Fundamentals of Circuit Breaker Maintenance
© AVO Training Institute, Inc. 2018
![Page 2: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/2.jpg)
2
Moderator
n Ron Spataro AVO Training Institute Marketing Manager
![Page 3: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/3.jpg)
3
Q&A
n Send us your questions and comments during the presentation
![Page 4: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/4.jpg)
4
Today’s Presenter
Mike Carter AVO Training Institute, Senior Instructor and Curriculum Advisor
![Page 5: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/5.jpg)
5
• Definition • A circuit breaker is an automatically operated electrical
switch designed to protect an electrical circuit from damage caused by excess current from an overload or short circuit. Its basic function is to interrupt current flow after a fault is detected.
• Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset (either manually or automatically) to resume normal operation.
Definition and Purpose of Circuit Breakers
![Page 6: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/6.jpg)
6
• Definition • Circuit breakers are made in varying sizes, from small
devices that protect low-current circuits or individual household appliance, up to large switchgear designed to protect high voltage circuits feeding an entire city.
• The generic function of a circuit breaker, RCD or a fuse, as an automatic means of removing power from a faulty system is often abbreviated as OCPD (Over Current Protection Device).
Definition and Purpose of Circuit Breakers
![Page 7: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/7.jpg)
7
• Purpose • Interconnection of multiple generator sources into an
electrical grid required development of circuit breakers with increasing voltage ratings and increased ability to safely interrupt the increasing short-circuit currents produced by networks.
• Simple air-break manual switches produced hazardous arcs when interrupting high voltages; these gave way to oil-enclosed contacts, and various forms using directed flow of pressurized air, or of pressurized oil, to cool and interrupt the arc.
Definition and Purpose of Circuit Breakers
![Page 8: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/8.jpg)
8
• Purpose • All circuit breaker systems have common features in their
operation, but details vary substantially depending on the voltage class, current rating and type of the circuit breaker.
• The circuit breaker must first detect a fault condition. • In small mains and low voltage circuit breakers, this is
usually done within the device itself. • Circuit breakers for large currents or high voltages are
usually arranged with protective relay pilot devices to sense a fault condition and to operate the opening mechanism.
Definition and Purpose of Circuit Breakers
![Page 9: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/9.jpg)
9
• Purpose • These typically require a separate power source, such as a
battery, although some high-voltage circuit breakers are self-contained with current transformers, protective relays, and an internal control power source.
• Once a fault is detected, the circuit breaker contacts must open to interrupt the circuit; this is commonly done using mechanically stored energy contained within the breaker, such as a spring or compressed air to separate the contacts.
Definition and Purpose of Circuit Breakers
![Page 10: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/10.jpg)
10
• Purpose • Circuit breakers may also use the higher current caused by
the fault to separate the contacts, such as thermal expansion or a magnetic field.
• Small circuit breakers typically have a manual control lever to switch off the load or reset a tripped breaker, while larger units use solenoids to trip the mechanism, and electric motors to restore energy to the springs.
Definition and Purpose of Circuit Breakers
![Page 11: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/11.jpg)
11
• Purpose • The circuit breaker contacts must carry the load current
without excessive heating, and must also withstand the heat of the arc produced when interrupting (opening) the circuit.
• Contacts are made of copper or copper alloys, silver alloys and other highly conductive materials.
• Service life of the contacts is limited by the erosion of contact material due to arcing while interrupting the current.
Definition and Purpose of Circuit Breakers
![Page 12: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/12.jpg)
12
Air, Low- Voltage Power Circuit Breakers
![Page 13: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/13.jpg)
13
• Visual and Mechanical Inspection • Inspect physical and mechanical condition. • Inspect anchorage, alignment, and grounding. • Verify that all maintenance devices are available for
servicing and operating the breaker. • Prior to cleaning the unit, perform as-found tests, if required. • Clean the unit. • Inspect arc chutes. • Inspect moving and stationary contacts for condition, wear,
and alignment.
