GENERAL NOTES APPLICABLE CODES AND STANDARDS LEGEND · ansi/tia-568-c.0, generic telecommunications...
Transcript of GENERAL NOTES APPLICABLE CODES AND STANDARDS LEGEND · ansi/tia-568-c.0, generic telecommunications...
INSTALL (1) CATEGORY 6 CABLE FOR VOICE AND (#) CATEGORY 6A CABLES FOR DATA, WHERE (#) IS THE NUMBER OF DATA CABLES. AT THE DEVICE LOCATION, TERMINATE CATEGORY 6 CABLES WITH CATEGORY 6 JACKS AND TERMINATE CATEGORY 6A CABLES WITH CATEGORY 6A JACKS ALL INSTALLED IN A SINGLE-GANG FACEPLATE MOUNTED AT 18" AFF, UON, OR IN A MODULAR FURNITURE OR FLOOR-BOX ADAPTER PLATE. IN THE TELECOM ROOM, TERMINATE CATEGORY 6 CABLES ON WALL-MOUNTED 110-TYPE BLOCKS AND CATEGORY 6A CABLES ON RACK-MOUNTED CATEGORY 6A PATCH PANELS.
INSTALL (#) CATEGORY 6A CABLES FOR VOICE AND DATA, WHERE (#) IS THE NUMBER OF CABLES. AT THE DEVICE LOCATION, TERMINATE CABLES WITH CATEGORY 6A JACKS INSTALLED IN A SINGLE-GANG FACEPLATE MOUNTED AT 18" AFF, UON, OR IN A MODULAR FURNITURE OR FLOOR-BOX ADAPTER PLATE. IN THE TELECOM ROOM, TERMINATE CABLES ON A RACK-MOUNTED CATEGORY 6A PATCH PANEL.
INSTALL (2) CATEGORY 6A CABLES AND TERMINATE EACH WITH A CATEGORY 6A JACK FOR A WIRELESS ACCESS POINT. AT THE DEVICE LOCATION, INSTALL THE JACKS IN A BISCUIT-TYPE BOX. WHERE CABLES ARE INSTALLED TO AN ACCESSIBLE (DROP-DOWN, CEILING TILE) CEILING, LEAVE 15' OF CABLE COILED ABOVE THE TILE WHERE THE ACCESS POINT IS LOCATED. WHERE CABLES ARE INSTALLED IN AN AREA THAT HAS NO CEILING OR HAS A HARD CEILING, PROVIDE A SINGLE-GANG OUTLET BOX WHERE THE ACCESS POINT IS LOCATED WITH CONDUIT RUNNING BACK TO THE ACCESSIBLE CEILING OR CABLE TRAY, AND LEAVE 15' OF CABLE COILED IN THE CABLE TRAY. IN THE TELECOM ROOM, TERMINATE THE CABLES ON A RACK-MOUNTED 48-PORT CATEGORY 6A PATCH PANEL
INSTALL (1) CATEGORY 6 CABLE AND TERMINATE WITH A CATEGORY 6 JACK FOR A WALL-PHONE. AT THE DEVICE LOCATION, INSTALL THE JACK IN A SINGLE-GANG WALL-PHONE FACEPLATE MOUNTED AT 48" AFF. IN THE TELECOM ROOM, TERMINATE THE CABLE ON A WALL-MOUNTED 110-TYPE BLOCK.
INSTALL (2) CATEGORY 6A CABLES AND TERMINATE WITH CATEGORY 6A JACKS FOR A FLAT SCREEN DISPLAY. AT THE DEVICE LOCATION, INSTALL JACKS IN A SINGLE-GANG FACEPLATE MOUNTED AT APPROXIMATELY 50” AFF, UON (SEE AV DRAWINGS FOR DETAILS). IN THE TELECOM ROOM, TERMINATE THE CATEGORY 6A CABLES ON A RACK-MOUNTED 48-PORT CATEGORY 6A PATCH PANEL.
INSTALL (4) CATEGORY 6A CABLES AND TERMINATE WITH CATEGORY 6A JACKS FOR AN AUDIO-VISUAL EQUIPMENT RACK. AT THE DEVICE LOCATION, INSTALL JACKS IN A SINGLE-GANG FACEPLATE MOUNTED BEHIND THE RACK (COORDINATE EXACT HEIGHT WITH AV DRAWINGS). IN THE TELECOM ROOM, TERMINATE THE CATEGORY 6A CABLES ON A RACK-MOUNTED 48-PORT CATEGORY 6A PATCH PANEL.
INSTALL (2) CATEGORY 6A CABLES FOR DIGITAL SIGNAGE. AT THE DEVICE LOCATION, TERMINATE THE CABLES WITH CATEGORY 6A JACKS INSTALLED IN A SINGLE-GANG FACEPLATE MOUNTED AT APPROXIMATELY 50" AFF, UON (SEE AV DRAWINGS FOR DETAILS). IN THE TELECOM ROOM, TERMINATE CABLES ON A RACK-MOUNTED CATEGORY 6A PATCH PANEL.
INSTALL (2) CATEGORY 6A CABLES FOR A SECURITY CAMERA. AT THE DEVICE LOCATION, TERMINATE THE CABLES WITH CATEGORY 6A JACKS INSTALLED IN A BISCUIT-TYPE BOX. IN THE TELECOM ROOM, TERMINATE CABLES ON A RACK-MOUNTED CATEGORY 6A PATCH PANEL.
