w w w . l i t t e l f u s e . c o m© 2005 Littelfuse • POWR-GARD™ Products Catalog
General Purpose Fuses
KLLU Class L Fuses 26-28
FLNR_ID/FLSR_ID Indicator® Class RK5 Fuses 29-32
FLNR/FLSR Class RK5 Fuses 33
KLNR/KLSR Class RK1 Fuses 34-35
NLN/NLS Class K5 Fuses 36-37
RLN/RLS Class H Fuses 38
JLS Class J Fuses 39-40
JLLN/JLLS POWR-T ™ Class T Fuses 41-43
SLC Class G Fuses 44
Class CC and Class CD Fuses 45-47
Plug Fuses 48
Catalog 25-48.indd 25 5/30/07 6:18:47 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose FusesG
ener
al P
urpo
se F
uses
26 w w w . l i t t e l f u s e . c o m © 2005 Littelfuse • POWR-GARD™ Products Catalog
KLLU series UL Listed, time-delay, Class L fus es are quality fuses, de vel oped to provide a some what lower priced al ter nate to the POWR-PRO® KLPC series fuses. KLLU series fuses meet or exceed all UL re quire ments for Class L fus es. For superior protection and performance, spec i fi ca tion-grade POWR-PRO KLPC series fus es are the rec om mend ed fuse. Com plete in for ma tion on KLPC fus es may be found in the POWR-PRO Fuse section of this catalog.
Applications
Service switchesSwitchboard mains and feedersBolted pressure contact switchesMotor control center mainsLarge motor branch circuitsUL Listed series rated protection for molded case circuit breaker
panelboards and loadcenters. See panelboard manufacturers’ literature for recommended fuse rating.
Safety
• 200,000 A.I.R. — Provides reliable in ter rup tion of all overcurrents up to 200,000 am peres.
• When used for motor branch circuit pro tec tion, KLLU fuses may be sized close to the motor full load current, providing excellent protection to branch circuit con duc tors, motor control equip ment and motors.
Longer Equipment Life
• Current-Limiting — Reduces short-circuit damage to systems and equipment.
• Reduced downtime.• Ten second minimum time-delay at 500% current eliminates
needless downtime caused by heavy starting currents of large motors and other in duc tive loads.
• Selective coordination — KLLU fuses co or di nate well with other Class L fuses and with all current-limiting Littelfuse fuses rated 600 amps or less. This means less time spent trying to locate short-circuits or over load ed equipment, because only the fuse im me di ate ly on the line side of the af fect ed circuit opens.
Easy To Use
• 200,000 A.I.R. rating minimizes need for short-circuit cal cu la tions, while meeting present and future system re quire ments.
• KLLU fuse time-current characteristics closely match typical time-current curves of circuit breakers. Although fuse/circuit breaker systems can seldom be 100% coordinated, KLLU series fuses permit use of a wider range of breaker setting than fast acting Class L fuses. Ex cel lent protection for a single breaker or a group of breakers.
KLLU Class L Fuses
600 VAC • Time-Delay • 601 – 4000 Amperes
Specifications
Voltage Ratings: AC: 600 Volts DC: Contact factoryInterrupting Ratings: 200,000 am peres rms symmetricalAmpere Range: 601 – 4000 amperesApprovals: Standard 248-10, Class L UL Listed (File No: E81895) CSA Certified (File No: LR29862)
Ampere Ratings
601 750 1000 1400 1800 3000650 800 1200 1500 2000 3500700 900 1350 1600 2500 4000
Example part number (series & amperage): KLLU 1000
Catalog 25-48.indd 26 5/30/07 6:18:52 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose Fuses
General Purpose Fuses
27w w w . l i t t e l f u s e . c o m© 2005 Littelfuse • POWR-GARD™ Products Catalog
KLLU Class L Fuses
600 VAC • Time-Delay • 601 – 4000 Amperes
BC
J
F
M
FIG.1
A ABC
J
D E F
N
M
FIG.2
D E FABC
G
H
NM
J
FIG. 3
NM G
D E FABC
HJ
FIG. 4
KL
Amperes Fig. No.Dimensions In Inches (mm in parentheses)
A B C D E F G H J K L M N
601 – 800 133⁄4
(95.3)53⁄4
(146.1)63⁄4
(171.5) — —8 5⁄8
(219.1) — —2
(50.8)21⁄2
(63.5)3⁄8
(9.5)5⁄8 x 11⁄8
(15.9) x (28.6)—
801 – 1200 233⁄4
(95.3)53⁄4
(146.1)63⁄4
(171.5)91⁄4
(235.0)91⁄2
(241.3)103⁄4
(273.1) — —2
(50.8)21⁄2
(63.5)3⁄8
(9.5)5⁄8 x 3⁄4
(15.9) x (19.1)5⁄8 x 11⁄8
(15.9) x (28.6)
1201 – 1600 233⁄4
(95.3)53⁄4
(146.1)63⁄4
(171.5)91⁄4
(235.0)91⁄2
(241.3)103⁄4
(273.1) — —23⁄8
(60.3)3
(76.2)7⁄16
(11.1)5⁄8 x 3⁄4
(15.9) x (19.1)5⁄8 x 11⁄8
(15.9) x (28.6)
1601 – 2000 233⁄4
(95.3)53⁄4
(146.1)63⁄4
(171.5)91⁄4
(235.0)91⁄2
(241.3)103⁄4
(273.1) — —23⁄4
(69.9)31⁄2
(88.9)1⁄2
(12.7)5⁄8 x 3⁄4
(15.9) x (19.1)5⁄8 x 11⁄8
(15.9) x (28.6)
2001 – 2500 3 453⁄4
(146.1)63⁄4
(171.5)91⁄4
(235.0)91⁄2
(241.3)103⁄4
(273.1)15⁄8
(41.3)13⁄4
(44.5)31⁄2
(88.9)5
(127.0)3⁄4
(19.1)5⁄8 x 3⁄4
(15.9) x (19.1)5⁄8 x 11⁄8
(15.9) x (28.6)
2501 – 3000 3 453⁄4
(146.1)63⁄4
(171.5)91⁄4
(235.0)91⁄2
(241.3)103⁄4
(273.1)15⁄8
(41.3)13⁄4
(44.5)4
(101.6)5
(127.0)3⁄4
(19.1)5⁄8 x 3⁄4
(15.9) x (19.1)5⁄8 x 11⁄8
(15.9) x (28.6)
3001 – 4000 4 453⁄4
(146.1)63⁄4
(171.5)91⁄4
(235.0)91⁄2
(241.3)103⁄4
(273.1)13⁄4
(44.5)31⁄4
(82.6)43⁄4
(120.7)53⁄4
(146.1)
3⁄4(19.1)
5⁄8 x 13⁄8(15.9) x (34.9)
5⁄8 x 13⁄8(15.9) x (34.9)
Catalog 25-48.indd 27 5/30/07 6:18:54 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose FusesG
ener
al P
urpo
se F
uses
28 w w w . l i t t e l f u s e . c o m © 2005 Littelfuse • POWR-GARD™ Products Catalog
KLLU Class L Fuses
600 VAC • Time-Delay • 601 – 4000 Amperes
1000800600
400300
200
1008060
4030
20
1086
43
2
1.8.6
.4
.3
.2
.1.08.06
.04
.03
.02
.01
2000
3000
4000
6000
8000
1000
0
2000
0
3000
040
000
6000
080
000
1000
00
2000
00
3000
0040
0000
6000
0080
0000
1000
00080 100
200
300
400
600
800
100050
601A
800A
1200
A16
00A
2000
A30
00A
3500
A40
00A
TIM
E IN
SEC
ON
DS
CURRENT IN AMPERES SYMMETRICAL R.M.S. AMPERESAVAILABLE FAULT CURRENT
PEA
K LE
T-TH
RU IN
AM
PERE
S
800A1200A1600A2000A3000A4000A
10000000
1000000
100000
10000
1000
10
00
100
2000
00
1000
00
1000
0
Current-Limiting Effects of KLLU (600V) fuses
Short-Circuit Current*Apparent RMS Symmetrical Current for Various Fuse Ratings
800A 1200A 1600A 2000A 3000A 4000A
5,000 5,000 5,000 5,000 5,000 5,000 5,000
10,000 10,000 10,000 10,000 10,000 10,000 10,000
15,000 11,900 15,000 15,000 15,000 15,000 15,000
20,000 13,000 18,500 20,000 20,000 20,000 20,000
25,000 14,000 20,000 25,000 25,000 25,000 25,000
30,000 14,500 21,000 26,500 30,000 30,000 30,000
35,000 15,000 22,000 28,500 34,000 35,000 35,000
40,000 16,000 23,000 30,000 35,000 37,000 40,000
50,000 17,000 24,000 32,000 38,000 39,000 44,000
60,000 18,000 26,000 34,000 42,000 43,000 50,000
80,000 19,000 28,000 36,000 44,000 46,000 54,500
100,000 21,000 30,000 38,000 46,000 48,000 57,500
150,000 24,000 35,000 44,000 50,000 51,000 68,000
200,000 26,000 38,000 48,000 53,000 60,000 74,000
* Prospective RMS Symmetrical Amperes Short-Circuit CurrentNote: Data Derived from Peak Let-Thru Curves
Catalog 25-48.indd 28 5/30/07 6:18:55 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose Fuses
General Purpose Fuses
29w w w . l i t t e l f u s e . c o m© 2005 Littelfuse • POWR-GARD™ Products Catalog
Littelfuse FLNR_ID/FLSR_ID Indicator fuses provide blown fuse indication at a glance. The patented state-of-the-art solid state design provides maximum reliability and superior performance characteristics in a true dual-element design. The use of Indicator fuses reduces downtime and nuisance openings, increases safety, and can save thousands of dollars in lost production time.
