Generator and Power Station Protection_2012.pdf

download Generator and Power Station Protection_2012.pdf

of 62

Transcript of Generator and Power Station Protection_2012.pdf

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    1/62

    Generator and

    Power Station Protection

    Synopsis

    Disclaimer

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    GENERATOR and

    POWER STATION

    PROTECTION

    Barrie Moor, B Eng (Elec)

    Slide [email protected]

    DisclaimerSeminar Synopsis

    [email protected]@powersystemprotection.com.auwww.powersystemprotection.com.au

    Slide [email protected]

    Disclaimer

    The material presented in this module is for Educational purposes

    only.

    This module contains a summary of information for the protection of

    various types of electrical equipment. Neither the author, nor

    anyone acting on his behalf, makes any warranty or representation,

    express or implied, as to the accuracy or completeness of theinformation contained herein, nor assumes any responsibility or

    liability for the use, or consequences of the use, of any of this

    information.

    The practical application of any of the material contained herein

    must be in accordance with legislative requirements and must give

    due regard to the individual circumstances.

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    2/62

    Generator and

    Power Station Protection

    Synopsis

    Disclaimer

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    Seminar Synopsis

    Over Current Protection

    Differential Protection

    High Impedance Differential Protection

    Biased Differential Protection

    Sequence Components

    Motor Protection

    Generator Protection

    Generator Faults

    Generator Events

    Power System Events

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    3/62

    Seminar costs will vary depending on attendeenumbers and your individual circumstances.However, by organising your own in-houseseminar:

    You can expect savings of between 40%and 65%.

    Plus you eliminate travel andaccommodation expenses for all of yourattendees.

    We provide:

    2 or 3 day seminar presentation All seminar handout material, notes, folders,

    CDs, etc Laptop Computer and Data Projector Note that we guarantee that all seminars will be presented personally by

    our principal engineer and seminar author, Barrie Moor

    Each attendee receives:

    Two or three day seminar presentation Hard copy manual with all presentations, plus supporting technical

    papers

    CD with all printed material, plus considerable extra material and tools,including: pdf of seminar colour slides 2 per page additional technical papers tools for sequence component analysis of single, double and three

    phase faults tools for grading of IDMT overcurrent relays tools for distance relay calculations, apparent impedance calculations,

    fault resistance, mho and offset mho characteristic load limits

    Certificate of attendance

    You provide:

    Seminar conference room (preferably on-site, within your own facilities) Whiteboard Any catering for lunch and tea breaks

    To discuss your requirements, or to obtain a firm price quotation,please contact us at:

    [email protected]

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    4/62

    Generator and

    Power Station Protection

    Over Current Protection

    Fuses and Contactors

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    GENERATOR and

    POWER STATION

    PROTECTION

    Barrie Moor, B Eng (Elec)

    Slide [email protected]

    OVER CURRENTPROTECTION

    Overcurrent Relays

    Fuses & Contactors

    Directional Relays

    Slide [email protected]

    Over Current Protection

    Over Load Protection

    Operation to the thermal capability of plant

    Over Current Protection

    Primarily for clearance of faults

    Some measure of over load protection may be provided

    Slide [email protected]

    Discrimination by Time

    Setting chosen to ensure CB nearest to the fault opens

    first

    Often referred to as

    Independent Definite Time Delay Relay

    Timing intervals selected to ensure upstream relays do

    not operate before CBs trip at fault location

    Disadvantage

    Longest fault clearing time occurs in section closest tothe power source where fault level is the highest

    Slide [email protected]

    Discrimination by Time

    RELAY A RELAY B RELAY C

    RELAY C

    RELAY B

    RELAY A

    CURRENT

    TIME

    0.4 secs

    0.4 secs

    Slide [email protected]

    Discrimination by Current

    Apply where fault current varies with fault location due to

    intermediate impedance

    Set to operate at current values so that only relay

    nearest to fault trips its CB

    Difficulties

    Same fault level at the end of one zone and the start of the

    next

    Fault levels vary with changing source impedance(eg. As generators come on and go off line)

    Slide [email protected]

    Discrimination by Current

    RELAY A RELAY B

    Relay A cannot distinguishbetween a fault here, forwhich it needs to operate

    And a fault here forwhich it should notoperate

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    5/62

    Generator and

    Power Station Protection

    Over Current Protection

    Fuses and Contactors

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    Discrimination by Current

    Significant difference betweencurrents seen for Faults A & B

    Set HV OC to 1.3 x maximum

    through current for LV Fault

    HV OC

    FDR OC

    FDR OC

    FDR OC

    FDR OC

    A

    B

    Slide [email protected]

    Discrimination by Time & Current

    Time and currentcoordination

    RELAY A RELAY B RELAY C

    RELAY C

    RELAY B

    RELAY A

    CURRENT

    TIME

    ICmax IBmax IAmax

    IAmax IBmax ICmax

    Instantaneouselement

    Slide [email protected]

    Inverse Over Current Relays

    Time of operation inversely proportional to fault current

    Faster operating times at higher fault levels

    Faster operating times for faults nearer to the source

    Curves generally plotted in log - log or

    log(current) linear(time) format

    Slide [email protected]

    Discrimination w ithInverse Time Over Current Relays

    Inverse time andcurrent coordination

    RELAY A RELAY B RELAY C

    RELAY C

    RELAY B

    RELAY A

    CURRENT

    TIME

    ICmax IBmax IAmax

    IAmax IBmax ICmax

    Instantaneouselement

    Slide [email protected]

    Relay Curves to IEC 60255(BS142)

    I = Actual relay current

    Relay Settings

    TMS = Time Multiplier Setting

    P = Plug (Current) pickup setting

    Usual curve for t ransmission and distribution systems

    1P

    I

    TMS14.0TIME

    02.0Inverse_dardtanS

    =

    Slide [email protected]

    Relay Curves to IEC 60255(BS142)

    I = Actual relay current

    Relay Settings

    TMS = Time Multiplier Setting

    P = Plug (Current) pickup setting

    Systems where the fault level decreases significantlybetween relaying points

    1P

    I

    TMS5.13TIME Inverse_Very

    =

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    6/62

    Generator and

    Power Station Protection

    Over Current Protection

    Fuses and Contactors

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    Relay Curves to IEC 60255(BS142)

    I = Actual relay current

    Relay Settings

    TMS = Time Multiplier Setting

    P = Plug (Current) pickup setting

    Grading with fuses

    1P

    I

    TMS80TIME

    2Inverse_Extremely

    =

    Slide [email protected]

    Relay Curves to IEC 60255(BS142)

    I = Actual relay current

    Relay Settings

    TMS = Time Multiplier Setting

    P = Plug (Current) pickup setting

    Long time thermal protection

    Motor & Generator Protection

    1P

    I

    TMS120TIME

    Inverse_Time_Long

    =

    Slide [email protected]

    Standard Characteristics to IEC 60255

    Long Time (LTI)

    Extremely Inverse (EI)

    Very Inverse (VI)

    Standard Inverse (SI)

    Relay Characteristic

    1I

    TMS14.002.0

    1I

    TMS5.13

    1I

    TMS802

    1I

    TMS120

    100 1.103

    1.104

    0.1

    1

    10

    100

    Standard Inverse

    Very Inverse

    Etremely Inverse

    Long Time Inverse

    IDMT Relay Grading Curves

    Fault Current

    Seconds

    Slide [email protected]

    US Characteristics to IEC 60255

    U5 Short Time Inverse

    U4 Extremely Inverse *

    U3 Very Inverse

    U2 Inverse

    U1 Moderately Inverse

    Relay Characteristic

    +1M

    0104.00226.0TD

    02.0

    +1M

    95.5180.0TD

    2

    +1M

    88.30963.0TD

    2

    +1M

    64.502434.0TD

    2

    +1M

    00342.000262.0TD

    02.0

    TD = Time dial (TMS)M = Multiple of pick-up current

    Slide [email protected]

    Electro Mechanical Relays

    FLUX PRODUCED BY INPUT

    TAPPEDCOIL

    I

    - L

    SHADING LOOP

    FLUX PRODUCED BY INPUT CURRENT

    DISC DISC

    FLUX PRODUCED BY SHADING LOOP

    kI

    L

    (1-k) I

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    7/62

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    8/62

    Generator and

    Power Station Protection

    Over Current Protection

    Fuses and Contactors

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    Instantaneous Element

    Reduces tripping time at high fault levels

    Allows a the discriminating curves behind the high set

    element to be lowered Grading of upstream relay now occurs at the instantaneous

    setting and not at maximum fault level

    Minimises fault damage in both cases

    Beware Simple E/M instantaneous elements may have a substantial

    transient overreach on fault currents that include DC offset

    OC OC

    100 1.103

    1.104

    0.5

    1

    1.5

    2

    2.5

    3

    3.5

    4IDMT Relay Grading Curves

    Fault Current

    Seconds

    100 1.103

    1.104

    0.5

    1

    1.5

    2

    2.5

    3

    3.5

    4IDMT Relay Grading Curves

    Fault Current

    Seconds

    100 1.103

    1.104

    0.5

    1

    1.5

    2

    2.5

    3

    3.5

    4IDMT Relay Grading Curves

    Fault Current

    Seconds Set Tx HV inst

    element and nowgrade here

    OC

    OC

    GENERATOR and

    POWER STATION

    PROTECTION

    Barrie Moor, B Eng (Elec)

    Slide [email protected]

    OVER CURRENTPROTECTION

    Setting andCoordination

    Procedures

    Slide [email protected]