INSTALL (2) CATEGORY 6A CABLES FOR A PROJECTOR. AT THE DEVICE LOCATION, TERMINATE THE CABLES WITH CATEGORY 6A JACKS INSTALLED IN A BISCUIT-TYPE BOX. IN THE TELECOM ROOM, TERMINATE CABLES ON A RACK-MOUNTED CATEGORY 6A PATCH PANEL.
INSTALL (1) CATEGORY 6A CABLE AND TERMINATE WITH A CATEGORY 6A PLUG FOR AN AUDIO-VISUAL DEVICE AT THIS LOCATION. IN THE TELECOM ROOM, TERMINATE THE CABLES ON A RACK-MOUNTED 48-PORT CATEGORY 6A PATCH PANEL. SEE AV CONDUIT DIAGRAMS FOR BOX AND CONDUIT REQUIREMENTS.
INSTALL (1) CATEGORY 6 CABLE AND LEAVE 10 FEET COILED AT THE DEVICE LOCATION FOR AN EMERGENCY TELEPHONE AT THIS LOCATION. IN THE TELECOM ROOM, TERMINATE THE CABLE ON A WALL-MOUNTED 110-TYPE BLOCK.
INDICATES THAT CABLES ARE TO BE INSTALLED IN A FLOOR BOX OR POKE-THROUGH.
INDICATES THAT CABLES ARE TO BE INSTALLED IN OR ABOVE THE CEILING.
AP
W
#
D
AVR
DS
SEC
P
#
AVD
ET
ALL MATERIALS AND WORK SPECIFIED HEREIN SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF:
GENERAL NOTES APPLICABLE CODES AND STANDARDS LEGEND
SHEET LIST
ABBREVIATIONS
CONVENTIONS
DETAIL DESIGNATION NUMBER DENOTES DETAIL IDENTIFICATION
INDICATES DRAWING NUMBER WHERE DETAIL IS DRAWN
1
T4.1
AFF ABOVE FINISHED FLOOR
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING MATERIALS
BICSI BUILDING INDUSTRY CONSULTING SERVICES INTERNATIONAL
EIA ELECTRONICS INDUSTRY ASSOCIATION
FCC FEDERAL COMMUNICATIONS COMMISSION
IEEE INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS
ISO INTERNATIONAL STANDARDS ORGANIZATION
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS' ASSOCIATION
NESC NATIONAL ELECTRICAL SAFETY CODE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
POE POWER OVER ETHERNET
RUS RURAL UTILITY SERVICE (FORMERLY REA)
SMPTE SOCIETY OF MOTION PICTURE AND TELEVISION ENGINEERS
TIA TELECOMMUNICATIONS INDUSTRY ASSOCIATION
UL UNDERWRITER'S LABORATORIES, INC.
UON UNLESS OTHERWISE NOTED
1. TIA-526-7 (OFSTP-7), MEASUREMENT OF OPTICAL FIBER LOSS OF INSTALLED SINGLE-MODE FIBER CABLE PLANT.
2. TIA-526-14-B (OFSTP-14), OPTICAL POWER LOSS MEASUREMENTS OF MULTIMODE FIBER CABLE PLANT.
3. ANSI/TIA-568-C.0, GENERIC TELECOMMUNICATIONS FOR CUSTOMER PREMISE.
4. ANSI/TIA-568-C.1, COMMERCIAL BUILDING TELECOMMUNICATIONS CABLING STANDARD.
5. ANSI/TIA-568-C.2, BALANCED TWISTED PAIR CABLING COMPONENTS STANDARD.
6. ANSI/TIA-568-C.3, OPTICAL FIBER CABLING COMPONENTS STANDARDS.
7. ANSI/TIA-568-C.4, BROADBAND COAXIAL CABLING COMPONENTS STANDARD.
8. ANSI/TIA-569-C, TELECOMMUNICATIONS PATHWAYS AND SPACES.
9. ANSI/TIA-606-B, ADMINISTRATION STANDARD FOR COMMERCIAL TELECOMMUNICATIONS INFRASTRUCTURE.
10. ANSI/TIA-607-B, GENERIC TELECOMMUNICATIONS BONDING AND GROUNDING (EARTHING) FOR CUSTOMER PREMISES.
11. ANSI/TIA-758-B, CUSTOMER-OWNER OUTSIDE PLANT TELECOMMUNICATIONS INFRASTRUCTURE STANDARD.
12. ANSI/TIA-862-A, BUILDING AUTOMATION SYSTEMS CABLING STANDARD.
13. ANSI/TIA-942-A, TELECOMMUNICATIONS INFRASTRUCTURE STANDARDS FOR DATA CENTERS.
14. ANSI/TIA-1005, TELECOMMUNICATIONS INFRASTRUCTURE FOR INDUSTRIAL PREMISES.
15. ANSI/TIA-1179, HEALTHCARE FACILITY TELECOMMUNICATIONS INFRASTRUCTURE STANDARD.
16. ISO/IEC 11801, GENERIC CABLING FOR CUSTOMER PREMISES.
17. IEEE 802.3af, POWER OVER ETHERNET (PoE) STANDARD.
18. IEEE 802.3at, POWER OVER ETHERNET + (PLUS).
19. IEEE 802.3an, PHYSICAL LAYER AND MANAGEMENT PARAMETERS FOR 10 Gbps OPERATION TYPE 10GBASE-T.
20. IEEE 802.3ba, MEDIA ACCESS CONTROL PARAMETERS, PHYSICAL LAYERS AND MANAGEMENT PARAMETERS FOR 40 GbpsAND 100 Gbps OPERATION.
