PT2E-1581
Gas detector head
GD-70D-ET
Operating Manual for
PoE method communication
Preface
Thank you for choosing our gas detector head GD-70D-ET. This manual explains how to use the gas detector GD-70D-ET. Not only the first-time users but also the user who have already used a GD-70D-ET must read and understand the operating manual before using this product. Throughout this manual, the following indications are used to ensure safe and effective work.
DANGER This message indicates that improper handling may cause serious damage on life, health or assets.
WARNING This message indicates that improper handling may cause serious damage on health or assets.
CAUTION This message indicates that improper handling may cause minor damage on health or assets.
NOTE This message indicates advice on handling.
GD-70D-ET comprises part of a system used to manage various information in the field by using PoE method communications. Please be sure to read the operating manuals of related equipment. Liability limitation:
Any results caused by programs that communicate with GD-70D-ET shall be out of our
responsibilities.
Notation of numerical number:
Decimal numeral : Number only ( 1 100 1000 etc…)
Hexadecimal numeral : “0x” before number ( 0x00 0x64 0x3EB etc…)
<Contents>
Preface
1. Start-up ................................................................................................... 1
1-1. Installment ................................................................................................ 1
1-1-1. How to install PoE switching hub .............................................................. 1
1-1-2. How to install switching hub (Non PoE type) ............................................. 1
1-2. Setting...................................................................................................... 2
1-2-1. How to set an IP address of GD-70D-ET................................................... 2
1-2-2. How to set an IP address of PC ................................................................ 3
1-2-3. Communication test .................................................................................. 4
1-3. Web functions .......................................................................................... 5
1-3-1. How to set a browser ................................................................................ 5
1-3-2. How to login to User Mode ....................................................................... 6
1-3-3. How to login to Authorized User Mode ...................................................... 7
1-4. PLC communication functions .................................................................. 8
1-4-1. Connection to PLC (OMRON CJ/CS series) ............................................. 8
1-4-2. Communication with PLC (OMRON CJ/CS series) .................................... 9
1-4-3. Connection to PLC (MELSEC Q series) .................................................... 10
1-4-4. Communication with PLC (MELSEC Q series) .............................................. 11
2. Web functions ................................................................................................. 12
2-1. Cautions of usage environment ................................................................ 12
2-2. Table list of functions ................................................................................ 14
2-3. Components of Web screens………………………………………………….. 15
2-3-1. User screen .............................................................................................. 15
2-3-2. Authorized user screen ............................................................................. 18
2-4. Auto mailing function (gas alarm / fault alarm)........................................... 30
3. Modbus / TCP communication functions .............................................. 32
3-1. Communication specification .................................................................... 32
3-2. Registered map ........................................................................................ 32
3-3. Command ................................................................................................ 37
3-4. Exceptional responses ............................................................................. 38
3-4-1. Non-corresponding function ...................................................................... 38
3-4-2. In case being specified the outlying address ............................................. 38
3-4-3. In case being specified the access to the outlying address ........................ 38
3-4-4. In case being specified the writing on the unwritable address .................... 38
4. PLC communication functions .............................................................. 39
4-1. Communication specification .................................................................... 39
4-2. Data types ................................................................................................ 40
4-2-1. Basic Data (Small) .................................................................................... 40
4-2-2. Basic Data (Large) ................................................................................... 40
4-2-3. Basic Data (Small) + Optional Data........................................................... 41
4-2-4. Basic Data (Large) + Optional Data .......................................................... 42
4-3. Communication setting ............................................................................. 43
4-4. Data map ................................................................................................. 44
4-4-1. Basic Data (Small) .................................................................................... 44
4-4-2. Basic Data (Large) ................................................................................... 45
4-4-3. Optional Data ........................................................................................... 47
4-5. Command ................................................................................................ 48
4-5-1. How to issue command 1 (Setting Alteration) ............................................ 48
4-5-2. How to issue command 2~9 ............................................................................ 49
Basic data (Large) only.
4-5-3. How to issue command 10 (Setting alarm test concentration) ................... 50
Basic Data (Large) only.
4-5-4. Command related data to Basic Data (Large) ........................................... 51
4-5-5. Command related data to Optional Data ................................................... 53
4-5-6. How to alter alarm points setting ............................................................... 54
4-5-7. How to operate inhibit ............................................................................... 55
1
1. Start-up
This part of section, how to connect the cables, how to set the system, what the Web screen of
GD-70D-ET is like, and how to communicate with PLC are shown.
1-1. Installment
GD-70D-ET and PC shall be connected as below.
1-1-1. How to install PoE switching hub
イーサネットケーブル
スイッチングハブ
パソコン
GD-70D-ET
(PoE)
1-1-2. How to install switching hub (Non PoE type)
GD-70D-ET shall be supplied DC24V.
PC
Switching hub
Ethernet cable
Ethernet cable
Switching hub
PC
AC-DC power supply
Power source
2
1-2. Setting
1-2-1. How to set an IP address of GD-70D-ET
Turn ON the power switch of GD-70D-ET.
Set the IP address 192.168.1.1 and the Subnet mask 255.255.255.0 by pressing keys on
the front panel.
Roles of keys
① MODE key
② ▲▼ keys
③ SET key
Setting procedure
① Press the MODE key for three seconds to enter the maintenance mode.
(Display shows [1-1/ZERO] )
② Press the ▲ and ▼ keys to move to [1-8/M MODE] display and press the SET key.
(Display shows [----/M MODE] )
③ Press the SET key for three seconds.
(Display shows [2-0/GAS TEST] )
④ Press the ▲ and ▼ keys to move to [2-10/SETTING2 ] display and press the SET key.
(Display shows [SET 0/ADDRESS] )
⑤ Press the ▲ and ▼ keys to move to [SET 18/ETHERNET ] display and press the SET
key. (Display shows [XX/MAC1] )
⑥ Press the ▲ and ▼ keys to move to [XXX/IP1] display and press the SET key.
(Display shows [XXX/IP1] *XXX is flickered number )
⑦ Press the ▲ and ▼ keys to move to [192/IP1] display and press the SET key.
(Display shows [192/IP1] )
⑧ The same procedure as ⑥ and ⑦, set 168,1,1/255,255,255,0 to IP2~4/SUB1~4.
⑨ Press the ▲ and ▼ keys to move to [ /SAVE] display and press the SET key.