Applications
Service entrance switchesSwitchboard main and feeder switchesMotor control center mains and motor branch circuitsIndividual fused combination motor controllersDistribution panelboardsIndustrial control panelsProtection of fully rated panelboards and loadcentersAll general purpose circuits
Features/Benefits
• Reduce Downtime — A glance at the indicating window of a FLNR_ID or FLSR_ID Indicator fuse pinpoints open fuses. If the indicating strip is black, the fuse has opened. It’s that simple.
• Reduce Nuisance Opening — FLNR_ID and FLSR_ID Indicator fuses have superior time-delay and cycling characteristics which can lengthen fuse life and decrease needless opening.
• Reduce Fuse Inventory — Because FLNR_ID and FLSR_ID Indicator fuses have superior performance characteristics, they can be used on a variety of ap pli ca tions, thus decreasing fuse inventory.
• Reduce Equipment Damage — FLNR_ID and FLSR_ID Indicator fuses have superior overload and short-circuit protection which can reduce equipment damage.
• Reduce Accidents — The FLNR_ID and FLSR_ID Indicator fuses improve safety by minimizing exposure to live circuits. Unlike other forms of blown fuse indication, it doesn’t matter if the power is on or off. No second guessing whether a light means a fuse is good or bad, and no current going across a blown fuse to power a lighted accessory.
FLNR_ID/FLSR_ID Indicator® Class RK5 Fuses
250/600 VAC • Dual-Element, Time Delay • 1/10 – 600 Amperes
Specifications
Voltage Ratings: AC: 250 Volts (FLNR_ID); 600 Volts (FLSR_ID) DC: 125 Volts (FLNR 1⁄10 – 30A); 125 Volts (FLNR_ID 35 – 600A); 300 Volts (FLSR_ID)Interrupting Ratings: AC: 200,000 amperes rms symmetrical 300,000 amperes rms sym met ri cal (Littelfuse self-certified) DC: 20,000 amperesAmpere Range: 1⁄10 – 600 amperesApprovals: Standard 248-12, Class RK5 UL Listed (File No: E81895) CSA Certified (File No: LR29862) MSHA 300 Volt Listing (FLSR_ID) QPL: Federal Specification WF-1814
Ampere Ratings
1⁄10** 6⁄10 18⁄10 4 8 30 80 2251⁄8 8⁄10 2 41⁄2 9 35 90 250
15⁄100 1 21⁄4 5 10 40 100 3002⁄10 11⁄8 21⁄2 56⁄10 12 45 110 3501⁄4 11⁄4 28⁄10 6 15 50 125 400
3⁄10 14⁄10 3 61⁄4 171⁄2 60 150 4504⁄10 11⁄2 32 ⁄10 7 20 70 175 5001⁄2 16⁄10 31⁄2 71⁄2 25 75* 200 600
*FLSR_ID only **FLNR onlyEx am ple part number (series & am per age): FLSR100IDNOTE: For 1⁄10 – 30 ampere 250 volt fuses, order non-indicating FLNR series fuses.NOTE: All FLNR_ID fuses rated 35 – 600A are Indicator fuses.NOTE: All FLSR_ID fuses rated 1 amp and above are Indicator fuses.
Recommended Fuse Blocks
LR250 series (for FLNR_ID series fuses)LR600 series (for FLSR_ID series fuses)Refer to Blocks & Holders section of this catalog for ad di tion al in for ma tion.
Catalog 25-48.indd 29 5/30/07 6:18:56 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose FusesG
ener
al P
urpo
se F
uses
30 w w w . l i t t e l f u s e . c o m © 2005 Littelfuse • POWR-GARD™ Products Catalog
FLNR_ID/FLSR_ID Indicator® Class RK5 Fuses
250/600 VAC • Dual-Element, Time Delay • 1/10 – 600 Amperes
TIM
E IN
SEC
ON
DS
CURRENT IN AMPERES
FLSR_ID
.01
.02
.03
.04
.06
.08.1
.2
.3
.4
.6
.81
23468
10
2030406080
100
200300400600800
1000
10864321 1000080006000400030002000
1000800600400300200
1008060403020
1A 1.25
A1.
6A2A 2.
5A3A 4A 6A 10
A15
A20
A25
A30
A
1000800600
400300
200
1008060
403020
1086
43
2
1.8.6
.4
.3
.2
.1.08.06
.04
.03
.02
.01
2 3 4 6 8 10 20 30 40 60 80 100
200
300
400
600
800
1000.1 .2 .3 .4 .6 .8 1
2/10
A1/
4A3/
10A
4/10
A1/
2A6/
10A
8/10
A1A 1
1/4A
1 4/
10A
2A 2 1/
2A4
1/2A
5A 7A 7 1/
2A9A
FLNR
TIM
E IN
SEC
ON
DS
CURRENT IN AMPERES
AF
EC
DG B
A
J
K
H
B
C
F D G
70-600AFIG. 1 FIG. 2
E
Amperes Refer ToFig. No. SeriesDimensions In Inches (mm in parentheses)
A B C D E F G H J K
1/10 – 30 1FLNR 2 (50.8) 1⁄2 (12.7) 1⁄2 (12.7) 9⁄16 (14.3) 5⁄64 (2.0) 5⁄32 (4.0) 3⁄8 (9.5) — — —
FLSR_ID 5 (127.0) 3⁄4 (19.1) 5⁄8 (15.9) 13⁄16 (20.6) 3⁄32 (2.4) 3⁄16 (4.8) 5⁄8 (15.9) — — —
35 – 60 1FLNR_ID 3 (76.2) 3⁄4 (19.1) 5⁄8 (15.9) 13⁄16 (20.6) 3⁄32 (2.4) 3⁄16 (4.8) 5⁄8 (15.9) — — —
FLSR_ID 51⁄2 (139.7) 1 (25.4) 5⁄8 (15.9) 11⁄16 (27.0) 3⁄32 (2.4) 1⁄4 (6.4) 7⁄8 (22.2) — — —
70 – 100 2FLNR_ID 57⁄8 (149.2) 1 (25.4) 11⁄16 (27.0) 11⁄16 (27.0) 1⁄8 (3.2) 3⁄4 (19.1) 11⁄4 (31.8) 1⁄4 (6.4) 9⁄32 (7.1) 1⁄2 (12.7)
FLSR_ID 77⁄8 (200.0) 11⁄4 (31.8) 11⁄16 (27.0) 15⁄16 (33.3) 1⁄8 (3.2) 3⁄4 (19.1) 11⁄2 (38.1) 1⁄4 (6.4) 9⁄32 (7.1) 1⁄2 (12.7)
110 – 200 2FLNR_ID 71⁄8 (181.0) 11⁄2 (38.1) 115⁄32 (37.3) 119⁄32 (40.5) 3⁄16 (4.8) 11⁄8 (28.6) 127⁄32 (46.8) 7⁄16 (11.1) 9⁄32 (7.1) 11⁄16 (17.5)
FLSR_ID 9 5⁄8 (244.5) 13⁄4 (44.5) 115⁄32 (37.3) 127⁄32 (46.8) 3⁄16 (4.8) 11⁄8 (28.6) 23⁄32 (53.2) 7⁄16 (11.1) 9⁄32 (7.1) 11⁄16 (17.5)
225 – 400 2FLNR_ID 85⁄8 (219.1) 2 (50.8) 115⁄16 (49.2) 23⁄32 (53.2) 1⁄4 (6.4) 15⁄8 (41.3) 211⁄32 (59.5) 5⁄8 (15.9) 13⁄32 (10.3) 15⁄16 (23.8)
FLSR_ID 115⁄8 (295.3) 21⁄2 (63.5) 2 (50.8) 219⁄32 (65.9) 1⁄4 (6.4) 15⁄8 (41.3) 227⁄32 (72.2) 5⁄8 (15.9) 13⁄32 (10.3) 15⁄16 (23.8)
450 – 600 2FLNR_ID 103⁄8 (263.5) 21⁄2 (63.5) 2 3⁄8 (60.3) 219⁄32 (65.9) 1⁄4 (6.4) 2 (50.8) 227⁄32 (72.2) 3⁄4 (19.1) 17⁄32 (13.5) 11⁄8 (28.6)
FLSR_ID 133⁄8 (339.7) 3 (76.2) 213⁄32 (61.1) 33⁄32 (78.6) 1⁄4 (6.4) 2 (50.8) 311⁄32 (84.9) 3⁄4 (19.1) 17⁄32 (13.5) 11⁄8 (28.6)
For additional application information request Product Bulletin EL-4
Catalog 25-48.indd 30 5/30/07 6:19:03 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose Fuses
General Purpose Fuses
31w w w . l i t t e l f u s e . c o m© 2005 Littelfuse • POWR-GARD™ Products Catalog
Current-Limiting Effects of FLNR_ID (250V) fuses
Short-Circuit Current*Apparent RMS Symmetrical Current for Various Fuse Ratings
30A 60A 100A 200A 400A 600A
5,000 1,400 2,100 3,100 5,000 5,000 5,000
10,000 1,550 2,500 3,900 6,500 9,500 10,000
15,000 2,000 3,150 4,400 7,250 10,500 14,000
20,000 2,250 3,400 5,000 8,250 12,000 16,000
25,000 2,400 3,750 5,250 9,000 12,500 16,500
30,000 2,550 4,100 5,600 9,500 13,500 18,000
35,000 2,650 4,300 5,800 9,750 14,000 19,000
40,000 2,800 4,400 6,250 10,250 15,000 20,000
50,000 3,000 5,000 6,500 10,500 16,000 21,000
60,000 3,200 5,250 7,000 11,500 17,000 23,000
80,000 3,400 5,750 7,500 12,500 19,000 25,500
100,000 3,850 6,000 8,000 13,500 21,000 27,500
150,000 4,100 7,000 9,000 15,200 24,000 31,500
200,000 4,300 7,500 9,750 16,500 26,000 34,000
* Prospective RMS Symmetrical Amperes Short-Circuit CurrentNote: Data Derived from Peak Let-Thru Curves
Current-Limiting Effects of FLSR_ID (600V) fuses
Short-Circuit Current*Apparent RMS Symmetrical Current for Various Fuse Ratings
30A 60A 100A 200A 400A 600A
5,000 1,250 2,100 3,200 5,000 5,000 5,000
10,000 1,600 2,850 4,300 7,250 10,000 10,000
15,000 1,800 3,400 5,000 8,500 13,500 15,000
20,000 2,250 3,800 5,500 9,500 15,750 19,000
25,000 2,450 4,100 5,700 10,250 17,000 21,000