21. BUILDING INDUSTRY CONSULTING SERVICES INTERNATIONAL (BICSI) TELECOMMUNICATIONS DISTRIBUTION METHODSMANUAL.
22. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION.
23. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 70 - NATIONAL ELECTRICAL CODE.
24. UNDERWRITERS LABORATORY (UL) OR EQUIVALENT.
T0.0 TELECOM CABLING - GENERAL NOTES AND SYMBOLS
T1.0 TELECOM CABLING - SITE PLAN
T2.1 TELECOM CABLING - GROUND FLOOR PLAN
T2.2 TELECOM CABLING - SECOND FLOOR PLAN
T2.3 TELECOM CABLING - THIRD FLOOR PLAN
T3.1 TELECOM CABLING - GROUND FLOOR RCP
T3.2 TELECOM CABLING - SECOND FLOOR RCP
T3.3 TELECOM CABLING - THIRD FLOOR RCP
T4.1 TELECOM CABLING - TR LAYOUTS, RISER, AND INSTALL DETAILS
1. THESE TELECOMMUNICATIONS DRAWINGS ARE PREPARED AND COORDINATED WITH THE SCOPE OF WORK DOCUMENT AND THESPECIFICATIONS. TOGETHER THESE DOCUMENTS FORM THE CONTRACT DOCUMENTS.
2. THE TELECOMMUNICATIONS SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE BICSI AND TIA/EIA STANDARDS.
3. ALL CABLE PATHWAYS ARE DESIGNED WITH A MAXIMUM 40 PERCENT FILL RATIO UNLESS OTHERWISE NOTED. FILL REQUIREMENTSMAY ALTER FROM INITIAL DESIGN DUE TO CLIENT REQUIREMENTS DURING INSTALLATION.
4. ALL CABLE PATHWAYS SHALL BE FREE FROM PROJECTIONS AND ROUGH OR SHARP EDGES THROUGHOUT THE ENTIRE PATH. ALLPOINTS OR EDGES THAT CABLING MUST PASS, AND MAY BE SUBJECT TO INJURY OR WEAR, SHALL BE ROUNDED, PADDED, ORBUSHED.
5. THE TELECOMMUNICATIONS DRAWINGS INDICATE THE GENERAL LOCATION OF EQUIPMENT, CABLE PATHWAYS, AND OUTLETS.ALTHOUGH THE DRAWINGS DO NOT NECESSARILY DICTATE THE ACTUAL ROUTES OF CABLE TRAYS AND CONDUITS, LOCATION OFEQUIPMENT AND OUTLETS, AND OTHER SUPPORTING ITEMS, THEY SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE TO THE DESIGNIN THIS DOCUMENT. IT SHALL BE THE INSTALLING CONTRACTOR'S RESPONSIBILITY TO COORDINATE THE INSTALLATION OF ALLTELECOMMUNICATION ITEMS WITH ALL OTHER CONTRACTORS.
6. ALL BLOCKS, PANELS AND CABLE SHALL BE ASSIGNED, LABELED AND RECORDED BY THE INSTALLING CABLE CONTRACTOR, ANDDELIVERED TO THE ENGINEER.
7. SEE NOTES ON INDIVIDUAL DRAWINGS FOR CROSS REFERENCE TO PERTINENT DETAILS, SECTIONS, ETC. SHOWN ON OTHERDRAWINGS IN THIS DRAWING SET.
8. SCALES NOTED ON THE TELECOMMUNICATIONS DRAWINGS ARE FOR GENERAL INFORMATION AND USED FOR REFERENCE ONLY.
9. ALL MOUNTING HEIGHTS SHOWN ARE MEASURED FROM FINISHED FLOOR TO BOTTOM OF MOUNTED EQUIPMENT UNLESS OTHERWISENOTED.
10. FIRE STOP ALL STRUCTURE PENETRATIONS WITH FIRE STOPPING MATERIAL EQUAL TO OR GREATER THAN THAT OF PENETRATEDSTRUCTURE. INSTALL FIRE STOPPING MATERIAL AFTER COMPLETE INSTALLATION OF CABLING. USE ONLY LISTED FIRE STOPPINGMATERIAL IN ACCORDANCE WITH UL, NFPA, AND OTHER AUTHORITIES HAVING JURISDICTION.
11. TELECOMMUNICATIONS ROOMS SHALL NOT BE USED AS STORAGE SPACE BY ANY CONTRACTOR EXCLUDING THE INSTALLINGCONTRACTOR FOR THE TELECOMMUNICATIONS SYSTEM. WHEN THE INSTALLATION OF A TELECOMMUNICATIONS SPACE ISCOMPLETE, ALL ITEMS AND EQUIPMENT NOT SUPPORTING THE FUNCTIONS OF THAT SPACE SHALL BE REMOVED FROM THE SPACE.
12. ALL TELECOMMUNICATIONS ROOMS WILL HAVE 3/4" x 4' x 8' FIRE RETARDANT PLYWOOD INSTALLED VERTICALLY, STARTINGAPPROXIMATELY 2' ABOVE THE FLOOR.
