1 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ General Needs Flatted Accommodation Fire Risk Assessment (FRA) Regulatory Reform (Fire Safety) Order 2005 Responsible person Chief Executive-London Borough of Newham Address of Premises 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ The Fire Risk Assessment was undertaken by The assessor detailed in the Assessment Summary below who has the necessary qualifications, competency and experience in Fire Risk Management that give him/her the status of “Competent Person” as described in articles 15 and 18 of the ‘Regulatory Reform (Fire Safety) Order 2005', for properties in England & Wales, and the 'Fire Safety (Scotland) Regulations 2006' for those in Scotland. This legislation now supersedes all previous fire legislation for England, Wales & Scotland and forms the ‘Fire Regulations'. Date of Survey 01/07/2017

Transcript of General Needs Flatted Accommodation Fire Risk Assessment ...

Page 1: General Needs Flatted Accommodation Fire Risk Assessment ...

1 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

General Needs Flatted Accommodation Fire Risk Assessment (FRA)

Regulatory Reform (Fire Safety) Order 2005

Responsible person Chief Executive-London Borough of Newham

Address of Premises

1-98 Aubrey Moore Point

Abbey Lane London E15 2RZ

The Fire Risk Assessment was undertaken by The assessor detailed in the Assessment Summary

below who has the necessary qualifications, competency and experience in Fire Risk

Management that give him/her the status of “Competent Person” as described in articles 15

and 18 of the ‘Regulatory Reform (Fire Safety) Order 2005', for properties in England & Wales,

and the 'Fire Safety (Scotland) Regulations 2006' for those in Scotland. This legislation now

supersedes all previous fire legislation for England, Wales & Scotland and forms the ‘Fire

Regulations'.

Date of Survey 01/07/2017

Page 2: General Needs Flatted Accommodation Fire Risk Assessment ...

2 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

TABLE OF CONTENTS

SECTION 1 Assessment Summary 2 Survey Drawings 3 Risk Assessment: Summary by Area 4 Risk Assessment Details 5 Assessment Paragraphs 6 Action Summary 7 Action Details

Page 3: General Needs Flatted Accommodation Fire Risk Assessment ...

3 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

SECTION ONE

ASSESSMENT SUMMARY

Page 4: General Needs Flatted Accommodation Fire Risk Assessment ...

4 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Assessment Summary

Asset Image

Site Address: 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Ownership: Newham

Date Due: 01/07/2017

Date Assessed: 01/07/2017

Person managing fire safety for the premises: Head of Housing Property & Initiatives

Uploaded by

Risk Level Moderate

Risk Description

It is essential that efforts are made to reduce the risk. Risk reduction measures should be implemented within a defined time period. Where moderate risk is associated with consequences that constitute extreme harm, further assessment might be required to establish more precisely the likelihood of harm as a basis for determining the priority for improved control measures.

Validated By

(Where Applicable)

Surveyed By Assessment Notes:

This assessment was undertaken by

98 residential flats, 22 floors, 2 staircases and 2no fireman's lifts. There is a concierge on site. Parking bays round the block. Front entrance and 2no side exits. Play area in front of the block. Tenants room on the 1st floor

Page 5: General Needs Flatted Accommodation Fire Risk Assessment ...

5 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

The purpose of this report is to provide an assessment of the risk to life from fire in these premises,

and, where appropriate, to make recommendations to ensure compliance with fire safety legislation.

The report does not address the risk to property or business continuity from fire. If you have any

questions about this Fire Risk Assessment please contact:

Direct House, Bridge Road Depot, Abbey Road, London E15 3LX

This Fire Risk Assessment should be reviewed by a competent person if it is no longer valid, or if there has been a significant

change in the matters to which it relates, or if a fire occurs.

1. Introduction This report has been prepared as a written record of the Fire Risk Assessment, carried out at 1-

98, Aubrey Moore Point, Abbey Lane, , London under the requirements of the Regulatory

Reform (Fire Safety) Order 2005.

1.1 The objectives of this Fire Risk Assessment are: a. To identify all current significant fire hazards to which relevant persons on the premises,

or in the immediate vicinity of the premises, will be exposed.

b. To reasonably quantify the level of residual fire risk that is attributed to the premises

and its use, with regard to existing (preventive and protective) controlling measures.

c. To advise on the nature and extent of any additional (preventive and protective)

controlling measures which should be implemented in order to counteract this residual

risk, in accordance with the ‘Principles of Prevention’ as defined in Article 10 of The

Regulatory Reform (Fire Safety) Order 2005.

1.2 Risk Assessments Risk Assessments are not a ‘one off’ activity, and are part of a dynamic process. It is thus a

requirement under Article 9(3) of The Regulatory Reform (Fire Safety) Order 2005 to review and

modify the risk assessment when either:

a. There is reason to suspect that it is no longer valid, perhaps due to a gradual change in

the nature of the tenancy numbers or type, wear & tear on facilities, a large number of

small changes, an appreciation of a hazard (e.g. highlighted by fire evacuation drill), or

b. the occurrence of an incident (e.g. actual fire or near miss), which triggers a need to

review, OR there is a significant change in the matters to which it relates, (i.e. following

major organisational changes or any refurbishment, alterations or extension).

1.3 This Risk Assessment This risk assessment is a ‘dynamic’ working document that should be used as a guide to

planning future actions aimed at improving Health & Safety for tenants and others who may be

affected by a potential fire at the premise. Notwithstanding the requirements noted in Section

1.2 above, it is a requirement of London Borough of Newham that Fire Risk Assessments are

normally reviewed annually, unless otherwise advised by the Fire Risk Assessment report. Some

reasonable flexibility is permitted to accommodate logistical and financial constraints.

Page 6: General Needs Flatted Accommodation Fire Risk Assessment ...

6 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Scope and Methodology

1.4 Statutory Requirement

Article 9 of The Regulatory Reform (Fire Safety) Order 2005 requires every responsible person

to make a suitable and sufficient assessment of the fire risks to which relevant persons are

exposed, with respect to premises within their control. This is for the purpose of identifying the

general fire precautions that are needed to comply with the requirements and prohibitions

imposed by the Order. The responsible person, or any other person who has to any extent

control of the premises, must ensure that the duties imposed by the relevant articles of The

Regulatory Reform (Fire Safety) Order 2005 are complied with in respect of those premises, so

far as the requirements relate to matters within their control. Where the premises are licensed,

an alterations notice is in force, or the responsible person has five or more employees, it is a

requirement to record the significant findings of the fire risk assessment including the measures

which have been or will be taken as a result of the assessment and details of any group of

persons identified by the assessment as being especially at risk. This report therefore

incorporates such relevant information, significant findings and recommended actions that are

considered necessary to demonstrate compliance with The Regulatory Reform (Fire Safety)

Order 2005.

1.5 Identification of Fire Hazards

In order to identify the significant fire hazards within the premise, a checklist is used which

considers the particular fire hazards associated with this type of building and the nature of the

occupancy. The hazard identification process will consider each item with due regard to the

existing ‘control measures’, which are either already inherent within the building fabric design

or are implemented through the management policy procedures for the premise. The answers

to all questions should be YES, NO or NOT APPLICABLE (Na).

