GEH-6804 Industrial Remote Interface Unit (IRIU) · The Industrial Remote Interface Unit (IRIU) I/O...
Transcript of GEH-6804 Industrial Remote Interface Unit (IRIU) · The Industrial Remote Interface Unit (IRIU) I/O...
Public Information
GEH-6804
Industrial Remote Interface Unit (IRIU)
User Guide
November 2019
2 GEH-6804 Public Information IRIU User Guide
These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible
contingency to be met during installation, operation, and maintenance. The information is supplied for
informational purposes only, and GE makes no warranty as to the accuracy of the information included herein.
Changes, modifications, and/or improvements to equipment and specifications are made periodically and these
changes may or may not be reflected herein. It is understood that GE may make changes, modifications, or
improvements to the equipment referenced herein or to the document itself at any time. This document is
intended for trained personnel familiar with the GE products referenced herein.
GE may have patents or pending patent applications covering subject matter in this document. The furnishing of this document does not provide any license whatsoever to any of these patents.
Public Information – This document contains non-sensitive information approved for public disclosure.
GE provides the following document and the information included therein as is and without
warranty of any kind, expressed or implied, including but not limited to any implied statutory
warranty of merchantability or fitness for particular purpose.
For further assistance or technical information, contact the nearest GE Sales or Service Office, or an authorized GE Sales Representative.
Issued: November 2019 © 2019 General Electric Company.
* Indicates a trademark of General Electric Company and/or its subsidiaries.
All other trademarks are the property of their respective owners.
IRIU User Guide Public Information GEH-6804 3
Safety Symbol Legend
Warning
Indicates a procedure or condition that, if not strictly observed, could
result in personal injury or death.
Caution
Indicates a procedure or condition that, if not strictly observed, could
result in damage to or destruction of equipment.
Attention
Indicates a procedure or condition that should be strictly followed to
improve these applications
4 GEH-6804 Public Information IRIU User Guide
Contents 1 Overview ............................................................................................................................................... 7
2 Specification .......................................................................................................................................... 8
2.1 Agency Certifications and Standards ............................................................................................ 8
3.1 Chassis Bonding............................................................................................................................. 9
3.2 Mating Half Connectors .............................................................................................................. 10
3.3 Harness Shielding, Screened Cables ........................................................................................... 10
3.4 Pollution Environment ................................................................................................................ 10
4.1 Power Requirements .................................................................................................................. 12
4.2 Embedded Ethernet Interface (PROFINET) ................................................................................. 13
4.2.1 Embedded Ethernet Specifications ..................................................................................... 13
4.2.2 Network I/O Device Diagnostics ......................................................................................... 13
4.3 Protection Functions ................................................................................................................... 14
4.4 Power-off and Restart Logic ........................................................................................................ 14
4.5 Failure Analysis Probability ......................................................................................................... 14
5.1 ToolboxST Configuration and Parameters .................................................................................. 15
5.2 Configuration and Diagnostics .................................................................................................... 17
5.3 Thermocouple, Type K ................................................................................................................ 18
5.3.1 Specifications ...................................................................................................................... 18
5.3.2 Configuration ...................................................................................................................... 19
5.3.3 Inputs .................................................................................................................................. 19
5.4 Installation .................................................................................................................................. 20
5.5 Current Input (with Loop Power) ................................................................................................ 23
5.5.1 Specification ........................................................................................................................ 24
5.5.2 Configuration ...................................................................................................................... 24
5.5.3 Inputs .................................................................................................................................. 25
5.5.4 Installation .......................................................................................................................... 25
5.6 Current Input (External Loop Power) .......................................................................................... 28
5.6.1 Specification ........................................................................................................................ 28
5.6.2 Configuration ...................................................................................................................... 29
5.6.3 Inputs .................................................................................................................................. 29
5.6.4 Installation .......................................................................................................................... 30
IRIU User Guide Public Information GEH-6804 5
5.7 RTD, PT100 (IEC60751) 3 Wire .................................................................................................... 31
5.7.1 Specification ........................................................................................................................ 31
5.7.2 Configuration ...................................................................................................................... 32
5.7.3 Inputs .................................................................................................................................. 32
5.7.4 Installation .......................................................................................................................... 33
5.8 Current Output, 0-20mA ............................................................................................................. 34
5.8.1 Specification ........................................................................................................................ 34
5.8.2 Configuration ...................................................................................................................... 34
5.8.3 Inputs .................................................................................................................................. 35
5.8.4 Outputs ............................................................................................................................... 35
5.8.5 Installation .......................................................................................................................... 35
5.9 Speed Input with Repeater ......................................................................................................... 36
5.9.1 Specification ........................................................................................................................ 36
5.9.2 Configuration ...................................................................................................................... 36
5.9.3 Inputs .................................................................................................................................. 37
5.9.4 Installation .......................................................................................................................... 37
5.10 Relay Drive with Fuse Monitor .................................................................................................... 39
5.10.1 Specification ........................................................................................................................ 39
5.10.2 Configuration ...................................................................................................................... 40
5.10.3 Inputs .................................................................................................................................. 40
5.10.4 Outputs ............................................................................................................................... 40
5.10.5 Installation .......................................................................................................................... 40
5.11 Contact Inputs, Isolated .............................................................................................................. 43
5.11.1 Specification ........................................................................................................................ 43
5.11.2 Configuration ...................................................................................................................... 43
5.11.3 Inputs .................................................................................................................................. 44
5.11.4 Installation .......................................................................................................................... 44
5.12 Woodward GS6 Valve ................................................................................................................. 45
5.12.1 Specification ........................................................................................................................ 45
5.12.2 Configuration ...................................................................................................................... 46
5.12.3 Inputs .................................................................................................................................. 46
5.12.4 Outputs ............................................................................................................................... 49
5.12.5 Installation .......................................................................................................................... 49
6 GEH-6804 Public Information IRIU User Guide
5.13 GE Sensing DPS 8000 Pressure Transducer ................................................................................. 50
5.13.1 Specification ........................................................................................................................ 50
5.13.2 Configuration ...................................................................................................................... 51
5.13.3 Inputs .................................................................................................................................. 51
5.13.4 Installation .......................................................................................................................... 52
5.14 Dynamic Pressure, PCB Piezotronics, Dual Sensor...................................................................... 52
5.14.1 Specification ........................................................................................................................ 54
5.14.2 Configuration ...................................................................................................................... 54
5.14.3 Inputs .................................................................................................................................. 56
5.14.4 Outputs ............................................................................................................................... 59
5.14.5 Installation .......................................................................................................................... 60
6.1 Maintenance ............................................................................................................................... 61
6.2 Repair and Replacement ............................................................................................................. 61
6.3 Repair and Renewals ................................................................................................................... 62
IRIU User Guide Public Information GEH-6804 7
1 Overview The Industrial Remote Interface Unit (IRIU) I/O device provides a signal conversion and manipulation interface between sensors and effectors. The IRIU utilizes an embedded micro-controller that runs factory-loaded software specific to its application and a round-robin scheduler that does not require an operating system. It can be mounted on plant equipment in harsh environments and communicates within a system through an Ethernet connection. The module’s highly flexible and rugged design suits a diverse range of applications, such as wind turbines, gas and steam turbines, and combined-cycle power plants.
The IRIU performs the following functions:
• Reads data from analog and digital sensors
• Performs required signal processing and conditioning
• Generates the analog and digital signals for effectors
• Communicates with the system controller
• Reads and applies the system configurable parameters required by the application
IRIU I/O Device
The IS421IRIUH1A is the only IRIU version currently available and supports Simplex configuration only.
The IRIU can be configured using the ToolboxST* application. It is integrated with ControlST* Software
Suite V07.07.00C and later but may be used with earlier versions upon download of the GSDML. Refer
to the chapter Configuration for IRIU configuration details for each I/O type.
Note: For additional information, refer to the following documents:
• ToolboxST User Guide for Mark Controls Platform (GEH-6700 or GEH-6703)
• ControlST Software Suite Release Notes (GEI-100746)
8 GEH-6804 Public Information IRIU User Guide
2 Specification
Item IRIU Specification
Input Power Refer to the section Power Requirements
Programming Alternative interface configurations can be supplied upon request
Dimensions 411 x 391 x 39 mm (16.2 x 5.4 x 1.5 in) (H x D x W)
Weight 6 kg (13 lb)
Mounting Refer to the section Mounting Requirements
Cooling Convection
Operating temperature
-40 to 80°C (-40 to 176°F), with excursions to 90°C (194 °F) for 30 minutes
Storage Temperature -40 to 85°C (-40 to 185°F)
Humidity 5% to 90% non-condensing
Reliability MTBF across operating temperature
350k hrs (30°C) to 150k hrs (80°C) typical
Certifications Refer to the section Agency Certifications and Standards
Interface Specification
Refer to the chapter Configuration
2.1 Agency Certifications and Standards
The IRIU is compliant with the following certifications and standards:
• ATEX Directive 2014/34/EU: BS EN 60079-0; BS EN 60079-7;
o Group II Category 3 Environment G Explosion Protection Ex ec Gas Group IIC
Temperature Class T3 Equipment Protection Level Gc (II 3G Ex ec IIC T3 Gc)
• IP66 rated: BS EN 60529 International Protection Directive
• CE marking directive: defined in ATEX Directive 2014/34/EU
• EMC Directive 2014/30/EU: BS EN 61326-1 Electrical equipment for measurement, control
and laboratory use†
• ROHS 2011/65/EU
†Note: This was achieved using fully screened cable, terminated within the backshell of the circular
connectors.
IRIU User Guide Public Information GEH-6804 9
3 Mounting and Installation Requirements The mounting requirements for the IRIU are as follows:
• Directly mount the IRIU to the desired location using the four mounting points
• Unit can be mounted in any orientation; however, it is recommended that it is not mounted with the connectors facing upwards to avoid the potential for liquid to pool within the connectors
• The operating temperature envelope is 25 mm (0.98 in) from any point on the IRIU
IRIU Installation Drawing
3.1 Chassis Bonding The unit chassis is fully isolated from field power and instrument power electronics circuitry. The unit does
not require the chassis to be bonded for safe and correct operations; however, ATEX regulations require
a chassis bonding strap to be installed and a fixing point is provided for this purpose (refer to installation
drawing).
Caution
To maintain ATEX compliance and prevent equipment damage, do not
remove, insert, or adjust connectors while power is applied to the
equipment.
10 GEH-6804 Public Information IRIU User Guide
3.2 Mating Half Connectors The following table provides the connector part numbers for J1 to J5 which are all MIL-DTL-38999 Series
III type, along with suggested mating halves.
Connector Part Number
IRIU Connector Suggested Mating Half
J1 AE40E/20FJ35AN-201 D38999/26FJ35SN
J2 AE40E/20FJ35AA-201 D38999/26FJ35SA
J3 AE40E/20FJ35AB-201 D38999/26FJ35SB
J4 AE40E/20FJ35AC-201 D38999/26FJ35SC
J5 AE40E/20FJ35AD-201 D38999/26FJ35SD
The following table provides the connector part numbers for J6 and J7 which are screw locking M12 type,
along with suggested mating halves†.