13. THE TELECOMMUNICATIONS DRAWINGS INDICATE THE GENERAL LOCATION OF THE BACKBONE CONDUIT FOR THE TELECOM ROOMS.THE INSTALLER SHALL VERIFY THE EXACT LOCATION OF THE CONDUIT(S). CONDUITS SHALL BE POSITIONED SO THEY ENTER ANDEXIT TELECOM ROOMS IN THE CORNERS AS SHOWN ON THE TELECOM ROOM DRAWINGS.
14. NOT ALL HARDWARE FOR INSTALLATION IS IDENTIFIED/SHOWN. THE TELECOMMUNICATIONS CONTRACTOR IS RESPONSIBLE FOR ALLMOUNTING HARDWARE REQUIRED FOR A COMPLETE AND PROPERLY OPERATING INSTALLATION.
15. NOT ALL ITEMS, COMPONENTS AND SYSTEMS SPECIFIED IN THIS DRAWING SET OR THE SPECIFICATIONS ARE DETAILED.CONTRACTOR TO PROVIDE MANUFACTURERS' SPECIFICATIONS AND DETAIL SHEETS IN THE PRECONSTRUCTION SUBMITTALS FORSELECTION PER THE SPECIFICATIONS.
16. THE TELECOMMUNICATIONS CONTRACTOR SHALL INSTALL COMPONENTS OR SYSTEMS PER THE MANUFACTURERS' INSTALLATIONINSTRUCTIONS OR SPECIFICATIONS.
17. ALL CABLE SHALL COMPLY WITH THE SPECIFICATIONS AND SHALL BE SUITABLE AND LISTED FOR THE ENVIRONMENT IN WHICH IT ISINSTALLED.
18. ALL CONDUIT RUNS SHALL FOLLOW BICSI STANDARDS FOR BENDS, FILL AND JUNCTION BOX PLACEMENT. NO CONDUIT RUNS SHALLHAVE GREATER THAN 180 DEGREES OF BEND WITHOUT A PROPERLY SIZED AND PLACED PULL BOX.
19. ALL CONDUIT RUNS AND CABLE TRAY SHOWN ARE DIAGRAMMATICAL. REPORT ANY MAJOR DEVIATION TO CONSTRUCTION MANAGERFOR APPROVAL.
20. ALL CONDUITS FROM BELOW SHALL STUB UP 4" A.F.F.
21. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING FINAL SYSTEMS, EQUIPMENT LAYOUT AND CONDUIT ROUTING AS SHOWNON DRAWING WITH SITE CONDITIONS.
22. CONTRACTOR SHALL ENSURE PROPER SEPARATION OF CLASS 1, CLASS 2, AND CLASS 3 CIRCUITS PER NEC 725-54.
23. CONTRACTOR SHALL VERIFY THE SIZE OF ALL CONDUCTORS, CONDUIT, AND JUNCTION BOXES (40 % MAXIMUM FILL). INSTALLATIONSHALL BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE (NEC) AND ALL LOCAL CODES HAVING JURISDICTION.
24. LOW VOLTAGE VOICE AND DATA CABLING SHALL NOT BE INSTALLED IN THE SAME CONDUIT AS 120 VAC POWER CABLES.
25. CONTRACTOR SHALL PROMPTLY NOTIFY OWNER OR OWNER'S REPRESENTATIVE PRIOR TO INSTALLATION OF WORK IF ANYMOUNTING LOCATIONS NOTED ON THE DRAWINGS ARE OBSTRUCTED AND/OR IF ANY CONFLICTS OR PROBLEMS ARE DISCOVERED.
26. CONTRACTOR SHALL PROVIDE AND INSTALL EQUIPMENT AND HARDWARE IN ORDER TO MEET THE INTENT OF THE DESIGN AND TOPROVIDE OWNER WITH A COMPLETE AND FULLY OPERATIONAL CABLING SYSTEM AS SPECIFIED. QUESTIONS REGARDING THEINTENT OF THE DESIGN SHALL BE PROMPTLY BROUGHT TO THE ATTENTION OF THE ENGINEER.
27. ANY DEVICE SHOWN ON THESE DRAWINGS THAT IS LOCATED IN AN OPEN OR HARD CEILING SPACE SHALL HAVE A SINGLE-GANG BOXWITH A CONDUIT TO THE NEAREST ACCESSIBLE CEILING UNLESS OTHERWISE NOTED.
Seal:
GWWO INC.
800 WYMAN PARK DRIVE, SUITE 300
BALTIMORE, MARYLAND 21211, 410-332-1009
Revisions:
Job No.
Scale
Date
Drawing Title
Sheet
Drawn
Checked
Approved
Drawing Number
Of
Seal:
KEY PLAN:
1/4" = 1'-0"
10/2
9/2
019
12
:04:3
6 P
MB
IM 3
60://J
HU
O'C
onno
r R
ec C
ente
r A
dditio
n-R
eno
va
tio
n-2
019
/18
016
-JH
U-O
RC
-Te
chn
olo
gy-2
01
9.r
vt
RALPH S. O'CONNOR CENTERFOR RECREATION AND
WELL-BEING
JOHNS HOPKINS UNIVERSITY
18016
10/31/2019
JSC
JBC
JBC
TELECOM CABLING -GENERAL NOTES AND
SYMBOLS T0.0
100% CONSTRUCTION DOCUMENTS
C 2019 GWWO INC.