1.6 Assessment of Fire Risk

Each identified hazard is assessed in accordance with the fire risk-rating matrix detailed in

Section 4.0 of this report. This matrix has due regard to the person or group of persons who are

likely to be affected by each hazard, by considering the hazards in terms of their potential to

harm (severity) and their likelihood (probability) of actually occurring. The matrix allows the

assignment of a specific risk rating for each perceived hazard, which subsequently assists in

determining the nature and extent of any necessary additional controlling measures, (both

physical and procedural deficiencies), as well as the timescale in which these measures should

be reasonably implemented.

Page 7: General Needs Flatted Accommodation Fire Risk Assessment ...

7 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

1.7 The Fire Risk Assessment Action Schedule

This Action Schedule details the blend of technical and procedural measures, which are

considered necessary to adequately address the residual risk that has been previously

identified, semi-quantified and assigned a ‘risk-rating’. This risk control plan is essentially an

inventory of remedial / advisory actions which should be carried out by London Borough of

Newham Group or an appointed representative, within the recommended timescales. These

timescales are suggested purely to aid reasonable implementation of the Action Schedule, but

for the residual risk to be reduced to an acceptable level, it will be necessary to implement all

Action Items on the schedule. It is a requirement of London Borough of Newham that P1

timescales may not be exceeded without the recorded authorisation of a senior manager, Head

of Department or a Director.

1.8 Information Source

Information for the completion of this assessment was obtained by a semi non-invasive physical

inspection of the premise, inspection of records and drawings (where available). For accurate

identification of hazard location, digital photographs are enclosed to ‘pin-point’ the specified

hazard.

Page 8: General Needs Flatted Accommodation Fire Risk Assessment ...

8 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

SECTION TWO

ASSESSMENT ATTACHMENTS

Page 9: General Needs Flatted Accommodation Fire Risk Assessment ...

9 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

2. Survey Drawings and Documentation

2.1 Information Source

Information for the completion of this assessment was obtained by a semi non-invasive physical

inspection of the premise, inspection of records and drawings (where available). For accurate

identification of hazard location, digital photographs are enclosed to ‘pin-point’ the specified

hazard.

Page 10: General Needs Flatted Accommodation Fire Risk Assessment ...

10 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

SECTION THREE

RISK ASSESSMENT: SUMMARY BY AREA

Page 11: General Needs Flatted Accommodation Fire Risk Assessment ...

11 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

3. Risk Assessment: Summary by Area

Risk Assessment: Summary by Area

Area Risk Category Question Answer Probability Severity Risk Action Due

All Areas Arson - Fire Load 1. Is fire load close to the premises minimised?

No 2 2 Moderate (4) 01/08/2017

All Areas Arson - Security 2. Are premises adequately secured against potential arson?

No 2 2 Moderate (4) 01/08/2017

All Areas Arson - Security 3. Are there suitably located and secured provisions for the disposal of waste and recyclable material?

No 2 2 Moderate (4) 01/08/2017

All Areas Combustible Materials - Housekeeping

4. Are any potential combustible materials adequately segregated from any sources of ignition?

No 2 2 Moderate (4) 01/08/2017

All Areas Combustible Materials - Housekeeping

5. Are quantities of combustible waste allowed to accumulate in the premises such as Paper, cardboard, wood shavings, dust?

Yes 2 2 Moderate (4) 01/08/2017

All Areas Fire Detection - Alarms 6. Are fire alarm tests recorded? Na 0 0 Trivial (0) 01/07/2018

All Areas Fire Detection - Alarms 7. Is automatic detection and/or manual alarm provided in the premises? If yes, describe system.

No 1 1 Tolerable (1) 01/04/2018

Page 12: General Needs Flatted Accommodation Fire Risk Assessment ...

12 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

All Areas Fire Detection - Alarms 8. Is further automatic detection and/or manual alarm provision required? If yes, state what.

No 0 0 Trivial (0) 01/07/2018

All Areas Fire Detection - Alarms 9. Is the alarm system adequately maintained?

Na 0 0 Trivial (0) 01/07/2018

All Areas Fire Detection - Alarms Q10. Is the fire alarm system in working order?

Na 0 0 Trivial (0) 01/07/2018

All Areas Fire Fighting Equipment - Entry 11. Is the fireman's switch working correctly?

Yes 0 0 Trivial (0) 01/07/2018

All Areas Fire Fighting Equipment - Extinguishers

12. Are fire extinguishers adequately maintained?

Yes 0 0 Trivial (0) 01/07/2018

All Areas Fire Fighting Equipment - Extinguishers

13. Are other fire extinguishing systems provided/accessible and in good working condition?

Na 0 0 Trivial (0) 01/07/2018

All Areas Fire Fighting Equipment - Extinguishers

14. Are portable fire extinguishers provided/accessible and in good working condition?

No 2 2 Moderate (4) 01/10/2017

All Areas Fire Fighting Equipment - Other 15. Are all bin chamber doors secure? Yes 0 0 Trivial (0) 01/07/2018

All Areas Fire Fighting Equipment - Risers 16. Are dry/wet risers in good order? Yes 0 0 Trivial (0) 01/07/2018

All Areas Fire Fighting Equipment - Risers 17. Are rising mains adequately maintained?

Na 0 0 Trivial (0) 01/07/2018

All Areas Flammable Substances - Housekeeping

18. Are there any highly flammable substances in the premises?

No 0 0 Trivial (0) 01/07/2018

All Areas General Hazards - Any Other Issues

19. Are there any other issues? Please specify

Yes 2 2 Moderate (4) 01/10/2017

All Areas Limiting Fire Spread - Compartmentation

20. Are any installed linings appropriate for limiting the spread of

No 2 2 Moderate (4) 01/10/2017

Page 13: General Needs Flatted Accommodation Fire Risk Assessment ...

13 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

fire?

All Areas Limiting Fire Spread - Compartmentation

21. Is the current level of compartmentation adequate for the premise?

No 2 2 Moderate (4) 01/08/2017

All Areas Limiting Fire Spread - Dampers 22. Where required, are dampers provided?

Yes 0 0 Trivial (0) 01/07/2018

All Areas Maintenance Checks - General 23. Are appropriate building maintenance checks undertaken regularly?

No 2 2 Moderate (4) 01/10/2017

All Areas Maintenance Checks - General 24. Are lifts adequately maintained? Yes 0 0 Trivial (0) 01/07/2018

All Areas Maintenance Checks - General 25. Are the premises generally well maintained?

Yes 2 2 Moderate (4) 01/10/2017

All Areas Maintenance Checks - General 26. Have all installed or portable electrical appliances been tested in accordance with regulations?

Yes 2 2 Moderate (4) 01/10/2017

All Areas Maintenance Checks - General 27. Is the lightning protection system adequately maintained?

Yes 0 0 Trivial (0) 01/07/2018

All Areas Maintenance Checks - General 28. Is the sprinkler system adequately maintained?

Na 0 0 Trivial (0) 01/07/2018

All Areas Means Of Escape - Lighting 29. Are all exits and exit routes adequately illuminated (internal and external)?

Yes 0 0 Trivial (0) 01/07/2018

All Areas Means Of Escape - Lighting 30. Are any other areas as required adequately illuminated?

Yes 0 0 Trivial (0) 01/07/2018

All Areas Means Of Escape - Lighting 31. Are emergency escape lighting tests recorded?

Yes 0 0 Trivial (0) 01/07/2018

Page 14: General Needs Flatted Accommodation Fire Risk Assessment ...

14 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

All Areas Means Of Escape - Lighting 32. Is the emergency escape lighting adequately maintained?

No 2 2 Moderate (4) 01/10/2017

All Areas Means Of Escape - Lighting 33. Where fitted, is the emergency escape lighting in good working order?