30,000 2,700 4,500 6,400 10,750 18,000 23,000
35,000 2,900 4,800 6,700 11,500 19,000 24,250
40,000 3,000 5,000 7,250 12,000 19,500 27,000
50,000 3,400 5,250 7,750 13,000 21,000 29,000
60,000 3,600 5,750 8,100 14,000 22,000 30,500
80,000 3,900 6,250 9,000 15,000 24,000 33,000
100,000 4,300 6,750 9,750 16,500 26,000 35,000
150,000 4,500 7,600 11,100 19,000 28,000 38,000
200,000 4,600 8,400 12,250 21,500 30,000 40,000
* Prospective RMS Symmetrical Amperes Short-Circuit CurrentNote: Data Derived from Peak Let-Thru Curves
FLNR_ID/FLSR_ID Indicator® Class RK5 Fuses
250/600 VAC • Dual-Element, Time Delay • 1/10 – 600 Amperes
Catalog 25-48.indd 31 5/30/07 6:19:05 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose FusesG
ener
al P
urpo
se F
uses
32 w w w . l i t t e l f u s e . c o m © 2005 Littelfuse • POWR-GARD™ Products Catalog
FLNR_ID/FLSR_ID Indicator® Class RK5 Fuses
250/600 VAC • Dual-Element, Time Delay • 1/10 – 600 Amperes
600A400A200A100A60A30A15A
5 10080604030201086 10000080000
60000
40000
30000
20000
100008000
6000
4000
3000
2000
1000800
600
400
300
200
.01
.02
.03
.04
.05
.06
.08.1
.2
.3
.4
.6
.81
2
3
4
6
810
20
30
40
60
80100
200
300
400
600
8001000
CURRENT IN AMPERES
TIM
E IN
SEC
ON
DS
FLSR_ID600A400A200A100A60A
50 1000800
600
400
300
200
1008060 1000000800000
600000
400000
300000
200000
10000080000
60000
40000
30000
20000
100008000
6000
4000
3000
2000
.01
.02
.03
.04
.06
.08.1
.2
.3
.4
.6
.81
2
3
4
6
810
20
30
40
60
80100
200
300
400
600
8001000
TIM
E IN
SEC
ON
DS
CURRENT IN AMPERES
FLNR_ID
60A
100A
200A
400A
600A
1000000
800000
600000
400000
300000
200000
100000
80000
60000
40000
30000
20000
10000
8000
6000
4000
3000
2000
1000
800
600
400
300
200
100 1000
800
600
400
300
200
100
200000
100000
80000
60000
40000
30000
20000
10000
8000
6000
4000
3000
2000
FLNR_ID
PEA
K L
ET -
THRU
IN
AM
PERE
S
AVAILABLE FAULT CURRENTSYMMETRICAL R.M.S. AMPERES
600A
400A
200A
100A
60A
30A
15A
1000000
800000
600000
400000
300000
200000
100000
80000
6000050000
40000
30000
20000
10000
8000
60005000
4000
3000
2000
1000
800
600
400
300
200
100 1000
800
600
400
300
200
100
200000
100000
80000
60000
40000
30000
20000
10000
8000
6000
4000
3000
2000
PEA
K L
ET -
THRU
IN
AM
PERE
S
AVAILABLE FAULT CURRENTSYMMETRICAL R. M. S. AMPERES
FLSR_ID
Catalog 25-48.indd 32 5/30/07 6:19:06 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose Fuses
General Purpose Fuses
33w w w . l i t t e l f u s e . c o m© 2005 Littelfuse • POWR-GARD™ Products Catalog
Littelfuse FLNR/FLSR series fuses have been the superior UL Class RK5 dual-element time-delay fuses, and are the most widely used class of fuses. FLNR/FLSR series fuses provide excellent protection for all types of circuits especially those containing motors. However, users and specifiers should consider the significant benefits offered by Indicator fuses. Complete information on these fuses may be found earlier in this section.
Applications
Service entrance switchesSwitchboard main and feeder switchesMotor control center mains and motor branch circuitsIndividual fused combination motor controllersDistribution panelboardsIndustrial control panelsProtection of fully rated panelboards and loadcentersAll general purpose circuits
Safety
• 200,000 A.I.R. — Reliable interruption of all overcurrents up to 200,000 amperes.
• Faster acting short-circuit protection than any non-current-limiting mechanical protective device.
Reliability
• Accurate and reliable — Automated, precision manufactured and assembled parts ensure accurate, consistent response to overloads and short-circuits.
Longer Equipment Life
• Reduced damage to equipment caused by heating and magnetic forces of short-circuits.
• Equipment runs cooler with low-resistance dual-element fuses.
FLNR/FLSR Class RK5 Fuses
250/600 VAC • Dual-Element, Time-Delay • 1/10 – 600 Amperes
Specifications
Voltage Ratings: AC: 250 Volts (FLNR) 600 Volts (FLSR) DC: 125 Volts (FLNR) 300 Volts (FLSR)Interrupting Ratings: AC: 200,000 amperes rms symmetrical DC: 20,000 amperesAmpere Range: 1⁄10 – 600 amperesApprovals: Standard 248-12, Class RK5 UL Listed (File No: E81895) CSA Certified (File No: LR29862) MSHA 300 Volt Listing (FLSR) QPL: Federal Specification WF-1814
Dimensions
Refer to FLNR_ID series for FLNR dimensions and FLSR_ID series for FLSR dimensions.
Ampere Ratings
1⁄10 6⁄10 18⁄10 4 8 30 80 2251⁄8 8⁄10 2 41⁄2 9 35 90 250
15⁄100 1 21⁄4 5 10 40 100 3002⁄10 11⁄8 21⁄2 56⁄10 12 45 110 3501⁄4 11⁄4 28⁄10 6 15 50 125 400
3⁄10** 14⁄10 3 61⁄4 171⁄2 60 150 4504⁄10 11⁄2 32 ⁄10 7 20 70 175 5001⁄2 16⁄10 31⁄2 71⁄2 25 75 200 600
**FLNR only, Ex am ple part number (series & am per age): FLSR100
Recommended Fuse Blocks
LR250 series (for FLNR series fuses)LR600 series (for FLSR series fuses)Refer to Blocks & Holders section of this catalog for ad di tion al in for ma tion.
Catalog 25-48.indd 33 5/30/07 6:19:07 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose FusesG
ener
al P
urpo
se F
uses
34 w w w . l i t t e l f u s e . c o m © 2005 Littelfuse • POWR-GARD™ Products Catalog
KLNR/KLSR Class RK1 Fuses
250/600 VAC • Fast Acting • 1 – 600 Amperes
SpecificationsVoltage Ratings: AC: 250 Volts (KLNR); 600 Volts (KLSR) DC: 125 Volts (1 – 600A KLNR); 250 Volts (1 – 30A KLSR); 300 Volts (35 – 600A KLSR). In ter rupt ing Ratings: AC: 200,000 amperes rms sym met ri cal DC: 20,000 amperesAmpere Range: 1 – 600 amperes.Approvals: AC: Standard 248-12, Class RK1 UL Listed (File No: E81895) CSA Certified (File No: LR29862) DC: Littelfuse self-certified
Ampere Ratings1 10 40 100 2502 12 45 110 3003 15 50 125 3504 20 60 150 4005 25 70 175 4506 30 80 200 5008 35 90 225 600
Example part number (series & amperage): KLNR 200
Recommended Fuse BlocksLR250 series (for KLNR series fuses)LR600 series (for KLSR series fuses)Refer to the Blocks & Holders section of this catalog for additional in for ma tion.
KLNR/KLSR series RK1 fuses were the earliest type of current-limiting fuses developed. Their single-element, silver link design enables them to provide fast-acting overload and short-circuit pro tec tion. When used to protect inductive loads such as motors, solenoids, and trans form ers, KLNR/KLSR series fuses must be greatly oversized to prevent opening the fuses on harmless in-rush currents. In such applications, KLNR/KLSR series fuses may only provide short-circuit pro tec tion.
We recommend using POWR-PRO® LLNRK/LLSRK series Class RK1, dual-element, time-de lay fuses in all new applications re quir ing the current-limiting ability of UL Class RK1 fuses. POWR-PRO LLNRK/LLSRK series fuses are also recommended in existing applications where fast-acting RK1 or RK5 fuses have been open ing on harmless system surges such as motor start ing currents.