No. Date Description
DN
EOIEOI
T
ETSEC
EXISTING PRACTICE FIELD
EXISTING MAIN CIRCLE
EXISTING BUILDING CORDISH
LACROSSE CENTER
EXISTING PARKING
EXISTING PARKING
EXISTING PARKING
EXISTING BUILDINGWHITE ATHLETIC CENTER -
LOCKER ROOMS AND SHOWER ACCESS
EXISTING ADA
PARKING
EXISTING ADA RAMP
EXISTING BUILDINGWHITE ATHLETIC CENTER - NATATORIUM
Seal:
GWWO INC.
800 WYMAN PARK DRIVE, SUITE 300
BALTIMORE, MARYLAND 21211, 410-332-1009
Revisions:
Job No.
Scale
Date
Drawing Title
Sheet
Drawn
Checked
Approved
Drawing Number
Of
Seal:
KEY PLAN:
1" = 20'-0"
10/2
9/2
019
12
:04:4
4 P
MB
IM 3
60://J
HU
O'C
onno
r R
ec C
ente
r A
dditio
n-R
eno
va
tio
n-2
019
/18
016
-JH
U-O
RC
-Te
chn
olo
gy-2
01
9.r
vt
RALPH S. O'CONNOR CENTERFOR RECREATION AND
WELL-BEING
JOHNS HOPKINS UNIVERSITY
18016
10/31/2019
JSC
JBC
JBC
TELECOM CABLING -SITE PLAN T1.0
100% CONSTRUCTION DOCUMENTS
C 2019 GWWO INC.
1" = 20'-0"1
TELECOMMUNICATIONS - SITE PLAN
No. Date Description
W
W
W
2
2
D
AVD
2
AVD
AVD
ET
AVD
DD
DD
D
AVD
AVD
AVD
AVD
1a 1b
M
N
P
Q
R
R.2
S
U
V
W
X
Y
17 16.9 16 14.814.7 14 12 10 8 7 5 3
L
J.8
J
G
E
C
B.5
A
26
2422.5
2220
1815
1311 9 6 4 2 1
B
D
F
H
K
1x2x
ELEC
140MECH
141
RACQUETBALL
COURT
E120
PROGRAM
ROOM A
148
PROGRAM
ROOM B
149
ENCLOSED
WEIGHT AREA
143
STORAGE
147
OFFICE
146
FIRE SERVICE
E111
ELEV. MACH
E130
SQUASH
COURT
E119
STORAGE
145
EXISTING
WEIGHT ROOM
E127
WEIGHT ROOM
142
GYM ACCESS
E113
FUNCTIONAL
TRAINING
144
STAIR C
S103
STRETCHING
151
CLIMBING
WALL
E126
GYMNASIUM
E115
SEATING AREA
E116
TEL CLOSET
E109
VENDING
E101
LOWER LOBBY
E100a
MEN'S TOILET
E108
CUSTODIAN
E107
WOMEN'S
TOILET
E106
CORRIDOR
E100b
GENERAL
STORAGE
E105
EQUIPMENT
ROOM
E103
T4.1
1
RACQUETBALL
COURT
E118
STAIR NO. 2
E102
STAIR B
RACQUETBALL
COURT
E117
ADD ALTERNATE #1
S.1
Seal:
GWWO INC.
800 WYMAN PARK DRIVE, SUITE 300
BALTIMORE, MARYLAND 21211, 410-332-1009
Revisions:
Job No.
Scale
Date
Drawing Title
Sheet
Drawn
Checked
Approved
Drawing Number
Of
Seal:
KEY PLAN:
1/8" = 1'-0"
10/2
9/2
019
12
:04:5
1 P
MB
IM 3
60://J
HU
O'C
onno
r R
ec C
ente
r A
dditio
n-R
eno
va
tio
n-2
019
/18
016
-JH
U-O
RC
-Te
chn
olo
gy-2
01
9.r
vt
RALPH S. O'CONNOR CENTERFOR RECREATION AND
WELL-BEING
JOHNS HOPKINS UNIVERSITY
18016
10/31/2019
JSC
JBC
JBC
TELECOM CABLING -GROUND FLOOR PLAN T2.1
100% CONSTRUCTION DOCUMENTS
C 2019 GWWO INC.
1/8" = 1'-0"1
TELECOM CABLING - GROUND LEVEL
8 0 8 16
SCALE OF FEET1/8" = 1'-0"
No. Date Description
W
W
2
2
2
2
2
2
2
2
2
2 2
2
2
2
22
2
22
22
2
2
2
W
2
D
D2
AV
R
SEC
AV
D
2
AV
D
2
DD
2
2
2
2
22
2
AV
D
AV
D
AV
D2
1a 1b
M
N
P
Q
R
R.2
S
U
V
W
X
Y
17 16.9 16 14.8 14.7 14 12 10 8 7 5 3
L
J.8
J
G
E
C
B.5
A
26
2422.5
2220
1815
1311
96
4
2
1
B
D
F
H
K
1x2x
MEETING RM
248
MEMBERSHIP
SERVICES
245
VESTIBULE
240
LOBBY
241
INFORMATION
DESK
243
WAITING AREA
242
SMALL
MEETING
247
CARDIO
271
JOGGING
ACCESS
E223
PUMP ROOM
220
JOGGING
TRACK
E219
STAIR B
S202
STRETCHING
E224
CORRIDOR
246
STORAGE
265
CAFE STORAGE
263
SHARED
OFFICE 3
250
SHARED
OFFICE 2
252
SHARED
OFFICE 1
253
WORK ROOM
251
OFFICE
E204 OFFICE
E211
OFFICE
E212
OFFICE
E205
OFFICE
E206
STORAGE
E209STORAGE
E208aOFFICE
E208
KITCHEN
E207
OFFICE
E210
STAIR A
S201
WOMENS
TOILET
E215 CORR
E213
MENS TOILET
E217
CUSTODIAN
E216
Room
E226 LOBBY
E214
MOTHER'S RM
280
UNIV. W/C
260
CAFE KITCHEN
262
CAFE
261
T4.1
3
1
S.1
Seal:
GWWO INC.