Connector Part Number
IRIU Connector Suggested Mating Half†
J6 Harting 21033712403 Harting 21032811405
J7 Harting 21033712403 Harting 21032811405
† †Note: The suggested mating half is for example only from a product line of compatible connectors. The
integrator should review compatible mating half suitability for intended application.
3.3 Harness Shielding, Screened Cables It is recommended that cable harness outer shielding is terminated at both ends. The IRIU EMC
compliance was achieved using fully screened cable, terminated within the backshell of the circular
connectors.
Note: Individual, specific interface signal screened cables, for example, thermocouple interface signals,
will be terminated to ground pins as defined by the interface definitions throughout the chapter
Configuration.
3.4 Pollution Environment The IRIU unit should be used in an area of at least pollution degree 3, as defined in IEC 60664-1.
IRIU User Guide Public Information GEH-6804 11
4 Operation
An IRIU provides a variety of flexible analog interfaces with industrial application subsystem sensors and effectors and with internal system components. It also provides a quantity of serial bus interfaces, which may be used to provide local field buses and/or to connect to other industrial application data bus standards. It provides a connection to the industrial application system network to allow it to form part of, and be functionally integrated with, a distributed management system, or simply to enable it to communicate with other industrial application instruments.
System Interface Context Diagram
12 GEH-6804 Public Information IRIU User Guide
4.1 Power Requirements
Item Min Nom Max Units
Input Power 28 Watts
Voltage 20 28 32 Vdc
Input Capacitance 26 32 µF
Reverse polarity protection is
provided
Reversing the + and - input will not damage the
IRIU, nor will it power up
IRIU Power Requirements
Instrument power within the unit is isolated from field power supply, unit chassis ground and the internal circuit reference (GND).
The instrument power input pins are given below;
Description Pin
28V Instrument Power (+ve) J1-025
28V Instrument Power Return (-ve) J1-015
Field power within the unit is isolated from instrument power and chassis ground.
The field power input pins are given below;
Description Pin
24V Field Power (+ve) J5-002
24V Field Power Return (-ve) J5-003
IRIU User Guide Public Information GEH-6804 13
4.2 Embedded Ethernet Interface (PROFINET) The IRIU contains an Ethernet interface using the PROFINET standard that maps analog and digital I/O through a Slave node to the Mark* VIe controller. It provides the functions, services, and protocols running 100Mbps Ethernet interfaces as follows:
• Cyclic exchange of input and output data from PROFINET I/O devices, asynchronous with Mark VIecontroller frame
• Displays values of inputs and outputs through ToolboxST application• Displays diagnostic messages from devices to resolve issues
The Ethernet connection is made through either the J6 or J7 connector as described in Mating Half Connectors; only one connection is required. The unit utilizes the PROFINET protocol, however, is not
PROFINET certified.
Interface Description Pin
J6
Receive Low 4
Receive High 2
Transmit Low 3
Transmit High 1
J7
Receive Low 4
Receive High 2
Transmit Low 3
Transmit High 1
For configuration details, refer to the ToolboxST User Guide for Mark Controls Platform (GEH-6700 or GEH-6703), the section PPNG PROFINET Module Configuration.
4.2.1 Embedded Ethernet Specifications
4.2.2 Network I/O Device Diagnostics
Diagnostic alarms are not supported.
Diagnostic data is included in the cyclic data. Refer to chapter Configuration and Diagnostics.
Item Specification
Ethernet cabling supported Cat 5e STP
I/O device data update rates Configurable: 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms, 512ms
Number of MAC addresses Three
Network topology supported Star (typical), Line (daisy-chain), or combination
Maximum data rate 6 KB per millisecond
Network Speed 100 Mbps full duplex on dedicated network
Media Redundancy Protocol (MRP) Not supported
14 GEH-6804 Public Information IRIU User Guide
4.3 Protection Functions The IRIU does not provide any protection or safety mechanisms.
4.4 Power-off and Restart Logic On application of power to the IRIU, all driven outputs are held in a de-energized state while it performs the following actions;
• Perform a set of tests to determine its operational integrity. o On failure the IRIU performs a restart to attempt a recovery. o On successful completion of the tests the IRIU continues.
• Await initialization and parameterization from the controller. Once initialized the IRIU proceeds with normal operation until the IRIU is;
• disconnected from the controller; when it will return to an initialization state waiting for reconnection to the controller; all driven outputs are held in a de-energized state.
• A manual shutdown occurs when instrument power to the IRIU is removed; all driven outputs are held in a de-energized state.
• A global fault is detected (which affect the operational integrity of the IRIU) the IRIU will first restart to attempt a recovery.
4.5 Failure Analysis Probability Reliability parameters are calculated using MIL-HDBK-217 FN2 Parts Count models and the appropriate
failure rates from the IRIU failure modes and effects.
Failure Rate (In FPMH): 8.6 (30 oC) to 19.7 (80 oC)
MTBF (hrs): 116,830 (30 oC) to 50,795 (80 oC) (MIL-HDBK-270 parts count prediction only)
Environment: GB, GC - Ground Benign, Controlled
IRIU User Guide Public Information GEH-6804 15
5 Configuration
5.1 ToolboxST Configuration and Parameters
An Embedded PROFINET Gateway (Embedded PPNG) module or PPNG PROFINET Gateway
Module is required to interface to the IRIU for use as part of a Mark VIe control system.
The IRIU supports a simplex Line PROFINET topology.
For more information, refer to the Mark VIe and Mark VIeS Control Systems Volume II: General-
purpose Applications System Guide (GEH-6721_Vol_II), the sections Embedded PROFINET
Gateway (Embedded PPNG) Module or PPNG PROFINET Gateway Module.
To import and configure the GSDML file
1. Right click on the PPNG and select Add PROFINET IO Device.
2. Browse and Import the GSDML file from the archive.
3. Select Add Device to add the IRIU to ToolboxST.
4. Select the imported GSDML and make sure the Device Host Name in the Configuration area is in accordance with the following figure and the following table.
16 GEH-6804 Public Information IRIU User Guide
The IRIU Station Name is determined using the configuration pins on the unit; the Device Host Name
must align with this selection. Configuration is made by loop-back connections between the indicated
pins in the following table, loop-back connections should be kept as short as possible to avoid the
possibility of interference.
For example, Station Name industrialriu08 is set by making a loop-back connection from J4-053 to
J4-043 & J4-019 to J4-020 and leaving J4-052, J4-041 and J4-040 unconnected.
Station Name Configuration Pin
J4-053 J4-052 J4-041 J4-040 J4-020
industrialriu00 - - - - J4-019
industrialriu01 - - - J4-029 J4-019
industrialriu02 - - J4-030 - J4-019
industrialriu03 - - J4-030 J4-029 J4-019
industrialriu04 - J4-042 - - J4-019
industrialriu05 - J4-042 - J4-029 J4-019
industrialriu06 - J4-042 J4-030 - J4-019
industrialriu07 - J4-042 J4-030 J4-029 J4-019
industrialriu08 J4-043 - - - J4-019
industrialriu09 J4-043 - - J4-029 J4-019
industrialriu10 J4-043 - J4-030 - J4-019
industrialriu11 J4-043 - J4-030 J4-029 J4-019
industrialriu12 J4-043 J4-042 - - J4-019
industrialriu13 J4-043 J4-042 - J4-029 J4-019
industrialriu14 J4-043 J4-042 J4-030 - J4-019
industrialriu15 J4-043 J4-042 J4-030 J4-029 J4-019
Note: – indicates the configuration pin should be left unconnected.
IRIU User Guide Public Information GEH-6804 17
5.2 Configuration and Diagnostics
There are two classes of failures of the IRIU; global failures which affect the operational integrity of the
IRIU and local failures which are isolated to a selection of interfaces.
A global failure is when an internal test failure occurs which affects the operational integrity of
the IRIU all outputs are held in a de-energized state and there are no external communications
from the IRIU. If a global failure occurs the IRIU should be retuned for repair or replacement as
defined in Repair and Replacement.
Care should be taken as the IRIU will appear in a similar state during normal operations if it has
not yet established communication with the controller. Therefore, before determining the IRIU has
a global failure the following should be confirmed;
• Physical configuration pins are as defined in
• ToolboxST Configuration and Parameters and match the Device Host Name in
ToolboxST.
• Instrumentation Power is correctly applied
• A connection exists between the IRIU and the PPNG (embedded or external)
A local failure is when an internal test failure occurs that does not affect the operational
integrity the IRIU and as is limited to a subset of functionality.
Degraded operations continue with the affected interfaces flagged as faulty by setting the
‘Interface Fault’ flag in the ‘Status bits’ of the slot Input data.
If any interface is flagged as faulty the ‘CBIT_UNIT_DEGRADED’ flag in the ‘Fault bits 00’ of the
Diagnostic slot is set. Additional diagnostic information is provided in the Diagnostic slot. If a
local failure occurs the IRIU should be retuned for repair or replacement as defined in Repair
and Replacement.
18 GEH-6804 Public Information IRIU User Guide
5.3 Thermocouple, Type K
The temperature is calculated from the measured thermoelectric voltage and is compensated using an internal measurement of cold-junction temperature. The measurement of the thermoelectric voltage is made through (Hw /a, /b); where (Hw /a) is the positive input and (Hw /b) the negative input. (Hw /c) provides an optional shield grounding.
The temperature is reported in degrees Celsius or Fahrenheit using (Di /a). The cold-junction temperature is reported in degrees Celsius or Fahrenheit using (Di /d). The template reports if the temperature is outside a configurable range using (Di /c). The template includes functionality to detect a sensor wire off condition which is reported using (Di /b). A software function applies additional filtering to the voltage measurement if required.
Hardware Interfaces Functional Blocks Data Interfaces
Voltage Measurement
andSoftware Filter
Hw /b: Alumel Temperature Calculation
Di /a: Temperature
Analogue (F32)
Hw /a: Chromel
Cold-Junction Temperature
Di /d: Cold Junction
Analogue (F32)
Wire off Detection
Di /b: Wire Off
Discrete
Range Check
Di /c: Out of Range
Discrete
Hw /c: Shield
Interface BIT
Di /f: Interface Fault
Discrete
5.3.1 Specifications
Item Specification
Number of channels 23
Thermocouple type K
Valid thermoelectric voltage -1.889mV to 51.355mV
A/D converter 24-bit A/D converter
Cold junction compensation Reference junction temperature measured internally
Measurement range
(Temperature) -50 to 1270°C (-58 to 2318°F)
Measurement accuracy
(Temperature) ±1.66°C (±3° F)
Reporting resolution 0.05°C (0.1° F)
Scan time All inputs are sampled every 40 milliseconds
IRIU User Guide Public Information GEH-6804 19
5.3.2 Configuration
Parameter Description Choices
Temperature Scale Selects the temperature scale of the
Temperature and Cold Junction inputs
Celsius, Fahrenheit
Upper Limit If the Temperature is greater than this
parameter, the Out of Range input will be set
True (1).
