Fusesaver® - Tennessee Electric Cooperative Association
Transcript of Fusesaver® - Tennessee Electric Cooperative Association
Fusesaver – Reduced Operational Cost
Reclose for Transient Faults without Melting Fuses
LINE CLASH BIRD / WILDLIFE STRIKE
LIGHTNING VEGETATION / TREES
SIEMENS Fusesaver®
Some Typical Transient Faults
Fusesaver - OC & O-CO Modes
Fusesaver OC Fusesaver OCO
Fusesaver clears transient faults before fuse melts. Fusesaver clears transient fault
Fuse clears permanent fault. Fusesaver does 2nd trip to lockout to clear permanent fault.
Best application where fuses are already installed. Just add a Fusesaver OC to achieve improved reliability of fused lateral lines.
Best application on networks that don’t use fuses, i.e. replaces the drop out sectionalizer with better performance.
Automation At The Fuse What makes up a Fusesaver
Page 5
Termination Mounting Assembly
Manual protection Setting lever
Termination
Fusesaver - Automation At The Fuse The Fusesaver Architecture
Page 6
Integrated UFCB
Wireless communications module
Manual and Laptop Operation
Siemens Fusesaver Safety Features
Feature Light Weight – 12lb Can be easily lifted into position. Once installed, no external movement Fault breaking is contained inside the
Fusesaver. For type OC type, the fuse breaks permanent fault and can be easily replaced. For the O-CO type, reset is made by pushing the external close lever.
60 seconds “walk away” Once a TRIP or CLOSE lever is pushed there is a 60 second delay to clear the area before operation. The LED light indicates status.
Automation At The Fuse Single-phase or Three-phase “ganged” configuration
The Fusesaver can operate in either a pure single-phase mode or as a member of a coordinated group of two or three. Short range radios in the Fusesaver allow it to connect to up to two nearby Fusesavers and form a “tribe”. Allows synchronized manual tripping of three phases. Allows three-phase lockout
Page 9
Siemens Fusesaver – Product Family Installation Types
Typical pole-mounted
installation
Line-clamp assembly
Typical cross-arm mounted
installation Through bolt Fish plate
Automation At The Fuse Installation Possibilities
Should target the shortest installation time possible – 20 mins per phase might be typical.
Page 11
Installed on line Installed on cross-arms
Siemens Connect: PC with wireless connection
Siemens Connect provides a means for utility personnel to interface with the Fusesaver during installation, workshop testing, system upgrades, and for fault finding Wirelessly connects to the Fusesaver Automatically downloads all events and data logs on connection. Saves data into an offline database for offsite analysis Data analysis to verify performance or identify settings modifications
Page 13
Fusesaver - Automation At The Fuse Pre-defined and Configurable Device Profiles
A profile is uploaded into each Fusesaver that determines how the device will behave. An appropriate, pre-validated profile is selected from a profile database containing only those profiles relevant to the user. Pre-defined profiles speed up installation by keeping commissioning to a minimum.
Page 14
Siemens Fusesaver Event Log
The Fusesaver’s event database saves up to 3,000 significant events such as a protection trip, auto close, manual operation, protection mode change or line current off. The events are normally marked with the time of occurrence and are displayed in sequence.
Siemens Fusesaver Site performance data
Reliability Data Availability Data The purpose of the line reliability analysis tool is to allow the user to generate useful reliability performance data for a particular line.
The availability analysis tool is to assist the user to assess whether there is enough line current available to power the Fusesaver on a consistent basis. The line availability represents the percentage of time that line current is on in a given period.
Siemens Fusesaver Load Profiling
The Fusesaver is normally installed on lines where the utility typically has few devices that provide information on demand.
The Fusesaver captures the minimum, maximum and average current for each 24 hour period.
This data is stored in on-board non-volatile memory and is downloaded by Siemens Connect as part of the event log.
Note : Load profile data is not available as a DNP3 analogue point. The user would use the line current as DNP 3 analogues in this case.
