g 2 t Installation Manual

27
POWER GAS BURNERS Certified for Natural & LP Gases Installation, Operation, Maintenance Manual G2T Series WARNING If the information in these instructions are not followed exactly a fire or explosion may result, causing property damage, personal injury or death. Code compliance is the sole responsibility of the installer. If You Smell Gas! Do not try to light any appliance. Do not touch any electrical switch. Do not use any phone in your building. Immediately call your gas supplier from a neighbor's phone. If you cannot reach your gas supplier call the fire department. CAUTION Do not store gasoline flammable liquids or vapors in the vicinity of this or any other fuel burning appliance. Installation and service must be performed by a qualified installer, service agency or the gas supplier Installer Affix this manual adjacent to the burner! Inform and demonstrate the correct operation and maintenance of the burner.

description

manual

Transcript of g 2 t Installation Manual

  • POWER GAS BURNERSCertified for Natural & LP Gases

    Installation, Operation,Maintenance Manual

    G2T Series

    WARNINGIf the information in these instructions are notfollowed exactly a fire or explosion mayresult, causing property damage, personalinjury or death.Code compliance is the sole responsibility ofthe installer.

    If You Smell Gas!Do not try to light any appliance.Do not touch any electrical switch.Do not use any phone in yourbuilding.Immediately call your gas supplierfrom a neighbor's phone.If you cannot reach your gas suppliercall the fire department.

    CAUTION

    Do not store gasoline flammable liquids orvapors in the vicinity of this or any other fuelburning appliance.

    Installation and service must be performed by aqualified installer, service agency or the gassupplier

    Installer Affix this manual adjacent to the burner!Inform and demonstrate the correct operation and maintenance of the burner.

  • TABLE OF CONTENTS

    ADAMS POWER GAS CONVERSION BURNER, G-2 SERIES 1SPECIFICATIONS 2STANDARD EQUIPMENT 2INSTALLATION

    I VENTILATION 3II PREPARATION OF THE HEATING PLANT 3,4,5III FLUE PIPE, DRAFT DIVERTER/DOUBLE ACTING BAROMETRIC DAMPER 5,6IV CHIMNEYS 6,7,8V ELECTRICAL 7,9,25VI GAS PIPING 9,10

    PARTS DIAGRAM 11G-2 SERIES PARTS LIST. 12

    VII GAS ORIFICE SIZING 13,14VIII OIRIFICE CHANGE OUT PROCEDURES 14IX INITIAL START UP AND ADJUSTMENT 14,15X BURNER CONTROL SEQUENCE OF OPERATION 15,16XI THE GAS VALVE MOUNTING PLATE ASSEMBLY : 16XII THE BLOWER MOTOR ASSEMBLY 16XIII ELECTRODE SETTING SPECIFICATIONS 17XIV MAINTENANCE INSTRUCTIONS 17

    BURNER IDENTIFICATION SYSTEM 18LIGHTING AND SHUTDOWN INSTRUCTIONS 18,19G-2 TROUBLE SHOOTING GUIDE 19

    MOTOR DOES NOT START 20CONTROL SYSTEM WITH PREPRUGE TIMER

    IGNITION ARC ESTABLISHED - NO FLAME 21NO IGNITION ARC ESTABLISHED 21NO IGNITION - NO GAS VALVE OPERATION 22LOSES FLAME DURING CYCLE - CONTROL LOCKOUT ON SAFETY 22BURNER CYCLES ERRATICALLY 23

    HOW TO OBTAIN WARRANTY 23.BACK PAGI

    ADAMS MANUFACTURING COMPANY9790 MIDWEST AVENUE - CLEVELAND, OHIO 44125 PHONE (216) 587-6801

  • SERIES Power Gas Conversion Burners

    itMODELS G2T AND G2SD

    The Adams Model G2 direct spark ignitionconversion burner is adjustable to most heatingappliances that have a suitable combustionchamber. Do not use in sectional type heatingappliances or on revertible (diving) flue designapplications.

    This design series of gas conversion burners arecertified by the CTL Test Laboratoriesthe ANS Z21.17/CSA 2.7-1998 Gas ConversionBurner Standards.

    The installation must conform with local codes or,in the absence of local codes, with the Standard forthe Installation of Domestic Gas ConversionBurners, ANSI Z21.8, the National Fuel Gas Code,ANSI Z223.1, or the CAN/CGA-B149, InstallationCodes.

    If an external electrical source is utilized, theconversion burner, when installed must beelectrically grounded in accordance with localcodes or, in the absence of local codes, with theNational Electrical Code, ANSI/NFPA 70, or theCanadian Electrical Code, CSA C22.1.

    These publications are available from the CanadianStandards Association or from the NationalFireprotection Association.

    ^WARNINGCARBON MONOXIDEPOISONING HAZARD

    CARBON MONOXIDE IS A COLORLESS,ODORLESS GAS THAT CAN KILL. FOLLOWTHESE RULES TO CONTROL CARBONMONOXIDE.

    Do not use this burner in an unvented, enclosedarea. Carbon monoxide may accumulate.

    Do not adjust the pressure regulator. Highpressures produce carbon monoxide.

    Check flue gases for carbon monoxide. Thischeck requires specialized equipment.

    Allow only qualified burner service persons toadjust the burner. Special instruments andtraining are required.

    ^WARNINGOVERHEATING HAZARD

    SHOULD OVERHEATING OCCUR:(1) Shut off the manual gas control to the

    appliance.(2) Do not shut off the control switch to the pump

    or blower.

  • SPECIFICATIONS G-2 SERIES

    MODELMax. InputBTU/Hr.

    Win. InputBTU/Hr.

    . Burner Head Dia.over screws

    Inlet Press. Nat.

    LPG

    Standard Voltage

    Ignition System

    Flame Safety

    G2T

    240,000

    50,000

    3-7/16" (8.73cm)5.0-13"W.C.

    1.24- 3.23 kPa.11.0-13"W.C.2.74 -3.23 kPa.

    120V 60 HZ

    Direct SparkIgnition

    Electronic

    G2SD

    255,000

    70,000

    3-7/16" (8.73cm)5.0-13-W.C

    1.24- 3.23 kPa.11.0-13-W.C.2.74- 3.23 kPa.

    120V 60 HZ

    Direct SparkIgnition

    Electronic

    STANDARD EQUIPMENT

    Precision balanced centrifugal blowerMotor with integral end switch to prove

    rotation.Stainless steel combustion head(s) andflame shield.Low voltage automatic gas valve.Low voltage motor relay and transformerfor 2 wire control system.Adjustable pedestal or air tube flangeUsable air tube lengths 5.24", 8" and 11".