No 2 2 Moderate (4) 01/10/2017

All Areas Means Of Escape - Routes 34. Are all escape routes clear and unobstructed?

No 2 2 Moderate (4) 01/10/2017

All Areas Means Of Escape - Routes 35. Are all floors free from slipping/tripping hazards?

No 2 2 Moderate (4) 01/10/2017

All Areas Means Of Escape - Routes 36. Are corridors sub-divided (where appropriate)?

Yes 0 0 Trivial (0) 01/07/2018

All Areas Means Of Escape - Routes 37. Are doors on escape routes easily opened and do they open in the correct direction?

Yes 0 0 Trivial (0) 01/07/2018

All Areas Means Of Escape - Routes 38. Are there reasonable arrangements in the building for means of escape for disabled people?

Yes 0 0 Trivial (0) 01/07/2018

All Areas Means Of Escape - Routes 39. Are travel distances to fire exits satisfactory - single and two-way?

Yes 0 0 Trivial (0) 01/07/2018

All Areas Means Of Escape - Routes 40. Do all escape routes lead to a place of safety?

Yes 0 0 Trivial (0) 01/07/2018

All Areas Means Of Escape - Routes 41. Does the escape route design meet the necessary Home Office guidelines?

Yes 0 0 Trivial (0) 01/07/2018

All Areas Means Of Escape - Routes 42. Is adequate separation evident on all escape routes (as appropriate)?

Yes 0 0 Trivial (0) 01/07/2018

All Areas Means Of Escape - Routes 43. Is the number and provision of exits adequate?

Yes 0 0 Trivial (0) 01/07/2018

All Areas Means Of Escape - Routes 44. Is there adequate protection provided/installed to all escape routes?

Yes 0 0 Trivial (0) 01/07/2018

Page 15: General Needs Flatted Accommodation Fire Risk Assessment ...

15 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

All Areas Means Of Escape - Signage 45. Are signs clearly visible and not obstructed?

Yes 0 0 Trivial (0) 01/07/2018

All Areas Means Of Escape - Signage 46. Is there adequate provision of fire safety signs and notices?

No 2 2 Moderate (4) 01/10/2017

All Areas Other Issues - General 47. Are there any other issues to specify?

Yes 2 2 Moderate (4) 01/10/2017

All Areas Premises Management - Records And Security

48. Are there appropriate fire safety procedures in place?

Yes 0 0 Trivial (0) 01/07/2018

All Areas Premises Management - Records And Security

49. Are there provisions in place for liaison to take place with the local fire and rescue service?

Yes 0 0 Trivial (0) 01/07/2018

All Areas Premises Management - Records And Security

50. Is there an available and suitable record of fire safety arrangements?

No 2 2 Moderate (4) 01/08/2017

All Areas Records - Fire Maintenance 51. Are fire safety maintenance records available for the premises?

No 2 2 Moderate (4) 01/08/2017

All Areas Sources Of Ignition - Smoking 52. Is there evidence of any smoking related activities taking place in non designated areas?

No 0 0 Trivial (0) 01/07/2018

All Areas Training - Evacuation 53. Where fire evacuation safety drills are considered appropriate, are they carried out at regular intervals?

Na 0 0 Trivial (0) 01/07/2018

All Areas Training - Trained Personnel 54. Are staff trained in fire safety via induction and/or annual refreshers?

No 2 2 Moderate (4) 01/10/2017

All Areas Training - Trained Personnel 55. Is fire safety training recorded? Yes 0 0 Trivial (0) 01/07/2018

Page 16: General Needs Flatted Accommodation Fire Risk Assessment ...

16 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

SECTION FOUR

RISK ASSESSMENT DETAILS

Page 17: General Needs Flatted Accommodation Fire Risk Assessment ...

17 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

4. Risk Assessment Details

4.1 Fire Risk Rating Matrix

The following risk rating matrix is used to enable semi-quantification of the itemised fire safety deficiencies (hazards) that were found during the recent survey of the premise.

The matrix allows the identified significant fire hazards to be classified in terms of the harmful or unwanted consequences (severity) that the hazard would cause, if it were to occur and also the likelihood (probability) that such harm will occur. These factors are considered with due regard to the existing fire safety features and procedures (controlling measures), which are either incorporated within the building design or procedurally implemented within the premise.

Risk Control Plan

Score Degree Consequence

0 Trivial No action is required and no detailed records need to be kept.

1-3 Tolerable No major additional controls required. However, there might be a need for improvements that involve minor or limited cost.

4 Moderate

It is essential that efforts are made to reduce the risk. Risk reduction measures should be implemented within a defined time period. Where moderate risk is associated with consequences that constitute extreme harm, further assessment might be required to establish more precisely the likelihood of harm as a basis for determining the priority for improved control measures.

6 Substantial

Considerable resources might have to be allocated to reduce the risk. If the building is unoccupied, it should not be occupied until the risk has been reduced. If the building is occupied, urgent action should be taken.

9 Intolerable Building (or relevant area) should not be occupied until the risk is reduced.

Severity

Pro

bab

ility

0 1 2 3

0 0 0 0 0

1 0 1 2 3

2 0 2 4 6

3 0 3 6 9

Page 18: General Needs Flatted Accommodation Fire Risk Assessment ...

18 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Probability Level

Level Degree Probability of Exposure to Harm 0 Very Low Risk No known instances of such an event occurring 1 Low Risk Unlikely to occur, but still possible 2 Medium Risk Likely to occur at some stage in the foreseeable future 3 Very High Risk Very likely to occur frequently and/or in the near future unless actively prevented

The product of the severity and probability factors will equate to a specific risk rating for each identified hazard. The following band matrix can then be used to assign a comparative degree of risk (Very Low , Low, Medium or Very High) to each individual fire safety deficiency. This will assist in determining the extent of any necessary additional controlling measures, as well as the timescale in which these measures should be implemented.

4.2 Assessment of Fire Risk

The table details the systematic approach that has been taken to assess the individual level of risk

that is inherent in each identified hazard / fire safety deficiency, recorded during the inspection of

this premise.

Each hazard (item) has been considered with regard to the specific group of people that it threatens;

its potential severity and its probability of being realised. Existing control measures are taken into

account before determining the nature and extent of any additional control measures deemed

necessary to contend with the residual fire risk that remains.

The table below provides timescales for remedial action proportionate to the risk.

Degree of Risk Risk Rating Score Priority Level for Action

Timescales for Remedial Action ( maximum time limits )

Very High Risk 9 P1 Within 1 Week

High Risk 6 P2 Within 3 Months

Medium Risk 4 P3 Within 6 months

Low Risk 1 to 3 P4 Within 9 months

Very Low Risk 0 to 0 P5 As required

The Action Items contained in Section 6 of this report, details the optimum measures that are considered necessary.

Page 19: General Needs Flatted Accommodation Fire Risk Assessment ...

19 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

4.3 Sheltered Accommodation Containing Vulnerable Persons

The same method is used but the overall fire risk rating is adjusted up one level. For example, if the

individual risk ratings on the itemised schedule is a Low Risk then the fire risk rating for the premises

is categorised as Moderate Risk.

4.4 Exceptional Circumstances

Where the assessor risk or receiving manager feels the method of calculation has arrived at a grossly

disproportionate fire risk rating, the matter should be referred to the Director for consideration and

advice.

