3.0%
Financing Rate: 6.00% Average SREC Value ($/kWh) $0.191Period Additional Energy kWh Energy Cost Additional SREC Interest Loan Net Cash Cumulative
Cash Outlay Production Savings Maint Costs Revenue Expense Principal Flow Cash Flow0 $0 0 0 0 $0 0 0 0 01 $0 541,878 $83,449 $0 $135,470 $149,943 $108,080 ($39,105) ($39,105)2 $0 539,169 $85,953 $0 $134,792 $143,277 $114,746 ($37,279) ($76,383)3 $0 536,473 $88,531 $0 $134,118 $136,200 $121,824 ($35,374) ($111,757)4 $0 533,790 $91,187 $0 $133,448 $128,686 $129,337 ($33,389) ($145,146)5 $0 531,121 $93,923 $5,471 $132,780 $120,709 $137,315 ($36,791) ($181,937)6 $0 528,466 $96,741 $5,443 $105,693 $112,240 $145,784 ($61,033) ($242,970)7 $0 525,824 $99,643 $5,416 $105,165 $103,248 $154,775 ($58,632) ($301,602)8 $0 523,194 $102,632 $5,389 $104,639 $93,702 $164,322 ($56,141) ($357,743)9 $0 520,578 $105,711 $5,362 $104,116 $83,567 $174,457 ($53,559) ($411,302)10 $0 517,976 $108,882 $5,335 $77,696 $72,807 $185,217 ($76,780) ($488,082)11 $0 515,386 $112,149 $5,308 $77,308 $61,383 $196,641 ($73,875) ($561,957)12 $0 512,809 $115,513 $5,282 $76,921 $49,254 $208,769 ($70,871) ($632,828)13 $0 510,245 $118,979 $5,256 $76,537 $36,378 $221,645 ($67,764) ($700,592)14 $0 507,693 $122,548 $5,229 $50,769 $22,707 $235,316 ($89,935) ($790,527)15 $0 505,155 $126,224 $5,203 $50,515 $8,194 $249,830 ($86,487) ($877,014)
Totals: 7,849,756 $1,552,065 $58,694 $1,499,967 $1,322,295 $2,548,057 ($877,014) ($5,918,944)Net Present Value (NPV)
Photovoltaic System 100% Financing - 15 year
13.63
($633,744)