Fuling Inverter User Manual

download Fuling Inverter User Manual

of 54

Transcript of Fuling Inverter User Manual

Chapter 1 Safety and Cautions Chapter 2 Product Introduction Chapter 3 Mechanical and Electrical Installation Chapter 4 Operation and Display Chapter 5 Function Parameters List Chapter 6 Parameter DescriptionF0 Basic Function Parameters F1 Motor Parameters F2 Input and Output Terminal Function Parameters F3 Human Machine Interface Parameters F4 Application Function Parameters F5 Protection Pa rameters F6 Communication Parameters

1 6 7 17 22 34 34 42 46 54 57 66 69 73 81 82 85 98 100

Chapter 7 Fault Diagnosis and CountermeasuresChapter 8 Quality GuaranteeAppendix A Standard Specifications Appendix B Serial Communications Appendix C Dimensions Appendix D Accessories List

DZB Series

Preface

PrefaceThank you for choosing DZB Series high-performance AC Motor Drives. DZB200&300 Series are manufactured by adopting high-quality components, material and incorporating the latest microprocessor technology availa ble. Ge tting Started This manual will be helpful in the installation, parameter setting, troubleshooting, and daily maintenance of the AC motor drives. To guarantee safe operation of the equipment, read the fo llowing safety guideline s before connecting power to the AC drives. Keep this operating manual handy an d distribute to all users for refere nce.

! WARNINGATTENTION: Always read this manual thoroughly before using DZB series AC Motor Drives. DANGER! AC input power must be disconnected before any maintenance. WARNING! Do not c onnect or disconnect wires and connectors while power is applied tothe circuit.Maintenance must be performed by qualified technicians.

WARNING! To avoid personal injury, do not remove the cover of the AC motor drive until all of thedigital keypad "DISPLAY LED" lamps are off . The DC-link capacitor remains charged with a ha zardous voltage even after input power is removed.

ATTENTION: Grounding the DZB100B drive is done by c onnecting the Earth Ground to the driveground terminal .

CAUTION: There are highly sensitive components on the printed circuit boards. These components areespecially sensitive to ESD (electrostatic discharge). To avoid damage to the drive ,do not touch components or the circuit boards until static control precautions have been taken.

CAUTION: Never connect the main circuit output terminals U, V, and W directly to the AC main circuitpower supply as this will damage the drive.

CAUTION: Do not apply the antirust to screws for fastening drives; Please cle an the drives and screwswith dry c loth or alcohol, not with synthetic cleaner. Fasten the screws with washers and rated torque lest the enclosure corners of drive s be distorted.

This manual is for DZB20 0&DZB300 Series AC Motor Drive.

-1-

DZB Series

Chapter 1 Safety and Cautions

DZB Series

Chapter 1 Safety and Cautions

Chapter 1 Safety and CautionsNote

Safety DefinitionThere are two kinds of safety cautions in the manual: Operations which are not performed according to the requirements may cause severe hurt or even death. Operations which are not performed according to requirements may cause moderate hurt or light hurt or equipment damage.

Danger

Do not connect the input terminals with the output termina ls (U, V, W), otherw ise the inverter may be damaged! Ens ure the wiring mee t the EMC requirements and the local safety standard. The wire size shall be det ermined according to the manual, otherwise accident may occur! Brake resistor must not be connected between the DC bus terminals (+) and (-), otherwise fire may occur!

Note

1.1 Safety Cautions1.Before Installation

4. Before Power-o nDanger

Danger

Do not use the inverter that is damaged or has defec t, or there will be danger of injury.

Pleas e confirm the mains voltage level is c onsistent with that of the inverter and the input and output wirings are correct, and check if there is any short circuit in peripheral circuit and if the wiring is fixed and fast, otherwise the inverter may be damaged! Mount the cover plate properly before power-on the inverter, otherwise there will be danger of electric shock.

2.During InstallationDanger

Note

Mount the inverter on incombustible surface like metal, and keep awa y from flammable substances! Otherwise it may cause fire.

Note

Dielectric strength test had been done at factory. Therefore, user needs not do this test again, otherwise accident may occur! All the peripheral parts shall be connected correctly according to the manual, or accident may occur!

When more than two inverters are to be installed in one cabinet, ple ase pay attention to the installation locations to ensure the cooling effect (refer to Chapter 3 Mechanical and Ele ctrical Installation). Do not drop the lead wire stub or screw in the inverter, or the inverter may be damaged.

5.After Power-on

Danger

3.WiringDanger

Only the qualified electrical engineer can perform the wiring, otherwise there will be danger of electric shock. A circuit breaker must be installe d between the mains and the inverter, otherwise there w ill be danger of fire. Wiring can only be done after the mains input is cut off, otherwise there will be danger of electric shock. Please connect the inverter to the ground according to the standard, otherwise there will be danger of electric shock.

Do not open the cover of the inverter after power-on, otherw ise there will be danger of electric shock! Do not touch the inverter and its circuit with wet hand, other wise there will be danger of electric shock. Do not touch the inverter terminals, otherw ise there will be danger of electric shock. At power-on, the inverter will perform the security check of the external heavy-current circuit automatically, so at this time please do not touch the terminals U, V and W, or the terminals of motor, otherwise there will be danger of electric shock.

- 1-

- 2-

DZB Series

Chapter 1 Safety and Cautions

DZB Series

Chapter 1 Safety and Cautions

1.2 CautionsNote

1. Check the Insulation of the Motor

If parameter identification is required, please pay attention that the rotating motor may injure people, otherwise ac cident may occur! Do not change the factory settings, otherwise the inver ter may be damaged!

When the motor is used for the first time, or reused after storing for a long time, or in regular checkup, the user mus t check the insulation of the motor to prevent the poor insulation of the windings of motor from damaging the inverter. The motor connection must be divided from the inverter during the insulation che ck. It is recommended to use a 500V Mega-Ohm-Meter to check and the insulation resistance shall not be less than 5M. 2. Thermal P rotection of Motor If the rated capacity of the motor selected is not matching that of the inverter, espec ially when the rated power of the inverter is bigger than that of the motor, make sure to adjust the parameters for motor protection inside the inverter or to install a thermal relay to the motor to guarantee the protection to the motor. 3. Running a t Frequency Above Rated Frequency The output frequency of this inverter is 0~600Hz. Please consider the capability of the mechanical devices whe n the customer needs the inverter to run at the frequency higher than 50Hz . 4. Motor He at and Noise Since the output voltage of the inverter is in PWM wave with some harmonics, the temperature may rise, the noise and vibration may increase compared with the inverter running at main frequency. 5. Pressure-sensitive Device or Capacitor at the Output Side of the Inverter Because the inverter outputs PWM wave, the capacitor used for improving power factor and pressuresensitive res istor used for lightening-proof shouldn't be installed at the output side of the inverter, otherwise the inverter may have transient over-current and may be damaged. 6. Switches Used at the Input a nd Output terminal of the Inverter If the contactor is required to be installed betw een the inverter and the power supply, it is prohibited to start or stop the inverter with the contactor. If the user has to use the contactor to start a nd stop the inverte r, the interval between the start and stop shall be less than one hour. Frequent charging and discharging ma y reduce the life of the capacitor. If the switches like contactors are connected between the output terminal and the motor, make sure to start and stop the inverter when the inverter has no output, otherwise the modules in the inverter may be damaged. 7. Usage Outside the Range of Rated Voltage The DZB series inverter shall not be used out of the specified range of operation voltage, otherwise the internal components of the inverter may be damaged. If needed, please use corresponding voltage regulation device to change the voltage. 8. 3-phase Input Modified Into 2-phase Input The modification of DZB series inverter from 3-phase input to 2-phase input is not allowed, or fault may occur. 9. Lightning Strike Protection There are lightning protection devices inside the inverter, But the user should install other lightning protection device at the front end of the inverter if lightning strike occurs frequently. 10. Altitude and Deration When the altitude is higher than 1000m, the cooling effect of inverter is deteriorated because of the rarefaction of air, the deration must be used and please consult our company for detailed technical support.

6. Running

Danger

Do not approach the equipment when restart function is enabled, otherwise there w ill be danger of injury. Do not touch the fan and the discharging resistor to check the temperature, otherwise burning may occur! Non-prof essional person shall not measure the signal of a running inverter, otherwise there will be danger of injury or damaging the inverter!

Note

Do not let objects fall in a running inverter, otherwise the inverte r may be damaged! Do not start and stop the inverter by on/off of the contactor, othe rwise the inverter may be damaged!