800 WYMAN PARK DRIVE, SUITE 300
BALTIMORE, MARYLAND 21211, 410-332-1009
Revisions:
Job No.
Scale
Date
Drawing Title
Sheet
Drawn
Checked
Approved
Drawing Number
Of
Seal:
KEY PLAN:
1/8" = 1'-0"
10/2
9/2
019
12
:05:0
1 P
MB
IM 3
60://J
HU
O'C
onno
r R
ec C
ente
r A
dditio
n-R
eno
va
tio
n-2
019
/18
016
-JH
U-O
RC
-Te
chn
olo
gy-2
01
9.r
vt
RALPH S. O'CONNOR CENTERFOR RECREATION AND
WELL-BEING
JOHNS HOPKINS UNIVERSITY
18016
10/31/2019
JSC
JBC
JBC
TELECOM CABLING -SECOND FLOOR PLAN T2.2
100% CONSTRUCTION DOCUMENTS
C 2019 GWWO INC.
1/8" = 1'-0"1
TELECOM CABLING - (ENTRANCE) SECOND LEVEL
8 0 8 16
SCALE OF FEET1/8" = 1'-0"
KEYED NOTES
1 EXISTING MAIN TELECOM ROOM, 277, IN NEWTON BUILDING. NEW BACKBONE CABLES WILL ORIGINATE HERE. NO NEW HORIZONTAL CABLES WILL BE INSTALLED TO THIS LOCATION.
No. Date Description
W
W
W
AVDAVD
AV
DA
VD
D
1a 1b
M
N
P
Q
R
R.2
S
U
V
W
X
Y
17 16.9 16 14.814.7 14 12 10 8 7 5
3L
J.8
J
G
E
C
B.5
A24
22.522
2018
1513
11 9 6 4 2 1
1x2x
CARDIO/WEIGHTS
326b
PROGRAM B
E310
PROGRAM A
323
TEL
320
CORRIDOR
321
STORAGE
E306
ROOF ACCESS
E307
STAIR NO. 3
S301
ELEVATOR
EL301
WOMEN'S
TOILET
E305
MEN'S TOILET
E304
CUSTODIAN
CLOSET
E303
LOBBY
E302
STAIR B
S302
STAIR C
S303
T4.1
4
STORAGE A
323A
STORAGE B
310A
LOUNGE
322
APPROXIMATELY 96" AFF
S.1
Seal:
GWWO INC.
800 WYMAN PARK DRIVE, SUITE 300
BALTIMORE, MARYLAND 21211, 410-332-1009
Revisions:
Job No.
Scale
Date
Drawing Title
Sheet
Drawn
Checked
Approved
Drawing Number
Of
Seal:
KEY PLAN:
1/8" = 1'-0"
10/2
9/2
019
12
:10:3
7 P
MB
IM 3
60://J
HU
O'C
onno
r R
ec C
ente
r A
dditio
n-R
eno
va
tio
n-2
019
/18
016
-JH
U-O
RC
-Te
chn
olo
gy-2
01
9.r
vt
RALPH S. O'CONNOR CENTERFOR RECREATION AND
WELL-BEING
JOHNS HOPKINS UNIVERSITY
18016
10/31/2019
JSC
JBC
JBC
TELECOM CABLING -THIRD FLOOR PLAN T2.3
100% CONSTRUCTION DOCUMENTS
C 2019 GWWO INC.
1/8" = 1'-0"1
TELECOM CABLING - THIRD LEVEL
8 0 8 16
SCALE OF FEET1/8" = 1'-0"
No. Date Description
SEC
SEC
SEC
AP
AP
AP
AP
AP
AP
AP
AP
AP AP
AP
AP
AP
APAP
1a 1b
M
N
P
Q
R
R.2
S
U
V
W
X
Y
17 16.9 16 14.8 14.7 14 12 10 8 7 5
3 L
J.8
J
G
E
C
B.5
A
26
2422.5
2220
1815
1311 9 6 4 2 1
B
D
F
H
K
1x2x
ELEC
140MECH
141
RACQUETBALL
COURT
E120
PROGRAM
ROOM A
148
PROGRAM
ROOM B
149
ENCLOSED
WEIGHT AREA
143
STORAGE
147
OFFICE
146
FIRE SERVICE
E111
ELEV. MACH
E130
SQUASH
COURT
E119
STORAGE
145
EXISTING
WEIGHT ROOM
E127
WEIGHT ROOM
142
GYM ACCESS
E113
FUNCTIONAL
TRAINING
144
STAIR C
S103
STRETCHING
151
CLIMBING
WALL
E126
GYMNASIUM
E115
SEATING AREA
E116
TEL CLOSET
E109
VENDING
E101
MEN'S TOILET
E108
CUSTODIAN
E107
WOMEN'S
TOILET
E106GENERAL
STORAGE
E105
EQUIPMENT
ROOM
E103
CORRIDOR
E100b
LOWER LOBBY
E100a
STAIR NO. 5
E131
RACQUETBALL
COURT
E117
RACQUETBALL
COURT
E118
T4.1
2
S.1
Seal:
GWWO INC.