Air, Low- Voltage Power Circuit Breakers
![Page 14: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/14.jpg)
14
• Visual and Mechanical Inspection • Verify that primary and secondary contact wipe and other
dimensions vital to satisfactory operation of the breaker are correct.
• Perform all mechanical operator and contact alignment tests on both the breaker and its operating mechanism in accordance with manufacturer’s published data.
Air, Low- Voltage Power Circuit Breakers
![Page 15: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/15.jpg)
15
• Visual and Mechanical Inspection • Inspect bolted electrical connections for high resistance
using one or more of the following methods: • Use of a low-resistance ohmmeter • Verify tightness of accessible bolted electrical connections
by calibrated torque-wrench method in accordance with manufacturer’s published data or Neta Table 100.12.
• Perform a thermographic survey
Air, Low- Voltage Power Circuit Breakers
![Page 16: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/16.jpg)
16
• Visual and Mechanical Inspection • Verify cell fit and element alignment. • Verify racking mechanism operation. • Use appropriate lubrication on moving current-carrying parts
and on moving and sliding surfaces. • Perform adjustments for final protective device settings in
accordance with coordination study provided by end user. • Perform as-left tests. • Record as-found and as-left operation counter readings.
Air, Low- Voltage Power Circuit Breakers
![Page 17: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/17.jpg)
17
• Electrical Test • Perform resistance measurements through bolted
connections with a low-resistance ohmmeter. • Perform insulation-resistance tests for one minute on each
pole, phase-to-phase and phase-to-ground with the circuit breaker closed, and across each open pole. Apply voltage in accordance with manufacturer’s published data. In the absence of manufacturer’s published data, use Neta Table 100.1.
Air, Low- Voltage Power Circuit Breakers
![Page 18: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/18.jpg)
18
• Electrical Test • Perform a contact/pole-resistance test. • (Optional) Perform insulation-resistance tests on all control
wiring with respect to ground. The applied potential shall be 500 volts dc for 300-volt rated cable and 1000 volts dc for 600-volt rated cable. Test duration shall be one minute
• Determine long-time pickup and delay, short-time pickup and delay, ground-fault pickup and delay and instantaneous pickup current by primary current injection.
Air, Low- Voltage Power Circuit Breakers
![Page 19: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/19.jpg)
19
• Electrical Test • (Optional)Test functions of the trip unit by means of
secondary injection. • Perform minimum pickup voltage test on shunt trip and close
coils in accordance with Neta Table 100.20. • Verify correct operation of auxiliary features such as trip and
pickup indicators, zone interlocking, electrical close and trip operation, trip-free, antipump function, and trip unit battery condition.
Air, Low- Voltage Power Circuit Breakers
![Page 20: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/20.jpg)
20
• Electrical Test • Reset all trip logs and indicators. • Verify operation of charging mechanism.
• Test Values – Visual and Mechanical • Compare bolted connection resistance values to values of
similar connections. Investigate values which deviate from those of similar bolted connections by more than 50 percent of the lowest value.
Air, Low- Voltage Power Circuit Breakers
![Page 21: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/21.jpg)
21
• Test Values – Visual and Mechanical • Bolt-torque levels should be in accordance with
manufacturer’s published data. In the absence of manufacturer’s published data, use Neta Table 100.12.
• Results of the thermographic survey. • Settings shall comply with coordination study
recommendations. • Operations counter should advance one digit per close-open
cycle.
Air, Low- Voltage Power Circuit Breakers
![Page 22: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/22.jpg)
22
• Test Values – Electrical • Compare bolted connection resistance values to values of
similar connections. Investigate values which deviate from those of similar bolted connections by more than 50 percent of the lowest value.
• Insulation-resistance values of breakers should be in accordance with manufacturer’s published data. In the absence of manufacturer’s published data, use Neta Table 100.1. Values of insulation resistance less than this table or manufacturer’s recommendations should be investigated.
Air, Low- Voltage Power Circuit Breakers
![Page 23: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/23.jpg)
23
• Test Values – Electrical • Microhm or dc millivolt drop values should not exceed the
high levels of the normal range as indicated in the manufacturer’s published data. If manufacturer’s data is not available, investigate values that deviate from adjacent poles or similar breakers by more than 50 percent of the lowest value.
