General Specifications <<Contents>> <<Index>> Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant Resource Manager Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Tel.: 81-422-52-5634 Fax.: 81-422-52-9802 GS 33Y05Q10-32E GS 33Y05Q10-32E ©Copyright July 26, 2006 (YK) 20th Edition June 30, 2017 (YK) GENERAL Plant Resource Manager (PRM®) is an asset management software tool for the digital network era. The PRM software efficiently manages and supports maintenance work of field devices, which contributes in reducing total cost of ownership (TCO) of an industrial plant. The PRM software packages support intelligent devices such as Foundation™ fieldbus, HART, PROFIBUS, and ISA100.11a field wireless devices as well as conventional analog devices. PRODUCT OVERVIEW Plant Resource Manager (PRM) consists of the following components: l PRM server • Maintenance related data such as device status, device parameters, device alarms, and inspection memo of the field devices are collected and stored. • Centralized device information such as device master, inspection schedules and records, user-created electronic documents, and parts lists are generated and managed as database. • Maintenance alarms for field devices are generated with attributes such as problem, cause, and action, and these alarms are notified to the people who need them. l PRM client • Device navigator windows in hierarchy tree view are provided for monitoring and managing field devices. • Automatic device recognition and registration (plug & play) are performed by using full digital, bi-directional, field digital networks such as Foundation fieldbus, HART, PROFIBUS, and ISA100.11a. Monitors device health status with maintenance alarms and communication errors. With PRM Advanced Diagnostic Function, the PRM also performs device status diagnosis, device parameter setting using device diagnostic tools (i.e. DeviceViewer, DTM Works, and DD menu). • Status icons are displayed reflecting the communication and device status to let operators grasp the device status intuitively. Status icons appear for the devices with unacknowledged maintenance alarms (of the device health status). • A status signal of a field device complying with NAMUR NE107 specifications is displayed on the Signal view of the Device navigator. The NE107 is a recommendation for self-monitoring and diagnosis of field devices published by NAMUR, an international user association of automation technology in process industries headquartered in Germany. • Device icons displayed on the device navigator can be freely defined by a user. The user can customize those fonts and icons out of three choices depending on the user requirements and the screen size. • Maintenance marks are a kind of flags to be assigned to devices for setting and checking maintenance status. The maintenance mark icon is displayed upon setting, and enables to temporarily change device access level. The maintenance marks can also be linked with CENTUM’s operation marks so that the maintenance engineers and operators can share the same information and coordinate their work. • Online device adjustment/setting are performed on screen using the same user interface with FieldMate versatile device management tool which is an on-site device adjustment/setting tool. • Parameters and maintenance information between the PRM and the FieldMate can be exchanged. • PRM advanced diagnosis application, device diagnosis data historian, and general-purpose diagnosis tool for PRM advanced diagnosis function are provided, in addition to the maintenance alarm function and device diagnostics function. • Registration of conventional analog field devices as well as field digital devices such as Foundation fieldbus, HART, PROFIBUS, and ISA100.11a can be performed for a true, centralized device management. • Third-party calibration and diagnostic software tools as PLUG-IN applications can be performed. DeviceViewer (*1) and PLUG-IN ValveNavi are available from Yokogawa. • FDT/DTM (Field device tool/Device type manager) and EDDL (Electronic device description language) technologies that enable the PRM to interface with field devices are supported. DTMs of FDT1.2 and FDT2.0 are supported. *1: A field device information and its status signal complying with NAMUR NE107 are displayed on the DeviceViewer. Download device definition files from each device vendor to run on the DeviceViewer prior to its use. The DeviceViewer is a PLUG-IN application of the PRM client and it can be displayed on CENTUM VP/CENTUM CS 3000 (R3.07 or later) HIS. To let only the DeviceViewer run on the HIS, DeviceViewer on HIS has to be installed.

Transcript of General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV Models SSS7700,...

Page 1: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

GeneralSpecifications

<<Contents>> <<Index>>

Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750Plant Resource Manager

Yokogawa Electric Corporation2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 JapanTel.: 81-422-52-5634 Fax.: 81-422-52-9802

GS 33Y05Q10-32E

GS 33Y05Q10-32E©Copyright July 26, 2006 (YK)

20th Edition June 30, 2017 (YK)

GENERALPlant Resource Manager (PRM®) is an asset management software tool for the digital network era. The PRM software efficiently manages and supports maintenance work of field devices, which contributes in reducing total cost of ownership (TCO) of an industrial plant.The PRM software packages support intelligent devices such as Foundation™ fieldbus, HART, PROFIBUS, and ISA100.11a field wireless devices as well as conventional analog devices.

PRODUCT OVERVIEWPlant Resource Manager (PRM) consists of the following components:

lPRM server•Maintenancerelateddatasuchasdevicestatus,deviceparameters,devicealarms,andinspectionmemoofthefielddevicesarecollectedandstored.

•Centralizeddeviceinformationsuchasdevicemaster,inspectionschedulesandrecords,user-createdelectronicdocuments, and parts lists are generated and managed as database.

•Maintenancealarmsforfielddevicesaregeneratedwithattributessuchasproblem,cause,andaction,andthesealarmsarenotifiedtothepeoplewhoneedthem.

l PRM client•Devicenavigatorwindowsinhierarchytreeviewareprovidedformonitoringandmanagingfielddevices.•Automaticdevicerecognitionandregistration(plug&play)areperformedbyusingfulldigital,bi-directional,fielddigitalnetworkssuchasFoundationfieldbus,HART,PROFIBUS,andISA100.11a.Monitorsdevicehealthstatuswithmaintenancealarmsandcommunicationerrors.WithPRMAdvancedDiagnosticFunction,thePRMalsoperformsdevicestatusdiagnosis,deviceparametersettingusingdevicediagnostictools(i.e.DeviceViewer,DTMWorks,andDDmenu).

•Statusiconsaredisplayedreflectingthecommunicationanddevicestatustoletoperatorsgraspthedevicestatusintuitively.Statusiconsappearforthedeviceswithunacknowledgedmaintenancealarms(ofthedevicehealthstatus).

•AstatussignalofafielddevicecomplyingwithNAMURNE107specificationsisdisplayedontheSignalviewoftheDevicenavigator.TheNE107isarecommendationforself-monitoringanddiagnosisoffielddevicespublishedbyNAMUR,aninternationaluserassociationofautomationtechnologyinprocessindustriesheadquarteredinGermany.

•Deviceiconsdisplayedonthedevicenavigatorcanbefreelydefinedbyauser.Theusercancustomizethosefontsandiconsoutofthreechoicesdependingontheuserrequirementsandthescreensize.

•Maintenancemarksareakindofflagstobeassignedtodevicesforsettingandcheckingmaintenancestatus.Themaintenancemarkiconisdisplayeduponsetting,andenablestotemporarilychangedeviceaccesslevel.ThemaintenancemarkscanalsobelinkedwithCENTUM’soperationmarkssothatthemaintenanceengineersandoperators can share the same information and coordinate their work.

•Onlinedeviceadjustment/settingareperformedonscreenusingthesameuserinterfacewithFieldMateversatiledevicemanagementtoolwhichisanon-sitedeviceadjustment/settingtool.

•ParametersandmaintenanceinformationbetweenthePRMandtheFieldMatecanbeexchanged.•PRMadvanceddiagnosisapplication,devicediagnosisdatahistorian,andgeneral-purposediagnosistoolforPRMadvanceddiagnosisfunctionareprovided,inadditiontothemaintenancealarmfunctionanddevicediagnosticsfunction.

