GE Grid Solutions€¦ · Title: untitled Created Date: 2/3/2006 10:35:05 AM

27
W650 Wind Generator Protection System System Protection & Improved Operational Uptime

Transcript of GE Grid Solutions€¦ · Title: untitled Created Date: 2/3/2006 10:35:05 AM

  • W650 Wind Generator Protection System

    System Protection & Improved Operational Uptime

  • 2 /GE Multilin

    2005

    Why W650?Protection to Provide Backup to Wind Turbine Controls & Excitation

    Better Wind Farm Economics by Improving System Uptime & Time to Restoration• Address Lack of Wind Turbine & System Event

    DiagnosticsDiagnostic in W650 can tell what happened, why, and when … to the mSec

  • 3 /GE Multilin

    2005

    What is the W650?

    Part of an Overall Protection System … but can be used as a stand alone protective device

    Overlay to Existing Wind Turbine & Farm Control by Providing Unit Protection, Wind Farm System Protection, Unit, & System Diagnostics

    Substation Protection Controller

    W650 1 in Wind Turbine

    W650 2 in Wind Turbine

    W650 n in Wind Turbine

    Windfarm Substation Protection Controller sends Trip and Block Commands to and From W650’s

    W650’s can also send trip and block commands to each other

  • 4 /GE Multilin

    2005

    Some Definitions …

  • 5 /GE Multilin

    2005

    Definition of Larger Wind Farm System (Units > 1MW on a Coordinated Farm)

    G

    G

    G

    G

    G

    G

    G

    G

    G

    G

    G

    G

    G

    G

    G

    G

    G

    G

    G

    G

    G

    G

    G

    G

    G

    Utility (e.g. 33kV)Tie Breaker

    Step Up TransformerBus Breaker

    Windfarm SubstationBus

    Collector Feeder Breakers

    Collector Bus

    Transformer BreakerLine

  • 6 /GE Multilin

    2005

    Definitions with Wind Turbine

    WTG

    GeneratorExcitation

    Transformer

    Wind Tower Breaker

    Generator Output Voltage (e.g. - 575V or 3kV … depends on MW size of Generator)

    Collector System Voltage (e.g. - 3kV or 13.8 … depends on MW size of Generator & Presence Transformer)

    Wind Tower

  • 7 /GE Multilin

    2005

    Sources of Faults

    Inside the Wind Turbine• Tower Cable• Transformer Faults• Wiring Inside the Electrical

    Distribution Panel• Wind Turbine Generator• Excitation System Fault

    On the Wind Farm• Collector Bus Cable Fault• Step Up Transformer• Substation Bus Structure

    Fault• Feeder Fault Impact on

    Stability

    External to the Wind Farm• Voltage Stability• Reverse Power Flow

  • 8 /GE Multilin

    2005

    How Faults Manifest Themselves

    Inside the Wind Turbine• IOC, TOC, Ground Fault

    On the Wind Farm• Voltage/Current Unbalance

    External to the Wind Farm

    •IOC, TOC, Voltage Stability

  • 9 /GE Multilin

    2005

    Subjects for Discussion … Gaps Today

    1. No backup Protection in Wind Turbines/Towers … Need for a System Wide Protective Application apart from Control

    2. Lack of Coordinated Event Record & Oscillography make it Difficult to Determine What Happened & When, resulting in Prolonged Time to Return to Service

    3. Lack of Overall Coordinated Wind Farm System Protection can result in Lack of Operational Selectivity and Reduced System Uptime

  • 10 /GE Multilin

    2005

    What does the W650 do ?

  • 11 /GE Multilin

    2005

    W650 Wind Turbine Protection CapabilitiesW650 for Protection, Metering, and Coordination to Upstream Substation ProtectionCommunications to GE Wind Turbine Controller via CANopen protocol

    •Available Protection –Under/overvoltage, Under/overfrequency, voltage unbalance, directional over-current, zero sequence overvoltage, aux voltage, and breaker failure

    Configurable Display & LED’s

    Keypad & ShuttleFront Port Upload & Download

  • 12 /GE Multilin

    2005

    W650 Hardware Construction

    The W650 features advantage such as:• Modular hardware architecture:

    Main CPU board with two plug and play comm boardsUniversal magnetic (CTs & VTs) moduleProgrammable I/O moduleSingle or redundant power supplyFront board: HMI ( Graphical or alphanumerical display, LEDs, RS232)

    • Modern and open communication protocols for easy integration

  • 13 /GE Multilin

    2005

    W650 Wind Turbine Protection (con’t)• Metering – current (+/- 0.5%),

    voltage (+/- 1%), power(+/-1%), energy (1%), power factor (0.02)

    • Event capture – up to 479 events time stamped to 1mSec

    • Oscillography – Up to 20 oscillography files programmable from 4-64 samples/cycle, 1MB of data, analog and digital signals. Retrievable via front panel or system communications.