ApplicationsResistance heatersLighting circuitsNon-inductive loadsMolded case circuit breaker load centers and panelboards have
increased in ter rupt ing ratings when series rated with Littelfuse KLNR/KLSR Class RK1 fuses. Refer to panelboard manufacturer’s literature for UL Listed com bi na tion of fuses and panelboards. Series ratings up to 200,000 amperes are available.
Safety• 200,000 A.I.R. — Reliable interruption of all overcurrents up to
200,000 amperes.• Extremely current-limiting — Stops dam ag ing short-circuit current
faster than any mechanical pro tec tive device.• Fast-acting — Provides fast acting protection to equipment such
as variable speed drives, rectifiers and other equip ment containing surge-sensitive com po nents.
Longer Equipment Life• Current-limiting design reduces damage to equip ment caused by
heating and magnetic effects of short-circuit currents.
Economical• Extremely current-limiting — often permits use of readily available,
less costly equipment.• Used as input or output fuses for surge sensitive com po nents such
as variable speed drives and rectifiers, fast acting KLNR/KLSR fuses may prevent opening of ex pen sive semiconductor fuses protecting individual components.
Easy To Use• 200,000 A.I.R. rating min i miz es need for short-circuit calculations.
Dimensions• Refer to FLNR_ID for KLNR dimensions and FLSR_ID for KLSR
dimensions.
Catalog 25-48.indd 34 5/30/07 6:19:10 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose Fuses
General Purpose Fuses
35w w w . l i t t e l f u s e . c o m© 2005 Littelfuse • POWR-GARD™ Products Catalog
KLNR/KLSR Class RK1 Fuses
250/600 VAC • Fast Acting • 1 – 600 Amperes
1000800600
400300
200
1008060
4030
20
1086
43
2
1.8.6
.4
.3
.2
.1.08.06
.04
.03
.02
.01
200
300
400
600
800
1000
2000
3000
4000
6000
8000
1000
0
2000
0
3000
040
000
6000
080
000
1000
0010 20 30 40 60 80 100
30A
60A
100A
200A
400A
600A
TIM
E IN
SEC
ON
DS
CURRENT IN AMPERES
1000800600
400300
200
1008060
4030
20
1086
43
2
1.8.6
.4
.3
.2
.1.08.06
.04
.03
.02
.01
200
300
400
600
800
1000
2000
3000
4000
6000
8000
1000
0
2000
0
3000
040
000
6000
080
000
1000
0010 20 30 40 60 80 1005
30A
60A
100A
200A
400A
600A
TIM
E IN
SEC
ON
DS
CURRENT IN AMPERES
2000
3000
4000
6000
8000
1000
0
2000
0
3000
040
000
6000
080
000
1000
00
2000
00100
200
300
400
600
800
1000
100
200
300400
600800
1000
2000
30004000
60008000
10000
20000
3000040000
6000080000
100000
200000
300000400000
600000800000
1000000
600A400A
200A
100A60A
30A
PEA
K LE
T-TH
RU IN
AM
PERE
S
AVAILABLE FAULT CURRENTSYMMETRICAL R. M. S. AMPERES
2000
3000
4000
6000
8000
1000
0
2000
0
3000
040
000
6000
080
000
1000
00
2000
00100
200
300
400
600
800
1000
100
200
300400
600800
1000
2000
30004000
60008000
10000
20000
3000040000
6000080000
100000
200000
300000400000
600000800000
1000000
600A400A
200A
100A
60A
30A
PEA
K LE
T-TH
RU IN
AM
PERE
S
AVAILABLE FAULT CURRENTSYMMETRICAL R. M. S. AMPERES
KLSRKLNR
KLSRKLNR
Catalog 25-48.indd 35 5/30/07 6:19:13 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose FusesG
ener
al P
urpo
se F
uses
36 w w w . l i t t e l f u s e . c o m © 2005 Littelfuse • POWR-GARD™ Products Catalog
NLN/NLS Class K5 Fuses
250/600 VAC • “One-Time” • 1 – 600 Amperes
NLN and NLS series fuses provide low cost protection for general purpose feeder and branch circuits when avail able short-circuit currents are less than 50,000 amperes. They replace all Class H fuses which have only a 10,000 ampere interrupting rating. They are suitable for use in many res i-den tial and smaller commercial and industrial applications.
NLKP series fuses are Canadian “Code” fuses specifically de signed to meet Canadian Electrical Code Type P fuse re quire ments for residential use. They have a 10,000 ampere interrupting rating.
However, to obtain the added benefits of time-delay, cur rent-limitation, and higher interrupting rating, consider the use of POWR-PRO® FLNR_ID and FLSR_ID Indicator® fuses for circuits up to 600 volts. The user gets all the benefits of time-delay RK5 fuses plus the added benefits of an indicating fuse that shows when it has opened. Complete information on these fuses may be found in the POWR-PRO fuse section of this catalog. For circuits up to 250 volts, see FLNR fuses in this section of the catalog.
Applications
General purpose residential and commercial circuits with little or no motor load.
Resistive heating loads.
Economical
• For use in applications where lowest initial cost is the major consideration.
Safety
• 50,000 A.I.R., Class K5 — Adequate in ter rupt ing capacity for residences and many smaller facilities.
NOTE: NLKP series fuses have limited interrupting rating and should be used only where available short-circuit current is known to be less than the fuse interrupting rating. Where available fault current is unknown, where it exceeds NLN/NLS interrupting rating, or where it may increase in the future, 200,000 ampere interrupting rating Littelfuse POWR-PRO FLNR_ID/FLSR_ID Indicator fuses and FLNR/FLSR series fuses provide superior pro tec tion for all motor and general purpose circuits con tain ing inductive loads.
SpecificationsVoltage Ratings: AC: 250 Volts (NLN, NLKP) 600 Volts (NLS) DC: 250 Volts (NLN) 400 Volts (NLS 35 – 60A) 500 Volts (NLS 8 – 30A) (NLS 225 – 600A) 600 Volts (NLS 1 – 7A) (NLS 70 – 200A)Interrupting Ratings: AC: 50,000 amperes rms sym met ri cal (NLN/NLS) 10,000 amperes (NLKP) DC: 20,000 amperes (NLN/NLS 1 – 60A) 50,000 amperes (NLN/NLS 70 – 600A)Ampere Range: 1– 600 amperes (NLN/NLS) 15 – 60 amperes (NLKP)Ap prov als: NLN/NLS: Standard 248-9, Class K5 UL Listed (File No: E81895) CSA Certified (File No: LR29862)** **Excludes NLN 15-60A NLKP: Standard 248-6, Class H UL Listed (File No: E81895) CSA Certified (File No: LR29865) Meets CSA “Type P” requirements
Ampere Ratings
1 7 *25 *60 125 3002 8 *30 70 150 3503 10 *35 80 175 4004 12 *40 90 200 4505 *15 *45 100 225 5006 *20 *50 110 250 600
* NLKP series avail able only in those amperages preceded by an asterisk.Example part number (series & amperage): NLS 125
Recommended Fuse Blocks
LH250 series (for NLN and NLKP series fuses)LH600 series (for NLS series fuses)Refer to the Blocks & Holders section of this catalog for additional in for ma tion.