ATTENTION: This value must be greater than the
Lower Limit parameter.
Floating Point, 32-bit (REAL)
Scale defined by the Temperature
Scale parameter
Lower Limit If the Temperature is less than this parameter,
the Out of Range input will be set True (1).
ATTENTION: This value must be less than the
Upper Limit parameter.
Floating Point, 32-bit
Scale defined by the Temperature
Scale parameter
Low Pass Filter Enables a 2Hz single-pole low-pass recursive
software filter
No Filtering 2Hz
5.3.3 Inputs
Input Description Type
Temperature Compensated temperature of the k-type thermocouple
sensor.
Scale defined by the Temperature Scale parameter
Floating Point, 32-bit
Cold Junction Reference temperature used by the k-type
thermocouple interface.
Scale defined by the Temperature Scale parameter
Floating Point, 32-bit (REAL)
Status bits -
Out of Range
Indicates Temperature is outside the limits set by the
Upper Limit and Lower Limit parameters.
Discrete single bit
True (1) = Out of range
False (0) = Inside range
Status bits -
Wire Off
Indicates the Temperature is invalid due to an external
fault.
Discrete single bit
True (1) = Data is Invalid
False (0) = Data is Valid
Status bits -
Interface Fault
Indicates the Temperature is invalid due to an internal
fault.
Discrete single bit
True (1) = Fault
False (0) = No Fault
20 GEH-6804 Public Information IRIU User Guide
5.4 Installation
Each interface has up to 3 connections: wire colors follow [IEC60584] color coding. An optional GND is
allocated to each interface supporting a signal wire shield that requires termination.
Interface Description Lbl Pin No.
601_A01
Voltage Input (+) Nickel-Chromium (green) a J1-122
Voltage Input (-) Nickel-Aluminium (white) b J1-123
Shield (optional GND) c J1-116
601_A02
Voltage Input (+) Nickel-Chromium (green) a J1-124
Voltage Input (-) Nickel-Aluminium (white) b J1-125
Shield (optional GND) c J1-117
601_A03
Voltage Input (+) Nickel-Chromium (green) a J1-126
Voltage Input (-) Nickel-Aluminium (white) b J1-127
Shield (optional GND) c J1-128
601_A04
Voltage Input (+) Nickel-Chromium (green) a J1-118
Voltage Input (-) Nickel-Aluminium (white) b J1-119
Shield (optional GND) c J1-120
601_B01
Voltage Input (+) Nickel-Chromium (green) a J2-001
Voltage Input (-) Nickel-Aluminium (white) b J2-002
Shield (optional GND) c J2-009
601_B02
Voltage Input (+) Nickel-Chromium (green) a J2-003
Voltage Input (-) Nickel-Aluminium (white) b J2-004
Shield (optional GND) c J2-010
601_B03
Voltage Input (+) Nickel-Chromium (green) a J2-005
Voltage Input (-) Nickel-Aluminium (white) b J2-006
Shield (optional GND) c J2-007
601_B04
Voltage Input (+) Nickel-Chromium (green) a J2-122
Voltage Input (-) Nickel-Aluminium (white) b J2-123
Shield (optional GND) c J2-116
601_B05
Voltage Input (+) Nickel-Chromium (green) a J2-124
Voltage Input (-) Nickel-Aluminium (white) b J2-125
Shield (optional GND) c J2-117
IRIU User Guide Public Information GEH-6804 21
Interface Description Lbl Pin No.
601_B06
Voltage Input (+) Nickel-Chromium (green) a J2-126
Voltage Input (-) Nickel-Aluminium (white) b J2-127
Shield (optional GND) c J2-128
601_B07
Voltage Input (+) Nickel-Chromium (green) a J2-011
Voltage Input (-) Nickel-Aluminium (white) b J2-012
Shield (optional GND) c J2-013
601_B08
Voltage Input (+) Nickel-Chromium (green) a J2-118
Voltage Input (-) Nickel-Aluminium (white) b J2-119
Shield (optional GND) c J2-120
601_C01
Voltage Input (+) Nickel-Chromium (green) a J3-001
Voltage Input (-) Nickel-Aluminium (white) b J3-002
Shield (optional GND) c J3-009
601_C02
Voltage Input (+) Nickel-Chromium (green) a J3-003
Voltage Input (-) Nickel-Aluminium (white) b J3-004
Shield (optional GND) c J3-010
601_C03
Voltage Input (+) Nickel-Chromium (green) a J3-005
Voltage Input (-) Nickel-Aluminium (white) b J3-006
Shield (optional GND) c J3-007
601_C04
Voltage Input (+) Nickel-Chromium (green) a J3-122
Voltage Input (-) Nickel-Aluminium (white) b J3-123
Shield (optional GND) c J3-115
601_C05
Voltage Input (+) Nickel-Chromium (green) a J3-124
Voltage Input (-) Nickel-Aluminium (white) b J3-125
Shield (optional GND) c J3-117
601_C06
Voltage Input (+) Nickel-Chromium (green) a J3-126
Voltage Input (-) Nickel-Aluminium (white) b J3-127
Shield (optional GND) c J3-128
601_C07
Voltage Input (+) Nickel-Chromium (green) a J3-011
Voltage Input (-) Nickel-Aluminium (white) b J3-012
Shield (optional GND) c J3-013
22 GEH-6804 Public Information IRIU User Guide
Interface Description Lbl Pin No.
601_D01
Voltage Input (+) Nickel-Chromium (green) a J4-001
Voltage Input (-) Nickel-Aluminium (white) b J4-002
Shield (optional GND) c J4-009
601_D02
Voltage Input (+) Nickel-Chromium (green) a J4-003
Voltage Input (-) Nickel-Aluminium (white) b J4-004
Shield (optional GND) c J4-010
601_D03
Voltage Input (+) Nickel-Chromium (green) a J4-005
Voltage Input (-) Nickel-Aluminium (white) b J4-006
Shield (optional GND) c J4-007
601_D04
Voltage Input (+) Nickel-Chromium (green) a J4-011
Voltage Input (-) Nickel-Aluminium (white) b J4-012
Shield (optional GND) c J4-013
IRIU User Guide Public Information GEH-6804 23
5.5 Current Input (with Loop Power)
The sensor is connected to an internal shunt resistor using (Hw /b) and uses (Hw /c) to provide loop power. An optional unit ground is provided by (Hw /d). An external loop-back is required to connect (Hw /a) to (Hw /e); loop-back connections should be kept as short as possible.
The voltage across this shunt resistor is measured via (Hw /a) and converted into an equivalent current, which is reported via (Di /a). (Di /a) is compared to two fixed ranges which is reported on; Range Check (Di /b) and Sensor Health (Di /p).
Voltage Measurement
and Software
Filter
Current Calculation
Analogue Comparison
Hw /a: Sensor
Hw /b: Shunt 1
Rs
Analogue (F32)
Di /a: Current
Discrete
Di /b: Out of Range
Hardware Interfaces Functional Blocks Data Interfaces
Hw /c: Excitation24V
Interface BIT Discrete
Di /h: Interface FaultHw /d: Ground
Hw /e: Shunt 2
Discrete
Di /p: Sensor Health
Sen
sor
Wir
ing
Each interface supports either a two or three wire sensor using the connections, as illustrated in the following figures.
24 GEH-6804 Public Information IRIU User Guide
5.5.1 Specification
Item Specification
Number of channels 11
Interface type 2-wire or 3-wire, with loop power
A/D converter 16-bit A/D converter
Measurement range 0 to 22.7 mA
Measurement accuracy ±69 μA
Scan time All inputs are sampled every 20 milliseconds
5.5.2 Configuration
Parameter Description Choices
Range Upper
Limit
If the Value is greater than this parameter, the Out of
Range output will be set True (1).
ATTENTION: This value must be greater than the
Range Lower Limit parameter.
Signed 16-bit integer (INT)
with resolution of 1 µA/bit.
Range Lower
Limit
If the Value is less than this parameter, the Out of
Range output will be set True (1).
ATTENTION: This value must be less than the Range
Upper Limit parameter.
Signed 16-bit integer (INT)
with resolution is 1 µA/bit.
Health Upper
Limit
If the Value is greater than this parameter, the
Unhealthy output will be set True (1).
ATTENTION: This value must be greater than the
Health Lower Limit parameter.
Signed 16-bit integer (INT)
with resolution of 1 µA/bit.
Health Lower
Limit
If the Value is less than this parameter, the Unhealthy
output will be set True (1).
ATTENTION: This value must be less than the Health
Upper Limit parameter.
Signed 16-bit integer (INT)
with resolution is 1 µA/bit.
Low Pass Filter Enables a single-pole low-pass recursive software
filter with selected cut off frequency.
No Filtering
0.75Hz
1.5Hz
3Hz
6Hz
IRIU User Guide Public Information GEH-6804 25
5.5.3 Inputs
Input Description Type
Value Measured current of the loop sensor. Floating Point, 32-bit
in mA
Status bits -
Out of Range
Indicates Value is outside the limits set by the
Range Upper Limit and Range Lower Limit
parameters.
Discrete single bit
True (1) = Out of range
False (0) = Inside range
Status bits -
Sensor Health
Indicates Value is outside the limits set by the
Health Upper Limit and Health Lower Limit
parameters.
Discrete single bit
True (1) = Unhealthy
False (0) = Healthy
Status bits -
Interface Fault
Indicates the Value is invalid due to an internal
fault.