    Relay Coordination ProcedureCurrent Setting

    Start with selection of relay characteristic

    As far as possible, use relays of the same characteristic

    Choose current settings

    Determine maximum load current limitations

    Determine starting current requirements

    As far as possible, select operating current of each

    upstream relay greater than that of the successive

    downstream relay

    Slide [email protected]

    Relay Current Pick-up Setting

    Set above maximum load current

    Allow for emergency loading conditions

    Allow safety margin

    Allow for relay reset ratio

    Set below the current pickup level of the next upstream

    relay

    Allow for load pickup current

    Slide [email protected]

    Load Pickup Current

    Motor starting current

    Auxiliary heaters

    Transformer magnetising inrush

    Capacitor charging current

    Lighting loads - 10s to 100s of msec

    Filaments and electrodes heating

    Arc lamps starting

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    9/62

    Generator and

    Power Station Protection

    Over Current Protection

    Fuses and Contactors

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    Load Pickup Current

    Hot load pickup

    Short term loss of supply and subsequent load pickup

    currents on return of supply

    Cold load pickup

    Load pickup, but now with loss of diversity between cyclicloads

    Voltage recovery pickup

    Pickup currents not as severe as for complete loss of

    supply and subsequent hot load pickup

    But more motors may still be on-line as under voltage

    releases may not have disconnected them

    Slide [email protected]

    Relay Coordination ProcedureTime Multip lier Setting

    Coordinate relays via time multipliers to achieve

    appropriate grading margins

    Determine, under various system configurations, thevalues of short circuit current that will flow through eachprotective device

    Set relays to give minimum operating time at maximum

    fault currents

    Check performance (discrimination) at lower fault levels

    Plot and coordinate relay curves on log/log or log/linear

    format

    Plot to a common current base (across transformers)

    Slide [email protected]

    Relay TMS Grading

    Must provide for

    CB tripping time (0.1 sec ??)

    Relay timing errors

    Relay overshoot

    CT errors (10% ??)

    Safety margin (10% ??)

    A typical figure of 0.3 - 0.4 seconds is usually OK

    0.3 for numerical relays

    0.4 for electromechanical relays

    Alternatively calculate a margin

    Only necessary for slow tripping times (> 1.0 sec)

    Slide [email protected]

    Relay TMS Grading

    Relay TMS Grading

    Hence for an E/M relay tr ipping in 0.5 seconds

    t = (7.5 + 7.5 + 10)% x 0.5 + 0.1 + 0.05 + 0.1

    t = 0.375 seconds

    0.30.30.350.4Typical margin (s)

    0.030.030.050.1Safety Margin (s)

    0.020.020.030.05Overshoot Time (s)

    5557.5Timing Error %

    NumericalDigitalStaticElecto-

    Mechanical

    Relay Technology

    CT Errors Slide [email protected]

    Grading of Parallel Elements

    Worst case for grading is with only 1 transformer in service But this will be an unusual operating condition

    E/M & Electronic Relays Only a single relay setting is available

    Hence, effectively no option but to set for the worst case, namely1 transformer case

    And accept slower performance for system normal,namely when both transformers are in service

    Microprocessor based relays

    These relays have multiple setting groups

    So, maybe set Group 1 for system normal : 2 transformers

    And change to group 2 when one transformer is OOS Automatically ??

    Via SCADA & operator intervention ??

    OC OC

    OC OC

    OC

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    10/62

    Generator and

    Power Station Protection

    Over Current Protection

    Fuses and Contactors

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Grading of Parallel Elements

    Maximum through fault level occurs when both transformers

    are in service

    But the maximum individual transformer current flows whenthe 2nd transformer is OOS

    Need to consider both conditions when grading relays

    HV OC

    HV OCFdr_1 OC

    3 Fault Levels 2 Tx IN : 16000A 1 Tx IN : 12000A

    3 Fault Levels 2 Tx IN : 10000A 1 Tx IN : 7500A

    33kV 11kV

    20MVA

    20MVA

    300A FLC

    800A FLC

    Fdr_2 OCSI 400ATMS 0.2

    Fdr1_TMS 0.28=Fdr1_TMS round Fdr1_TMS .003+ 2,( ):=Round Up

    Fdr1_TMS 0.276=

    Fdr1_TMS 1Fdr1_Tmin

    Fdr1_TMS_1:=Hence we can calculate the required TMS to achieve the required tripping time

    Fdr1_TMS_1 2.971=This would result in a tripping time of

    Fdr1_TMS_1 SI Fdr1_Plug 1.0, Imax,( ):=Assume TMS = 1.0

    Fdr1_Tmin 0.821=Fdr1_Tmin Fdr2_Tmin 0.4+:=Required tripping time

    Imax

    Fdr1_Plug10=Fdr1_Plug 1000:=So select settings for Feeder 1

    Fdr2_Tmin 0.421=Fdr2_Tmin SI Fdr2_Plug Fdr2_TMS, Imax,( ):=Tripping time at maximum fault level

    Fdr2_TMS 0.2:=

    Imax

    Fdr2_Plug25=

    Fdr2_Plug 400:=Given data for Feeder 2

    Imax 10000:=Grade Fdr_1 OC over Fdr_2 OC at the maximum through fault level of 10kASet Fdr_1 OC above maximum feeder load of 800A

    and check against maximum fault level of 10kA

    SI P TMS, I,( ) 0.14TMS

    I

    P

    0.02

    1

    :=Relay Characteristic

    Feeder 1 Relay_2n

    SI Fdr2_Plug Fdr2_TMS, I2n

    ,( ):= SI Fdr2_Plug Fdr2_TMS, Imax,( ) 0.421=

    Feeder 2 Relay_1n

    SI Fdr1_Plug Fdr1_TMS, I1n

    ,( ):= SI Fdr1_Plug Fdr1_TMS, Imax,( ) 0.832= _T 0.411=

    100 1 .103

    1 .104

    1 .105

    0

    0.2

    0.4

    0.6

    0.8

    1

    1.2

    1.4

    1.6

    1.8

    2

    2.2

    2.4

    2.6

    2.8

    3

    Fdr 2 OCFdr 1 OC

    Tx OC Grading (11kV Base Currents)

    Tx_HV_TMS 0.36=Tx_HV_TMS round Tx_HV_TMS .003+ 2,( ):=Round up

    Tx_HV_TMS 0.355=

    Tx_HV_TMS 1 Tx_HV_Tmin

    Tx_HV_TMS_1:=Hence we can calculate the required TMS to achieve the required tripping time

    Tx_HV_TMS_1 3.297=This would result in a tripping time of

    Tx_HV_TMS_1 SI Tx_HV_Plug 1.0, Imax,( ):=Assume TMS = 1.0

    Tx_HV_Tmin 1.169=Tx_HV_Tmin Fdr1_Tmin 0.4+:=Transformer HV OC

    Fdr1_Tmin 0.769=Fdr1_Tmin SI Fdr1_Plug Fdr1_TMS, Imax,( ):=Fdr Tripping time at maximum fault level

    Tx_HV_Plug 1500=

    Tx_HV_Plug 3 Tx_HV_Plug:=Allow for 33/11kV ratio

    Tx_HV_Plug 500:=Set130% FLC_33kV 455=FLC_33kV 350=FLC_33kV 20000000

    3 33000:=

    Imax 12000:=

    Grade Transformer HV OC under the maximum current condition, namely with one transformer OOS

    Feeder 1 Relay_1n

    SI Fdr1_Plug Fdr1_TMS, I1n

    ,( ):= SI Fdr1_Plug Fdr1_TMS, Imax,( ) 0.769=

    Tx HV Relay_3n

    SI Tx_HV_Plug Tx_HV_TMS, I3

    n

    ,

    ( ):= SI Tx_HV_Plug Tx_HV_TMS, Imax,( ) 1.187= _T 0.418=

    100 1.10

    3

    1.10

    4

    1.10

    50

    0.2

    0.4

    0.6

    0.8

    1

    1.2

    1.4

    1.6

    1.8

    2

    2.2

    2.4

    2.6

    2.8

    3

    Fdr 2 OC

    Fdr 1 OC

    Tx HV OC

    Tx OC Grading (11kV Base Currents)

    Slide [email protected]

    Sequential Operation of Over CurrentRelays

    As CBs trip, fault current magnitudes and flows will change

    We need to integrate how far each relay progresses towardstripping in each stage

    To determine total tripping times

    To ensure relays that should not trip, remain stable

    Relay 1 operating time must have a suitable margin above thetotal of Relay 2 and the subsequent Relay 3 operations

    Relay 3Relay 2

    Relay 1

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    11/62

    Generator and

    Power Station Protection

    Over Current Protection

    Fuses and Contactors

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    GENERATOR and

    POWER STATION

    PROTECTION

    Barrie Moor, B Eng (Elec)

    Slide [email protected]

    OVER CURRENTPROTECTION

    Directional Relays

    Slide [email protected]

    Directional Over Current Relays

    Extra discrimination may be achieved by making the

    response of the relay directional when current can flow in

    both directions Achieved via voltage (polarising) connections to the relay

    Digital and numeric relay achieve phase displacementsvia software

    EM & Static relays require suitable connection of input

    quantities to the relay

    Slide [email protected]

    Directional Over Current RelaysAppl ication to Paral lel Feeders

    Apply directional relays at the feeder receiving ends

    Typically set to 50% of FLC, TMS = 0.1

    Grade below non-directional relays at the source end

    Ensure DOC relay thermal rating is OK

    OC OC

    OCOC

    Fdr 1

    Fdr 2

    BA

    Slide [email protected]

    0.90.9

    0.