Catalog 25-48.indd 36 5/30/07 6:19:13 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose Fuses
General Purpose Fuses
37w w w . l i t t e l f u s e . c o m© 2005 Littelfuse • POWR-GARD™ Products Catalog
NLN/NLS Class K5 Fuses
250/600 VAC • “One-Time” • 1 – 600 Amperes
CURRENT IN AMPERES
TIM
E IN
SEC
ON
DS
NLS60
0A
.01
.02
.03
.04
.05
.06
.08.1
.2
.3
.4
.6
.81
2
3
4
6
810
20
30
40
60
80100
200
300
400
600
8001000
5 10080604030201086 10000080000
60000
40000
30000
20000
100008000
6000
4000
3000
2000
1000800
600
400
300
200
400A
200A
100A
60A
30A
25A
20A
15A
TIM
E IN
SEC
ON
DS
CURRENT IN AMPERES
NLN
.01
.02
.03
.04
.06
.08.1
.2
.3
.4
.6
.81
2
3
4
6
810
20
30
40
60
80100
200
300
400
600
8001000
5 10080604030201086 10000080000
60000
40000
30000
20000
100008000
6000
4000
3000
2000
1000800
600
400
300
200
200A
100A
400A
600A
60A
30A
25A
20A
15A
A
C CDA E
BB F D G
FIG. 1 FIG. 2
Amperes Refer toFig. No. SeriesDimensions In Inches (mm in parentheses)
A B C D E F G
1 – 30 1NLNNLKP 2 (50.8)
1⁄2 (12.7) 1⁄2 (12.7) 9⁄16 (14.3) — — —
NLS 5 (127.0) 3⁄4 (19.1) 5⁄8 (15.9) 13⁄16 (20.6) — — —
35 – 60 1NLNNLKP 3 (76.2)
3⁄4 (19.1) 5⁄8 (15.9) 13⁄16 (20.6) — — —
NLS 51⁄2 (139.7) 1 (25.4) 5⁄8 (15.9) 11⁄16 (27.0) — — —
70 – 100 2NLN 57⁄8 (149.2) 1 (25.4) 1 (25.4) 11⁄16 (27.0) 1⁄8 (3.2) 3⁄4 (19.1) 15⁄16 (33.3)
NLS 77⁄8 (200.0) 11⁄4 (31.8) 1 (25.4) 15⁄16 (33.3) 1⁄8 (3.2) 3⁄4 (19.1) 19⁄16 (39.7)
110 – 200 2NLN 71⁄8 (181.0) 11⁄2 (38.1) 13⁄8 (34.9) 19⁄16 (39.7) 3⁄16 (4.8) 11⁄8 (28.6) 17⁄8 (47.6)
NLS 9 5⁄8 (244.5) 13⁄4 (44.5) 13⁄8 (34.9) 127⁄32 (46.8) 3⁄16 (4.8) 11⁄8 (28.6) 23⁄32 (53.2)
225 – 400 2NLN 8 5⁄8 (219.1) 2 (50.8) 17⁄8 (47.6) 23⁄32 (53.2) 1⁄4 (6.4) 15⁄8 (41.3) 213⁄32 (61.1)
NLS 115⁄8 (295.3) 21⁄2 (63.5) 17⁄8 (47.6) 219⁄32 (65.9) 1⁄4 (6.4) 15⁄8 (41.3) 27⁄8 (73.0)
450 – 600 2NLN 10 3⁄8 (263.5) 21⁄2 (63.5) 21⁄4 (57.2) 219⁄32 (65.9) 1⁄4 (6.4) 2 (50.8) 27⁄8 (73.0)
NLS 13 3⁄8 (339.7) 3 (76.2) 21⁄4 (57.2) 33⁄32 (78.6) 1⁄4 (6.4) 2 (50.8) 37⁄16 (87.3)
Catalog 25-48.indd 37 5/30/07 6:19:16 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose FusesG
ener
al P
urpo
se F
uses
38 w w w . l i t t e l f u s e . c o m © 2005 Littelfuse • POWR-GARD™ Products Catalog
RLN/RLS Class H Fuses
250/600 VAC • Renewable • 1 – 600 Amperes
Littelfuse RLN/RLS series renewable fuses are a quality product that have traditionally been used to provide low cost protection of general purpose feeder and branch circuits where available short-circuit currents do not exceed 10,000 amperes. However, increased levels of available fault current and the possibility that renewable fuses may be im prop erly renewed is a potential safety hazard. In addition, escalating labor costs
and increasing automation, which makes down time very expensive, have greatly re duced or eliminated the cost savings attributed to renewable fuses.
We recommend the use of POWR-PRO® FLSR_ID series Indicator® fuses for circuits between 250 and 600 volts and FLNR_ID series for circuits 250 volts and below. Complete information on POWR-PRO
Indicator fuses may be found in the POWR-PRO fuse section of this catalog. FLNR fuses are in this section of the catalog.
Cost Considerations
• When comparing the cost of using re new able fuses with the cost of other fuses, the labor required for replacing links and the cost of ad di-tion al downtime should be included.
Cautions
• Renewable fuses should only be used where short-circuit currents are known to be less than 10,000 amperes, and where correct replacement of open links is assured.
• After disassembly of fuse, examine carefully. Discard any fuses which show evidence of weak ened tube or damaged components.
• Remove all link residue from fuse tube.• Carefully clean all contact surfaces, and remove metal spatter from
all surfaces.• Install the proper rated fuse link and tighten all con nec tions
securely.• Vi su al ly ex am ine fuses for cor rect align ment of blades.
Dimensions
• For dimensions, please refer to NLN series for RLN di men sions and NLS series for RLS dimensions.
Specifications
Voltage Ratings: AC: 250 Volts (RLN); 600 Volts (RLS)In ter rupt ing Ratings: AC: 10,000 am peres rms sym met ri calAmpere Range: 1 – 600 amperesAp prov als: Standard 248-6, Class H UL Listed (File No: E81895) CSA Certified (File No: LR29862)FUSE LINKS: To order, specify LKN (250V) or LKS (600V) plus ampere rating.
Ampere Ratings
1 6 20 45 90 175 350*2 8** 25 50 100 200 400*3 10 30 60 110 225* 450*4 12** 35 70 125 250* 500*5 15 40 80 150 300* 600*
*These ampere ratings require two links per fuse.**RLS Only.
Example part number (series & amperage): RLN 20
Recommended Fuse Blocks
LH250 series (for RLN series fuses)LH600 series (for RLS series fuses)Refer to the Blocks & Holders section of this catalog for additional in for ma tion.
Catalog 25-48.indd 38 5/30/07 6:19:18 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose Fuses
General Purpose Fuses
39w w w . l i t t e l f u s e . c o m© 2005 Littelfuse • POWR-GARD™ Products Catalog
JLS Class J Fuses
600 VAC • Fast Acting • 1 – 600 Amperes
Specifications
Voltage Ratings: 600 Volts ACInterrupting Ratings: 200,000 amperes rms symmetricalAmpere Range: 1 – 600 amperesApprovals: Standard 248-8, Class J UL Listed (File No: E81895) CSA Certified (File No: LR29862) QPL: Federal Specification No: WF-1814
Ampere Ratings
1 25 60 125 3003 30 70 150 3506 35 80 175 40010 40 90 200 45015 45 100 225 50020 50 110 250 600
Example part number (series & amperage): JLS 110
Recommended Fuse Blocks
LPSJ series, LJ600 series Refer to the Blocks and Holders section of this catalog for additional in for ma tion.
JLS series fuses provide space saving, fast acting overload and short-circuit protection for non-inductive loads. When used for motors or other inductive loads, the ampere rating of JLS series fuses must be increased to prevent nuisance opening on in-rush currents. In such applications, JLS fuses may provide only short-circuit protection. Con sid er using Littelfuse POWR-PRO® JTD or JTD_ID series time-delay fuses in such circuits.
Applications
General purpose circuits with little or no motor load.Resistive loads, such as resistance electric heat.Loads requiring fast acting overload protection, such as equipment
containing solid-state devices.
Space Saving
• JLS fuse characteristics are similar to KLNR/KLSR fast acting Class RK1 fuses, but dimensionally are much smaller.
Safety
• 200,000 A.I.R. — Reliable interruption of all overcurrents up to 200,000 amperes.
• Extremely current-limiting — Stops dam ag ing short-circuit current faster than any mechanical pro tec tive device.
• Fast acting — Provides fast acting protection to equipment such as variable speed drives, rectifiers and other equip ment containing surge sensitive com po nents.
Longer Equipment Life
• Current-limiting design reduces damage to equip ment caused by heating and magnetic effects of short-circuit currents.
Economical
• Extremely current-limiting design often permits use of readily available, less costly equipment.
• Manufacturers of equipment containing dual voltage devices can simplify manufacturing and reduce inventory by stan dard iz ing on 600 volt JLS fuses and Class J fuse blocks for all AC voltage ratings.
Easy to use
• 200,000 A.I.R. rating minimizes need for short-circuit cal cu la tions.
NOTE: Littelfuse JLS fuses are not time-delay fuses. For ap pli ca tions where short-duration surg es and spikes may cause nuisance fuse opening, consider the use of Littelfuse POWR-PRO JTD or JTD_ID series time-delay fuses.
Catalog 25-48.indd 39 5/30/07 6:19:20 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose FusesG
ener
al P
urpo
se F
uses
40 w w w . l i t t e l f u s e . c o m © 2005 Littelfuse • POWR-GARD™ Products Catalog
JLS Class J Fuses
600 VAC • Fast Acting • 1 — 600 Amperes
1000800600
400300
200
1008060
4030
20
1086
43
2
1.8.6
.4
.3
.2
.1.08.06
.04
.03
.02
.01
200
300
400
600
800
1000
2000
3000
4000
6000
8000
1000
0
2000
0
3000
040
000
6000
080
000
1000
008 10 20 30 40 60 80 1005
30A
60A
100A
200A
400A
600A
TIM
E IN
SEC
ON
DS
CURRENT IN AMPERES
A
C
DG F
EHA
BCD
Fig. 1 Fig. 2
2000
3000
4000
6000
8000
1000
0
2000
0
3000
040
000
6000
080
000
1000
00
2000
00100
200
300
400
600
800
1000
100
200
300400
600800
1000
2000
30004000
60008000
10000
20000
3000040000
6000080000
100000
200000
300000400000
600000800000
1000000
600A
400A
200A
100A60A
30A
PEA
K LE
T-TH
RU IN
AM
PERE
S
AVAILABLE FAULT CURRENTSYMMETRICAL R. M. S. AMPERES
Amperes Refer to Fig. No.