Discrete single bit
True (1) = Fault
False (0) = No Fault
5.5.4 Installation
Interface Description Lbl Pin No
630_C01
Connect to J3-008 a J3-014
Signal from Sensor b J3-021
24V Excitation from Instrument Power c J3-018
Ground (GND – 3 Wire Transmitter Only) d J3-016
Connect to J3-014 e J3-008
630_C02
Connect to J3-015 a J3-024
Signal from Sensor b J3-022
24V Excitation from Instrument Power c J3-019
Ground (GND – 3 Wire Transmitter Only) d J3-017
Connect to J3-024 e J3-015
26 GEH-6804 Public Information IRIU User Guide
Interface Description Lbl Pin No
630_C03
Connect to J3-025 a J3-034
Signal from Sensor b J3-023
24V Excitation from Instrument Power c J3-020
Ground (GND – 3 Wire Transmitter Only) d J3-027
Connect to J3-034 e J3-025
630_C04
Connect to J3-026 a J3-035
Signal from Sensor b J3-032
24V Excitation from Instrument Power c J3-029
Ground (GND – 3 Wire Transmitter Only) d J3-028
Connect to J3-035 e J3-026
630_C05
Connect to J3-036 a J3-046
Signal from Sensor b J3-033
24V Excitation from Instrument Power c J3-030
Ground (GND – 3 Wire Transmitter Only) d J3-039
Connect to J3-046 e J3-036
630_C06
Connect to J3-037 a J3-047
Signal from Sensor b J3-043
24V Excitation from Instrument Power c J3-031
Ground (GND – 3 Wire Transmitter Only) d J3-040
Connect to J3-047 e J3-037
630_C07
Connect to J3-038 a J3-057
Signal from Sensor b J3-044
24V Excitation from Instrument Power c J3-041
Ground (GND – 3 Wire Transmitter Only) d J3-050
Connect to J3-057 e J3-038
630_C08
Connect to J3-048 a J3-058
Signal from Sensor b J3-045
24V Excitation from Instrument Power c J3-042
Ground (GND – 3 Wire Transmitter Only) d J3-051
Connect to J3-058 e J3-048
IRIU User Guide Public Information GEH-6804 27
Interface Description Lbl Pin No
630_C09
Connect to J3-049 a J3-068
Signal from Sensor b J3-055
24V Excitation from Instrument Power c J3-053
Ground (GND – 3 Wire Transmitter Only) d J3-052
Connect to J3-068 e J3-049
630_C10
Connect to J3-059 a J3-069
Signal from Sensor b J3-056
24V Excitation from Instrument Power c J3-054
Ground (GND – 3 Wire Transmitter Only) d J3-062
Connect to J3-069 e J3-059
630_C11
Connect to J3-060 a J3-070
Signal from Sensor b J3-066
24V Excitation from Instrument Power c J3-064
Ground (GND – 3 Wire Transmitter Only) d J3-063
Connect to J3-070 e J3-060
28 GEH-6804 Public Information IRIU User Guide
5.6 Current Input (External Loop Power)
The sensor is connected to an internal shunt resistor and a pedestal resistor via (Hw /a, /b).
The voltage across this shunt resistor is measured and converted into an equivalent current, which is reported via (Di /a). (Di /a) is compared to two fixed ranges which is reported on; Range Check (Di /b) and Sensor Health (Di /p).
Voltage Measurement
and Software
Filter
Current Calculation
Analogue Comparison
Rs
Analogue (F32)
Di /a: Current
Discrete
Di /b: Out of Range
Hardware Interfaces Functional Blocks Data Interfaces
Interface BIT Discrete
Di /h: Interface Fault
Discrete
Di /p: Sensor Health
Hw /a: Signal
Hw /b: Return
Rp
+-
5.6.1 Specification
Item Specification
Number of channels 4
A/D converter 24-bit A/D converter
Measurement range 0 to 30 mA
Measurement accuracy ±150 μA
Scan time All inputs are sampled every 20 milliseconds
IRIU User Guide Public Information GEH-6804 29
5.6.2 Configuration
Parameter Description Choices
Range Upper
Limit
If the Value is greater than this parameter, the Out of
Range output will be set True (1).
ATTENTION: This value must be greater than the
Range Lower Limit parameter.
Signed 16-bit integer (INT)
with resolution of 1 µA/bit.
Range Lower
Limit
If the Value is less than this parameter, the Out of
Range output will be set True (1).
ATTENTION: This value must be less than the Range
Upper Limit parameter.
Signed 16-bit integer (INT)
with resolution is 1 µA/bit.
Health Upper
Limit
If the Value is greater than this parameter, the
Unhealthy output will be set True (1).
ATTENTION: This value must be greater than the
Health Lower Limit parameter.
Signed 16-bit integer (INT)
with resolution of 1 µA/bit.
Health Lower
Limit
If the Value is less than this parameter, the Unhealthy
output will be set
True (1).
ATTENTION: This value must be less than the Health
Upper Limit parameter.
Signed 16-bit integer (INT)
with resolution is 1 µA/bit.
Low Pass Filter Enables a single-pole low-pass recursive software
filter with selected cut off frequency
No Filtering
0.75Hz
1.5Hz
3Hz
6Hz
5.6.3 Inputs
Input Description Type
Value Measured current of the loop sensor. Floating Point, 32-bit
in mA
Status bits -
Out of Range
Indicates Value is outside the limits set by the
Range Upper Limit and Range Lower Limit
parameters.
Discrete single bit
True (1) = Out of range
False (0) = Inside range
Status bits -
Sensor Health
Indicates Value is outside the limits set by the
Health Upper Limit and Health Lower Limit
parameters.
Discrete single bit
True (1) = Unhealthy
False (0) = Healthy
Status bits -
Interface Fault
Indicates the Value is invalid due to an internal
fault.
Discrete single bit
True (1) = Fault
False (0) = No Fault
30 GEH-6804 Public Information IRIU User Guide
5.6.4 Installation
Interface Description Lbl Pin No
621_A01 Current Input a J1-010
Current Input Return b J1-003
621_A02 Current Input a J1-011
Current Input Return b J1-004
621_A03 Current Input a J1-012
Current Input Return b J1-005
621_A04 Current Input a J1-013
Current Input Return b J1-006
IRIU User Guide Public Information GEH-6804 31
5.7 RTD, PT100 (IEC60751) 3 Wire
The RTD is excited by a resistor-isolated, DC voltage source (Hw /a) and is referenced to a (unit) ground (Hw /f). The excitation resistance consists of two resisters in series Re and Rs; where Rs is a high accuracy shunt resistor which can be used to calculate current when used with the internal voltage monitor (Hw /c). An external loop-back is required to connect (Hw /b) to (Hw /d); loop-back connections should be kept as short as possible.
The interface uses a three-wire sensing methodology. Within the three-wire methodology, inaccuracies caused by the resistance within the lead wire are compensated.
The function also provides the ability to define the range over which the temperature measurement is considered valid, and subsequently, if the temperature goes out of range, a fault status bit is reported using (Di /c). The value of the sensor is reported using (Di /a). The temperature scale is selectable between Celsius, Fahrenheit and Resistance. A software function applies additional filtering to the voltage measurement if required.
Voltage Measurement and Software Filter
Resistance Calculation
Temperature Calculation
Re
Hardware Interfaces Functional Blocks Data Interfaces
Ve
Hw /a: Excitation A
Hw /b: Excitation B
Hw /d: Sensor Voltage
Hw /e: Wire Voltage
Hw /f: Ground
R Wire
R Wire
R Wire
Voltage Measurement and Software Filter
Voltage Measurement and Software Filter
Analogue Comparison
Analogue (F32)
Di /a: Value
Interface BIT
Di /q: Interface Fault
Discrete
Di /c: Out of Range
Discrete
Rs
Hw /c: Excitation Voltage
5.7.1 Specification
Item Specification
Number of channels 2
RTD type PT100 [IEC60751]
A/D converter 16-bit A/D converter
Measurement range -51 to 700°C (-59.8 to 1292 °F)
79.91 to 345.28Ω
Measurement accuracy ±2.70°C (±4.87° F)
±1.05Ω
Reporting resolution 0.1°C (0.1° F)
0.1Ω
Scan time All inputs are sampled every 40 milliseconds
32 GEH-6804 Public Information IRIU User Guide
5.7.2 Configuration
Parameter Description Choices
Temperature
Scale
Selects the measurement type and resolution of the
Value input
Celsius,
Fahrenheit,
Resistance
Upper Limit If the Value is greater than this parameter, the Out of
Range output will be set True (1)
ATTENTION: This value must be greater than the
Lower Limit parameter.
Floating Point, 32-bit scale
defined by the Temperature
Scale parameter
Lower Limit If the Value is less than this parameter, the Out of
Range output will be set True (1)
ATTENTION: This value must be less than the Upper
Limit parameter.
Floating Point, 32-bit scale
defined by the Temperature
Scale parameter
Low Pass Filter Enables a single-pole low-pass recursive software
filter with selected cut off frequency
No Filtering,
0.75Hz,
1.5Hz,
3Hz
5.7.3 Inputs
Input Description Type
Value Measured value of the RTD sensor, which can
be a temperature or resistance depending on
the Temperature Scale parameter
Floating Point, 32-bit scale
defined by the Sensor Type
parameter
Status bits -
Out of Range
Indicates Value is outside the limits set by the
Upper Limit and Lower Limit parameters
Discrete single bit
True (1) = Out of range
False (0) = Inside range
Status bits -
Interface Fault
Indicates the Value is invalid due to an internal
fault
Discrete single bit
True (1) = Fault
False (0) = No Fault
IRIU User Guide Public Information GEH-6804 33
5.7.4 Installation
Each interface has three connections: wire colors follow IEC60751 color coding.
Interface Description Lbl Pin No
608_B01
IEC60751 PT100 Sensor (red) a J2-014
Connect to J2-018 b J2-024
Connect to J2-024 d J2-018
IEC60751 PT100 Sensor (white) e J2-019
IEC60751 PT100 Sensor (white) f J2-008
608_B02
IEC60751 PT100 Sensor (red) a J2-022
Connect to J2-020 b J2-023
Connect to J2-023 d J2-020
IEC60751 PT100 Sensor (white) e J2-021
IEC60751 PT100 Sensor (white) f J2-016
34 GEH-6804 Public Information IRIU User Guide
5.8 Current Output, 0-20mA
This interface drives a controlled current through an external load with resistance inside the specified Load resistance. The output current level is commanded using (Di /a) which is used to drive the output (Hw /a), the low-side of the external load must be connected to (Hw /b), where it is internally returned to ground.
The command is limited from 0 to 20mA should the input command exceed these limits. The command is set to a default value (0mA) until a valid command is applied. The voltage across resistor R1 is measured using (Hw/c) and converted into an equivalent current, which is reported using (Di /b).
The user application should compare Command (Di /a) and Current Feedback (Di /b) in order to detect problems with the interface.
Hardware Interfaces Functional Blocks Data Interfaces
Di /a: CommandCurrent
Output Control
Interface BIT
Load
Analogue (F32)
Hw /a: Current Output
R1
Current Measurement
Di /b: Current Feedback
Analogue (F32)
Range LimitCmd Drive
Di /c: Interface Fault
Discrete
Hw /b: Ground Return
Hw /c: Current Feedback
5.8.1 Specification
Item Specification
Number of channels 2
Load resistance 0 to 550Ω
Output range 0 to 20 mA
Output accuracy ±250 μA
Scan time All outputs are updated every 20 milliseconds
Default output state 0 mA
5.8.2 Configuration
This interface does not require any parameters from the controller.
IRIU User Guide Public Information GEH-6804 35
5.8.3 Inputs
Input Description Type
Value The internally measured value of the Current
output.
Floating Point, 32-bit
in mA
Status bits -
Interface Fault
Indicates the Value is invalid due to an internal
fault.
Discrete single bit
True (1) = Fault
False (0) = No Fault
5.8.4 Outputs
Output Description Type
Command The commanded value of the Current output. Floating Point, 32-bit
in mA
5.8.5 Installation
Interface Description Lbl Pin No
620_D01 Current Output 0-20mA a J4-021
Current Output Return b J4-032
620_D02 Current Output 0-20mA a J4-022
Current Output Return b J4-033
36 GEH-6804 Public Information IRIU User Guide
5.9 Speed Input with Repeater
A differential frequency signal from the speed probe is applied to (Hw /a, /b) and is amplified and conditioned prior to providing a repeater differential output at (Hw /c, /d).