    5

    0

    .5

    0.1 0.1

    1.3

    1.

    7

    2.1 2.1

    1.

    7

    1.31.3

    Ring Mains Systems

    Open the ring at thesupply point

    And then gradeclockwise

    And then anticlockwise

    Source substation relaysdo not HAVE to be

    directional Intermediate substation

    slower relays do notHAVE to be directional

    GENERATOR and

    POWER STATIONPROTECTION

    Barrie Moor, B Eng (Elec)

    Slide [email protected]

    OVER CURRENTPROTECTION

    Earth Fault Relays

    Slide [email protected]

    Earth Fault Protection

    Implement more sensitive protection responding only to

    residual current of the system

    Low settings are permissible and beneficial

    Earth faults are the most frequent

    Earth faults may be limited by earth fault resistance

    Earth faults may be limited by neutral earth impedance

    Typical settings 20 - 40% x FLC

    Time grade in the same manner as for phase OC relays

    Beware of the burden that electromechanical relays may

    place on CTs at low current settings

    Although burden does decrease at very high currents with

    saturation of the relays magnetic circuits

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    12/62

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    13/62

    Generator and

    Power Station Protection

    Over Current Protection

    Fuses and Contactors

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    Expulsion Fuses

    Used where expulsion gases cause no problem such as in overhead

    circuits and equipment

    Special materials (fiber, melamine, boric acid, liquids such as oil orcarbon tetrachloride ) located in close proximity to fuse element andarc rapidly create gases

    These produce a high pressure turbulent medium surrounding the

    arc

    Expulsion process deionises gases them as well as removing themfrom arc area

    In inductive circuits, transient recovery voltage (TRV) will be

    maximum at current zero.

    Slide [email protected]

    Fuses & TRV Performance

    0 0 .0 02 0 .0 04 0 .0 06 0 .0 08 0 .0 1 0 .0 12 0 .0 14 0 .0 16 0 .0 18 0 .0 2 0 .0 22 0 .0 242

    1.5

    1

    0.5

    0

    0.5

    1

    1.5

    2

    Circuit VoltageFuse Voltage

    Current

    0 0 .0 02 0 .0 04 0 .0 06 0 .0 08 0 .0 1 0 .0 12 0 .0 14 0 .0 16 0 .0 18 0 .0 2 0 .0 22 0 .0 242

    1.5

    1

    0.5

    0

    0.5

    1

    1.5

    2

    Circuit VoltageFuse Voltage

    Current

    0 0 .0 02 0 .0 04 0 .0 06 0 .0 08 0 .0 1 0 .0 12 0 .0 14 0 .0 16 0 .0 18 0 .0 2 0 .0 22 0 .0 242

    1.5

    1

    0.5

    0

    0.5

    1

    1.5

    2

    Circuit VoltageFuse Voltage

    Current

    0 0 .0 02 0 .0 04 0 .0 06 0 .0 08 0 .0 1 0 .0 12 0 .0 14 0 .0 16 0 .0 18 0 .0 2 0 .0 22 0 .0 242

    1.5

    1

    0.5

    0

    0.5

    1

    1.5

    2

    Circuit VoltageFuse Voltage

    Current

    0 0 .0 02 0 .0 04 0 .0 06 0 .0 08 0 .0 1 0 .0 12 0 .0 14 0 .0 16 0 .0 18 0 .0 2 0 .0 22 0 .0 242

    1.5

    1

    0.5

    0

    0.5

    1

    1.5

    2

    Circuit VoltageFuse Voltage

    Current

    Current lagsVoltage by 90

    deg

    SystemVoltage

    Currentinterrupted at

    naturalcurrent zero

    TRV acrossblown fuse

    element

    Fuse Voltage

    Slide [email protected]

    Current Limiting Fuses (HRC Fuses)

    Fuse is designed to insert a large resistance

    Hence, prospective level of fault current is reduced

    And zero crossing of the current and voltage will be reasonably

    in phase TRV significantly reduced

    Fuse element is completely surrounded with f iller material, typically

    silica sand

    Arc energy melts the sand, thus inserting the required high

    resistance

    But this design may have difficulty interrupting low level overloads.Overcome by

    M Effect designs

    Spring assisted designs

    Slide [email protected]

    Current Limiting Fuses

    Tin for M Effect lowoverload fuse performanceSee later

    Slide [email protected]

    Current Limiting Fuses

    Slide [email protected]

    Current Limiting FusesM Effect for low level overloads

    M Effect : A.W. Metcalf - 1939

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    14/62

    Generator and

    Power Station Protection

    Over Current Protection

    Fuses and Contactors

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    Current Limiting Fuses

    Slide [email protected]

    Grading Relays wi th Fuses

    Extremely Inverse curve

    follows a similar I2t

    characteristic Relay current setting should

    be approximately 3 times the

    fuse rating

    Grading margin of not less

    than 0.4 seconds

    recommended

    Or 15.04.0' + tT

    1PI

    TMS80TIME

    2Inverse_Extremely

    =

    Slide [email protected]

    Grading Relays with Fuses

    First relay upstream of the fuse should be set to EI

    characteristic

    Now to coordinate further upstream relays

    Option 1 : Also select EI characteristics

    Option 2 : Check also for the possibility of setting

    The next relay to a VI characteristic

    And subsequent further upstream relays to SI characteristics

    Slide [email protected]

    Fuse Contactors

    High fault level applications eg

    40kA fault level

    Contactor rated to only 10kA

    Fuse operates for all faults above say 7 kA

    Contactor and associated protection relay operate for

    lower fault levels

    Warning the fuse may also have a minimum breaking

    capacity and the contactor must be set to operate abovethis point

    Slide [email protected]

    100 1.103

    1.104

    1.105

    0.01

    0.1

    1

    10

    100

    Fuse

    Relay / ContactorFuse

    Fuse Contactors

    10kA Contactoroperates for faults

    below 7kA

    Fuse operates forfaults above 7kA

    Fuse operationbelow 2kA is not

    permissible

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    15/62

    Generator and

    Power Station Protection High Impedance Differential Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    GENERATOR and

    POWER STATION

    PROTECTION

    Barrie Moor, B Eng (Elec)

    Slide [email protected]

    HIGH IMPEDANCEDIFFERENTIALPROTECTION

    Busbar Protection and

    Galvanically Connected

    Plant

    Slide [email protected]

    Synopsis

    HZ Differential Protection Principles

    Determination of setting voltage

    CT requirements

    Current operated schemes and stabilising resistors

    Limiting secondary system voltages to safe levels

    Primary operating current and application of shuntresistors

    CT supervision requirements

    Application of high impedance differential protection

    schemes to other galvanically connected plant

    Slide [email protected]

    SIMP

    LE!!!

    Bus Zone Protection Requirements

    Dependability

    Must trip for all in-zone faults

    Discrimination

    Must not trip for any out-of-zone faults

    Security

    Against all sources of mal-tripping

    Speed of operation

    As quickly as possible

    Dependability & Security

    Slide [email protected]

    CT Connections & Polarity

    S2

    P2

    S1

    P1

    I1

    I2

    P2

    S2

    P1

    I1 S1

    I2

    Slide [email protected]

    RELAY

    Internal Fault

    Slide [email protected]

    RELAY

    External Fault

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    16/62

    Generator and

    Power Station Protection High Impedance Differential Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    3 Phase CT Connections

    CT MARSHALLING

    DIFFERENTIALRELAY

    Slide [email protected]

    Current Mismatch

    CT Manufacturing Variations

    Inequality of CT Burdens

    CT Saturation

    Highest Fault Current on CT exposed to through fault

    Worst possible mismatch is

    Total saturation of the CT on the faulted plant

    All other CTs transform perfectly

    Slide [email protected]

    15000A 5000A

    RELAY

    5000A

    External Fault

    5000A

    External Fault & CT Saturation

    Slide [email protected]

    RELAY

    External Fault

    Rlead

    Rlead

    Rct High

    Impedance

    Relay

    CT Saturates :Magnetising branch

    impedance becomes zero

    LEADSCTFAULTRELAY RRIV

    Slide [email protected]

    Setting Voltage and Margins

    Fault current comprises

    AC Component

    DC Component

    Hence, employ a DC Stabilised Relay

    No additional margin on the setting is required

    And considering 0% / 100% CT saturation case

    This in an unrealistically extreme case

    100% safety margin is automatically built in

    So, no additional safety margin on setting is required

    Slide [email protected]

    RELAY

    Internal Fault

    High

    Impedance

    Relay

    RELAYKNEE V2V

    CTs will saturate under internal fault conditions, butrelay operation is assured provided absolutely all CTs

    meet the requirement

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    17/62

    Generator and

    Power Station Protection High Impedance Differential Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    CT Selection

    All CTs to be the same ratio

    All CTs to have Vk 2.Vsetting

    This is an absolute MUST

    Preferably Vk 5.Vsetting

    Need to know

    Knee Point voltage

    CT Resistance

    Class Requirements

    Not absolutely critical

    But highly recommended to specify class PX CTs

    0.1 PX 500 R3

    Magnetisingcurrent at kneepoint voltage

    Magnetisingcurrent at kneepoint voltage

    CT knee

    point voltage

    CT knee

    point voltage

    CT internalresistance

    CT internalresistance

    Slide [email protected]