(Display shows [ /SAVE Y/N] )
⑩ Press the SET key to write the IP address to GD-70D-ET.
(Writing the IP address takes approximately 10 seconds, then display shows [SET18/
ETHERNET] )
⑪ Press the MODE key for three seconds to return to the detection mode.
②
①
③
3
1-2-2. How to set an IP address of PC
Set IP address in Propety of Internet Protocol (TCP/IP).
Set IP address 192.168.1.2 and the Subnet mask 255.255.255.0.
(A figure below is an sample screen of Windows7.)
4
1-2-3. Communication test
Input as follows in Command Prompt of Windows.
ping 192.168.1.1 [Enter]
<Screen shows communication test is succeeded>
<Screen shows communication test is failed>
Confirm the installment and the setting if communication test is failed.
Display of GD-70D-ET shows (TX)/(RX) during data transmission/data reception.
5
1-3. Web functions
1-3-1. How to set a browser
Enter to [Internet options] and move to [connections] tab, and click [LAN settings].
Uncheck [Use a proxy server for your LAN] in case of being checked.
6
1-3-2. How to login to User Mode
Input to [Address] in Internet explorer as follows, and click [Move].
http://192.168.1.1
In User Mode, basic information (gas name and alarm points…etc) is displayed.
(Screen is varied depending on the version of Internet explorer and the settings)
Refer to “2. Web functions” for the details.
7
1-3-3. How to login to Authorized User Mode
Input to [Address] in Internet explorer as follows, and click [Move].
http://192.168.1.1/login.html
Screen below is displayed. Input “GD-70D” to the default password and click [Login]
In Authorized User Mode, detail information of GD-70D is displayed, and the settings are
alterable.
8
1-4. PLC communication functions
1-4-1. Connection to PLC (OMRON CJ / CS series)
PLC shall be connected as below.
(Figure shows an example with PoE switching hub)
イーサネットケーブル
スイッチングハブ
パソコン
GD-70D-ET
PLC(OMRON CJ)
(PoE)
Set IP address 192.168.1.10 and FINS/UDP port 9600 to PLC.
PC
Switching hub
Ethernet cable
9
1-4-2. Communication with PLC (OMRON CJ / CS series)
Click [Network], located the left side of Authorized User Web screen, and set the right side of
Authorized User Web screen as below. Write Basic Data (Small) to 0 address in D memory
of PLC (IP address192.168.1.10, NODE10 and FINS/UDP port 9600).
Refer to “4. PLC communication functions” for the details.
Screen below shows how data is written to D memory.
(Increment of D2 counter is carried out)
(CX-Programmer PLC memory screen)
Refer to “PLC operation manuals” for PLC settings.
CAUTION
There is a possibility that wrong setting for rewriting PLC memory causes unexpected PLC
action. Be sure setting is correct.
10
1-4-3. Connection to PLC (MELSEC Q series)
PLC shall be connected as below.
(Figure shows an example with PoE switching hub)
イーサネットケーブル
スイッチングハブ
パソコン
GD-70D-ET
PLC(MELSEC Q)
(PoE)
Set IP address 192.168.1.11 and UDP port 5000 to PLC.
PC
Switching hub
Ethernet cable
11
1-4-4. Communication with PLC (MELSEC Q series)
Click [Network], located the left side of Authorized User Web screen, and set the right side of
Authorized User Web screen as below. Write basic data (Small) to 0 address in D memory of
PLC (IP address192.168.1.11, UDP port 5000).
Refer to “4. PLC communication functions” for the details.
Screen below shows how data is written to D memory
(Increment of D2 counter is carried out)
(GX-Developer memory devices screen)
Refer to “PLC operation manuals” for PLC settings.
CAUTION
There is a possibility that wrong setting for rewriting PLC memory causes unexpected PLC
action. Be sure setting is correct.
12
2. Web functions
2-1. Cautions for usage environment
Web functions shall be used with Microsoft Internet Explorer6~8.
There is a possibility that browsers other than Microsoft Internet Explorer6~8 cause
unexpected action.
Set [Active scripting] to be enable. (Web functions are based on browser script.)
13
Confirm proxy server settings (Windows7 Internet Explorer 8)
CAUTION
Above settings are valid if GD-70D-ET is used with local address only. Web functions are
invalid if GD-70D-ET is used via proxy server.
As settings are altered by GD-70D-ET operation, screen is displayed again and [Date is
updated] is displayed at the end of the maintenance mode.
GD-70D-ET records login histories whenever Authorized user is login, and recorded
histories are automatically deleted when GD-70D-ET is turned OFF the power.
(Error is displayed as the result of non-displayed screen is displayed, which is the situation
that browser is opened and GD-70D-ET is turned from OFF to ON the power. Close browser
and login again to reset the error.)
Do not alter settings at the same time by Web functions and GD-70D-ET operation.
There is no Check for [Use a proxy server for your LAN], Web functions can be used without any alterations.
[Internet options]
[Connections] tab
→ [LAN settings] → [Local area network (LAN) settings]
There is a Check for [Use a proxy server for your LAN], check to [Bypass proxy server for local addresses]. [Proxy settings] is displayed in [Advanced].
Write IP address of GD-70D-ET to [Do not use proxy server for addresses beginning with:] in [Exceptions]
14
2-2. Table list of functions
○: Displayed ×: Non-Displayed
HOME Authorized
User Deteils of functions
User screen Authorized
User screen
HOME Status ○ ○ Show GD-70D-ET settings
Event History ○ ○ Show listed 100 histries and a trend
graph
Calibration
History × ○
Show listed 100 histories
Log out × ○ Logout menu for Authorized Users
CALIBREATION Zero
Calibration × ○
Zero calibration function
Span
Calibration × ○
Span calibration function
TEST Alarm Test × ○ Alrm test function
Fault Test × ○ Fault test function
AUTHORIZED
USERS Alarm × ○
Confirm and alter settings related to
alarm
Network × ○ Confirm and alter settings related to
communication / mail / network
Date/Time × ○ Confirm and alter date / time
Configuration × ○
Confirm and alter settings related to
detail information of GD-70D-ET and
sensor
MAINTENANCE × ○ Enter the maintenance mode
INHIBIT × ○ Put inhibit condition ON
ALARM RESET × ○ Reset alarms
15
2-3. Components of Web screen
Start up Microsoft Internet Explorer and specify address.
([xxx] is GD-70D-ET IP address)
User screen (User)
http://xxx.xxx.xxx.xxx Password is not required.