For each of the measurements the frequency is converted to a speed, which is dependent on the number of pulses per shaft revolution and is reported using (Di /a).
The interface provides wire off detection, which is reported using (Di /g), and sets the Speed to 0 rpm.
Frequency Measurement
andConversion
withWire Off
Detection
Analogue (F32)
Di /a: Speed
Hardware Interfaces Functional Blocks Data Interfaces
Hw /a: Speed In +
Interface BIT Discrete
Di /c: Interface Fault
Hw /c: Repeater Out +
Speed Probe
Hw /b: Speed In -
Hw /d: Repeater Out -
RepeaterOutput
Signal Conditioning
andFrequency Repeater
Circuit
Hw /e: Repeater Ground
Discrete
Di /g: Wire Off
5.9.1 Specification
Item Specification
Number of channels 4
Input Frequency Range 2 to 20000Hz
Input Frequency Amplitude 0.028 to 200 V peak to peak
Speed Measurement
Accuracy 0.05% of reading
Speed Reporting Resolution 0.01 rpm
Scan time All inputs are sampled every 10 milliseconds
Repeater Frequency
Amplitude -5 to 5 V
5.9.2 Configuration
Parameter Description Choices
PR Scale Configurable parameter used to convert pulses/sec to
rpm for Speed.
1 to 255
IRIU User Guide Public Information GEH-6804 37
5.9.3 Inputs
Input Description Type
Speed Measured speed of the sensor Floating Point, 32-bit (REAL)
in RPM
Status bits -
Wire Off
Indicates there is an external fault with the
interface.
Not functioning in 2P hardware.
Discrete single bit
True (1) = Fault
False (0) = No Fault
Status bits -
Interface Fault
Indicates there is an internal fault with the
interface.
Discrete single bit
True (1) = Fault
False (0) = No Fault
5.9.4 Installation
Interface Description Lbl Pin No
619_D01
Speed Sensor + a J4-115
Speed Sensor - b J4-122
Speed Repeater + c J4-097
Speed Repeater - d J4-086
Speed Repeater Ground (GND) e J4-098
619_D02
Speed Sensor + a J4-123
Speed Sensor - b J4-124
Speed Repeater + c J4-099
Speed Repeater - d J4-088
Speed Repeater Ground (GND) e J4-087
619_D03
Speed Sensor + a J4-125
Speed Sensor - b J4-126
Speed Repeater + c J4-100
Speed Repeater - d J4-111
Speed Repeater Ground (GND) e J4-110
38 GEH-6804 Public Information IRIU User Guide
Interface Description Lbl Pin No
619_D04
Speed Sensor + a J4-127
Speed Sensor - b J4-128
Speed Repeater + c J4-090
Speed Repeater - d J4-078
Speed Repeater Ground (GND) e J4-089
IRIU User Guide Public Information GEH-6804 39
5.10 Relay Drive with Fuse Monitor
This interface controls a relay and monitors the status of a fuse. The Discrete Output State is commanded using a received Command (Di /a) which is used to switch the output (Hw /a). The command is set to a default state of 'Open' before a command is received.
The intended application of the interface is to provide an output which can drive a relay coil by switching between 5VDC and Ground. The low-side of the relay coil must be connected to (Hw /b), where it is internally returned to ground.
An internal monitor (Hw /c) measures the state of the discrete output and reports this using (Di /b). The user application should compare Command (Di /a) and Relay Status (Di /b) in order to detect problems with the interface.
The interface measures the fuse voltage for the relay (Hw /d) and determines the Fuse Status which is reported using (Di /c). The Field Power voltage is monitored (external to this interface) and no change is reported in (Di /c) if the Field Power is interrupted.
Hw /c: DOP Status
Hardware Interfaces Functional Blocks Data Interfaces
Optical Isolation
Hw /a: Relay Drive
Fault Logic
Di /a: Command
Discrete
Voltage Measurement
Interface BIT
Di /e: Interface Fault
Discrete
24V Field Power
Discrete Output
Internal Monitor
Fuse
Relay
Hw /d: Fuse Voltage
Di /b: Relay Status
Discrete
Hw /b: Relay Drive Ground
Di /c: Fuse Status
Discrete
Field Power Monitor
Performed Outside Interface
Field Power Return
Solenoid
5.10.1 Specification
Item Specification
Number of channels 19
External coil resistance 270 to 450Ω
Continuous output current 10 mA
Scan time All outputs are updated every 20 milliseconds
Default output state Open
40 GEH-6804 Public Information IRIU User Guide
5.10.2 Configuration
This interface does not require any parameters from the controller.
5.10.3 Inputs
Input Description Type
Status bits -
Relay Status
Indicates the internally monitored state of the
Relay Drive Output.
Discrete single bit
True (1) = Closed
False (0) = Open
Status bits -
Fuse Status
Indicates if state of the externally monitored
fuse
Discrete single bit
True (1) = Fault
False (0) = No Fault
Status bits -
Interface Fault
Indicates there is an internal fault with the
interface.
Discrete single bit
True (1) = Fault
False (0) = No Fault
5.10.4 Outputs
Output Description Type
Command The commanded state of the Relay Drive
Output.
Discrete single bit
True (1) = Closed
False (0) = Open
5.10.5 Installation
Interface Description Lbl Pin No
607_E01
Relay Drive Signal a J5-082
Relay Drive Return (GND) b J5-071
Fuse Voltage d J5-028
607_E02
Relay Drive Signal a J5-093
Relay Drive Return (GND) b J5-081
Fuse Voltage d J5-029
IRIU User Guide Public Information GEH-6804 41
Interface Description Lbl Pin No
607_E03
Relay Drive Signal a J5-094
Relay Drive Return (GND) b J5-083
Fuse Voltage d J5-030
607_E04
Relay Drive Signal a J5-095
Relay Drive Return (GND) b J5-072
Fuse Voltage d J5-031
607_E05
Relay Drive Signal a J5-103
Relay Drive Return (GND) b J5-091
Fuse Voltage d J5-032
607_E06
Relay Drive Signal a J5-104
Relay Drive Return (GND) b J5-092
Fuse Voltage d J5-036
607_E07
Relay Drive Signal a J5-105
Relay Drive Return (GND) b J5-084
Fuse Voltage d J5-037
607_E08
Relay Drive Signal a J5-106
Relay Drive Return (GND) b J5-085
Fuse Voltage d J5-038
607_E09
Relay Drive Signal a J5-113
Relay Drive Return (GND) b J5-090
Fuse Voltage d J5-039
607_E10
Relay Drive Signal a J5-114
Relay Drive Return (GND) b J5-102
Fuse Voltage d J5-040
607_E11
Relay Drive Signal a J5-115
Relay Drive Return (GND) b J5-096
Fuse Voltage d J5-041
42 GEH-6804 Public Information IRIU User Guide
Interface Description Lbl Pin No
607_E12
Relay Drive Signal a J5-116
Relay Drive Return (GND) b J5-086
Fuse Voltage d J5-042
607_E13
Relay Drive Signal a J5-117
Relay Drive Return (GND) b J5-098
Fuse Voltage d J5-043
607_E14
Relay Drive Signal a J5-118
Relay Drive Return (GND) b J5-087
Fuse Voltage d J5-044
607_E15
Relay Drive Signal a J5-119
Relay Drive Return (GND) b J5-099
Fuse Voltage d J5-045
607_E16
Relay Drive Signal a J5-120
Relay Drive Return (GND) b J5-100
Fuse Voltage d J5-046
607_E17
Relay Drive Signal a J5-121
Relay Drive Return (GND) b J5-101
Fuse Voltage d J5-047
607_E18
Relay Drive Signal a J5-122
Relay Drive Return (GND) b J5-107
Fuse Voltage d J5-048
607_E19
Relay Drive Signal a J5-123
Relay Drive Return (GND) b J5-097
Fuse Voltage d J5-049
IRIU User Guide Public Information GEH-6804 43
5.11 Contact Inputs, Isolated
This sensor interface detects the state of a contact input.
An Excitation voltage (Hw /b) is provided through resistor (Re) which utilises the externally supplied Field Power which is nominally 24V. A pull-down resistor (Rs) within the unit enables the state of an 'Open' switch to be reliably determined.
This interface measures DC single ended voltage (Hw /a) and then applies thresholds to determine the Logic status which is reported by (Di /a).
The Field Power voltage is monitored (external to this interface) and no change is reported in if the Field Power is interrupted.
Hardware Interfaces Functional Blocks Data Interfaces
Optical IsolationHw /a: Signal
Analogue to Discrete
Di /a: Status
Discrete
Voltage Measurement
Interface BIT
Di /e: Interface Fault
DiscreteRs
Field Power Monitor
Re
Field Return
Field Supply
Hw /b: Excitation
Performed Outside Interface
5.11.1 Specification
Item Specification
Number of channels 6
Scan time All outputs are updated every 20 milliseconds
5.11.2 Configuration
This interface does not require any parameters from the controller.
44 GEH-6804 Public Information IRIU User Guide
5.11.3 Inputs
Input Description Type
Status bits -
Status Indicates the status of the Contact Input
Discrete single bit
True (1) = Closed
False (0) = Open
Status bits -
Interface Fault
Indicates the Status is invalid due to an
internal fault.
Discrete single bit
True (1) = Fault
False (0) = No Fault
5.11.4 Installation
Interface Description Lbl Pin No
610_E01 Signal a J5-057
Excitation b J5-034
610_E02 Signal a J5-056
Excitation b J5-033
610_E03 Signal a J5-055
Excitation b J5-027
610_E04 Signal a J5-054
Excitation b J5-026
610_E05 Signal a J5-053
Excitation b J5-025
610_E06 Signal a J5-052
Excitation b J5-024
IRIU User Guide Public Information GEH-6804 45
5.12 Woodward GS6 Valve
This interface defines an implementation of a CANopen data bus and master controller specifically configured to interface with up to two Woodward TM GS6 gas metering systems.
An internal termination resistor is provided for termination of one end of the bus (Hw /d, /e).
This interface is responsible for:
• Initializing the internal CAN sub-system to drive a single CAN channel as a master node, at a configurable Baud rate.
• Performing bus critical operations during start-up. Broadcast transmission of the Reset Node message to all nodes to prepare the CAN slave nodes for the provision of data to the CAN master, in normal operations.
• Receiving and reporting data from the Woodward GS6 gas metering systems.
• Providing indication of PDO freshness which should be used by the user application to determine the health of the interface.
Configuration is accomplished using the Woodward configuration tool. Refer to the Woodward Installation and Operation Manual for the GS6 Gas Metering System (Manual 26513).
5.12.1 Specification
Item Specification
Number of channels Up to 2 devices on the same bus.
Scan time All inputs are updated every 1280 milliseconds
Default output state All communications stopped.
46 GEH-6804 Public Information IRIU User Guide
5.12.2 Configuration
Parameter Description Choices
Bus Speed
Configurable speed of the CAN bus.