    (13.3cm, 20.32cm & 27.9cm)

  • I. VENTILATION

    The area in which the heating system is locatedmust have an adequate supply of air for bothcombustion and draft diverter dilution. Openbasements and below grade utility rooms or crawlspaces without storm windows or tight doors willgenerally permit adequate air infiltration.

    if the heating system is located in a separate roomwith a tight door, ventilation must be provided to anopen area within the building or to the outside. Ifthe openings are within the building two open grillsmust be installed, one near the floor and one closeto the ceiling. The open (non-adjustable) grillsmust have a free area of at least one square inch(6.45cm) per 1,000 BTU of burner input.If the building is of unusually tight construction orhas a large exhaust fan installed, on a basement,crawl space or slab construction home, provisionsmust be made for an outside air supply that isducted into the furnace room. It must have apermanent (non-adjustable) opening of at least onesquare inch (6.45cm) of free area per 1,000 BTUinput. Consult the National Fuel Gas Code latestedition, or the CAN/CGA-B149 Installation Codes,for more detailed information.

    With direct spark ignition system the burnerperforms well under slight or momentary back draftconditions. However, it is not intended foroperation under sustained reverse draft conditions.This condition is fairly common in buildings withlarge ventilating fans. The fans can create a sub-atmospheric pressure in the building causing adown draft in the chimney. This will causehazardous flue gas products to be drawn into thebuilding from the draft diverter. The conditionsmust be corrected promptly.

    II. PREPARATION OF THE HEATINGAPPLIANCE

    The heating appliance must be in good repairand have adequate capacity to heat thestructure.

    Keep all materials, combustible or otherwise, atleast two feet (.61m) from the heating appliance.

    Thoroughly clean the heat exchanger andinspect for cracks or other defects - the installermust determine if the appliance is safe toupgrade.

    The combustion chamber must be free fromdeterioration and adequately sized.

    Stainless steel chambers must be lined withceramic fiber material to prevent deterioration.

    Coal Fired Units

    To convert an appliance that was coal fired, thefollowing consideration need to be observed:

    Select feed door or ash-pit door for burnermounting.

    Ash-pit: Remove grates and install combustionchamber.

    Feed Door: Fill bottom with suitable material(vertniculite, etc.), secure door.

    Warm Air Furnaces

    If combustion chamber upgrade is necessary,do not reduce the original height or outletconfiguration.

    Boilers, Cast Iron & Steel, Steam or Hot Water

    Inspect for leaks and repair any that are found.Check the ceramic or fire brick combustionchambers. Replace if not in good condition.NOTE - Do not remove the chamber from a drybase boiler. Clean the gauge glass on steamboilers so that all safety devices and controls areoperating according to the manufacturer'sspecifications.

    See Table 1 and figure 1 for set-ups.

  • TABLE 1- RECOMMENDED MINIMUM INSIDE DIMENSIONS OF REFRACTORY COMBUSTION CHAMBERS

    InputBTU/Hr.

    ' 50,000

    70,000

    90,000

    110,000

    140,000

    165,000

    180,000

    210,000

    240,000

    270,000

    300,000

    340,000

    Length(L)

    In. cm

    7 17.B

    8 20.3

    8 20.3

    9 22.9

    10 25.4

    11 27.9

    11 27.9

    12 30.5

    14 35.6

    15 38.1

    16 40.6

    18 45.7

    Width(W)

    in. cm

    6' 19.2

    7 17.8

    7 17.8

    8 20.3

    9 22.9

    10 25.4

    10 . 25.4

    11 27.9

    11 27.9

    12 30.5

    12 30.5

    13 33.0

    Dimension(C)

    in. cm

    3.5 8.90

    4.0 10.2

    4.5 11.4

    4.5 11.4

    5.0 12.7

    5.0 12.7

    5.0 12.7

    5.5 14.0

    5.5 14.0

    5.5 14.0

    6.0 15.2

    6.0 15.2

    Suggested Height(H)

    in. cm

    7 17.8

    8 20.3

    9 22.9

    9 22.9

    10 25.4

    10 25.4

    10 254

    11 27.9

    11 27.9

    11 27.9

    12 30.5

    12 30.5

    Mln. Dia.Vertical Cyl.in. cm

    7 17.8

    8 20.3

    8 20.3

    9 22.9

    10 25.4

    11 27.9

    11 27.9

    12 30.5

    13 33.0

    14 35.6

    15 38.1

    17 43.2See Figure 1 for chamber sectional view and burner head setback note.

    Figure 1

    OPTIONAL TYPE DUALACTION DRAFT CONTROLCAN BE USED ON ANY

    APPLIANCE

    SEAL DOORSWITH FURNACE

    CEMENT

    "II I/2"(8UHNER HEAD MUST NOT(1.3cm) -EXTEND INTO CHAMBER)

    (HOT WATER or STEAM BOILER)WET BASE BOILER

    l/Z" ( BURNER HEAD MUST NOT(1.3cm) EXTEND INTO CHAMBER )

    (HOT WATER or STEAM BOILER)DRY BASE BOILER

  • Figure 1 continued

    CERAMIC FIBER CHAMBER

    SEAL AROUND FLUE PIPEWITH FURNACE CEMENT

    (1247-C) 2300" INSULATING BRCK

    (BURNER HEAD MUST NOT {&HST "*"EXTEND INTO CHAMBER) CHAMBER'

    FORCED AIR FURNACE HORIZONTAL FURNACE

    III. FLUE PIPE, DRAFT DIVERTER/ DOUBLEACTING BAROMETRIC DAMPER

    Method 1 - Reduction of flue pipe size.

    Select the proper size of galvanized flue pipe anddraft diverter from the chart.

    Burner InputBTU/Hr.

    Up to 120,000120,00010175,000175,000 to 250,000250,000 to 325,000

    Draft Diverter &Flue Pipe Dia.

    5" (12.7cm)6" (15.2cm)7" (17.8cm)8" (20.3cm)

    NOTE - If the flue pipe length exceeds 10' (3.04m)or contains more than two elbows, use the nextsize larger flue pipe and draft diverter.

    NOTE - Any reduction in the flue pipe diametermust be made at healing appliance flue outlet byuse of a fixed collar reducer. Flue pipe must be 24aa. or heavier steel.

    NOTE - Where local codes permit, install a doubleacting barometric damper, rather than a draftdiverter. Less heated air is lost up the chimneywith a barometric damper than with a draft diverter.

    WARNING: SPILL SWITCH

    A device which will automatically shut off gas to theburner in the event of sustained backdraft isrequired. It shall be of the listed manual reset typeand installed and adjusted by a qualified servicetechnician in accordance with the manufacturer'sinstructions.

    Method 2 - Same diameter pipe as the applianceflue collar and a neutral pressure adjuster. Ifdiameter of the flue pipe is greater than thediameters shown in Method 1 a neutral pressurepoint adjuster shall be installed between the fluecollar of the appliance and the relief opening of thedraft diverter. It shall be constructed so that it ispermanently locked in the adjusted position andcannot be changed accidently in a manner that willinterfere with the normal operation of the burner.5

  • Raure 2 illustrates a suggested method forconstructing this device. The neutral pressurepoint adjuster shall then be left in the fully openposition until after the burner rating has beenestablished.Figure 2

    Suggested form ofneutral pressure pointadjuster. Insert in sawslot in flue pipe.

    When adjustment Iscompleted scribe lineon adjuster so it can berelocated.

    Remove adjuster, trimoff excess, slitremainder vertically.Bend segments inalternate directions.