7. Maintenance

Danger

Please do not repair or maintain the inverter with power on, otherwise there will be danger of electric shock! Please repair or maintain the inverter after confirming the charge LED turns off, otherwise there may be human injury caused by the residual voltage of the capacitor! Only qualified electrical engineer can repair or maintain the inverter, otherwise there will be danger of human injury or damaging the equipment.

- 3-

- 4-

DZB Series

Chapter 1 Safety and Cautions

DZB Series

Chapter 2 Product Introduction

11. Special Usages The user can consult our company if he wants to use another method instead of the recommended connecting method provided in the manual, such as shared DC bus. 12. Cautions for Scrap of Inverter The electrolytic capacitors in the main circuits and PCB may explode when they are burned a nd poisonous gas may be generated when the plastic parts are burned. Please dispose the inverter as industrial rubbish. 13. About Applicable M otor 1) The standard motor used is the 4-pole squirrel cage asynchronous induction motor. If other kind of motor is used, please be sure to select the applicable inverter according to the rated current of the motor, and please consult us if the user wants the inverter to drive the permanent magnetic synchronized motor. 2) The cooling fan of non-variable frequency motor is connected to the rotor in the same bearing, so the cooling effect is weakened if the speed is low, therefore use the variable-fr equency motor or install a cooling fan in the overheat condition the motor. 3) The inverter has already been configured with the standard parameters for applicable motor, please be sure to modify the default values or perform the motor parameter identification according to the actual conditions, otherwise the oper ation effect or prot ection performance may be reduced. 4) Short-circuit in the cable or motor may cause the inve rter alarm or even damage the inverte r. Therefore, please conduct the insulation short-circuit test to the cable and the motor installed for the first time. The shor t-circuit test shall also be carried out in routine maintenance. Pay attention that the inverter shall be separated from the unit during such test. The purpose of this chapter is to provide specific, yet simple information to unpack , install the AC drive. This chapter contains information on the following:

Chapter 2 Product Introduction

2.1 Receiving, Transportation, and Storage 2.2 Nameplate Information

2.1 Receiving, Storage and TransportationThe AC motor drive has gone through rigorous quality control tests at the factory before shipment. After receiving the AC drive, check for the following.

Receiving1.Che ck to make sure that the package includes an AC drive,the User Manual,dust covers and bushings. 2.Inspect the unit to insure it was not damaged during shipment. 3.Make sure that the part number indicated on the nameplate corresponds with the part number of your order. rubber

StorageThe AC Drive should be kept in the shipping carton before installation. In order to retain the warranty cove rage, the AC drive should be stored properly when it is not to be used for an extended period of time. Some storage suggestions are:

1.Store in a clean, dry location. 2.Store within an ambient te mperature range of -20C to +65C. 3.If possible, store in an air-conditioned environment where the relative humidity is less than 95% , non-condensing. 4.Do not store the AC drive in places where it coul d be exposed to corrosive gases. 5.Please store the AC drive on a shelf or on an stable surface.

Transpo rtationTempe rature: -25C to +70C; R.H.: 0% to 95%; Air Pressure: 70kPa to 106kPa.

- 5-

- 6-

DZB Series

Chapter 2 Product Introduction

DZB Series

Chapter 3 Mechanical and Electric al Installation

Chapter 3 Mechanical and Electrical Installation2.2 Nameplate Information3.1 Mechanical InstallationNameplate

1. Installation Environment 1) Ambient temperature: Ambient temperature influences the inverter life grea tly, so it should be w ithin the range of -10~50. 2) Mount the inverter in a flame retardant surface and the clearance around the inverter shall be enough because the inverter will generate lots of heat during running, besides mount the inverter on the base vertically with screws. 3) Mount in the location where vibration is less than 0.6G; the inverter shall be far away from impa cting lathe. 4) Please do not install the inverter in the place with direct sunlight, high humidity and water. 5) Mount the inverter in the location free of corrosive gas, e xplosive gas or combustible gas. 6) Mount the inverter in the location free of oil dirt, dust, and metal powder.Description ofACMotor Drive Model:

2.Installation Location up

DZB300

B

0015

L 4 AFunction level code: A -braking unit inside B -non braking unit Input vol tage2-220V 4-400V 6-660V Freq. Range L0-600.0Hz Applicable motor capacity0015 1.5KW SeriesB: General-Purpose Model P:Fan&Pump Model Series name : DZB300 Series

1 0 0mm DZB A D ZB A

right

DZB 1 0 0mmNote: No need to consider the dimension A for inverter of 22kW or below. A shall be bigger than 50mm for the inverter of 22kW or above Note: Install an airflow- guidance plate for the up and down installation of inverters.

Description of Serial Number::

06 10 8888Production number Production month Production year

Installation of single inverter

Up and down installation of inverters

Fig.3-1 DZB Series Inverter Installation Location The user shall focus on the heat dissipation i ssues when installing the inverter, and pay attention to the following points: 1) Ins tall the inverter vertically so that the heat may be expelled from the top, but do not install the inverter upside down. When two Variable Speed Drives are mounted up and dow n, an air flow diverting plate should be fixed in between as shown in Fig. 3-1. 2) Ins tallation space is shown in Fig.3-1 so as to ensure the heat dissipation space, but consider the heat dissipation of other components when placing the inverter. 3) The installation bracket must be flame ret ardant. 4) Ins tall the heat sink outside of the cabinet if the inverter is installed in the area with metal powder. And i n this case, the space inside the sealing cabinet shall be big enough.

- 7-

- 8-

DZB Series

Cha pter 3 Mechanical and Electrical Installation

DZB Series

Chapter 3 Mechanical and Electric al Installation

3.2 Electrical Installation2. Wiring Diagram of Peripheral Equipment 1.Applicable devices and recommendable wiring of main circuit:MODEL Applicable Motor DZB300 (KW) Series0005L2 0007L2 0015L2 0022L2 0037L2 0007L4 0015L4 0022L4 0037L4 0055L4 0075L4 0110L4 0150L4 0185L4 0220L4 0300L4 0370L4 0450L4 0550L4 0750L4 0930L4 1100L4 1320L4 1600L4 1870L4 2000L4 2200L4 2500L4 2800L4 3150L4 4000L4 5000L4 6300L4 0.55 0.75 1.5 2.2 3.7 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 93 110 132 160 187 200 220 250 280 315 400 500 630 DZ20-800(800A) CJ20-800 DZ20-630(600A) DZ20-400(400A) DZ20-630(500A) CJ20-630 120*2(240) 120*2(240) 150* 2(300) 150 *2(300) 35 *2(70) 50* 2(100) 50* 2(100)G rounding M otor

INPUT(RST) Air Circu it Breakers MCCB

Wire Size(mm 2)

Pow er Supply

Ma gnetic Contactor MC

Power Terminal

DC Reactor

Breaking Terminal

Control TerminalBreaker or Leakage Sw itch

1.5 DZ20-100(16A) CJ20-16 2.5 4

1.5 2.5

DZ20-100(32A)

CJ20-40

4

6

4M agnetic Contact or( M C)

1.5 DZ20-100(16A) CJ20-16 2.5 4

1.5

2.5Input AC Reacto r(AC)

DZ20-100(32A)

4 6 6 4 CJ20-40 8 8 10 CJ20-63 16 16 CJ20-100 6Inpu t Side Interference Filte r

Braking Resis tor

DZ20-100(50A)

DZ20-100(63A) DZ20-100(80A) DZ20-100(100A)

Pow e r-factor-im proving D C Reactor(D C)

0.5

25 35

25 25* 2(50) 35* 2(70) 50 *2(95)

Inverter0.7510 16O utput AC Reactor(AC ) G rounding

DZ20-200(200A)

CJ20-160

25*2(50) 35*2(70)

DZ20-400(250A) CJ20-250 DZ20-400(350A)

50*2(95)

25 70 *2(150)

CJ20-400

70 *2(150) 95 *2(185)

70*2(150) 95*2(185)

16 *2(35)O utput Side N oise Filter

25 *2(50)

DZ20-1250(1000A) CJ20-500*2 185*2(370) 185 *2(370) DZ20-1250(1250A) CJ20-630*2 185*2(370) 185*2(370)

- 9-

- 10-

DZB Series

Cha pter 3 Mechanical and Electrical Installation

DZB Series

Chapter 3 Mechanical and Electric al Installation

3. Basic Wiring DiagramUsers must conne ct wires according to the following circuit diagram show n below.

4. Main Circuit Terminals and WiringDanger

DC Link Reactor (option)Use a disconnect and fuse Power source R 3 phase 200-240V or S 380-480V 50/60Hz

P1 DC+ R (BR+) S T

P2 No te: DC(BR-) U

Wiring can only be done after the mains input is cut off, otherwise there will be danger of electric shock! O nly qualified and trained engineer can perform the wiring, otherwise there will be danger of elect ric shock! G rounding cable must be grounded, otherwise there will be danger of electric shock or fire!