•RegistrationofconventionalanalogfielddevicesaswellasfielddigitaldevicessuchasFoundationfieldbus,HART,PROFIBUS,andISA100.11acanbeperformedforatrue,centralizeddevicemanagement.

•Third-partycalibrationanddiagnosticsoftwaretoolsasPLUG-INapplicationscanbeperformed.DeviceViewer(*1)andPLUG-INValveNaviareavailablefromYokogawa.

•FDT/DTM(Fielddevicetool/Devicetypemanager)andEDDL(Electronicdevicedescriptionlanguage)technologiesthatenablethePRMtointerfacewithfielddevicesaresupported.DTMsofFDT1.2andFDT2.0aresupported.

*1: AfielddeviceinformationanditsstatussignalcomplyingwithNAMURNE107aredisplayedontheDeviceViewer. DownloaddevicedefinitionfilesfromeachdevicevendortorunontheDeviceViewerpriortoitsuse.TheDeviceViewerisa

PLUG-INapplicationofthePRMclientanditcanbedisplayedonCENTUMVP/CENTUMCS3000(R3.07orlater)HIS. ToletonlytheDeviceViewerrunontheHIS,DeviceVieweronHIShastobeinstalled.

Page 2: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

2

All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 33Y05Q10-32E Sep. 7, 2016-00

l Field communications serverThissoftwareistosetandacquirefielddevicedataonline.Thefieldcommunicationserverprovidesinformationsuchasdevicestatusmonitoring,deviceadjustment,anddevicediagnosistothemaintenancesupportapplication.

Connecting with field devicesFollowingmethodsareavailabletoconnectwithfielddevices.•FoundationfieldbusCommunicationModulesforCENTUMVP/CS3000•AI/AOmodulesoranalogdigitalI/OmodulewithHARTcommunicationforCENTUMVP/CS3000•PROFIBUS-DPcommunicationmoduleforCENTUMVP•FoundationfieldbusCommunicationModulesforSTARDOM•AI/AOmoduleswithHARTcommunicationforSTARDOM•PROFIBUScommunicationmoduleforSTARDOM•AI/AOmodulesoranalogdigitalI/OmoduleswithHARTcommunicationforProSafe-RS•NI-FBUScard•3rdpartyHARTmultiplexers(PepperandFuchs,MTL,ELCON,orSTAHL)•3rdpartyPROFIBUScommunicationdevices(CommunicationDTM/GatewayDTMcommunications)•FieldWirelessAccessPointandFieldWirelessManagementStation(CommunicationDTM/GatewayDTMcommunications)

l Multiple server switchoverPRMcanmanagefielddevicesthatarecontrolledbyaCENTUMVP/CS3000,ProSafe-RS,orSTARDOMproject.PRMcanalsomonitoralarge-scaleprojectwhichisgeographicallydistributedinremotelocationsatasinglelocation.Forthelarge-scaleprojectwheretensofthousandsoffielddevicesareinstalled,dividingthemintomultiplenumbersofPRMserversisinevitable.PRM’smultipleserverfunctionenablestoselectwhichPRMserverisreferredtobyaPRMclient.Inthisway,asinglePRMclientcanmonitorseveralPRMservers.

l PRM advanced diagnosis server function (optional)Thisseverfunctionprovidesanenvironmentforexecutingdiagnosticalgorithmsbyutilizingfielddeviceparameters.ThediagnosticalgorithmapplicationcanbeconfiguredbyusingthePRMadvanceddiagnosticsoftwaredevelopmentkit(PAA-developmentkit)withoutanyadditionalsoftwareprogram.Bymonitoringparametersandprocessdatatransmittedfromfielddevices,thePRMadvanceddiagnosisserverfunctionconfiguresandexecutesdiagnosisofthedevicesandassets.Formoredetails,refertotheGS“PRMadvanceddiagnosisserver”(GS33Y05Q21-32E).

l PST scheduler package (optional)PST(*1)standsforapartialstroketest.ThePSTschedulerschedulesPST,automaticallyexecutesPSTinaccordancewiththeschedule,andmanagestheresultsinunifiedmanners.FunctionstomodifytheplannedschedulesandswitchPSTexecutionfromautomatictomanualareavailable.Fordetails,refertotheGS“PSTSchedulerPackage”(GS33Y05Q23-32E).

*1: Byslightlyoperatingemergencyshutdown(ESD)valvesonlinewhicharenotactivatedundernormalconditions,PSTistocheckifESDvalvesfunctioncorrectlyincaseofemergency.ByusingPST,theintervalperiodbetweenfullstroketestscanbeprolongedwithoutdisturbingthesafetyoftheESDvalves,thusthemaintenancecostforthoseESDvalvescanbereduced.

l Interface for Computerized maintenance management system (optional)PRMhasaninterfacewithMaximoAssetManagement,acomputerizedmaintenancemanagementsystem(CMMS),fromIBMSoftware,Inc.Withthisinterface,PRMcanprovidemaintenanceinformationtothemaintenancemanagement system online.Fordetails,refertotheGS“InterfaceforCMMS”(GS33Y05Q20-32E).

l Interface for GE Energy’s System 1® (optional)PRMcanprovideasinglemonitoringwindowfordiagnosisofturbines,rotatingequipmentandreciprocatingequipmentundermanagementbyGEEnergy’sSystem1optimizationanddiagnosticssoftwareplatforminadditiontofielddevicessuchaspressuretransmittersandflowmeters.Fordetails,refertotheGS“InterfaceforGEEnergy’sSystem1”(GS33Y05Q22-32E).

Page 3: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

3<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation GS 33Y05Q10-32E Sep. 7, 2016-00

SYSTEM CONFIGURATIONPRMmanagesinformationoffielddevicesbythePRMserverasaunit.ThePRMsystemcanbeconfigurableinscalableways–aminimumsystemconsistsofaPRMserver,aFieldcommunicationsserver,andaPRMclientallresidedinasinglecomputer,oralargesystemwithmultipleclients.ExamplesofPRMsystemconfigurationsareshown in this section.

l System configurationCENTUM VP/CS 3000

CENTUM HIS/ENG

PRM client

PRM server

Ethernet

Ethernet

Control network

HART devices

AnalogHART I/O module

ALP121(*2)

PROFIBUS-DP

PROFIBUS devices

FieldMate

ALF111

FCS FCS FCS

F01E.ai

Terminator

YFGW410Field wirelessmanagementstation

FOUNDATION fieldbusPower supply + Terminator

YFGW410Field wirelessmanagement

station

Firewall

L3 switch

Wide-area field network

Field wireless devicesHIS: Human interface stationENG: FCS: Field control stationALF111: FOUNDATION fieldbus communication module

FF-H1 devices

Field wireless devices

(*1)

ALE111

ALE111: Ethernet communication moduleALP121: PROFIBUS-DP communication module

Field communications server

Engineering station

TM1READY

FUSE RL1 CN1 (PSU-L) TM2 100-120V AC

CN2 (PSU-R)

TM1READY

FUSE RL1 CN1 (PSU-L) TM2 100-120V AC

CN2 (PSU-R)

TM1READY

FUSE RL1 CN1 (PSU-L) TM2 100-120V AC

CN2 (PSU-R)

Figure CENTUM VP System Configuration (for FIO)Note:APRMserver,aPRMClientandaFieldCommunicationsServercanrunonasinglecomputer. APRMclientcanrunonthesamecomputerwhereHIS/ENGisalreadyinstalled. APRMserveroraFieldcommunicationsservercannotrunonthesamecomputerwhereHIS/ENGisalreadyinstalled.*1: ProcessdataanddiagnosisstatuscanbedisplayedonanHIS. AsforconfigurationofISA100.11afieldwireless,refertotheGS“Fieldwirelesssystemoverview”(GS01W01A01-01EN).*2: ALP121issupportedbyCENTUMVPR5.02orlaterrevision.