    Replace in flue pipe,recheck adjustments toascertain unchangedconditions. Fastenadjuster in place withsheet metal screws.

    Scribe linearoundflue pipe.

    ^Trim off excess stock.

    - Scribe lines.

    No manually adjusted flue pipe damper shall be in-stalled on any Gas Conversion Installation. Thehorizontal run of flue pipe shall be pitched upward1/4" (.64cm) per foot or more. Number of elbowsmust be kept to a minimum to avoid excessiveresistance to flue gas flow. Secure all joints withsheet metal screws to avoid sagging or dis-placement. The flue pipe must be spaced at least6" (14.2cm) from combustible materials, 12"(30.5cm) if uninsulated. Flue pipe must be firmlycemented into the chimney opening. It must notextend beyond the inner wall. Where two or moreappliances use the same chimney, be sure not toenter the chimney with both flues at the same level.Under no circumstances should the flue pipe beconnected to the flue of any open fireplace. A draftDiverter must be CSA Certified (or one approvedby the local gas company) and installed in the fluepipe. The draft diverler should be the same size asthe flue pipe and located higher than the highestpart of the heating appliance.

    Vertical draft diverters should have two flue pipediameters between the skirt and any surface underit. This distance may be reduced to one diameteron the horizontal or horizontal to vertical diverters.

    Where the flue pipe passes through a combustiblepartition a ventilated thimble must be used. Thedraft diverter must be located in the same room asthe heating appliance.

    On forced warm air furnaces where the flue outletis located on the suction side if the circulating airblower, make certain the flue pipe connection isfully sealed to prevent flue products from beingdrawn into the circulating air.

    IV. CHIMNEYS

    The chimney height is determined by the buildingroof line and surrounding trees and buildings. Itshould be at least two feet (5.1cm) higher than theroof ridge with no obstructions from adjacent treesand buildings. When two flues enter the samechimney, it is recommended that the higher BTUinput appliance flue enter at a lower point.

  • The internal construction of the chimney should becorrosion resistant tile, stainless steel or someother material that will withstand flue gas products.If the chimney is unlined, consult the local gascompany for their recommendations. Refer tofigure 4 on page 8 for chimney instructions.

    Many prefabricated chimneys on either slabconstruction or basement homes, terminate nearthe ceiling level. During rainstorms it is commonfor water to run down the heating appliance fluepipe. Many warm air heating appliances have aflue outlet directly above the burner. There isalways a possibility that the water from the fluepipe will drain out upon the burner and its controls.This condition must be corrected by installing a capor rain shield on top of the chimney.

    TYPICAL CHIMNEY CONDITIONS APT TORESULT IN BACK-DRAFTS

    Figure 3

    WIND

    MINIMUMCLEARANCE 2 FT. (5cm)

    L-MIN. 3 FT.'- (7.6cm)

    WIND

    ii MINIMUM'. (5cm)

    REGIONOF HIGH jPRESSURE-^ j

    1

    DOWN-DRAFT

    -BECAUSE OFPRESSUREDIFFERENCE

    V. ELECTRICAL

    All wiring should conform to the National ElectricalCode ANSI/NFPA 70 or, the Canadian ElectricalCode CSA C22.1, or the legally authorized code inyour area. Use multiple conductor wiring notlighter than 14 gauge for line voltage wiring. Theconversion burner must be grounded. A groundterminal is provided in the 4 x 4 (10.2cm x 10.2cm)field wiring box, maximum amperage draw 5.7amperes. See figure 5 on page 9 for wiringdiagram.

    If an external electrical source is utilized, theconversion burner, when installed, must beelectrically grounded in accordance with localcodes or, in the absence of local codes, with theNational Electrical Code, ANSI/NFPA 70, or theCanadian Electrical code, CSA C22.1.

    CAUTION: Label all wires prior to disconnectionwhen servicing controls. Wiring errors can causeimproper and dangerous operation.Verify proper operation after servicing.

    Each burner has its own 30VA, 24 volt controltransformer. Under no circumstances should anyother electrical equipment be operated from thistransformer.

    Locate the thermostat where it will sense thenatural air circulation within the building. Do notplace it in a location where it will be subjected tocold drafts from doors or windows or where it cansense the warm air from registers or radiators. It isnot recommended that a thermostat be installed onan outside wall, in front of a fireplace or at the baseof an open stairwell.

    In addition to the thermostat each installation mustinclude an operating and/or high limit control asshown in the wiring diagram

    NOTE: When the thermostat wires terminate onthe G2 primary control box'T1 terminals, the heatanticipator setting for the G2 burners is determinedby adding the primary control current 1o the gasvalve current. The result is the anticipator setting.(Example: .2 + .6 = .8 amps.)

  • Figure 4

    COMMON CHIMNEY TROUBLES AND THEIR CORRECTIONS

    Troubta

    Top of rfinwvr toww

    Chmney op or venAtor.

    CWWrcBw.**

    Dbrturion ii difnwy.

    Joitl projecting into

    Break ft cttmey hng

    Cokctim of not itnarrow JpK in flueCapering.

    Offset

    Two or more openingsinto same chimney.

    Loon-sated pipe influ. opening

    Smoke pipe e (tendskMcHWT.

    Fa*jre to attend tfwteic* of fk* parttion down lo the Roar.

    loowftel dearxxil*x

    Severs down draftcondition.

    Examination

    OteetviSm

    Obmlon.

    ObKmlion.

    Can bt tart or IgMnd imw tiflectingandtiam in (hmney.UwtrinB llghlonuteraon coni

    Smoke HsUaH imudge

    gpering. mktling forsmoke escape.

    Lower Kghton

    Lower igU onertenaol

    found br fBpecoon

    Smoke lest

    Mwuementolpiiefrom wrtfin or observg-tion of pipe by means of> lowered earn.

    By inspection orsmoke left

    Smoke Ut

    By drift metertill

    Conetlanoi

    blend dinner (tuttl otiecu wrta feet

    DemoK.

    Make opong et hrget nsdf of cfirnney.

    Use weigM B bneknidnblgt

    Musi be henrfed tf erampeM brick

    Musi be fanned by ecnmpeM brickconextor.

    Qnn out with wtijtited

    gram on end of tie

    Change b might Or to

    The least important

    using some othercfamnerht.

    Leaks ihoukf beeimraad bf cementinga pipe openrgj.Lengti of pioe must bereduced fa eSow end ofpit* to be flush withradedSe.

    EAndpnioon tofloor level

    dose el kaki m*cement

    fnstell e Briderttype vent up.

  • If the thermostat wires are not terminated on theburner box "T" terminals, and these terminals areJUMPERED, you must then determine what thecontrolling device at the point where the thermostatwires terminate. Typically, this information can befound on the body or cover of the controllingdevice.

    When the current draw cannot be determinedaccurately by the above method, measure thecurrent with an ampere meter using the 1 AMPscale. Connect the meter leads in series with oneof the thermostat-leads for the accurate reading.

    Steam and vapor systems must also be protectedwith a low water cutoff to prevent firing a dry boiler.

    The usual temperature and pressure settings forheating appliances are shown below.