~Danger Grounding

M

T

Multi-func tion input 1 Multi-func tion input 2 Multi-func tion input 3 Multi-func tion input 4 Multi-func tion input 5 Multi-func tion input 6 Digital sig nal common

S1 S2 S3 S4 S5 S6 DCM

A C B

Multi-function indication output contact AC 250V 2A below DC 30V 2A below

( F2.21)Multi-function PHC output 48V 50mA below

Please confi rm the mains volta ge level is same with that of the inverter, otherwise the inverter may be damaged! Make sure the ratings of the driven motor are in compliance with the inverter, otherwise the motor may be damaged or the inverter may be in protection status! Do not confuse the input terminals with the output terminals (U, V, W), otherwise there will be danger of damaging the inverter! Brake resistor cannot be conne cted between the DC bus terminals (+) and (-), otherwise fire may occur!

(F2.19~F2.20)

1Ma in Cir c u it Te r min a ls o f I n ver te r

TerminalsRS T ( LN)FM ACM

De scriptionAC input line terminals Motor connection Connection for the br aking resistor (option) Connection for the br aking unit (option) Connection for the DC Link Reactor (option) G r ou nd

(F2.01~F2.06)DC 20 V ~ 24V ( 50mA Max. )

EV

+Analog frequency/ current meter DC0-10V

-

UV W B R + B R P 1 ( D C + )DC P 1P 2

Frequency setting 0~10VDC Vr:3k~5k Current input 4~20mA

3 2 1

10V VI CI ACM VI CI SG+ SG-

( F2.22)

Signal+ SignalRS-485 Serial interface

E

2N ot e s o n Wi r i ngA. Input power supply L and N or R, S and T: There is no phase-ration requirement for the input of inverter. B. DC bus (DC+) and (DC-) terminals: Pay attention that the DC bus terminals (DC+) and (DC-) still have voltage after power off, and the user can only touch the terminals after the CHARGE LED turns off and the voltage is below 36V, otherwise there is a danger of electric shock. When selecting the brake unit for the inverter above 18.5kW,pay attention that the polarity of (DC+) and (DC-) cannot be reverse, otherwise the inverter may burn or be damaged. The cable length of brake unit shall be less than 10m and twisted pair cables shall be used. Do not connect the brake resistor directly to the DC bus, otherwise the inverter may burn or be damaged.

shows main circuit

shows control circuit

Fig.3-3 Basic Wiring Diagram

NoteBreaking resistor terminals BR+/BR- f or the inverter of 15KW or below.B raking unit and DC Link Reactor terminals P1/P2/DC-for the inverter 18.5KW~30KW. B raking unit terminals(DC+/DC-)for the inverter above 37KW .

- 11-

- 12-

DZB Series

Cha pter 3 Mechanical and Electrical Installation

DZB Series

Chapter 3 Mechanical and Electric al Installation

C.Brake resistor terminals ofBR+ BR- The brake resistor terminal is effective only for the inverte r of 15kW or below and has a built-in brake unit. Select the recommended resistor w ith the cable length of less than 5m, otherwise the inverter may burn or be damaged. D. Inverter output U, V and W: Inverter output terminals cannot connect to capacitors or surge snub devices, otherwise the inverter may be in protective status or damaged. If the cables between the motor and the inverter are too long, electrical resona nce may occur due to the distributed capacitance, which may result in damaging the motor insulation or big leakage current, so if the cable length is longer than 100m, AC reactor must be installed. E. Grounding Terminal : Grounding Terminal must be connected to earth reliably and the grounding resistance shall be less than 5, otherwise the equipment may work abnormally or be damaged. Do not sha re the PE and neutral line of the mains supply.

3N ote s o n C on t rol Te r m in al s:

A) Analog input terminal: Since the weak analog voltage signal is easily disturbed by external disturbance source, shielded cable shal l be used and the c able shall be as short as possible and the length shall not exceed 20m, as shown in the figure 3-6:

Less than 20m

+10V DZBPotentionmeter

VI

ACM5. Control Terminals and Wiring 1Layout of Control Terminals(Fig.3-4,Fig3-5)A S1 B C 10V S4 V C FM AC M MO1 MO 2 MCM S5 S6 D C M EVCI

Fig. 3 -6 Analog Input Terminal of DZB Serie s Inverter If the analog signal is severely disturbed, filter capacitor or ferrite core shall be installed at the analog signal source as show n in the Fig. 3-7

S2 D C M S3S4 S5

SG + SG FM ACM SG+ SGA1 B1 A B C

S1 S2 DCM S3

S6 DCM EV MO1MCM 10V VI

2Function of Control Terminals Function Terminal MO 1-MCM Multi-function PHC output 1 MO 2-MCM Multi-function PHC output 2 Multi-function indication output co ntact Refer toF2.19F2.21 A-B Multi-function indication output co ntact B-C A1-B1 S1-DCM S2-DCM S3-DCM S4-DCM S5-DCM S6-DCM EV-DCM VI-ACM CI-ACM FM-ACM SG+,SGMulti-function indication output co ntact Multi-function input 1 Multi-function input 2 Multi-function input 3 Multi-function input 4 Multi-function input 5 Multi-function input 6 Auxiliary control power source Analog voltage input Analog current input Analog frequency/current meter DC 24V (50mA Max.) 0~10 V (Max. output freq.) Input4~20 mA (Max. output freq.) Input

Wind 2 - 3 turnsC

VI ACMFerrite core

External analog source0.022 uF50V

DZB

Fig. 3 -7 Analog Input Terminal With Filter devices

B) Digital input terminal: Refer to F2.00F2.06 The inverter judges the ON/OFF status of these terminals by receiving the digital signal. Hence, all the external contactors are those with high reliability of weak signal conduction. If the open collector is employed to provide ON/OFF signal for the inverte r digital input terminal, then it shall be considered that there is error operation caused by power supply interference. It is recommended to use contact control mode. C) Digital Output terminal: When digital output terminal drives a relay, the coil of the relay shall be installed a snubbing diode, othe rwise the DC 24V power supply may be damaged.

Serial communication interface 10V~ACM Power supply for speed setting

0 ~10 V (Max. output freq.) Output Refer to F2. 22 RS-485 serial port+10 V (20 mA max. output current)

- 13-

- 14-

DZB Series

Cha pter 3 Mechanical and Electrical Installation

DZB Series

Chapter 3 Mechanical and Electric al Installation

2) Reducing the disturbance to the inverter from other equipment

Note: Pay attention to the polarity of the diode as shown in the figure 3-8. Otherwise if the digital output terminal has output, the DC24V power supply will be damaged.

The re lay, contactor or electronic -magnetic braking device will disturb t he invert er. Take the following act ions to solve this issue: A) Install surge suppressing devices to the disturbing de vice B) Install filter to the input of t he inverter C) Inverter's c ontrol cables shall be shie lded and the shielding layer shall be grounded 3) Method to reduce the disturbance from the inverter to the equipment Two kinds of noises, one is the radiation from the inverte r itself, and another is the radiation from the

DZB300 EV

Relay

Diode

cable between the inverter and the motor. These two kinds of radiations induce the cables of the equipment and make the equipment work abnormally. Following method can be used: A) If t he measuring meters, radio equipment and sensors and their signal cables are install ed in a cabinet together with t he drive , these equipment cables will be easily dist urbed. Take the actions below to solve the problem: The equipment and the signal cables should be as far away from the inverter as possible; Signal cables and power cables shall not be routed in parallel or bound togethe r;

MO1

MCM

The signal and power cables should be shielded; Install r adio noise filter and linea r noise filter at the input and output sides of the inverter B) If the exter nal equipment shares a sa me AC supply wi th the inverter, and the above cannot eliminate