ATTENTION: value must match the Baud
Rate of the devices. All devices must be
configured to the same Baud Rate.
500kbps
250kbps
125kbps
Device Node ID [01] Node ID for Device 01
Valid Node IDs are 1-31.
Unused Devices should be set
to Node ID 0
Device Node ID [02] Node ID for Device 02
Valid Node IDs are 1-31.
Unused Devices should be set
to Node ID 0
5.12.3 Inputs
Input Description Type
PDO1 Count Incremented each time a PDO1 (Actual
Position and Status from Valve) message is
received. Counter wraps around once
maximum value is reached.
Unsigned, 8-bit integer
Position Feedback [Manual 26513] - Position Feedback Unsigned, 16-bit integer
Status bits –
Alarm
[Manual 26513] - Alarm Discrete single bit
Status bits –Shutdown System [Manual 26513] – Shutdown System Discrete single bit
Status bits –Shutdown Position [Manual 26513] – Shutdown Position Discrete single bit
Status bits –Shutdown [Manual 26513] – Shutdown Discrete single bit
Status bits –
Manual Resolver Test In Progress
[Manual 26513] –
ManualResolverTestInprogress
Discrete single bit
PDO2 Count Incremented each time a PDO2 (Input
Voltage and Electronics Temperature)
message is received. Counter wraps around
once maximum value is reached.
Unsigned, 8-bit integer
Input Voltage [Manual 26513] - Input Voltage Floating Point, 32-bit (REAL)
Electronics Temperature [Manual 26513] - Electronics Temperature Floating Point, 32-bit (REAL)
PDO3 Count Incremented each time a PDO3 (Efficiency
and Analog Position In) message is received.
Counter wraps around once maximum value
is reached.
Unsigned, 8-bit integer
Efficiency [Manual 26513] - Efficiency Floating Point, 32-bit (REAL)
IRIU User Guide Public Information GEH-6804 47
Input Description Type
Analog Input [Manual 26513] - Analog Input Floating Point, 32-bit
PDO4 Count Incremented each time a PDO4 (Actual
current and Actual Current Filtered) message
is received. Counter wraps around once
maximum value is reached.
Unsigned, 8-bit integer
Current Feedback [Manual 26513] - Current Feedback Floating Point, 32-bit (REAL)
Current Feedback Filtered [Manual 26513] - Current Feedback Filtered Floating Point, 32-bit (REAL)
PDO5 Count Incremented each time a PDO5 (Actual
Position 1 and Actual Position 2) message is
received. Counter wraps around once
maximum value is reached.
Unsigned, 8-bit integer
Actual Position 1 [Manual 26513] - Actual Position 1 Floating Point, 32-bit (REAL)
Actual Position 2 [Manual 26513] - Actual Position 2 Floating Point, 32-bit (REAL)
PDO6 Count Incremented each time a PDO6 (Error Status
Bits) message is received. Counter wraps
around once maximum value is reached.
Unsigned, 8-bit integer
Diagnostic Word 1 -
MainEepromWriteFail
[Manual 26513] - MainEepromWriteFail Discrete single bit
Diagnostic Word 1 -
MainEepromReadFail
[Manual 26513] - MainEepromReadFail Discrete single bit
Diagnostic Word 1 -
ParameterErr
[Manual 26513] - ParameterErr Discrete single bit
Diagnostic Word 1 -
ParameterVersionErr
[Manual 26513] - ParameterVersionErr Discrete single bit
Diagnostic Word 1 -
Adc5VoltErr
[Manual 26513] - Adc5VoltErr Discrete single bit
Diagnostic Word 1 -
AdcRefErr
[Manual 26513] - AdcRefErr Discrete single bit
Diagnostic Word 1 -
Plus15VoltErr
[Manual 26513] - Plus15VoltErr Discrete single bit
Diagnostic Word 1 -
Min15VoltErr
[Manual 26513] - Min15VoltErr Discrete single bit
Diagnostic Word 1 -
AdcErr
[Manual 26513] - AdcErr Discrete single bit
Diagnostic Word 1 -
SpiAdcErr
[Manual 26513] - SpiAdcErr Discrete single bit
Diagnostic Word 1 -
FactoryCalibrationErr
[Manual 26513] - FactoryCalibrationErr Discrete single bit
Diagnostic Word 2 -
StartupPositionSensorErr
[Manual 26513] - StartupPositionSensorErr Discrete single bit
48 GEH-6804 Public Information IRIU User Guide
Input Description Type
Diagnostic Word 2 -
PositionSensorErr
[Manual 26513] - PositionSensorErr Discrete single bit
Diagnostic Word 2 -
PositionErr
[Manual 26513] - PositionErr Discrete single bit
Diagnostic Word 2 -
CurrentControlErr
[Manual 26513] - CurrentControlErr Discrete single bit
Diagnostic Word 2 -
DigitalNotAllSlowDataReceived
[Manual 26513] -
DigitalNotAllSlowDataReceived
Discrete single bit
Diagnostic Word 2 -
AnalogInputHighErr
[Manual 26513] - AnalogInputHighErr Discrete single bit
Diagnostic Word 2 -
AnalogInputLowErr
[Manual 26513] - AnalogInputLowErr Discrete single bit
Diagnostic Word 2 -
PowerupReset
[Manual 26513] - PowerupReset Discrete single bit
Diagnostic Word 2 -
WatchdogReset
[Manual 26513] - WatchdogReset Discrete single bit
Diagnostic Word 2 -
ShutdownInputActive
[Manual 26513] - ShutdownInputActive Discrete single bit
Diagnostic Word 2 -
DigitalComErr
[Manual 26513] - DigitalComErr Discrete single bit
Diagnostic Word 2 -
DigitalAnalogTrackingErr
[Manual 26513] - DigitalAnalogTrackingErr Discrete single bit
Diagnostic Word 2 -
InputVoltageLowErr
[Manual 26513] - InputVoltageLowErr Discrete single bit
Diagnostic Word 2 -
InputVoltageHighErr
[Manual 26513] - InputVoltageHighErr Discrete single bit
Diagnostic Word 2 -
PositionSensor2Err
[Manual 26513] - PositionSensor2Err Discrete single bit
Diagnostic Word 3 -
DualResolverDiff1Err (ALM)
[Manual 26513] - DualResolverDiff1Err
(ALM)
Discrete single bit
Diagnostic Word 3 -
StartupPositionSensor2Err (ALM)
[Manual 26513] - StartupPositionSensor2Err
(ALM)
Discrete single bit
Diagnostic Word 3 -
DualResolverDiff2Err (SD)
[Manual 26513] - DualResolverDiff2Err (SD) Discrete single bit
IRIU User Guide Public Information GEH-6804 49
5.12.4 Outputs
Input Description Type
Position Demand [Manual 26513] - Position Demand Unsigned, 16-bit integer
Command bits -
Shutdown
[Manual 26513] - Shutdown Discrete single bit
Command bits -
Reset diagnostic bits
[Manual 26513] - Reset diagnostic bits Discrete single bit
Command bits -
Resolver check enabled
[Manual 26513] - Resolver check enabled Discrete single bit
Command bits -
AnalogPrimaryDemand
[Manual 26513] - AnalogPrimaryDemand Discrete single bit
Command bits -
UseAnalogBackup
[Manual 26513] - UseAnalogBackup Discrete single bit
TrackingMaxDiff [Manual 26513] - TrackingMaxDiff Floating Point, 32-bit (REAL)
TrackingTime [Manual 26513] - TrackingTime Unsigned, 16-bit integer
DualResolverDiffErrMode [Manual 26513] - DualResolverDiffErrMode Unsigned, 16-bit integer
DualResolverMaxDiff1 [Manual 26513] - DualResolverMaxDiff1 Floating Point, 32-bit (REAL)
DualResolverMaxDiff2 [Manual 26513] - DualResolverMaxDiff2 Floating Point, 32-bit (REAL)
5.12.5 Installation
Interface Description Lbl Pin No
631_D01
Hi a J4-103
Lo b J4-104
CAN Ground c J4-079
Connect to J4-093 d J4-092
Connect to J4-092 e J4-093
50 GEH-6804 Public Information IRIU User Guide
5.13 GE Sensing DPS 8000 Pressure Transducer
This interface defines an implementation of a CANopen data bus and master controller specifically configured to interface with up to eight GE Sensing DPS 8000 pressure transducers.
An internal termination resistor is provided for termination of one end of the bus (Hw /d, /e).
This interface is responsible for:
• Initializing the internal CAN sub-system to drive a single CAN channel as a master node, at a configurable Baud rate.
• Performing bus critical operations during start-up. Broadcast transmission of the Reset Node message to all nodes to prepare the CAN slave nodes for the provision of data to the CAN master, in normal operations.
• Receiving and reporting data from the GE Sensing DPS 8000 pressure transducers.
• Providing indication of PDO freshness which should be used by the user application to determine the health of the interface.
The configuration of the DPS device needs to be set by a GE Sensing approved CANopen configuration tool prior to being installed on the CANopen bus.
The DPS sensors are not intended to be individually powered down and hot-swapping with power on is not supported.
Removing power from any single DPS sensor may have adverse effects on measurements from other sensors on the same network. When performing maintenance on any DPS sensor, always remove power from all sensors on the CANbus for at least four seconds. Perform offline maintenance using the precautions listed in the DPS User Manual and then restore power to all DPS sensors.
5.13.1 Specification
Item Specification
Number of channels Up to 8 devices on the same bus.
Scan time All inputs are updated every 1280 milliseconds
Default output state All communications stopped.
IRIU User Guide Public Information GEH-6804 51
5.13.2 Configuration
Parameter Description Choices
Bus Speed
Configurable speed of the CAN bus.
ATTENTION: value must match the Baud
Rate of the devices. All devices must be
configured to the same Baud Rate.
1000 kbps
500kbps
250kbp
125kbps
50 kbps
20kbps
Device Node ID [01] Node ID for Device 01 Valid Node IDs are 1-127. Unused
Devices should be set to Node ID 0
Device Node ID [02] Node ID for Device 02 Valid Node IDs are 1-127. Unused
Devices should be set to Node ID 0
Device Node ID [03] Node ID for Device 03 Valid Node IDs are 1-127. Unused
Devices should be set to Node ID 0
Device Node ID [04] Node ID for Device 04 Valid Node IDs are 1-127. Unused
Devices should be set to Node ID 0
Device Node ID [05] Node ID for Device 05 Valid Node IDs are 1-127. Unused
Devices should be set to Node ID 0
Device Node ID [06] Node ID for Device 06 Valid Node IDs are 1-127. Unused
Devices should be set to Node ID 0
Device Node ID [07] Node ID for Device 07 Valid Node IDs are 1-127. Unused
Devices should be set to Node ID 0
Device Node ID [08] Node ID for Device 08 Valid Node IDs are 1-127. Unused
Devices should be set to Node ID 0
5.13.3 Inputs
Input Description Type
PDO1 Count
Incremented each time a message is received.
Counter wraps around once maximum value is
reached.