    Gravity Hot Water 140 - 212 F (59 - 99C)Forced Hot Water 140 - 240 F (59 - 114C)Gravity Warm Air 250 F (120 C)Forced Warm Air 200 F (92C) limit, blower

    "on" 115(46C), blower "off' 100F (37C)'Steam "off13 lbs.(1.3kg), "on" 1

    lb.(.44kg) "differential" 2 lbs.(,87kg)Vapor "off" 4 oz.(12.4kg), "on" 2 oz.

    (62gr) "differential" 2 oz.(62gr)MOTE: Each burner installation "MUST1 have asafety limit wired in series with the burner.

    MOTE: Should overheating of any appliance occur:(1) shut off the manual gas control to theappliance, (2) DO NOT shut off the control switchto the pump or blower.

    Figure 5 & 5A

    'Unless otherwise noted: If any of the original wireas supplied with the conversion burner must bereplaced, it must be replaced with type 105 C(600V)AWM wire or its equivalent.

    VI. GAS PIPING

    It is recommended that a separate gas line be runfrom the meter to the burner. Size the pipe inaccordance with the following chart:

    STEEL PIPE SIZE FOR NATURAL GASBurner

    Firing RateBTU/Hr.

    50,000

    100,000

    150,000

    200,000

    250,000

    300,000

    350,000

    400,000

    Feet (cm) of pipe from Meter to Burner

    10(3m).5

    (1.3cm).75

    (1.9cm)75

    (1.9cm).75

    (1.9cm)1

    (2.5cm)1

    (2,5cm)1

    (2.5cm)1

    (2.5cm)

    20(6m)

    .5(1.3cm)

    .75(1 .9cm)

    1(2.5cm)

    1(2.5cm)

    1(2.5cm)

    1(2.5cm)

    1.25(3.2cm)

    125(3.2cm)

    30(9.1m)

    .75(1.9cm)

    .75(1.9cm)

    1(2.5cm)

    1(2.Scm)

    1.25(3.2cm)

    1.25(3.2cm)

    1.25(3.2cm)

    1.25(3.2cm)

    40(12.2m)

    .75(1.9cm)

    .75(1 .9cm)

    1(2.5cm)

    1(2.5cm)

    1.25(3.2cm)

    1.25(3.2cm)

    1.25(3.2cm)

    1.25(32cm}

    50(15.2m)

    .75(1.9cm)

    1(2.5cm)

    1.25(3.2cm)

    1.25(3.2cm)

    1.25(3.2cm)

    1.25(3.2cm)

    1.25(3.2cm)

    1.25(3.2cm)

  • The pipe diameter may be reduced one size if LPGgas is used. Use steel pipe and Malleable ironfittings for gas service lines. Provide rigid supportsfor the pipe. If the pipe size must be reduced usereducing couplings only. Avoid the use of reducingbushings. Remove all burrs and inspect the pipefor dirt or other foreign material.

    A main manual gas cock is to be installedapproximately 5' (1.5m) above the floor level. A teeis located on the vertical drop at an appropriatelevel to attach the burner gas valve. The gas lineextends down to the floor with a cap on the end.This extension provides the required drip leg. Seefigure 6. If the gas pipe passes through a jacketedenclosure the union must be located inside thejacket so that the burner can be removed forservice. The manual gas cock is located outsidethe jacket. The gas valve used on all G2 burnershave a main line pressure tap on the inlet side ofthe gas valve.

    Figure 6MAIN SHUT-OFF VALVE

    ( BY INSTALLER)

    Piping must comply with local codes. When pipingLPG burners use pipe joint compound that isresistant to LP gas.

    The appliance and its individual shutoff valve mustbe disconnected from the gas supply piping systemduring any pressure testing of that system at testpressures in excess of 1/2 PSIG (3.45kPa).

    The appliance must be isolated from the gassupply piping system by closing its individualmanual shutoff valve during any pressure testing ofthe gas supply piping at tests pressures equal to orless than 1/2 PSIG (3.45kPa).A 1/8-inch (.32cm) NIPT plugged tapping,accessible for test gage connection, must beprovided immediately upstream of the gas supplyconnection to the conversion burner.

    WARNING: Explosion Hazard! The control canmalfunction if it gets wet. Never try to use one thathas beenwet - replace it.

    Never use a match or open flame for leakdetection. Use only soap solution.

    MAIN GAS LINEPRESSURE

    TAP

    VALVE DIALMANIFOLD PRESSURE TAP

    GAS PRESSURE REGULATORFLAME ROD TERMINAL

    CONTROL

    MOTOR OIL TUBES(TOP OF MOTOR )

    REST VERTICALPIPING ON FLOOR

    MAIN AIRADJUSTMENT SECONDARY AIRADJUSTMENT

    ( IF REQUIRED )10

  • GMWtvc

    Primary Control

    02 Educlor Manifold Assemb!

    OrlBce Cm and -O- Ri

    B3SO Motor and Mounting Plate Assembly

    Btowet Wheel

    Screws. 1M-20 X 6/8" Flat Head (4)

    Air Tube

    Housing

    Flange Housing GasketAir Band

    Air Shutter Assert*!)-

    Flange GasketHead. Electrode Assembly

    62 Wire KH consists olwires marked "A" above

    Electrode Assembly,Flame Proving

    Electrode Assembly Ignition

    11

  • MODEL G2 PARTS LfST

    PARTNUMBER

    388451084-A

    51076036BK51076064BK51076094BK

    21002

    2383

    51198050351198071551198101551096050

    51067050

    31191349351197

    33807101951196388551082

    DESCRIPTION

    Air BandAir Shutter AssemblyAir Tube, 5.25" (13.3cm)Air Tube, 8" (20.3cm)Air Tube, 11" (27.9cm)Blower Wheel, G2SD,5.2S" x 2.47" (13.3cm x 6.27cm)Blower Wheel, G2T,

    -6.25" x 3.44" (15.9cm x 8.74cm)G2 Eductor Tube Manifold Assy.Fits 5.25" (13.3cm) Air tubeFits 8" (20.3cm) Air tubeFits 11" (27.9cm) Air tubeElectrode Assy. Flame Prvg. 11"(27.9cm)Electrode Assy. Ignition 11"(27.9cm)Electrode ClampEscutcheon PlateFlame Proving Connecting WireAssy.Flange/Housing, GasketGas ValveG2 Wire KitFlange GasketAl. Manifold

    PARTNUMBER

    HT110AHT110BHT110DHT110FHA1 10AHA110BHA110CHA110DHA110EHA110F5107431182511952106521082-A51194

    See TableSee Table71025US710113892499

    2106621067

    RSS.495078

    DESCRIPTION

    Head Elec. Assy. G2T (GT2)Head Elec. Assy. G2T (GT4)Head Elec. Assy. G2T (GT6)Head Elec. Assy. G2T (GTS)Head Elec. Assy. G2SD (GO)Head Elec. Assy. G2SD (G2)Head Elec. Assy. G2SD (G3)Head Elec. Assy. G2SD (G4)Head Elec. Assy. G2SD (G5)Head Elec. Assy. G2SD (G6)Housing AssemblyManifold Mounting Plate GasketMotor Mounting Plate Assy. G2SDMotor G2SDMotor G2TOrifice Cap & "O" Ring KitOrificeOrifice AuxiliaryPrimary ControlRelayRetainer, 3.125" (7.9cm) Air TubeScrew, .25"-20 x .625" (.64cm-20 x 1.6cm)Flat Hd.Transformer (24vorts)Transformer, IgnitionAir Frovinfl Switch