• Insulation-resistance values of control wiring should be comparable to previously obtained results but not less than two megohms.
Air, Low- Voltage Power Circuit Breakers
![Page 24: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/24.jpg)
24
• Test Values – Electrical • Pickup values and trip characteristic should be as specified
and within manufacturer’s published tolerances. • Minimum pickup voltage on shunt trip and close coils should
be in accordance with manufacturer’s published data. In the absence of manufacturer’s published data, refer to Neta Table 100.20.
• Auxiliary features should operate in accordance with manufacturer’s published data.
Air, Low- Voltage Power Circuit Breakers
![Page 25: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/25.jpg)
25
Circuit Breakers, Air, Medium-Voltage
![Page 26: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/26.jpg)
26
• Visual and Mechanical Inspection • Inspect physical and mechanical condition. • Verify that all maintenance devices are available for
servicing and operating the breaker. • Perform operator analysis (first-trip) test. • Prior to cleaning the unit, perform as-found tests, if required. • Inspect arc chutes. • Inspect moving and stationary contacts for condition, wear,
and alignment.
Circuit Breakers, Air, Medium-Voltage
![Page 27: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/27.jpg)
27
• Visual and Mechanical Inspection • If recommended by manufacturer, slow close/open breaker
and check for binding, friction, contact alignment, contact sequence, and penetration.
• Verify that contact sequence is in accordance with manufacturer’s published data.
• Perform all mechanical operation tests on the operating mechanism in accordance with manufacturer’s published data.
Circuit Breakers, Air, Medium-Voltage
![Page 28: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/28.jpg)
28
• Visual and Mechanical Inspection • Inspect bolted electrical connections for high resistance
using one or more of the following methods: • Use of a low-resistance ohmmeter, verify tightness of
accessible bolted electrical connections by calibrated torque-wrench or perform a thermographic survey.
• Verify cell fit and element alignment. • Verify racking mechanism operation.
Circuit Breakers, Air, Medium-Voltage
![Page 29: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/29.jpg)
29
• Visual and Mechanical Inspection • Inspect puffer operation. • Use appropriate lubrication on moving current-carrying parts
and on moving and sliding surfaces. • (Optional) Perform time-travel analysis. • Perform as-left tests. • Record as-found and as-left operation-counter readings.
Circuit Breakers, Air, Medium-Voltage
![Page 30: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/30.jpg)
30
• Electrical Tests • Perform resistance measurements through bolted
connections with a low-resistance ohmmeter. • Perform insulation-resistance tests for one minute on each
pole, phase-to-phase and phase-to-ground with the circuit breaker closed, and across each open pole. Apply voltage in accordance with manufacturer’s published data. In the absence of manufacturer’s published data, use Table 100.1.
Circuit Breakers, Air, Medium-Voltage
![Page 31: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/31.jpg)
31
• Electrical Tests • Perform a contact/pole-resistance test. • With the breaker in a test position, perform the following
tests: • Trip and close breaker with the control switch. • Trip breaker by operating each of its protective relays. • Verify mechanism charge, trip-free, and antipump functions. • (Optional)Perform minimum pickup voltage tests on trip and
close coils
Circuit Breakers, Air, Medium-Voltage
![Page 32: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/32.jpg)
32
• Electrical Tests • (Optional) Perform power-factor or dissipation-factor tests
with breaker in both the open and closed positions and each bushing equipped with a power-factor/capacitance tap. In the absence of a power-factor/ capacitance tap, perform hot-collar tests.
• (Optional) Perform a dielectric withstand voltage test on each phase with the circuit breaker closed and the poles not under test grounded. Test voltage should be in accordance with manufacturer’s published data or Neta Table 100.19.
Circuit Breakers, Air, Medium-Voltage
![Page 33: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/33.jpg)
33
• Electrical Tests • Verify blowout coil circuit continuity. • Verify operation of cubicle space heaters.
