Gas Insulated Substation Presentation

13
1 -1- IEEE/PES Substation Committee - GIS Subcommittee T&D Chicago GIS IEEE/PES Substation Committee - GIS Subcommittee Substations Committee GIS Subcommittee K2 Module Gas Insulated Substation (GIS) Basics IEEE -2- IEEE/PES Substation Committee - GIS Subcommittee T&D Chicago GIS IEEE/PES Substation Committee - GIS Subcommittee Contents GIS Basics A Introduction to GIS C Design Features of GIS

Transcript of Gas Insulated Substation Presentation

Page 1: Gas Insulated Substation Presentation

1

- 1 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Substations CommitteeGIS Subcommittee K2

ModuleGas Insulated Substation (GIS)

Basics

IEEE

- 2 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

ContentsGIS Basics

A Introduction to GISC Design Features of GIS

Page 2: Gas Insulated Substation Presentation

2

- 3 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

ContentsGIS Basics

A Introduction to GIS

- 4 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Introduction to GISTypical Air Insulated Substation 345/230/115kV

Page 3: Gas Insulated Substation Presentation

3

- 5 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Introduction to GISTypical Gas Insulated Substation 345/115kV

- 6 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Introduction to GISCable Feeder Unit

Page 4: Gas Insulated Substation Presentation

4

- 7 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Introduction to GISDimension ComparisonGIS Technology

SF6 used as the insulating media

Reduced clearances- 345 kV AIS 4.6 m (15 feet)- 345 kV GIS 380 mm (15 inches)

- 8 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Introduction to GISView into Bus Bar: Conductor/Enclosure Dimension

Page 5: Gas Insulated Substation Presentation

5

- 9 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Busbar DisconnectorCurrent TransformerCircuit Breaker

CableConnection

DisconnectorCurrent TransformerCircuit Breaker

Introduction to GISClassic Single Phase Enclosure of GIS

- 10 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Introduction to GISMidway Sunset Sunoco Cogen 242 kV GIS

4

242 kV

2000 A

40 kA

No. of breakers

Rated voltage

Rated current

Rated short-circuit current

1988Supply year

Page 6: Gas Insulated Substation Presentation

6

- 11 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Introduction to GISClassic Three Phase Enclosure of 72.5 to 170 kV GIS

- 12 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Introduction to GISAdvanced Three Phase GIS 72.5 to 145 kV

Page 7: Gas Insulated Substation Presentation

7

- 13 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Introduction to GISAdvanced Three Phase GIS 72.5 to 145 kV

- 14 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

ContentsGIS Basics

B Design Features of GIS

Page 8: Gas Insulated Substation Presentation

8

- 15 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Design Features

GIS technology: compact, low-life cycle cost andmodular for indoor and outdoor applications

Modular design, factory pre-assembled and tested units

Space requirement less than 20 % of comparable AIS

Safety (enclosed energized components)

Continous monitoring of SF6 densitity

Sealed for operating life > 50 years

Major inspection: not before 25 years 1)

1) Is influenced by the operation duties

- 16 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Design Features

GIS technology: compact, low-life cycle cost andmodular for indoor and outdoor applications

Corrosion-resistant

Low fault-probability/high availability

Protected against aggressive environmental conditions

Seismic resistant

Low EMF and susceptibility to EMC

Page 9: Gas Insulated Substation Presentation

9

- 17 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Design FeaturesSpace Savings

Space Reductionappr. 70 %

Previous

Afterwards

Retrofit of an existing AIS Substation byCompact Substation

145 kV/31,5 kA 4000 A

- 18 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Design FeaturesModular Structure (schematic)

Page 10: Gas Insulated Substation Presentation

10

- 19 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Design FeaturesModular Structure (devices)

- 20 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Design FeaturesGIS Pressure Systems

Closed pressure systems:

The closed pressure system uses isolated apparatus compartments with o-ring sealed bolted flanges.

The tightness characteristic of a closed pressure system stated by the manufacturer shall be consistent with a minimum maintenance and inspection philosophy.

The leakage rate from any single compartment of GIS to atmosphere and between compartments shall not exceed 0.5 % per year for the service life of the equipment.*

Practical experiences to the today’s design of GIS show as low as 0.2 % per year.

* IEC 62271-203 Gas Insulated Switchgear for voltages above 52 kV

Page 11: Gas Insulated Substation Presentation

11

- 21 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Sealant

O-Ring

Insulating Spacer

Air Side

SF6 Gas Side

Flange

■ O-RING

■ LIQUID SILICONE SEALANT

GAS SEALING

PROTECTION AGAINSTGISEnclosure

� WATER INGRESS FROM AIR SIDE

� RUST OF FLANGE

Design FeaturesExample for Static Double Sealing System

- 22 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Design FeaturesExample for Corrosion Protection

– – – Tectyl 506 coating for external area A- - - - Trost Multifunction Oil coating for inner area B

Grease bolts with “Molykote Longterm 2”before inserting

gap protection by seal coating

Page 12: Gas Insulated Substation Presentation

12

- 23 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Design FeaturesExample for Dynamic Sealing System

Coupling of operating rodSF6 gas compartmentSF6 gas compartment

Coupling of operating rod

Shaft SF6 seal Operating lever

- 24 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Design FeaturesTypical Grounding / Earthing Arrangement of GIS

Earthing of the buildingConnection to GIS bayOutside the buildingEarthing in the floor/ceilingConnection earthing of floor/ceiling to building

Page 13: Gas Insulated Substation Presentation

13

- 25 -

IEEE/PES Substation Committee - GIS Subcommittee

T&D Chicago GIS

IEEE/PES Substation Committee - GIS Subcommittee

Thank you for your attention.