    • Monitoring – 4x20 character display … optional graphic display …

  • 14 /GE Multilin

    2005

    W650 Wind Turbine Protection (con’t)

    •Control – programmable unit control

    •Communications – IEC61850 communications to peer W650’s and Substation Protection Relays

    Substation Protection Controller

    W650 1 in Wind Turbine

    W650 2 in Wind Turbine

    W650 n in Wind Turbine

    IEC61850 Communications Protocol Uses Ethernet to Send Block and Trip Commands from WTG Relays to Substation Controller as well as via Peer to Peer

  • 15 /GE Multilin

    2005

    W650 Wiring

  • 16 /GE Multilin

    2005

    How does the W650 Integrate into the Entire Wind Farm?

  • 17 /GE Multilin

    2005

    Examples of Wind Farm Protection Requirements

    1. Open Collector Breakers Upon Fault in Cable to Host Utility

    – All Wind Turbines, Selective, or Entire Collector2. Open Collector Breakers Upon Transformer Fault

    – All Wind Turbines, Selective, or Entire Collector

    3. Collector Bus Cable fault Requires Selective Trip Wind Turbine Breakers

    4. Issues in a Specific Wind Turbine to Prompt Block Command to Other Wind Turbines

  • 18 /GE Multilin

    2005

    Electrical Protection TopologyInterconnect

    Protection

    GSU Protection

    Bus Protection

    Feeder Protection

    Feeder Protection

    Feeder Protection

    Feeder Protection

    Turb. Prot.

    Turb. Prot.

    Turb. Prot.

    Turb. Prot.

    Turb. Prot.

    Turb. Prot.

    Turb. Prot.

    Turb. Prot.

    Turb. Prot.

    Turb. Prot.

    Turb. Prot.

    Turb. Prot.

  • 19 /GE Multilin

    2005

    Network TopologyInterconnect

    Protection

    GSU Protection

    Bus Protection

    Feeder Protection

    Feeder Protection

    Feeder Protection

    Feeder Protection

    Turb. Prot.

    Turb. Prot.

    Turb. Prot.

    EnetSwitch

    EnetSwitch

    EnetSwitch

    Ethernet Switch

    Feeder 2 Feeder 3 Feeder 4

    •Fault Tolerant Ring

    •Support WTG outside a break in the ring

    •Requires 2 Fiber Strands

    •Worst case 1 micro Sec Delay by Switch

    •Unmanaged Switch in WTG

    •Managed Switch w/VLAN in Substation

    Protection System Overlays Parallel Control System

  • 20 /GE Multilin

    2005

    Alternate Network Topology (if 3rd Party Wind Farm Protection is Used)

    Sub controller

    Turb. Prot.

    Turb. Prot.

    Turb. Prot.

    EnetSwitch

    EnetSwitch

    EnetSwitch

    Ethernet Switch

    Feeder 2 Feeder 3 Feeder 4

    Other Supplier’s Protection

    Hardwired IO

  • 21 /GE Multilin

    2005

    Transfer Trip Capabilities of W650

    1. send a “block” or “transfer trip” from the protection offering in the Wind Farm substation protection (GE or other) to entire collector bus or individual wind turbine

    2. “block” or “transfer trip” command from individual wind turbine to substation protection

  • 22 /GE Multilin

    2005

    Transfer Trip Example

    1. Transformer Protection detects Differential Fault and Initiates Transfer Trip Command

    – Transformer Breaker Opens

    2. Collector Bus W650’s Receive Transfer Trip Command and Issue Command to Trip Breaker

    3. Collector Bus and WTG’s Isolated

  • 23 /GE Multilin

    2005

    Economics

    • Yellow Items Represent Customer Specific Variables

    • Payback Calculated on Improved System Operations

    • Equipment/Personnel Damage Avoidance Not Included

    Wind Farm Energy Sell Price ($/kWH) 0.08$

    Size of Individual WTG (MW) 1.5

    Size in kW 1500

    Downtime of 1 WTG (hours) 48

    Lost Revenue of 1 WTG 5,760.00$

    % Improvement of W650 Diagnostics 50%

    $ to Operating Bottom Line for 1 occurance 2,880.00$

    Number of Windturbines in Windfarm 16

    Cost of W650 system 24,660.00$ Estimated # of WTG Outages/Year 24

    Savings to W650 System 69,120.00$

    Payback Period (years) 0.36

  • 24 /GE Multilin

    2005

    How do I get more information?

  • 25 /GE Multilin

    2005

    Support Resources Available from GE Multilin• Available On-line at www.gemultilin.com• Product Cut Sheet

    • Product Presentation• Whitepaper on Transfer Trip Technologies and

    Benefits• Guideform Specification to Assist Consultants and

    EPC’s• Wiring/Installation Information

    • Pricing and Ordering Information Available On-Line

  • 26 /GE Multilin

    2005

    Ordering Information

    Greenfield Installations•Specify to Wind Turbine OEM & Wind Farm EPC•Request to Include with Wind Farm Substation and Wind Turbine’s•Field Integration Services Available

    Retrofit Bill of Material•1 W650 per Wind Turbine•1 Ethernet Switch per Wind Turbine (GE Multilin model ML600)•1 Ethernet Switch in Wind Farm Substation (GE Multilin model ML2400)•Substation Protection Controller (GE Multilin C30)

  • 27 /GE Multilin

    2005

    Who to Contact for Questions

    •GE Multilin – John Garrity, 518.877.8860, [email protected]

    •GE PSEC – tbd

    •GE Wind - tbd