Geotechnical Engineering Report...Geotechnical Engineering Report Fitts Park Pedestrian Bridge South...
Transcript of Geotechnical Engineering Report...Geotechnical Engineering Report Fitts Park Pedestrian Bridge South...
REPORT C OVER PAGE
Geotechnical Engineering Report Fitts Park Pedestrian Bridge
South Salt Lake, Utah
July 26, 2018
Terracon Project No. 61175201
Prepared for:
Kinley-Horn and Associates, Inc.
Salt Lake City, UT
Prepared by:
Terracon Consultants, Inc.
Midvale, Utah
Responsive Resourceful Reliable
REPORT TOPICS
REPORT TOPICS
INTRODUCTION ............................................................................................................. 1 SITE CONDITIONS ......................................................................................................... 1
PROJECT DESCRIPTION .............................................................................................. 2 GEOTECHNICAL CHARACTERIZATION ...................................................................... 2 GEOTECHNICAL OVERVIEW ....................................................................................... 3 EARTHWORK ................................................................................................................ 4 SHALLOW FOUNDATIONS ........................................................................................... 7
SEISMIC CONSIDERATIONS ...................................................................................... 10 LIQUEFACTION ........................................................................................................... 10 GENERAL COMMENTS ............................................................................................... 12
Note: This report was originally delivered in a web-based format. Orange Bold text in the report indicates a referenced
section heading. The PDF version also includes hyperlinks which direct the reader to that section and clicking on the
logo will bring you back to this page. For more interactive features, please view your project online at
client.terracon.com.
ATTACHMENTS
EXPLORATION AND TESTING PROCEDURES
SITE LOCATION AND EXPLORATION PLANS
EXPLORATION RESULTS (Boring Logs and Laboratory Data)
SUPPORTING INFORMATION (General Notes and Unified Soil Classification System)
Responsive Resourceful Reliable 1
INTRODUCTION
Geotechnical Engineering Report
Fitts Park Pedestrian Bridge
3050 South 500 East
South Salt Lake, Utah Terracon Project No. 61175201
July 26, 2018
INTRODUCTION This report presents the results of our subsurface exploration and geotechnical engineering
services performed for the proposed Fitts Park Pedestrian Bridge to be located at 3050 South
500 East in South Salt Lake, Utah. The purpose of these services is to provide information and
geotechnical engineering recommendations relative to:
The geotechnical engineering scope of services for this project included the advancement of two
test borings to depths of approximately 50 feet below existing site grades.
Maps showing the site and boring locations are shown in the Site Location and Exploration
Plan sections, respectively. The results of the laboratory testing performed on soil samples
obtained from the site during the field exploration are included on the boring logs in the
Exploration Results section of this report.
SITE CONDITIONS
The following description of site conditions is derived from our site visit in association with the
field exploration and our review of publicly available geologic and topographic maps.
Item Description
Parcel Information 3050 South 500 East in South Salt Lake, Utah.
See Site Location
Existing
Improvements Existing public park surrounded by residential properties.
Subsurface soil conditions Foundation design and construction
Groundwater conditions Frost considerations
Site preparation and earthwork Seismic site classification per IBC
Excavation considerations Lateral earth pressures
Geotechnical Engineering Report
Fitts Park Pedestrian Bridge South Salt Lake, Utah
July 26, 2018 Terracon Project No. 61175201
Responsive Resourceful Reliable 2
Item Description
Current Ground
Cover Trees, grass, shrubs, and landscaping.
Existing Topography Moderate to steep slopes along Mill Creek.
PROJECT DESCRIPTION
Our initial understanding of the project was provided in our proposal and was discussed in the
project planning stage. A period of collaboration has transpired since the project was initiated,
and our final understanding of the project conditions is as follows:
Item Description
Project Description Planned construction of a pedestrian bridge over Mill Creek in Fitt’s Park in South Salt Lake, Utah.
Proposed Structure Pedestrian bridge structure. The bridge structure will be single-span and approximately 45 to 50 feet long.
Bridge Construction Reinforced concrete or metal girders supported on reinforced concrete abutments supported on shallow or deep foundations.
Maximum Loads
Factored Loads
Dead Load: 87.5 kips (reported) Live Load: 39.4 kips (reported)
Grading/Slopes Minimal cut and fills expected to be 3 feet or less.
Below Grade Structures None
Free-Standing Retaining Walls
None
Below Grade Areas None
GEOTECHNICAL CHARACTERIZATION
Subsurface Profile
We have developed a general characterization of the subsurface soil and groundwater conditions
based upon our review of the data and our understanding of the geologic setting and planned
construction. The following table provides our geotechnical characterization.
The geotechnical characterization forms the basis of our geotechnical calculations and evaluation
of site preparation, foundation options and pavement options. As noted in General Comments,
the characterization is based upon widely spaced exploration points across the site, and variations
are likely.
Geotechnical Engineering Report
Fitts Park Pedestrian Bridge South Salt Lake, Utah
July 26, 2018 Terracon Project No. 61175201
Responsive Resourceful Reliable 3
Stratum Approximate Depth to
Bottom of Stratum (feet) Material Description Consistency/Density
Surface 6 inches Topsoil N/A
1 7 to 9½ Silt with sand, silty sand Medium stiff / very
loose to loose
2 51½ 1 Lean clay, silty clay, occasional silt
with sand layers Very soft to stiff
1. Maximum depth explored
Conditions encountered at each boring location are indicated on the individual boring logs shown
in the Exploration Results section and are attached to this report. Stratification boundaries on
the boring logs represent the approximate location of changes in native soil types; in situ, the
transition between materials may be gradual.
Groundwater Conditions
The boreholes were observed while drilling and after completion for the presence and level of
groundwater. The water levels observed in the boreholes can be found on the boring logs in
Exploration Results, and are summarized below.
Boring Number Approximate Depth to Groundwater while
Drilling (feet) 1
B-1 10
B-2 8
1. Below ground surface
Due to water content of the soil samples, groundwater is expected to be at an approximate depth of
5’ deep. Groundwater level fluctuations occur due to seasonal variations in the amount of rainfall,
runoff and other factors not evident at the time the borings were performed. Therefore,
groundwater levels during construction or at other times in the life of the structure may be higher
or lower than the levels indicated on the boring logs. The possibility of groundwater level
fluctuations should be considered when developing the design and construction plans for the
project.
GEOTECHNICAL OVERVIEW
Based on the results of the subsurface exploration, laboratory testing, and our analyses, it is our
opinion that the site is suitable for the proposed construction, provided the recommendations
presented in this report are followed. Geotechnical considerations for this project include:
Geotechnical Engineering Report
Fitts Park Pedestrian Bridge South Salt Lake, Utah
July 26, 2018 Terracon Project No. 61175201
Responsive Resourceful Reliable 4
Near Surface Soils – Fine-grained near-surface soils are susceptible to pumping and
rutting under the weight of construction equipment, especially when wetted. Special
measures will be required to complete earthwork activities and and foundation
construction. The use of crushed stone (Stabilization Fill) in combination with geotextiles
may be required to form stable surfaces for construction.
