Generator Specification · 2020. 8. 10. · Engine ref. P126TI-II Engine type 4-stroke diesel...

4
D388D6 INDUSTRIAL RANGE POWERED BY DOOSAN POWER DEFINITION PRPPrime Power is abailanle for an unlimited number of annual operating hours in variable load applications, in accordance with ISO 8528-1. ESP:The standby power rating is applicable for supplying emergen- cy power in variable load applications in accordance with ISO 8528-1.Overload is not allowed TERMS OF USE According to the standard, the nominal power assigned by the genset is given for 25 ° C Air Intlet Temperature, of a barometric pressure of 100 kPA (100 m A.S.L), and 30 % relative humidity. For particular conditions in your installation, refer to the derating table. TERMS OF USE For the generating sets used indoor, where the acoustic pressure levels depends on the installation conditions, it is not possible to specify the ambient noise level in the exploitation and maintenance instructions. You will also find in our exploitation and maintenance instructions a warning concerning the air noise dangers and the need to imple- ment appropriated preventive measures. Generator Specification POWER kVA 350 388 POWER kW r.p.m 280 310 RATED SPEED 1800 STANDARD VOLTAGE V AVAILABLE VOLTAGES V RATED AT POWER FACTOR Cos Phi 0,8 SERVICE PRP EPS Weight And Dimensions Length(L) Dimension Open Silent mm 2970 4155 mm 1450 1155 mm Kg 2700 3620 L 730 600 1725 2210 Net Weight Fuel Tank L H W L H W B ISO 9001 BUREAU VERITAS U R E Certification A U V E R I T A S 1 8 2 8 Copy Right 2020 @ AGG POWER www.aggpower.com WATER-COOLED THREE PHASE 60 Hz 60 HZ DIESEL D DUAL-WALL FUEL TANK OptionalWidth(W) Height(H) TBD 220/127 440/254

Transcript of Generator Specification · 2020. 8. 10. · Engine ref. P126TI-II Engine type 4-stroke diesel...

  • D388D6 INDUSTRIAL RANGE POWERED BY DOOSAN

    POWER DEFINITIONPRP:Prime Power is abailanle for an unlimited number of annual operating hours in variable load applications, in accordance with ISO 8528-1.ESP:The standby power rating is applicable for supplying emergen-cy power in variable load applications in accordance with ISO 8528-1.Overload is not allowed

    TERMS OF USEAccording to the standard, the nominal power assigned by the genset is given for 25 ° C Air Intlet Temperature, of a barometric pressure of 100 kPA (100 m A.S.L), and 30 % relative humidity. For particular conditions in your installation, refer to the derating table.

    TERMS OF USEFor the generating sets used indoor, where the acoustic pressure levels depends on the installation conditions, it is not possible to specify the ambient noise level in the exploitation and maintenance instructions.You will also find in our exploitation and maintenance instructions a warning concerning the air noise dangers and the need to imple-ment appropriated preventive measures.

    Generator Specification

    POWER kVA 350 388

    POWER kW

    r.p.m

    280 310

    RATED SPEED 1800

    STANDARD VOLTAGE V

    AVAILABLE VOLTAGES V

    RATED AT POWER FACTOR Cos Phi 0,8

    SERVICE PRP EPS

    Weight And DimensionsLength(L)

    Dimension Open Silent

    mm 2970 4155

    mm 14501155

    mm

    Kg 2700 3620

    L 730 600

    1725 2210

    Net Weight

    Fuel Tank

    L

    H

    W

    L

    H

    W

    B

    ISO 9001BUREAU VERITAS

    UR

    E

    Certification

    A U V ERITA

    S

    1 8 2 8

    Copy Right 2020 @ AGG POWER www.aggpower.com

    WATER-COOLED THREE PHASE 60Hz 60 HZ DIESEL D DUAL-WALL FUEL TANK (Optional)

    Width(W)

    Height(H)

    TBD

    220/127 440/254

  • Engine Specifications

    Engine brand DOOSAN

    Engine ref. P126TI-II

    4-stroke dieselEngine type

    Governor type Electronic

    DirectInjection

    Aspiration

    Number of cylinders and arrangement

    Bore and stroke

    Displacement

    Cooling system

    Lube oil consumption with full load

    Engine oil capacity

    Compression Ratio

    Total coolant capacity

    Air Filter

    TI

    6-L

    123*155

    11.1

    Water-cooled

    mm

    L

    L

    17.1:1

    0.5%-1% of fuel consumption

    23

    L

    Type

    51

    Dry

    General Engine Data General Engine Data

    Fuel

    Consumption @ 100% load ESP

    Consumption @ 100% load PRP

    Consumption @ 75% load PRP

    Consumption @ 50% load PRP

    L/H

    L/H

    L/H

    L/H

    89.5

    73.8

    56.0

    37.0

    Alternator Specifications

    Number of phase 3 Self-excited, brushless

    AVR (Electronic)