Dimensions In Inches (mm in parentheses)
A B C D E F G H
1 – 30 1 21⁄4 (57.2) — 1⁄2 (12.7) 13⁄16 (20.6) — — — —
35 – 60 1 23⁄8 (60.3) — 5⁄8 (15.9) 11⁄16 (27.0) — — — —
70 – 100 2 25⁄8 (66.7) 317⁄32 (89.7) 323⁄32 (94.5) 45⁄8 (117.5) 1 (25.4) 3⁄4 (19.1) 9⁄32 (7.1) 1⁄8 (3.2)
110 – 200 2 3 (76.2) 49⁄32 (108.7) 415⁄32 (113.5) 5 3⁄4 (146.1) 11⁄2 (38.1) 11⁄8 (28.6) 9⁄32 (7.1) 3⁄16 (4.8)
225 – 400 2 33⁄8 (85.7) 51⁄8 (130.2) 53⁄8 (136.5) 71⁄8 (181.0) 2 (50.8) 15⁄8 (41.3) 13⁄32 (10.3) 1⁄4 (6.4)
450 – 600 2 33⁄4 (95.3) 527⁄32 (148.4) 65⁄32 (156.4) 8 (203.2) 21⁄2 (63.5) 2 (50.8) 17⁄32 (13.5) 3⁄8 (9.5)
Catalog 25-48.indd 40 5/30/07 6:19:22 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose Fuses
General Purpose Fuses
41w w w . l i t t e l f u s e . c o m© 2005 Littelfuse • POWR-GARD™ Products Catalog
JLLN/JLLS POWR-T™ Class T Fuses
300/600 VAC • Fast-Acting • 1 – 1200 Amperes
Specifications
Voltage Ratings: AC: 300 Volts (JLLN); 600 Volts (JLLS) DC: 125 Volts (JLLN 1 – 30A) 160 Volts (JLLN 35 – 60A) 125 Volts (JLLN 110 – 1200A) 300 Volts (JLLS)Interrupting Ratings: AC: 200,000 amperes rms symmetrical DC: 20,000 amperes (JLLN 110 – 1200A) (JLLS 1 – 1200A)Ampere Range: 1– 1200 amperesApprovals: AC: Standard 248-15, Class T UL Listed (File No: E81895): JLLN/JLLS (1 – 800A) UL Recognized (File No: E71611): JLLS (900 – 1200A) CSA Certified (File No: LR29862): JLLN/JLLS (1 – 600A) DC: UL Listed (File No: E81895): JLLN (110 – 1200A) Littelfuse self-certified: JLLN 1-60A JLLS (1 – 1200A)
Ampere Ratings
1 30 90 250 8002 35 100 300 900*3 40 110 350 10006 45 125 400 110010 50 150 450 120015 60 175 50020 70 200 60025 80 225 700
* JLLS onlyExample part number (series & amperage): JLLS 100Note: Contact the factory for RoHS compliant Class T fuses.
Recommended Fuse Blocks
LT300 series (for JLLN series fuses)LT600 series (for JLLS series fuses)LSCR002 (for JLLN/JLLS 700-1200A fuses)Refer to the Blocks and Holders section of this catalog for additional in for ma tion.
Space saving POWR-T fuses are the most compact fuses available in ratings above 30 amperes — less than one-third the size of comparable Class R fuses. When rated in ac cor dance with the NEC®, POWR-T fuses provide fast acting overload and short-circuit protection for non-inductive circuits and equipment. Used in inductive circuits, the ampere rating of POWR-T fuses must be increased to prevent opening on in-rush currents. In such instances, POWR-T fuses may provide only short-circuit protection.
Applications
Littelfuse Class T fuses can be used in applications that require fast-acting protection, such as equipment containing variable speed drives, rectifiers, and other surge-sensitive components. Main switches containing Class T fuses may be used to provide protection to individual electric services and meter stacks. Molded case circuit breaker load centers and Panelboards also will have increased interrupting ratings when “series rated” with Class T fuses.
Features/Benefits
Space-Saving – Switch enclosures, fuse pullouts, and other equipment using Class T fuses are usually more compact. Typical three-pole Class T fuse blocks require less than 50% of the panel space required by similar Class R blocks.
Longer Equipment Life and Increased Safety – Class T fuses provide fast, reliable protection against overcurrents up to 200,000 amperes. Extremely current-limiting design minimizes the damaging heating and magnetic effects caused by short-circuit currents.
Optional Mounting Types – In addition to the Class T dimensions, Littelfuse offers select ratings with PC board mounting tabs for specialty applications. PC board mount versions are UL Recognized. Contact the factory for more information.
NOTE: JLLN Class T 300 volt fuses are UL Listed for circuits not exceeding 300 volts to ground. However, since UL does not include testing 300 volt Class T fuses on 277/480 volt three-phase bolted faults, Littelfuse does not rec om mend using 300 volt Class T fuses where phase-to-phase voltage exceeds 300 volts.
Catalog 25-48.indd 41 5/30/07 6:19:23 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose FusesG
ener
al P
urpo
se F
uses
42 w w w . l i t t e l f u s e . c o m © 2005 Littelfuse • POWR-GARD™ Products Catalog
JLLN/JLLS POWR-T™ Class T Fuses
300/600 VAC • Fast Acting • 1 – 1200 Amperes
B
CA
F
D F
EA
B
C
D
G
A
C
D
Fig. 1 Fig. 2 Fig. 3
Amperes Refer toFig. No. SeriesDimensions in Inches (mm in parentheses)
A B C D E F G
1 – 30 1JLLN 7⁄8 (22.2) — 9⁄32 (7.1) 13⁄32 (10.3) — — —
JLLS 11⁄2 (38.1) — 9⁄32 (7.1) 9⁄16 (14.3) — — —
35 – 601 JLLN 7⁄8 (22.2) — 9⁄32 (7.1) 9⁄16 (14.3) — — —
2 JLLS 19⁄16 (39.7) 13⁄16 (20.6) 13⁄32 (10.3) 1 (25.4) 1⁄16 (1.6) 13⁄32 (27.8) —
70 – 100 3JLLN 25⁄32 (54.8) 19⁄16 (39.7) 3⁄4 (19.1) 13⁄16 (20.6) 27⁄32 (21.4) 9⁄32 (7.1) 1⁄8 (3.2)
JLLS 261⁄64 (75.0) 223⁄64 (59.9) 3⁄4 (19.1) 13⁄16 (20.6) 141⁄64 (41.7) 9⁄32 (7.1) 1⁄8 (3.2)
110 – 200 3JLLN 27⁄16 (61.9) 111⁄16 (42.9) 7⁄8 (22.2) 11⁄16 (27.0) 27⁄32 (21.4) 11⁄32 (8.7) 3⁄16 (4.8)
JLLS 31⁄4 (82.6) 21⁄2 (63.5) 7⁄8 (22.2) 11⁄16 (27.0) 121⁄32 (42.1) 11⁄32 (8.7) 3⁄16 (4.8)
225 – 400 3JLLN 23⁄4 (69.9) 127⁄32 (46.8) 1 (25.4) 15⁄16 (33.3) 53⁄64 (21.0) 13⁄32 (10.3) 1⁄4 (6.4)
JLLS 35⁄8 (92.1) 223⁄32 (69.1) 1 (25.4) 119⁄32 (40.5) 123⁄32 (43.7) 13⁄32 (10.3) 1⁄4 (6.4)
450 – 600 3JLLN 31⁄16 (77.8) 21⁄32 (51.6) 11⁄4 (31.8) 119⁄32 (40.5) 7⁄8 (22.2) 31⁄64 (12.3) 5⁄16 (7.9)
JLLS 363⁄64 (101.2) 261⁄64 (75.0) 11⁄4 (31.8) 21⁄16 (52.4) 149⁄64 (44.8) 31⁄64 (12.3) 5⁄16 (7.9)
700 – 800 3JLLN 33⁄8 (85.7) 2 7⁄32 (64.3) 13⁄4 (44.5) 21⁄16 (52.4) 7⁄8 (22.2) 35⁄64 (13.9) 3⁄8 (9.5)
JLLS 4 21⁄64 (109.9) 311⁄64 (80.6) 13⁄4 (44.5) 21⁄2 (63.5) 155⁄64 (47.2) 35⁄64 (13.9) 3⁄8 (9.5)
900 – 1200 3JLLN 4 (101.6) 217⁄32 (64.3) 2 (50.8) 21⁄2 (63.5) 11⁄32 (26.2) 39⁄64 (15.5) 7⁄16 (11.1)
JLLS 5.27 (133.9) 3.80 (96.5) 2 (50.8) 2.63 (66.8) 2.30 (58.4) 0.67 (15.5) 0.44 (11.2)
Current-Limiting Effects of JLLS (600V) fuses
Short Circuit
Current*
Apparent RMS Symmetrical Current for Various fuse ratings
30A 60A 100A 200A 400A 600A 800A 1200A
5,000 750 1,225 1,400 2,850 4,600 5,000 5,000 5,000
10,000 945 1,525 1,700 3,600 6,000 8,500 9,400 10,000
15,000 1,050 1,700 2,000 4,050 6,600 9,750 10,500 13,000
20,000 1,150 1,900 2,200 4,450 7,250 10,500 11,000 14,750
25,000 1,300 2,050 2,400 4,800 8,000 11,500 12,500 15,500
30,000 1,375 2,150 2,450 5,000 8,250 12,000 13,750 16,500
35,000 1,400 2,250 2,600 5,100 8,500 13,000 14,000 17,000
40,000 1,425 2,400 2,800 5,200 8,700 14,000 14,750 18,000
50,000 1,600 2,450 2,900 6,000 9,500 14,500 16,000 20,000
60,000 1,650 2,625 3,100 6,250 10,000 15,500 17,300 21,000
80,000 1,825 2,800 3,400 7,000 11,000 17,000 18,750 23,000
100,000 2,000 3,100 3,700 7,250 12,000 18,000 20,000 25,000
150,000 2,250 3,400 4,300 8,500 13,000 21,000 23,000 28,500
200,000 2,450 3,800 4,600 9,000 15,000 23,000 25,000 31,000
* Prospective RMS Symmetrical Amperes Short-Circuit CurrentNote: Data Derived from Peak Let-Thru Curves
Current-Limiting Effects of JLLN (300V) fuses
Short Circuit
Current*
Apparent RMS Symmetrical Current for Various fuse ratings
30A 60A 100A 200A 400A 600A 800A 1200A
5,000 700 775 1,100 1,650 3,500 4,000 5,000 5,000
10,000 900 1,000 1,400 2,100 4,400 5,100 6,750 8,250
15,000 1,000 1,100 1,600 2,400 5,000 5,900 7,750 10,000
20,000 1,100 1,250 1,800 2,700 5,500 6,500 8,750 11,000
25,000 1,230 1,300 1,950 2,900 6,000 7,000 9,500 12,000