Unsigned 8-bit integer
Pressure Pressure measurement Floating Point, 32-bit
in PSI
Acquisition Time Elapsed Time since device was powered on Unsigned 32-bit integer (UINT32)
in milliseconds
52 GEH-6804 Public Information IRIU User Guide
5.13.4 Installation
Interface Description Lbl Pin No
647_D02
CAN Hi a J4-113
CAN Lo b J4-114
CAN Ground c J4-091
Connect to J4-121 d J4-102
Connect to J4-102 e J4-121
5.14 Dynamic Pressure, PCB Piezotronics, Dual Sensor
This is an interface to two PCB Piezotronics Differential Charge Amplifiers which are connected to differential output charge sensors.
The interface performs the following functionality for each channel:
• Hardware Conditioning: Hardware elements which condition and filter the input signal which includes bias removal.
• Wire Off Detection: Detects a sensor wire off condition (Hw /e, /f) and reports using (Di /n, /m).
• Voltage Measurement and Software Filter: Samples the signal (Hw /a, /c) and (Hw /b, /d), applies software anti-alias filtering and selectable software filtering and stores each in a buffer of depth.
• RMS: Calculates the root mean square (RMS) voltage of the time-domain sampled and filtered signal over a number of samples.
• RMS Scan Average: Calculates an average RMS using a configurable number of root mean square (RMS) voltage calculations. Calculates the pressure by scaling the average RMS using configurable parameters and outputs using (Di /a, /d).
• Windowed Fast Fourier Transform: Calculates the frequency domain peak-to-peak magnitude and bin frequency, based on time-domain sampled and filtered signal. The Fast Fourier Transform has a Bin Quantity and Range.
• Bin Exclude Control: Eliminates the frequency peak for the specified bins (Di /p(x)). Applies to both channels.
• Peak to Peak Scan Average per Bin: Provides a frequency domain peak-to-peak magnitude average per frequency bin, over a configurable number of Scans.
• Band Sort: Average frequency domain peak-to-peak data is sorted into separate frequency bands. The bands are configurable.
• Maximum Peak to Peak Average in each Band: The maximum of the average peak-to-peak magnitudes from each frequency band and its corresponding frequency bin are calculated and output using (Di /b(n)) & (Di /c(n)) and (Di /e(n)) and (Di /f(n)).
IRIU User Guide Public Information GEH-6804 53
The interface performs the following functionality on the data calculated for both channels:
• Peak to Peak Average in each Band: Calculates the average peak to peak magnitude overboth channels for each band and outputs using (Di /g(n))
• Maximum Peak to Peak Average in each Band: Calculates the maximum peak to peakmagnitude over both channels for each band and outputs using (Di /j(n)) along with the channelon which it occurred (Di /h(n)) and the Frequency Bin (Di /i(n)).
• Range check each Band: The maximum peak to peak magnitude over both channels for eachband is compared to a configurable maximum threshold. The status is indicated using (Di /k(n))
Hardware Interfaces Functional Blocks Data Interfaces
Voltage Measurement & Software Filter
RMSRMS Scan Average & Output Scaling
Di /a: Pressure Ch1
Analogue (F32)
Windowed Fast Fourier
Transform
Peak to Peak Scan Average
per Bin
Maximum Peak to Peak Average
in each Band
Di /b(n): Max Avg PTP Ch1 B(n)
Analogue (F32)
Peak to Peak Average in each
Band
Di /g(n): Avg PTP B(n)
Analogue (F32)
Di /c(n): Max Avg PTP Ch1 B(n) Freq
Analogue (U16)
Range Check each Band
Maximum Peak to Peak Average
in each Band
Voltage Measurement & Software Filter
RMSRMS Scan Average & Output Scaling
Di /d: Pressure Ch2
Analogue (F32)
Windowed Fast Fourier
Transform
Peak to Peak Scan Average
per Bin
Maximum Peak to Peak Average
in each Band
Di /e(n): Max Avg PTP Ch2 B(n)
Analogue (F32)
Di /f(n): Max Avg PTP Ch2 B(n) Freq
Analogue (U16)
NOTE: For Data Interfaces (n) is 1 to 6
Di /j(n): Max Avg PTP B(n)
Analogue (F32)
Di /i(n): Max Avg PTP B(n) Freq
Analogue (U16)
Di /h(n): Max Avg PTP B(n) Channel
Analogue (U16)
Di /k(n): Limit Exceeded B(n)
Discrete
Ch
ann
el 1
Ch
ann
el 2
Both
Ch
ann
els
Band Sort
Band Sort
Interface BIT
Di /l: Interface Fault
Discrete
Hw /a: Signal 1
Hw /c: Signal 1 Return
Differential Charge Amplifier
Hw /b: Signal 2
Hw /d: Signal 2 Return
Differential Charge Amplifier
Hardware Conditioning
Hardware Conditioning
Di /m: Wire Off Ch1
DiscreteWire Off
Detection
Wire Off Detection
Di /n: Wire Off Ch2
Discrete
Bin Exclude Control
Di /p(x): Frequency Exclude (y)
Analogue (U16)
NOTE: For Data Interfaces
- (x) is 1 to 9
- (y) is A to I
Di /s: Applied Gain
Analogue (F32)
Hw /e: Monitor 1
Hw /f: Monitor 2
The Applied Gain is common to both Channel 1 and
Channel 2 but is only shown from Channel 2 for simplicity.
54 GEH-6804 Public Information IRIU User Guide
5.14.1 Specification
Item Specification
Number of channels 2
Supported charge amplifier PCB Piezotronics Charge Amplifier
Excitation voltage 22 to 28 V
Constant current excitation 3.1 to 4.1 mA
Sample rate 10240 Hz
Frequency bin quantity 2048
Frequency bin range 2.5 Hz
Scan time All inputs are updated every 80 milliseconds
5.14.2 Configuration
Parameter Description Choices
Probe Sensitivity Pressure sensor probe sensitivity Floating Point, 32-bit (REAL)
Amplifier Sensitivity Charge Amplifier sensitivity Floating Point, 32-bit (REAL)
Band 1 Limit (psi) If the Maximum Peak-Peak Amplitude within Band 1
is greater than this parameter, the Limit Exceeded
output will be set True (1).
Floating Point, 32-bit (REAL)
Band 2 Limit (psi) If the Maximum Peak-Peak Amplitude within Band 2
is greater than this parameter, the Limit Exceeded
output will be set True (1).
Floating Point, 32-bit (REAL)
Band 3 Limit (psi) If the Maximum Peak-Peak Amplitude within Band 3
is greater than this parameter, the Limit Exceeded
output will be set True (1).
Floating Point, 32-bit (REAL)
Band 4 Limit (psi) If the Maximum Peak-Peak Amplitude within Band 4
is greater than this parameter, the Limit Exceeded
output will be set True (1).
Floating Point, 32-bit (REAL)
Band 5 Limit (psi) If the Maximum Peak-Peak Amplitude within Band 5
is greater than this parameter, the Limit Exceeded
output will be set True (1).
Floating Point, 32-bit (REAL)
Band 6 Limit (psi) If the Maximum Peak-Peak Amplitude within Band 6
is greater than this parameter, the Limit Exceeded
output will be set True (1).
Floating Point, 32-bit (REAL)
IRIU User Guide Public Information GEH-6804 55
Parameter Description Choices
Gain The Gain applied to the input before measurement.
ATTENTION: If not set to AUTO, care should be
taken to avoid saturating the input circuitry.
1/16
1/8
1/4
1/2
1
2
4
8
Auto
RMS Length The number of the most recent ADC samples to be
included in an RMS scan.
Fixed at 4096
RMS Average
Length
Defines the number of the most recent RMS scans
to be included in the RMS calculation
Unsigned, 16-bit integer
1 to 32
FFT Average
Length
Defines the number of scans to average the FFT
magnitude over.
Unsigned, 16-bit integer
1 to 100
Low Start Configurable Frequency Band 1 Lower limit (Hz)
ATTENTION: This value must be lower than the
Low to Middle Break parameter.
Unsigned, 16-bit integer
Low to Middle
Break
Configurable Frequency Band 1 Upper limit (Hz)
and Band 2 Lower Limit (Hz)
ATTENTION: This value must be greater than the
Low Start parameter and less than the Middle to
High Break parameter.
Unsigned, 16-bit integer
Middle to High
Break
Configurable Frequency Band 2 Upper limit (Hz)
and Band 3 Lower Limit (Hz)
ATTENTION: This value must be greater than the
Low Start parameter and less than the High to
Screech Break parameter.
Unsigned, 16-bit integer
High to Screech
Break
Configurable Frequency Band 3 Upper limit (Hz)
and Band 6 Lower Limit (Hz)
ATTENTION: This value must be less than the
Screech End parameter and less than the
Transverse End parameter.
Unsigned, 16-bit integer
Low-Low Start Configurable Frequency Band 4 Lower limit (Hz)
ATTENTION: This value must be less than the low-
Low End parameter.
Unsigned, 16-bit integer
Low-Low End Configurable Frequency Band 4 Upper limit (Hz)
ATTENTION: This value must be greater than the
Low-Low Start parameter.
Unsigned, 16-bit integer
Transverse Start Configurable Frequency Band 5 Lower limit (Hz)
ATTENTION: This value must be less than the
Transverse End parameter.
Unsigned, 16-bit integer
56 GEH-6804 Public Information IRIU User Guide
Parameter Description Choices
Transverse End Configurable Frequency Band 5 Upper limit (Hz)
ATTENTION: This value must be greater than the
Transverse Start parameter.
Unsigned, 16-bit integer
Screech End Configurable Frequency Band 6 Upper limit (Hz)
ATTENTION: This value must be greater than the
Transverse Start parameter.
Unsigned, 16-bit integer
Software Filter Configurable Software Filter before FFT calculations No Filtering,
150Hz High Pass,
150-450Hz Band Pass
10Hz High Pass
Maximum Expected
Pressure
The maximum expected pressure, which is used
when the Gain is set to Auto
Unsigned, 16-bit integer
5.14.3 Inputs
Input Description Type
Repeated for each Channel
Pressure Measured RMS value of Pressure Floating Point, 32-bit in PSI
Status bits –
Wire Off
Indicates the data is invalid due to an external
fault.
Discrete single bit
True (1) = Data is Invalid
False (0) = Data is Valid
Status bits –
Interface Fault
Indicates the data is invalid due to an internal
fault.