Shallow Foundations – Relatively soft compressible native clay soils were encountered
at the bridge foundation locations. Structural Fill or a Compacted Aggregate Pier (CAP)
improved subgrade is required below shallow footings to provide support for bearing and
limit settlement to 1 inch or less. Shallow spread footings may require embedment beyond
frost depth for lateral resistance or scour. Dewatering may be required in foundation
excavations.
Shallow Groundwater - Shallow groundwater is anticipated at this site. Excavations
extending deeper than about 5 feet below existing grade are anticipated to encounter
groundwater. The presence of groundwater at these depths will present difficulties during
construction that may impact the long-term performance of the structure. De-watering
during construction may be required.
Geotechnical engineering recommendations for the planned pedestrian bridge and other earth-
connected phases of the project are outlined below. The recommendations contained in this
report are based upon the results of field and laboratory testing (which are presented in
Appendices A and B), engineering analyses, and our current understanding of the proposed
project.
The General Comments section provides an understanding of the report limitations.
EARTHWORK
Earthwork will include clearing and grubbing landscaped areas, and possible excavations and fill
placement. The following sections provide recommendations for use in the preparation of
specifications for the work. Recommendations include critical quality criteria as necessary to
render the site in the state considered in our geotechnical engineering evaluation for foundations,
floor slabs, and pavements.
Site Preparation
Topsoil, deleterious materials, fill, loose or disturbed soil, and any other unsuitable materials
should be removed from within construction areas. Following removal of unsuitable materials, the
exposed subgrade below foundations, including areas which will receive fill, should be proofrolled
Geotechnical Engineering Report
Fitts Park Pedestrian Bridge South Salt Lake, Utah
July 26, 2018 Terracon Project No. 61175201
Responsive Resourceful Reliable 5
to aid in assessing subgrade condition. Proofrolling should be performed using rubber-tired
equipment. Soft, pumping or otherwise unsuitable conditions, identified during proof rolling,
should be removed and replaced with Structural Fill or stabilized using geotextiles and
Stabilization Fill.
Backfill of excavations above the groundwater level should be completed using properly placed
and compacted Structural Fill. Backfill of excavations below groundwater level should be
completed using properly placed and compacted Free-Draining Granular Backfill.
The site should be initially graded to create a relatively level surface to receive fill, and to provide
for a relatively uniform thickness of fill beneath foundations and site grading areas.
Stabilization of subgrade may also be accomplished using lime or cement to treat the clay
subgrade soils. Additional testing will be required to determine the percent lime or cement
required.
Although evidence of underground facilities, such as septic tanks, cesspools, and unknown
utilities, was not observed during the site reconnaissance, such features could be encountered
during construction. If unexpected underground facilities are encountered, such features should
be removed and the excavation thoroughly cleaned prior to backfill placement and/or construction.
Fill Material Types
Fill should meet the following material property requirements:
Fill Type 1
Recommended Use Acceptable Parameters (for Structural Fill)
Structural Fill
Below foundations,
above groundwater
level
Liquid Limit less than 32. Plasticity index less than 6
Less than 15% retained on #200 sieve
Free-Draining
Granular Backfill
Below groundwater
level
1½ inch minus, 25% to 60% particles passing ½ inch
sieve, less than 5% passing #200 sieve
Stabilization Fill Soft spot repair 6 inch minus with 5% max passing No. 200 sieve.
1. Structural and general fill should consist of approved materials free of organic matter and debris. Frozen
material should not be used, and fill should not be placed on a frozen subgrade. A sample of each material
type should be submitted to the Geotechnical Engineer for evaluation prior to use on this site.
Fill Compaction Requirements
Engineered fill should meet the following compaction requirements.
Geotechnical Engineering Report
Fitts Park Pedestrian Bridge South Salt Lake, Utah
July 26, 2018 Terracon Project No. 61175201
Responsive Resourceful Reliable 6
Item Structural Fill Free-Draining Granular
Backfill
Maximum Lift Thickness
8 inches or less in loose thickness when heavy, self-propelled compaction equipment is used
4 to 6 inches in loose thickness when hand-guided equipment (i.e. jumping jack or plate compactor) is used
Same as Structural Fill
Minimum Compaction
Requirements 1, 2, 3
95% of max. Same as Structural Fill
Water Content
Range 1
+/-2% of optimum
As required to achieve min. compaction requirements
1. Maximum density and optimum water content as determined by the modified Proctor test (ASTM D 1557). 2. If the granular material is a coarse sand or gravel, or of a uniform size, or has a low fines content,
compaction comparison to relative density may be more appropriate. In this case, granular materials should be compacted to at least 70% relative density (ASTM D 4253 and D 4254).
Stabilization Fill should be densified using a smooth drum roller with a minimum of 4 passes.
Grading and Drainage
Any areas of standing surface water should be drained as far in advance of construction as possible.
Any saturated soils should be removed prior to placing fill or proceeding with construction.
Surface water should not be allowed to pond on the site and soak into the soil during construction.
Construction staging should provide drainage of surface water and precipitation away from
structures. Any water that collects over or adjacent to construction areas should be promptly
removed, along with any softened or disturbed soils. Surface water control in the form of sloping
surfaces, drainage ditches and trenches, and sump pits and pumps will be important to avoid ponding
and associated delays due to precipitation and seepage.
Earthwork Construction Considerations
Excavations for the proposed construction are anticipated to be accomplished with conventional
construction equipment.
Construction traffic over the completed subgrade should be minimized to reduce damage to the
subgrade. The site should also be graded to prevent ponding of surface water on the prepared
subgrades or in excavations. If the subgrade should become frozen, desiccated, saturated, or
disturbed, the affected material should be removed and replaced with compacted Structural Fill
or the materials moisture conditioned and recompacted prior to foundation construction
Geotechnical Engineering Report
Fitts Park Pedestrian Bridge South Salt Lake, Utah
July 26, 2018 Terracon Project No. 61175201
Responsive Resourceful Reliable 7
The groundwater table could affect over-excavation efforts, especially for over-excavation and
replacement of lower strength soils. A temporary dewatering system consisting of sumps with pumps
could be necessary to achieve the recommended depth of over-excavation.
As a minimum, excavations should be performed in accordance with OSHA 29 CFR, Part 1926,
Subpart P, “Excavations” and its appendices, and in accordance with any applicable local, and/or
state regulations.