4.5 Extent of Common Areas

Internal and External Communal areas including but not limited to the following: Entrances, Exits , Escape Stairs, Landings, Lobbies, Electrical Intake/service cupboards, Pram shed areas, Refuse areas. 4.6 How are occupants who warrant special consideration identified?

In the event of an emergency any vulnerability information is obtainable from the Housing

database which is available to the LBN Emergency Officer.

Page 20: General Needs Flatted Accommodation Fire Risk Assessment ...

20 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Question Details

Area All Areas

Risk Category Arson - Fire Load

Question 1. Is fire load close to the premises minimised?

Answer Title No

Question Notes 1.Refuse/recycling bins AND BULK WASTE must not be stored directly adjacent to the building .

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Date Action Due 01/08/2017

Documents

Pic 1

Pic 1a

Page 21: General Needs Flatted Accommodation Fire Risk Assessment ...

21 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Question Details

Area All Areas

Risk Category Arson - Security

Question 2. Are premises adequately secured against potential arson?

Answer Title No

Question Notes External garage door lock had been breached - rough sleeper present - forwarded to supervisor to arrange for door to be secured.(pic 2)

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Date Action Due 01/08/2017

Documents

Pic 2

Question Details

Area All Areas

Risk Category Arson - Security

Question 3. Are there suitably located and secured provisions for the disposal of waste and recyclable material?

Answer Title No

Question Notes Refer Q1

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Date Action Due 01/08/2017

Page 22: General Needs Flatted Accommodation Fire Risk Assessment ...

22 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Documents

Question Details

Area All Areas

Risk Category Combustible Materials - Housekeeping

Question 4. Are any potential combustible materials adequately segregated from any sources of ignition?

Answer Title No

Question Notes Combustibles found in service riser cupboards( some removed at time of inspection - concierge informed)

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Date Action Due 01/08/2017

Documents

Question Details

Area All Areas

Risk Category Combustible Materials - Housekeeping

Question 5. Are quantities of combustible waste allowed to accumulate in the premises such as Paper, cardboard, wood shavings, dust?

Answer Title Yes

Question Notes EXCESSIVE AMOUNT OF COMBUSTIBLES OUTSIDE INCLUDING PLASTIC WHEELIE BIN AND ARMCHAIR - PHONED SUPERVISOR TO REMOVE AND ESCALATED TO ENFORCEMENT /COMPLIANCE. Combustibles are being stored by tenants in communal areas.

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Date Action Due 01/08/2017

Documents

Pic 4

Page 23: General Needs Flatted Accommodation Fire Risk Assessment ...

23 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Pic 5

Pic 5a

Pic 5c

Page 24: General Needs Flatted Accommodation Fire Risk Assessment ...

24 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Pic 5e

Pic 5f

Pic 5d

Page 25: General Needs Flatted Accommodation Fire Risk Assessment ...

25 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Question Details

Area All Areas

Risk Category Fire Detection - Alarms

Question 6. Are fire alarm tests recorded?

Answer Title Na

Question Notes no alarm system

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category Fire Detection - Alarms

Question 7. Is automatic detection and/or manual alarm provided in the premises? If yes, describe system.

Answer Title No

Question Notes

Probability 1

Severity 1

Score 1

Risk Tolerable (1)

Date Action Due 01/04/2018

Page 26: General Needs Flatted Accommodation Fire Risk Assessment ...

26 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Documents

Question Details

Area All Areas

Risk Category Fire Detection - Alarms

Question 8. Is further automatic detection and/or manual alarm provision required? If yes, state what.

Answer Title No

Question Notes

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category Fire Detection - Alarms

Question 9. Is the alarm system adequately maintained?

Answer Title Na

Question Notes

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category Fire Detection - Alarms

Question Q10. Is the fire alarm system in working order?

Answer Title Na

Question Notes

Probability 0

Severity 0

Page 27: General Needs Flatted Accommodation Fire Risk Assessment ...

27 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category Fire Fighting Equipment - Entry

Question 11. Is the fireman's switch working correctly?

Answer Title Yes

Question Notes

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category Fire Fighting Equipment - Extinguishers

Question 12. Are fire extinguishers adequately maintained?

Answer Title Yes

Question Notes Fire extinguishers in concierge are in date and correctly sited (pic 12) Tenants room not accessed.

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Pic 12

Page 28: General Needs Flatted Accommodation Fire Risk Assessment ...

28 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Question Details

Area All Areas

Risk Category Fire Fighting Equipment - Extinguishers

Question 13. Are other fire extinguishing systems provided/accessible and in good working condition?

Answer Title Na

Question Notes

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category Fire Fighting Equipment - Extinguishers

Question 14. Are portable fire extinguishers provided/accessible and in good working

Page 29: General Needs Flatted Accommodation Fire Risk Assessment ...

29 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

condition?

Answer Title No

Question Notes No fire extinguishers observed in plant rooms

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Date Action Due 01/10/2017

Documents

Question Details

Area All Areas

Risk Category Fire Fighting Equipment - Other

Question 15. Are all bin chamber doors secure?

Answer Title Yes

Question Notes

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category Fire Fighting Equipment - Risers

Question 16. Are dry/wet risers in good order?

Answer Title Yes

Question Notes All dry risers were inspected and seals in place.(pic 16) Tested 18/10/2016

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Page 30: General Needs Flatted Accommodation Fire Risk Assessment ...

30 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Question Details

Area All Areas

Risk Category Fire Fighting Equipment - Risers

Question 17. Are rising mains adequately maintained?

Answer Title Na

Question Notes All dry risers were inspected and seals in place.(pic 16) Tested 18/10/2016

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category Flammable Substances - Housekeeping

Question 18. Are there any highly flammable substances in the premises?

Answer Title No

Question Notes

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category General Hazards - Any Other Issues

Question 19. Are there any other issues? Please specify

Answer Title Yes

Question Notes 1. Ground floor service riser cupboards - overhead cables are poorly secure. 2.Tenants room unable to access

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Page 31: General Needs Flatted Accommodation Fire Risk Assessment ...

31 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Date Action Due 01/10/2017

Documents

19

19a

19b

Page 32: General Needs Flatted Accommodation Fire Risk Assessment ...

32 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Question Details

Area All Areas

Risk Category Limiting Fire Spread - Compartmentation

Question 20. Are any installed linings appropriate for limiting the spread of fire?

Answer Title No

Question Notes

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Date Action Due 01/10/2017

Documents

20

20a

Page 33: General Needs Flatted Accommodation Fire Risk Assessment ...

33 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

20b

20c

20d

Page 34: General Needs Flatted Accommodation Fire Risk Assessment ...

34 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

20e

20f

Page 35: General Needs Flatted Accommodation Fire Risk Assessment ...

35 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

20g

20h

Page 36: General Needs Flatted Accommodation Fire Risk Assessment ...

36 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Question Details

Area All Areas

Risk Category Limiting Fire Spread - Compartmentation

Question 21. Is the current level of compartmentation adequate for the premise?

Answer Title No

Question Notes 1.PRIOR TO COMMENCING ANY WORKS ON STAIRWELL DOORS CONFIRMATION IS REQUIRED THAT THEY MEET FD30 STANDARD (REFER pic21e) . Fire doors/closures in the following locations require easing/adjusting to ensure door close flush to frame or other wise stated in actions. 2. Fire stopping required in several areas - details in actions. Some cover panels missing in riser cupboards. Excessive use of foam observed throughout. 3. Several GERDA flat front doors missing letter boxes 4. Ground floor stairwell door to lift lobby - unable to confirm fire resistant glass panels. Examples of good fire stopping within service riser/cupboard (pics 21r,s,t,u )

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Date Action Due 01/08/2017

Documents

21

Page 37: General Needs Flatted Accommodation Fire Risk Assessment ...

