Generator Protection

41
® Basler Generator Protection

Transcript of Generator Protection

Page 1: Generator Protection

®Ba

sle

r

Generator Protection

Page 2: Generator Protection

Generator Protection

Purpose

• Generator, prime mover

• External power system, processes it supplies

Considerations

• Expense

• Risk

• Continuity of service

• Damage to system, processes it supplies

• MW rating

• Utility interface requirements

Page 3: Generator Protection

ANSI/IEEE Device Numbers

• Protective relays are generally referred to by standard device numbers

• Letters can be added to clarify application

Examples :

– 51 is a time overcurrent relay – 51 is a time overcurrent relay

– 50 is an instantaneous overcurrent

– 27/59 is a combination under/over voltage relay

– 87T is a transformer differential relay

– 59G is a ground overvoltage relay

Page 4: Generator Protection

Device numbers commonly used

Protective Function ANSI code

Stator Differential 87G

Underimpedance 21

Current Unbalance 46

Loss of Excitation 40

Reverse Power 32

Thermal Protection 49

Breaker Failure 50BF

Time Overcurrent with Voltage Restraint 51VTime Overcurrent with Voltage Restraint 51V

Stator Ground 64G

Ground Fault Overvoltage 59N

Ground Overcurrent 51GN

Over-excitation 24

Phase Sequence Voltage 47

Overvoltage 59

Undervoltage 27

Over and Underfrequency 81

Page 5: Generator Protection

Types of Protection

Faults

• Ground fault

• Phase fault

Abnormal operating conditions

• Reverse power• Reverse power

• Loss of field

• Thermal

• Uncleared external fault

• Overexcitation

• Negative-sequence overcurrent

• Off-frequency operation

Page 6: Generator Protection

Ground Fault Protection

Level of fault current

• grounding impedance (low, medium, high)

• location of fault in winding

• pre-fault voltage level

Fault near generator neutral

• low probability due to less insulation stress • low probability due to less insulation stress (mostly mechanical)

• Protection goal: ≤≤≤≤ 10% of winding uncovered

Selectivity

• determined by system configuration and relay scheme

Page 7: Generator Protection

Grounding impedance

Grounding

impedance High Medium Low

Ground fault

current limited to 3% In 5% to 40% In >In

- Limit damage

during a fault

- easy detection of

ground fault

location

- when it is important

that the power source

is effectively groundedlocation is effectively grounded

- limit arcing fault

overvoltage

- limit overvoltage

during fault on line-

ground connected load

- only a moderate

damage limitation

needed

Description

Ground fault

elevated the

sound phase

voltages to a

nominal 173%

of rated.

Page 8: Generator Protection

Summary: Level of Ground Fault

EXTERNALSOURCE

(1)

GENERATOR

VFG

Fault current level depends on:

• location of fault relative to generator neutral

• voltage at fault point

• generator grounding impedance (low, med, high)

Page 9: Generator Protection

Generator ground fault current level -High impedance grounded system

100

80

60

40FA

ULT

CU

RR

EN

T-

OF

TE

RM

INA

LFA

ULT

1

•Fault voltage level is proportional to the location of fault from the generator neutral

•High to moderate neutral or fault impedance will make fault level proportionate to voltage

40

20

1008560

FAULT LOCATION - % FROM NEUTRAL(Z and Z ) >> Z

4520

F%

O

0, SOURCE N WINDING

Page 10: Generator Protection

Phase-ground Fault: High resistance grounding

G

59N

DISTRIBXFMR.(n:1)

59P

I

I

N

N

• Resistor size

– terminal fault current of 5-10 A primary

– based on generator line-ground capacitive reactance

• Low fault current minimizes generator damage

• IN contains 3rd harmonic

59P

Page 11: Generator Protection

Phase-ground Fault: High resistance grounding

G

59N

Alternate

DISTRIBXFMR.(n:1)

27-3N

59P

I

I

N

N

Low fault current

• 87G will not operate

• 59N provides ground fault protection for most of stator ground faults

• Like overcurrent relays, 59N is blind for faults near neutral

5/5

59P

51GN

Page 12: Generator Protection

Phase fault

Alternate

G

A B

• 51 is simplest phase fault protection

• Fault clearing delayed as 51 coordinates with down-stream relays

51A - Senses generator contribution to generator fault;

does not sense utility contribution to generator fault.

B - Senses utility contribution to generator fault;blind to generator fault when breaker open andwhen running isolated from utility.