    Summary

    Ensure Stability under through faults

    Ensure Operation for genuine in-zone faults

    Beware of short cut methods

    Do not simply set

    RELAYKNEE V2V

    2

    VV KNEERELAY=

    LEADSCTFAULTRELAY RRIV

    Preferably 5 times to optimiserelay performance, but 2 is theabsolute minimum to ensure

    reliable relay operation

    Preferably 5 times to optimiserelay performance, but 2 is theabsolute minimum to ensure

    reliable relay operation

    Slide [email protected]

    Current Operated Schemes

    Voltage operated

    Current operated, incl stabilising

    resistor

    Typical current settings

    as low as possible, but

    > 20% of plant rating

    < 30% of fault current

    20% setting is usually OK

    Assuming the CT has been

    selected to match plant

    rating

    V = I.R = 0.2 x (200 + 10) = 42 volts

    Relay0.2A

    10 ohms

    200 ohms

    Slide [email protected]

    Metrosils

    In the case of a heavy internal fault, secondary system voltages maybecome excessive

    Implications include damage to equipment and safety of personnel

    Empirical Formula

    VK = CT RMS knee point voltage

    VF = Maximum RMS voltage that would occur if the CT did notsaturate

    Install metrosils if this voltage become excessive(eg. >2.8kV peak)

    KFKPEAK VVV22V

    Slide [email protected]

    Metrosil Parameters

    Where V & I are PEAK

    values

    C = Metrosil constant

    B = Metrosil constant

    (0.2 0.25)

    And, because of the

    non-linearity

    I52.0IRMS

    ICV METROSIL NON-LINEAR RESISTORS

    V = C . IB

    10

    100

    1000

    1104

    0.001 0.01 0.1 1 10 100

    C = 450 B = 0.25

    C = 600 B = 0.25

    C = 900 B = 0.25

    Metrosil Current - Amps

    Slide [email protected]

    Metrosil Parameters

    Based on the previous equations, the RMS current at the

    relay setting voltage Vs(rms) is:-

    52.0

    I

    2

    CV RMS

    RMSSetting

    1

    Setting

    RMSC

    V252.0I RMS

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    18/62

    Generator and

    Power Station Protection High Impedance Differential Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    MAGMETROSILRELAYP INIICTI

    RELAYImag

    R

    shunt

    Ishunt

    Irelay

    Imet r

    osil

    Imag

    N = Number of CTs in parallel

    Primary Operating Current

    Slide [email protected]

    Shunt Resistors

    Desensitise scheme

    Prevent tripping on open CTs

    Primary operating current > maximum plant loading

    Effectively becomes a medium impedance scheme

    Slide [email protected]

    MAGSHUNTMETROSILRELAYP INIIICTI

    RELAYImag

    R

    shunt

    Ishunt

    Irelay

    Imet r

    osil

    Imag

    N = Number of CTs in parallel

    Primary Operating Current

    Slide [email protected]

    CT Supervision

    Effect of CT problems when Shunt Resistors are installed

    Scheme is part way to a trip condition

    Effect of CT problems when BZ Check scheme is installed

    Half of the scheme is already tripped

    CT Supervision Setting Principles

    Set to 50% of minimum load

    Operation : initially (eg. < 3 secs)

    Nil : allow for correct operation of BZ protection

    Operation : short time (eg. > 3 secs)

    Alarm

    CT Shorting

    GENERATOR and

    POWER STATION

    PROTECTION

    Barrie Moor, B Eng (Elec)

    Slide [email protected]

    HIGH IMPEDANCEDIFFERENTIALPROTECTION

    Application to other

    Plant

    Slide [email protected]

    HZ Protn Application to Plant

    Requires Galvanic Connection

    All CT ratios the same

    Can Apply To

    Busbars

    Transformers

    Generators & Motors

    Capacitors

    Reactors

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    19/62

    Generator and

    Power Station Protection High Impedance Differential Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    Relays

    StabilisingResistors

    Generators & Motors

    Slide [email protected]

    DIFF

    Auto Transformers

    All CT r atio s tobe the same

    This CT will carrymaximum currentand hencedictates ALL CTratios

    But this CT is internaland may have a singlefixed ratio.Thus, must be specifiedcorrectly at time ofpurchase !!

    Slide [email protected]

    REF

    Restric ted Earth Fault Protection

    CT terminalsaway fromprotected objectare connected

    CT terminalsnear toprotected objectare connected

    Slide [email protected]

    DIFFDIFF

    A

    DIFF

    B C

    Reactors Earthed Neutral

    Slide [email protected]

    DIFFDIFF

    A

    DIFF

    B C

    Reactors Floating Neutral

    Floating neutralbus is also protected

    Slide [email protected]

    DIFFDIFF

    A

    DIFF

    B C

    Capacitors Earthed Neutral

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    20/62

    Generator and

    Power Station Protection High Impedance Differential Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    DIFFDIFF

    A

    DIFF

    B C

    Capacitors Floating Neutral

    Floating neutralbus is also protected

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    21/62

    Generator andPower Station Protection Sequence Components

    Barrie Moor : 2012 [email protected](07) 3298 5260

    GENERATOR and

    POWER STATION

    PROTECTION

    Barrie Moor, B Eng (Elec)

    Slide [email protected]

    SEQUENCECOMPONENTS

    A Quick Review

    Slide [email protected]

    Sequence Components

    Positive Sequence

    A B C

    Equal in magnitude 120 degrees apart

    Negative Sequence

    A C B

    Equal in magnitude

    120 degrees apart

    Zero Sequence

    A B C

    Equal in magnitude

    In phase

    V1

    V2

    V0

    I1

    I2

    I0

    Slide [email protected]

    Sequence Components

    I1 I2 I0

    I phase

    IC

    IB

    IA

    Slide [email protected]

    Sequence Networks

    Source

    RelayLocation

    FaultLocation

    PositiveSequenceNetwork

    Z1s

    Z1f

    I1

    Source

    RelayLocation

    FaultLocation

    NegativeSequenceNetwork

    Z2f

    Z2s

    I2

    Source

    RelayLocation

    FaultLocation

    Zero

    SequenceNetwork

    Z0f

    Z0s

    I0

    V1 = 1 / 0 V2 = 0 V0 = 0

    Slide [email protected]

    Sequence ComponentsThree phase conditions

    Positive sequence only

    Three phase load

    Three phase fault

    No neutral (earth fault) current

    Slide [email protected]

    In = 0

    3 Phase Balanced Current

    Balanced currents sum to zero

    Positive sequence currents

    Negative sequence currents

    But zero sequence current will sum to 3.IoIn = 3.Io

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    22/62

    Generator andPower Station Protection Sequence Components

    Barrie Moor : 2012 [email protected](07) 3298 5260

    Slide [email protected]

    Sequence Networks3 Phase Fault

    Source

    RelayLocation

    FaultLocation

    PositiveSequenceNetwork

    Z1s

    Z1f

    I1

    f1Zs1ZZ

    Z

    V1II

    POS

    POS

    Fault_Phase_3

    =

    Slide [email protected]

    Sequence ComponentsPhase Phase fault

    Positive and Negative sequence components only

    And consider the special case where A phase equal in magnitude but opposite in phase

    B to CPhase to Phase fault

    Slide [email protected]

    Sequence Networks (A phase)Phase Phase fault

    A phase

    IA1 & IA2 antiphaseSum to zero

    B phase

    IB1 & IB2 at 60o

    C phase IC1 & IC2 at 60o

    IB = - IC

    Source

    RelayLocation

    FaultLocation

    Positive

    SequenceNetwork

    Z1s

    Z1f

    I1

    Source

    RelayLocation

    FaultLocation

    NegativeSequenceNetwork

    Z2f

    Z2s

    I2

    2I1I=

    Slide [email protected]

    Sequence Networks (A phase)Phase Phase fault

    Source

    RelayLocation

    FaultLocation

    Positive

    SequenceNetwork

    Z1s

    Z1f

    I1

    Source

    RelayLocation

    FaultLocation

    NegativeSequenceNetwork

    Z2f

    Z2s

    I2

    Since Z1 ~ Z2

    |I1| = |I2| = 50%of 3 phase faultlevel

    negpos ZZ

    V2I1I

    =

    Slide [email protected]

    Sequence ComponentsPhase Phase fault

    |I1| = |I2| = 50% of 3 phase fault level

    Thus |IB| = |IC| = 86.6% of 3 phase fault level(because of 60o angles)

    Slide [email protected]

    Sequence ComponentsEarth Fault

    A phase positive sequencenegative sequencezero sequence

    Equal in magnitudeand phase

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    23/62

    Generator andPower Station Protection Sequence Components

    Barrie Moor : 2012 [email protected](07) 3298 5260

    Slide [email protected]

    Sequence ComponentsEarth Fault

    Slide [email protected]

    Sequence NetworksA Phase Earth Fault

    Source

    RelayLocation

    FaultLocation

    PositiveSequenceNetwork

    Z1s

    Z1f

    I1

    Source

    RelayLocation

    FaultLocation

    NegativeSequenceNetwork

    Z2f

    Z2s

    I2

    Source

    RelayLocation

    FaultLocation

    ZeroSequenceNetwork

    Z0f

    Z0s

    I0

    Slide [email protected]

    Sequence NetworksA Phase Earth Faul t

    Source

    RelayLocation

    FaultLocation

    PositiveSequenceNetwork

    Z1s

    Z1f

    I1

    Source

    RelayLocation

    FaultLocation

    NegativeSequenceNetwork

    Z2f

    Z2s

    I2

    Source

    RelayLocation

    FaultLocation

    Ze

    roSequenceNetwork

    Z0f

    Z0s

    I0

    I = 1.0 I = 1.0 I = 1.0

    V1 = 1 / 0 V2 = 0

    V0 = -0.15

    V0 = -0.50

    V2 = -0.10

    V2 = -0.25

    V0 = 0

    V1 = 0.90

    V1 = 0.75

    = 0.10 = 0.10

    = 0.15= 0.15

    = 0.15

    = 0.35

    Slide [email protected]