37 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

21a

Page 38: General Needs Flatted Accommodation Fire Risk Assessment ...

38 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

21b

21c

21d

21e

Page 39: General Needs Flatted Accommodation Fire Risk Assessment ...

39 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

21f

21g

21h

Page 40: General Needs Flatted Accommodation Fire Risk Assessment ...

40 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

21i

21j

21k

Page 41: General Needs Flatted Accommodation Fire Risk Assessment ...

41 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

21l

21m

Page 42: General Needs Flatted Accommodation Fire Risk Assessment ...

42 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

21n

21o

Page 43: General Needs Flatted Accommodation Fire Risk Assessment ...

43 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

21q

21r

21s

Page 44: General Needs Flatted Accommodation Fire Risk Assessment ...

44 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

21t

21u

Question Details

Area All Areas

Risk Category Limiting Fire Spread - Dampers

Page 45: General Needs Flatted Accommodation Fire Risk Assessment ...

45 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Question 22. Where required, are dampers provided?

Answer Title Yes

Question Notes Chute room ground floor - there are 2 chutes - UNABLE TO CONFIRM dampers activated by fusible links are present .

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

22

Question Details

Area All Areas

Risk Category Maintenance Checks - General

Question 23. Are appropriate building maintenance checks undertaken regularly?

Answer Title No

Question Notes 1.Tenants room not access to check fixed electrical equipment . 2. Numerous ceiling wire trunking covers throughout have dropped or missing screws. 3. Twin door service risers on each floor have incorrect top bolt which drops down allowing doors to be accessed and combustibles dumped inside.

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Date Action Due 01/10/2017

Page 46: General Needs Flatted Accommodation Fire Risk Assessment ...

46 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Documents

23

23a

23b

23c

Page 47: General Needs Flatted Accommodation Fire Risk Assessment ...

47 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

23d

Question Details

Area All Areas

Risk Category Maintenance Checks - General

Question 24. Are lifts adequately maintained?

Answer Title Yes

Question Notes

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Page 48: General Needs Flatted Accommodation Fire Risk Assessment ...

48 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Question Details

Area All Areas

Risk Category Maintenance Checks - General

Question 25. Are the premises generally well maintained?

Answer Title Yes

Question Notes

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Date Action Due 01/10/2017

Documents

Question Details

Area All Areas

Risk Category Maintenance Checks - General

Question 26. Have all installed or portable electrical appliances been tested in accordance with regulations?

Answer Title Yes

Question Notes Tenants room not accessed

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Date Action Due 01/10/2017

Documents

Question Details

Area All Areas

Risk Category Maintenance Checks - General

Question 27. Is the lightning protection system adequately maintained?

Answer Title Yes

Question Notes Tested 27/01/2015

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Page 49: General Needs Flatted Accommodation Fire Risk Assessment ...

49 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Documents

Question Details

Area All Areas

Risk Category Maintenance Checks - General

Question 28. Is the sprinkler system adequately maintained?

Answer Title Na

Question Notes

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category Means Of Escape - Lighting

Question 29. Are all exits and exit routes adequately illuminated (internal and external)?

Answer Title Yes

Question Notes Emergency lighting fitted to lobbies/ staircases/external (pic 29)

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

29

Page 50: General Needs Flatted Accommodation Fire Risk Assessment ...

50 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

29a

29b

Question Details

Area All Areas

Risk Category Means Of Escape - Lighting

Page 51: General Needs Flatted Accommodation Fire Risk Assessment ...

51 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Question 30. Are any other areas as required adequately illuminated?

Answer Title Yes

Question Notes

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category Means Of Escape - Lighting

Question 31. Are emergency escape lighting tests recorded?

Answer Title Yes

Question Notes Tested 01/04/2016. 2017 Programme under way.

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category Means Of Escape - Lighting

Question 32. Is the emergency escape lighting adequately maintained?

Answer Title No

Question Notes Ceiling light covers were missing or dropped.

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Date Action Due 01/10/2017

Documents

Page 52: General Needs Flatted Accommodation Fire Risk Assessment ...

52 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Question Details

Area All Areas

Risk Category Means Of Escape - Lighting

Question 33. Where fitted, is the emergency escape lighting in good working order?

Answer Title No

Question Notes As per Q32.

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Date Action Due 01/10/2017

Documents

Question Details

Area All Areas

Risk Category Means Of Escape - Routes

Question 34. Are all escape routes clear and unobstructed?

Answer Title No

Question Notes EXTREME Storage of bulk items belonging to - called supervisor to remove asap. , bikes & scooters (outside flats ), armchair, wheelie bin, Tesco trollies stored by ground floor staircase and other items would impede safe means of egress.(pics 34,a,b,c)(also pics 5,a,b,c)

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Date Action Due 01/10/2017

Documents

5

Page 53: General Needs Flatted Accommodation Fire Risk Assessment ...

53 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

5a

5c

5f

Page 54: General Needs Flatted Accommodation Fire Risk Assessment ...

54 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Question Details

Area All Areas

Risk Category Means Of Escape - Routes

Question 35. Are all floors free from slipping/tripping hazards?

Answer Title No

Question Notes 1.refer Q34 also opposite - metal sit up bar has been screwed to storage cupboard presenting trip hazard. (pic 34d) 2. External - uneven paving slabs present risk of STF's (pic 35a)

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Date Action Due 01/10/2017

Documents

35

Page 55: General Needs Flatted Accommodation Fire Risk Assessment ...

55 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

35a

Question Details

Area All Areas

Risk Category Means Of Escape - Routes

Question 36. Are corridors sub-divided (where appropriate)?

Answer Title Yes

Question Notes Twin - lobby doors installed (pic 36)

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

36

Page 56: General Needs Flatted Accommodation Fire Risk Assessment ...

56 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Question Details

Area All Areas

Risk Category Means Of Escape - Routes

Question 37. Are doors on escape routes easily opened and do they open in the correct direction?

Answer Title Yes

Question Notes

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category Means Of Escape - Routes

Question 38. Are there reasonable arrangements in the building for means of escape for disabled people?

Answer Title Yes

Question Notes LBN, in liaison with London Fire Brigade, have a stay put policy.

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category Means Of Escape - Routes

Question 39. Are travel distances to fire exits satisfactory - single and two-way?

Answer Title Yes

Question Notes

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Page 57: General Needs Flatted Accommodation Fire Risk Assessment ...

57 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category Means Of Escape - Routes

Question 40. Do all escape routes lead to a place of safety?

Answer Title Yes

Question Notes

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category Means Of Escape - Routes

Question 41. Does the escape route design meet the necessary Home Office guidelines?

Answer Title Yes

Question Notes

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category Means Of Escape - Routes

Question 42. Is adequate separation evident on all escape routes (as appropriate)?

Answer Title Yes

Page 58: General Needs Flatted Accommodation Fire Risk Assessment ...

58 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Question Notes

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category Means Of Escape - Routes

Question 43. Is the number and provision of exits adequate?

Answer Title Yes

Question Notes

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category Means Of Escape - Routes

Question 44. Is there adequate protection provided/installed to all escape routes?

Answer Title Yes

Question Notes

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Page 59: General Needs Flatted Accommodation Fire Risk Assessment ...