Page 13: Generator Protection

Phase-phase fault

G

Typical setting should be 175% of rated current

• override swings due to slow clearing external fault

• starting of motors

• transformer energization

51

Page 14: Generator Protection

Phase fault: Generator fault current decay

• 51 must operate before current decays below MPU

• 3∅∅∅∅ fault is worst

SUBTRANSIENT

TD = 0.03S″

6

4

∅∅∅∅−−−− ∅ ∅ ∅ ∅ PL

EO

FR

AT

ED

• 3∅∅∅∅ fault is worst case

• Pre-fault load current provides more time to operate

2

3∅∅∅∅FAULT

51 PICKUP

STEADY-STATE (3∅∅∅∅) STEADY-STATE (∅∅∅∅−−−− ∅∅∅∅)

∅∅∅∅−−−− ∅ ∅ ∅ ∅

FAULT3∅∅∅∅ WITH

FULL LOAD @30°LAG

1.75

0.9

0

1

TIME - SECONDS

CU

RR

EN

T-

MU

LT

IP

Page 15: Generator Protection

Voltage-restrained TOC Relay 51V

G

• Pickup of relay depends on voltage

• Relay must not pickup at full load and normal voltage

51V

Page 16: Generator Protection

Voltage-restrained TOC Relay 51/27VR

• 51V relay pickup decreases with decreases in the voltage

• Voltage restrained: 51/27R

–MPU set above rated current (typically 175%)

–MPU proportional to voltage: decreases when fault occursoccurs

–More work to coordinate

–More secure from swings and motor starting

• 51V less susceptible to operation on swings of motor starting condition that depresses the voltage

Page 17: Generator Protection

Voltage-restrained TOC Relay 51/27VR

100%

25%

PU

100%25%V

• If relay pickup is set at 175% of rated current:

–relay picks up at 175% of rated current at 100% rated voltage

–relay picks up at 44% (25% of 175%) of rated current at 25% voltage

Page 18: Generator Protection

Phase fault differential protection 87G

51V

G

• 87G provides fast phase fault protection

• 87G immune to load current and external fault

• CTs on both sides must be of same ratio

• Sensitivity (setting) depends on CT quality

• 51V backs up 87G and external relays

87G

Page 19: Generator Protection

Reverse Power Protection

• Power flows to generator due to failure of prime mover input

• Prime mover failure can

–cause overheating of low pressure blades in steam turbinein steam turbine

–create fire hazards due to unburnt fuel in diesel generator set

–cause mechanical damage to gas turbine

Page 20: Generator Protection

Reverse power protection

G

32

POWERSOURCE

• 32 senses real power flow into the generator.

• Typical time delay setting for 32 should be 15 seconds (synchronizing).

• CT location is not important for 32 operation.

32

Page 21: Generator Protection

Reverse power protection

32-1

G

32SOURCE

OFMOTORING

POWER

• 32-1 relay supervises generator tripping relays until motoring occurs (delay @ 3s)

• 32-2 trips generators directly, e.g. for governor control malfunction (delay @ 15-30s)

32-2

Page 22: Generator Protection

Reverse power protection

4964 32-2

32-1

86NE

86NE

86E

NON-

ELEC

TRIPS

OTHER

ELEC

TRIPS

86NE

86NE 86E

86E

86E

TURBINE TRIP BKR TRIP FIELD TRIP

86

NE86E

Page 23: Generator Protection

Reverse power protection

Prime Mover Motoring Power(% of rated)

Protection Setting

Diesel Engine 5-25

Gas Turbine 10-15(split shaft)

>50%50%

of motoringpower

>50%(single shaft)

Hydro 0.2-2(blades out of water)

>2 cavitation(blades in water)

Steam Turbine 0.5-6

Page 24: Generator Protection

Loss-of-field protection

• Generator eventually runs as induction generator with complete loss of excitation.

• Machine runs above synchronous speed, i.e. negative slip.

–Excessive current can flow in rotor winding and cause overheating.

–Stator thermal overload relay 49 cannot detect this condition.

• Rotor thermal overload can occur even due to partial reduction of field

–due to operator error or regulator malfunction

• Minimum Excitation Limiter is backup to relay

Page 25: Generator Protection

Loss-of-field protection

• Loss of field can cause voltage reduction and oscillation - adverse effect on sensitive load.

• If unit is large compared to external source system, system instability can result.

• 40 provides loss-of-field protection• 40 provides loss-of-field protection

– time delay of 0.1 sec. is recommended to override transient load swings

– timer is included in the relay

Page 26: Generator Protection

Loss-of-Field Protection

G POWERSOURCE

40

40

Page 27: Generator Protection

Loss-of-field protection: Power trajectory

0.75

A

jQ

P

BE1-GPS100 and BE1-40QCHARACTERISTICS

GEN.