    Sequence NetworksA Phase Earth Fault

    PositiveSequence

    FaultLocation

    NegativeSequence

    FaultLocation

    ZeroSequence

    FaultLocation

    RelayLocation

    ZS1

    Zl

    ZS2

    Zl

    I2I1

    RelayLocation

    ZS0

    Zl

    I0

    RelayLocation

    zeronegpos ZZZ

    V0I2I1I

    =

    0I2I1IIA

    0IB=

    0IC=

    0I3INEUT

    Slide [email protected]

    Sequence ComponentsSummary

    Positive Sequence

    Balanced three phase load

    Balanced three phase fault

    No neutral (earth) current

    Negative Sequence

    Unbalanced load

    Phase to phase fault

    No neutral (earth) current Zero Sequence

    Earth fault

    Neutral current = 3 . Io

    Cannot flow into or out of a delta

    Can circulate around (within) the delta

    Io = 0

    Io = 0

    Io = 0

    Io

    Io

    Io

    3Io

    GENERATOR and

    POWER STATION

    PROTECTION

    Barrie Moor, B Eng (Elec)

    Slide [email protected]

    TRANSFORMERSand

    SEQUENCECOMPONENTS

    DifferentialProtection

    Requirements

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    24/62

    Generator andPower Station Protection Sequence Components

    Barrie Moor : 2012 [email protected](07) 3298 5260

    Slide [email protected]

    Transformer Current Flows

    Star / Star Transformer : LV Earth Fault Current flows in corresponding HV winding

    Appears as EF on the HV system also

    I1, I2 & I0I1, I2 & I0I1, I2 & I0I1, I2 & I0

    Slide [email protected]

    Transformer Current Flows

    Star / Star Transformer : LV Earth Fault But, suppose we dont have an upstream power system earth However, consider the effect of adding a delta connected tertiary

    winding HV line current flows in a 2:1:1 ratio No I0 on the HV system as there is no path for neutral current flow

    I1, I2I1, I2

    I0I0

    I1, I2 & I0I1, I2 & I0

    So where did the I0 go ??So where did the I0 go ??

    Slide [email protected]

    Transformer Current Flows

    Star / Star Transformer : LV Earth Fault

    Retain the delta connected tertiary winding

    But, lets reinstate the power system earth

    Power system and delta winding zero sequence current flowdistributions will depend on their relative Z0 impedances

    I1, I2 & I0I1, I2 & I0I1, I2, I0I1, I2, I0

    I0I0

    Slide [email protected]

    Transformers, Sequence Componentsand Differential Protection

    Star/Star transformers, with a delta tertiary winding:

    Will have a mismatch between zero sequence current flows onthe HV & the LV windings

    It is thus necessary to exclude zero sequence current from thedifferential relay protection algorithms

    Star/Star transformers, without a delta tertiary winding:

    May still have a mismatch between zero sequence current flowson the HV & the LV windings

    The transformer tank can act as a low quality tertiary delta winding It is thus still necessary to exclude zero sequence current from

    the differential relay protection algorithms

    Slide [email protected]

    Transformer Current Flows

    Delta / Star Transformer : LV Earth Fault Current in corresponding HV winding only

    Appears as phase to phase fault from the perspective ofthe HV system

    I1 & I2 onlyI1 & I2 only

    So where did the I0 go ??So where did the I0 go ??

    I1, I2 & I0I1, I2 & I0

    Slide [email protected]

    Positive Sequence Network

    LVZS

    ZS HVZ1HL

    HV

    LV

    Zfdr

    Zfdr

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    25/62

    Generator andPower Station Protection Sequence Components

    Barrie Moor : 2012 [email protected](07) 3298 5260

    Slide [email protected]

    Negative Sequence Network

    ZS

    ZS Z1HL

    LV

    HV

    HV

    LV

    Zfdr

    Zfdr

    Slide [email protected]

    Zero Sequence Network

    ZS

    ZS Z1HL

    LV

    HV

    HV

    LV

    Zfdr

    Zfdr

    Slide [email protected]

    Transformer Current Flows

    Delta / Star Transformer : LV phase to phase fault Current in 2 LV windings

    Current in 2 HV windings

    Appears as 2:1:1 fault on the HV system

    I1 & I2I1 & I2I1 & I2I1 & I2

    Slide [email protected]

    Transformer Current Flows

    Star / Delta Transformer : LV phase to phase fault Current in all 3 LV windings

    Current in all 3 HV windings

    Appears as 2:1:1 fault on the HV system

    I1 & I2I1 & I2I1 & I2I1 & I2

    Slide [email protected]

    Sequence ComponentsTransformer LV ph-ph fault

    30 deg

    Consider B-C fault on the LV of either of Star Delta transformer Delta Star transformer

    30 deg phase shift Positive seq components Negative seq components

    will shift + 30 deg

    will shift - 30 deg

    Slide [email protected]

    Sequence ComponentsTransformer LV ph-ph fault

    LV phase to phase fault HV distribution is 1 : 2 : 1 LV distribution is 0 : 1 : 1

    So be careful when grading HV & LV IDMT OC Relays |I1| = |I2| = 50% of 3 fault level But note that I1 & I2 are 60o apart on the LV, but are shifted 30o and

    are thus, for the 2 phase, in phase on the HV LV current is 86.6% of 3 fault level in both phases HV current in the 2 phase is the same as for LV 3 fault !!

    30 deg

    LVHV

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    26/62

    Generator andPower Station Protection Sequence Components

    Barrie Moor : 2012 [email protected](07) 3298 5260

    Slide [email protected]

    Transformers, Sequence Componentsand Differential Protection

    Compensate for the transformer phase shift

    Exclude zero sequence current from the differential relay

    protection scheme Zero sequence current can flow into and out of earthed

    star windings

    Zero sequence current cannot flow into or out of deltawindings

    Zero sequence current can circulate around delta windings(said to be trapped in the delta)

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    27/62

    Generator and

    Power Station Protection Transformer Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    GENERATOR and

    POWER STATION

    PROTECTION

    Barrie Moor, B Eng (Elec)

    Slide [email protected]

    TRANSFORMERPROTECTION

    Slide [email protected]

    Types of Fault

    Phase-ground faults - from winding to core or winding to tank

    Phase-phase faults - between windings

    Interturn faults - between single turns or adjacent layers of the samewinding (Buchholz)

    Arcing contacts

    Local hotspots caused by shorted laminations

    Low level internal partial discharges (moisture ingress or designproblems)

    Bushing faults (internal to the tank)

    Tapchanger faults (often housed in a separate tank)

    Terminal faults (external to the tank, but inside the transformer zone)

    Slide [email protected]

    Buchholz Protection

    Two floats in the relay:

    Upper float

    Detects accumulation of gas

    Detects loss of oil

    Incipient faults

    Partial discharge

    Winding & core overheating

    Bad contacts and joints

    May alarm only or may be set to trip

    Lower float

    Detects surge in oil < 100ms

    Although it does take a finite time for

    pressure waves to initiate Buchholz

    tripping

    To Conservator

    Gas Sample

    Trip

    Alarm

    BUCHHOLZ RELAY

    Float

    To Tank

    Float

    Slide [email protected]

    Pressure Relief Device (Qualitrol )

    Spring assisted pressure relief devices

    Relieves pressure impulses due to massive internal fault conditions.

    Helps prevent the tank bursting or splitting

    Relay contacts are also connected to trip the transformer.

    Since pressure waves travel with a finite velocity, they may rupture

    the tank locally before the pressure wave has reached the pressure

    relief device, if it is some distance away. Several units may therefore

    be required on larger transformers.

    Slide [email protected]

    Basic Transformer Protection

    Fuses

    Transformers without CBs

    Perhaps to a few MVA

    Overcurrent & Earth Fault Protection

    Transformers with CBs

    Perhaps 5 - 50MVA

    Differential Protection

    Transformers > 10MVA Fast

    Can be sensitive

    May detect terminal faults also

    GENERATOR and

    POWER STATION

    PROTECTION

    Barrie Moor, B Eng (Elec)

    Slide [email protected]

    TRANSFORMERPROTECTION

    Biased Differential

    Protection

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    28/62

    Generator and

    Power Station Protection Transformer Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    Differential Protection

    DifferentialRelay

    P1

    S1

    P2

    S2

    SIDE OF CT AWAYFROM PROTECTEDPLANT CONNECTS

    TO RELAY

    CURRENT FLOWSINTO PLANT

    CURRENT FLOWSOUT OF PLANT

    CURRENT FLOWSINTO RELAY

    CURRENT FLOWSOUT OF RELAY

    SIDE OF CT AWAYFROM PROTECTEDPLANT CONNECTS

    TO RELAY

    TRIPELEMENT

    IT IS NOT THE P1/S1 OR P2/S2ORIENTATIONS THAT ARE

    IMPORTANT, BUT THEPREFERENCE FOR THE

    AWAY SIDES OF THE CTsTO CONNECT TO THE RELAY

    Slide [email protected]

    Differential Protection of Transformers

    11/132kV

    2400/1 200/12400A 200A

    1A 1A

    BIAS orRESTRAINTELEMENT

    BIAS orRESTRAINTELEMENT

    TRIPPING ELEMENTDETECTS ONLY THE

    MIS-MATCH CURRENT

    TRIPELEMENT

    Slide [email protected]

    Transformer Differential Mismatch

    Differential CT ratio selection

    CT ratios selected to compensate for the transformer turnsratio

    Mismatched CTs

    CTs do not exactly compensate for transformer turns ratio

    Transformer turns ratio changes with tap changing

    Implement a biasing restraint system

    Magnetizing current in the CTs, especially as somesaturation due to DC fault current sets in.