    ORIFICE PART NUMBER TABLEFIRING RATE IN BTU'S/HOUR

    BURNER FUEL

    G2SD3.5' (,87kPa)NGas3.5"(.87kPa)UPG62T3.5" (,87kPa)NGas3.5" (.87kPa) LPG

    70,000

    3119418731194156

    3119419631194144

    80,009

    3116419631194166

    3119421331194158

    90.000

    3119421331194177

    3119422131194166

    100.000

    3119*22131194187

    3119423531194187

    125,000

    3119425031194203

    3119425731194213

    150,000

    3119426131194221

    3119429531194242

    175,000

    3119429531194242

    3119431231194260

    200,090

    3119432331194257

    3119435031194281

    225,000

    3119434831194272

    3119437531194300

    250.000

    311943753119429&

    3119441331194316

    NOTE: The last three digits of the part number reflect the diameter of the orifice in inches. Too convert the last three numbers to cenSmetere multiplyby 2.54.

    WHEN OROERINO BURNER PARTS, ALWAYS SPECIFY- BURNER MODEL NO., PART NO., AIR TUBE LENGTH & FIRING RATE.

    12

  • VII. GAS ORIFICE SIZING AND BURNER HEADSELECTION

    The gas input rate should be set to the rate deter-mined by the building heat loss calculations or bythe heating appliance labeled input rating. Do notexceed the maximum input of the heating applianceor the burner head firing range.

    The input rate and the type of gas to be used mustbe determined by the installer. Once this has beendetermined, the proper burner head and orifice canbe obtained from your Adams distributor.Whenever the precise orifice is not known at thetime of purchase, the burner will be equipped andtested at the factory to fire natural gas at theminimum input range of the installed burner head.On the opposite end of the orifice spring inside thegas manifold will be the orifice that delivers theminimum rate for LP gas with the burner headselected. See figure 8 page 14 for installationdetails. The orifice that is inserted into themanifold first is the one that determines the inputrate with the gas being used.

    The burner is designed for use with either Naturalor LP gases at 3.5" W.C. (.87kPa) manifoldpressure. The only burner adjustment that isrequired, in order to convert from one type of gasto the other, is the selection of the proper orifice forthe burner head range and the type of gas beingused. The following charts outline the head firingranges and orifice rates in thousands of BTU's perhour for the respective gas types at 3.5" W.C.(.87kPa) manifold pressure.

    The inside diameter of the orifice can be enlargedwith a taper reamer to obtain a higher rate withinthe burner head firing range, or the desired orificecan be obtained from your Adams distributor.

    All orifice sizes in the chart are approximate, theactual burner input rate will vary slightly with localheating values supplied. It is recommended thatinquiry be made of the gas supplier for the correctheating value. The actual firing rate can then bedetermined by following the instructions outlined inSection IX item 11.

    G2T HEAD SELECTIONHOW TO SELECT THE BURNER HEAD

    Desired Firing Rate BTU/HR

    50,000 to 11 0.00011 0.000 to 180.000180.000 to 21 0,00021 0,000 to 240,000

    Use Head

    GT2GT4QT6GTS

    TOTAL CERTIRED RANGESFOR NATURAL AND Ip GASES

    Head

    GT2GT4GTSGT6GT7GT8

    Minimum - Maximum BTU/HR

    50,000-120,00070,000-180,00090,000 - 200.000

    100,000-210,000110,000-230,000120,000-240.000

    01 G2T ModelG2T GAS ORIFICE SIZING CHART

    FiringRateBTU/HR

    50,000

    60,000

    70.000

    80.000

    90.000

    100,000

    110.000

    120.000

    130,000

    140.000

    150.000

    160.000

    170.000

    180,000

    190.000

    200.000

    210.000

    220.OOO

    230.000

    240.000

    Manifold Press. 3.5" W.C.(.87kPa) for Bom Gases

    Natural Gas

    Drill Ete

    5*32

    16

    H

    #3

    *2

    16/54

    D

    F

    I

    K

    M

    N

    5/16pQ

    S

    23/64

    3/B

    25(64

    2.

    Hole SizeIn. (on)

    .156 (.40)

    .176 (.45)

    .196 (.50)

    .213 (54)

    .221 (SKI

    .235 (.60)

    .246 (.62)

    .257 (.65)

    .272 (.69)

    .281 (.71)

    .295 (.79)

    .300 (.76)

    .312 (.79)

    .323 (.82)

    .332 (.84)

    .350 (.89)

    .360 (.91)

    .375 (.95)

    391 (.99)

    .413 (1.05)

    LPGas

    Drill Size

    #32

    Ma

    *27

    5/32

    019

    3/16

    m

    3

    e15164

    C

    1/4

    G

    1

    J

    K

    M

    N

    5/16

    0

    Note Sizefn. (cm)

    .116 (.29)

    .125 (.32)

    .144 (.36)

    .156 (.40)

    .186 (.42)

    .187 (.47)

    .196 (.50)

    .213 (.54)

    .221 (.56)

    .235 (.60)

    .242 (.61)

    .250 (.64)

    .260 (.66)

    .272 (.69)

    .277 (.70)

    .281 (.71)

    .295 (.75)

    .300 (.76)

    .312 (.79)

    .316 (.00)

    13

  • The orifice chart above all rates were calculated using the followingheating values: 1000 BTU's per cubic foot of natural gas and 2500BTU's per cubic foot of LPG.

    G2SD HEAD SELECTION

    Figure 8

    HOW TO SELECT THE BURNER HEAD

    Desired Firing Rate BTU/HR

    70,00010110,00080.000 to 180,000

    120,000 to 200.000150,000 to 240,000170,000 to 260,000190,00010255,000

    Use Head

    GOG2Q304G5GS

    G2SD GAS ORIFICE SIZING CHART

    FiringRate

    BTU/HR

    70,000

    80,000

    90,00

    100,000

    125,000

    150,000

    175,000

    200,000

    225.000

    250.000

    Manifold Pressure 3.5T/V.C. (,87cm) for Both GasesNatural Gas

    Drill Size

    3/16

    M

    S3

    2

    1/4

    8/32

    M

    p

    S

    38

    Hole SizeIn. (cm).187 (.47).198 (50)

    .213 (54)

    .221 (.56)

    .250 (.64)

    .281 (.71)

    .285 (.75)

    .323 (..82)

    .348 (.eft)

    .375 (.95)

    LPGas

    Drill Size

    5/32

    tin016

    sne

    1304

    a

    c

    F

    1

    M

    Hole SizeIn. (cm).156 (.40).166 (.42).177 (.45).187 (.47).203 (52)

    .221 (56)

    .242 (.61)J257 (.85).272 (.69)

    .295 (.75)

    VIII. ORIFICE CHANGE OUT PROCEDURE

    It is not necessary to disassemble the burner tochange gas orifices. Figure 8 shows a detailedview of the change procedure. Simply remove theorifice cap and install the proper primary orifice onthe spring. Insert the spring assembly into themanifold and tighten the orifice cap. Do not over-tighten.