Page 4: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

4

All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 33Y05Q10-32E

CENTUMHIS/ENG

A2EN40: N-ESB Bus coupler moduleNIU: Node interface unit

PRM serverField communications server

Control network

Ethernet

F12E.ai

HARTdevices

FCS (A2FV50) (*1)

PRM client

N-IO I/O unit

A2EN40

TM1READY

FUSE RL1 CN1 (PSU-L) TM2 100-120V AC

CN2 (PSU-R)

HARTdevices

FCS (A2FV70) (*2)

I/O unit

A2EN40

TM1READY

FUSE RL1 CN1 (PSU-L) TM2 100-120V AC

CN2 (PSU-R)

NIUNIU

Figure CENTUM VP System Configuration (for N-IO)Note:APRMserver,aPRMclientandaFieldcommunicationsservercanrunonasinglecomputer. APRMclientcanrunonthesamecomputerwhereHIS/ENGisalreadyinstalled. APRMserveroraFieldcommunicationsservercannotrunonthesamecomputerwhereHIS/ENGisalreadyinstalled.*1: A2FV50issupportedbyCENTUMVPR6.01orlaterrevisionandPRMR3.02orlaterrevision.*2: A2FV70issupportedbyCENTUMVPR6.03orlaterrevisionandPRMR3.31.00orlaterrevision.

June 30, 2017-00

Page 5: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

5<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation GS 33Y05Q10-32E

STARDOMMessagesfromSTARDOMcontrollersaretransmittedtoaPRMserverviaanOPCserver.FCN/FCJOPCserverforWindows(asoftwarepackage)isrequired.

HMI client

FCN/FCJ

HMI serverData server

OPC server

Control network

Ethernet

FCN

PRM client

PRM serverField communications server

Logic designer resource configurator

Controller

VDS/HMI PRM

CPU NFLF 111 PSU

FCJ (with FOUNDATION fieldbus H1 port)

F10E.ai

FOUNDATION fieldbus H1 Fieldbus

FOUNDATION fieldbus H1 Fieldbus

Terminator

Coupler

Terminator

Coupler

Field wireless devices

YFGW410Field wireless managementstation

YFGW510Field wirelessaccess point

HART I/O module

PROFIBUS-DP

HART devices

FCN Controller

PSU NFAI 141

CPU NFAI 841

NFAI 835

NFAI 135

PROFIBUSslave devices

NFLP 121

CPU

FieldMate

VDS: STARDOM versatile data serverHMI: Human machine interfaceFCU: STARDOM autonomous controller (field control node)FCJ: STARDOM autonomous controller (field control junction)NFLF111: FOUNDATION fieldbus communication moduleNFAI***: Analog I/O modules (with HART communication function)NFLP121: PROFIBUS-DP communication module

FF-H1 devices

FF-H1 devices

Figure STARDOM system configuration

Note: APRMserver,aPRMclientandaFieldcommunicationsservercanrunonasinglecomputer. APRMclientandanHMIclientcanrunonthesamecomputer. APRMserveroraFieldcommunicationsservercannotrunonthesamecomputerwhereVDSisalreadyinstalled.

Sep. 7, 2016-00

Page 6: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

6

All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 33Y05Q10-32E

Notes for STARDOM configuration:PRMpackagescannotbeinstalledonacomputerwhereSTARDOMversatiledataserver(VDS)isalreadyinstalled.InstallingtheFCN/FCJOPCserverforWindowspackageonadifferentcomputerseparatelyfromthePRMpackagesis recommended.RefertothetablebelowforcombinationofthesoftwarerevisionnumberswheninstallingFCN/FCJOPCserverforWindowspackageonthesamecomputerwiththePRM.Thosecombinationsotherthanshownhere,FCN/FCJOPCserverforWindowsmustbeinstalledonadifferentcomputerseparatelyfromthePRMpackages.

FCN/FCJ OPC server for Windows PRM

Revision R1.90 R3.02

R2.20 R3.03, R3.04

R3.01 to R3.10 R3.05

– R3.10

R3.20 to R3.40 R3.11

– R3.12 or later

Upto100unitsofFCN/FCJcontrollerscanbeconnectedtoaFieldcommunicationsserver.Asforalarge-scalesystem,multi-serverfunctionshouldbeusedtodividethenumberofcontrollersconnectedtoaPRMserverbythegroup of 100 units or less.

ProSafe-RSPRMcanmanageHARTfielddevicesconnectedtoProSafe-RS’sHARTI/Oanalogmodules.

HIS/ENG PRM clientPRM serverField communications server

Control networkBus 2Bus 1

F15E.ai

HART devices

ProSafe-RS

HART I/Omodule

SCS (S2SC70) (*1)

NIU

S2MMM843

SENG

HART devicesSENG: Safety engineering stationSCS: Safety control stationNIU: Node interface unit

TM1READY

FUSE RL1 CN1 (PSU-L) TM2 100-120V AC

CN2 (PSU-R)

Figure ProSafe-RS System ConfigurationNote:APRMclientandSENGcanrunonasinglecomputer. APRMserveroraFieldcommunicationsservercannotrunonthesamecomputerwhereSENGisalreadyinstalled.Note: FromR3.12onwards,PRMsupportsVnet/IP-Upstreamwherethecontrolbus’sbandwidthis2Mbpsorfaster.Formore

details,refertotheGS“ProSafe-RSSafetyInstrumentedSystemOverview(forVnet/IP-Upstream)”(GS32P01B30-01EN).*1: S2SC70issupportedbyProSafe-RSR4.01orlaterrevisionsandPRMR3.30orlaterrevisions.

Sep. 7, 2016-00

Page 7: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

7<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation GS 33Y05Q10-32E

Communication with HART devices via multiplexerPRMcancommunicatewithHARTdevicesviaaHARTmultiplexerconnectedtotheserialportsoftheFieldcommunicationsserver.

Ethernet

Field communications server

PRM client

HART devices

HART devices

HART devices

PRM server

Control network

Analog I/O module

F05E.ai

FCS

HIS/ENG

HART multiplexer(3rd party)

HART multiplexer(3rd party)

RS-485/ Ethernet converter

HART devices

HART digital signals

4 - 20 mA

TM1READY

FUSE RL1 CN1 (PSU-L) TM2 100-120V AC

CN2 (PSU-R)

Figure Serial port connection via HART multiplexer (Parallel connection and two-way data flow)Note:APRMserver,aPRMclient,andaFieldcommunicationsservercanrunonasinglecomputer.

Sep. 7, 2016-00

Page 8: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

8

All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 33Y05Q10-32E

FUNCTIONAL SPECIFICATIONSl Organization of functionsThefollowingfigureshowstheorganizationoffunctions.