    The amount of bias is increased under heavy through faultconditions to compensate for possible CT saturation

    Slide [email protected]

    Transformer Differential Mismatch

    Inrush on energisation (2nd harmonic)

    Over excitation (5th harmonic)

    Transformer phase shifts

    Earth fault (neutral zero sequence) currents

    Slide [email protected]

    Inrush Current onEnergisation of Transformer

    TRIPELEMENT

    Slide [email protected]

    Second Harmonic on Inrush

    Transformer inrush current on energization.

    Inrush current produces a current from the energizing side

    only, appearing as an internal fault.

    Inrush current magnitude can be as great as a through 3

    phase fault.

    This current is characterized by the appearance of secondharmonics, so additional restraint can be based on this 2nd

    harmonic signature

    Relay setting below the 2nd harmonic level is required(Ratio of 2nd harmonic to fundamental)

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    29/62

    Generator and

    Power Station Protection Transformer Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    Transformer Inrush Current

    2

    0

    2

    4

    6

    8

    10

    12

    0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5

    Transformer Inrush Current

    Current

    Seconds

    Inrush current : with 2nd Harmonic

    Slide [email protected]

    Fifth Harmonic on over excitation

    Overfluxing, caused by too high a voltage, or too low a frequency.

    Increased magnetising current

    This is characterized by third & fifth harmonics. Fifth harmonic restraint to retrain tripping of the differential

    element

    Typically no user calculations or settings are required

    Sustained overfluxing may damage the transformer

    Time delayed V/f tripping function (long time)

    Especially applicable to generator transformers

    Frequency can be anywhere from zero to nominal during run-up andrun down

    Not so necessary for transmission or distribution applications

    Frequency will not deviate significantly from nominal

    Slide [email protected]

    Bias Differential Protection

    Allow for Transformer turns ratio

    Allow for Transformer phase shifts

    Eliminate Zero Sequence currents from the relaying system

    OperatingWinding

    P1

    S1

    Bias Windings

    P1

    S1

    GENERATOR and

    POWER STATION

    PROTECTION

    Barrie Moor, B Eng (Elec)

    Slide [email protected]

    SEQUENCECOMPONENTS

    A Quick Review

    GENERATOR and

    POWER STATION

    PROTECTION

    Barrie Moor, B Eng (Elec)

    Slide [email protected]

    TRANSFORMERPROTECTION

    Continued

    Slide [email protected]

    CT Connections and Ratios

    Star/Delta and Delta/Star transformers have a 30 degree phase shift

    Compensate with CTs connected opposite to the transformer

    connections. ie:

    Star connected CTs on the delta side of the transformer

    Delta connected CTs on the star side of the transformer

    Phase shift compensated

    Zero sequence currents flowing in the transformer star windings

    prevented from entering the relaying system

    But how do we get the correct delta connection for our CTs ???

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    30/62

    Generator and

    Power Station Protection Transformer Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    Determination of CT Connection

    Diff Prot

    Yd11

    D11D11

    CT Primary is star connectedCT secondary is D11 connectedOverall connection is thus YD11

    Slide [email protected]

    Determination of CT Connection

    Dy11

    D1D1

    Diff Prot

    CT Primary is star connectedCT secondary is D1 connectedOverall connection is thus YD1

    Slide [email protected]

    Star/Delta and Delta/Star TransformersCT Connection Summary

    Transformer HV is STAR connected

    HV CTs are delta connected (ie. phase shift ing)

    HV CTs EQUAL to the transformer phase shift

    LV CTs in star

    Transformer LV is STAR connected

    LV CTs are delta connected (ie. phase shifting) LV CTs OPPOSITE to the transfor mer phase shift

    HV CTs in star

    Slide [email protected]

    CT Connection Summary

    Compensates for the phase shift across a star-deltatransformer.

    The correct vector group must be chosen for the CTs toensure that through currents balance.

    Prevents any zero sequence currents flowing in the starwinding from entering the relay

    Since they are not present in the line on the delta side.

    And for Star / Star transformers ??

    It is still necessary to eliminate Io from the relaying system

    Connect CTs delta / delta

    Or use the D12 / D12 feature of microprocessor relays

    Slide [email protected]

    A phase output is at "11 o'clock"

    A phase "S1" connects to B phase "S2"B phase "S1" connects to C phase "S2"C phase "S1" connects to A phase "S2"

    D11

    S2

    A

    S1

    S1

    C

    S2

    S1

    S2

    B

    C

    B

    A

    CT YD11 Connections

    D11D11

    Slide [email protected]

    A phase output is at "1 o'clock"

    A phase "S2" connects to B phase "S1"B phase "S2" connects to C phase "S1"C phase "S2" connects to A phase "S1"

    A phase output is at "11 o'clock"

    A phase "S1" connects to B phase "S2"B phase "S1" connects to C phase "S2"C phase "S1" connects to A phase "S2"

    D11

    S2

    A

    S1

    S1

    C

    S2

    S1

    S2

    B

    D1

    C

    B

    A

    S2B

    S2

    S1

    S1

    A

    S1C

    S2

    C

    B

    A

    CT YD1 Connections

    D1D1

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    31/62

    Generator and

    Power Station Protection Transformer Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    A B

    Bias Windings

    P1 P2

    S1 S2

    A1 A2

    OperatingWindings

    C

    a2 a1P1P2

    S2 S1

    Notice that theconnections forthe Delta windingsare the same !!

    Away side of CTs connected to relay.Hence, transformer current in or outcorresponds to relay current in or out.

    Away side of CTs connected to relay.Hence, transformer current in or outcorresponds to relay current in or out

    Slide [email protected]

    Transformer Current Flows

    There must be a path for the current to flow

    There must be an Ampere Turns balance

    If there is current flowing in one winding

    There must be current in the coupled winding

    If there is no current flowing in one winding

    There can be no current in the coupled winding

    A B

    Bias Windings

    P1 P2

    S1 S2

    A1 A2

    OperatingWindings

    C

    a2 a1P1P2

    S2 S1

    External Phase Earth Fault

    Protection Scheme remains balanced

    HV 0:1:1 (HV looks like a phase phase fault)

    LV 0:0:1 (LV is actually a single phase fault)

    A B

    Bias Windings

    P1 P2

    S1 S2

    A1 A2

    OperatingWindings

    C

    a2 a1P1P2

    S2 S1

    Protection Scheme remains balanced

    HV 1:2:1 (HV has a 2:1:1 current distribution)

    LV 0:1:1 (LV is actually a phase phase fault)

    External Phase Phase Fault

    Slide [email protected]

    Delta CTs and Ratio Selection

    CT ratios must allow for the fact

    that current flowing into therelay from the delta connected

    CTs is 3 times the CTsecondary current

    Hence, a standard 1A CT will

    result in relay current of 3times the CT secondary current

    Thus, CTs with ratios such as

    1000/0.577 are, for this reason,quite common.

    1/0

    1 / -120

    1/-

    240

    = 1.732 /-30

    1 / 0 1/-240

    Slide [email protected]

    Delta CTs and Ratio Select ion

    Ia - Ic = 1.732 /-30

    CT ratios must allow for the fact

    that current flowing into therelay from the delta connected

    CTs is 3 times the CTsecondary current

    Hence, a standard 1A CT will

    result in relay current of 3times the CT secondary current

    Thus, CTs with ratios such as

    1000/0.577 are, for this reason,quite common.

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    32/62

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    33/62

    Generator and

    Power Station Protection Transformer Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    CT Ratio Selection

    The CT ratios must be opposite to the transformer ratio

    Choose one CT ratio

    Base all other CT ratios on this selection and transformerturns ratio

    Not on winding MVA !!!

