Generator Data
Direct Axis Tran Reactance Xd´=20.8%Direct Axis Syn Reactance Xs = 182.5%
Rated MVA = 247
Rated Voltage = 15.75kVRated Amp = 9054A ,SCR:0.586
GT
UATG
ener
a to r
GT Rated MVA = 250MVAImpedance 14% ,420/15.75kVRated voltage 400kV,Ynd1Fault MVA 40kA (27712MVA)
UAT rated MVA 16MVARated voltage 15.75/6.9kVImpedance 7%,Dyn11
GEN
R
Generator & Out-Line Equipments
GT YNd1
UAT
GEN
NGT
CB122 3
4
ISO-D
ISO-A
ISO-B
ISO-C
M1
M2
TRCB
CB
UNIT BUS
UNIT BUS
CT500/ 1
CT-3600 / 510000 / 5
CT-3CT-310000 / 5
CT- 3
NCT 150 / 1
7
6
CT-3
CT-31600/11600 / 5
11 NCT400/ 1
Gen-PT-3
8
9. 95400A 10sec
9
NCT1600 / 5
NCT200/11600 / 5
NGR
NGR
15.75 kV/ 240V75 KVA
NGR0. 456340A 5min
BUS
1
GRP
Bus-PT-3
GCB
FBOPEN
UATC/O
GCBOPEN
A / B / A / B / C
BOILER TRIP A TURBINE
TRIPA / B
TURBINE
TRIP
10
BCT400/1
5
10000/5
100% Stator E/F &Inter-turn Fault
Dyn11
GCB OPEN & TLR operated
LA
List of Relays for Generator Protection
NO NAME OF RELAY PURPOSE ACTION
1 DIFFERENTIAL PROT. (87G) PROTECTION TRIPPING , CLASS-A
2 100% STATOR E/F (64G) PROTECTION TRIPPING, CLASS-A
3 ROTOR EARTH FAULT (64R) PROTECTION TRIPPING, CLASS-A
4 INTER-TURN FAULT (95G) PROTECTION TRIPPING, CLASS-A
5 STATOR BACK UP E/F (51NG) PROTECTION TRIPPING, CLASS-A
6 LOCAL BKR. BACKUP (50Z) PROTECTION TRIPPING, CLASS-A
7 BACKUP IMPD PRE-SYN (21G1) PROTECTION TRIPPING, CLASS-A
8 BACKUP IMP. POST-SYN (21G2) PROTECTION TRIPPING, CLASS-A
9 OVER VOLT. STAGE-1 (59G1) PROTECTION AVR AUTO C/O MAN CH
10 OVER VOLT. STAGE-2 (59G2) PROTECTION TRIPPING, CLASS-A
11 LOW FORWARD POWER (37G) PROTECTION TRIPPING, CLASS-C
12 REVERSE POWER (32G) PROTECTION TRIPPING, CLASS-B
13 OVER FREQUENCY (81F2) PROTECTION TRIPPING, CLASS-B
14 FIELD FAILURE (40G) PROTECTION TRIPPING, CLASS-B
15 UNDER FREQUENCY,(81F1) PROTECTION TRIPPING, CLASS-C
16 THERMAL OVERLOAD (51GTh) PROTECTION TRIPPING, CLASS-C
17 NEGATIVE PH SEQUENCE(46G) PROTECTION TRIPPING, CLASS-C
18 POLE SLIPPING (78G) PROTECTION TRIPPING, CLASS-C
19 CHECK SYNCHRONISING (25G) PROTECTION CLOSING PERMISSIVE
CLASS-A MFR,TLR & GEN CKT. BKR.OPEN, CLASS-B TLR,GEN CKT BKR OPEN, CLASS-CGEN CKT BKR
Generator Differential Relay(87G)
GEN GT
87 Class-A TripIop=10%
Stab. Res
CT-2 CT-3
Generator Stator Earth Fault(64G)
GEN GT
N Dis Unit & 3rd Her Unit
Generator Winding
Blnd Zone
N L3rd Her UnitNeutral Dis
Unit
Class-A Trip with tdPVMM163
V3
VN3
VL3
VL3
VN3
Slop
e m
1
Slope m2
Generator Rotor Earth Fault(64R)
Gen Fld Wndg
Main Exct
Resistance
Rotor E/F Relay
Class –A Trip
DC
Meas.volt Um
50V+/-
<80kOhm –Alarm & <5kOhm-Trip
Generator Field Failure Relay(40G)
GEN
40GClass-B Trip with td 2.0 Sec
-X
Z1=1.5Ohm
Z2=25.9Ohm
+R
Syn Gen.