Authorized user screen (Authorized Users)
http://xxx.xxx.xxx.xxx/login.html Password is required.
Password setting: Default password “GD-70D”
2-3-1. User screen
HOME
Status screen (User)
Real time status of GD-70D-ET is displayed.
Alarm settings and sensor setting are displayed.
Screen for printing a displayed page is displayed by clicking [Open Print Page].
16
Event History screen (User)
Event History
10 event histories are displayed in 1 page (maximum 100 histories for 10 pages).
Time stamps, event descriptions, [Graph] (If data has trend graphs) are displayed on screen.
A trend graph that shows 3 minutes trend before and after alarms are activated is displayed
by clicking [Graph]. Screen for printing all event pages, including non-displayed pages, is
displayed by clicking [Open Print All]. Screen for printing a displayed page is displayed by
clicking [Open Print Page].
Screen for printing [Open Print All] Screen for printing [Open Print Page]
17
Event History screen (User)
Trend graph
A trend graph that shows 3 minutes trend before and after alarms are activated is displayed
by clicking [Graph].
Screen for printing a displayed page is displayed by clicking [Open Print Page].
Return to Event History by clicking [Return].
18
2-3-2. Authorized user screen
HOME
Status screen (Authorized User)
Real time status of GD-70D-ET is displayed.
Alarm settings and sensor setting are displayed.
Alarm activated status is reset by clicking [ALARM RESET]
Screen for printing a displayed page is displayed by clicking [Open Print Page].
19
Event History screen (Authorized User)
Event History
10 event histories are displayed in 1 page (maximum 100 histories for 10 pages).
Time stamps, event descriptions, [Graph] (If data has trend graphs) are displayed on screen.
A trend graph that shows 3 minutes trend before and after alarms are activated is displayed
by clicking [Graph]. Screen for printing all event pages, including non-displayed pages, is
displayed by clicking [Open Print All]. Screen for printing a displayed page is displayed by
clicking [Open Print Page].
Screen for printing [Open Print All] Screen for printing [Open Print Page]
20
Event History screen (Authorized User)
Trend graph
A trend graph that shows 3 minutes trend before and after alarms are activated is displayed
by clicking [Graph].
Screen for printing a displayed page is displayed by clicking [Open Print Page].
Return to Event History by clicking [Return].
21
Calibration History screen (Authorized User)
Calibration History list is displayed in 10 histories for 1 page (maximum 100 histories for 10
pages).
Screen for printing all event pages, including non-displayed pages, is displayed by click
[Open Print All].
Screen for printing a displayed page is displayed by clicking [Open Print Page].
22
CALIBRATION
Zero Calibration screen (Authorized User)
Screen for Zero Calibration
CAUTION
To perform the Gas Calibration adequately, read the GD-70D series operating manual and
follow the procedures.
We provide services on regular maintenance including span adjustment, adjustment and
maintenance.
To make the calibration gas, dedicated tools, such as a gas cylinder of the specified
concentration and gas sampling bag must be used.
Our qualified service engineers have expertise and knowledge on the dedicated tools used
for services, along with other products. To maintain the safety operation of the gas detector,
please use our maintenance service.
Please contact our sales department or agents for more information.
23
Span Calibration screen (Authorized User)
Screen for Span Calibration
CAUTION
To perform adequate Gas Calibration, read the GD-70D series operating manual and follow
the procedures.
We provide services on regular maintenance including span adjustment, adjustment and
maintenance.
To make the calibration gas, dedicated tools, such as a gas cylinder of the specified
concentration and gas sampling bag must be used.
Our qualified service engineers have expertise and knowledge on the dedicated tools used
for services, along with other products. To maintain the safety operation of the gas detector,
please use our maintenance service.
Please contact our sales department or agents for more information.
24
TEST
Alarm Test screen (Authorized User)
Screen for Alarm Test
CAUTION
Before starting the alarm test, provide a notification to the related sections so that they can
prepare for false abnormalities. (The alarm contacts are activated during the alarm test.)
25
Fault Test screen (Authorized User)
Screen for Fault Test
CAUTION
Before starting the fault test, provide a notification to the related sections so that they can
prepare for false abnormalities. (The fault alarm contact is activated during the fault test.)
26
AUTHORIZED USERS
Alarm screen (Authorized User)
Screen for confirming and altering the settings.
Update input settings on GD-70D-ET by clicking [Update].
27
Network screen (Authorized User)
Screen for confirming and altering communication / mail / network.
Time synchronization function is to be activated, the time adjustment is automatically
excuted at the execution time by receiving the information from NTP server. (The time delay
caused by communicating with NTP server is not corrected.)
Update input setting on GD-70D-ET by clicking [Update].
Refer to “2-4. Auto mailing function (gas alarm / fault alarm)” for the details.
28
Date / Time screen (Authorized User)
Screen for comfirming and altering the date and time.
29
Configuration screen (Authorized User)
Screen for comfirming and altering TAG No. / Device name / Location of GD-70D-ET.
Update input data on GD-70D-ET by clicking [Update].
TAG No. is used as Mail Sender.
30
2-4. Auto mailing function (gas alarm / fault alarm)
AUTHORIZED USERS
Network screen (Authorized User)
Auto mailing function provides mail notification, which contains gas alarm and fault alarm, to
registered address from GD-70D-ET.
Register an address of mail sender.
Message is sent to maximum 10 addresses. (Message is sent to all registered addresses at
the same time.)
31
Examples of sent message
[1st gas alarm ]
[Low flow alarm]
32
3. Modbus / TCP communication functions
3-1. Communication specification
Protocol Modbus/TCP
Communication mode RTU
Port No. 502 port
Functions Read Holding Register (0x03)
Preset Multiple Registers (0x10)
Modbus/TCP specification is not shown in this manual.
Refer to “Modbus/TCP specifications”.
3-2. Registered map
Registered map of GD-70D-ET Modbus/TCP is shown as below.
Address Writability
(○ or ×) Content Description
40001 × Status
bit0-3:Mode(0: Initial 1: Measuring mode 3: Inhibit 5: Test mode)
bit5: Fault flag
bit6: Alarm: 1st flag
bit7: Alarm: 2nd flag
bit8: Alarm: 1st alarm relay contact flag
bit9: Alarm: 2nd alarm relay contact flag
bit10: Fault relay contact flag
bit11: Repeat 0 and 1 in 2 seconds period.