800 WYMAN PARK DRIVE, SUITE 300
BALTIMORE, MARYLAND 21211, 410-332-1009
Revisions:
Job No.
Scale
Date
Drawing Title
Sheet
Drawn
Checked
Approved
Drawing Number
Of
Seal:
KEY PLAN:
1/8" = 1'-0"
10/2
9/2
019
12
:05:1
7 P
MB
IM 3
60://J
HU
O'C
onno
r R
ec C
ente
r A
dditio
n-R
eno
va
tio
n-2
019
/18
016
-JH
U-O
RC
-Te
chn
olo
gy-2
01
9.r
vt
RALPH S. O'CONNOR CENTERFOR RECREATION AND
WELL-BEING
JOHNS HOPKINS UNIVERSITY
18016
10/31/2019
JSC
JBC
JBC
TELECOM CABLING -GROUND FLOOR RCP T3.1
100% CONSTRUCTION DOCUMENTS
C 2019 GWWO INC.
1/8" = 1'-0"1
TELECOM CABLING - GROUND LEVEL RCP
8 0 8 16
SCALE OF FEET1/8" = 1'-0"
No. Date Description
SEC
SEC
SEC
CA
MS
EC
SEC
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
1a 1b
M
N
P
Q
R
R.2
S
U
V
W
X
Y
1716.9 16 14.814.7 14 12 10 8 7 5
3 L
J.8
J
G
E
C
B.5
A
26
2422.5
2220
1815
1311 9 6 4 2 1
B
D
F
H
K
1x2x
MEETING RM
248
MEMBERSHIP
SERVICES
245
VESTIBULE
240
LOBBY
241
INFORMATION
DESK
243
WAITING AREA
242
SMALL
MEETING
247
CARDIO
271
SHARED
OFFICE 3
250
SHARED
OFFICE 2
252
SHARED
OFFICE 1
253
WORK ROOM
251
OFFICE
E204
OFFICE
E211
OFFICE
E212
OFFICE
E205
OFFICE
E206
STORAGE
E209
STORAGE
E208aOFFICE
E208
KITCHEN
E207
OFFICE
E210
STAIR A
S201
JOGGING
ACCESS
E223
PUMP ROOM
220
JOGGING
TRACK
E219
STAIR B
S202
WOMENS
TOILET
E215
CORR
E213
MENS TOILET
E217
CUSTODIAN
E216
STRETCHING
E224
Room
E226 LOBBY
E214
CORRIDOR
246
MOTHER'S RM
280
STORAGE
265
CAFE STORAGE
263UNIV. W/C
260
CAFE
261
S.1
Seal:
GWWO INC.
800 WYMAN PARK DRIVE, SUITE 300
BALTIMORE, MARYLAND 21211, 410-332-1009
Revisions:
Job No.
Scale
Date
Drawing Title
Sheet
Drawn
Checked
Approved
Drawing Number
Of
Seal:
KEY PLAN:
1/8" = 1'-0"
10/2
9/2
019
12
:05:2
5 P
MB
IM 3
60://J
HU
O'C
onno
r R
ec C
ente
r A
dditio
n-R
eno
va
tio
n-2
019
/18
016
-JH
U-O
RC
-Te
chn
olo
gy-2
01
9.r
vt
RALPH S. O'CONNOR CENTERFOR RECREATION AND
WELL-BEING
JOHNS HOPKINS UNIVERSITY
18016
10/31/2019
JSC
JBC
JBC
TELECOM CABLING -SECOND FLOOR RCP T3.2
100% CONSTRUCTION DOCUMENTS
C 2019 GWWO INC.
1/8" = 1'-0"1
TELECOM CABLING - (ENTRANCE) SECOND LEVEL RCP
8 0 8 16
SCALE OF FEET1/8" = 1'-0"
No. Date Description
SEC
P
P
AP
AP AP AP
AP
AP
AP
AP
AP
AP
AP
1a 1b
M
N
P
Q
R
R.2
S
U
V
W
X
Y
1716.9 16 14.814.7 14 12 10 8 7 5
3 L
J.8
J
G
E
C
B.5
A
2422.5
2220
1815
1311 9 6 4 2 1
1x2x
CARDIO/WEIGHTS
326b
PROGRAM B
E310PROGRAM A
323
TEL
320
CORRIDOR
321
T4.1
5
LOBBY
E302
STAIR NO. 3
S301
STORAGE
E306
ROOF ACCESS
E307
ELEVATOR
EL301
WOMEN'S
TOILET
E305MEN'S TOILET
E304
CUSTODIAN
CLOSET
E303
LOUNGE
322
STORAGE B
310A
STORAGE A
323A
STAIR C
S303
S.1
Seal:
GWWO INC.
800 WYMAN PARK DRIVE, SUITE 300
BALTIMORE, MARYLAND 21211, 410-332-1009
Revisions:
Job No.