    And, as noted before CT ratios must allow for the fact

    that current flowing into the relay from the delta connected

    CTs is 3 times the CT secondary current

    Slide [email protected]

    Modern Microprocessor Relays

    All CTs connected in Star

    Relay has to process phase shifts

    Relay has to remove neutral current

    P1

    P1

    P1

    S1

    S1

    S1

    S1

    S1

    S1

    P1

    P1

    P1

    Slide [email protected]

    Modern Microprocessor Relays

    P1

    P1

    P1

    S1

    S1

    S1

    S1

    S1

    S1

    P1

    P1

    P1

    ICIAIARELAY

    IAIBIBRELAY

    IBICICRELAY

    IC

    IB

    IA

    110

    011

    101

    3

    1

    IC

    IB

    IA

    RELAY

    RELAY

    RELAY

    IC

    IB

    IA

    110

    011

    101

    3

    1

    IC

    IB

    IA

    RELAY

    RELAY

    RELAY

    Slide [email protected]

    D1

    D11

    A phase output is at "1 o'clock"

    A phase "S2" connects to B phase "S1"B phase "S2" connects to C phase "S1"C phase "S2" connects to A phase "S1"

    A phase output is at "11 o'clock"

    A phase "S1" connects to B phase "S2"B phase "S1" connects to C phase "S2"C phase "S1" connects to A phase "S2"

    D11

    S2

    A

    S1

    S1C

    S2

    S1

    S2

    B

    D1

    C

    B

    A

    S2B

    S2

    S1

    S1

    A

    S1C

    S2

    C

    B

    A

    Modern Microprocessor Relays

    =

    IC

    IB

    IA

    110

    011

    101

    3

    1

    IC

    IB

    IA

    RELAY

    RELAY

    RELAY

    =

    IC

    IB

    IA

    101

    110

    011

    3

    1

    IC

    IB

    IA

    RELAY

    RELAY

    RELAY

    Slide [email protected]

    Modern Microprocessor Relays

    =

    IC

    IB

    IA

    211

    121

    112

    3

    1

    IC

    IB

    IA

    RELAY

    RELAY

    RELAY

    D12

    D1

    D11

    =

    IC

    IB

    IA

    110

    011

    101

    3

    1

    IC

    IB

    IA

    RELAY

    RELAY

    RELAY

    =

    IC

    IB

    IA

    101

    110

    011

    3

    1

    IC

    IB

    IA

    RELAY

    RELAY

    RELAY

    Slide [email protected]

    Modern Microprocessor RelaysD12 Zero sequence current elimination

    =

    IC

    IB

    IA

    211

    121

    112

    3

    1

    IC

    IB

    IA

    RELAY

    RELAY

    RELAY

    ( )ICIBIAIA33

    1=

    ( )( )ICIBIAIA33

    1++=

    ( )0I3IA33

    1=

    0IIA=

    ( )ICIBIA23

    1IARELAY =

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    34/62

    Generator and

    Power Station Protection Transformer Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    Modern Microprocessor Relays

    All CTs can now be connected in Star

    Relay internal processing adjusts for phase angle

    Relay internal processing rejects zero sequencecomponents

    CT ratios mismatches can also now be accommodated

    Internal processing within relay then adjusts CT current to

    match transformer turns ratio

    CTs can be fine tuned to match middle tap position

    Allows for more sensitive relay settings

    Slide [email protected]

    CT Phase and Ratio Adjustment

    Dyn120MVA 33/11kV

    1500/1400/1

    DifferentialElement

    350A 1050A

    0.7A

    -300

    0.875A

    00

    00

    1A

    00

    1A

    Transformer Microprocessor Differential Protection Relay

    Magnitudes normalised to transformer FLC Phase angles compensated Zero sequence current eliminated

    Yy0

    Software CTx 1.143

    Software CTx 1.429

    Yd11

    00 -300

    TAP POSITION

    SoftwareCT Ratio

    Adju stm ent

    Slide [email protected]

    Differential Relay Bias Settings

    CT ratio selection

    Select one ratio to meet load requirements

    Base all other ratios on the first (not on load !)

    Allow Margin (perhaps 10-15%) allowing

    the worst mismatch of transformer ratio

    and CT ratios (remember 3 for delta CTs !!!)

    To decide worst case - consider the overall scheme

    At the top tap position .......... & then

    At the bottom tap position.

    And both should be the same for a microprocessor based

    relay that is correctly mid tap balanced

    Slide [email protected]

    Differential Relay Bias Settings

    Use the relay equations to determined the worstmismatch

    Typically

    I1 & I2 are the currents into the two sides of thetransformer

    2I1IDiff

    2

    2I1IBias

    50%Not Average !!

    Slide [email protected]

    Tap Changer Position

    For any setting of tap changer and through current, andgiven the CT ratios, the values of bias current anddifferential current can easily be calculated.

    Base calculation on the relay algorithm not on anarbitrary or simple mismatch calculation Note that the previous equations are not the only options

    available to and used by relay manufacturers

    Hence use THE ACTUAL RELAY equations !!

    Allow the recommended safety margin Probably 10 15%

    And check your e lbow !!

    Slide [email protected]

    Transformer Bias Differential Protection

    0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 60

    0.5

    1

    1.5

    2

    2.5

    3

    3.5

    4

    15% Differential Setting

    25% Differential Setting

    35% Differential Setting

    Differential

    Current

    Diff I1 I2+:=

    Bias Current BiasI1 I2+

    2:=

    OPERATEOPERATE

    TransformerInternal Fault

    Protection Trips

    TransformerInternal Fault

    Protection Trips

    Through Fault withCT Saturation

    Through Fault withCT Saturation

    Through FaultMismatch due to CT Ratios &Transformer Tap Changing

    Through FaultMismatch due to CT Ratios &Transformer Tap Changing

    RESTRAINRESTRAIN

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    35/62

    Generator and

    Power Station Protection Transformer Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    CT Requirements

    Some CT saturation is permissible for through faults

    Such CT saturation occurs mainly due to the DC

    component of the fault current

    Most manufacturers provide simple equations to

    determine CT class

    No complex calculations required

    GENERATOR and

    POWER STATION

    PROTECTION

    Barrie Moor, B Eng (Elec)

    Slide [email protected]

    TRANSFORMERPROTECTION

    Winding Neutral

    End Faults

    Slide [email protected]

    Protection for neutral end earth faults

    Small current Many turns

    Large current Few turns

    Differential Protection

    Line current mismatchis too small to trip thedifferential relay

    We need to monitorneutral current flow

    Slide [email protected]

    Transformer Neutral Fault Current & Primary Current

    0 10 20 30 40 50 60 70 80 90 1000

    2

    4

    6

    8

    10

    12

    14

    16

    Fault Current in Shorted TurnsPrimary Current

    FAULT

    CURRENT

    multiples

    of

    rated

    current

    DISTANCE OF FAULT

    FROM NEUTRAL

    (Percentage of winding)

    Significant current flows in theactual fault near to the neutralend of the transformer winding

    But very little linecurrent flows at theHV terminals

    Slide [email protected]

    REF

    Restric ted Earth Fault Protection

    CT terminalsaway fromprotected objectare connected

    CT terminalsnear toprotected objectare connected

    Slide [email protected]

    DIFF

    Auto TransformerHigh Imp Phase Segregated Protection

    All CT r atio s tobe the same

    This CT will carrymaximum currentand hencedictates ALL CTratios

    But this CT is internaland may only have asingle fixed ratio.Therefore, this must bespecified correctly atthe time of purchase !!

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    36/62

    Generator and

    Power Station Protection Transformer Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    High Impedance Protection

    Especially sensitive in detecting earth faults in the

    bottom 25% of the winding

    Application to

    Auto Transformers

    REF earth fault schemes

    Tertiary windings not specifically protected

    Setting principles same as for bus zone

    Select voltage setting to achieve through fault stability

    CT Vk > 2.Vset to ensure scheme operation

    HighImpedanceRelays

    Tertiary

    HV CTs LV CTsNeutral CTs One per phase at neutral end But above the star point

    Restric ted Earth Fault Protection

    Restricted EF ProtRestricted EF Prot

    Transformer delta winding and star winding REF protection schemes

    LV scheme remainsstable for external EF

    HV scheme remainsstable for external EF

    HV scheme also remainsstable for all LV EFs

    GENERATOR and

    POWER STATION

    PROTECTION

    Barrie Moor, B Eng (Elec)

    Slide [email protected]

    EARTHINGTRANSFORMERS

    Operationand

    Protection

    Slide [email protected]

    Earthing Transformer

    LOAD

    Earthing Transformer Fault Currents

    Slide [email protected]

    B

    A

    C

    Earthing Transformer

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    37/62

    Generator and

    Power Station Protection Transformer Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    Earthing Transformer

    LOAD

    Earthing Transformer Fault Currents

    Slide [email protected]

    Earthing Transformers

    Provide a good earth reference for a delta winding duringearth faults

    Restrict the voltage rise on the healthy phase duringearth faults inoperative during balanced voltageconditions

    Carry significant current only during earth faultsie. 3 x I0 only

    Earthing transformer and associated power transformerconsidered as a single unit and tripped together

    Slide [email protected]

    Effectively Earthed System

    R0/X1 < 1

    X0/X1 < 3

    Limit voltage rise on unfaulted phases

    80% of rated phase - phase voltage

    Otherwise healthy phases can reach 100% of rated phase

    - phase voltage

    May even exceed this on transients

    Slide [email protected]

    Protection of Earthing Transformer

    Two types of faults we need to consider:

    Internal faults - faults inside the earthing transformer, the

    result of insulation breakdown.