40002 × (Reserved)
40003 ×
Concentration value
Floating decimal point
Address 40003: low 16 bits
Address 40004: high 16bits 40004 ×
40005 × Concentration value Magnification corrected integer number
Actual value is multipled decimal point code by unit of concentration.
40006 × (Reserved)
40007 × Concentration unit bit0-2: Decimal point code (000:1/1 001:1/10 010:1/100 011:1/1000)
bit8-11: Unit code (0001: ppm 0010: ppb 0100: vol% 1000: %LEL)
40008 × (Reserved)
40009 × (Reserved)
40010 × Date and time Low 16 bits of elapsed the number of second from 00:00 of 1st January 1970.
40011 × (Reserved)
40012 × (Reserved)
40013 ×
1st alarm point
Floating decimal point
Address 40013: low 16 bits
Address 40014: high 16bits 40014 ×
40015 ×
2nd alarm point
Floating decimal point
Address 40015: low 16 bits
Address 40016: high 16 bits 40016 ×
33
Address Writing
(○ or ×) Content Description
40017 × Alarm status bit0: Alarm / 1st
bit1: Alarm / 2nd
40018 × Fault status Bit1: Fault
40019 × (Reserved)
40020 × (Reserved)
40021 ○ (Reserved)
40022 ○ (Reserved)
40023 × Status
bit15: Maintenance
bit14: Test
bit13: Inhibit
bit12: Initial
bit11: Alarm / RANGE OVER
bit10: (Reserved)
bit9: Alarm / 2nd
bit8: Alarm / 1st
bit7: Fault / Sensor
bit6: Fault / Communication
bit5: Fault / Flow
bit4: Caution / Flow
bit2-3: concentration unit code(00: vol% 01: %LEL 10: ppm 11: ppb)
bit0-1: Decimal point code (00:1/1 01:1/10 10:1/100 11:1/1000)
40024 × Concentration value Magnification corrected integer number
Actual value is multipled decimal point code by unit of concentration.
40026 × (Reserved)
40025 × (Reserved)
40027 ○ Year / Month High byte: Year (The last 2 digits) Low byte: Month
40028 ○ Day / Hour High byte: Day Low byte: Hour
40029 ○ Minute / Second High byte: Minute Low byte: Second
40030 × Date and time Low 16 bits of elapsed the number of second from 00:00 of 1st January 1970.
(The same as the address 40010)
40031 × (Reserved)
40032 × (Reserved)
40033 × (Reserved)
40034 × (Reserved)
40035 × (Reserved)
40036 × (Reserved)
40037 × (Reserved)
40038 × (Reserved)
40039 × (Reserved)
40040 × (Reserved)
40041 × Full scale Magnification corrected integer number
Actual Full scale is multipled decimal point code by status of address 0.
40042 × Digit Magnification corrected integer number
Actual digit is multipled decimal point code by status of address 0.
40043 × Magnification 0:same magnification 1:One-tenth 2:One-hundredth 3:One-thousandth
40044 × Unit 0: vol% 1: %LEL 2: ppm 3: ppb
40045 ○ 1st alarm point Magnification corrected integer number
Actual 1st alarm point is multipled decimal point code by status.
40046 ○ 2nd alarm point Magnification corrected integer number
Actual 2nd alarm point is multipled decimal point code by status.
40047 ○ (Reserved)
40048 ○ Alarm delay time Unit: 10 millisecond
40049 × (Reserved)
40050 ○ (Reserved)
34
Address Writing
(○ or ×) Content Description
40051 ○ Alarm method 0: H-HH 1: L-LL 2: L-H
40052 ○ Alarm type 0: Non-Latching mode 1: Latching mode
40053 ○ Relay contact action
during alarm test 0: OFF 1: ON
40054 ○ (Reserved)
40055 ○ Open / Close
bit0 = Alarm: 1st (0: Open 1: Close)
bit1 = Alarm: 2nd ( 0: Open 1:Close)
bit2 = Fault (0: Open 1:Close)
40056 × (Reserved)
40057 × (Reserved)
40058 × (Reserved)
40059 ○ (Reserved)
40060 ○ (Reserved)
40061 ○ (Reserved)
40062 ×
(Reserved)
40063 ×
40064 ×
40065 ×
40066 ×
40067 ×
40068 ×
40069 ×
Serial No. ASCII Character string
Left-align Blanc is space (0x20)
40070 ×
40071 ×
40072 ×
40073 ×
40074 ×
40075 ×
40076 ×
40077 ×
40078 ×
40079 ×
Gas name ASCII Character string
Left-align Blanc is space (0x20)
40080 ×
40081 ×
40082 ×
40083 ×
40084 ○
TAG No. ASCII Character string
Left-align Blanc is space (0x20)
40085 ○
40086 ○
40087 ○
40088 ○
40089 ○
40090 ○
40091 ○
40092 ○
40093 ○
35
Address Writing
(○ or ×) Content Description
40094 ○
Device name ASCII Character string
Left-align Blanc is space (0x20)
40095 ○
40096 ○
40097 ○
40098 ○
40099 ○
40100 ○
40101 ○
40102 ○
40103 ○
40104 ○
Installed location ASCII Character string
Left-align Blanc is space (0x20)
40105 ○
40106 ○
40107 ○
40108 ○
40109 ○
40110 ○
40111 ○
40112 ○
40113 ○
40114 ○
Customer code ASCII Character string
Left-align Blanc is space (0x20)
40115 ○
40116 ○
40117 ○
40118 ○
40119 ×
Sensor serial No. ASCII Character string
Left-align Blanc is space (0x20)
40120 ×
40121 ×
40122 ×
40123 ×
40124 ×
40125 ×
40126 ×
40127 ×
40128 ×
40129 ×
Sensor model ASCII Character string
Left-align Blanc is space (0x20)
40130 ×
40131 ×
40132 ×
40133 ×
40134 × Sensor unit type 1:ESU 2:SGU 3:NCU 4:SSU 5:SSU
6:OSU(25%) 7:OSU(5%) 8:OSU(50%) 9:SCU
40135 ×
(Reserved)
40136 ×
40137 ×
40138 ×
40139 ×
40140 ×
40141 ×
40142 ×
40143 ×
Alarm / Fault new
flags
bit0: Alarm new flag
bit1: Fault new flag
36
Address Writing
(○ or ×) Content Description
40144
~
40250
○ (Reserved)
40251 ○ Command
Refer to 3-3. Command
40252 ○ Subcommand
40253 ○ Parameter 1
40254 ○ Parameter 2
40255 ○ Parameter 3
40256 ○ Parameter 4
37
3-3. Command
Following functions are excuted by writing commands on address 40251~40256.