Scale
Date
Drawing Title
Sheet
Drawn
Checked
Approved
Drawing Number
Of
Seal:
KEY PLAN:
1/8" = 1'-0"
10/2
9/2
019
12
:11:1
9 P
MB
IM 3
60://J
HU
O'C
onno
r R
ec C
ente
r A
dditio
n-R
eno
va
tio
n-2
019
/18
016
-JH
U-O
RC
-Te
chn
olo
gy-2
01
9.r
vt
RALPH S. O'CONNOR CENTERFOR RECREATION AND
WELL-BEING
JOHNS HOPKINS UNIVERSITY
18016
10/31/2019
JSC
JBC
JBC
TELECOM CABLING -THIRD FLOOR RCP T3.3
100% CONSTRUCTION DOCUMENTS
C 2019 GWWO INC.
1/8" = 1'-0"1
TELECOM CABLING - THIRD LEVEL RCP
8 0 8 16
SCALE OF FEET1/8" = 1'-0"
No. Date Description
INSTALL (1) 12-STRAND SINGLEMODE (OS2) AND (1) 12-STRAND MULTIMODE (OM4) ARMORED OPTICAL FIBERCABLE FROM THE EXISTING MAIN TELECOM ROOM IN NEWTON, 277. IN THE MAIN TR 277, TERMINATE WITHLC CONNECTORS INSTALLED IN ADAPTER PANELS MOUNTED IN AN EXISTING FIBER HOUSING. IN THE NEWTELECOM ROOM, 320, TERMINATE WITH LC CONNECTORS INSTALLED IN ADAPTER PANELS MOUNTED IN ANEW FIBER HOUSING.
INSTALL (1) 100-PAIR CATEGORY 3 COPPER RISER CABLE FROM THE EXISTING MAIN TELECOM ROOM INNEWTON, 277. ON EACH END, TERMINATE ON A RACK-MOUNTED 24-PORT PATCH PANEL, 1-PAIR PER PORT(COIL 25TH PAIR).
TR E109(EXIST)
TR 320(NEW)
2
GROUND FLOOR
SECOND FLOOR
THIRD FLOOR
MAIN TR277
(EXIST)
1
2
1
EXISTING SECURITY PANELS
EXISTING SECURITY CABINET TO BE REMOVED; CONTACT JHU IT PRIOR TO
REMOVAL
EXISTING RACK
NEW RACK
EXISTING CABLE TRAY
EXISTING RACKS WITH VERTICAL MANAGERS
NEW CABLE AND EQUIPMENT RACK WITH VERTICAL MANAGERS
AREA FOR SECURITY PANEL(S)
FIRE-RETARDANT PLYWOOD (ALL WALLS)
TELECOM GROUNDING
BUSBAR (TGB)
110-TYPE BLOCKS
12" WIDE CABLE TRAY
ACCESSIBLE CEILING
MINIMUM 1" CONDUIT STUBBED TO ACCESSIBLE
CEILING (USE 1-1/4" CONDUIT FOR MORE THAN 7 CABLES)
DOUBLE-GANG BOX
SINGLE-GANGREDUCER RING
FISHABLE WALL
SINGLE-GANGFACEPLATE
42W 2
D
DS
AVR
AP
SEC
P
AVD
ROUTE MINIMUM 1" CONDUIT TO NEAREST ACCESSIBLE CEILING
FINISHED CEILNG (INACCESSIBLE GYP-BOARD)OR
NO FINISHED CEILING (OPEN)
FINISHED CEILING (ACCESSIBLE CEILING TILE)
SINGLE-GANG OUTLET BOX
EXISTING CABLE TRAY
ADD NEW CABLE TRAY
Seal:
GWWO INC.
800 WYMAN PARK DRIVE, SUITE 300
BALTIMORE, MARYLAND 21211, 410-332-1009
Revisions:
Job No.
Scale
Date
Drawing Title
Sheet
Drawn
Checked
Approved
Drawing Number
Of
Seal:
KEY PLAN:
As indicated
10/2
9/2
019
12
:05:4
0 P
MB
IM 3
60://J
HU
O'C
onno
r R
ec C
ente
r A
dditio
n-R
eno
va
tio
n-2
019
/18
016
-JH
U-O
RC
-Te
chn
olo
gy-2
01
9.r
vt
RALPH S. O'CONNOR CENTERFOR RECREATION AND
WELL-BEING
JOHNS HOPKINS UNIVERSITY
18016
10/31/2019
JSC
JBC
JBC
TELECOM CABLING -TR LAYOUTS, RISER,
AND INSTALL DETAILS T4.1
100% CONSTRUCTION DOCUMENTS
C 2019 GWWO INC.
1/4" = 1'-0"1
TELECOM CABLING - GROUND LEVEL -EXISTING TR E109
1/4" = 1'-0"3
TELECOM CABLING - SECOND LEVEL -EXISTING MAIN TR 277 (NEWTON BUILDING)
1/4" = 1'-0"4
TELECOM CABLING - THIRD LEVEL - NEW TR320
1/4" = 1'-0"5
TELECOM CABLING - THIRD LEVEL RCP -NEW TR 320 RCP
NTS6
TELECOM CABLING RISER DIAGRAM
NTS7
BOX AND CONDUIT INSTALLATION DETAILS
NTS9
TERMINATION DETAILS
NTS8
HARD/OPEN CEILING BOX AND CONDUIT DETAIL
1/4" = 1'-0"2
TELECOM CABLING - GROUND LEVEL -EXISTING TR E109 RCP
No. Date Description