59 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Question Details

Area All Areas

Risk Category Means Of Escape - Signage

Question 45. Are signs clearly visible and not obstructed?

Answer Title Yes

Question Notes Examples of signage (pics 45, a,b,c,d,e)

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

45

45a

Page 60: General Needs Flatted Accommodation Fire Risk Assessment ...

60 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

45b

45c

Page 61: General Needs Flatted Accommodation Fire Risk Assessment ...

61 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

45d

45e

Page 62: General Needs Flatted Accommodation Fire Risk Assessment ...

62 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

45f

45g

Page 63: General Needs Flatted Accommodation Fire Risk Assessment ...

63 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Question Details

Area All Areas

Risk Category Means Of Escape - Signage

Question 46. Is there adequate provision of fire safety signs and notices?

Answer Title No

Question Notes Numerous fire action signs by lift call points missing or becoming unfixed and do not meet BS 5499 .

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Date Action Due 01/10/2017

Documents

Question Details

Area All Areas

Risk Category Other Issues - General

Question 47. Are there any other issues to specify?

Page 64: General Needs Flatted Accommodation Fire Risk Assessment ...

64 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Answer Title Yes

Question Notes Q47. 1.Flats either full access gained - flat front doors check - where access was gained smoke alarms tested and bathrooms , kitchens , cupboards where possible were inspected for any breaches in compartmentation. Example of good fire stopping in kitchen cupboard within a flat (pics47,a,b) 2.High number of GERDA FD30S doors where door closures had been removed . 3.Some fire internal fire alarms were not present in LEASEHOLD FLATS. 4.1st floor riser cupboard there is a small water heater permanently switched on - could possibly feed tenants room or concierge lodge.

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Date Action Due 01/10/2017

Documents

47

47a

Page 65: General Needs Flatted Accommodation Fire Risk Assessment ...

65 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

47b

47c

47d

Page 66: General Needs Flatted Accommodation Fire Risk Assessment ...

66 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Question Details

Area All Areas

Risk Category Premises Management - Records And Security

Question 48. Are there appropriate fire safety procedures in place?

Answer Title Yes

Question Notes

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category Premises Management - Records And Security

Question 49. Are there provisions in place for liaison to take place with the local fire and rescue service?

Answer Title Yes

Question Notes

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Page 67: General Needs Flatted Accommodation Fire Risk Assessment ...

67 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Documents

Question Details

Area All Areas

Risk Category Premises Management - Records And Security

Question 50. Is there an available and suitable record of fire safety arrangements?

Answer Title No

Question Notes

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Date Action Due 01/08/2017

Documents

Question Details

Area All Areas

Risk Category Records - Fire Maintenance

Question 51. Are fire safety maintenance records available for the premises?

Answer Title No

Question Notes

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Date Action Due 01/08/2017

Documents

Question Details

Area All Areas

Risk Category Sources Of Ignition - Smoking

Question 52. Is there evidence of any smoking related activities taking place in non designated areas?

Answer Title No

Question Notes Evidence of smoking in stairwells.(pic 52)

Probability 0

Severity 0

Page 68: General Needs Flatted Accommodation Fire Risk Assessment ...

68 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

52

Question Details

Area All Areas

Risk Category Training - Evacuation

Question 53. Where fire evacuation safety drills are considered appropriate, are they carried out at regular intervals?

Answer Title Na

Question Notes

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Question Details

Area All Areas

Risk Category Training - Trained Personnel

Question 54. Are staff trained in fire safety via induction and/or annual refreshers?

Answer Title No

Question Notes Concierge staff are trained in fire procedures but do not receive annual

Page 69: General Needs Flatted Accommodation Fire Risk Assessment ...

69 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

refresher training or have not received training for use of fire extinguishers .

Probability 2

Severity 2

Score 4

Risk Moderate (4)

Date Action Due 01/10/2017

Documents

Question Details

Area All Areas

Risk Category Training - Trained Personnel

Question 55. Is fire safety training recorded?

Answer Title Yes

Question Notes

Probability 0

Severity 0

Score 0

Risk Trivial (0)

Date Action Due 01/07/2018

Documents

Page 70: General Needs Flatted Accommodation Fire Risk Assessment ...

70 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

SECTION FIVE

ASSESSMENT PARAGRAPHS

Page 71: General Needs Flatted Accommodation Fire Risk Assessment ...

71 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Page 72: General Needs Flatted Accommodation Fire Risk Assessment ...

72 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

SECTION SIX

ACTION SUMMARY

Page 73: General Needs Flatted Accommodation Fire Risk Assessment ...

73 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

6. Action Summary

The timescales are deemed by London Borough of Newham to be a reasonable target for officers and managers when planning their implementation. P1 – Matters of very high risk posing an imminent threat of significant harm must be brought to the attention of the on-site management (where available) and the technical co-ordinator within London Borough of Newham by the fastest means. In any event, P1 items must be brought to the attention of the Director and Head of Department (HoD) to initiate immediate response for remedial action full controls to be in place within time specified above unless deemed necessary to remedy with immediate effect. P1 items may not exceed their target deadline without the recorded consent of a senior manager or Head of Department or Director. P2 and P3 items exceeding the target deadline must be reported. P4 items a recommendations but not a legal requirement. However, they should be remedied as budget and management constrains allow. In order to reduce the residual risk to an acceptable level, it will be necessary to implement all but P4 Action Items on the schedule.

Risk Assessment: Action Summary

Area Risk Category Action Risk Risk Due Due Date

All Areas Arson - Fire Load Other-Combustibles Moderate (4) 01/10/2017 01/10/2017

All Areas Arson - Security Relocate Where Possible Waste Disposal Provision.

Moderate (4) 01/10/2017 01/10/2017

All Areas Combustible Materials - Housekeeping

Inform Caretaking Services To Improve The Arrangements For The Disposal Of Waste And Rubbish.

Moderate (4) 01/10/2017 01/10/2017

All Areas Combustible Materials - Housekeeping

Remove Combustible Materials Moderate (4) 01/10/2017 01/10/2017

All Areas Fire Fighting Equipment - Extinguishers

Carry Out Maintenance/Servicing To Fire Extinguishers.

Trivial (0) 01/07/2018 01/07/2018

Page 74: General Needs Flatted Accommodation Fire Risk Assessment ...

74 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

All Areas Fire Fighting Equipment - Extinguishers

Other- Provisions Moderate (4) 01/10/2017 01/10/2017

All Areas General Hazards - Any Other Issues

Other- General Moderate (4) 01/10/2017 01/10/2017

All Areas Limiting Fire Spread - Compartmentation

Carry Out Survey To Determine Fire Check Provisions Required.

Moderate (4) 01/10/2017 01/10/2017

All Areas Limiting Fire Spread - Compartmentation

Repair/Install Fire Check Linings To Compartment.

Moderate (4) 01/10/2017 01/10/2017

All Areas Limiting Fire Spread - Compartmentation

Other- Compartments Moderate (4) 01/10/2017 01/10/2017

All Areas Limiting Fire Spread - Compartmentation

Other- Doors Moderate (4) 01/10/2017 01/10/2017

All Areas Limiting Fire Spread - Dampers

Where Installed Provide Up To Date Service/Maintenance Records.