40251 40252 40253 40254 40255 40256
Functions Command
Sub
command Parameter 1 Parameter 2 Parameter 3 Parameter 4
MM
(0x4D4D)
S
(0x0053) - - - -
Start the
maintenance
mode
E
(0x0045) - - - -
Finish the
maintenance
mode
GS
(0x4753)
W
(0x0057)
0x0000 - - - Inhibit off
0x0001 - - - Inhibit on
RA
(0x5241)
S
(0x0053) - - - -
Start the
alarm test
E
(0x0045) - - - -
Finish the
alarm test
W
(0x0057) Value - - -
Adapt the
value of
alarm test
SB
(0x5342)
W
(0x0057) - - - -
Reset the
alarm
To excute functions, writing commands on address 40251 is required as a trigger.
Commands, subcommand, Parameters (If needed) shall be excuted by a query.
If command only is written, functions shall be excuted by subcommands and parameters that
are already written.
CAUTION
If improper commands other than those above are written, exceptional response is not sent.
If the results of command execution are failure, exceptional response is not sent
ModbusTCP response is sent when writing is success or failure.
To distinguish between success and failure of the command execution processing, make
judgement from the results of status or concentration value after commands are executed.
38
3-4. Exceptional responses
3-4-1. Non-corresponding function
Examples of data:
Query 000000000006010400000001 Function code = 0x04
Response 000000000003018401 Exceptional responses 01 (Improper function)
Corresponding function of GD-70D-ET is “Read Holding Register (0x03)”, “Preset Multiple
Registers (0x10)”.
3-4-2. In case being specified outlying address
Examples of data:
Query 000000000006010301000001 Address = 40257
Response 000000000003018302 Exceptional responses 02
(Improper data address)
Address range of GD-70D-ET is 40001~40256.
3-4-3. In case being specified access to outying address
Examples of data:
Query 000000000006010300FF0002 Read 2 registers from 40256
Response 000000000003018303 Exceptional responses 03 (Improper data)
Although address is specified within address range, address exceeds the final address (40256)
by being specified data number.
3-4-4. In case being specified writing on the unwritable address
Examples of data:
Query 00000000000D0110002E000306000503E80000
Write 3 registers from address 40047 (Address 40049 is unwritable)
Response 000000000003019003 Exceptional responses 03 (Improper data)
If there is an unwritable address within writable ranges, whole functions is to be errow.
(Writable address is unable to be written while errow remains.)
39
4. PLC communication functions
4-1. Communication specification
Protocol FINS / UDP (for OMRON PLC), MC / UDP (for MELSEC PLC)
PLC OMRON CJ / CS series, MELSEC Q series
Deta type Basic Data (Small)
Basic Data (Largel)
Basic Data (Small) + Optional Data
Basic Data (Large) + Optional Data
PLC component (Recommendation) and maximum connected number of GD-70D-ET
Communication setting: Interval min = 1000msec
PLC component (Recommendation) Maximum connected number of GD-70D-ET
CPU Model Ethernet unit Model Data type
Basic Data: Small
Data type
Basic Data (Large)
Basic Data (Small)+Optional Data
Basic Data (Large)+Optional Data
OMRON CJ1H-CPU6□H CJ1W-ETN21(CJ1W-EIP21) 32 8
OMRON CJ1G-CPU4□H CJ1W-ETN21(CJ1W-EIP21) 32 8
OMRON CJ2H-CPU6□ CJ1W-ETN21(CJ1W-EIP21) 64 8
OMRON CJ2H-CPU6□-EIP - (CPU All-in-one) 64 32
MELSEC Q□□HCPU QJ71E71-100 8 8
MELSEC Q□□UDHCPU QJ71E71-100 64 8
MELSEC Q□□UDEHCPU - (CPU All in one) 64 8
Communication setting: Interval min = 3000msec
PLC component (Recommendation) Maximum connected number of GD-70D-ET
CPU Model Ethernet unit Model Data type
Basic Data: Small
Data type
Basic Data (Large)
Basic Data (Small)+Optional Data
Basic Data (Large)+Optional Data
OMRON CJ1H-CPU6□H CJ1W-ETN21(CJ1W-EIP21) 64 32
OMRON CJ1G-CPU4□H CJ1W-ETN21(CJ1W-EIP21) 64 32
OMRON CJ2H-CPU6□ CJ1W-ETN21(CJ1W-EIP21) 128 64
OMRON CJ2H-CPU6□-EIP - (CPU All-in-one) 128 64
MELSEC Q□□HCPU QJ71E71-100 64 32
MELSEC Q□□UDHCPU QJ71E71-100 128 64
MELSEC Q□□UDEHCPU - (CPU All-in-one) 128 64
Refer to “PLC operation manuals” for operations and specifications of PLC.
40
4-2. Data types
4-2-1 Basic Data (Small)
Basic Data (Small)
Write basic data such as alarm status, concentration values, alarm points.
4-2-2 Basic Data (Large)
Basic data (Large)
Write basic data such as alarm status, concentration values, alarm points, and date, gas name.
Read data in order to alter the settings of alarm actions, alarm points…etc.
GD-70D-ET
PLC memory (D,E…etc.)
16 WORD Basic Data (Small)
PLC memory (D,E…etc.)
42WORD Basic Data (Large)
Write data from GD-70D-ET
to PLC
GD-70D-ET
Write data from
GD-70D-ET to
PLC
22WORD Basic Data (Large)
Beginning address for
writing
Beginning address for
writing
Beginning address for
reading
Read data from
PLC to
GD-70D-ET
41
4-2-3 Basic Data (Small) + Optional Data
Basic Data (Small) + optional data
Write basic data such as alarm status, concentration values, alarm points.
Read extended data such as all sorts of names, sensor models, sensor serial No….etc.
Read data in order to alter all sorts of names…etc.
PLC memory (D,E…etc.)
GD-70D-ET
72WORD Optional Data
56WORD Optional Data
16WORD Basic Data (Small)
Beginning address for
reading
Beginning address for
writing
Write data from
GD-70D-ET to
PLC
Read data from
PLC to
GD-70D-ET
42
4-2-4 Basic Data (Large) + Optional Data
Basic Data (Large) + optional data
Write basic data such as alarm status, concentration values, alarm points, and date, gas name.
