GE Power Management - GE Grid Solutions · 50 Short Circuit/Mechanical Jam/Rapid Trip ... = 120/125...

28
GE Power Management 269Plus Motor Management Relay 269Plus Motor Management Relay

Transcript of GE Power Management - GE Grid Solutions · 50 Short Circuit/Mechanical Jam/Rapid Trip ... = 120/125...

GE Power Management

269Plus Motor Management Relay269Plus Motor Management Relay

GE Power Management 269Plus Motor Management Relay

Offering optimum motor protection in situations where other relays cannot, the 269 Plus Motor Management Relay possesses the unique feature of its ability to “learn” individual motor parameters, giving it the flexibility to adapt to each application by “learning” values of motor inrush current, negative sequence current K factor, cool down rates, start thermal capacity and acceleration time.

GE Power Management 269Plus Motor Management Relay

Presentation OverviewPresentation Overview

66 ApplicationsApplications

66 Protection and Protection and ControlControl

66 Metering andMetering andMonitoringMonitoring

66 Inputs and Inputs and OutputsOutputs

66 User InterfaceUser Interface

66 OrderingOrdering66 CommunicationsCommunications

66 Typical WiringTypical Wiring

ApplicationsApplications

GE Power Management 269Plus Motor Management Relay

The 269 Plus is a microprocessor basedproduct designed to provide complete andaccurate protection for industrial motorsand their associated mechanical systems.

=Three phase AC motors

=Mechanical system protection

MAINMAIN

GE Power Management Applications

3 /

269Plus RELAY

52 50 50G

400A

4160V BUS(4)

ISOLATEDANALOGOUTPUTS

COMMUNICATIONwith

METERING OPTION

VOLTSMETERING OPTION

AMPS MPM

48 46 66

50 51 49 37 86

47 55 27

7437

49

38

50G 51G

14

87 52b

RTD

MOTOR

14

87

LOAD

AMBIENT AIRSTATOR RTDs

BEARING RTDs

SPEED DEVICECONTACTS

DIFFERENTIALRELAY CONTACTS

SPARE INPUTSTARTER AUXILIARY B CONTACT

RS485REMOTE

COMMUNICATION

SELF TESTALARM

AUXILIARYRELAY #1

AUXILIARYRELAY #2

TRIPRELAY

ALARMRELAY

GROUND CT

PHASE CTs

FUSEDCONTACTOR

269PLUS RELAY269PLUS RELAY

FUNCTIONALBLOCK

DIAGRAM

MAINMAIN

Legend

GE Power Management Applications

14 Speed Device37 Undercurrent/Minimum Load38 Motor/Load Bearing Overtemperature46 Unbalance - Negative Sequence48 Multiple Starts/Locked Rotor49 Stator Winding Overtemperature49/51 Overload Curves/FlexCurves50 Short Circuit/Mechanical Jam/Rapid Trip50G/51G Zero Sequence Ground Fault50N/51N Residual Ground Fault52b Breaker74 One Alarm Relay, Two Auxiliary Relays86 Main Trip Latched Relay

Auxiliary Relay No. 1Auxiliary Relay No. 2

87 Differential Relay Contact Input66 Starts per hour47 Volts Phase Reversal (Meter Option)27 Undervoltage (Meter Option)

Frequency (Meter Option)55 Power Factor (Meter Option)

DEVICE PROTECTION

GE Power Management 269Plus Motor Management Relay

ProtectionProtection

=Stator windingovertemperature

=Bearingovertemperature

=Multiple starts

=Overloads

=8 standard overload curves

=Ground fault

=Undercurrent

=Phase reversal (meter option)

=Variable lock out time

=“Learns” individual motor parameters

=Short circuit

=User defined overloadFlexCurveTM

=Locked rotor

=Rapid trip/mechanical jam

=Unbalance/single phasing

MAINMAIN

GE Power Management

Start and RunningStart and Running

269Plus Motor Management Relay

=Motor is protected under both Acceleration and Runningconditions

The 269 Plus can trigger an alarm or trip the motor based on:

=normal acceleration time=number of starts per hour=multiple starts=time between starts=motor overload conditions

MAINMAIN

GE Power Management

=One of eight standard overload curves may be programmed based on motor manufacturer’s locked rotor time capability.

=Alternately, the user may program in a custom curve using the built-inFlexCurve™ function.

Protection

OverloadOverload

MAINMAIN

View 8 Standard Overload Curves

GE Power Management Protection

8 Standard Overload Curves

Full Load Current Setpoint Multiples of Full Load Current Setpoint

=The motor’s service factor value is entered as the overload pickup level

GE Power Management

FlexCurve can be used to protectmotors which have different rotorand stator damage, allowing totalmotor design capacity with complete protection.

When a FlexCurve is programmed,the 269 Plus develops a smoothcustom overload curve within a selected range.