• Test Values – Visual and Mechanical • Compare first-trip operation time and trip-coil current
waveform to manufacturer’s published data. In the absence of manufacturer's published data, compare first-trip operation time and trip coil current waveform to previously obtained results.
Circuit Breakers, Air, Medium-Voltage
![Page 34: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/34.jpg)
34
• Test Values – Visual and Mechanical • Compare bolted connection resistance values to values of
similar connections. Investigate values which deviate from those of similar bolted connections by more than 50 percent of the lowest value.
• Bolt-torque levels should be in accordance with manufacturer’s published data.
• Results of the thermographic survey. • Compare travel and velocity values to manufacturer’s
published data and previous test data.
Circuit Breakers, Air, Medium-Voltage
![Page 35: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/35.jpg)
35
• Test Values – Visual and Mechanical • Operations counter should advance one digit per close-open
cycle.
• Test Values – Electrical • Compare bolted connection resistance values to values of
similar connections. Investigate values which deviate from those of similar bolted connections by more than 50 percent of the lowest value.
Circuit Breakers, Air, Medium-Voltage
![Page 36: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/36.jpg)
36
• Test Values – Electrical • Insulation-resistance values of circuit breakers should be in
accordance with manufacturer’s published data. In the absence of manufacturer’s published data, use Neta Table 100.1. Values of insulation resistance less than this table or manufacturer’s recommendations should be investigated.
• Microhm or dc millivolt drop values shall not exceed the high levels of the normal range as indicated in the manufacturer’s published data. If manufacturer’s data is not available, investigate values that deviate from adjacent poles or similar breakers by more than 50 percent of the lowest value.
Circuit Breakers, Air, Medium-Voltage
![Page 37: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/37.jpg)
37
• Test Values – Electrical • Breaker mechanism charge, close, open, trip, trip-free, and
antipump features shall function as designed. • Minimum pickup for trip and close coils shall be in
accordance with manufacturer’s published data. • Power-factor or dissipation-factor values shall be compared
with previous test results of similar breakers or manufacturer’s published data.
Circuit Breakers, Air, Medium-Voltage
![Page 38: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/38.jpg)
38
• Test Values – Electrical • Power-factor or dissipation-factor and capacitance values
should be within ten percent of nameplate rating for bushings. Hot collar tests are evaluated on a milliampere/milliwatt loss basis, and the results should be compared to values of similar bushings.
• If no evidence of distress or insulation failure is observed by the end of the total time of voltage application during the dielectric withstand voltage test, the circuit breaker is considered to have passed the test.
Circuit Breakers, Air, Medium-Voltage
![Page 39: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/39.jpg)
39
• Test Values – Electrical • The blowout coil circuit should exhibit continuity. • Cubicle space heaters should be operational.
Circuit Breakers, Air, Medium-Voltage
![Page 40: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/40.jpg)
40
Circuit Breakers, Vacuum, Medium-Voltage
![Page 41: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/41.jpg)
41
• Visual and Mechanical Inspection • Inspect physical and mechanical condition. • Inspect anchorage, alignment, and grounding. • Verify that all maintenance devices are available for
servicing and operating the breaker • (Optional)Perform operator analysis (first-trip) test. • Prior to cleaning the unit, perform as-found tests, if required. • Clean the unit. • Inspect vacuum bottle assemblies.
Circuit Breakers, Vacuum, Medium-Voltage
![Page 42: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/42.jpg)
42
• Visual and Mechanical Inspection • Measure critical distances such as contact gap as
recommended by the manufacturer. • If recommended by the manufacturer, slow close/open the
breaker and check for binding, friction, contact alignment, contact sequence, and penetration.
• Perform all mechanical operation tests on the operating mechanism in accordance with manufacturer’s published data.
Circuit Breakers, Vacuum, Medium-Voltage
![Page 43: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/43.jpg)
43
• Visual and Mechanical Inspection • Inspect bolted electrical connections for high resistance
using one or more of the following methods: • 1. Use of a low-resistance ohmmeter. • 2. Verify tightness of accessible bolted electrical connections
by calibrated torque-wrench method in accordance with manufacturer’s published data. In the absence of manufacturer’s published data, use Neta Table 100.12.