Construction site safety is the sole responsibility of the contractor who controls the means,
methods, and sequencing of construction operations. Under no circumstances shall the
information provided herein be interpreted to mean Terracon is assuming responsibility for
construction site safety, or the contractor's activities; such responsibility shall neither be implied
nor inferred.
Construction Observation and Testing
The earthwork efforts should be monitored under the direction of the Geotechnical Engineer.
Monitoring should include documentation of adequate removal of vegetation and top soil, proof-
rolling and mitigation of areas delineated by the proof-roll to require mitigation.
Each lift of compacted fill should be tested, evaluated, and reworked as necessary until approved
by the Geotechnical Engineer prior to placement of additional lifts. Each lift of fill for bridge
construction components should be tested for density and water content
In areas of foundation excavations, the bearing subgrade should be evaluated under the direction
of the Geotechnical Engineer. In the event that unanticipated conditions are encountered, the
Geotechnical Engineer should prescribe mitigation options.
In addition to the documentation of the essential parameters necessary for construction, the
continuation of the Geotechnical Engineer into the construction phase of the project provides the
continuity to maintain the Geotechnical Engineer’s evaluation of subsurface conditions, including
assessing variations and associated design changes.
SHALLOW FOUNDATIONS
In our opinion, the proposed pedestrian bridge may be supported on a lightly loaded, shallow
spread footing foundation system bearing on a minimum of 24 inches of properly placed and
compacted Structural Fill or on a CAP improved subgrade. If the site has been prepared in
accordance with the requirements noted in Earthwork, the following design parameters are
applicable for shallow foundations.
Geotechnical Engineering Report
Fitts Park Pedestrian Bridge South Salt Lake, Utah
July 26, 2018 Terracon Project No. 61175201
Responsive Resourceful Reliable 8
Design Parameters – Compressive Loads
Item Description
Maximum Net Allowable Bearing
pressure by footing dimension 1, 2
6’ x 12’ 2200 psf
8’ X 12’ 1300 psf
10 x 12 1100 psf
Minimum Foundation Dimensions 6’ wide x 12’ long
Ultimate Coefficient of Sliding Friction 3
0.40 (granular material)
Minimum Embedment below
Finished Grade 4, 6
30 inches
Estimated Total Settlement from
Foundation Loads 5
Approximately 1 inch
Estimated Differential Settlement from
Foundation Loads 5
< ½ inch over 12 feet
1. The maximum net allowable bearing pressure is the pressure in excess of the minimum surrounding overburden pressure at the footing base elevation. An appropriate factor of safety has been applied. These bearing pressures can be increased by 1/3 for transient loads unless those loads have been factored to account for transient conditions. Values assume that exterior grades are no steeper than 20% within 10 feet of structure.
2. Values provided are for maximum loads noted in Project Description.
3. The sides of excavations for spread footings must be nearly vertical and the concrete should be placed neat against these vertical faces for the passive earth pressure values to be valid. If the loaded side is sloped or benched, and then backfilled, the allowable passive pressure will be significantly reduced. Passive resistance in the upper 2.5 feet of the soil profile should be neglected. If passive resistance is used to resist lateral loads, the base friction should be neglected.
4. Embedment necessary to minimize the effects of frost and/or seasonal water content variations. For sloping ground, maintain depth below the lowest adjacent exterior grade within 5 horizontal feet of the structure.
5. The foundation settlement will depend upon the variations within the subsurface soil profile, the structural
loading conditions, the embedment depth of the footings, the thickness of compacted fill, and the quality of
the earthwork operations.
6. Additional embedment may be required to resist lateral loading or uplift.
Foundation Construction Considerations
As noted in Earthwork, the footing excavations should be evaluated under the direction of the
Geotechnical Engineer. The base of all foundation excavations should be free of water and loose
soil, prior to placing concrete. Concrete should be placed soon after excavating to reduce bearing
soil disturbance. Care should be taken to prevent wetting or drying of the bearing materials during
construction. Excessively wet or dry material or any loose/disturbed material in the bottom of the
footing excavations should be removed/reconditioned before foundation concrete is placed.
If unsuitable bearing soils are encountered at the base of the planned footing excavation, the
excavation should be extended deeper to suitable soils, and the footings can bear directly on
properly placed and compacted Structural Fill or Free-Draining Granular Backfill extending to the
Geotechnical Engineering Report
Fitts Park Pedestrian Bridge South Salt Lake, Utah
July 26, 2018 Terracon Project No. 61175201
Responsive Resourceful Reliable 9
suitable soil. Fill placed above the groundwater table should be Structural Fill and fill below the
groundwater table should be Free-Draining Granular Backfill.. This is illustrated on the sketch
below.
Over-excavation for structural fill placement below footings should be conducted as shown below.
The over-excavation should be backfilled up to the footing base elevation, with Structural Fill
placed, as recommended in the Earthwork section.
Compacted Aggregate Pier Soil Reinforcement
To control settlement and increase bearing capacity proposed foundations may be supported on a
compacted aggregate pier improved subgrade. Aggregate pier systems are proprietary and
designed by a specialty contractor. The selected aggregate pier specialty contractor should be
contacted to provide engineering analysis and project-specific design information. Based on our
experience on other similar projects, a bearing capacity on the order of 3,000 psf to 4,000 psf may
be achieved. However, the actual spacing, depth, and bearing capacity should be designed by the
specialty contractor and reviewed and approved by Terracon’s geotechnical engineer.
Aggregate pier soil reinforcement systems consists of highly densified aggregate piers.
Reinforcing elements are constructed by excavating a cylindrical cavity (typically 30-inch
diameter) with conventional drilling equipment. The soils at the bottom of the cavity are densified
and prestressed by repeated impact from a specially designed tamper with a beveled head. The
excavation is then backfilled with well-graded crushed stone in compacted lifts. The process
effectively prestressed the soils at the bottom of the cavity vertically and the adjacent matrix soils
laterally. The resulting subgrade is a composite reinforced aggregate pier and soil matrix of
improved shear strength (bearing capacity), stiffness, and capacity to control settlement.
Compacted aggregate pier specialty contractors are design-build organizations and should be
contacted to provide detailed design and feasibility information for this project. We will work with
Geotechnical Engineering Report
Fitts Park Pedestrian Bridge South Salt Lake, Utah
July 26, 2018 Terracon Project No. 61175201
Responsive Resourceful Reliable 10
the specialty contractor to provide the soil information to assist in this system design. If this type
of system is selected, Quality Assurance testing should be performed during installation, including
the observation and documentation of the soil conditions encountered, shaft lengths, amount of
aggregate used, modulus test readings, and tests on the compacted aggregate lifts. Terracon
would be pleased to provide these Quality Assurance services.
SEISMIC CONSIDERATIONS
The seismic design requirements for buildings and other structures are based on Seismic Design
Category. Site Classification is required to determine the Seismic Design Category for a structure.