Device navigator

PRM

Maintenance information management

Audit trail management

Adjustment and diagnosis

Other functions

Plant viewNetwork viewClass viewSignal viewCustom view

Device masterInspection memoInspection scheduleParts listLink to document

Parameter setting and tuning - DTM works - Parameter mangerFF DD menu windowDeviceViewerCalibration management (Optional)

Operation logEvent log of deviceInspection logRecord filtering

PRM advanced diagnosis (Optional)

BrowserSecurityExportSelf-documentationPLUG-IN applicationDevice templateDatabase maintenance toolOnline instruction manualPRM system backupFieldMate synchronization

Diagnostic navigatorPRM advanced diagnosis application (PAA)Device diagnosis data historianGeneral-purpose diagnosis tool

Maintenance alarm

Message acquisitionDevice patrolFiltering

Maintenance mark

PST scheduler (Optional)

Interface for GE Energy’s System 1 (Optional)

PRM advanced diagnostic application softwaredevelopment kit (Optional)

Interface to computerized maintenance management system (Optional)

F03E.ai

Figure Organization of functions

Sep. 7, 2016-00

Page 9: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

9<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation GS 33Y05Q10-32E

l Device navigatorFourdifferentviews-plantview,networkview,classview,signalview,andcustomview–areprovided.Eachviewdisplaysdevicesinaplantintheformofaplanthierarchytreeview,intheWindowsexplorer-likeformat.Intheseviews,devicestatusanddevicepriority are shown with icons so that operators are able tojudgethemaintenancepriorityofthedevicesataglance.Wheretherearedeviceswithunacknowledgedmaintenance alarms, unacknowledged alarm icons are displayed.Useraccessescanberestrictedbasedonthedevicenavigatorhierarchy,whichpreventsanunauthorizedpersonnelfromoperatingdevicesbymistake.

Plant viewFacilitiesandequipmentintheplantinhierarchytreeviewaccordingtotheactualstructureoftheplantortheplantlayeraredisplayed.Not-in-usedevicescanbeallocatedeithertothe“Spare”folderforsparesandfailedorin-servicedevicestothe“Outofservice”folder.

Network viewThenetworkhierarchyoffielddevicesconnectedtothefieldnetworkinthetreeviewformisdisplayed.

Class viewFielddevicesinatreeviewbyvendors,models,andrevisionsaredisplayed.Userscanidentifythestatusofhowsparedevicesareusedwhiledevices-in-usearefailedorundermaintenance.Devicetemplatescanbecreated using this function.

Signal viewBasedonthefielddevicediagnosisresult,fielddeviceswhichareeitherhavingoperationalproblemorrequiringmaintenancearedisplayedinatablesortedbythestatussignals.Onlythefielddevicesthatrequiremaintenance can be shown on the list sorted by the category,whichenablestomaintainthefielddevicesknowing the priority. Four status signals - failure, check function,outofspecification,andmaintenancerequired-areprovidedbasedontheNE107recommendedbyNAMUR.

Custom viewUser-createdviewscanbecreatedanddisplayedinthehierarchicalstructure.Fielddevicescanbecategorizedby persons in charge of maintenance, inspection or replacement schedule, operation or failure status, and so on.

l Maintenance mark Maintenance marks are assigned electronically to each devicetoletmaintenanceengineersidentifystatusofadevice.ThemaintenancemarksareenabledtolinkwithCENTUM’soperationmarkssothatmaintenanceengineers and operators can share the same information and coordinate their work.

l Maintenance alarm functionAmessagesystemtonotifymaintenanceinformationandinformationnecessaryforfielddevicemaintenanceto all the maintenance engineers. The information contains not only messages generated by the fielddevices,butalsoattributessuchasmessageinformation,phenomenon,causes,andactions.Alarmsgeneratedbydiagnosticfunctionscanalsobedeliveredto the users.

Message acquisitionMessagesfromfielddigitaldevicesaswellaseventmessagesgeneratedbyCENTUM,STARDOMProSafe-RS,andthird-partysystemsareacquired.User-definedinformationsuchaseventpriorities,objectiveinformation,phenomenon,causes,andactionsareautomaticallyaddedtotheoriginaleventmessages, which are acknowledged as maintenance alarms,andpassedontothefilteringfunction.

Device patrolFielddevicestatusprovidedbydevice’sself-diagnosticsareacquiredtogeneratemaintenancealarmswiththeuser-definedattributessuchasmessagepriorities,objectiveinformation,phenomenon,causes, and actions. These maintenance alarms are handedovertothefilteringfunction.Dataacquisitionisperformed periodically or on demand. Information from deviceswhichdonotgeneratealarmmessagesbythemselvescanalsobeacquired.

Filtering functionAllthealarmsgeneratedbymessageacquisition,devicepatrol,advanceddiagnosticapplication,andmanually-enteredmessagesarefilteredandtheresultsarenotifiedtobyeachuser.

Sep. 7, 2016-00

Page 10: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

10

All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 33Y05Q10-32E

l Maintenance information managementPRMactsasacentraldatabasefordevicemaintenance information.

Device masterAlistoffielddevicesaregeneratedandmanagedwithalltherelevantinformation.Thelistofalltheregisteredfielddevicesanddetailedinformationoftheindividualfielddevicescanbedisplayed.Fielddeviceswithfieldcommunication function can be added automatically tothedevicelistbyplug&playwhenthedevicesarerecognized.

Inspection memoDetailsofinspection,maintenance,andservicingtasksperformedonadeviceorataplantareincluded.Comments and remarks by maintenance engineers duringservicingormaintenancecanalsobeincludedastheservicelogs.

Inspection scheduleSchedulesforinspection,adjustment,andcalibrationscanbemanagedbythefielddevice.

Parts listComponents and attribute information of parts whichcomposeofafielddeviceareincluded.AsforYokogawafielddeviceswithdigitalnetworkcommunication function, dedicated templates are provided.

Document linksFielddevicerelateddocumentssuchasplantstructures(e.g.P&IDandcontroldrawings),componentsparepartslist,onlineinstructionmanuals,anddeviceimages are freely allocated and enables users to accessthembythedevicetagnameaskeys.ThesedocumentscanbestoredinadocumentserveronanEthernetandaccessedbyURLaddresses.

l Audit trail managementHistoricalrecordsofPRMoperations,inspectionrecords,andeventinformationgeneratedbythemaintenance alarm function are managed and displayed on the PRM client. These historical records canbeshowninchronologicalorders,devicepriority,or message priority. The records can also be displayed filteringbythedeviceIDsordevicetagnames.

l Adjustment and diagnostic functionsOnlineadjustmentanddiagnosticfunctionsoffielddevicesaresupported.

Parameter tuning and comparisonDeviceparameterscanbesetanddisplayedonline.ThisfunctionenablesPRMtocomparethesavedparameterswithactualones.Theparametersetvaluesaresavedaslogs.Thedevicedatacanbeuploadedand stored to the database at any time. PRM also supports one-time uploading of all the connected devices.

ToolsDDmenu:forFoundationfieldbus UsingDDfilesprovidedbyvendors,PRMimplementsdevicediagnosticsandparametertuningandsetting,andcalibrations.ThespecificationsoftheDDfilesaredifferentbythefielddevices.

DeviceViewer:forFoundationfieldbus,HARTandISA100.11a

APLUG-INapplicationtodisplayresultsoffielddeviceself-diagnosis.Mostofthefielddevicesholdself-diagnosticresultsasthevendor-specificparameters.TheDeviceViewerreadsthoseself-diagnostic results and displays them in user-friendly ways.TheDeviceVieweralsodisplaysfielddeviceinformationwhichisusuallydisplayedontheLCDofthedevices,whichenablesuserstoremotelymonitorthedevicesconnectedtoPRMwithoutviewingthelocalLCDs.

DTMWorks:forFoundationfieldbus,HART,PROFIBUSandISA100.11a

UsingdeviceDTMsprovidedbyvendors,PRMimplementsdevicediagnosticsandparametertuningand setting, and calibrations.

PRMAdvancedDiagnosticFunction:forFoundation fieldbusandHART

PRMconductsadvanceddiagnosticanalysisforfielddevices.