Trivial (0) 01/07/2018 01/07/2018

All Areas Maintenance Checks - General

Other- General Moderate (4) 01/10/2017 01/10/2017

All Areas Maintenance Checks - General

Remove All Rubbish. Moderate (4) 01/10/2017 01/10/2017

All Areas Maintenance Checks - General

Other- PAT Testing Moderate (4) 01/10/2017 01/10/2017

All Areas Means Of Escape - Lighting Carry Out Repair To Emergency Lighting. Moderate (4) 01/10/2017 01/10/2017

All Areas Means Of Escape - Routes Ensure Existing Exit Routes And Exits Are Available For Use And Unobstructed.

Moderate (4) 01/10/2017 01/10/2017

Page 75: General Needs Flatted Accommodation Fire Risk Assessment ...

75 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

All Areas Means Of Escape - Routes Remove All Potential Tripping Hazards From Communal Areas.

Moderate (4) 01/10/2017 01/10/2017

All Areas Means Of Escape - Routes Remove Combustibles Items From Outside Dwellings.

Moderate (4) 01/10/2017 01/10/2017

All Areas Means Of Escape - Routes Remove/Repair Flooring To Remove Hazard.

Moderate (4) 01/10/2017 01/10/2017

All Areas Means Of Escape - Signage Other- Signage Moderate (4) 01/10/2017 01/10/2017

All Areas Means Of Escape - Signage Renew/Install Signage As Per Notes. Moderate (4) 01/10/2017 01/10/2017

All Areas Other Issues - General Other- General Moderate (4) 01/10/2017 01/10/2017

All Areas Premises Management - Records And Security

Review Current Procedures. Moderate (4) 01/10/2017 01/10/2017

All Areas Records - Fire Maintenance

Provide Up To Date Maintenance Records. Moderate (4) 01/10/2017 01/10/2017

All Areas Sources Of Ignition - Smoking

Carry Out Periodic Checks To Stop Non-Compliance.

Trivial (0) 01/07/2018 01/07/2018

All Areas Sources Of Ignition - Smoking

Ensure Tenants Are Aware Of The Smoking Policy Within The Estate.

Trivial (0) 01/07/2018 01/07/2018

All Areas Sources Of Ignition - Smoking

Provide Additional Signage. Trivial (0) 01/07/2018 01/07/2018

All Areas Training - Trained Personnel

Other- Staff Moderate (4) 01/10/2017 01/10/2017

Page 76: General Needs Flatted Accommodation Fire Risk Assessment ...

76 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

SECTION SEVEN

ACTION DETAILS

Page 77: General Needs Flatted Accommodation Fire Risk Assessment ...

77 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Action Details

Area All Areas

Risk Category Arson - Fire Load

Action Other-Combustibles

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q1-1.Refuse/recycling bins AND BULK WASTE must not be stored directly adjacent to the building -identify suitable area and relocate and manage.(pics 1,1a)

Documents

Action Details

Area All Areas

Risk Category Arson - Security

Action Relocate Where Possible Waste Disposal Provision.

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q3-Refer Q1 - action

Documents

Page 78: General Needs Flatted Accommodation Fire Risk Assessment ...

78 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Action Details

Area All Areas

Risk Category Combustible Materials - Housekeeping

Action Inform Caretaking Services To Improve The Arrangements For The Disposal Of Waste And Rubbish.

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q4- Combustibles found in service riser cupboards( some removed at time of inspection - concierge informed)

Documents

Action Details

Area All Areas

Risk Category Combustible Materials - Housekeeping

Action Remove Combustible Materials

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q5- 9th floor service riser -remove combustibles. Remove all combustibles from floors 20,15,2. IMPLEMENT ZERO TOLERENCE POLICY ON ANY COMBUSTIBLES WITHIN COMMUNAL AREAS.IMMEDIATE ACTION - ADVISED CONCIERGE ON SITE TO CHECK ALL CUPBOARDS REGULARLY. Remove all unnecessary combustibles from all ground floor stores rooms / risers cupboards.

Documents

Page 79: General Needs Flatted Accommodation Fire Risk Assessment ...

79 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Action Details

Area All Areas

Risk Category Fire Fighting Equipment - Extinguishers

Action Carry Out Maintenance/Servicing To Fire Extinguishers.

Risk Trivial (0)

Date Action Due 01/07/2018

Quantity 1.00

Action Notes

Q12-Tenants room on 1st floor must be accessed and fire extinguishers checked.

Documents

Action Details

Area All Areas

Risk Category Fire Fighting Equipment - Extinguishers

Action Other- Provisions

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q14-Consider the provision of fire extinguishers in all plant rooms .

Documents

Page 80: General Needs Flatted Accommodation Fire Risk Assessment ...

80 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Action Details

Area All Areas

Risk Category General Hazards - Any Other Issues

Action Other- General

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q19. 1.Ground floor service riser cupboards - competent person to secure all cables correctly (pics 19,a,b) IMMEDIATE ACTION WO 6381786/3 2.Tenants room 1st floor - instruct Concierge Supervisor to access room to confirm adequate housekeeping IMMEDIATE ACTION

Documents

Action Details

Area All Areas

Risk Category Limiting Fire Spread - Compartmentation

Action Carry Out Survey To Determine Fire Check Provisions Required.

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q20 - 2.Carry of intrusive surveys of external cladding( this may have already been sampled see Pics20e & f for examples - ONCE ESTABLISHED - REVIEW THIS FRA.

Q21 -2.Carry out inspections of the water service riser room on all floors to ensure correct fire stopping (not possible to access into deep areas high and low without PPE - Pics 21h,i,j) Q21-4 Ground floor stairwell door to lift lobby - confirm glass panels are fire rated to 30 minutes protection or upgrade glass/replace door with FD30S. (pic20h) Carry out inspection of all roof area including plant rooms and also all external ground floor main network power intake room , all other plants rooms and also garages(including tenants) to ensure adequate compartmentation .(pics 21n,o,q )

Documents

Action Details

Page 81: General Needs Flatted Accommodation Fire Risk Assessment ...

81 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Area All Areas

Risk Category Limiting Fire Spread - Compartmentation

Action Repair/Install Fire Check Linings To Compartment.

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q20 - 1.Repaint surfaces in the following areas using class O paint - 13th floor adjacent flat , 7th floor ceiling adjacent flat 6th floor by lifts ceiling and walls 2nd floor by lifts walls and ceilings , 1st floor ceiling by flat DAMP AROUND 1st floor lift panel (water ingress?) also check all communal areas for other delamination and rectify (pics20,a,b,c,d ).

Documents

Action Details

Area All Areas

Risk Category Limiting Fire Spread - Compartmentation

Action Other- Compartments

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q21- 2.Fire stopping by competent person required - 19th floor electrical riser and excess foam , 18th floor riser cupboard by flat excess foam (pic6), 17th floor riser cupboard by flat - breach in wall (pic6a), 16th floor electrical riser - fire stop and cover plate missing (pic6b), 15th floor example of excess foam use in comms cupboard (pic6c), 12th floor electrical riser by flat - cover missing (pic6d),8th floor dry riser cupboard - fire stopping , mains water riser by flat pipe has breached wall (pic6e), 1st floor chute room - fires stopping required. Concierge lodge cupboard - firestop (pics 6m,n )GROUND FLOOR ALL AREAS - CARRY OUT FULL SURVEY AS THERE ARE MANY BREACHES IN COMPARTMENTATION THROUGH ALL AREAS and replace all trunking panels . (examples - pics 6f,g,h,i,j,k,l) IMMEDIATE ACTION WO 6381786/2

Documents

Page 82: General Needs Flatted Accommodation Fire Risk Assessment ...