The Site Classification is based on the upper 100 feet of the site profile defined by a weighted
average value of either shear wave velocity, standard penetration resistance, or undrained shear
strength in accordance with Section 20.4 of ASCE 7-10.
Description Value
Site Class 1
E 2,3
Site Latitude 40.7047
Site Longitude 111.8800
So PGA 0.667
SS Spectral Acceleration for a Short Period 3
1.523g
S1 Spectral Acceleration for a 1-Second Period 3
0.584g
Fa Site Coefficient for a Short Period 0.9
Fv Site Coefficient for a 1-Second Period 2.4
1. Seismic site classification in general accordance with the 2012 International Building Code.
2. The 2012 International Building Code (IBC) uses a site profile extending to a depth of 100 feet for seismic
site classification. Borings at this site were extended to a maximum depth of 51½ feet. The site properties
below the boring depth to 100 feet were estimated based on our experience and knowledge of geologic
conditions of the general area. Additional deeper borings or geophysical testing may be performed to confirm
the conditions below the current boring depth. 3. These values were obtained using online seismic design maps and tools provided by the USGS
(http://earthquake.usgs.gov/hazards/designmaps/).
LIQUEFACTION
Potentially liquefiable soils were encountered in the soil profile of borings B-1, and B-2. Liquefaction
settlement on the order of 1 inch is expected during an earthquake event with a 2% probability of
exceedance in 50 years (PGA = 0.667g). CORROSIVITY
The table below lists the results of laboratory soluble sulfate, soluble chloride, electrical resistivity,
and pH testing. The values may be used to estimate potential corrosive characteristics of the on-
site soils with respect to contact with the various underground materials which will be used for
project construction.
Geotechnical Engineering Report
Fitts Park Pedestrian Bridge South Salt Lake, Utah
July 26, 2018 Terracon Project No. 61175201
Responsive Resourceful Reliable 11
Corrosivity Test Results Summary
Boring
Sample
Depth
(feet)
Soil Description Sulfate
(ppm)
Electrical
Resistivity
(Ω-cm)
pH
B-2 5 Silty Sand 523 611 7.66
An aggressive subsurface environment where corrosion can deteriorate the buried steel over its
design life can generally be identified by soil resistivity and pH tests. The following criteria for
corrosive soil are specified in AASHTO LRFD Section 10.7.5.
Electrical resistivity less than 2,000 ohm-cm
pH less than 5.5
pH between 5.5 and 8.5 in soils with high organic content
On-site soils are considered aggressive to buried steel based on laboratory test results.
Results of soluble sulfate testing indicate samples of the on-site soils tested possess moderate
sulfate concentrations when classified in accordance with Table 4.3.1 of the ACI Design Manual.
Concrete should be designed in accordance with the provisions of the ACI Design Manual,
Section 318, Chapter 4.
A corrosion engineer should be retained to provide additional corrosion protection
recommendations.
Geotechnical Engineering Report
Fitts Park Pedestrian Bridge South Salt Lake, Utah
July 26, 2018 Terracon Project No. 61175201
Responsive Resourceful Reliable 12
GENERAL COMMENTS
As the project progresses, we address assumptions by incorporating information provided by the
design team, if any. Revised project information that reflects actual conditions important to our
services is reflected in the final report. The design team should collaborate with Terracon to
confirm these assumptions and to prepare the final design plans and specifications. This facilitates
the incorporation of our opinions related to implementation of our geotechnical recommendations.
Any information conveyed prior to the final report is for informational purposes only and should
not be considered or used for decision-making purposes.
Our analysis and opinions are based upon our understanding of the project, the geotechnical
conditions in the area, and the data obtained from our site exploration. Natural variations will occur
between exploration point locations or due to the modifying effects of construction or weather.
The nature and extent of such variations may not become evident until during or after construction.
Terracon should be retained as the Geotechnical Engineer, where noted in the final report, to
provide observation and testing services during pertinent construction phases. If variations
appear, we can provide further evaluation and supplemental recommendations. If variations are
noted in the absence of our observation and testing services on-site, we should be immediately
notified so that we can provide evaluation and supplemental recommendations.
Our scope of services does not include either specifically or by implication any environmental or
biological (e.g., mold, fungi, bacteria) assessment of the site or identification or prevention of
pollutants, hazardous materials or conditions. If the owner is concerned about the potential for
such contamination or pollution, other studies should be undertaken.
Our services and any correspondence or collaboration through this system are intended for the
sole benefit and exclusive use of our client for specific application to the project discussed and
are accomplished in accordance with generally accepted geotechnical engineering practices with
no third party beneficiaries intended. Any third party access to services or correspondence is
solely for information purposes to support the services provided by Terracon to our client. Reliance
upon the services and any work product is limited to our client, and is not intended for third parties.
Any use or reliance of the provided information by third parties is done solely at their own risk. No
warranties, either express or implied, are intended or made.
Site characteristics as provided are for design purposes and not to estimate excavation cost. Any
use of our report in that regard is done at the sole risk of the excavating cost estimator as there
may be variations on the site that are not apparent in the data that could significantly impact
excavation cost. Any parties charged with estimating excavation costs should seek their own site
characterization for specific purposes to obtain the specific level of detail necessary for costing.
Site safety, and cost estimating including, excavation support, and dewatering
requirements/design are the responsibility of others. If changes in the nature, design, or location
of the project are planned, our conclusions and recommendations shall not be considered valid
unless we review the changes and either verify or modify our conclusions in writing.
ATTACHM ENTS
ATTACHMENTS
Geotechnical Engineering Report
Fitts Park Pedestrian Bridge South Salt Lake, Utah
July 26, 2018 Terracon Project No. 61175201
Responsive Resourceful Reliable
EXPLORATION AND TESTING PROCEDURES
Field Exploration
Number of Borings Boring Depth (feet) Planned Location
2 50 Bridge abutments
Boring Layout and Elevations: Unless otherwise noted, Terracon personnel provide the boring
layout. Coordinates are obtained with a handheld GPS unit (estimated horizontal accuracy of
about ±10 feet) and approximate elevations are obtained by interpolation from historical maps. If
elevations and a more precise boring layout are desired, we recommend borings be surveyed
following completion of fieldwork.