    Single bearing

    Flexible disc

    Standard (Vacuum impregnation)

    Power factor (Cos Phi) 0.8

    Poles 4

    Winding Connections (standard) Star-serie

    Insulation H class

    IP23Enclosure(according IEC-34-5)

    Excitation system

    No. of bearings

    Voltage regulator

    Coupling system

    Coating type

    Alternator Specifications Alternator Specifications

    Diesel engine Dry air filter Water jacked heater (Optional)

    Radiator water level sensor (Optional)

    Oil heater (Optional)

    Heavy duty air filter (Optional)

    Radiator with pusher fan

    Electronic govornor

    Hot parts protection

    Moving parts protection

    4-stroke cycle

    Water-cooled

    12V electrical system

    Water separator filter

    Self-excited and self-regulated

    IP23 protection

    Alternator pre-heater (Optional)

    Winding temp. measuring instrument (Optional)

    PMG/AREP/MAUX (Optional)H class insulation

    Copy Right 2020 @ AGG POWER www.aggpower.com

    D388D6

  • Application Data

    Genset version

    Fuel system

    Fuel oil specifications

    Standard fuel tank capacity (Open) L 730

    Diesel

    600Standard fuel tank capacity (Silent) L

    Exhaust system

    Maximum exhaust temperature

    Exhaust gas flow

    Maximum allowed back pressure

    °C

    kPa

    kW

    Ah

    580

    L/s 1070

    5.9

    6

    120

    2

    Air system

    Intake air flow

    Cooling air flow

    L/s 504

    L/s 8833

    Starting System

    Starting power

    Recommended batter

    Number of Batteries

    This document is not contractual - The AGG company reserves the right to modify any of the characteristics stated in this

    document without notice, in a constant effort to improve the quality of its products. *ISO 8528. .

    AGG Power gensets are compliant with ISO 9001 and CE standard, which include the following directives:

    ·2006/42/EC Machinery safety.

    ·2006/95/EC Low voltage

    ·EN 60204-1: 2006+A1: 2009, EN ISO 12100: 2010, EN ISO 13849-1: 2008, EN 12601 : 2010

    Standard reference ConditionsAmbient conditions of reference according to ISO 8528-1:2018 normative: 1000 mbar, 25ºC, 30% relative humidity.

    Weights and dimensions based on standard products. Illustrations may include optional equipment.

    Technical data described in this catalogue correspond to the available information at the moment of printing.

    Steel chasis Chassis with integrated fuel tank

    Fuel level gauge

    High mechanical strength

    Epoxy polyester powder coating

    Emergency stop button

    Anti-vibration shock absorbers

    Trailer type (Optional)

    Fuel tank drain plug

    Steel residential silencer - 20dbA attenuation

    Battery charger

    Dual-wall fuel tank (Optional)

    D388D6

    Copy Right 2020 @ AGG POWER www.aggpower.com

    24VAuxiliary voltage Vdc

  • Control Panel DataFeatures of the Control Panel

    Voltage between phases

    Voltage between neutral and phase

    Current intensities

    Frequency

    Apparent power (Kva)

    Active power (Kw)

    Reactive power (kVAr)

    Power factor

    Voltage between phases

    Emergency stop

    Binary inputs

    Analog inputs

    2x10A Current outputs

    I/O Configuration

    D+ Function

    Speed sensor

    Amf/Mrs

    GCB/MCB

    3ph voltage measurement Gen./Mains

    3ph current measurement

    kW/kWh/Kva

    Engine reading

    Engine protection

    Alternator protection

    Earth current protection

    History file

    RTC/Battery

    PLC

    4G

    Airgate

    ECU CAN

    MODBUS

    MODBUS IP

    SNMP

    SNMP TRAPS

    RS232

    RS485

    GSM/GPRS modem

    Remote screen

    Software for PC

    AGG UK | AGG China | AGG USA | AGG UAE

    [email protected] | www.aggpower.co.uk

    Follow us @facebook.com/aggpowergroup

    Follow us @linkedin.com/company/agg-power

    Follow us @ AGGPOWER

    D388D6

    Copy Right 2020 @ AGG POWER www.aggpower.com

    350

    3

    7/7

    Advanced Model (Optional)

    Standard: Not Available:Optional:

    Basic Model (Standard)

    6/6

    3

    150