Siemens Fusesaver Rating Overview
Model type Standard range High range Minimum line current for operation 0.5 A 1.0 A
Fuse ratings 5-50 A 5-100 A
Rated normal current 100 A 200 A
Rated short-circuit breaking current Isc 4 kA 4 kA
Rated short-circuit making current Ipeak 10 kA 10 kA
Rated short-time current 4 kA 4 kA
Rated short-time current duration 0.2 s 1.0 s
Fault break operations at 100% 30 30
Fusesaver has been type tested in accordance with the applicable sections of the IEC: 62271-100 circuit breaker standard. The Fusesaver is available in three models dependent upon minimum line current, rated current and fault current capability:
Siemens Fusesaver Product Overview
Model Type Low Range Standard Range High Range
Rated voltage 15.5 / 27 kV
Rated lightning impulse withstand voltage Up 110 / 125 kV
Rated power-frequency withstand voltage Ud (60 s) 50 / 60 kV
Minimum tripping current (configurable) X 0,5 fuse rating
Mechanical operations 2,000
Full fault operations 70
Rated frequency 50 / 60 Hz
Weight 5.5 kg Maximum operating ambient air temperature +50 °C Minimum operating ambient air temperature -40 °C Solar radiation 1.1 kW/m2
Maximum altitude 3000 m
Humidity 0 to 100 %
Fusesaver Features/Benefits
1. Optimal protection of spur/lateral lines. Minimizes number of customers affected and duration of outages due to transient faults.
2. Self powered from minimal line current – as little as 0.15A.
3. Isolate line in case of permanent fault.
4. Configurable and powerful protection options. a) Multiple curves possible b) Change of protection modes c) Three phase lock-out and backfeed blocking d) Thermal overload
Fusesaver Features/Benefits
5. Manual switching of line. 3-phase synchronous switching to full load current rating.
6. Fault passage indication in case of permanent fault.
7. Load profile data collection.
8. Comprehensive event log
9. Configure, reconfigure and download data via wireless connection from ground level – no need to remove unit from service
10. Light weight, simple and quick to install. Multiple installation options available
The Fusesaver – A Low Cost Switching Solution
1. Siemens Fusesaver Basic Operation Protects against outage from a Transient
(Temporary) Fault condition at Fuse
2. Siemens Fusesaver Advanced Operation
The addition of a communications module provides
advanced Fusesaver operations.
3. Siemens Fusesaver Advanced Operation + RCU SCADA Interface
The addition of RCU achieves greater value and
service of the Fusesaver asset
Uses the existing communications network
Fusesaver - Automation At The Fuse Fusesavers as participants in Distribution Automation
With their integrated sensing they are another point of SCADA visibility. With their self-powered magnetic actuator and remotely selectable protection modes they are another point of SCADA control. It has memory to store the histories of the events and loads seen by these sensors or to make these events available to SCADA and DA schemes. An application example could be for them to be put into single-shot mode after a particular fault event handled by DA.
Page 25
Fusesaver - Automation At The Fuse Siemens Remote Control Unit (RCU)
SIEMENS Remote Control Unit IP55
Solar power supply (optional) for Remote Control Unit
Fusesaver
Communication module attached to Fusesaver (mandatory for use with RCU)
1
2
3
4
1
2
3
4
Fusesaver – Remote Control Unit
Ø Remotely control Fusesavers including; Ø Trip and close Ø Change operational (policy) parameters Ø Local / Remote Modes
Ø Receive fault alerts including; Ø Protection Operation Alarm Ø Loss of supply Ø End of life Ø Low battery Alarm
Ø Retrieve events, reliability data and load data
Ø DNP3 SCADA Interface
and Radio Supply provided
The Siemens Remote Control Unit (RCU) acts as an interface between a set of installed Siemens Fusesavers and a utility’s SCADA system.
!
! ! ! O!
!4#C0.$'DED'6''F?$'40;$5*:$.'J.+K0-&'4*1#"G''
!
`$2)/+!N6N!%#'8%!3!-4.$(31!%$-+!3,&!311!*+*9+/%!'5!-#+!`)%+]30+/!53*$14666!
;-+*!=P>!!$%!-#+!`)%+]30+/!$-%+15!-#3-!$%!*'),-+&!',!-#+!&+3&<+,&!'5!-#+!%.)/!1$,+!3,&!./'0$&+%!-#+!(',,+(-$',!5/'*!-#+!%.)/!1$,+!(',&)(-'/!-'!-#+!.3/-,+/!ALC!5)%+!=N>6!!"#+%+!-8'!$-+*%!(',%-$-)-+!-#+!93%$(!`)%+]30+/!$,%-3113-$',!8#$(#!$%!+_.13$,+&!$,!&+-3$1!$,!-#+!/+%-!'5!-#$%!*3,)316!!"#+$/!'.+/3-$',!(3,!9+!%)**3/$%+&!3%g!!