• 3. Perform a thermographic survey
Circuit Breakers, Vacuum, Medium-Voltage
![Page 44: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/44.jpg)
44
• Visual and Mechanical Inspection • Verify cell fit and element alignment. • Verify racking mechanism operation. • Inspect vacuum bellows operation. • Use appropriate lubrication on moving current-carrying parts
and on moving and sliding surfaces. • Perform time-travel analysis. • Perform as-left tests. • Record as-found and as-left operation counter readings.
Circuit Breakers, Vacuum, Medium-Voltage
![Page 45: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/45.jpg)
45
• Electrical Test • Perform resistance measurements through bolted
connections with a low-resistance ohmmeter. • Perform insulation-resistance tests for one minute on each
pole, phase-to-phase and phase-to-ground with circuit breaker closed and across each pole with the breaker open. Apply voltage in accordance with manufacturer’s published data. In the absence of manufacturer’s published data, use Table 100.1.
Circuit Breakers, Vacuum, Medium-Voltage
![Page 46: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/46.jpg)
46
• Electrical Test • (Optional)Perform insulation-resistance tests on all control
wiring with respect to ground. • Perform a contact/pole-resistance test. • With breaker in a test position, perform the following tests: • 1. Trip and close breaker with the control switch. • 2. Trip breaker by operating each of its protective relays. • 3. Verify mechanism charge, trip-free, and antipump
functions.
Circuit Breakers, Vacuum, Medium-Voltage
![Page 47: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/47.jpg)
47
• Electrical Test • (Optional) Perform minimum pickup voltage tests on trip and
close coils. • (Optional) Perform power-factor or dissipation-factor tests on
each pole with the breaker open and each phase with the breaker closed.
• (Optional) Perform power-factor or dissipation-factor tests on each bushing equipped with a power-factor/capacitance tap. In the absence of a power-factor/ capacitance tap, perform hot-collar tests.
Circuit Breakers, Vacuum, Medium-Voltage
![Page 48: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/48.jpg)
48
• Electrical Test • Perform a vacuum bottle integrity (dielectric withstand
voltage) test across each vacuum bottle with the breaker in the open position in strict accordance with manufacturer’s published data.
• (Optional) Perform a dielectric withstand voltage test on each phase with the circuit breaker closed and the poles not under test grounded. Test voltage should be in accordance with manufacturer’s published data. In the absence of manufacturer’s published data, use Neta Table 100.19.
Circuit Breakers, Vacuum, Medium-Voltage
![Page 49: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/49.jpg)
49
• Test Values – Visual and Mechanical • Compare first-trip operation time and trip-coil current
waveform to manufacturer’s published data. In the absence of manufacturer's published data, compare first-trip operation time and trip coil current waveform to previously obtained results.
• Mechanical operation and contact alignment should be in accordance with manufacturer’s published data.
• Compare bolted connection resistance values to values of similar connections. Investigate values which deviate from those of similar bolted connections by more than 50 percent of the lowest value.
Circuit Breakers, Vacuum, Medium-Voltage
![Page 50: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/50.jpg)
50
• Test Values – Visual and Mechanical • Bolt-torque levels should be in accordance with
manufacturer’s published data. In the absence of manufacturer’s published data, use Neta Table 100.12.
• Results of the thermographic survey. • Compare travel and velocity values to manufacturer’s
published data and previous test data. • Operation counter should advance one digit per close-open
cycle.
Circuit Breakers, Vacuum, Medium-Voltage
![Page 51: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/51.jpg)
51
• Test Values – Electrical • Compare bolted connection resistance values to values of
similar connections. Investigate values which deviate from those of similar bolted connections by more than 50 percent of the lowest value.
• Insulation-resistance values of circuit breakers should be in accordance with manufacturer’s published data. In the absence of manufacturer’s published data, use Table 100.1.