30,000 1,300 1,475 2,050 3,100 6,400 7,500 10,000 12,500
35,000 1,330 1,575 2,150 3,300 6,750 7,750 10,500 13,500
40,000 1,430 1,600 2,300 3,500 7,000 8,000 11,000 14,000
50,000 1,500 1,750 2,400 3,700 7,500 8,750 12,000 15,000
60,000 1,700 1,900 2,700 4,000 8,000 9,500 12,500 16,000
80,000 1,850 2,100 2,800 4,400 9,000 10,500 14,000 17,500
100,000 2,000 2,250 3,150 4,800 9,750 11,500 15,000 18,500
150,000 2,300 2,600 3,600 5,500 11,000 13,000 17,500 22,000
200,000 2,600 2,800 3,900 6,000 12,000 14,500 19,500 24,000
* Prospective RMS Symmetrical Amperes Short-Circuit CurrentNote: Data Derived from Peak Let-Thru Curves
Catalog 25-48.indd 42 5/30/07 6:19:26 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose Fuses
General Purpose Fuses
43w w w . l i t t e l f u s e . c o m© 2005 Littelfuse • POWR-GARD™ Products Catalog
JLLN/JLLS POWR-T™ Class T Fuses
300/600 VAC • Fast Acting • 1 – 1200 Amperes
1000800600
400300
200
1008060
4030
20
1086
43
2
1.8.6
.4
.3
.2
.1.08.06
.04
.03
.02
.01
200
300
400
600
800
1000
2000
3000
4000
6000
8000
1000
0
2000
0
3000
040
000
6000
080
000
1000
008 10 20 30 40 60 80 1005
30A
60A
100A
200A
400A
600A
800A
1200
A
TIM
E IN
SEC
ON
DS
CURRENT IN AMPERES
1000800600
400300
200
1008060
4030
20
1086
43
2
1.8.6
.4
.3
.2
.1.08.06
.04
.03
.02
.01
200
300
400
600
800
1000
2000
3000
4000
6000
8000
1000
0
2000
0
3000
040
000
6000
080
000
1000
008 10 20 30 40 60 80 1005
30A
60A
100A
200A
400A
600A
800A
TIM
E IN
SEC
ON
DS
CURRENT IN AMPERES
2000
3000
4000
6000
8000
1000
0
2000
0
3000
040
000
6000
080
000
1000
00
2000
00100
200
300
400
600
800
1000
100
200
300400
600800
1000
2000
30004000
60008000
10000
20000
3000040000
6000080000
100000
200000
300000400000
600000800000
1000000
1200A800A600A400A
200A
100A
60A30A
PEA
K LE
T-TH
RU IN
AM
PERE
S
AVAILABLE FAULT CURRENTSYMMETRICAL R. M. S. AMPERES
2000
3000
4000
6000
8000
1000
0
2000
0
3000
040
000
6000
080
000
1000
00
2000
00100
200
300
400
600
800
1000
100
200
300400
600800
1000
2000
30004000
60008000
10000
20000
3000040000
6000080000
100000
200000
300000400000
600000800000
1000000
800A600A
400A
200A
100A60A
30A
PEA
K LE
T-TH
RU IN
AM
PERE
S
AVAILABLE FAULT CURRENTSYMMETRICAL R. M. S. AMPERES
JLLSJLLN
JLLSJLLN
Catalog 25-48.indd 43 5/30/07 6:19:28 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose FusesG
ener
al P
urpo
se F
uses
44 w w w . l i t t e l f u s e . c o m © 2005 Littelfuse • POWR-GARD™ Products Catalog
SLC Class G Fuses
480 VAC, 600 VAC • Medium Time-Delay • 1/2 – 60 Amperes
The compact design of Littelfuse SLC series Class G fuses offers a cost effective, space saving alternative to other fuse classes. The unique design of the SLC series provides superior time-delay characteristics over competitive products, which can increase system reliability and minimize downtime. Class G fuses meet NEC requirements for branch circuit protection and vary in length to prevent over-fusing when used with the appropriate Class G fuse block.
Features/Benefits
• Current-limiting – Reduces damage to equipment caused by heating and magnetic effects of short-circuit currents.
• 100,000 A.I.R. – Reliable interruption of all overcurrents up to 100,000 amperes.
• Time-Delay – Allows fuses to be sized closer to actual equipment requirements and may reduce downtime caused by power surges.
Note: For ap pli ca tions where greater time-delay is re quired, or where ratings exceed 60 am peres, con sid er se lect ing Littelfuse time-delay Class RK1, RK5, J or CC fuses.
A
B
C D
Specifications
Voltage Ratings: 600 Volts AC (1⁄2 – 20A) 480 Volts AC (25 – 60A)Interrupting Ratings: 100,000 amperes rms symmetricalAmpere Range: 1⁄2 – 60 amperesAp prov als: Standard 248-5, Class G UL Listed (File No: E81895) CSA Certified (File No: LR29862) QPL: Federal Specification No: WF-1814
Ampere Ratings
1⁄2 3 6 15 30 451 4 8 20 35 502 5 10 25 40 60
Example part number (series & amperage): SLC 10
Recommended Fuse Blocks
LG300 series; L300G30 (for 25 and 30 amp fuses)Refer to the Blocks & Holders section of this catalog for additional information.
Amperes Refer toFig. No.Dimensions in Inches (mm in parentheses)
A B C D1⁄2 – 15 1 15⁄16 (33.3) 3⁄8 (9.5) 9⁄32 (7.1) 13⁄32 (10.3)
20 1 113⁄32 (35.7) 3⁄8 (9.5) 9⁄32 (7.1) 13⁄32 (10.3)25, 30 1 15⁄8 (41.3) 3⁄8 (9.5) 9⁄32 (7.1) 13⁄32 (10.3)
35 – 60 1 21⁄4 (57.2) 3⁄8 (9.5) 1⁄2 (12.7) 13⁄32 (10.3)
1000800600
400300
200
1008060
4030
20
1086
43
2
1.8.6
.4
.3
.2
.1.08.06
.04
.03
.02
.01
20 30 40 60 80 100
200
300
400
600
800
1000
2000
3000
4000
6000
8000
1000
01 2 3 4 6 8 10
1/2A
1A 2A 3A 4A 5A 6A 8A 10A
12A
15A
20A
25A
30A
35A
40A
45A
50A
60A
TIM
E IN
SEC
ON
DS
CURRENT IN AMPERES
Fig. 1
Catalog 25-48.indd 44 5/30/07 6:19:29 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose Fuses
General Purpose Fuses
45w w w . l i t t e l f u s e . c o m© 2005 Littelfuse • POWR-GARD™ Products Catalog
Class CC and Class CD Fuses
600 VAC • 1/10 – 60 Amperes
Compared to other UL Listed fuses, Class CC has the most current-limiting fuse design available, rating for rating. Be cause they are physically compact, they provide this superior protection in a fraction of the space required by other fuse classes. For example, when 600V three-pole, 30 ampere Class R fuse blocks are replaced by Littelfuse Class CC fuse blocks, panel mounting space is reduced ap proximate ly 70%. This is especially important when a panel contains many fuses to protect multiple circuit components.
Applications
Three types of Class CC fuses, specifically designed to protect different types of components
1) Motor protection — CCMR series; dual-element, time-delay fuses specifically designed to protect motor circuits up to 40 HP**.
2) Small transformer protection (control power transformers) — KLDR series, time-delay fuses designed to withstand the high magnetizing in-rush of transformers.
3) General purpose protection of equipment requiring fast overload protection — KLKR series, fast-acting fuses used for protection of equip ment containing solid-state devices or other electronic components requiring fast response on overloads.
Safety
• 200,000 A.I.R. — Reliable interruption of all overcurrents up to 200,000 amperes.
• Extremely current-limiting — Reduces damage caused by heating and magnetic effects of short-circuit currents. Stops damaging short-circuit currents faster than any me chani cal protective device.
Space Saving
• Class CC and CD fuses are the smallest 600V, 200,000 A.I.R. fuses approved for branch circuit protection.
Economical
• Current-limiting design often permits use of readily avail able, less costly equipment.
Specifications
Voltage Ratings: AC: 600 Volts DC: 250 – 500 Volts (CCMR) † 300 Volts (KLDR) 300 Volts (KLKR)Interrupting Ratings: AC: 200,000 amperes rms symmetrical DC: 20,000 amperesAmpere Range: CCMR: 2 ⁄10 – 60 amperes KLDR: 1⁄10 – 30 amperes KLKR: 1⁄10 – 30 amperesApprovals: AC: Standard 248-4, Class CC UL Listed 1⁄10-30 Amps (File No: E81895) Standard 248, Class CD UL Listed 35-60 Amps (File No: E71611) CSA Certified 1⁄10-30 Amps (File No: LR29862) DC: Littelfuse Self-certified
Recommended Fuse Blocks
LPSC series (for 1⁄10–30A)L60030C series (for 1⁄10–30A)L60060C series (for CCMR 35–60A)Refer to the Blocks and Holders section of this catalog for ad di tion al in for ma tion.†Refer to the POWR-PRO® section for additional information.