Discrete single bit
True (1) = Fault
False (0) = No Fault
Band 1 (Low) -
Peak Amplitude (PSI pk-pk)
Maximum peak-to-peak amplitude measured in
Band 1
Floating Point, 32-bit in PSI
Band 2 (Mid) -
Peak Amplitude (PSI pk-pk)
Maximum peak-to-peak amplitude measured in
Band 2
Floating Point, 32-bit in PSI
Band 3 (High) -
Peak Amplitude (PSI pk-pk)
Maximum peak-to-peak amplitude measured in
Band 3
Floating Point, 32-bit in PSI
Band 4 (LowLow) -
Peak Amplitude (PSI pk-pk)
Maximum peak-to-peak amplitude measured in
Band 4
Floating Point, 32-bit in PSI
Band 5 (Transverse) -
Peak Amplitude (PSI pk-pk)
Maximum peak-to-peak amplitude measured in
Band 5
Floating Point, 32-bit in PSI
Band 6 (Screech) -
Peak Amplitude (PSI pk-pk)
Maximum peak-to-peak amplitude measured in
Band 6
Floating Point, 32-bit in PSI
Band 1 (Low) - Frequency (Hz)
at Peak Amplitude
Frequency within Band 1 at which the maximum
peak-to-peak amplitude was measured.
Unsigned 16-bit integer in
Hz
IRIU User Guide Public Information GEH-6804 57
Input Description Type
Band 2 (Mid) - Frequency (Hz)
at Peak Amplitude
Frequency within Band 2 at which the maximum
peak-to-peak amplitude was measured.
Unsigned 16-bit integer in
Hz
Band 3 (High) - Frequency
(Hz) at Peak Amplitude
Frequency within Band 3 at which the maximum
peak-to-peak amplitude was measured.
Unsigned 16-bit integer in
Hz
Band 4 (LowLow) - Frequency
(Hz) at Peak Amplitude
Frequency within Band 4 at which the maximum
peak-to-peak amplitude was measured.
Unsigned 16-bit integer in
Hz
Band 5 (Transverse) -
Frequency (Hz) at Peak
Amplitude
Frequency within Band 5 at which the maximum
peak-to-peak amplitude was measured.
Unsigned 16-bit integer in
Hz
Band 6 (Screech) - Frequency
(Hz) at Peak Amplitude
Frequency within Band 6 at which the maximum
peak-to-peak amplitude was measured.
Unsigned 16-bit integer in
Hz
Combination of both Channels
Band 1 (Low) -
Average Amplitude (PSI pk-pk)
Average of the Maximum peak-to-peak
amplitude measured on both Channels within
Band 1
Floating Point, 32-bit in PSI
Band 2 (Mid) -
Average Amplitude (PSI pk-pk)
Average of the Maximum peak-to-peak
amplitude measured on both Channels within
Band 2
Floating Point, 32-bit in PSI
Band 3 (High) -
Average Amplitude (PSI pk-pk)
Average of the Maximum peak-to-peak
amplitude measured on both Channels within
Band 3
Floating Point, 32-bit in PSI
Band 4 (LowLow) -
Average Amplitude (PSI pk-pk)
Average of the Maximum peak-to-peak
amplitude measured on both Channels within
Band 4
Floating Point, 32-bit in PSI
Band 5 (Transverse) -
Average Amplitude (PSI pk-pk)
Average of the Maximum peak-to-peak
amplitude measured on both Channels within
Band 5
Floating Point, 32-bit in PSI
Band 6 (Screech) -
Average Amplitude (PSI pk-pk)
Average of the Maximum peak-to-peak
amplitude measured on both Channels within
Band 6
Floating Point, 32-bit in PSI
Band 1 (Low) -
Peak Amplitude (PSI pk-pk)
Maximum peak-to-peak amplitude measured on
both Channels in Band 1
Floating Point, 32-bit in PSI
Band 2 (Mid) -
Peak Amplitude (PSI pk-pk)
Maximum peak-to-peak amplitude measured on
both Channels in Band 2
Floating Point, 32-bit in PSI
Band 3 (High) -
Peak Amplitude (PSI pk-pk)
Maximum peak-to-peak amplitude measured on
both Channels in Band 3
Floating Point, 32-bit in PSI
Band 4 (LowLow) -
Peak Amplitude (PSI pk-pk)
Maximum peak-to-peak amplitude measured on
both Channels in Band 4
Floating Point, 32-bit in PSI
Band 5 (Transverse) -
Peak Amplitude (PSI pk-pk)
Maximum peak-to-peak amplitude measured on
both Channels in Band 5
Floating Point, 32-bit in PSI
Band 6 (Screech) -
Peak Amplitude (PSI pk-pk)
Maximum peak-to-peak amplitude measured on
both Channels in Band 6
Floating Point, 32-bit in PSI
58 GEH-6804 Public Information IRIU User Guide
Input Description Type
Band 1 (Low) - Frequency (Hz)
at Peak Amplitude
Frequency within Band 1 at which the maximum
peak-to-peak amplitude (across both channels)
was measured.
Unsigned 16-bit integer in
Hz
Band 2 (Mid) - Frequency (Hz)
at Peak Amplitude
Frequency within Band 2 at which the maximum
peak-to-peak amplitude (across both channels)
was measured.
Unsigned 16-bit integer in
Hz
Band 3 (High) - Frequency
(Hz) at Peak Amplitude
Frequency within Band 3 at which the maximum
peak-to-peak amplitude (across both channels)
was measured.
Unsigned 16-bit integer in
Hz
Band 4 (LowLow) - Frequency
(Hz) at Peak Amplitude
Frequency within Band 4 at which the maximum
peak-to-peak amplitude (across both channels)
was measured.
Unsigned 16-bit integer in
Hz
Band 5 (Transverse) -
Frequency (Hz) at Peak
Amplitude
Frequency within Band 5 at which the maximum
peak-to-peak amplitude (across both channels)
was measured.
Unsigned 16-bit integer in
Hz
Band 6 (Screech) - Frequency
(Hz) at Peak Amplitude
Frequency within Band 6 at which the maximum
peak-to-peak amplitude (across both channels)
was measured.
Unsigned 16-bit integer in
Hz
Band 1 (Low) - Channel with
Peak Amplitude
Channel on which maximum peak-to-peak
amplitude was measured within Band 1
Unsigned 16-bit integer
Band 2 (Mid) - Channel with
Peak Amplitude
Channel on which maximum peak-to-peak
amplitude was measured within Band 2
Unsigned 16-bit integer
Band 3 (High) - Channel with
Peak Amplitude
Channel on which maximum peak-to-peak
amplitude was measured within Band 3
Unsigned 16-bit integer
Band 4 (LowLow) - Channel
with Peak Amplitude
Channel on which maximum peak-to-peak
amplitude was measured within Band 4
Unsigned 16-bit integer
Band 5 (Transverse) - Channel
with Peak Amplitude
Channel on which maximum peak-to-peak
amplitude was measured within Band 5
Unsigned 16-bit integer
Band 6 (Screech) - Channel
with Peak Amplitude
Channel on which maximum peak-to-peak
amplitude was measured within Band 6
Unsigned 16-bit integer
Limit Exceeded -
Band 1 (Low)
Maximum peak-to-peak amplitude measured in
Band 1 is greater than the configured limit
Discrete single bit
True (1) = Exceeded
False (0) = Not Exceeded
Limit Exceeded -
Band 2 (Mid)
Maximum peak-to-peak amplitude measured in
Band 2 is greater than the configured limit
Discrete single bit
True (1) = Exceeded
False (0) = Not Exceeded
Limit Exceeded -
Band 3 (High)
Maximum peak-to-peak amplitude measured in
Band 3 is greater than the configured limit
Discrete single bit
True (1) = Exceeded
False (0) = Not Exceeded
Limit Exceeded -
Band 4 (LowLow)
Maximum peak-to-peak amplitude measured in
Band 4 is greater than the configured limit
Discrete single bit
True (1) = Exceeded
False (0) = Not Exceeded
IRIU User Guide Public Information GEH-6804 59
Input Description Type
Limit Exceeded -
Band 5 (Transverse)
Maximum peak-to-peak amplitude measured in
Band 5 is greater than the configured limit
Discrete single bit
True (1) = Exceeded
False (0) = Not Exceeded
Limit Exceeded -
Band 6 (Screech)
Maximum peak-to-peak amplitude measured in
Band 6 is greater than the configured limit
Discrete single bit
True (1) = Exceeded
False (0) = Not Exceeded
5.14.4 Outputs
Input Description Type
Frequency Band
Exclude A
The magnitude of the FFT bin closest to the
specified frequency is permanently set to zero.
Unsigned,16-bit integer
in Hz
Frequency Band
Exclude B
The magnitude of the FFT bin closest to the
specified frequency is permanently set to zero.
Unsigned,16-bit integer
in Hz
Frequency Band
Exclude C
The magnitude of the FFT bin closest to the
specified frequency is permanently set to zero.
Unsigned,16-bit integer
in Hz
Frequency Band
Exclude D
The magnitude of the FFT bin closest to the
specified frequency is permanently set to zero.
Unsigned,16-bit integer
in Hz
Frequency Band
Exclude E
The magnitude of the FFT bin closest to the
specified frequency is permanently set to zero.
Unsigned,16-bit integer
in Hz
Frequency Band
Exclude F
The magnitude of the FFT bin closest to the
specified frequency is permanently set to zero.
Unsigned,16-bit integer
in Hz
Frequency Band
Exclude G
The magnitude of the FFT bin closest to the
specified frequency is permanently set to zero.
Unsigned,16-bit integer
in Hz
Frequency Band
Exclude H
The magnitude of the FFT bin closest to the
specified frequency is permanently set to zero.
Unsigned,16-bit integer
in Hz
Frequency Band
Exclude I
The magnitude of the FFT bin closest to the
specified frequency is permanently set to zero.
Unsigned,16-bit integer
in Hz
60 GEH-6804 Public Information IRIU User Guide
5.14.5 Installation
Interface Description Lbl Pin No
627_D01
Signal 1 a J4-082
Signal 1 Return d J4-083
Signal 1 Shield (GND) e J4-084
Signal 2 c J4-094
Signal 2 Return b J4-095
Signal 2 Shield (GND) f J4-096
IRIU User Guide Public Information GEH-6804 61
6 Maintenance and Replacement
Warning
6.1 Maintenance IRIUs do not have a known wear-out mechanism and do not require periodic maintenance.
6.2 Repair and Replacement
There are no user serviceable items within the unit. Unit is to be returned to manufacturer (refer to the section Repair and Renewals) for repair.
Troubleshooting should be done at the unit level. The failed IRIU should be removed, returned to GE, and replaced with a known good spare. Do not attempt to repair system components.
Caution
This equipment contains a potential hazard of burn. Only personnel
who are adequately trained and thoroughly familiar with the equipment
and the instructions should install, operate, or maintain this equipment.
To prevent equipment damage, do not remove, insert, or adjust
connectors while power is applied to the equipment.
62 GEH-6804 Public Information IRIU User Guide
6.3 Repair and Renewals
To order renewals and spares (or those not under warranty), contact the nearest GE Sales or Service
Office or an authorized GE Sales Representative, or contact the Parts Super Center.
Parts Super Center:
• Phone: 877-903-1151 • Online: https://www.partssupercenter.com/contact-us
Prior to ordering a repair or replacement units:
• Determine if the part is under warranty
• Identify the unit
The IRIU is identified by a Customer PNR on the unit label. The factory may substitute newer versions
based on availability and design enhancements; however, GE ensures backward compatibility of
replacements.
Public Information