Circuit Breakers, Vacuum, Medium-Voltage
![Page 52: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/52.jpg)
52
• Test Values – Electrical • Microhm or dc millivolt drop values shall not exceed the high
levels of the normal range as indicated in the manufacturer’s published data. If manufacturer’s data is not available, investigate values that deviate from adjacent poles or similar breakers by more than 50 percent of the lowest value.
• Breaker mechanism charge, close, open, trip, trip-free, and antipump features shall function as designed.
Circuit Breakers, Vacuum, Medium-Voltage
![Page 53: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/53.jpg)
53
• Test Values – Electrical • Minimum pickup for trip and close coils shall be in
accordance with manufacturer’s published data. In the absence of data use NetaTable 100.20.
• Power-factor or dissipation-factor values shall be compared to manufacturer’s published data. In the absence of manufacturer’s published data the comparison shall be made to similar breakers.
Circuit Breakers, Vacuum, Medium-Voltage
![Page 54: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/54.jpg)
54
• Test Values – Electrical • Power-factor or dissipation-factor and capacitance values
should be within ten percent of nameplate rating for bushings. Hot collar tests are evaluated on a milliampere/milliwatt loss basis, and the results should be compared to values of similar bushings.
• If no evidence of distress or insulation failure is observed by the end of the total time of voltage application during the vacuum bottle integrity test, the test specimen is considered to have passed the test.
Circuit Breakers, Vacuum, Medium-Voltage
![Page 55: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/55.jpg)
55
• Test Values – Electrical • If no evidence of distress or insulation failure is observed by
the end of the total time of voltage application during the dielectric withstand voltage test, the test specimen is considered to have passed the test.
• Heaters should be operational.
Circuit Breakers, Vacuum, Medium-Voltage
![Page 56: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/56.jpg)
56
• We discussed the definition and history of circuit breakers. • We addressed the Neta MTS maintenance standards for the
following circuit breaker types: • Low voltage air circuit breakers. • Medium voltage air circuit breakers. • Medium voltage vacuum breakers. • In future we will discuss oil circuit breakers of all voltage
classes as well as SF6 gas breakers.
Summary
![Page 57: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/57.jpg)
57
Save the Date for Our Next Webinar
Tuesday September 18, 2018 at 1pm – 2pm CDT Title: Vacuum Interrupter Technology
Presented by: Greg Richmond AVO Training Specialist - Instructor
![Page 58: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/58.jpg)
58
Megger®RecommendedEquipment
n EGIL • For substations 245kV and below • Vacuum CBs, OCBs, and gang operated
SF6 CBs • CBs with 1 break per phase and 1 operating
mechanism (gang op)
n TM1800 • 765kV substations and below • Can be used on all circuit breakers • 16 main and 16 Resistor contacts
per phase • Gang operated or IPO • OCBs, SF6, Vacuum, GIS,
Airblast… • Dualground™ testing
n CABA Win • Interfaces with EGIL, TM1600,
TM1700, and TM1800 • Detailed CB analysis and
comparison to historical tests • Simple consistent testing • Fully customizable testing with
Test Plan Editor (TPE)
n DLRO 100 • 100A micro ohmmeter • Smooth DC output • Programmable ramp up, time on, ramp down,
and output current • Battery and line operated
![Page 59: Fundamentals of Circuit Breaker Maintenance...manufacturer’s published data, use Neta Table 100.12. • Results of the thermographic survey. • Settings shall comply with coordination](https://reader030.fdocuments.in/reader030/viewer/2022040323/5e6ace20788c9b7e8616ef0b/html5/thumbnails/59.jpg)
59
Questions? After more than 50 years, AVO Training remains a global leader in safety and maintenance training for the electrical industry. We deliver an engaging, hands-on experience for our clients in a professional, real-world environment. We strive to provide industry relevant courses in a practical and flexible learning environment through an ongoing commitment to quality service, integrity, instruction, and client satisfaction. Our goal is to convey practical job skills and career development for our clients and students by saving lives through a world-class learning experience.