Fig. 3 -8 Digital Input Terminal of DZB Series Inverter6. EMC Issues 6 . 1 Influence of Harmonics 1) The high frequency harmonics of mains supply will influence the rectifying circuit of the inverter. The harmonics will heat the rectifying circuit and even damage the circuit. So, it is recommended to install the filtering device in the envir onment where the power quality is poor. 2) Since the inverte r output has high frequency harmonics, the output cannot be installed with capacitor or surge suppressing devices because the capacitor and surge suppressing device may resonate the circuit and damage the equipment. 6.2 EMI 1) Two kinds of EMI, one is the EMI a round the inverter and disturbs the inverter. This kind of EMI is weak, besides the inverter has been designed with strong immunity. Another is the EMI from the inverter that may influence the equipment around the inverter. The inverter itself is a disturba nce source because it outputs PWM wave through high carrier frequency, so solving the EMI issue is mainly to reduce the EMI of inverter. Methods: A) Inverter and other equipment shall be well grounded and the grounding resistance shall be less than 5ohm. B) Inverter's power cables shall be vertical instead of parallel with the control cables. C) For the application with strong disturbance, the powe r cables from the motor to the inverter shall be shielded and the shielding layer shall be grounded. D) The cables of disturbed equipment shall be twisted shielded cables and the shielding layer shall be grounded.

the disturbance, then t he user should install a linear filter or a radio noise filter. C) Ground the external equipment and e liminate the disturbance of the leakage current from the inverter's grounding ca ble. 6.3 Le akage current The inverter has two kinds of leakage current, one is the grounding leakage current and another is the leakage current between the lines: 1) Grounding leakage current: The distributed capaci tance exists betw een the cables and the ground, and the bigger the c apacitance and the bigger the leakage current, so the motor cables should be as short as possible. Besi des, the bigge r the carrier frequency is, the bigger the leakage current is, so the user can al so reduc e the carrier wave frequenc y, but the motor noise may increase. Insta lling rea ctor can also reduce the leakage current. The leakage current is increased with the increase of the circuit current, so the lea kage current is big if the motor power is big. 2) Lea kage current bet ween lines: The distributed capaci tance exists in the inverter output cable s, and resonance may occur if high frequency harmonics e xist in the current, thus the leakage current occurs, which may result in the wrong action of relay. The method to solve this issue is to reduce the carrier fre quency or install the output reactor. It is recommended to use inverter protection func tion instead of a thermal relay to protect the motor before using the inverter.

- 15-

- 16-

DZB Series

Chapter 4 Operation and Display

DZB Series

Chapter 4 Operatio n and Display

Chapter 4 Digital Keypad OperationRun

4.1

Description of the Digital Keypad D igital Keypad Par ts and FunctionsThis digital keypad module includes two parts: display panel and a keypad. The display pane l allow s the user to program the AC drive, a s well as view the different operating parameters. The keypad is the user interface to the AC motor drive. Refer to the following figure for a description of the different parts.

RUN

Used to s tart the AC drive operation. This key has no effect when the drive is set to terminal run. Stop

STOP

Used to s top the AC drive operation. If the AC drive has stopped due to a fault, press this button to reset the drive. Up / Down

RUN STOP JOG

Press the "Up" or "Down" button to change parameter settings.FWD REV

Function indicator

Digital display

These keys may also be used to scroll through different operating values or parameters.

Explanation of Screen DisplayUp and down keys

Forward / Reverse key

FWD REV

- 17-

PRGM RESET FUNC DATA

1. Explanation of Displayed Mes sages on Running status ( r efer to F3.05):Program key

JOGJog key

Displayed SymbolFunction / Data key

Displayed Message

OperationFUNC Press QUICK key DATA JOG

Sett ing frequency

RUNRun key

STOP

Stop / Reset key

Running frequency Output current

FUNC Press QUICK key DATA JOG

FUNC Press QUICK key DATA JOG

Fig. 4-1 Operation Panel Schematic Diagram

Output voltage

FUNC Press QUICK key DATA JOG

KeyPRGM RESETProgram / Reset First-stage menu entry or exit. Function / Data

Description

Running speed Output power Output torqueDisplays information on the AC drive status such as the reference frequency,output

FUNC Press QUICK key DATA JOG

FUNC Press QUICK key DATA JOG

FUNC Press QUICK key DATA JOG

DC bus voltage PID setpoint PID feedback Input terminal status Output terminal status VI value CI value Current segment of multi-speed control

FUNC Press QUICK key DATA JOG

FUNC DATA

frequency, or output current in the normal mode. While the drive is in the Program Mode, press this key once to display the current parameters. After changing the parameters, press this key again to store the new parameters. Forward / Reverse

FUNC Press QUICK key DATA JOG

FUNC Press QUICK key DATA JOG

FUNC Press QUICK key DATA JOG

FWD R EV

Used to toggle between forward and reverse operation. Pressing this key will cause the motor to ramp down to 0 Hz and then ramp up to the preset speed in the opposite direction. JOG/

FUNC Press QUICK key DATA JOG

FUNC Press QUICK key DATA JOG

FUNC Press QUICK key DATA JOG

JOG

Used to start the AC drive, then run at the jog frequency. When modify parameter, can select modified bit of the parameter.

FUNC Press QUICK key DATA JOG

- 18-

DZB Series2. Explanation of Displayed Messages on Stop status ( r efer to F3.05):Displayed Symbol Displayed Message Operation

Chapter 4 Operation and Display

DZB Series

Chapter 4 Operatio n and Display

Note: When operating 3-level menu, pressing PRG or DATA can return to second level menu. The difference is: pressing DATA will save the parameters and return to second le vel menu and then shift to the next function c ode, while pressing PRG will return to second level menu without saving the parameters. Example: Change the setting of F1.02 from 10.00Hz to 15.00Hz. (Bold means flash bit.)

Setting frequency DC bus voltage Input terminal status Out put terminal status PID setpoint PID feedback VI value CI value Current segment of multi-speed control

FUNC Press QUICK key DATA JOG

50.00P RG M RES ET PRGM RESET

FUNC Press QUICK key DATA JOG

FUNC Press QUICK key DATA JOG

FUNC Press QUICK key DATA JOG

F0

F1PRGM RESET

FUNC Press QUICK key DATA JOG

FUNC Press QUICK key DATA JOG

FUNC Press QUICK key DATA JOG

F1F UNC QUI CK DATA JO G

F1.03FU NC QUICK DATA J OG

FUNC Press QUICK key DATA JOG

FUNC Press QUICK key DATA JOG

F1. 00

15.00

4.2 Modify and Check the Function Codes DZB300 MD300 series inverters operation panel uses 3-level menu to conduc t parameter settings. 3-level menu: function parameter group (first level) function code (second le vel)setting of function code (third level). Operation procedure is shown in Fig. 4-2.

F1. 02

FU NC QUICK DATA JO G

JO G

10.00

10.00

Fig. 4-3 E xample for Parameter Changing In third level menu, if the parameter has no flash bit, it means the function code cannot be changed and the possible reasons are: 1) This parameter of this function code cannot be change d, such as the actually dete cted parameter and running record parameter. 2) This function code cannot be changed in operating status and can only be changed when the inverter is stopped.

50.00PRGM RESET PRGM RESET

Digital display

1 st level menu

F0FUNC QU ICK DATA JOG

Modify parameter group

4.3 How to View Status Param eters When DZB S eries inverter is in the stop or running status, several status parameter of the inverter can be displayed on the LED nixie tube. Pressing the keyDATA can display the stop or running status parameters. There are nine stop status parameters to be displayed in the stop status, Setting frequency,DC bus voltage,

PRGM RESET

2nd level menu

F0.07FUNC QU ICK DATA JOG

Modify function code

Input terminal status,Output te rminal status,PID setpoint,PID feedback, VI value,CI value,Current segment of multi-speed control . DZBSeries inverter has fif teen running status parameters to be displayed in the running status, Setting frequency,Running frequency,Output current,Output voltage,Running speed,Output power,Output torque, DC bus voltage,PID setpoint,PID feedback,Input terminal status,Output terminal status, VI value, CI value,

PRGM RESET

3 rd level menu 050.00

Modify value of function code

Current segment of multi-speed control . If the inverter is powered on again after power-off, the parameters displayed are defaulted as those selected before the power-off.

Fig. 4-2 Operation Procedures for 3-level Menu

- 19-

- 20-

DZB Series

Chapter 4 Operation and Display

DZB Series

Chapter 5 Function Parameters List

4.4 Password Setting DZB300 inverter provides password protection for users. When F3.00 is not zero, that is the user password, and the password protection function is valid once exiting the function code editing status. If the user presses PRG again, the inverter shall display ------, and the user can only enter the menu after inputting the user password. Otherwise, the user cannot enter. If the user wants to cancel the password protection function, F3.00 should be set 0. 4.5 Auto Tuning of Motor Parameters (Refe r to F1.11)NoteThis function is invalid for DZB200 Series.