82 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Action Details

Area All Areas

Risk Category Limiting Fire Spread - Compartmentation

Action Other- Doors

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q21 - 1.PRIOR TO COMMENCING ANY WORKS ON STAIRWELL DOORS CONFIRMATION IS REQUIRED THAT THEY MEET FD30 STANDARD (REFER pic21e) 20th floor- stairwell door opposite flat adjust so door meets frame (pic21) , 20th floor- stairwell door opposite flats so door meets frame (pic21a), 14th floor - stairwell door opposite flat adjust so door meets frame, 11th floor - stairwell door opposite flat adjust so door meets frame,4th floor stairwell door opposite flat adjust so door meets frame, 3rd floor stairwell door opposite - door closure appears vandalised (pic21g) , 1st floor stairwell door opposite flat adjust so door meets frame - ALSO - Stairwell doors - HAVE BEEN DAMAGED BY INSTALATION OF CLOSURES - COMPETENT PERSON TO ASSESS WHETHER THESE DOORS CAN BE SATISFACTORILY REPAIRED OR REPLACE DOORS ACCORDINGLY - CARRY OUT FULL SURVEY OF ALL STAIRWELL DOORS - EXAMPLES FOUND ON 13TH FLOOR OPPOSITE FLAT (pic21d &e). 12TH FLOOR OPPOSITE FLAT (pic21f) , 11th floor twin lobby doors

Documents

Action Details

Area All Areas

Risk Category Limiting Fire Spread - Dampers

Action Where Installed Provide Up To Date Service/Maintenance Records.

Risk Trivial (0)

Date Action Due 01/07/2018

Quantity 1.00

Action Notes

Chute room ground floor - confirm damper fusible links are present and annual maintenance is being carried out.or upgrade chutes(6 months action.(pic 22)

Documents

Page 83: General Needs Flatted Accommodation Fire Risk Assessment ...

83 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Action Details

Area All Areas

Risk Category Maintenance Checks - General

Action Other- General

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q23. 1.Tenants room - carry out fixed electrical testing and emergency lighting testing if applicable. 2.Ceiling wire trunking covers - carry out full survey and remedial repairs as necessary - defects observed on floors 18,13,12,10,8,1,ground (pics23,a) 3. Twin door service risers on each floor - carry out full survey and fit correct locking mechanism (pics 23c,d)

Documents

Action Details

Area All Areas

Risk Category Maintenance Checks - General

Action Remove All Rubbish.

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q25. Tenants room - remove all rubbish and unnecessary combustibles.

Documents

Page 84: General Needs Flatted Accommodation Fire Risk Assessment ...

84 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Action Details

Area All Areas

Risk Category Maintenance Checks - General

Action Other- PAT Testing

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q26. Tenants room - Carry out PAT testing on all portable electrical equipment if applicable.

Documents

Action Details

Area All Areas

Risk Category Means Of Escape - Lighting

Action Carry Out Repair To Emergency Lighting.

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q32. Carry out full survey to block to ensure all emergency lighting is in good condition. Replace missing light covers and reaffix dropped covers - carry out full survey of block - observations noted on floors 20 (both stairwells) , 19, 18, 1 (pic 29a,b)

Documents

Page 85: General Needs Flatted Accommodation Fire Risk Assessment ...

85 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Action Details

Area All Areas

Risk Category Means Of Escape - Routes

Action Ensure Existing Exit Routes And Exits Are Available For Use And Unobstructed.

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q34. Remove all bikes scooter, trollies etc. from communal areas.

Q35. Remove rubbish from all communal areas.

Documents

Action Details

Area All Areas

Risk Category Means Of Escape - Routes

Action Remove All Potential Tripping Hazards From Communal Areas.

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q35. Remove All Potential Tripping Hazards From Communal Areas

Documents

Page 86: General Needs Flatted Accommodation Fire Risk Assessment ...

86 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Action Details

Area All Areas

Risk Category Means Of Escape - Routes

Action Remove Combustibles Items From Outside Dwellings.

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q35. Remove Combustibles Items From Outside Dwellings.

Documents

Action Details

Area All Areas

Risk Category Means Of Escape - Routes

Action Remove/Repair Flooring To Remove Hazard.

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q35. Carry out Repairs to external paving WO 6381786/4

Documents

Page 87: General Needs Flatted Accommodation Fire Risk Assessment ...

87 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Action Details

Area All Areas

Risk Category Means Of Escape - Signage

Action Other- Signage

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q46. Review requirements for assembly point in THIS BLOCK AND ALL BLOCKS

Documents

Action Details

Area All Areas

Risk Category Means Of Escape - Signage

Action Renew/Install Signage As Per Notes.

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q46. Check all floors - Replace all fire action signs located by lift call (pics 45f,g) IMMEDIATE ACTION Initiate programme to replace all fire action notices by each lift call point to meet BS 5499 IN ALL TALL BLOCKS 6 MONTH ACTION

Documents

Page 88: General Needs Flatted Accommodation Fire Risk Assessment ...

88 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Action Details

Area All Areas

Risk Category Other Issues - General

Action Other- General

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q47. 2.Install door closures to GERDA FD30S doors and advise tenants of importance of fire doors/closure - (Pic 47c). Over 50 % of flat front doors are missing there door closures - advise ALL flat from doors are inspected to check door closures present . 3. - no smoke or heat detectors - refer to relevant department. 4. 1st floor riser cupboard there is a small water heater permanently switched on - Clarifiy requirements for this water heater and confirm testing regime under Electrical Regs.is being carried out.(pic )47d

Documents

Action Details

Area All Areas

Risk Category Premises Management - Records And Security

Action Review Current Procedures.

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q50. The current fire safety policy is draft form only and current arrangements/policies/procedures are fragmented.

Documents

Page 89: General Needs Flatted Accommodation Fire Risk Assessment ...

89 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Action Details

Area All Areas

Risk Category Records - Fire Maintenance

Action Provide Up To Date Maintenance Records.

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q51. Fire Safety maintenance records need to be made available.

Documents

Action Details

Area All Areas

Risk Category Sources Of Ignition - Smoking

Action Carry Out Periodic Checks To Stop Non-Compliance.

Risk Trivial (0)

Date Action Due 01/07/2018

Quantity 1.00

Action Notes

Q52. Estate Management to review procedures.

Documents

Page 90: General Needs Flatted Accommodation Fire Risk Assessment ...

90 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Action Details

Area All Areas

Risk Category Sources Of Ignition - Smoking

Action Ensure Tenants Are Aware Of The Smoking Policy Within The Estate.

Risk Trivial (0)

Date Action Due 01/07/2018

Quantity 1.00

Action Notes

Q52. Housing Compliance to write to tenants.

Documents

Action Details

Area All Areas

Risk Category Sources Of Ignition - Smoking

Action Provide Additional Signage.

Risk Trivial (0)

Date Action Due 01/07/2018

Quantity 1.00

Action Notes

Q52. Estate Management to provide additional signage.

Documents

Page 91: General Needs Flatted Accommodation Fire Risk Assessment ...

91 Uncontrolled when Printed - 1-98 Aubrey Moore Point Abbey Lane London E15 2RZ

Action Details

Area All Areas

Risk Category Training - Trained Personnel

Action Other- Staff

Risk Moderate (4)

Date Action Due 01/10/2017

Quantity 1.00

Action Notes

Q55. Arrange annual refresher training for fire procedures including lift control procedure and extinguisher training.

Documents