Subsurface Exploration Procedures: We advanced the borings with a truck-mounted, track-
mounted rotary drill rig using continuous flight augers (solid stem and/or hollow stem as necessary
depending on soil conditions). Four samples were obtained in the upper 10 feet of each boring
and at intervals of 5 feet thereafter. In the thin-walled tube sampling procedure, a thin-walled,
seamless steel tube with a sharp cutting edge is pushed hydraulically into the soil to obtain a relatively
undisturbed sample. In the split-barrel sampling procedure, a standard 2-inch outer diameter
split-barrel sampling spoon is driven into the ground by a 140-pound automatic hammer falling a
distance of 30 inches. The number of blows required to advance the sampling spoon the last 12
inches of a normal 18-inch penetration is recorded as the Standard Penetration Test (SPT)
resistance value. The SPT resistance values, also referred to as N-values, are indicated on the
boring logs at the test depths. We observed and recorded groundwater levels during drilling and
sampling. For safety purposes, all borings were backfilled with auger cuttings after their
completion.
The sampling depths, penetration distances, and other sampling information were recorded on the
field boring logs. The samples were placed in appropriate containers and taken to our soil laboratory
for testing and classification by a geotechnical engineer. Our exploration team prepared field boring
logs as part of the drilling operations. These field logs include visual classifications of the materials
encountered during drilling and our interpretation of the subsurface conditions between samples.
Final boring logs were prepared from the field logs. The final boring logs represent the
geotechnical engineer's interpretation of the field logs and include modifications based on
observations and tests of the samples in our laboratory.
Laboratory Testing
The project engineer reviews the field data and assigns various laboratory tests to better
understand the engineering properties of the various soil strata as necessary for this project.
Procedural standards noted below are for reference to methodology in general. In some cases,
Geotechnical Engineering Report
Fitts Park Pedestrian Bridge South Salt Lake, Utah
July 26, 2018 Terracon Project No. 61175201
Responsive Resourceful Reliable
variations to methods are applied because of local practice or professional judgment. Standards
noted below include reference to other, related standards. Such references are not necessarily
applicable to describe the specific test performed.
ASTM D2216 Standard Test Methods for Laboratory Determination of Water (Moisture)
Content of Soil and Rock by Mass
ASTM D4318 Standard Test Methods for Liquid Limit, Plastic Limit, and Plasticity Index of
Soils
ASTM D422 Standard Test Method for Particle-Size Analysis of Soils
ASTM D2850 Standard Test Method for Unconsolidated-Undrained Triaxial Compression
Test on Cohesive Soils
ASTM D2435/D2435M Standard Test Methods for One-Dimensional Consolidation
Properties of Soils Using Incremental Loading
The laboratory testing program often includes examination of soil samples by an engineer. Based
on the material’s texture and plasticity, we describe and classify the soil samples in accordance
with the Unified Soil Classification System.
SITE LOC ATION AND EXPLOR ATION PLAN S
SITE LOCATION AND EXPLORATION PLANS
SITE LOCATION
Kimley-Horn and Associates, Inc.-Fitts Park Ped Bridge South Salt Lake, UT
June 28, 2018 Terracon Project No. 61175201
TOPOGRAPHIC MAP IMAGE COURTESY OF THE U.S. GEOLOGICAL SURVEY QUADRANGLES INCLUDE: SALT LAKE CITY SOUTH, UT (1/1/1999) and SUGAR
HOUSE, UT (1/1/1998).
DIAGRAM IS FOR GENERAL LOCATION ONLY, AND IS NOT INTENDED FOR CONSTRUCTION PURPOSES
SITE
EXPLORATION PLAN
Kimley-Horn and Associates, Inc.-Fitts Park Ped Bridge South Salt Lake, UT
June 28, 2018 Terracon Project No. 61175201
DIAGRAM IS FOR GENERAL LOCATION ONLY, AND IS
NOT INTENDED FOR CONSTRUCTION PURPOSES AERIAL PHOTOGRAPHY PROVIDED
BY MICROSOFT BING MAPS
EXPLOR ATION RESULTS
EXPLORATION RESULTS
UU
33
30
30
35
43
96
80
32-24-8
38-19-19
34-19-15
42-22-20
2-1-2N=3
2-3-2N=5
0-0-0N=0
TV=1.5 ksfPP=3.5 ksf
0-2-2N=4
0-3-2N=5
2-4-8N=12
2-1-0N=1
0-0-0N=0
0-0-1N=1
0-0-0N=0
8
9
0
18
18
18
12
18
18
18
18
81
96
94
92
0.5
9.5
20.0
24.5
51.5
TOPSOILSILT WITH SAND (ML), brown, moist,medium stiff
no recovery at 7.5
LEAN CLAY (CL), greenish gray, wet, soft
SILTY CLAY (CL-ML), brown, wet, stiff
LEAN CLAY (CL), greenish gray to gray,wet, very soft
Boring Terminated at 51.5 Feet
GR
AP
HIC
LO
G
Hammer Type: AutomaticStratification lines are approximate. In-situ, the transition may be gradual.
TH
IS B
OR
ING
LO
G IS
NO
T V
ALI
D IF
SE
PA
RA
TE
D F
RO
M O
RIG
INA
L R
EP
OR
T.
G
EO
SM
AR
T L
OG
-NO
WE
LL 6
117
520
1 F
ITT
S P
AR
K P
ED
BR
.GP
J T
ER
RA
CO
N_D
AT
AT
EM
PLA
TE
.GD
T 7
/26/
18
CO
MP
RE
SS
IVE
ST
RE
NG
TH
(psf
)
ST
RA
IN (
%)
TE
ST
TY
PE
WA
TE
RC
ON
TE
NT
(%
)
DR
Y U
NIT
WE
IGH
T (
pcf)
LL-PL-PI
ATTERBERGLIMITS
WA
TE
R L
EV
EL
OB
SE
RV
AT
ION
S
DE
PT
H (
Ft.)
5
10
15
20
25
30
35
40
45
50
SA
MP
LE T
YP
E STRENGTH TEST
FIE
LD T
ES
TR
ES
ULT
S
RE
CO
VE
RY
()
PE
RC
EN
T F
INE
S
East Front Ave South Salt Lake, UTSITE:
Page 1 of 1
Advancement Method:
Abandonment Method:Boring backfilled with Auger Cuttings and/or Bentonite
Notes:
Project No.: 61175201
Drill Rig: Geoprobe 6620 DT
Boring Started: 06-11-2018
BORING LOG NO. B-1Kimley-Horn and Associates, Inc.CLIENT:Salt Lake City, UT
Driller: Direct Push
Boring Completed: 06-11-2018
Exhibit: A-1
See Exhibit A-3 for description of fieldprocedures.See Appendix B for description of laboratoryprocedures and additional data (if any).
See Appendix C for explanation of symbols andabbreviations.