Read data in order to alter the settings of alarm actions, alarm points…etc.
Read extended data such as all sorts of names, sensor models, sensor serial No….etc.
Read data in order to alter all sorts of names…etc.
PLC memory (D,E...etc.)
GD-70D-ET
22WORD Basic Data (Large)
72WORD Optional Data
56WORD Optional Data
42WORD Basic Data (Large)
Beginning address for
writing
Beginning address for
reading
Write data from
GD-70D-ET to
PLC
Read data from
PLC to
GD-70D-ET
43
4-3. Communication setting
Login to GD-70D-ET Web functions by authorized user, and set PLC communication settings in
network screen. Refer to “2. Web functions” for the details.
Content Description Remarks
PLC PLC Type
Choose PLC communication type.
FINS setting or MC setting of the table list is used
depending on which PLC type is chosen.
Not Used :Not use PLC(Default)
FINS :OMRON CJ / CS series
MC :MELSEC Q series
Type of Basic Data Type of Basic data Small :Small (Default)
Largel :Large
Use Optional Data Use or not use optional date Yes :Use
No :Not use (Default)
Interval
Min
Minimun Send Interval. Send Interval at abnormal
measuring condition (Alarm, Maintenance) with
data changing.
250~10000msec
Minimum time default :1000msec
(With concentration changing)
Maximum timede fault :3000msec
(Without concentration changing) Max
Maximum send interval. Send interval at normal
measuring without data changing.
Timeout
Timeout for receiving from PLC. Stop waiting for
a response from PLC when response time
exceeds a set time. Re-send when interval set
time is exceeded.
1~10sec
Default :5sec
FINS IP Address PLC IP address
Port UDP port No Default :9600
Detector Network
Address
GD-70D-ET network address
(Specification-based FINS setting value)
Node Address GD-70D-ET node address
(Specification-based FINS setting value)
Unit No. GD-70D-ET unit No.
(Specification-based FINS setting value)
PLC Network
Address
PLC network address
(Specification-based FINS setting value)
Node Address PLC node address
(Specification-based FINS setting value)
Unit No. PLC unit No.
(Specification-based FINS setting value)
Detector Write Memory
Address Writing memory address to PLC
Area Type Writing memory area from PLC
Detector Read Memory
Address Reading memory address from PLC
Area Type Reading memory area from PLC
MC IP Address PLC IP address
Port UDP port No. Default :5000
PLC Network
Address
PLC network address
( Specification-based MC setting value)
Node Address PLC node address
( Specification-based MC setting value)
Detector Write Memory
Address Beginning address for writing to PLC
Area Type Writing memory area to PLC
Detector Read Memory
Address Beginning address for reading from PLC
Area Type Reading memory area from PLC
44
4-4. Data map
4-4-1 Basic Data (Small)
Writing data map
Address Content Description
GD-70D-ET
Writing Area
GD-70D-ET
Data
0 Status
bit15: Maitenance
bit14: Test
bit13: Inhibit
bit12: Initial
bit11: Alarm / RANGE OVER
bit10: (Reserved)
bit9: Alarm: 2nd
bit8: Alarm: 1st
bit7: Fault: Sensor
bit6: Fault: communicatiom
bit5: Fault: Flow
bit4: Caution: Flow
bit2-3: Unit code (00:vol% 01:%LEL 10:ppm 11:ppb)
bit0-1: Decimal point code (00:1/1 01:1/10 10:1/100
11:1/1000)
1 Concentration value Magnification corrected integer number
Actual value is multipled decimal point code by status.
2 Counter for checking
existence
Value increased in each sending
Return to 0 at the overflow
3 Flow Unit: mL / min
4 Pyrolyzer temperature Unit: ℃ ( No pyrolyzer :0x8000)
5 IP address
(High 16 bits)
Anterior half of IP address
Ex.) 192.168.0.1: 0xC0A8
6 IP address
Low 16 bits)
Posterior half of IP address
Ex.) 192.168.0.1: 0x0001
7 Subnet mask
(High 16 bits)
Anterior half of subnet mask
Ex.) 255.225.225.0: 0xFFFF
8 Subnet mask
(Low 16 bits)
Posterior half of subnet mask
Ex.) 255.225.225.0: 0xFF00
9 Flag
bit6: Sensitivity correction (0: OFF 1:ON)
bit5: Zero tracking (0: OFF 1: ON)
bit4: Suppression type (0: Cut off 1:Slope)
bit3: Fault alarm action (0: Non-Latching 1:Latching)
bit2: Gas alarm action (0: Non-Latching 1:Latching)
bit0-1: Alarm type (0: H-HH 1: L-LL 2: L-H)
10 Full scale Magnification corrected integer number
Actual full scale is multipled decimal point code by status.
11 1st alarm point
Magnification corrected integer number
Actual 1st alarm point is multipled decimal point code by
status.
12 2nd alarm point
Magnification corrected integer number
Actual 2nd alarm point is multipled decimal point code by
status.
13 3200 portitioned
concentration value Relative value when full scale is assumed 3200
14 3200 portitioned
concentration value Relative value when full scale is assumed 3200
15 3200 portitioned
concentration value Relative value when full scale is assumed 3200
45
4-4-2 Basic Data (Large)
Writing data map
Address Content Description
GD-70D-ET
Writing Area
GD-70D-ET
Data 0~15
Concentration
Alarm status…etc
The same as Basic Data (Small)
( Refer to 4-1-1 Basic Data: Small)
16 Year / Month High byte: Year (The last 2 digits) Low byte: Month
17 Day / Hour High byte: Day Low byte: Hour
18 Minute / Second High byte: Minute Low byte: second
19 Alarm delay time Unit: 10 millisecond
20 Digit Magnification corrected integer number
Actual digit is multipled decimal point code by status.