Chapter 5 Function parameters listDZB300series inverter function parameters, which are grouped by functions, have F0-F6 total 7 groups. Each function group includes a number of function codes, which adopts three-stage me nu, for instance, F4.08means the 8th function code of F4th function. For the convenience of setting function code by using operation panel, the function group number is corresponding to Stage 1 menu, the function code is corresponding to Stage 2 menu and the function code parameter is corresponding to Stage 3 menu. 1. The column of function table is described as follows: The 1st column Function Code is the function parameter group and parameter code. The 2nd column Name is the complete name of the function pa rameter. The 3rd column Setting Range is the effective setting value ra nge of the function parameter, shown on the opera tion panel LCD. The 4th Default is the original factory setting value of this function parameter. The 5th Modification is the modification perf ormance of the function paramete r (i.e. whether or not it is permitted to modify and the modification c onditions), explained as follows, : indicates that the setting value of this parameter can be modified when the inverter is either in stop or ope rating status; : means that the setting value of this parameter cannot be modified when the inverter is in operating status; **: means that this parameter is a test value which cannot be modified. (Inverter has done the automatic detection restriction to the modification performance of each parameter, helping user to prevent mis-modific ation.) The 6th column Serial No is the number of function code at the storage inside. 2.Default indicates the value of the function c ode after it is refreshed while doing the manipulation of res toring the factory parameters; but the actually dete cted parameters or record values cannot be refreshed. 3.In order to effe ctively protect the parameters, the inverter provides the cryptoguard for the function code. Af ter the users password is set up (i.e. users password F3.00 parameter is not 0), when the user press PRG button to enter function code edit status, the system first enters the users password ve rification status, dis playing ----- , and the operator must input correctly the users password, otherwise it is impossible to enter. At the state that the cryptogua rd is not locked, the users password can be modified at any time, and the one finally input will be the users password. If F3.00 is set as 0, the users password can be cancelled; when the power is on, if F3.00 is not 0, parameters are protected by password. 4. When modify parameter using serial communic ation, usage of user password also abide above principle.

Before running the inverter that has sele cted the vector control mode, accurate motor nameplate parameters must be input to the inverter correctly. DZB300 inverter will configure the standard motor parameters according to the nameplate parameters. Vector control mode is highly dependent on the motor pa rameters and corre ct parameters must be acquired for achieving good control performance. Motor auto tuning procedures: Firstly set the comma nd source (F0.01) as the operation panel command channel. Then input the following parameters according to the actual parameters of motor: F1.01Rated power of motor F1.02Rated freque ncy of motor F1.03Rated speed of motor F1.04Rated voltage of motor F1.05Rated current of motor If the motor is disconnected from the load completely, select 1 (complete tuning) in F1.11, and press RU N in keypad, the inverter will calculate the parameters below automatically: F1.06Stator resistance F1.07Rotor inducta nce F1.08Leakage inductance F1.09Mutual inductance F1.10Excitation current with no load Motor tuning is finished automatically. If the motor cannot disconnect from its load, set F1-11 to 2(static tuning), and then press the RUN. The inverter will measure the stator resistance, rotor resistance and leakage inductance in sequence, but it will not calculate the mutual inductance and the excitation current with no load, and the user can us e the nameplate parameters that are rated voltage U, rated current I, rated frequency f and power factor to calc ulate these two pa rameters: The calc ulation methods of the motor current with no load and the mutual inductance are described as follows. Excitation current with no load: Mutual inductance calculation:

I 0 =I.1-2 L m = 23f . I -L6 0U

Where I 0 is the excitation current with no load, L m is the mutual inductance and L 6 is the leakage inductance.

- 21-

- 22-

DZB Series

Chapter 5 Function Parameters List

DZB Series

Chapter 5 Function Parameters List

Function Code

Name

Setting Range

Default Value

Modifi Serial cation No

Function Code

Name

Setting Range 2 Invalid durin g dece lerati on 0 Direct sta rt

Default Value

Modifi Serial cation No

F0 Basic Function ParametersF0.00 Control mode 0 Sp eed sensorl es s vector control (S VC) 1 V/F c ontrol 0 Ke yb oard F0.01 Comman d source selecti on 1 Term inal 2 Communi ca tion 0 Valid , a nd in ve rter memorize when power dow n F0.02 Keyboard a nd terminal UP/DOWN setting 1 Valid , a nd in ve rter does not mem orize when power down 2 Invalid 0 Ke yb oard 1 VI 2 CI F0.03 Frequency command Sele cti on 3 VI+ CI 4: Multi-speed 5: PID control 6: Communic ation F0.04 F0.05 F0.06 F0.07 F0.08 F0.09 Maximum o utput freq uency Upper limit frequ ency Lower limit frequ ency 10.00600.00Hz F0.06F0.04 0.00 HzF0.05 50.00Hz 50.00Hz 0.00Hz 50.00Hz 1 0.0s 1 0.0s 4. 5. F0.25 6. 7. Terminal command prote ction when po wer on 0 3. F0.2 0 F0.21 F0.2 2 F0.23 F0.2 4 F0.1 9 Stop Mode Begi nning Frequ en cy of brak ing Waiting ti me o f b ra king DC b ra king curre nt DC b ra king tim e De ad time between forward a nd reverse 0 2. F0.18 0 1. F0.15 F0.1 6 F0.1 7 Start fr eq uency Ho ld time of start frequ ency Braking c urrent be fore sta rting Braking time be fore sta rting 1 0. F0.1 4 Start Mod e

1 DC brakin g first and then start 2 Runnin g speed pick-u p and then start 0.0010.00Hz 0.050.0s 0.0150.0% 0.050.0s 0 DECEL Stop 1 Free ru n Sto p 0.00 F0.04 0.050.0s 0.0150.0% 0.050.0s 0.03600.0s 0 Term inal command in va lid when power on 1 Term inal command valid whe n po wer on

0

14.

0.5 0Hz 0.0s 0.0% 0.0s

15. 16. 17. 18.

0

19.

0.0 0Hz 0.0s 0.0% 0.0s 0.0s

20. 21. 22. 23. 24.

01

25.

Keyboard freq uency setting 0.00 HzF0.04 ACCEL time 1 DECEL time 1 0.13600.0s 0.13600.0s 0 Operati ng at default direction

F1 Motor Parameters8. 9. F1.0 0 F1.01 10. F1.0 2 F1.03 11. F1.0 4 Motor rated volta ge Motor rated current Motor sta tor resistance Motor rotor res istan ce Motor stator/ro tor induc tance F1.05 12. F1.0 6 F1.0 7 Inverter model Motor rated po wer Motor rated frequenc y Motor rated spee d 0 B mode l 1 P model 0.4900.0kW 0.01HzF0.04 0 36000rpm 0 460V 0.11000.0A 0.00165.535 0.00165.5 35 0.1 65 53.5 mH Set by mode l Set by mode l 50.00Hz Set by mode l Set by mode l Set by mode l Set by mode l Set by mode l Set by mode l 26. 27. 28. 29. 30. 31. 32. 33. 34.

F0.10

Operation d irection selecti on Carrie r frequenc y setting

1 Operati ng at reverse directio n 2 NO invers e operating

2

F0.11

1.015.0k Hz 0 NO ope ra tion

Set by model

F0.12

Functional parameters restoration

1 Restore default v alue 2Del ete failure r ec ords 0Inv ali d

0

F0.13

AVR sele cti on

1Val id all the time

1

13.

F1.08

- 23-

- 24-

DZB0 Series

Chapter 5 Function Parameters List

DZB Series

Chapter 5 Function Parameters List

Function Code F1.09 F1.10

Name Mutual inductance of motor sta tor/rotor No -l oad c urrent Self-learnin g of motor par ameters (Invalid for DZB200) Spee d loo p pr op or tional ga in1 Spee d loo p integral time1 Switching lo w po int frequenc y Spee d loo p pr op or tional ga in 2 Spee d loo p integral tim e 2 Switching high po int frequenc y VC slip compensating factor Up per torque limit setting V/F cur ve setting Torque boost Torque boost cut-o ff

Setting Range 0.16553.5mH 0.01655.35A 0NO operation 1comp lete tunin g Self-learning 2sta tic tu ning Se lf-learnin g

Default Value Set by model Set by model

Modifi Serial cation No

Function Code F2.05 F2.0 6

Name S5 Termi na l Function Sele ction S6 Termi na l Function Sele ction

Setting Range 6:Fr ee run stop 7:Failure reset

Default Value 12 13

Modifi Serial cation No

35. 36.