    IX. INITIAL START UP AND ADJUSTMENT

    1. Check aHjojQts for gas leaks. ReferenceSection IV Gas Piping for suggested methods.

    NOTE: Care must be taken to prevent wetting theelectronic components during the leak test.

    WARNING: Explosion Hazard! The control canmalfunction if it gets wet. Never try to use one thathas been wet - replace it.

    2. It is important to purge the gas line on longsupply lines. Loosen the union figure 6 on page 10and allow the air to escape into the atmosphereuntil the gas starts flowing, then tighten the union.CAUTION - Purging excessive amounts of gas intothe atmosphere can be dangerous, particularly withLPG, which is heavier than air.

    3. Apply a few drops of #20 SAE Oil to the motorbearings.

    4. Make certain that the gas valve dial is turned toon. Air band if used should be set at zero and airshutter open to position 2 or less.

    5. Turn on the burner power supply switch and setthe room thermostat above room temperature. Letthe burner run until flame is established or thecontrol locks out (45 seconds).

    14

  • 6. If the control locks out turn the main line powersupply switch off and back on. This action resetsthe control and another purge cycle can beperformed if desired.

    7. Burner should now light off if gas line has beenpurged. NOTE: There is a 4 second trial forignition. If burner does not light off reset thecontrol by repeating step # 6.

    8. The gas input for natural gas can be determinedby timing the gas meter. To vary the gas inputinstall the nearest size orifice then adjust thepressure regulator up or down for exact inputdesired. The manifold pressure is to be measuredat the pressure tap on the gas valve. NOTE: Donot exceed the gas valve manufacturersrecommended pressure adjustment range.9. Adjust the combustion air shutters (when required) until good combustion is obtained.NOTE: Always use combustion test equipmentwhen setting the burner. It is impossible tooptimized combustion with the "eyeball" method.Check the CO2 and the CO with instruments inorder to obtain the following recommended values:

    GAS

    Natural

    LPG

    WIN.00^02%

    8.5/6.0

    10.5/5.1

    MAX.COJ02%

    10.5/2.5

    12.0/2.8

    CO MAX.PPM

    100

    100

    After the final air adjustment is made lock thesettings to prevent tampering.

    10. Gross Flue Gas Temperatures: 350F (175C)minimum for an outside chimney with threeexposed walls. 300F (147C) minimum for achimney centrally located within the structure. Ifthe gross stack temperatures exceeds 550F(285C) to 600F (312C) the appliance may beover-fired or the heat exchanger surfaces may bepartially blocked. Recheck the input and inspectthe appliance.

    NOTE: Make certain all other gas appliances inthe home are turned off before clocking the gasmeter.

    11. To determine the firing rate accurately,measure the time required for 1 cu. ft. of gas to be

    consumed. Use the following formula to calculateBTU/HR input.

    3600 X BTU/Cu. Ft. * No. seconds for 1 cu. ft. =BTU/Hr.

    EXAMPLE: 3600 X 1000 - 20 = 180,000 BTU/Hr.(Nat. Gas)For subsequent normal starting and shutdownprocedure refer to instruction plate mounted on theburner.

    X. BURNER CONTROL SYSTEM SEQUENCEOF OPERATION

    1. Thermostat contacts close.

    2. Step down transformer (120V to 24V) energizescoil in motor relay and motor starts.

    3 When motor approaches full RPM, thecentrifugal switch contacts on the motor closesupplying 24 volts to the primary control.

    4. After 45 seconds time delay 20 or more voltsare supplied to the primary control.

    5. The contacts in relay, close supplying 120 voltsto the Ignition Transformer.

    6. Arc is immediately established and 20 or morevolts supplied to the gas valve

    7. The gas valve opens and flame is immediatelyestablished.

    8. As soon as flame is established and 3 or moremicroamp signal is sent back to the PrimaryControl, the ignition relay drops out killing theignition arc. If the flame cannot be proven by thesignal strength in 4 seconds the control goes tolock out and turns both the ignition and gas valveoff. The burner motor will continue to operateduring lockout, if the thermostat or controllingcircuit is calling for burner operation.

    15

  • 9. The primary control is reset by either turning offthe power to the burner or turning down thethermostat below room temperature and resetting itback again above room temperature.

    10. If during a firing cycle the burner loses flamefor any reason, other than power failure, theignition arc is re-established in 0.8 seconds or lessand the 4 second trial for ignition is initiated.

    XI. THE GAS VALVE MOUNTING ASSEMBLY

    The gas valve mounting plate assembly includesthe combination gas valve, gas manifold, eductortube and the valve mounting plate. This assemblyis removed as a unit by removing four screw in themounting plate and withdrawing the assembly fromthe blower housing. The 24 volt combination gasvalve serves these functions; manual main gasshutoff, main gas pressure regulation, automaticelectric gas shutoff. A redundant gas valve hastwo automatic electric gas shut off valves in thesame body for additional safety. The automaticshut off function is controlled by the motor relaywhich switches power through the motor centrifugalswitch.

    NOTE: If it is necessary to replace a defective gasvalve, it can be done with a Honeywell 24 voltvalve. This valve is available with either a fast orstep opening regulation. DO NOT replace with aslow opening valve. Make sure that thereplacement valve is designed for use with DirectSpark Ignition Systems.

    If the gas line pressure to the burner exceeds themaximum rated inlet pressure of 13" W.C. (3.2kPa), install an axillary gas pressure regulator,rated for main burner service, ahead of the gasvalve on the burner. Reduce the incoming gaspressure to between 5" W.C. (1.2kPa) to 10" W.C.(2.5kPa) for natural gas and 11" W.C. (2.7kPa) to13" W.C. (3.2kPa) for LPG.

    The gas valve regulator is factory set for 3.5" W.C.(.87kPa) manifold pressure. If the rate must beslightly adjusted, remove the regulator cap and turnthe screw either clockwise or counterclockwise toincrease or decrease the manifold pressure notmore than +/- 0.3" W.C. (.07kPa).

    When the gas valve mounting plate assembly isremoved from the housing during servicing, caremust be taken to relocate the "Z" dimension. Thisis accomplished by aligning the arrow on theaffixed label to the "Z" locator notch cut in the gasmounting plate, as outline in figure 9.

    The "Z" dimension is determined by removing theburner head assembly and measuring the distancefrom the eductor tube to the face of the air tube.This should be 1.5" (3.81cm).

    Figure 9

    1.5-(3.W:M> -IV DIMENSIONBURNHWHHEADREMOVED

    NOTE: When reinstalling the gas valve mountingplate assembly, be sure to insert the eductor tubeinto the centering ring located in the air tube. Thiscan be easily accomplished by looking under therear edge of the mounting late. You can observethe entry of the eductor tube into the centering ring.