21 Zero suppression
value
Magnification corrected integer number
Actualzero suppression value is multipled decimal point
code by status
22~27 Gas name ASCII Character string
Left-align Blanc is space (0x20)
28~34 (Reserved)
35~39 (Reserved)
Command
Data 40
Command execution
status (GD-70D-ET)
0: Normal condition
1: On processing
41 Command execution
result
Command 1 (setting alteration)
Success: bit ON Failure: bit OFF
bit12: Sensitivity correction
bit11: Date and time
bit10: Zero tracking
bit9: Zero suppression type
bit8: Zero suppression value
bit7: Alarm delay time
bit6: Fault alarm action
bit5: Gas alarm action
bit4: 2nd Alarm
bit3: 1st Alarm
bit2: Alarm type
bit1: Subnet mask
bit0: IP address
Command 2~
0: Failure
1: Success
46
Reading data map
Address Content Description
GD-70D-ET
Reading Area
GD-70D-ET
Setting
Data 0
IP address
(High 16 bits) Anterior half of IP address
1 IP address
(Low 16 bits) Posterior half of IP address
2 Subnet mask
(High 16 bits) Anterior half of subnet mask
3 Subnet mask
(Low 16 bits) Posterior half of subnet mask
4 Flag
bit3: Fault alarm action (0: Non-Latching 1: Latching)
bit2: Gas alarm action (0: Non-Latching 1: Latching)
bit0-1: Alarm type (0: H-HH 1: L-LL 2: L-H)
5 1st Alarm point
Magnification corrected integer number
Actual 1st alarm point is multipled decimal point code by
status of address 0.
6 2nd Alarm point
Magnification corrected integer number
Actual 2nd alarm point is multipled decimal point code by
status of address 0.
7 Year / Month High byte: Year (The last 2 digits) Low byte: Month
8 Day / Hour High byte: Day Low byte: Hour
9 Minute / Second High byte: Minute Low byte: second
10 Alarm delay time Unit: 10 millisecond
11 Zero suppression
value
Magnification corrected integer number
Actual zero suppression value is multipled decimal point
code by status of address 0.
12~15 (Reserved)
Command
Data 16
Command execution
status (PLC)
0: Normal condition
1: Excute processing
17 Command code
(Refer to 4-5 command)
18 Parameter
19~21 (Reserved)
47
4-4-3 Optional Data
Writing data map
Address
Basic Data
(Small)
Address
Basic Data
(Large)
Content Description
GD-70D-ET
Writing Area
GD-70D-ET
Data 16~25 42~51 TAG No.
ASCII Character string
Left-align Blanc is space (0x20)
26~35 52~61 Device name ASCII Character string
Left-align Blanc is space (0x20)
36~45 62~71 Installed location ASCII Character string
Left-align Blanc is space (0x20)
46~50 72~76 Customer code ASCII Character string
Left-align Blanc is space (0x20)
51~55 77~81 Sensor model ASCII Character string
Left-align Blanc is space (0x20)
56~65 82~91 Sensor serial No. ASCII Character string
Left-align Blanc is space (0x20)
66~67 92~93 Sensor unit type ASCII Character string
Left-align 3 characters
68~85 94~111 (Reserved)
Command
Data 86 112
Command execution
status (GD-70D-ET)
0: Normal condition
1: Complete processing
87 113 Command execution
result
Command 1 (setting alteration)
Success: bit ON Failure: bit OFF
bit3: Customer code
bit2: installed location
bit1: device name
bit0: TAG No.
Command 2~ (Reserved)
0: Failure
1: Success
Reading data map
Address
Basic Data
(Small)
Address
Basic Data
(Large)
Content Description
GD-70D-ET
Reading Area
GD-70D-ET
Setting
Data
0~9 22~31 TAG No. ASCII Character string
Left-align Blanc is space (0x20)
10~19 32~41 Device name ASCII Character string
Left-align Blanc is space (0x20)
20~29 42~51 Installed location ASCII Character string
Left-align Blanc is space (0x20)
30~34 52~56 Customer code ASCII Character string
Left-align Blanc is space (0x20)
35~49 57~71 (Reserved)
Command
Data 50 72
Command
Execution status
(PLC)
0: Normal condition
1: Excute processing
51 73 Command code (Refer to 4-5 Command )
52 74 Parameter
53~55 75~77 (Reserved)
48
4-5 Command
Write to Basic Data (Large) and GD-70D-ET setting data, command execute status (PLC),
command code, parameter of Optional Data, and then execute all sorts of functions.
4-5-1 How to issue command 1 (Setting alteration)
Check [Command execution status (PLC)] = 0 (Normal condition)
↓
[GD-70D-ET setting data] ← Set data to desirable contents (Plurally contents are settable)
[Command data] ← Set 1 (Setting alteration)
[Parameter] ← Set bit values of desirable contents which are turned on.
(Plurally bit values are settable)
↓
[Command execution status (PLC)] ← Set 1 (Execute processings)
↓
[Command execution status (GD-70D-ET)] = Check 1 (Complete processings)
↓
[Command execution status (PLC)] ← Set 0 (Normal condition)
Success to setting alteration:
[Command execution result] = Bits of desirable contents are ON.
Failure to setting alteration:
[Command execution result] = Bits of desirable contents are OFF.
CAUTION
Do not alter values of [GD-70D-ET setting data], [Command code], [Parameter] at the period
between commands are issued and processings are completed.
49
4-5-2 How to issue command 2~9 (Basic Data (Large) only)
[Command execution status (PLC)] = Check 0 (Normal condition)
↓
[GD-70D-ET seting data] ← Set data to desirable contents (Plurally contents are settable)
[Command code] ← Set 2~9
[Parameter] ← Set 0 (Unused) (Command 2~9)
↓
[Command execution status (PLC)] ← Set 1 (Execute processing)
↓
[Command execution status (GD-70D-ET)] = Check 1 (Complete processing)
↓
[Command execution status (PLC)] ← Set 0 (Normal condition)
Success to setting alteration: [Command execution result] = 1
Failure to setting alteration: [Command execution result] = 0
CAUTION
Do not alter values of [GD-70D-ET setting data], [Command code], [Parameter] at the period
between commands are issued and processings are completed.
50
4-5-3 How to issue command 10 (Set concentration value of alarm test)
(Basic Data (Large) only)
[Command execution status (PLC)] = Check 0 (Normal condition)
↓
[GD-70D-ET setting data] ← Set data to desirable contents (Plurally contents are settable)
[Command code] ← Set 10 (Set concentration values of alarm test)
[Parameter] ← Set concentration value of alarm test
↓
[Command execution status (PLC)] ← Set 1 (Execution processing)
↓
[Command execution status (GD-70D-ET)] = Check 1 (Complete processing)
↓
[Command executionstatus (PLC)] ← Set 0 (Normal condition)
Success to setting alteration: [Command execution result] = 1
Failure to setting alteration: [Command execution result] = 0
CAUTION
Do not alter values of [GD-70D-ET setting data], [Command code], [Parameter] at the period
between commands are issued and processings are completed.