Protection

FlexCurveFlexCurve™™

1

2

3

4

5

Multiples of Full Load Current Setpoint

6500 HP, 13800 Volt INDUCED DRAFT FAN MOTOR

1) Programmed 269 Plus Custom Curve

2) Running Safetime (Rotor Limited)

3) Acceleration Safetime(Rotor Limited)

4) Motor Current @ 100% Voltage

5) Motor Current @ 80% Voltage

GE Power Management Protection

Thermal ModelingThermal Modeling

The Thermal Model within the 269Plus has the ability to computethe motor I2t value based on actual motor load current.

=thermal model calculates value in terms of thermal capacity used

=RTDs (resistance temperature units) measuring stator temperature act as a thermal capacity check to confirm value calculated bythermal model. RTDs may be used for monitoring stator, bearing,ambient, or other temperature monitoring.

=thermal capacity used is then updated to reflect the higher of the two values

MAINMAIN

GE Power Management Protection

MotorMatch modifies the initially entered relay parameters to match actual measured motor characteristics. The key elements include:

=accumulated I2t in the memory=RTD input to the memory=learned cooldown time from run to stop=learned cooldown time from run-overload to run-normal

=learned acceleration time=learned negative sequence contribution (K-factor)

Motor MatchMotor Match

MAINMAIN

GE Power Management Protection

RTD Hot Motor CompensationRTD Hot Motor Compensation

When hot motor compensation is enabled:=RTD feedback from actual stator temperature checks

the thermal capacity model

=User has the capability to match the motor thermalcharacteristics with a dual slope RTD bias curve

=The two part curve allows for easy fitting of hot and cold motor damage curves to the RTD bias feature

MAINMAIN

GE Power Management 269Plus Motor Management Relay

User InterfacesUser Interfaces

=PC Software for setting, monitoring=48 character alpha-numeric backlit

LCD display=Five Target LED indicators=MPM (meter) com port=RS485 com port (ModBus® RTU)

MAINMAIN

GE Power Management User Interfaces

HELP KEY=Help key can be pressed at

any time to provide additionalinformation

PROTECTIVE COVER=Rugged, corrosion and flameretardant case

=Meets IP53/NEMA 12

MAINMAIN

GE Power Management User Interfaces

DISPLAY=48 Character alpha-numeric backlitLCD display for viewing actual values, causes of alarms and trips, and programming setpoints.

STATUS INDCATORS=5 LEDs indicate when an output isactivated. When an LED is lit the cause of the output relay operationwill be shown on the display.

KEYPAD=Used to select the display of actual values, causes of alarms, causes of trips, fault diagnosis and toprogram setpoints.

I 1=120 I 2=120I 3=121 (AMPS)

MAINMAIN

LINE

2 9 3 0 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 4 0 4 1 4 2 4 3

T R IPN C R E L A Y N O

RS422

MULTILIN

269 B200REV. C608/96

TM201

TM201

TM202

TM202

TM203

TM203

TM217

TM216

TM204

TM212

TM205

TM213

TM206

TM214

TM207

TM215

RX-RX+

A L A R MN C R E L A Y N O

A U X 1N C R E L A Y N O

A U X 2N C R E L A Y N O

C O N T R O L P O W E RL ( + ) G L 2 / N ( - )

SPARE- +

METER

- +DIFF.- +

SP. SW.

- +AC

CESS

- +EM

.RST- +

EX. RES- +

- +RS485- +

R228

G N DJ 2 0 1H P O T

8 3 8 2 8 1 8 0 7 9 7 8 7 7 7 6 7 5 7 4 7 3 7 2

G R O U N D F A U LT2 0 0 0 C O M : 5

P H A S E 3: 1 C O M 5

P H A S E 2: 1 C O M 5

P H A S E 1: 1 C O M 5

T201

T202

T203

T204

44

47

51

56

47

639

684

45

48

52

57

88

S H D

648

693

46

50

55

46

621

0

675

49

54

59

611

1

666

711

53

58

601

2

657

702

GE Power Management User Interfaces

CONTROL POWER=120/125 AC/DC=240/250 AC/DC=24 AC/DC, 48 AC/DC

4 OUTPUT RELAYS=Programmable alarm and trip conditions activated by:=programmable setpoints=switch input=remote communication control

RTD 7-10=Can be assigned to monitor motor and load bearings, and ambient temperature

INPUTS/OUTPUTS=Spare input=MPM (meter) com port=Differential relay input=Speed switch input=Access input=Emergency restart=External output=Analog output=RS485 com port

RTD 1-3=Typically used for statorwinding protection

RTD 4-6=Typically used for statorwinding protection

Phase and ground CT inputs Contrast dial MAINMAIN

GE Power Management 269Plus Motor Management Relay

CommunicationsCommunications

=Successfull interface with many PLCssuch as Modicon, Square D, Allen Bradleyand GE Fanuc

