Presented to the RC 03/4/03 1
Generator Reactive Capabiltiy
VerificationBy
Component Testing
Presented to the RC 03/4/03 2
Problem – Contingency Capability
In some special cases, the full VAR capability of a generator is needed for contingency conditions, not normal conditions.
In these cases, creating the conditions that would require the generator’s full VAR output would be dangerous.
The ISO and Satellites will intentionally not create such conditions.
Presented to the RC 03/4/03 3
Normal Conditions
1160 850 200 200
AVR: 357 kV AVR: 357 kV
357 kV
Presented to the RC 03/4/03 4
VAR Test Conditions
1160 850 600 200
VR-manual: 600 MVAR
AVR: 357 kV
357 kV
Presented to the RC 03/4/03 5
VAR Test Conditions:Post Contingency
1160 0 600 0 VR-manual: 600 MVAR
AVR: ----
370 kV
Presented to the RC 03/4/03 6
Solution – Component Certification
Provide these special case generators with an alternative to actual VAR testing.
One alternative could be to require certification of the major components of the generator’s VAR capability:
Synchronous machine Cooling system Excitation system Protection systems …
Presented to the RC 03/4/03 7
RequirementsRigorous
Timely
Subject to audit
Accountable Professional Engineers stamp?
Presented to the RC 03/4/03 8
Next StepIdentify Special Cases
Develop Component Test Requirements
Presented to the RC 03/4/03 9
Questions ?