Calibration data managementThedevicecalibrationdataaremanagedandmaintained by the PRM. Calibration results, differences,andjudgment(passorfail)areregisteredto the database and displayed on a PRM client. The calibrationdataapprovalfunctionallowsonlytheauthorizedpersontomodifythecalibrationdataonceitisapproved.Themodificationofthecalibrationdatais recorded as an operation history by the historical operation management function.When the documenting calibrator is used, the calibrationdatacanbeupload/downloadviacommunication. The calibration results are automaticallysavedintothedatabase.Thedocumentingcalibratorconnectionisprovidedasoptional.

Sep. 7, 2016-00

Page 11: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

11<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation GS 33Y05Q10-32E

l Other functionsBrowserAspecificdevicecanbesearchedbythedeviceattributesinformationaskeywordssuchasdeviceID,devicetagname,devicetagcomments,blockname,and parameters.

SecurityFormaintainingfielddevices,onlytheauthorizedpersonnel is allowed to access PRM or the scope of workislimitedsoastopreventtroublescausedbymis-operations from happening or secure system safety.Ausernameisusedtoidentifytheuserandtheusername is recorded to the operation records. The user operationsanditsprivilegesarerestrictedbytheusergroup where they belong.Byusingthedevicesecurityfunction,fielddevicescanbedisplayedonthedevicenavigatoronlyforthespecifiedusergroup.

ExportAdevicelist(deviceID,devicetagname,devicetagcomments, etc.) registered to the PRM database can beexportedasatextfileinCSVfileformatsothatthePRM’sdeviceinformationcanbeutilizedbyothersoftware such as asset management.

Self-documentationThe data stored in the PRM database can be output inadocumentformattolettheusersmanagedevice-related information electronically and print out on demands. The information displayed on each window can also be printed out in a format to be used as a maintenance report.The following printing properties can be edited.•Printingrange•Tableofcontents•Header/footer•Coverpage

PLUG-IN applicationsAPLUG-INapplicationisYokogawaorathird-partysoftware program that runs on a PRM client computer. FielddevicesandPRMdatabaseareaccessedviaPLUG-INapplicationlibrary.

Supported PLUG-IN applications•DeviceViewer•PLUG-INValveNaviforYVP110(PRMR2.1orlater)(*1)

•OtherthirdpartyPLUG-INapplicationsapprovedbyYokogawa.

*1: PLUG-INValveNaviisasoftwareprogramforYVP110valvepositionercompliedwithFoundation fieldbus to calibrate and execute advanceddiagnosticsusingsignaturefunctionsuchasdevicediagnosis.ItsfunctionsareequivalenttoYVP20S,astand-alonetypeValveNavi.FormoredetailsoftheValveNavifunctions,pleaserefertotheGS"YVPManagementSoftware"(GS21B04C50-01E).

Device template functionTemplatesareprovidedwithwhichausercandefinedeviceinformationofitsown.Thesetemplateshelpsimplifyengineeringworkofindividualdevicesettings.

Database maintenance toolPRM’sdatabasesizeincreasesinaccordancewiththenumberoffielddevicesconnected.Historicalrecordsofparametersalsoincreaseoveralongperiodofoperations.ThistoolhelpstuningandoptimizingthePRMdatabasetobeusedefficiently.Thedatacanalsobe maintained easily.

Online instruction manualAlltheinstructionmanualsareprovidedinPDFformatonaCD-ROM.Usersareabletoviewandprinttheelectronic instruction manuals on-demand.

PRM system back-up scriptUserscanbackupandrestorethePRMdatabasedontheuserenvironment.Registryinformation,PRMdatabase,advanceddiagnosisdatabaseandsooncanbe backed up.

l Relevant solutionField asset KPI reportThistoolprovidesservicesolutionsforplantequipmentsuch as status monitoring, performance diagnosis, andefficiencyimprovements.Usingtheintelligentfunctionsofthefielddevices,thetoolacquiresdevicestatus,availability,numberofalarms&events,andtheir rankings to automatically create the KPI report. Thereporthelpsoperatorstograsptheoverallstatusofthefielddeviceswiththeirowneyes.TheKPI report also helps make maintenance plans with prioritiesdependingonthedeviceconditions.Fordetails,refertotheGS“FieldAssetKPIReport”(GS43D02S03-02EN).

F13E.ai

Figure Field Asset KPI Report for PRM

Sep. 7, 2016-00

Page 12: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

12

All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 33Y05Q10-32E

l Supported functionsPRM’ssupportedfunctionsdifferbythekindsoffielddevices.Therelationshipbetweenthefielddevicesandtheircomplied functions are as shown below.

Table Supported Functions

Function Conventional

Devices(*1)

Foudation fieldbus

HART (*2)

ISA100.11a(*3)

PROFIBUS(*4)

Devicenavigationfunction

Plantview XX XX XX XX XXNetworkview — XX XX XX XXClassview XX XX XX XX XXSignalview — XX XX XX XXCustomview XX XX XX XX XX

Maintenance mark XX XX XX XX XX

Maintenance information management functions

Devicemaster XX XX XX XX XXPlug&Play — XX XX XX XXRegister from host fileset — XX X — X

Inspection memo XX XX XX XX XXInspection schedule XX XX XX XX XXParts list XX XX XX XX XXLinktodocument XX XX XX XX XX

Audittrailmanagement function

Parameter history — XX XX XX XXInspection memo history XX XX XX XX XX

Operationhistory XX XX XX XX XXDeviceeventmessage — XX XX — XX(*5)

Adjustmentanddiagnosis

Parameter tuning and comparison — XX XX XX —

Status display — XX XX XX XXTool — XX XX XX XXCalibration — XX XX — —

Maintennancealarm

Plantview — XX XX XX XXNetworkview — XX XX XX XXClassview — XX XX XX XXCustomview — XX XX XX XX

Otherfunctions

Browser XX XX XX XX XXSecurity XX XX XX XX XXPrinting XX XX XX XX XXPLUG-INapplication — XX XX XX —FieldMate synchronization XX XX XX XX XX

XX: Supported X: Partly supported —: Not applicable

*1: Theconventionaldevicesreferto4to20mAanalogdevicesandstaticdevicessuchasmotors.*2: HART5,6,and7aresupported,butWirelessHARTisnotsupported.*3: ConformstoISA100.11awirelesssystemforindustrialautomation.(ISA=InternationalSocietyofAutomation)*4: ConditionmonitoringwithdevicenavigatorisavailableforPROFIBUSPAdevicewhichconformstoPAprofile.Tofindoutif

thedevicesconformtoPAprofile,visitthePROFIBUSInternationalwebsiteoritsdevicevendors.*5: PROFIBUSdeviceeventmessagesareacquiredviaALP111orALP121PROFIBUS-DPCommunicationmodule.

Sep. 7, 2016-00

Page 13: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

13<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation GS 33Y05Q10-32E

MULTIPLE SERVER SWITCHOVERAssetmanagementofmultipleplantscanbeintegrallymanaged.A“server-set”concepthasbeenintroducedandenablesaPRMclienttoswitchfromaFieldcommunicationsserverandaPRMservertootherservers.Auserhastodefinetheserver-setbeforeuse.Withthisswitchoverfunction,aPRMclientmanagesallthedevicemanagementinformation of the multiple plants at a single location.

PRMcanbeconnectedwithCENTUM,STARDOM,orProSafe-RSsystemsonthesameEthernet.