56. 57.

8:External fault input 9:Fr eq uency setting(UP)

F1.11

0

37. 10:Fre quency setting(DOWN) 11:Frequency up/down setting clear 12:Multi-Speed Terminal 1

F1.12 F1.13 F1.14 F1.15 F1.16 F1.17 F1.18 F1.19 F1.20 F1.21 F1.22 F1.23 F1.24

0100 0.0110.00s 0.00HzF1.1 7 0100 0.0110.00s F1.14F0.04 50%200%

30 0.50s 5.00Hz 25 1.0 0s 10.00Hz 100%

**

38. 39.

13:Multi-Speed Terminal 2 40. 41. 42. 43. 44. 45. 46. F2.0 7 0 20.0% 100% 0 47. 48. F2.08 49. F2.0 9 Energy Con se rv ati on Sele cti on 0:No Operation 1:Energy Conservation 50. F2.1 0 F2.11 5 1 2 4 7 51. 52. 53. 54. F2.1 6 55. F2.1 2 F2.13 F2.1 4 F2.15 UP/DOWN frequen cy in crem en t v ariable rate VI lowe r limit VI lowe r limit correspond ing setting VI upper limit VI upp er limit correspond ing setting VI inpu t filtering time CI lo wer lim it CI lo wer lim it correspond ing setting CIuppe r limit 14:Multi-Speed Terminal 3 15:ACCEL/DECEL Time selection 16:PID con trol pause 17:Tra ve rse pause at current frequency 18:Tra ve rse res et 19:ACCEL/DECEL forbid 2025:Reserved 0two-wire con trol 1 Terminal control mode 1two-wire con trol 2 2three-wi re control 1 3three-wi re control 2 0.0150.00Hz/s 0.00V10.00V -100.0%100.0% 0.00V10.00V -100.0%100.0% 0.00s10.00s 0.00V10.00V -100.0%100.0% 0.00V10.00V 0.50Hz/s 0.0 0V 0.0% 10.00V 100.0% 0.10s 0.0 0V 0.0% 10.00V 59. 60. 61. 62. 63. 64. 65. 66. 67. 0 58.

0.0200.0%(inver ter rated current) 150.0% 0Lin ear V/F curve 1square tor qu e V/F c urve 0.0%(auto) 0.1 30 .0 0

0.0% 50.0% (relative to motor rated frequency)

V/F slip compensation limit 0.0200.0%

F2 Input and Output Terminal Function Parame tersF2.00 F2.01 F2.02 F2.03 F2.04 On-off sig na l filte r tim es S1 Terminal Function Sele cti on S2 Terminal Function Sele cti on S3 Terminal Function Sele cti on S4 Terminal Function Sele cti on 110 0:No Function 1:Forward 2:Reverse 3:th ree-wir e c ontrol 4:Forward Jo gging 5:Rever se Jogging

- 25-

- 26-

DZB Series

Chapter 5 Function Parameters List

DZB Series

Chapter 5 Function Parameters List

Function Code F2.17 F2.18 F2.19 F2.20 F2.21

Name CI upper limit correspond ing s etting CI input filtering ti me Mo1output selection Mo2output selection Relay outp ut se lec tion

Setting Range -100.0%100.0% 0.00s10.00s 0NO output 1Frequency reache d 2FDT output 3Fault outpu t 4Motor running forward 5Motor running reverse 6Null speed operati ng 7Upp er limit frequency reach ed 8Low er limit frequency reach ed 910Reserved 0Setting frequency 1Run ning frequency 2Output curr ent 3Output voltage

Default Value

Modifi Serial cation No

Function Code

Name

Setting Range 0Keypad control valid 1Keypad and terminal control valid 2Keypad and communic ation control valid 3All control modes valid 0external keyboard preferentia l ENB 1Local and external keyboard simultaneous display, only external key-press is valid.

Default Value

Modifi Serial cation No

100.0% 0.10s 1 2 3

68. 69. F3.03 70. 71. 72.

STOP fun ction option

0

81.

F3.0 4

Key pad d is pla y op tio n

2Local panel and external keyboard simultaneous display, only Local key-press is valid. 3Local and external keyboard simultaneous display, and all key-presses are valid (both are OR logical relation) Displayed Message0:Setting frequ ency 1:Running freq uency 2:Output current

0

82.

Code 1 2 4 8 16 32 64 128 25 6 51 2 1024 2048 4096 8192 163841 2

F2.22

FM An alog outp ut sele ction

4Run ning sp eed 5Output power 6Output torq ue 7VI input value 8CI input value 910Reserved F3.05operation statu s display parameter option

0

73.

3:Output voltage 4:Running speed 5:Output power 6:Output torque 7:DC bus voltage 8:PID setpoint

255

83.

F2.23 F2.24 F2.25 F2.26

AO Lowe r limit Lower limit correspond ing AO output AO Uppe r limit Upper limit correspond ing AO output

0.0%100.0% 0.00V10.00V 0.0%100.0% 0.00V10.00V

0.0 % 0.00V 100.0% 10 .00V

74.9:PID feedbac k

75. 76. 77.

10:Input terminal status 11:Output terminal status 12:VI value 13:CI value

F3 Human Machine Interface ParametersF3.00 F3.01 F3.02 User pas sword Reserved Reserved 065535 0 78. 79.F3.0 6 Stop status display parameter option

14:Current segment of multi-speed control Setting frequency DC bu s voltage

255

84.

80.

- 27-

- 28-

DZB Series

Chapter 5 Function Parameters List

DZB Series

Chapter 5 Function Parameters List

Function Code

Name

Setting Range Input terminal status Output terminal status PID setpoint PID feedback VI value CI value Current segment of multi-speed control 4 8 16 32 64 128 256

Default Value

Modifi Serial cation No

Function Code

Name

Setting Range 18 :Communication fa ult(E01 8) 19 :Current detect e rror( E0 15 ) 20 :Motor self-learning error(E016) 21 :EEPROM o peration error (E00F) 22 :PID feedback di sconne ct er ror (E02E) 23 :Brak in g unit e rr orE01 A 24 :Reserved

Default Value

Modifi Serial cation No

F3.07 F3.08 F3.09 F3.10 F3.11 F3.12 F3.13

operation status display p referential option IGBT module temperature Softwa re version Accumulative op er ating time The fault be fore previous fault type Previous fault type Curr en t fault type

0- 14 (0:inv ali d ) 0100 .0

0

** **

85. F3.1 4 86. 87. 88. 89. 90. 91. F4.0 0 F4.01 F4.0 2 F4.03 F4.0 4 F4.05 F4.0 6 F4.0 7 F4.08 F4.0 9 F4.1 0 F4.11 F4.1 2 F3.15 F3.1 6 F3.1 7 F3.18

Operating freq uency at curre nt faul t Outp ut amperag e at curre nt faul t Bus voltage at curr ent fa ult Input terminal statu s at curre nt faul t Outp ut terminal statu s at curre nt faul t

0.0 0Hz 0.0A 0.0V 0 0

** ** ** ** **

92. 93. 94. 95. 96.

0655 35h 0No fault 1:IGBT U phase protection(E009) 2:IGBT V phase protection(E019) 3:IGBT W phase protection(E029) 4:Acceleration over-current(E004) 5:Decelera tion over- current(E005) 6:Constant speed over-current (E006) 7:Acceleration over-voltage(E002) 8:Decelera tion over- voltage(E00A) 9:Constant speed over-voltage (E003) 10:Bus under-voltage fau ltE 001 11:Motor overload (E007)

0

** ** ** **

F4 Application Function ParametersACCEL Time 2 DECEL Time 2 Jogg ing freq uen cy Jogg ing ACCEL time Jogg ing D ECEL time Skip fre quency Skip fre quency range Traverse frequen cy range Kick frequ ency ran ge Traverse frequen cy up time Traverse frequen cy dow n time Fault auto -r eset times Interval ti me setting of au tomatic re setting fa ult

0.1 36 00 .0s 0.1 36 00 .0s 0.0 0F0.04 0.1 36 00 .0s 0.1 36 00 .0s 0.0 0F0.04 0.0 0F0.040.0 10 0.0% relative to se t frequen cy 0.0 50 .0%(relative to traverse frequ ency range)

10 .0s 10 .0s 5.0 0Hz 10 .0s 10 .0s 0.0 0Hz 0.0 0Hz 0.0% 0.0% 5.0s 5.0s 0 1.0s

97. 98. 99. 100. 101. 102. 103. 104. 105. 106. 107.10 8. 10 9.