Ind.Gen
Load
Loss of Field
U/V (<75%) Class-B Trip Inst.
CT-2
Generator Low Forward Power Relay(37G)
GEN
37G
Power Flow
GT
UAT
UAT
GCB
Class-C Trip TLRFB Close
TLR Reset
Blocking
CT-2
Generator Reverse Power Relay(32G)
GEN GT
32G
UAT
UAT
GCB
TLR Class-C Trip with Td 2.5 Sec
Power Flow
Class-B Trip with Td 5.0 Sec
Setting: 0.5%Pn
Ch. Angle: 90Deg
VBY
VR
VYVB
IRIV θ
)
CT-2
Generator Under Frequency Relay(81F1)
GEN
Class-C Trip with Td 2.5 Sec
81G1
Generator Over Frequency Relay(81F2)
GEN
Class-B Trip with Td 2.5 Sec
81G2
Generator Pole Slipping relay(ZTO)
GEN
78GClass-C Trip
75deg
Load AreaSource
Area+R
X
Dir. Unit (A)
Blinder Unit (B)
Ope
ratin
g .Z
one
R
Locus of Pole Slip
Typical Power Swing Locus
40msT
CT-2
Generator Negative Phase Seq.(RARIB)
GEN
46G
Class-C Trip Start of time measure at (8% of Im)
0.1
1.0
10
100
1000
10 100 250Insc
(t/K)
5005
K=8
Operating Curve
CT-2
Generator Over voltage(Stage-I)59G1
GEN
59G1AVR Change over from Auto to Man
Setting 110% 2.0Sec
Generator Over voltage(Stage-II)59G2
GEN
59G2
Setting 120% 1.0Sec
Class-A Trip
Generator Over current Relay(51G)
GEN
51GAlarm only
CT-2
Generator Thermal Over Load(51Gth)
GEN
51GthClass C Trip
Thermal current setting=0.92XIn
Heating Time constant TH =1min
t=THln(Ieq/Is)²
(Ieq/Is)²-1.0609CT-2
Generator Intern Fault Protection(95G)
95G
NGR
IVT 110/80v
IVT 25.4/110v
R
Y
B
PT Supply
Setting 7.5v0.456
Generator Stator Backup Earth Fault(51NG)
Class-A TripN Dis Unit
GEN GT
51NG
NGR
0.456ohm
0.456 /300A
150/1 A
15.75kV/240V,75kVA
Generator LBB Protection (50Z)
GEN GT
GCB
50Z
UAT
UAT
Class-A Trip with td
+ ve Trip relay
Optd (86)
CT-1
Generator Check-Syn. Relay(25)
GEN GT
CHK. SYN. RELAY
EHV BUS
GEN PT
(VR-Y)
BUS PT
(VR-N)
YNd1
VR-N
R
YB
R
Y
BN
T=1/(fR-fI)
VR
VI
VR
VI
V
t
P
21G1 Gen Backup Impd. Relay(Pre-Syn)
GEN GT
21G1Class-A Trip with td
GCB
GCB OFF
14.24%UAT
UAT
7%
Reverse Reach 25%
of Frd
16%
Z=1.5ohm Td=0.5s
CT-2
21G2 Gen Backup Impd. Relay (Post-Synchronize)
GEN GT
21G121G2
GCB
Class-A Trip with td
IBT 12%
Reverse Reach 25%
of Frd
UAT
UAT
UAT
Z=1.68ohm Td=2.0s
CT-3