Ethernet

Ethernet

Router

Control network

Server set A

PRMclient

PRM clientwith multiple servertswitchover function

F07E.ai

PRMserver

Switchover between the server sets

Field communications server

HIS

FCS

Ethernet

Control network

Server set B

PRMclient

PRMserver

Field communications server

HIS

FCS

Router

TM1READY

FUSE RL1 CN1 (PSU-L) TM2 100-120V AC

CN2 (PSU-R)

TM1READY

FUSE RL1 CN1 (PSU-L) TM2 100-120V AC

CN2 (PSU-R)

Figure Multiple server switchover

Sep. 7, 2016-00

Page 14: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

14

All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 33Y05Q10-32E

OPERATING ENVIRONMENTl Hardware requirementsTherequiredmainmemorysizeanddiskcapacitydependonthenumberoffielddevicesregisteredtothePRM.Theminimumhardwarerequirementisdescribedherewhennomorethan3000devicesareconnectedtoaPRMserver.Forconnectingmorethan3000devices,pleaseconsultYokogawa.IncasethesizeoftherequiredmainmemorydiffersbetweentheWindowsOSandthePRMpackages(PRMserver,PRMclient,andFieldcommunicationsserver),applythelargerofthetwovalues.

Main memory size required by Windows OSThemainmemorysizesrequiredbytheapplicableWindowsOSareasdescribedasbelow:

Table Required main memory size by Windows OS

Memory Size OS

Minimum memoryrequirement

Recommended(for better performance)

Windows Vista Business Edition SP2 512MB 1GBormore

Windows Server 2008 Standard Edition SP2 or Windows Server 2008 R2 Standard Edition SP1 512MB 2GBormore

Windows 7 Professional Edition SP1 2GB 4GBormore

PRM serverCPU:Refertothetablebelow.Main memory: Refer to the table below.Harddiskspace:Refertothetablebelow.Peripheraldevices:DVD-ROMdrive Ethernet cardDisplayresolution/colors:256colorsormore

Table PRM server hardware requirements (without Advanced diagnosis server)

Number of field devices300 units or less 1000 units or less 3000 units or less

CPU Pentium-1GHzorhigher(required)

Pentium-1GHzorhigher(required)Pentium4-2.8GHzorhigher(recommended)

Pentium4–2.8GHzorhigher(required)XeonDual–2.8GHzorhigher(recommended)

Main memory 512MBormore(required)2GBormore(recommended)

512MBormore(required)2GBormore(recommended)

1GBormore(required)2GBormore(recommended)

Harddiskcapacity(*1) 6GBormore(required)

8GBormoreoffreespace(required)Useofahigh-speeddiskdrivesuchasSCSIorRAIDdriveisrecommended.

13GBormoreoffreespace(required)Useofahigh-speeddiskdrivesuchasSCSIorRAIDdriveisrecommended.

Devicedatabasecapacity(*2) 600MB 2GB 6GB

Note: WhenthesystemconfigurationincludesAdvanceddiagnosisserver,refertotheGSof“PRMAdvanceddiagnosisserver(R3)”(GS33Y05Q21-32E)forhardwarerequirements.

*1: Therequiredharddiskcapacityincludesthedatabasecapacityspecifiedin(*2).*2: Thedevicedatabasecapacitycoverstherequiredsizeforoneyearoperation.Thesizeiscalculatedwiththeassumption

thatcomparingandsavingtheparametersofalldevicesandfunctionblockswithparametermanagerforfivetimesayear.

PRM clientCPU:Pentium1GHzorhigherMainmemory:512MBormore(required),1GBormore(recommended)Harddiskspace:2GBormoreCommunication unit: Ethernet cardPeripheraldevices:DVD-ROMdriveDisplayresolution/colors:1024x768orhigher,256colorsormore

Sep. 7, 2016-00

Page 15: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

15<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation GS 33Y05Q10-32E

Field communications serverCPU:PentiumIII1GHzorhigherForconnecting2000devicesormore,2.8GHzorhigherisrequired.Main memory: Refer to the table below.Harddiskspace:1GBormoreCommunication unit: Refer to the table below.Peripheraldevices:DVD-ROMdriveDisplayresolution/colors:256colorsormore

Table Hardware requirements for Field communications server

Connecting with CENTUM VP/CS

3000 or ProSafe-RSConnecting with

STARDOM

Connecting via NI-FBUS simplified

system for Foundation fieldbus

Connecting withsimplified system

for HART device or HART multiplexer

Connecting viacommDTM/

gatewayDTM

Main memory (*1)(*2)

•FCS/SCS1-16units(100+80 x number ofFCS/SCS)MBormore recommended

•FCN/FCJ1-16units(100+60 x number ofFCN/FCJ)MBormore recommended 256MBormore

required512MBormorerecommended

256MBormorerequired512MBormorerecommended

256MBormorerequired{30+(commDTM/gatewayDTMmainmemory)×(No. of node)}MBormorerecommended

•FCS/SCS17-44units (1380+10 x (numberofFCS/SCS-16))MBormore recommended

•FCN/FCJ17-100units (1060+5 x (numberofFCN/FCJ-16)MBormorerecommended

Communication devices

Ethernet card Control bus interface card Control network interfacecard(VF702,VI702)

Ethernet card Ethernet cardFoundationfieldbusH1interfacecard

Ethernet cardCOMport Ethernet Card

*1: ThespecifiedhardwarerequirementsdonotincludetherequirementforthirdpartyCommDTM/GatewayDTM.RefertotherespectiveDTMdocumentation.

*2: Thetotalmemoryrequirementshouldbethesumofthememoryrequirementforeachrequiredfunctionandconnectedsystem.

All-in-one configuration (when all components – PRM server, Field communications server, and PRM client - are installed in a single computer)

NumberofconnectableFCS/SCS:Maximum24stationsorless.Whenthenumberofstationsexceeds25,installPRMserverandfieldcommunicationsserveronseparatecomputers.

CPU:ThemaximumCPUcapabilityamongthoserequiredfortherespectivepackages,orhigher.Mainmemory:Totalsumofmemorysizerequiredfortherespectivepackagesortheoperatingsystem(whichever

is higher) or more.Harddiskcapacity:Inadditiontothetotalsumofavailableharddiskspacesrequiredfortherespectivepackages,

approx.1GBormoreofvirtualmemoryareaisrequired.Displayresolution/colors:1024x768orhigher,256colorsormore

OPC server (for STARDOM system)CPU:Pentium300MHz,400MHz,orfasterrecommendedMainmemory:256MB,512MB,ormorerecommendedDiskcapacity:Minimum1GBoffreespace.Ethernetcard:100BASE-TX,10BASE-T,10BASE-5

ForSTARDOMconnection,twocommunicationdevicesarerequiredtosegregateinformationandcontrolnetworks.

Sep. 7, 2016-00

Page 16: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

16

All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 33Y05Q10-32E

l Software requirementsPRM server, PRM client, and Field communications server

Windows XP Professional

Windows Server 2003

Windows Server 2003 R2

Windows Vista Business Edition

Windows 7 Professional

Windows Server 2008

Standard

Windows Server

2008 R2 Standard

32-bit 32-bit 32-bit 32-bit 64-bit 32-bit 64-bitSP2 SP3 SP1 SP2 — SP2 SP1 SP2 SP1 SP2 SP1

R3.01 X N/A X N/A X N/A N/A N/A N/A N/A N/A

R3.02 X N/A N/A X N/A X N/A N/A N/A N/A N/A

R3.03 N/A X N/A X N/A X X N/A N/A N/A N/A

R3.04 N/A X N/A X N/A X X N/A N/A N/A N/A

R3.05 N/A X N/A X N/A X X X N/A X N/A

R3.10 N/A N/A N/A N/A N/A N/A N/A X X X X

R3.11 N/A N/A N/A N/A N/A N/A N/A X X X X

R3.12 N/A N/A N/A N/A N/A N/A N/A X X X X

R3.20 N/A N/A N/A N/A N/A N/A N/A X X X X

R3.30 N/A N/A N/A N/A N/A N/A N/A X X X X

R3.31.00/R3.31.10 N/A N/A N/A N/A N/A N/A N/A X X X X

SP:Servicepack X:Applicable N/A:Notapplicable

PRM serverInternet Explorer 8.0, 9.0, or 11.0MicrosoftSQLServer2012SP3(32-bit)isusedasadatabasesoftwareandisincludedinthesoftwaremedia(SSSSM02) for the Plant Resource Manager. (R3.31.10)