    XII. THE BLOWER MOTOR ASSEMBLY

    The blower motor assembly includes the motor andthe blower wheel.

    Occasional cleaning of the blower wheel and inletair damper may be required. Accumulation of lintand dirt around the shutters and band mayindicated cleaning is necessary. The appearanceof the flame can also indicate a lack of combustion

    If the motor fails to operate, first check the motorrelay and determine if it is functioning and thatelectrical power is available to the motor beforedetermining the motor is defective.

    16

  • XIII. ELECTRODE SETTING SPECIFICATIONS

    Figure 10 -G2T

    ^

    KM UtCTWOOl

    NOTE: Install the burner head assembly into theair tube in this position only. The ignition electrodewill always be in the lower right hand area, asshown.

    Figure 11-G2SDUvf.II IKCTMOCC

    NOTE: Install the burner head assembly into theair tube in this position only. The ignition electrodewill always be in the lower right hand area, asshown.

    XIV. MAINTENANCE INSTRUCTIONS

    1. A qualified gas service agency must becontacted for service for malfunction of the burneror appliance.

    2. The burner motor bearings require lubricationonce annually. Apply a few drops of #20 weightnon-detergent oil to each bearing lubrication tube.

    3. Observe the burner flame occasionally. Ifyellow smoky tips are noticed call your serviceagency and have the burner adjusted.

    4. Keep all materials, combustible or otherwise, atleast two feet (12.7 cm) away from the heatingappliance. Do not store gasoline or otherflammable vapors or liquids in the room where theheating appliance is located.

    5. Combustion and ventilating air openings mustnot be blocked off for any reason or obstructed bymaterials. During the routine servicing of theburner, the service agency should make sure thatall lint, dust or other foreign materials thoroughlycleaned from the burner head assembly and theblower wheel

    17

  • BURNER IDENTIFICATIONSYSTEM - 62SD/G2T

    1. Basic Model - Identified by G2SD or G2T.

    2. Burner Head - Identified by the numbers 0 thru6 (G2SD), or 2 thru 8 (G2T). The firing rate rangeof each head is shown in the block adjacent to thehead identification.

    3. Air Tube Length - The number to the right showthe useable air tube length in 1/8" (.32 cm) in-crements. The number to the left shows the lengthin 1" (2.54 cm) increments. Example: "52", the 2means two eights or 1/4" (.64 cm). The fivemeans 5" (12.7 cm). The two numbers mean thatthe useable air tube length is 5.25" (13.3cm).4. Blower Wheel & Air Band1st Letter - B, identifies a 5.25" (13.3cm) dia.Blower Wheel2nd Letter - D, Identifies a blank air band.2nd Letter, - C, Identifies a 10 slot air band.

    For example: The complete Model Number -G2SD052BD identifies a G2SD burner with GOcombustion head, (firing range 70,000-110,000BTUH), a 5.25" (13.3cm) useable air tube and a5.25" (13.3cm) diameter blower wheel with blankair band.

    5. Serial Numbers - Will be sequential.

    2 3 4 5

    70.000-110.COO [

    ill 60.000-1 SO.COO Ig,\l.... ...... i - '.

    LIGHTING AND SHUTDOWN INSTRUCTIONS

    To Light Burner

    1. Turn "ON" gas valve in supply line.

    2. Rotate knob on the gas valve counterclockwiseto "ON" position.

    3. If combustion air has been previously adjusteddo not re-adjust. If not, open the air shutter toposition "2" or less.

    NOTE: Final settings must be determined by testinstruments.

    5. Set thermostat above room temperature.

    6. Burner motor will now start and run for 45seconds. The gas valve then opens, ignitiontransformer provides spark and the burner will lightoff.

    7. If burner fails to light off in 4 seconds the safetycontrol will lock out and shut the gas valve off.

    8. Reset the safety control by turning roomthermostat below room temperature and back upagain or turning off power supply to the burner andback on again.

    4. Turn "ON" switch for burner power. 18

  • The burner will start again and repeat step "6".NOTE: If burner fails to light off and sustain flameafter three or four tries turn "OFF" main shut offvalve and call a qualified burner service agency.

    To Shut Down Burner

    1. Rotate knob on gas valve clockwise to the"OFF" position.

    2. Turn "OFF" the switch for the burner powersupply.

    5. Be familiar with the G-2 Installation Manual.Wiring diagrams and burner operation data arefound in the Manual as well as on the burnercontrol box and nameplate.

    CAUTION: Be certain that the manual gas valveand the burner power supply switch are turned oflbefore removing any part for servicing.

    G - 2 TROUBLE SHOOTING GUIDE

    Before beginning these trouble shootingprocedures, ALWAYS observe the following basicguidelines:

    1. Check the electrical line voltage at the burnerwiring box connections for a nominal 120 volts AC.CAUTION: When testing electrical equipmentALWAYS follow standard electrical safetyprocedures.

    2. Make sure the thermostat or other controllingdevice is calling for burner operation.

    3. Check the inlet gas pressure to verify that youhave adequate pressure at the gas valve. Makesure there are no "air locks" or gas leaks in thepiping system. Turn the manual valve to the "ON"position.

    4. To successfully service the G-2 power gasburner, you need these test instruments:

    a. An Oxygen or Carbon Dioxide analyzer.b. A CO (Carbon Monoxide) test kit.c. A flue gas stack thermometer.d. A draft gauge. Scale should read +.10" to -

    .25" W.C. (+ .02 kPa to -.06kPa).e. A volt/ohm/milliampere multimeter that is

    capable of reading 24 volts AC, 120 volts ACand up to 20 microamperes DC.

    f. A manometer capable of reading up 15"W.C. (3.7kPa).

    19

  • MOTOR DOES NOT START

    1. Check the low voltage transformer for 24 voltoutput between terminal 3 on the motor startrelay and either of the "T" terminals on thecontrol box.

    NO Check electrical wiringand connections. OK)/

    Replace 24 volt AC30 VA Transformer

    2. Check for 24 volts AC between terminals 1 and3 on motor start relay.

    Check electrical wiringand connections. OK)

    /Replace motorstart relay.

    3. Check for 120 volts AC between terminal 2 onmotor start relay and neutral line.

    4. Check Electrical wiring and connections.

    5. Does motor shaft turn freely?

    6. Replace motor.

    NO)-y

    Check electrical wiringand connections. OK)

    NO 1. Check for Blower clearance.2. Lubricate motor bearings.OK

    Replace motorstart relay.

    20

  • CONTROL SYSTEM WITH PREPURGE TIMER

    IGNITION ARC ESTABLISHED - NO FLAME

    1. Reset Control - Motor starts - Completes 35-45 second prepurge cycle. Ignition arcs for four seconds. No flameis established. Control locks out after four second trial for ignition period.NOTE: The burner motor will continue to operate during the lock out mode when the thermostat circuit is callingfor burner operation.

    2. Check for correct orifice/air setting relationship.

    In order for the following functional tests to be made,the control must be reset and the tests monitored duringthe four second trial for ignition period that occurs atthe END of the prepurge cycle.