PROJECT: Fitts Park Ped Bridge
6949 S High Tech Dr Ste 100Midvale, UT
10 feet while drilling
WATER LEVEL OBSERVATIONS
DEPTH
LOCATION See Exhibit A-2
Latitude: 40.7047° Longitude: -111.8799°
UU
2-2-1N=3
3-4-3
3-3-4N=7
3-3-3N=6
0-0-2N=2
6-9-8N=17
1-1-1N=2
0-0-1N=1
0-0-0N=0
0-0-0N=0
0-0-0N=0
4-3-3N=6
36
32
26
37
43
88
NP
29-19-10
NP
29-19-10
38-22-16
5
12
18
18
18
12
10
15
18
18
18
18
42
87
75
91
92
0.5
7.0
18.5
23.0
51.5
TOPSOIL, reddish brownSILTY SAND (SM), brown, moist, veryloose to loose
LEAN CLAY (CL), light gray to greenishgray, moist, medium stiff to very soft
SILT WITH SAND (ML), brown, wet, stiff
LEAN CLAY (CL), greenish gray, wet, verysoft to medium stiff, silt lenses
trace silt lenses at 45'
Boring Terminated at 51.5 Feet
GR
AP
HIC
LO
G
Hammer Type: AutomaticStratification lines are approximate. In-situ, the transition may be gradual.
TH
IS B
OR
ING
LO
G IS
NO
T V
ALI
D IF
SE
PA
RA
TE
D F
RO
M O
RIG
INA
L R
EP
OR
T.
G
EO
SM
AR
T L
OG
-NO
WE
LL 6
117
520
1 F
ITT
S P
AR
K P
ED
BR
.GP
J T
ER
RA
CO
N_D
AT
AT
EM
PLA
TE
.GD
T 7
/26/
18
CO
MP
RE
SS
IVE
ST
RE
NG
TH
(psf
)
ST
RA
IN (
%)
TE
ST
TY
PE
WA
TE
RC
ON
TE
NT
(%
)
ATTERBERGLIMITS
WA
TE
R L
EV
EL
OB
SE
RV
AT
ION
S
DE
PT
H (
Ft.)
5
10
15
20
25
30
35
40
45
50
SA
MP
LE T
YP
E STRENGTH TEST
FIE
LD T
ES
TR
ES
ULT
S
RE
CO
VE
RY
()
DR
Y U
NIT
WE
IGH
T (
pcf)
LL-PL-PI
PE
RC
EN
T F
INE
S
East Front Ave South Salt Lake, UTSITE:
Page 1 of 1
Advancement Method:
Abandonment Method:Boring backfilled with Auger Cuttings and/or Bentonite
Notes:
Project No.: 61175201
Drill Rig: Geoprobe 6620 DT
Boring Started: 06-11-2018
BORING LOG NO. B-2Kimley-Horn and Associates, Inc.CLIENT:Salt Lake City, UT
Driller: Direct Push
Boring Completed: 06-11-2018
Exhibit: A-2
See Exhibit A-3 for description of fieldprocedures.See Appendix B for description of laboratoryprocedures and additional data (if any).
See Appendix C for explanation of symbols andabbreviations.
PROJECT: Fitts Park Ped Bridge
6949 S High Tech Dr Ste 100Midvale, UT
8 feet while drilling
WATER LEVEL OBSERVATIONS
DEPTH
LOCATION See Exhibit A-2
Latitude: 40.7047° Longitude: -111.8797°
Before Consolidation
Sample Diameter (in): 2.50 Moist Unit Weight (pcf): 120
Sample Height (in): 1 Moisture Content (%): 25
Sample Volume (cf): 0.0028 Dry Unit Weight (pcf): 96
After Consolidation
Sample Diameter (in): 2.50 Moist Unit Weight (pcf): 130
Sample Height (in): 0.91276 Moisture Content (%): 24
Sample Volume (cf): 0.0026 Dry Unit Weight (pcf): 105
Liquid Limit: 38 Percent Fines: 96
Plasticity Index: 19 Classification: Lean Clay (CL)
Project Name:
Project No.:
Location:
Sample:
Consolidation Test Data (ASTM D 2435-04 )
Fitt's Park Pedestrian Bridge
61175201
B-1 @10 ft.
Salt Lake City, UT
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
0.1 1 10 100
VER
TIC
AL
STR
AIN
, %
VERTICAL STRESS, ksf
Before Consolidation
Sample Diameter (in): 2.50 Moist Unit Weight (pcf): 114
Sample Height (in): 1 Moisture Content (%): 42
Sample Volume (cf): 0.0028 Dry Unit Weight (pcf): 80
After Consolidation
Sample Diameter (in): 2.50 Moist Unit Weight (pcf): 126
Sample Height (in): 0.8006 Moisture Content (%): 26
Sample Volume (cf): 0.0023 Dry Unit Weight (pcf): 100
Liquid Limit: 42 Percent Fines: 92
Plasticity Index: 20 Classification: Lean Clay (CL)
Project Name:
Project No.:
Location:
Sample:
Consolidation Test Data (ASTM D 2435-04 )
Fitt's Park Pedestrian Bridge
61175201
B-1 @35 ft.
Salt Lake City, UT
0.0
5.0
10.0
15.0
20.0
25.0
30.0
0.1 1 10 100
VER
TIC
AL
STR
AIN
, %
VERTICAL STRESS, ksf
Before Consolidation
Sample Diameter (in): 2.50 Moist Unit Weight (pcf): 118
Sample Height (in): 1 Moisture Content (%): 33
Sample Volume (cf): 0.0028 Dry Unit Weight (pcf): 88
After Consolidation
Sample Diameter (in): 2.50 Moist Unit Weight (pcf): 128
Sample Height (in): 0.8537 Moisture Content (%): 24
Sample Volume (cf): 0.0024 Dry Unit Weight (pcf): 104
Liquid Limit: 29 Percent Fines: 87
Plasticity Index: 10 Classification: Lean Clay (CL)
Project Name:
Project No.:
Location:
Sample:
Consolidation Test Data (ASTM D 2435-04 )
Fitt's Park Pedestrian Bridge
61175201
B-2 @12.5 ft.