PRM clientSoftwarefordocument:AdobeReader10.1,11.0,andDCField communication serverDriver: WhenPRMisconnectedwithCENTUMVP/CS3000and/orProSafe-RS,acontrolnetworkdriver (Vnet/IPorVnet)isrequired.(*1) ForconnectingwithsimplifiedsystemforFF-H1deviceadjustment,FF-H1fieldbusinterfacecarddriver

isrequired.Forcommunicatingwithdevicesviathird-partygatewaydevices,thethird-partyCommDTM/GatewayDTMarerequired(*2)

*1: Thecontrolnetworkdriverorcontrolnetworkitnerfacecards(VF702/VF701)arenotrequiredwhencommunicatingwithHARTdevicesviaHARTmultiplexersandCommDTM/GatewayDTM.

*2: Asforthethird-partysuppliedCommDTM/GatewayDTM,pleaseconfirmthevendorforwhichOSissupported.

l Software requirements for connected systemCENTUM VPCENTUMVP:R4.01orlater R4.01orlatertosupportHARTcommunication R4.02.30orlatertosupportISA100fieldwirelesscommunication R4.03.00orlatertosupportFastdevicepatrolforHARTForconnectingwithCENTUMVP,ExaopcOPCinterfacepackage(forHIS)R4.01orlaterorExaopcOPCInterfacePackage(NTPF100)R3.50orlaterisrequired.

CENTUM CS 3000CS 3000: R3.01 or later R3.02orlatertosupportHARTdevices R3.07orlatertonotifyHISofoperatorguidemessage R3.08orlaterforassociationwithConsolidatedalarmmanagementsoftwareforHIS(CAMSforHIS)ForconnectingwithCENTUMCS3000,ExaopcOPCinterfacepackage(forHIS)R3.01orlaterorExaopcOPCinterfacepackage(NTPF100)R3.01orlaterisrequired.AsforHARTdevicesupport,ExaopcOPCinterfacepackage(forHIS)R3.02orlaterisrequired.

June 30, 2017-00

Page 17: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

17<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation GS 33Y05Q10-32E

Exaopc OPC interface packages required for connecting PRM with CENTUM systems

PurposeExaopc OPC interface package

(for HIS) (Model: LHS2411)

Exaopc OPC interface package(Model: NTPF100)

PRMtoacquirealarmmessagesfromCENTUMHIS X X

NotifyoperatorguidemessagesfromPRMtoCENTUMHIS X X(*1)

PRMtosynchronizethemaintenancemarkswithCENTUMoperation marks X X(*1)

X:Available*1: SupportedbyPRMR3.30orlaterrevision.

ProSafe-RSProSafe-RS: R1.02 or later R2.20orlatertosupportupstreamprojects R3.02.10orlatertosupportVnet/IPnarrowbandsystem R4.01.00orlatertosupportdevicestatusnotificationforHARTdevicesthatareconnectedtoN-IO.ForconnectingwithProSafe-RS,ExaopcOPCinterfacepackage(forHIS)needstobeR3.06orlater;andR3.07orlatertonotifyHISofoperatorguidemessage.Or,useExaopcOPCinterfacepackage(NTPF100)R3.01orlater.

STARDOMSTARDOM: R1.40orlater R1.60orlatertosupportHARTdevicesFCN/FCJOPCServerforWindows:R1.40orlater R1.60orlatertosupportHARTdevices

FieldMatePRM: R3.02orlatertosupportsynchronizationwithFieldMate.FieldMate: R1.03orlatertosupportsynchronizationwithPRM.

YOKOGAWA PRODUCTS AVAILABLE TO RESIDE WITH PRM ON THE SAME COMPUTER

l PRM clientCENTUMVPHIS CENTUMCS3000/HIS ProSafe-RS SENG STARDOMHMIClientComputer

MODELS AND SUFFIX CODESPRM Basic Set (for new installation)

Description Model PRMSET Plant resource manager basic set

Suffix Codes -S Basicsoftwarelicenseandmediafee 1 Always1 1 Englishversion

Option Codes

/N0025 Maximumnumberofconnecteddevices:25/N0300 Maximumnumberofconnecteddevices:300/N1000 Maximumnumberofconnecteddevices:1000/N3000 Maximumnumberofconnecteddevices:3000

Note: ThebasicsetincludeslicensesofaPRMclient,aPRMserver,andaFieldcommunicationsserver;asoftwaremediaforPRM;adevicefilesmedia;andanelectronicinstallationmanualmedia.

Sep. 7, 2016-00

Page 18: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

18

All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 33Y05Q10-32E

PRM server (for new installation)

DescriptionModel SSS7700 PlantResourceManager(server)[Mediamodel:SSSSM02-C11]

Suffix Codes

-S Basicsoftwarelicense-C Multiple software licenses (for 2 or more) 1 Always1 1 Englishversion

Option Codes /N0300 MaximumNumberofconnecteddevices:300/N1000 MaximumNumberofconnecteddevices:1000/N3000 MaximumNumberofconnecteddevices:3000

Note: EveryprojectrequiresonePRMserver.Note: ThispackagecannotbeinstalledwithacomputerwhereCENTUMVP/CS3000HIS/ENG,ProSafe-RSSENG,or

STARDOMHMIclientisinstalled.Note: ThispackagecanbeinstalledinasinglecomputerwhereaPRMClientandaFieldcommunicationsserverareinstalled.Note: ExaopcOPCinterfacepackageforHIS(LHS2411)isrequiredtoacquiredevicealarmsandevents.

PRM server (for expansion)

Description Model SSS7700 PlantResourceManager(server)[Mediamodel:SSSSM02-C11]

Suffix Codes -A Softwarelicenseforadditionaldevices 1 Always1 1 Englishversion

Option Codes

/N0003 Expandmaximumnumberofconnecteddevices:25to300/N0010 Expandmaximumnumberofconnecteddevices:25to1000/N0310 Expandmaximumnumberofconnecteddevices:300to1000/N0030 Expandmaximumnumberofconnecteddevices:25to3000/N0330 Expandmaximumnumberofconnecteddevices:300to3000/T01 Add1000unitsofconnecteddevices/T02 Add2000unitsofconnecteddevices

Note: Optioncodesof/T01and/T02areapplicabletothePRMserverlicensefor1000devicesonlyandthetotalnumberofconnecteddevicesshouldnotexceed3000deviceswiththisoption.

PRM client

Description Model SSS7710 PlantResourceManager(client)[Mediamodel:SSSSM02-C11]

Suffix Codes

-S Basicsoftwarelicense-C Multiple software licenses (for 2 or more) 1 Always1 1 Englishversion

Note:ThispackagecanbeinstalledwithacomputerwhereCENTUMVP/CS3000HIS/ENG,ProSafe-RSSENG,orSTARDOMHMIclientisinstalled.

Note: ThispackagecanbeinstalledinasinglecomputerwhereaPRMServerandaFieldcommunicationsserverareinstalled.However,insuchcase,thispackagecannotbeinstalledonthesamecomputerwhereCENTUMVP/CS3000’sHIS/ENG,ProSafe-RS’sSENG,and/orSTARDOM’sHIMclientreside.