!"#$%&'()#'$*+,#$%'-(#.(,$("#$,%+'$/0)#$*'-1$%#'1&)#)($*&+/(,$&)2$("#$3+,#4&5#'$%'-(#.(,$("#$%&'()#'$*+,#$*'-1$6#0)7$6/-8)$69$('&),0#)($*&+/(,6!!
"'!8'/^!./'.+/14!-#+!`)%+]30+/!#3%!3!,)*9+/!'5!%+--$,2%!8#$(#!3/+!&$%()%%+&!13-+/6!
I1%'!%#'8,!$,!6N!N!$%!3!B'**),$(3-$',%!W'&)1+!=O>!.1)22+&!$,-'!-#+!),&+/%$&+!'5!-#+!`)%+]30+/6!!"#+!B'**),$(3-$',%!W'&)1+!(',,+(-%!&$/+(-14!-'!-#+!+1+(-/',$(%!*'&)1+!$,!-#+!`)%+]30+/!3,&!#3%!3!%#'/-!/3,2+!8$/+1+%%!('**),$(3-$',%!(3.39$1$-4!%'!-#3-!-#+!`)%+]30+/!(3,!9+!(',5$2)/+&:!$,-+//'23-+&!3,&!(',-/'11+&!5/'*!2/'),&!1+0+16!!
"#+!B'**),$(3-$',%!W'&)1+!$%!,++&+&!-'!$,%-311!3,&!('**$%%$',!3!`)%+]30+/!9)-!$%!'.-$',31!-#+/+35-+/6!"#+!B'**),$(3-$',%!W'&)1+!(3,!9+!$,%-311+&!3,&!/+*'0+&!5/'*!2/'),&!1+0+1!8$-#!3!1$0+<1$,+!%-$(^6!
U#+,!-#+!B'**),$(3-$',%!W'&)1+!$%!1+5-!.+/*3,+,-14!5$--+&!-#$%!311'8%!`)%+]30+/%!',!-8'!'/!-#/++!.#3%+!1$,+%!-'!9+!'.+/3-+&!$,!3!23,2+&!*'&+6!!
C.+/3-$',%!.+/%',,+1!$,%$&+!-#+!-/)(^!=Q>!!3/+!)%$,2!3!('*.)-+/!!+b)$..+&!8$-#!-#+!:&-)$;-))#.(!%'5-83/+!3,&!:&-)$<4=$>)(#))&!#3/&83/+6!"#$%!('*.)-+/!$%!('**),$(3-$,2!0$3!-#+!@3',![]M!I,-+,,3:!-#/')2#!-#+!B'**),$(3-$',%!W'&)1+!3,-+,,3!-'!-#+!`)%+]30+/!$-%+156!!"#$%!311'8%666!
5
>>> SCADA system
1 2
3
4 5
Fusesaver Fuse
Communications module Crew using Siemens Connect
Siemens RCU
1 2 3 4 5
Fusesaver - Automation At The Fuse Fusesavers as participants in Distribution Automation
Page 28
+
SCADA
Sub-Station Data
Concentrator
Radio Control Unit (RCU)
DNP3
IEC
6185
0
Wireless
Wireless
Fusesaver - Automation At The Fuse Benefits of integrating the fuse level into DA
Reduces operating costs with remote control, fault and event data, and automated mode changes. More real network information available to the over distribution SCADA. Greater network granularity for the DA scheme perspective in both network awareness and control.
Page 29
Fusesaver - Automation at the fuse RCU Characteristics
Purpose designed for installation outdoors. Wireless connection between Fusesaver and Communications Unit Provides battery backup to ride-through loss of mains Simple or no HMI – user preference Transceiver mounting tray and power supply available.
Page 30
RCU
Fusesaver - Automation At The Fuse Protocol, Bandwidth, and Communications Medium
DNP3 available. Bandwidth demand can be adjusted through protocol point selection. Communications medium is typically determined by user requirements – cellular, mesh radio, licensed radio, WiMAX
Page 31
Automation At The Fuse Questions?
Thank You!