Salt Lake City, UT
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
20.0
0.1 1 10 100
VER
TIC
AL
STR
AIN
, %
VERTICAL STRESS, ksf
Unconsolidated-Undrained Triaxial Compression Test on Cohesive Soils(ASTM D2850) © IGES 2005, 2018
Project: Boring No.:No: Sample:
Location: Depth:Date: Sample Description:
By: Sample type:
Specific gravity, Gs 2.70 AssumedSample height, H (in.) 5.989
Sample diameter, D (in.) 2.867
Sample volume, V (ft3) 0.0224 Wet soil + tare (g) 494.28
Wt. rings + wet soil (g) 1136.25 Dry soil + tare (g) 379.97Wt. rings/tare (g) 0.00 Tare (g) 127.48
Moist soil, Ws (g) 1136.25 Water content, w (%) 45.3Moist unit wt., m (pcf) 112.0 Confining stress,3 (psf) 4320
Dry unit wt., d (pcf) 77.1 Shear rate (in/min) 0.0180
Saturation (%) 102.6 Strain at failure, f (%) 1.95
Void ratio, e 1.19 Deviator stress at failure, 1-3)f (psf) 1751
Axial d Q Shear stress at failure, qf = 1-3)f/2 (psf) 876
Strain 1-3 1/2 d
(%) (psf) (psf)0.00 0.0 0.00.05 131.8 65.90.10 210.7 105.40.15 313.0 156.50.20 353.7 176.90.25 464.6 232.30.30 546.1 273.1 Maximum data point 160.35 621.7 310.9 Strain at max deviator stress 1.9510.40 700.2 350.1 Max deviator stress 1751.480.45 758.1 379.0 Max shear stress 875.740.70 1093.3 546.60.95 1371.7 685.81.20 1570.3 785.11.45 1678.3 839.11.70 1733.7 866.81.95 1751.5 875.72.20 1717.4 858.72.45 1675.0 837.52.70 1627.0 813.52.95 1573.5 786.73.20 1545.8 772.93.45 1535.3 767.63.70 1536.1 768.03.95 1534.0 767.04.20 1537.6 768.84.45 1532.7 766.34.70 1547.4 773.74.95 1575.9 787.95.45 1604.7 802.35.95 1627.5 813.76.45 1600.6 800.36.95 1576.5 788.27.45 1539.1 769.57.95 1528.9 764.48.45 1556.4 778.28.95 1567.4 783.79.45 1554.3 777.19.95 1538.5 769.210.45 1514.9 757.410.95 1488.9 744.411.45 1494.2 747.111.95 1512.3 756.112.45 1514.6 757.312.95 1473.4 736.713.45 1450.3 725.113.95 1414.6 707.314.45 1396.9 698.414.95 1396.8 698.4
Z:\PROJECTS\M00385_Terracon\260_Fitts_Park_Ped_Bridge\[UUv1.xlsm]1Reviewed:___________
Entered by:___________
Terracon B-1M00385-260 (61175201)
EH Undisturbed
Fitts Park Ped Bridge 35.0-36.5'6/18/2018 Grey clay
1751
0
200
400
600
800
1000
1200
1400
1600
1800
0 5 10 15
Dev
iato
r st
ress
, 1- 3
(psf
)
Axial strain (%)
Unconsolidated-Undrained Triaxial Compression Test on Cohesive Soils(ASTM D2850) © IGES 2005, 2018
Project: Boring No.:No: Sample:
Location: Depth:Date: Sample Description:
By: Sample type:
Specific gravity, Gs 2.80 AssumedSample height, H (in.) 6.003
Sample diameter, D (in.) 2.856
Sample volume, V (ft3) 0.0223 Wet soil + tare (g) 490.80
Wt. rings + wet soil (g) 1224.88 Dry soil + tare (g) 403.35Wt. rings/tare (g) 0.00 Tare (g) 127.15
Moist soil, Ws (g) 1224.88 Water content, w (%) 31.7Moist unit wt., m (pcf) 121.3 Confining stress,3 (psf) 1500
Dry unit wt., d (pcf) 92.2 Shear rate (in/min) 0.0180
Saturation (%) 98.5 Strain at failure, f (%) 14.95
Void ratio, e 0.90 Deviator stress at failure, 1-3)f (psf) 2297
Axial d Q Shear stress at failure, qf = 1-3)f/2 (psf) 1148
Strain 1-3 1/2 d
(%) (psf) (psf)0.00 0.0 0.00.05 101.8 50.90.10 170.5 85.30.15 218.2 109.10.20 262.9 131.40.25 304.5 152.20.30 340.1 170.0 Maximum data point 480.35 381.6 190.8 Strain at max deviator stress 14.9510.40 420.1 210.1 Max deviator stress 2296.990.45 458.6 229.3 Max shear stress 1148.4950.70 650.3 325.10.95 826.2 413.11.20 983.4 491.71.45 1128.0 564.01.70 1248.2 624.11.95 1356.0 678.02.20 1448.6 724.32.45 1529.0 764.52.70 1606.1 803.02.95 1676.8 838.43.20 1735.7 867.83.45 1791.2 895.63.70 1837.8 918.93.95 1881.2 940.64.20 1921.5 960.74.45 1955.9 977.94.70 1987.1 993.54.95 2012.5 1006.25.45 2057.0 1028.55.95 2095.3 1047.66.45 2130.3 1065.16.95 2156.4 1078.27.45 2182.0 1091.07.95 2207.2 1103.68.45 2221.1 1110.58.95 2231.9 1115.99.45 2239.7 1119.89.95 2252.7 1126.310.45 2262.6 1131.310.95 2269.7 1134.811.45 2284.5 1142.211.95 2280.4 1140.212.45 2281.5 1140.712.95 2285.0 1142.513.45 2288.4 1144.213.95 2286.3 1143.114.45 2294.4 1147.214.95 2297.0 1148.515.45 2291.9 1145.915.95 2286.7 1143.316.45 2286.3 1143.116.95 2285.7 1142.817.45 2287.5 1143.717.95 2284.1 1142.018.45 2283.0 1141.518.95 2269.6 1134.819.45 2263.4 1131.719.95 2254.6 1127.3
Z:\PROJECTS\M00385_Terracon\260_Fitts_Park_Ped_Bridge\[UUv1.xlsm]2
Entered by:___________
Reviewed:___________
6/20/2018 Grey clay
BRR Undisturbed
Terracon B-2M00385-260 (61175201) Fitts Park Ped Bridge 12.5-14.0'
2297
0
500
1000
1500
2000
2500
0 5 10 15 20
Dev
iato
r st
ress
, 1- 3
(psf
)
Axial strain (%)
SUPPORTING INFORM ATION
SUPPORTING INFORMATION
Steeplechase Project Phase 2 Eagle Mountain, Utah
7/6/2018 Terracon Project No. 61185018A
500 to 1,000
> 8,000
4,000 to 8,000
2,000 to 4,000
1,000 to 2,000
less than 500
Unconfined Compressive StrengthQu, (psf)
AugerCuttings
ModifiedCaliforniaRingSampler
ModifiedCaliforniaRingSampler
GrabSample
ShelbyTube
StandardPenetrationTest
Trace
PLASTICITY DESCRIPTION
Water levels indicated on the soil boring logs arethe levels measured in the borehole at the timesindicated. Groundwater level variations will occurover time. In low permeability soils, accuratedetermination of groundwater levels is notpossible with short term water levelobservations.