    External faults - faults on the system outside the earthing

    transformer. These can cause overheating of the earthing

    transformer

    Slide [email protected]

    Over Current Protection

    Over Current Protection

    Interturn, interwinding or winding-to-core faults

    Fed from delta-connected current transformers, so thatearth faults on the system, which generate only zero

    sequence current, are not seen

    Hence, O/C setting can be very low

    Slide [email protected]

    Earth Fault Protection

    Earth Fault Protection

    Long term low level unbalance may cause thermal

    damage

    Need to consider and set earth fault below

    continuous rating capability

    short-time rating capability

    Combination of IDMT and definite time functions used

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    38/62

    Generator and

    Power Station Protection Transformer Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    Earthing Transformer

    O/C relay does not operate for externalearth faultsDef Time and IDMT E/F relays operate forexternal earth faults IDMT E/F relay

    Def Time E/F relay

    O/C relay

    LOAD

    Slide [email protected]

    Overcurrent Setting Must be:

    Greater than the magnetising current

    Greater than the maximum inrush current. This depends on

    Earthing transformers B-H characteristics The point-on-wave of the energisation

    The remanence of the core

    One common estimate of upper bound is 50x the magnetising

    current

    Tolerant of Earthing Transformer manufacturing variations

    Impedances variations between the individual phases of the

    earthing transformer may result in some spill current from the

    delta CTs under through EFs

    Slide [email protected]

    Earth Fault Protection

    Affected by long term residual voltage, which may cause

    thermal damage

    remember - no over temperature sensor is provided

    Need to consider and set earth fault below

    continuous rating capability

    short-time rating capability

    Combination of IDMT and definite time relays used to do

    this

    Thermal Protection

    10 100 1 103

    1 1040.1

    1

    10

    100

    1 103

    1 104

    1 105

    EARTHING TRANSF THERMAL PROTECTION

    EARTH FAULT CURRENT - AMPS

    TIME-SECONDS

    30

    2300

    contrating30A

    max E/Fcurrent2300A

    adiabatic thermal limit

    actual thermal limit

    earthing transformer E/F relay - Definite Time

    downstream E/F relay

    earthing transformerE/F relay - IDMT

    Slide [email protected]

    Biased Differential Protection

    Earthing transformers are included inside the biased differential

    zone of their power transformer

    Current transformer connections important

    LV CTs will be star connected

    Thus Io can flow to the differential relay

    And earthing transformer now supplies Io

    Thus stability for external earth faults becomes an issue

    To eliminate Io from the relaying system

    YD12 CT connection with microprocessor differential relay

    Or utilise additional Earthing Transformer CT connections

    0

    C

    B

    A

    400/0.577

    132 / 33 kV

    externalearthfault

    1600/1

    0

    c

    b

    0a

    Earthing Transformer CTsDifferential Trip due to LV I0 Currents

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    39/62

    Generator and

    Power Station Protection Transformer Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    all 1600/0.333

    0

    C

    B

    A

    400/0.577

    132 / 33 kV

    Nexternal

    earthfault

    1600/1

    0

    c

    b

    0a

    Earthing Transformer CTsEliminate I0 from the relaying system

    Slide [email protected]

    Zero Sequence Current Trap

    Star connected interposingCTs with neutral connection

    Interposing CT secondarywithout neutral connection

    CT includes a delta tertiary

    winding to trap zerosequence currents

    3 wire connection to the relayI1 & I2 only

    Slide [email protected]

    D1

    D11

    Modern Microprocessor Relays

    IC

    IB

    IA

    110

    011

    101

    3

    1

    IC

    IB

    IA

    RELAY

    RELAY

    RELAY

    IC

    IB

    IA

    101

    110

    011

    3

    1

    IC

    IB

    IA

    RELAY

    RELAY

    RELAY

    IC

    IB

    IA

    211

    121

    112

    3

    1

    IC

    IB

    IA

    RELAY

    RELAY

    RELAY

    D12

    No phase change

    But, removes neutral current

    GENERATOR and

    POWER STATION

    PROTECTION

    Barrie Moor, B Eng (Elec)

    Slide [email protected]

    TRANSFORMERPROTECTION

    Delta Windings withEarthed Corner

    Slide [email protected]

    Delta windings with earthed corner

    Typical for transformer tertiary windings

    To maintain stability on through faults

    Need to include CT in the earthed corner

    CT to be the same ratio as the main CT

    Connect in parallel with the earthed phase CT

    This cannot be overcome with phase shifting and Io

    facilities of microprocessor based relays

    Earthed Delta Corners inside theDifferential Zone

    CT installed on the earthed corner.Same ratio as phase CTsIn parallel with the phase CT onthe earthed phase

    This is also required formicroprocessor relay schemes

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    40/62

    Generator and

    Power Station Protection Transformer Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    GENERATOR and

    POWER STATION

    PROTECTION

    Barrie Moor, B Eng (Elec)

    Slide [email protected]

    TRANSFORMERPROTECTION

    Neutral Displacement

    Protection

    Slide [email protected]

    Neutral Displacement Protection

    Applicable to delta windings with no earth reference

    Connected to open delta of VT secondary

    To provide a zero sequence flux path

    3 x 1 phase VTs or

    5 limb VT

    Relay must be immune to 3rd harmonics

    Tripping time can be relatively slow

    Problems can occur with resonance on energisation

    Slide [email protected]

    Neutral Displacement Protection

    VoltageDisplacement

    Relay

    VT with open deltasecondary winding

    Slide [email protected]

    Neutral Displacement Protection

    Measures 3.Vo for a solid E/F

    Healthy phases rise to full phase-phase potential

    Healthy phases are now only 60 deg apart

    Thus, for standard 63.5V VT, output voltage is 190.5V

    Set relay to 10% say 20V

    NeutralDisplacement

    Protection

    0 V0 V

    VB = 3VC = 3

    VA = 0

    -150+150

    63.5 V63.5 V110 V110 V190.5 V190.5 V

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    41/62

    Generator and

    Power Station Protection Motor Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    GENERATOR and

    POWER STATION

    PROTECTION

    Barrie Moor, B Eng (Elec)

    Slide [email protected]

    MOTORPROTECTION

    Slide [email protected]

    Motor Protection

    To detect faults within the motor and supply system

    Faults on the supply system, cables, etc

    Internal faults

    Often as a result of previous thermal events

    Thermal Withstand

    Motor overload

    Starting and Stalling currents & times

    Unbalanced voltage supply (NPS)

    System events

    Loss of load, under voltage, etc.

    Slide [email protected]

    Motor Protection

    Thermal Protection

    Extended Start Protection

    Stalling Protection

    Number of Starts Limitation

    Negative Sequence Current Detection

    Short Circuit Protection

    Earth Fault Protection Under Voltage Protection

    Loss of Load Protection

    Winding RTD measurement and trip

    THERMALPROTECTION

    GENERATOR and

    POWER STATION

    PROTECTION

    Barrie Moor, B Eng (Elec)

    Slide [email protected]

    MOTORPROTECTION

    Thermal Protection

    Slide [email protected]

    Thermal Overload Protection

    Winding failures are often due to previous heating

    Because of the motors thermal mass

    Infrequent short term overloads may have no affect

    But sustained overloads, of even just a few percent, may

    cause aging and premature insulation failure

    Insulation life may be halved for operation every 10 deg Cabove rated maximum.

    Slide [email protected]

    Starting Current

    High starting current reducesto full load current as the motor

    gains speed

    Positive sequence impedance

    of the motor at any slip is :-

    SYNC

    ACTSYNC

    N

    NNSlip

    =

    2

    1R1S

    2

    1R1SPOS XX

    S

    RRZ

    0 250 500 750 1000 1250 15000

    0.2

    0.4

    0.6

    0.8

    1

    Z s( )

    s

    0 250 500 750 1000 1250 15000

    1

    2

    3

    4

    5

    6

    I s( )

    s

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    42/62

    Generator and

    Power Station Protection Motor Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    Negative Sequence Equivalent Circuitof Induction Motor

    Positive Sequence Equivalent Circuitof Induction Motor

    (Rs2 + Rr2)

    (Rs1 + Rr1)

    j(Xs2 + Xr2)

    (S - 1) Rr2

    (2 - S)

    j(Xs1 + Xr1)

    S

    (1 - S) Rr1

    Motor Impedances

    Slide [email protected]

    Positive Sequence Impedance

    At any slip

    At standstill with slip = 1.0

    This is a small impedance, hence high starting current

    eg. up to 6 pu

    21R1S

    2

    1R1SPOS XX

    SRRZ

    2

    1R1S

    2

    1R1SPOS XXRRZ

    Slide [email protected]

    Negative Sequence Impedance

    At any slip

    At normal running with slip 0

    2

    2R2S

    2

    2R2SNEG XX

    S2

    RRZ

    2

    2R2S

    22R

    2SNEG XX2

    RRZ

    Slide [email protected]

    Motor Impedances

    Positive Sequence : Standstill

    Negative Sequence : Running

    R is small compared with X:

    These will be approximately the same !!

    2

    1R1S

    2

    1R1SPOS XXRRZ

    2

    2R2S

    2

    2R2SNEG XX

    2

    RRZ

    RUNNINGSTANDSTILL NEGPOSZZ =

    Slide [email protected]

    Motor Impedances Consider an example where ISTART/IFLC = 6

    Hence, 1pu positive sequence supply voltage results in:

    1 pu current when running at full load

    6 pu current at start-up

    But the negative sequence impedance at running is thesame as the positive sequence impedance at startup

    So, when running, 1 pu NPS supply voltage wouldresult in:

    6 pu NPS current

    Or, as a typical example, when running, 1% NPSsupply voltage would result in:

    6% NPS current

    Slide [email protected]

    CurrenttartingS

    CurrentLoadFull

    Z

    Z

    RUNNING

    STARTING

    POS

    POS=

    Motor Impedances

    Positive sequence impedances at Start-up & Running

    And since:

    CurrenttartingS

    CurrentLoadullF

    Z

    Z

    RUNNING

    RUNNING

    POS

    NEG=

    RUNNINGSTARTING NEGPOSZZ =

    eg. 1/6 th

    eg. ZNEG = ZPOS / 6

    So, what does this

    mean for NPS current

  • 8/10/2019 Generator and Power Station Protection_2012.pdf

    43/62

    Generator and

    Power Station Protection Motor Protection

    Barrie Moor : 2012 [email protected]

    (07) 3298 5260

    Slide [email protected]

    Negative Sequence Current

    Negative sequence current will equal:

    % of NPS in the supply voltage

    Multiplied by the ratio of starting / full load current

    Multiplied by full load current

    =NPSI

    POS

    NPS

    V

    V

    FLC

    CurrentStarting[ ]

    FLCI