12:Inverter overload(E008) 13:Input side phase failur e(E012) 14:Output sid e phase failure(E013) 15:(Diode mo dule overhe at fault (E00E) 16:IGBT module overheat fa ult ( E0 1E) 17:External faul t(E017)

0.1 36 00 .0s 0.1 36 00 .0s0 3 0.1 100.0s

- 29-

- 30-

DZB Series

Chapter 5 Function Parameters List

DZB Series

Chapter 5 Function Parameters List

Function Code F4.13 F4.14 F4.15

Name FDT level de tection value FDT delay detection value Frequency reaching detection range Brake Thresho ld Value Voltage

Setting Range 0.00 F0.04 0.0100.0%(FDT level) 0.0100.0%(maximum freque ncy) 115.0140 .0%( standard DC bus voltage) 380V 115.0140 .0%( standard DC bus voltage) 220V 0.1999.9% Speed=1 20running frequencyF4.17/pole number 0Given by Keyboard(F4.1 9) 1Given by Analog Chan nel V I

Default Value 50.00Hz 5.0 % 0.0 % 130.0%

Modifi Serial cation No

Function Code F4.31 F4.3 2 F4.33 F4.3 4

Name Multi-S peed 2 Multi-S peed 3 Multi-S peed 4 Multi-S peed 5 Multi-S peed 6 Multi-S peed 7

Setting Range -100.0100.0% -100.0100.0% -100.0100.0% -100.0100.0% -100.0100.0% -100.0100.0%

Default Value 0.0% 0.0% 0.0% 0.0% 0.0% 0.0%

Modifi Serial cation No

110. 111. 112.

12 8. 12 9. 13 0. 13 1. 13 2. 13 3.

F4.16

120.0%

F4.35 113. F4.3 6

F5 Protection Parameters100.0%

F4.17

Spee d displ ay ratio

114. F5.0 0

0No protection Motor Overload Protection Op tion 1nor mal motor 2Variable Frequency motor F5.01 Motor Overload Protection Curre nt Power-down Frequ ency Drop Poi nt Instan t p ower-down Frequency drop ra te Over-vol tage Stall P rotectio n Over-vol tage Stall Protection Vo ltage Auto li mi t curr ent level Li mi t curr ent frequ ency drop rate 20.0%120.0% (motor rated current) 70.0110.0%(standard b us voltage) 0.00HzF0.04 0prohibit 1allow 110150% (380V) 110150% (220V) 100200% 0.0050.00Hz/s 0 120% 115% 200% 0.00Hz/s 100.0% 80 .0% 0.0 0Hz 1

13 4.

13 5. 13 6. 13 7.

F4.18

PID setpoint Sour ces Option

2Given by Analog Chan nel CI 3Given by Remote Communication 4Mu lti-seg setpoint

0

115. F5.0 2 F5.03

F4.19

Preset PID setpoint

0.0%100.0% 0VI Feedba ck

0.0 %

116. F5.0 4

13 8.

F4.20

PID Feedback Sour ces Option

1CI Feed back 2VI+ CI Feedback 3Communication feedb ack 0

117.

F5.05 F5.0 6

13 9. 14 0. 14 1.

F4.21 F4.22 F4.23 F4.24 F4.25 F4.26 F4.27 F4.28 F4.29 F4.30

PID Output Characteristics 0positi ve Option 1Pnegative Proportional gain (Kp) Integral time (Ti) Differential time (Td) Sampli ng cycle time (T) PID control discrepancy limit Feedba ck disconnection detecting value Feedba ck disconnection detecting time Multi-Speed 0 Multi-Speed 1 0.00100.00 0.0110.00s 0.0010.00s 0.01100.00s 0.0100.0% 0.0100.0% 0.0 36 00.0 s - 100.01 00.0% - 100.01 00.0%

0 1.00 0.10s 0.00s 0.10s 0.0 % 0.0 % 1.0 s 0.0 % 0.0 %

118. 119.

F5.0 7

F6 Communication ParametersF6.0 0 120. 121. 122. 123. 124. 125. 126. 127. F6.01 Baud r ate setting Commun ication Address 1247,0 is the broadcast address 01200BPS 12400BPS 24800BPS 39600BPS 419200BPS 538400BPS 0:N o checkN,8,1 for RTU 3 1

14 2.

14 3.

F6 .02

Data pattern

1:Odd check E,8 ,1for RTU 2:Even checkO,8,1 fo r RTU

0

144.

- 31-

- 32-

DZB Series

Chapter 5 Function Parameters List

DZB Series

Chapter 6 Parameter Description

Chapter 6 Parameter DescriptionFunction Code Name Setting Range 3:No check N,8,2for RTU 4:Odd checkE ,8,2for RTU 5:Even che ck O,8,2for RTU 6:No check N,7,1for ASCII 7:Odd checkE ,7,1for AS CII 8:Even che ck O,7,1for ASC II 9:No check N,7,2for ASCII 10:Odd che ck E,7,2 fo r ASCII 11:Even ch eck O,7,2for ASCII 12:No checkN ,8,1for AS CII 13:Odd che ck E,8,1for ASC II 14:Even ch eckO,8,1for ASCII 15:No checkN ,8,2for AS CII 16:Odd che ck E,8,2 fo r ASCII 17:Even ch eckO,8,2for ASCIIF6.03 F6.04

Default Value

Modifi Serial cation No

F0 Basic Function ParametersFunction Code F0.00 Name Setting Range 0 Sp eed sensorless vector control (S VC) 1 V/F controlSelection of Speed Control Mode 0: Vector Control without PG: Open loop vector control This control mode is suitable for the application requiring high torque at low speed and superior speed control. One inverter can drive only one motor. E.g. machine tool, wiring machine, plastic injection machine etc. 1: V/F Control Mode V/F control mode is suitable for the application which does not require high control accuracy, e.g. pump and fans, and also suitable for cases with one inverter driving multiple motors. Note: If vector control mode is selected, it is a must to correctly set up the nameplate parameters of motor, and accomplish self learning of motor parameters before operation to acquire correct motor parameters. Only obtaining correct motor parameters can exert the high performance of vector control mode.

Default Value 1

Control mode

Function Code

Name

Setting Range 0 Ke yb oard

Default Value

Communication response delay Communication overtime fault time

0200 ms

5ms 0.0s

145. 146.

F0.0 1

Comman d source sele ction

1 Te rmin al 2 Communica tion

0

0.0in va lid 0.1 100.0s 0Alarm and free ru n sto p 1No alarm and keep run ning

Path Selection for the inverter Control Command 0: Keyboard Command Path The buttons RUN and STOP on the keyboard are for operation control. 1:Terminal Command Path

F6.05

Communication error measure

2No alarm and stop accordin g to stop mode (b y communication ) 3No alarm and stop accordin g to stop mode (b y all co ntrol mod e)

1

147.

Multifunction input terminals of forward, reverse, forward jogging, reverse jogging and so on, perform the operation command control. 2:Communication Command Path Operation command control is performed through communication pattern by upper level machine.

F6.06

Response measure

0Response whe n write 1No respon se when wri te0 148.

Function Code

Name

Setting Range 0 Ke yb oard and terminal UP/DOWN setting

Default Value

F0.02

Keyboard a nd terminal UP/DOWN setti ng

1 Valid , a nd in ve rter do es not memorize whe n power down 2 Invalid

0

DZB200&300series inverter can set up the frequency though "" and "" buttons on the keyboard and terminal UP/DOWN (Frequency setting inc rease /Frequency setting decrease), a nd as it has the highest purvie w, it can combine with any other frequency setting path to mainly accomplishes the fine adjustment of inverter output freque ncy during control system commissioning.

- 33-

- 34-

DZB Series

Chapter 6 Parameter Description

DZB Series6Remote communication

Chapter 6 Parameter Description

0: Valid, and the inverter memorizes when power down. Able to set up frequency command, and memorize this set frequency when the inverter is power down. When the power is back,automatically combine it with current frequency setting. 1: Valid, and the inverter does not memorize when power is down. Able to set up frequency,but when the inverter power is down, this frequency setting is not memorized. 2: Invalid. The frequency set through keyboard and terminal UP/DOWN is automatically cleared,and the settings through keyboard and terminal UP/DOWN are invalid.Note: After the user restores the default values of inverter function parameters, the frequency value, set through keyboard and terminal UP/DOWN , is automatically cleared.