THERMALCAPACITY

• First quadrant of diagram applies to lagging PF; fourth quadrant applies to leading PF

• Trajectory starts at point A, moves to a point in 4th quadrant

– can exceed thermal capability of machine

CHARACTERISTICS

OPERATINGZONE

8°-0.4

-0.6

Page 28: Generator Protection

Thermal Protection

Stator thermal protection relay (49) connected to resistor temperature detector embedded in stator

BE1-49

GCONSTANTCURRENTSOURCE

RTD SENSING

embedded in stator slot

LOWER TEMPALARM

UPPER TEMPTRIP

Typical settings:

- Alarm 120°C

- Trip 130°C

Page 29: Generator Protection

Overexcitation protection

• Overexcitation can occur due to:– higher than rated voltage– lower than rated frequency at rated or

less than rated voltage– unit off line and voltage regulator out of service

or defective

• Overexcitation condition produces thermal stress • Overexcitation condition produces thermal stress to the generator.

• IEEE C50.13 specifies that generator should withstand 105% of rated voltage at full load.

• With unit off line and voltage control regulator at reduced frequency (without overexcitation limiter), overexcitation can occur.

Page 30: Generator Protection

Overexcitation protection

• 24 provides V/Hz protection.

• 24 and voltage regulators should be provided with separate ac

1000

100

CO

ND

S

GEN

XFMR

separate ac potential sources.

• Curve indicates 24 characteristic and generator withstand capability.

10

100% 110%

DEF. TIME

ALARM

120% 130% 140% 150%

1

TIM

EIN

SE

C

EXCITATION - V/Hz

INVERSE-SQUAREDCURVE IN RELAY

Page 31: Generator Protection

Negative Sequence Overcurrent Protection

CAUSE:

Negative sequence currents could result from:

- Unbalanced loads

- Asymmetrical faults

- Open phase conditions- Open phase conditions

DAMAGES:

Negative sequence current induces double

frequency current in rotor winding.

-> overheats the iron surface, retaining rings, slot Wedges

Page 32: Generator Protection

Negative Sequence Overcurrent Protection

G

46

ALARM TRIP

• Generator should be able to withstand 5-10% of continuous I2 current

• Short term capability is specified by I22t limit

(“K= I22t” with k : Generator thermal capacity constant)

ALARM TRIP

Page 33: Generator Protection

Characteristics of a Static Negative-Sequence Time-Overcurrent Relay

1000

500

50

“K” SETTINGADJUSTABLE OVER

RANGE 2-40

MAXIMUMOPERATING TIME990 SEC.

300

30

200

100

40

10

5

2

.01

5

.5

TIM

E IN

SE

CO

ND

S

30

3

2

.3

20

.1

.2

10MINIMUM PICK-UP

.04 PU

1

.02.03.05 .1 .2 .3

PER UNIT I2

.5 1 2 3 5 10

Page 34: Generator Protection

Student exercice

Generator K factor = 10

Generator nominal current In

Negative sequence current I2 = 30% of In

What is the maximum time generator will

withstand I2?

t = K / I2^2; t = 10/0.3^2 = 111 s

Page 35: Generator Protection

Off-frequency operation

• Diesel engines safely operated at off-frequency

• Gas turbine controls provide protection for off-frequency operation.off-frequency operation.

• Frequency relays applied to steam turbine units to minimize turbine blade fatiguing

Page 36: Generator Protection

Field Ground detection 64F

G

64F

Check insulation level of the exciter field

ALARM 1

DC Power Supply

ALARM 2

Page 37: Generator Protection

Field Ground detection 64F

ROTOR

RL

GROUND

FAULT

GENERATOR FIELD

EXCITER

GROUND FAULT DETECTOR

A

+ -

VBIAS

55VDC

Page 38: Generator Protection

Field Ground detection 64F

• In normal operation, rotating circuit-generator rotor, exciter an diodes is completely insulated from the shaft.

• Accidental ground doesn’t affect operation.

• Problem arise in case of 2nd ground fault :• Problem arise in case of 2nd ground fault :

- magnetic unbalanced

- Vibration appear increasing with the excitation current

- Shaft deformation: rotor will touch the stator

Page 39: Generator Protection

INTEGRATED APPLICATION EXAMPLE

Page 40: Generator Protection

Integrated application examples:Extended protection

G

64F

60

51N

87T

87G

6349

REG

51

25

87T24

81U

47

2762

59 81O

32-1

59N

51-GN

32-2

27-3N

40 51V50EI

46

51

Page 41: Generator Protection

Questions?