DESCRIPTION OF SYMBOLS AND ABBREVIATIONSGENERAL NOTES
> 30
11 - 30
1 - 10Low
Non-plastic
Plasticity Index
#4 to #200 sieve (4.75mm to 0.075mm
Boulders
12 in. to 3 in. (300mm to 75mm)Cobbles
3 in. to #4 sieve (75mm to 4.75 mm)Gravel
Sand
Passing #200 sieve (0.075mm)Silt or Clay
Particle Size
Water Level Aftera Specified Period of Time
Water Level After aSpecified Period of Time
Water InitiallyEncountered
Soil classification is based on the Unified Soil Classification System. Coarse Grained Soils have more than 50% of theirdry weight retained on a #200 sieve; their principal descriptors are: boulders, cobbles, gravel or sand. Fine Grained Soilshave less than 50% of their dry weight retained on a #200 sieve; they are principally described as clays if they are plastic,and silts if they are slightly plastic or non-plastic. Major constituents may be added as modifiers and minor constituentsmay be added according to the relative proportions based on grain size. In addition to gradation, coarse-grained soils aredefined on the basis of their in-place relative density and fine-grained soils on the basis of their consistency.
GRAIN SIZE TERMINOLOGY
RELATIVE PROPORTIONS OF FINESRELATIVE PROPORTIONS OF SAND AND GRAVEL
DESCRIPTIVE SOIL CLASSIFICATION
LOCATION AND ELEVATION NOTES
SAMPLING WATER LEVEL FIELD TESTSN
(HP)
(T)
(DCP)
UC
(PID)
(OVA)
Standard Penetration TestResistance (Blows/Ft.)
Hand Penetrometer
Torvane
Dynamic Cone Penetrometer
Unconfined CompressiveStrength
Photo-Ionization Detector
Organic Vapor Analyzer
Medium
0Over 12 in. (300 mm)
>12
5-12
<5
Percent ofDry Weight
TermMajor Component of Sample
Modifier
With
Trace
Descriptive Term(s) ofother constituents
>30Modifier
<15
Percent ofDry Weight
Descriptive Term(s) ofother constituents
With 15-29
High
Unless otherwise noted, Latitude and Longitude are approximately determined using a hand-held GPS device. Theaccuracy of such devices is variable. Surface elevation data annotated with +/- indicates that no actual topographicalsurvey was conducted to confirm the surface elevation. Instead, the surface elevation was approximately determined fromtopographic maps of the area.
Descriptive Term(Consistency)
0 - 6
Standard Penetration orN-Value
Blows/Ft.
CONSISTENCY OF FINE-GRAINED SOILS
Hard
Very Loose
Loose
Medium Dense
Dense
Very Dense
Descriptive Term(Density)
Standard Penetrationor N-ValueBlows/Ft.
Ring SamplerBlows/Ft.
0 - 3
4 - 9 7 - 18
10 - 29 19 - 58
30 - 50 59 - 98
> 30
> 50 > 99 Very Stiff
Stiff
Medium Stiff
Soft
Very Soft
(50% or more passing the No. 200 sieve.)Consistency determined by laboratory shear strength testing, field visual-manual
procedures or standard penetration resistance
STRENGTH TERMS
RELATIVE DENSITY OF COARSE-GRAINED SOILS
(More than 50% retained on No. 200 sieve.)Density determined by Standard Penetration Resistance
0 - 1
2 - 4
4 - 8
8 - 15
15 - 30
UNIFIED SOIL CLASSIFICATION SYSTEM
Fitts Park Pedestrian Bridge South Salt Lake, Utah
July 26, 2018 Terracon Project No. 61175201
UNIFIED SOIL C LASSIFIC ATION SYSTEM
Criteria for Assigning Group Symbols and Group Names Using Laboratory Tests A Soil Classification
Group
Symbol Group Name B
Coarse-Grained Soils:
More than 50% retained
on No. 200 sieve
Gravels:
More than 50% of
coarse fraction
retained on No. 4 sieve
Clean Gravels:
Less than 5% fines C
Cu 4 and 1 Cc 3 E GW Well-graded gravel F
Cu 4 and/or 1 Cc 3 E GP Poorly graded gravel F
Gravels with Fines:
More than 12% fines C
Fines classify as ML or MH GM Silty gravel F, G, H
Fines classify as CL or CH GC Clayey gravel F, G, H
Sands:
50% or more of coarse
fraction passes No. 4
sieve
Clean Sands:
Less than 5% fines D
Cu 6 and 1 Cc 3 E SW Well-graded sand I
Cu 6 and/or 1 Cc 3 E SP Poorly graded sand I
Sands with Fines:
More than 12% fines D
Fines classify as ML or MH SM Silty sand G, H, I
Fines classify as CL or CH SC Clayey sand G, H, I
Fine-Grained Soils:
50% or more passes the
No. 200 sieve
Silts and Clays:
Liquid limit less than 50
Inorganic: PI 7 and plots on or above “A”
line J
CL Lean clay K, L, M
PI 4 or plots below “A” line J ML Silt K, L, M
Organic: Liquid limit - oven dried
0.75 OL Organic clay K, L, M, N
Liquid limit - not dried Organic silt K, L, M, O
Silts and Clays:
Liquid limit 50 or more
Inorganic: PI plots on or above “A” line CH Fat clay K, L, M
PI plots below “A” line MH Elastic Silt K, L, M
Organic: Liquid limit - oven dried
0.75 OH Organic clay K, L, M, P
Liquid limit - not dried Organic silt K, L, M, Q
Highly organic soils: Primarily organic matter, dark in color, and organic odor PT Peat
A Based on the material passing the 3-inch (75-mm) sieve
B If field sample contained cobbles or boulders, or both, add “with cobbles
or boulders, or both” to group name.
C Gravels with 5 to 12% fines require dual symbols: GW-GM well-graded
gravel with silt, GW-GC well-graded gravel with clay, GP-GM poorly graded gravel with silt, GP-GC poorly graded gravel with clay.
D Sands with 5 to 12% fines require dual symbols: SW-SM well-graded
sand with silt, SW-SC well-graded sand with clay, SP-SM poorly graded sand with silt, SP-SC poorly graded sand with clay
E Cu = D60/D10 Cc =
6010
2
30
DxD
)(D
F If soil contains 15% sand, add “with sand” to group name.
G If fines classify as CL-ML, use dual symbol GC-GM, or SC-SM.
H If fines are organic, add “with organic fines” to group name.
I If soil contains 15% gravel, add “with gravel” to group name.
J If Atterberg limits plot in shaded area, soil is a CL-ML, silty clay.
K If soil contains 15 to 29% plus No. 200, add “with sand” or “with
gravel,” whichever is predominant.
L If soil contains 30% plus No. 200 predominantly sand, add
“sandy” to group name.
M If soil contains 30% plus No. 200, predominantly gravel, add
“gravelly” to group name.
N PI 4 and plots on or above “A” line.
O PI 4 or plots below “A” line.
P PI plots on or above “A” line.
Q PI plots below “A” line.