A817129.CDR Fig. 1 Fig. 2 INSTALLATION INSTRUCTIONS G13/GL13 LUMINAIRE TO ROUNDPOLE IMPORTANT: WARNING: Read all instructions before performing any work. Be sure prior to installing luminaires. Fixture must be grounded in accordance with appropriate codes. Failure to do so may result in serious injury. all power is off NOTE: For installation other than a roundpole, follow the instructions provided with the adaptor kit. 1. Place luminaire with lens facing up on a non-scratching surface. 2. Unlatch door and slowly open until stopped by safety cable. Remove and retain wing nut that secures safety cable. Disengage safety cable from threaded stud and pull free from ballast clamp. Open door further until hinge clamp lock is accessible. Rotate hinge clamp lock to free hinge clamp(Fig.1). Carefully rotate door toward the closed position until hinge disengages. 3. Place luminaire mounting surface against round pole so that the mounting holes align. With an assistant holding the luminaire, insert the bolster plate into the inside of the pole. Secure the luminaire using the 5/16” bolts and lock washers supplied (Fig.2). Tighten bolts to 15ft-lbs. Gardco Lighting 1611 Clovis Barker Road, San Marcos, TX 78666 Gardco and Emco are Philips group brands A817129 6/6/01 - REV D 1 OF 2

Transcript of G13/GL13 LUMINAIRE TO ROUND UTILITY POLE · as desired and re-install. Fig. I Fig. 2 . GARDCO by...

Page 1: G13/GL13 LUMINAIRE TO ROUND UTILITY POLE · as desired and re-install. Fig. I Fig. 2 . GARDCO by @ignify 5. 6. For LED units: Remove four #8 screws and matte surrounding LED board.

A817129.CDR

Fig. 1

Fig. 2

INSTALLATION INSTRUCTIONSG13/GL13 LUMINAIRE TO ROUNDPOLE

IMPORTANT:

WARNING:

Read all instructions before performing any work. Be sure prior toinstalling luminaires.

Fixture must be grounded in accordance with appropriate codes. Failure to do so mayresult in serious injury.

all power is off

NOTE: For installation other than a roundpole, follow theinstructions provided with the adaptor kit.

1. Place luminaire with lens facing upon a non-scratching surface.

2. Unlatch door and slowly open untilstopped by safety cable. Removeand retain wing nut that securessafety cable. Disengage safetycable from threaded stud andpull free from ballast clamp.Open door further until hingeclamp lock is accessible. Rotatehinge clamp lock to free hingeclamp(Fig.1). Carefully rotatedoor toward the closed positionuntil hinge disengages.

3. Place luminaire mounting surfaceagainst round pole so that themounting holes align. With anassistant holding the luminaire,insert the bolster plate into theinside of the pole. Secure theluminaire using the 5/16” boltsand lock washers supplied(Fig.2). Tighten bolts to 15ft-lbs.

Gardco Lighting1611 Clovis Barker Road, San Marcos, TX 78666Gardco and Emco are Philips group brands

A8171296/6/01 - REV D

1 OF 2

Page 2: G13/GL13 LUMINAIRE TO ROUND UTILITY POLE · as desired and re-install. Fig. I Fig. 2 . GARDCO by @ignify 5. 6. For LED units: Remove four #8 screws and matte surrounding LED board.

Fig. 3

A817129.CDR

INSTALLATION INSTRUCTIONSG13/GL13 LUMINAIRE TO ROUNDPOLE

4. Feed luminaire wires into pole. Make electrical connections and secure supply wires using the wire tieanchor mounted to the bolster plate(Fig.3). Where more than one luminaire is mounted to the pole,make electrical connections after all luminaires are mounted.

5. Install pole top cap.

6. Aiming arrow on reflector must match aiming direction on site plan. If reflector rotation is required, see thefollowing instructions:For HID units: Loosen the four 8-32 phillips pan head screws holding the reflector to the housing. Loosenthe two thumb screws and slide latches to disengage. Remove reflector, reposition as desired and re-install.For LED units: Remove four #8 screws and matte surrounding LED board. Remove four #8 screws holdingheatsink/light engine assembly and rotate as desired. Secure heatsink/light engine assembly with screwspreviously removed. Reinstall matte with four screws previously removed.

7. Install lamp (where applicable). Make sure the lamp and wattage are as indicated in the productidentification label on the reflector. Clear lamp required for optimum photometric performance.

8. Re-install door by engaging the hinge end with the door in the almost closed position. Swing door openand lock the hinge clamp by returning the hinge clamp lock to its original position. Re-install safety cablethrough ballast clamp and onto stud. Re-install wingnut and tighten.

9. Close door making sure latch is fully engaged.

Gardco Lighting1611 Clovis Barker Road, San Marcos, TX 78666Gardco and Emco are Philips group brands

A8171296/6/01 - REV D