ProtocolProtocol>> Modbus® RTU protocol

Terminals for RS485 located on rear port of the relay

MAINMAIN

GE Power Management 269Plus Motor Management Relay

MeteringMetering

=average and individual phase currents=RTD temperatures (hottest, individual, maximum)=unbalance ratio (%In/Ip)=ground leakage current=thermal capacity remaining / estimated time to tripat present overload level

=motor load as a percent of full load=phase to phase or phase to neutral voltage(meter option)

=W, var, MWhr, PF, Hz (meter option)

Actual ValuesActual Values

MAINMAIN

GE Power Management 269Plus Motor Management Relay

MonitoringMonitoring

=immediate overload/stall warning=ground fault=mechanical jam=unbalance=undercurrent=RTD overtemperature, broken RTD sensor, low temperature RTD

=self-test-service=under/overvoltage (meter option)=low power factor (meter option)

Prior AlarmsPrior Alarms

MAINMAIN

GE Power Management 269Plus Motor Management Relay

MonitoringMonitoring

Fault DiagnosisFault Diagnosis

=269 Plus displays the cause of the trip andwill show the remaining lock-out time if applicable

=cause of the last trip and pre-trip values can be recalled for rapid fault diagnosis.

MAINMAIN

GE Power Management 269Plus Motor Management Relay

Statistical Data (Statistical Data (StatTracStatTracTMTM))

=StatTracTM provides statistical data of motor use foroperations monitoring, maintenance, and fault diagnosis.

=Using the Keypad, the user can display:

MonitoringMonitoring

=running hours and number of starts since last commissioning =number of all trips=number of specific types of trips=total Watt-hours (with meter option)

MAINMAIN

GE Power Management 269Plus Motor Management Relay

InputsInputs

==Speed Switch InputSpeed Switch Input

==Differential Relay InputDifferential Relay Input

==Spare InputSpare Input

=enables the user to use an external speed device

=provided terminals to accept contact closure from an externaldifferential relay

=all protective functions grouped through one main relay

=spare input terminals configurable to represent either a standard contact input(ie-pressure switch), or a specific contact input (circuit breaker/contactor status)

=52b contact from a circuit breaker = positive identification of the position of the breaker(open or closed)

MAINMAIN

GE Power Management 269Plus Motor Management Relay

OutputsOutputs

==4 Output Relay Contacts4 Output Relay Contacts=Trip Relay as main latched output relay =Alarm output relay (latched or unlatched)=Auxiliary 1 output relay (latched or unlatched)=Auxiliary 2 output relay

==Analog outputAnalog output=Used to indicate motor thermal capacity used,motor current, hottest stator RTD, bearing RTD, or CTsecondary current

MAINMAIN

MOTOR

MOTOR

ZERO SEQUENCE GROUND CONNECTION

269Plus TYPICAL WIRING

RESIDUAL GROUND CONNECTION

(ALTERNATE)

ALTERNATE CONNECTIONFOR

COMMON SHIELD

START STOP FUSE

GROUNDBUS

52b

METER COM PORT

EXTERNAL CONTACTSEXTERNAL CONTACTS

JUMPER OR KEYSWITCH

KEYSWITCH

EXTERNAL RESETAMMETER OR PROGRAMMABLE CONTROLLER

RS485 COM PORT

GROUNDED AT MASTER ONLY

PHASE A CT

MAINMAIN

PHASE B CT

PHASE C CT 50:0.025 GROUND CT

PHASE A CT

PHASE B CT

PHASE C CT

269PLUS * * * * * *269PLUS Motor Management RelaySV Standard version

D/O Drawout versionPhase CT 1 Ground CT (required for D/O only)

1 :5 2000:12 :5 :53 :1 2000:14 :1 :5

Relay fail safe code2 (required for D/O only)Trip Alarm Aux1 Aux2

1 FS NFS NFS FS2 NFS FS NFS FS3 FS FS NFS FS4 NFS NFS FS FS5 FS NFS FS FS6 NFS FS FS FS7 FS FS FS FS8 NFS NFS NFS FS

Relay contact arrangement3 (required for D/O only)Alarm Aux1 Aux2

1 N.O. N.O. N.O.2 N.O. N.O. N.C.3 N.O. N.C. N.O.4 N.O. N.C. N.C.5 N.C. N.O. N.O.6 N.C. N.O. N.C.7 N.C. N.C. N.O.8 N.C. N.C. N.C.

100P 100 Ohm platinum RTD10C 10 Ohm copper RTD

100N 100 Ohm nickel RTD120N 120 Ohm nickel RTD

120 120 AC/125 DC control voltage240 240 AC/250 DC control voltage24DC 24 DC control voltage48DC 48 DC control voltage

OORRDDEERR

CCOODDEE

GE Power Management

269Plus Motor Management Relay269Plus Motor Management Relay

Contact : GE Power Management

215 Anderson Ave., Markham, Ont. Canada L6E 1B3

Tel: 905-294-6222

Fax: 905-201-2098

Email: [email protected]