Field communications server

Description Model SSS7720 FieldCommunicationsServer[Mediamodel:SSSSM02-C11]

Suffix Codes

-S Basicsoftwarelicense-C Multiple software licenses (for 2 or more) 1 Always1 1 Englishversion

Note: The functions to communicate with Foundationfieldbus,HART,PROFIBUS,andISA100.11adevicesisincludedinthebasic software license.

Note: ThispackagecannotbeinstalledwithCENTUMVP/CS3000HIS/ENG,ProSafe-RSSENG,orSTARDOMHMIclientcomputer.

Note: ThispackagecanbeinstalledinasinglecomputerwhereaPRMserverandaPRMclientareinstalled.

Sep. 7, 2016-00

Page 19: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

19<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation GS 33Y05Q10-32E

Documenting calibrator interface for PRM client

Description Model SSS7711 DocumentingCalibratorInterface[Mediamodel:SSSSM02-C11]

Suffix Codes -S Basicsoftwarelicense 1 Always1 1 Englishversion

Option Code /FLK01 ForFluke743B/744/754

Note: AbasiclicenseisvalidforinstallationsintwoormorePRMclientcomputers.Software media for Plant Resource Manager

Description Model SSSSM02 Software media for Plant Resource Manager

Suffix Codes -C Suppliedmedia:DVD-ROM 1 Always1 1 Englishversion

Note: TheelectronicinstructionmanualforthissoftwareisincludedinthemediamodelSSSSD02.Device files media

Description Model SSSSM03 Devicefilesmedia

Suffix Codes -C Suppliedmedia:DVD-ROM 1 Always1 1 Englishversion

Note: ThismediacontainsfielddevicerelatedfilessuchasDDandDTM.Electronic instruction manual media for PRM

Description Model SSSSD02 Electronic instruction manual media for Plant Resource Manager

Suffix Codes -C Suppliedmedia:CD-ROM 1 Always1 1 Englishversion

Note: ThePRMsoftwaremedia(SSSSM02)isrequiredtousethismedia.Note: Nolicenseisrequiredtousetheelectronicinstructionmanual.

PLUG-IN ValveNavi

Description Model SSS7750 PLUG-INValveNavi[Mediamodel:SSSAM02-C11]

Suffix Codes

-S Basicsoftwarelicense-C Multiple software license (for 2 or more) 1 Always1 1 Englishversion

Option Code /FF-H1 For Foundationfieldbusdevices(*1)

Note: This package runs on a computer where a PRM client (SSS7710) is installed.Note: OnlyFoundationfieldbusdevicesaresupported.Note: ThispackageisfortousewithYVP110advancedvalvepositioner.*1: ToconnectwithFoundationfieldbusdevices,ensuretospecifytheoptioncodeof“/FF-H1.”

Software media for PLUG-IN ValveNavi

Description Model SSSAM02 PLUG-INapplicationmediaforPlantResourceManager

Suffix Codes -C Suppliedmedia:CD-ROM 1 Always1 1 Englishversion

Note: ElectronicinstructionmanualforPLUG-INValveNaviisincludedinthissoftwaremedia.FCN/FCJ OPC server for WindowsFor more information, refer to GS 34P02Q61-01E.

Sep. 7, 2016-00

Page 20: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

20

All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 33Y05Q10-32E

SOFTWARE LICENSE VERSION UPGRADE FROM R2 TO R3ThissectionisdedicatedforthePRMR2userswhowishtoupgradetoR3forthebenefitofusingnewfunctionsthatareonlyavailablefromR3.PurchaseeveryupgradingR3licensethatmatchwiththeexistingR2(basicandmultiplelicenses).SpecifythesamenumberofconnecteddevicesasR2.

PRM server for upgrading from R2 to R3

Description Model SSS7700RU PlantResourceManager(server)upgrade[Mediamodel:SSSSM02-C11]

Suffix Codes

-S Basicsoftwarelicense-C Multiple software license (for 2 or more) 1 Always1 1 Englishversion

Option Codes /N0300 Maximumnumberofconnecteddevices:300/N1000 Maximumnumberofconnecteddevices:1000/N3000 Maximumnumberofconnecteddevices:3000

Note: Theoptioncodeof“/N0100”inR2.10orearlierformaximumnumberofconnecteddevices100unitshasbeenexpandedto300unitsinR3.Specify“/N0300”inplaceof“/N0100.”

Note: PRMR3.12requiresMicrosoftSQLServer2012whichdoesnotsupportWindows2000/XP/2003.TherearetwowaystocopewithPRMR2operatingonWindows2000/XP/2003.OneistonewlyinstallR3.12.TheotheristoupgradetoR3.04first,replacetheOStothenewone,theninstallR3.12.Inthelattercase,thedevicefilesandotherdatabasecanbesaved.

PRM client for upgrading from R2 to R3

Description Model SSS7710RU PlantResourceManager(client)upgrade[Mediamodel:SSSSM02-C11]

Suffix Codes

-S Basicsoftwarelicense-C Multiple software license (for 2 or more) 1 Always1 1 Englishversion

Field communications server for upgrading from R2 to R3

Description Model SSS7720RU FieldCommunicationsServerupgrade[Mediamodel:SSSSM02-C11]

Suffix Codes

-S Basicsoftwarelicense-C Multiple software license (for 2 or more) 1 Always1 1 Englishversion

Note: CommunicationwithHARTdevicesisincludedasastandardfunctionfromR3,andthereisnoneedtospecify“/HART”option code which was necessary for R2.

Documenting calibrator interface for upgrading from R2 to R3

Description Model SSS7711RU DocumentingCalibratorInterfaceupgrade[Mediamodel:SSSSM02-C11]

Suffix Codes -S Basicsoftwarelicense 1 Always1 1 Englishversion

Option Codes /FLK01 ForFluke743B/744/754

Sep. 7, 2016-00

Page 21: General Models SSS7700, SSS7710, 6SHFL¿FDWLRQV … · General 6SHFL¿FDWLRQV   Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750 Plant

21<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation GS 33Y05Q10-32ESubjecttochangewithoutnotice.

PRM basic set for upgrading from R2 to R3

Description Model PRMSETRU Plant Resource Manager basic set upgrade

Suffix Codes -S Basicsoftwarelicenseincludesupgradesandmediafees 1 Always1 1 Englishversion

Option Codes

/N0025 Numberofconnecteddevice:25unitsorless/N0300 Numberofconnecteddevice:300unitsorless/N1000 Numberofconnecteddevice:1000unitsorless/N3000 Numberofconnecteddevice:3000unitsorless

Note: PRM basic set for upgrading can only be purchased when a user has R2 PRMSET. Specify the number of connecting devicesasthesameastheexistingone.

Note: ThebasicsetincludesaPRMserver,aPRMclient,afieldcommunicationsserver,asoftwaremediaforPRM,andanelectronic instruction manual media.

Note: Theoptioncodeof“/N0100”inR2.10orearlierformaximumnumberofconnecteddevices100unitshasbeenexpandedto300unitsinR3.Specify“/N0300”inplaceof“/N0100.”

ORDERING INFORMATIONSpecifymodelandsuffixcodes.

TRADEMARKS•PRMisaregisteredtrademarkofYokogawaElectricCorporation.•CENTUM,Vnet/IPandProSafeareregisteredtrademarksofYokogawaElectricCorporation.•STARDOMisatrademarkofYokogawaElectricCorporation.•Otherproductandcompanynamesappearinginthisdocumentaretrademarksorregisteredtrademarksoftheirrespectiveholders.

Sep. 7, 2016-00