51
4-5-4 Command related data to Basic data (Large)
Address Content Description
GD-70D-ET
Writing Area
40 Command Execution
Status (GD-70D-ET)
0: Normal condition
1: On processing
41 Command Execution
Result
Command 1 (Setting alteration)
Success: bit ON failure: bit OFF
bit12: Sensitivity correction
bit11: Date and time
bit10: Zero tracking
bit9: Zero suppression type
bit8: Zero suppression value
bit7: Alarm delay time
bit6: Fault alarm action
bit5: Gas alarm action
bit4: 2nd alarm point
bit3: 1st alarm point
bit2: Alarm type
bit1: Subnet mask
bit0: IP address
Command 2~
0: Failure
1: Success
Address Content Description
GD-70D-ET
Reading Area
0~15 All sorts of Setting Data
16 Command Execution
Status (PLC)
0: Normal condition
1: Execute processing
17 Command Set command code
18 Parameter Depending on command
(Refer to command code table below)
Command code table of Basic Data (Large)
Command code Content Parameter
1 Setting Alteration Setting flag
(Refer to table below)
2 Buzzer Stop Unused
3 Inhibit ON Unused
4 Inihibit OFF Unused
5 Start the Maintenance Mode Unused
6 Finish the Maintenance Mode Unused
7 Execute Zero Calibration Unused
8 Start the Alarm Test Mode Unused
9 Finish the Alarm Test Mode Unused
10 Set Concentration Value
of Alarm Test
Test concentration
value
52
Parameter (Setting flag) of command 1 (Setting alteration)
Plurally contents are alterable. (Plurally bits are turned on at the same time.)
Parameter (Bit) Content
Bit15 (Reserved)
Bit14 (Reserved)
Bit13 (Reserved)
Bit12 Sensitive correction
Bit11 Date and time
Bit10 Zero tracking
Bit9 Zero suppression type
Bit8 Zero suppression value
Bit7 Alarm delay time
Bit6 Fault alarm action
Bit5 Gas alarm action
Bit4 2nd alarm point
Bit3 1st alarm point
Bit2 Alarm type
Bit1 Subnet mask
Bit0 IP address
53
4-5-5 Command related data to Optional Data
Address
Basic
Data
(Small)
Address
Basic
Data
(Large)
Content Description
GD-70D-ET
Eriting Area
86 102
Command
Execution Status
(GD-70D-ET)
0: Normal condition
1: On processing
87 103 Command
Execution Result
Command 1 (Setting alteration)
Success: bit ON Failure: bit OFF
bit3: Customer code
bit2: Installed location
bit1: Device name
bit0: TAG No.
Command 2~ (Reserved)
0: NG
1: OK
Address
Basic
Data
(Small)
Address
Basic
Data
(Large)
Content Description
GD-70D-ET
Reading Area
0~49 22~71 All sorts of Setting
Data
50 72
Command
execution status
(PLC)
0: Normal condition
1: On processing
17 73 Command Set command code
18 74 Parameter Depending on command
(Refer to command code table below)
Command code of Optional Data
Command code Content Parameter
1 Setting Alteration Setting flag (Refer to table below)
Parameter (Setting flag) of command code 1 (Setting alteration)
Parameter (Bit) Content
Bit15 (Reserved)
Bit14 (Reserved)
Bit13 (Reserved)
Bit12 (Reserved)
Bit11 (Reserved)
Bit10 (Reserved)
Bit9 (Reserved)
Bit8 (Reserved)
Bit7 (Reserved)
Bit6 (Reserved)
Bit5 (Reserved)
Bit4 (Reserved)
Bit3 Customer code
Bit2 Installed location
Bit1 Device name
Bit0 TAG No
54
4-5-6 How to alter alarm points setting.
Set 1st alarm point to 500, 2nd alarm point to1000.
Address
[GD-70D-ET setting data (1st alarm point)] : Basic Data (Large) GD-70D-ET Reading area address 5
[Command execution status (PLC)] : Basic Data (Large) GD-70D-ET Reading area address 16
[Command code] : Basic Data (Large) GD-70D-ET Reading area address 17
[Parameter] : Basic Data (Large) GD-70D-ET Reading area address 18
[Command execution status (GD-70D-ET)] : Basic Data (Large) GD-70D-ET Writing area address 40
[Command execution result] : Basic Data (Large) GD-70D-ET Writing area address 41
[Command execution status (PLC)] = Check 0 (Normal condition).
↓
[GD-70D-ET setting data] ← 500
[Command code] ← Set 1 (Setting alteration)
[Parameter] ← 0x0018
Setting flag: Values that are turned on 1st alarm point (bit3) and 2nd alarm point (bit4)
↓
[Command execution status (PLC)] ← Set 1 (Complete processing)
↓
[Command execution status (GD-70D-ET)] = Check 1 (Complete processing)
↓
[Command execution status (PLC)] ← Set 0 (Normal condition)
Success to setting alteration: [Command execution result] = 0018
1st alarm point (bit3) and 2nd alarm point (bit4) are ON.
Failure to setting alteration: [Command execution result] = 0000
1st alarm point (bit3) and 2nd alarm point (bit4) are OFF.
55
4-5-7 How to operate inhibit
Address
[Command execution status (PLC)] : Basic Data (Large) GD-70D-ET Reading area address 16
[Command code] : Basic Data (Large) GD-70D-ET Reading area address 17
[Parameter] : Basic Data (Large) GD-70D-ET Reading area address 18
[Command execution status (GD-70D-ET)] : Basic Data (Large) GD-70D-ET Writing area address 40
[Command execution result] : Basic Data (Large) GD-70D-ET Writing area address 41
[Command execution status (PLC)] = Check 0 (Normal condition)
↓
[Command code] ← Set 3 (Inhibit on)
(Inhibit off: 4)
[Parameter] ← 0 (Parameter unsed)
↓
[Command execution status (PLC)] ← Set 1 (execute processing)
↓
[Command execution status (GD-70D-ET)] = Check 1 (Complete processing)
↓
[Command execution status (PLC)] ← Set 0 (Normal condition)
Success to setting alteration: [Command execution result] = 1
Failure to setting alteration: [Command execution result] = 0