GAS INSULATED SUB-STATION
RONAL PARMAR140080707003
CONTENTS Typical bay overview Enclosures Conductor SF6 sealing Insulators SF6 accessories Circuit Breaker Disconnector ( Isolator ) Earthing ( grounding) switch Current transformer Voltage transformer Surge arrester GAS-insulated line / bus
TYPICAL BAY OVERVIEW
ENCLOSURES
Aluminium alloy◦ No corrosion◦ Low resistance to
return current◦ No eddy current
losses◦ Lower weight◦ Industrial casting ,
except straight extruded / welded tubes
CONDUCTORS Aluminium alloy material ,most often
For light weightFor mechanical propertiesSilver-plating for sliding contact
SF6 SEALINGSealing design recruitments
Tightness (<0.5% per year)Lifetime ( 50 year)Avoid under-gasket corrosion
Gasket material is essentialNo electronic corrosionLifetimeTight across the temperature rangeTight dynamic sealing
Sealing manufacture requires utmost carePrevent leakages
INSULATORS Insulators
Gas barriersSupports insulators
3-ph gas barrier
Support insulatorGas barrier
SF6 ACCESSORIES Each GIS compartment shall be
associated with one set of accessoriesDensity sensor
oPresser switch oAnalogue / digital sensor oSensors should be same temp as
enclosures temp. SF6 valve
oValve can be no return /tapoSection shall be high enough to
enables appropriate vacuum (< 1 mbar) within a reasonable time
o Moisture absorber = molecular sieveAbsorption surface: 20 to 800 sq.m/gAbsorption ratio: 10~20%, by mass
o Pressure reliefPressure does not go beyond the enclosureheat-resistant deflector shall protect person in
case of internal flashover
SF6 ACCESSORIES
CIRCUIT-BREAKER
Main sub-station itemgrading capacitors in case of several breaks per
poleTested at 10,000 close/open cycles
CIRCUIT-BREAKER DRIVEDifferent types
Spring drive with no driving fluid
Hydraulic drivegas storageSpring storage
Pneumatic drivesOut-datedNeed of water draining
No move when CB is not operated, while hydraulic and pneumatic mechanisms daily require several pump starts for pressure topping up
Stable timing, insensitiveness to temperature and pressure, ideal for POW(point of wave) switching.
CIRCUIT-BREAKER DRIVE
DISCONNECTOR ( ISOLATOR ) Does not break any other current than
capacitive current of short length of GIS: <0.1~0.5ATransfer current of double BB substation: 1600A @ 10-40V
Can be associated with a grounding switch
EARTHING (GROUNDING) SWITCH
Insulation Grounding switch is normally
connected the ground Can be insulated to tests
o Contact resistanceo CB timingo CT primary injection
Safety issueo Never disconnect a GS
from ground when 0 voltage is not ascertained
Current transformer
Rating Power Accuracy Safety factor Saturation
Low ratios Difficult to achieve with a single primary turn
Overvoltage protection Specific design to implement inside GIS
VOLTAGE TRANSFORMER
Ratings Powero Quite often over-specified
AccuracyFerro-resonance
Mainly in case of CB grading capacitors
Can be avoided using a special inductance
SURGE ARRESTEROverhead line connections
Generally air-insulated Sometimes gas-insulated
Cable connection / direct transformer connection
GAS-INSULATED LINE/BUS
FURTHER PRESENTATION WORK
Construction of low & medium voltage GIS sub-stationConstruction of high voltage GIS sub-stationMaintenance of GIS sub-stationGIS approach in the GRID Visit of 400/220KV GIS substation located at DASTAN
, bardoli .