1.880 REF.
.850 +-.02035-60A
** Consult the Motor Protection Tables in the Fuseology section for specific motor sizing information
1.50"(38.1 mm)
.50"(12.7 mm)
.41"(10.3 mm)
.25"(6.4 mm)
.125"(3.2 mm)
0-30A
Catalog 25-48.indd 45 5/30/07 6:19:32 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose FusesG
ener
al P
urpo
se F
uses
46 w w w . l i t t e l f u s e . c o m © 2005 Littelfuse • POWR-GARD™ Products Catalog
Class CC and Class CD Fuses
600 VAC • 1/10 – 60 Amperes
For space saving protection of motor circuits up to 40 HP**, we recommend Littelfuse POWR-PRO® CCMR series fuses. These fuses are the only true dual-element time-delay CC fuses specifically en gi neered for motor branch circuit pro tec tion. They pro vide Type 2 “No Damage” pro tec tion to both NEMA-rated and the more sensitive IEC (International Electrotechnical Commission) type motor circuit components.
CCMR series fuses are now available in larger sizes — from 35 to 60 amperes! No other 600V fuse is avail able with this current carrying capacity in a package this small.
For more information on CCMR series Class CC fuses, see the CCMR series pages in the POWR-PRO section of this catalog.1⁄10 – 30A: UL Listed Class CC 35 – 60A: UL Listed Class CD
KLDR fuses are time-delay fuses specifically designed for the protection of control transformers, so le noids and similar inductive com ponents with high mag ne tiz ing currents during the first half-cycle. They closely match most control power transformer characteristics, which permits the fuses to be sized in ac cor dance with the latest revisions of UL 508 (Industrial Control) and UL 845 (Motor Control Centers). When the time delay of KLDR fuses is adequate to carry motor starting current, they provide ex cel lent protection of motor branch circuits con tain ing IEC or NEMA rated motor con trol lers or contactors.
CCMR Series
KLKR Series
KLDR Series
KLKR series Class CC fuses are fast acting fuses intended for general purpose branch circuit protection. Their compact size, fast acting overload response, and highly current-limiting design make them ideal for use in OEM equipment and control panels. Solid state devices such as SCRs and other electronic equipment generally require fast acting protection.
Ampere Ratings
2 ⁄10 11⁄4 21⁄2 5 9 301⁄4 14⁄10 28⁄10 56⁄10 10 35
3⁄10 11⁄2 3 6 12 401⁄2 16⁄10 32 ⁄10 61⁄4 15 45
6⁄10 18⁄10 31⁄2 7 171⁄2 508⁄10 2 4 71⁄2 20 601 21⁄4 41⁄2 8 25
Example part number (series & amperage): CCMR 30**Consult the Motor Protection Tables in the Fuse-ology section for specific motor sizing information
Ampere Ratings
1⁄10 6⁄10 18⁄10 41⁄2 101⁄8 3⁄4 2 5 12
15⁄100 8⁄10 21⁄4 5 6⁄10 15⁄16 1 21⁄2 6 171⁄2
2 ⁄10 11⁄8 28⁄10 61⁄4 201⁄4 11⁄4 3 7 25
3⁄10 14⁄10 32 ⁄10 71⁄2 304⁄10 11⁄2 31⁄2 81⁄2 16⁄10 4 9
Example part number (series & amperage): KLDR 5 6⁄10
Ampere Ratings
1⁄10 1⁄2 21⁄2 6 121⁄8 3⁄4 3 7 15
2⁄10 1 31⁄2 8 201⁄4 11⁄2 4 9 25
3⁄10 2 5 10 30
Example part number (series & amperage): KLKR 25
Catalog 25-48.indd 46 5/30/07 6:19:36 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose Fuses
General Purpose Fuses
47w w w . l i t t e l f u s e . c o m© 2005 Littelfuse • POWR-GARD™ Products Catalog
Class CC and Class CD Fuses
600 VAC • 1/10 – 60 Amperes
1000800600
400300
200
1008060
4030
20
1086
43
2
1.8.6
.4
.3
.2
.1.08.06
.04
.03
.02
.01
2 3 4 6 8 10 20 30 40 60 80 100
200
300
400
600
800
1000.1 .2 .3 .4 .6 .8 1
1/8A
2/10
A
3/10
A1/
2A6/
10A
3/4A
1A 1.8A
2A 2 1/
2A3A 4A 6
1/4A
8A 10A
TIM
E IN
SEC
ON
DS
CURRENT IN AMPERES
1000800600
400300
200
1008060
4030
20
1086
43
2
1.8.6
.4
.3
.2
.1.08.06
.04
.03
.02
.01
2 3 4 6 8 10 20 30 40 60 80 100
200
300
400
600
800
1000.1 .2 .3 .4 .6 .8 1
1/10
A1/
8A
2/10
A1/
4A3/
10A
1/2A
3/4A
1A 1 1/
2A
2A 3A 4A 5A 6A 8A 9A 10A
12A
15A
20A
25A
30A
TIM
E IN
SEC
ON
DS
CURRENT IN AMPERES
PEA
K LE
T-TH
RU IN
AM
PERE
S
AVAILABLE FAULT CURRENTSYMMETRICAL R. M. S. AMPERES
2000
3000
4000
6000
8000
1000
0
2000
0
3000
040
000
6000
080
000
1000
00
2000
00100
200
300
400
600
800
1000
100
200
300400
600800
1000
2000
30004000
60008000
10000
20000
3000040000
6000080000
100000
200000
300000400000
600000800000
1000000
10A
8A6A4A
2000
3000
4000
6000
8000
1000
0
2000
0
3000
040
000
6000
080
000
1000
00
2000
00100
200
300
400
600
800
1000
100
200
300400
600800
1000
2000
30004000
60008000
10000
20000
3000040000
6000080000
100000
200000
300000400000
600000800000
1000000
30A25A20A15A12AP
EAK
LET-
THRU
IN A
MPE
RES
AVAILABLE FAULT CURRENTSYMMETRICAL R. M. S. AMPERES
For performance data on Littelfuse CCMR series Class CC fuses, see the CCMR pages in the POWR-PRO® section of this catalog.
KLDR KLKR
KLDR KLKR
Catalog 25-48.indd 47 5/30/07 6:19:42 PM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
-
General Purpose FusesG
ener
al P
urpo
se F
uses
48 w w w . l i t t e l f u s e . c o m © 2005 Littelfuse • POWR-GARD™ Products Catalog
Plug Fuses125 VAC • Time-Delay • 1/4 – 30 Amperes
Edison-base Plug fuses
TOO Fuses are dual-element time-delay Edison-base fuses designed for motor and motor branch circuit protection; also suitable for all general purpose circuits. Use for replacement purposes only.
Ampere Ratings
3⁄10 11⁄8 21⁄4 4 7 154⁄10 11⁄4 21⁄2 41⁄2 8 201⁄2 14⁄10 28⁄10 5 9 25
6⁄10 16⁄10 3 5 6⁄10 10 308⁄10 18⁄10 32 ⁄10 6 121 2 31⁄2 61⁄4 14
TLO Fuses are medium time-delay Edison-base fuses designed for general purpose branch circuit protection. See TOO and SOO fuses for motor protection. Use for re place ment purposes only.
Ampere Ratings
15 20 25 30
Type S Plug fusesSOO Fuses are dual-element time-delay Type S fuses designed for motor and motor branch circuit protection; also suitable for all general purpose circuits.
Ampere Ratings
1⁄4 1 2 31⁄2 61⁄4 143⁄10 11⁄8 21⁄4 4 7 154⁄10 11⁄4 21⁄2 41⁄2 8 201⁄2 14⁄10 28⁄10 5 9 25
6⁄10 16⁄10 3 5 6⁄10 10 308⁄10 18⁄10 32 ⁄10 6 12
SLO Fuses are medium time-delay Type S fuses for general purpose branch circuit protection.
Ampere Ratings
15 20 25 30
Littelfuse Plug fuses provide overcurrent protection to general purpose circuits and small motor loads. Edison-base Plug fuses (TOO and TLO series) feature metal threads similar to incandescent lamp bases. Type S Plug fuses (SOO and SLO series) utilize a nonmetallic threaded base and must be used with Type S adapters (SAO series). The National Electrical Code permits Edison-base Plug fuses to be used for replacement purposes only. Type S fuses and adapters prevent shunting open fuses and over-fusing.
SAOAdapter Rating
AcceptsFuse Ratings:
Other SOO Fuse Ratings Which Fit
SAO 1 3⁄10 – 1 —SAO 11⁄4 11⁄8, 11⁄4 3⁄10 – 1SAO 16⁄10 14⁄10, 16⁄10 3⁄10 – 11⁄4
SAO 2 18⁄10, 2 —SAO 21⁄2 21⁄4, 21⁄2 18⁄10, 2SAO 32 ⁄10 28⁄10, 3 2 ⁄10 18⁄10 – 21⁄2
SAO 4 31⁄2, 4 —SAO 5 41⁄2, 5 31⁄2, 4
SAO 61⁄4 31⁄2, 61⁄4 31⁄2 – 5SAO 8 7, 8 —SAO 15 7, 8, 9 10, 12, 14, 15 7, 8, 9, 10SAO 20 20 only —SAO 30 20, 25, 30 —
Specifications
Voltage Rating: 125 VAC Interrupting Rating: 10,000 amperes rms symmetricalApprovals: UL Listed Plug Fuses, Standard UL 248-11
Note: See NEC Article 240-V for additional information on Plug fuse applications.
Catalog 25-48.indd 48 5/30/07 6:19:43 PM