    3. Check for 24 volts AC at gas valve terminals.^JOKL^

    4. Make sure leads are on the correct gas valve terminals.

    NO)V

    Check electrical wiringand connections. Be sureleads are on correct gasvalve terminals.

    OK) Replace electronicprimary control.

    5. Check for correct manifold regulated pressure.

    6. Replace gas valve.

    NO IGNITION ARC ESTABLISHED

    1. Reset Control Motor starts - Completes 35-45 second prepurge cycle. Gas valve opens, regulating adequate gas pressure. No flame established - Primary control locks out after (4) four seconds trial for ignition period.

    In order for the following functional tests to be made,the control must be reset and the tests monitored duringthe 4 second trial for ignition that occurs at the end ofthe prepurge cycle.

    2. Check for 120 volts AC between the neutral line andthe junction of the blue primary control lead and theblack ignition transformer lead.

    rtc3. Check electrical wiring and connections.

    4. Check high voltage lead and connection to ignitionelectrode rod.

    5. Inspect ignition electrode for cracked insulator andcorrect spark gap. (Typically 3/32" (.24cm).

    ! 6. Replace ignition transformer.

    Check electrical wiring and connections.

    Check the flame sensing circuit for (1) groundedflamerod. (2) Damage to fiamerod lead insulation.NOTE: Make sure that the flamerod circuit and/orprimary control is moisture-free.

    Replace electronic primary control.

    21

  • NO IGNITION - NO GAS VALVE OPERATION

    1. Reset Control - Motor starts - After 35-45 second prepurge cycle, motor continues to run but flame is not established.

    In order to perform the following functional tests, theprimary control must be reset and the tests monitoredduring the 4 second trial for ignition period that occursat the end of the prepurge cycle.

    2. Check for 24 volts AC at the 25 volt primary controlinput terminals.

    3. Check for 24 volts AC between the yellow centrifugalswitch lead at the timer terminal and the yellow/red-striped lead at the primary control input terminal.

    4. Check electrical wiring and connections. OK) /

    Replace motor - The centrifugalswitch is defective.

    LOSES FLAME DURING CYCLE - CONTROLLOCKS OUT ON SAFETY

    1. Reset Control Completes 35-45 second prepurge cycle. Flame is established Sometimes the control locks out before the thermostat or controlling circuit is satisfied.

    2. Disconnect flamerod lead from primary control.Connect (+) positive lead (DC Microampere Meter) tothe primary control terminal. Connect the (-) negativemicroampere meter lead to the flamerod lead terminal.

    3. Reset control, after prepurge cycle, flame isestablished. A stable microampere current of 3 ormore is required for dependable operation.

    -N-y

    4. Microampere reading is less than 3 or unstable.

    Probable cause of erratic lockout:1. Flame proving circuit grounded by moisture.2. Damaged insulation on flamerod lead or loos,

    terminal.3. Flamerod improperly positioned in flame.4. Poor ground path to primary control.5. Defective primaiy r-orrtoL

    Probable causes:1. Extremely poor combustion level.2. Flamerod improperly positioned in fiame.3. Defective primary control.

    22

  • BURNER CYCLES ERRATICALLY

    1. Check for proper thermostat installation and location.

    2. Check thermostat heat anticipator for correct setting.

    3. Check low voltage circuit for bad wiring, electricalconnections and/or switches.

    4. Check line voltage circuit for bad wiring, electricalconnections and/or switches.

    NOTE: When the thermostat wires terminate onthe G2 primary control box "T" terminal, the heatanticipator setting value for the G2 burner isdetermined by adding the primary control current tothe gas valve current. The result is the anticipatorsetting. (Example: .2 + .6 = .8 amps.)

    Set anticipator to correct value if adjustable type. Ifproper setting cannot be made, replace with compatiblethermostat.

    If the thermostat wires are not terminated on theburner control box "T1 terminals, and theseterminals are JUMPERED, you must thendetermine what the correct anticipator setting is byinspecting the controlling device at the point wherethe thermostat wires terminate. Typically, this in-formation can be found on the body or cover of thecontrolling device.

    When the current draw cannot be determinedaccurately by the above method, measure thecurrent with an ampere meter using the 1 ampscale. Connect the meter leads in series with oneof the thermostat leads for the accurate reading.

    HOW TO OBTAIN WARRANTY

    The Adams statement of burner warranty isoutlined below. Warranty on the component parts(motors, gas valves, transformers and controls) isdetermined by the specific manufacturer's datecode covering the component.

    The manufacturers of component parts used on theburner have established service agencies anddistributors for handling warranty for theirmanufacture. The use of these local agenciesoffers a convient source of parts and also savesthe cost and delay of returning defective parts to

    When local agencies are not available, however,defective parts may be returned directly to Adams.

    23

  • WIRING DIAGRAM! mf 1072 H

    Limit ControlDS 1072 H

    L I Ho;

    120V/SO Hz I

    L2 Neutro: | itini^ mj

    Dashed wiringand components bymstal ler

    Unless otherwise noted,'If any of the originalwire as supplied with trieconversion burner mustbe replaced., it must bereplaced with 300Vtype AWM 100*0 or itsequivalent.' Burner Motor

  • LIMITED WARRANTY

    Adams Manufacturing Co. (Adams) warrants its products and components to be free from defects due tofaulty workmanship or defective materials at the time of shipment and under normal use and service fortwelve (12) months from date of installation by a qualified installer or eighteen (18) months from date ofmanufacturing, which ever date occurs first. This LIMITED WARRANTY does not extend or apply to Adamsproducts, or any component there of, which has been misused, neglected, improperly installed or otherwiseabused. Equipment which is defective in material or workmanship and which is removed within the specifictime period will be repaired or replaced as follows:

    (1) Components, controls, motors & transformers should be returned to an authorized distributor.(2) Products determined to be covered under this LIMITED WARRANTY by Adams shall be either repaired

    or replaced at Adams' sole option.

    (3) Adams is not responsible for any labor cost for removal and replacement of said products andequipment associated therewith.

    (4) Controls, motors & transformers, other components which are so repaired will carry this limited warrantyequal to the unexpired portion of the original products LIMITED WARRANTY.

    (5) If inspection by Adams does not disclose any defects covered by this LIMITED WARRANTY, theproduct will be repaired or replaced at the expense of the customer and Adams' regular charges willapply.

    THE FORGOING STATES THE SOLE AND EXCLUSIVE REMEDY FOR ANY BREACH OF WARRANTYOR FOR ANY OTHER CLAIM BASED ON ANY DEFECT IN, OR NON-PERFORMANCE OF, THEPRODUCTS, WHETHER SOUNDING IN CONTRACT, WARRANTY OR NEGLIGENCE. NO OTHERWARRANTY, WHETHER EXPRESSED OR IMPLIED, INCLUDING ANY WARRANTY OFMERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, SHALL EXIST IN CONNECTIONWITH THE SALE OR USE OF SUCH PRODUCTS AND IN NO EVENT WILL ADAMS BE LIABLE FORANY INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY NATURE. Adams neither assumes norauthorizes any persons to assume for Adams any other liability or obligation in connection with the sale ofthese products.

    4-9-2012 11_48_44 AMG2TInstallationManual