The frequency command is given in the communication mode by upper position machine.For details, please refer to DZB Series inverter ModBus Communication Protocol. Function Code F0.04 Name Maximum o utpu t freq uency Setting Range 10.00 600.00Hz Default Value 50.00Hz

It is used to set up the maximum output frequency of inverter. Please note that, it is the basis of frequency setting and acceleration/deceleration speed.

Functio n Cod e

Name

Setting Range 0Keyboard 1VI 2CI

Default Value

Function Code F0.0 5

Name Upper limit frequ ency

Setting Range F0.06F0 .04

Default Value 50.00Hz

It is the upper limit of invert er output frequency, whi ch should be less than or equal to the maximum output frequency.0 Function Code F0.06 Name Lower limit frequ ency Setting Range 0.0 0 Hz F0.05 Default Value 0 .00Hz

F0.03

Frequency command Selection

3VI+ CI 4: Multi-spe ed 5: PID co ntrol 6: Commun ication

The lower limit of inverter output frequency. If setpoint frequency is lower than lower limit frequency when startup, inverter can not run.operate at the lower limit frequency, stop or be dormant. Therein, Maximum output frequency upper limit frequency low er limit frequency.

Selection of inverter frequency command input channels. There are 7 main frequency s etting channels: 0: Keyboard Accomplish keyboard frequenc y setting by means of modifying the value of function code F0.07 Keyboard frequency setting. 1:VI 2:CI 3:VI+ CI This means that the frequency is set up through ana log input terminals. DZB series inverter provides 2 analog input channel. VI is 0-10V voltage input mode, while CI can be 0-10V input or 0 (4)-20mA input. The 100.0% setting of analog input is corresponding to the maximum frequency (Function Code F0.04), and -100.0% is corresponding to maximum reverse fre quency (Function Code F0.04). 4:Multi-speed operation The inverter is operated in the mode of multi-speed once this frequency setting mode is chosen. It is needed to set up the parameters of F2 Group and F4 Group Multi-speed control group to determine the coincidence relation between given percentage and given frequency. 5PID control Selection of this parameter means that the operation mode of inverter is PID control mode.In this case, it is required to set up F4 Group PID control group . The operation frequency of inverter is the frequency value which PID gives. Please refer to the description of F4 Group PID functions for the definition of PID setpoint source, assigned value, feedback source and so on.

Function Code F0.0 7

Name

Setting Range

Default Value 50.00Hz

Keyboard freq uency setting 0.0 0 Hz F0.04

When Frequency Command is chosen as keyboard Setting, this function code value is the initial set value of inverter frequency.Function Code F0.0 8 F0.09 Name ACCEL time 1 DECEL time 1 Setting Range 0.1 36 00.0s 0.1 36 00.0s Default Value 10.0s 10.0s

Ac celeration time means the time t 1 required for inverter to accelerate to the maximum output frequency (F0.04) from 0Hz. D eceleration time is the time t2 required for inverte r to decelerate to 0Hz from the maximum output frequency (F0.04). It is indicated by following figure

- 35-

- 36-

DZB SeriesOutput frequency f

Chapter 6 Parameter Description

DZB Series

Chapter 6 Parameter Description

f max f s et

Function Code F0.11

Name Carrie r frequency setti ng

Setting Range 1.0 15 .0kHz

Default Value Set by model

Carrier frequency

Electr onmagnetic noise

Cacophony, Leakage current

Heat radiation

1KHzactua l acce. tim e set acce.time a ctual dece. time set de ce.time

large

small

small

Time t

10K Hzsmall large large

Fig 6-1 Acceleration and D eceleration time diagramWhen the set frequency is equal to the maximum frequency, the actual Acceleration/Deceleration time are equal to the set Acceleration/De celeration time. When the set frequency is less than the maximum frequency, the actual Acceleration/Deceleration time are less than the set Acceleration/Deceleration time. Actual Acceleration /Deceleration time = set Acceleration/Decelerat ion time(set frequency/max. frequency) DZB200&300 series inverter ha s 2 groups of Acceleration/Deceleration time. 1st group: F0.08, F0.09; 2nd group: F4.00, F4.01; The Acceleration /Deceleration time can be chosen through multifunction digital input terminal (F2 Group).

15K Hz

Fig 6-2 Relationship between environment and Carrier frequency Relati onship between M odel and Carrier frequency Carrier frequency Model Max carr ier frequency (KHz) Min carrier frequency (KHz) Factory setting (KHz)

B0 . 4 k W1 1 K W P0 . 7 5 kW1 5 KW B1 5 k W5 5 K W P1 8 . 5 kW7 5 KW B7 5 k W3 0 0 K W P9 0 k W3 1 5 K W2

15

1

8

8

1

4

Functio n Cod e

Name

Setting Range 0Operating at de fault direction

Default Value

6

1

2

F0.1 0

Operation direction selection

1Operating at reverse d irection 2NO inverse ope ra ting

This function is mainly used to improve the motor operating noise and inverter interference to external. The advantages of using high carrier frequency: relatively ideal current wave shape, less harmonic current wave and low motor noise; The disadvantages of using high carrier frequency: increased switch loss and inverter temperature rises, affecting inverter output capacity so that it should be operated at derating under high carrier freque ncy conditions; in the mean time, inverter leaka ge current and its e lectromagnetic interference to external are increa sed. The situations of using low carrier frequency is on the contrary. Too low carrier frequency can c ause operation unstable, torque reduced and even oscillation at low frequency. When inverter is factory released, its ca rrier frequency has been set properly. Generally the user does not need to modify this parameter.

0: Operating at default direction. When the inverter is power connected, it operates at the ac tual direction. 1: Operating at reverse direction. By means of changing the function code, the motor rotati ng direction can be changed without changing any other parameters, which is equivalent to change the motor rotating direction by exchanging any two of motor cables (U, V, W). Note: After the parameters are initialized, the motor operating direction can be restor ed to be its original state. Be caution to use it in the case that changing motor rotating direction is forbidden after the system commissioning is completed. 2: Forbid inverse operating. Forbidding inverter inverse operation is sui table to specific application that inverse operating is forbidden.

- 37-

- 38-

DZB Series

Chapter 6 Parameter Description

DZB Series

Chapter 6 Parameter Description

Functio n Cod e

Name

Setting Range 0NO operation

Default Value

starting frequency, inverter doe s not operate and is at stand-by state. The start ing frequency value is not restricted by the lower limit frequency. During FWD/REV switching, the starting frequency is inactive.

F0.1 2

Functiona l parameters restoratio n

1Restore de faul t value 2 Del ete failure records

0

Function Code F0.1 7

Name Braking current before starting Braking time before starting

Setting Range 0.0 150.0% 0.0 50.0s

Default Value 0.0 % 0.0s

1: The inverter restores all parameters to their default value. 2: The inverter deletes recent failure records. After the chosen function operation is completed, this function code is automatically restored to 0. When it is being started, the inverter first performs DC braking according to the set prior-to-startingFunctio n Cod e F0.1 3 Name AVR selection Setting Range 0 Invalid 1 Valid a ll the ti me 2 Invalid dur ing decelerationAVR means output voltage auto regulation. When AVR is invalid, output voltage will change a ccording to the change of input voltage (or DC bus voltage); When AVR is valid,output voltage will remain constant within output capacity.

F0.1 8

Default Value 1

DC braking current, and after t he set prior-to-starting DC braking time is passed then begins to perform acceleration. If the set DC braking time is 0, DC braking is invalid. The bigger the DC braking current, the greater the braking force. The prior-to-starting DC braking current is the percentage of the rated inverter current.Function Code F0.19 Name Stop Mode Setting Range 0DECEL Sto p 1Fre e run Stop 0 Default Value

0: Deceleration stopFunctio n Cod e Name Setting Range 0 Direct sta rt F0.1 4 Start Mode 1 DC brakin g fir st an d then sta rt 2 Runnin g speed pick-u p and then start 0 Default Value

After the stop command is enabled, the inverter decreases the output frequency ac cording to the Deceleration mode and the defined A cceleration /Deceleration time, and the motor is stopped when the frequency is 0. 1: Free-run stop Once the stop command is valid, the inverter immediately ends the output. The loading is freely stopped by its mechanical inertia.Function Code F0.20 F0.2 1 F0.22 F0.23 Name Beginning Frequency of braking Waiting ti me o f braking DC bra king current DC bra king time Setting Range 0.00 F0.04 0.0 50.0s 0.0 150.0% 0.0 50.0s Default Value 0.0 0Hz 0.0s 0.0 % 0.0s

0: Direct start: start from the starting frequency. 1: DC braking first and then start: First perform DC bra king (pay attention to set up parameters F0.17 and F0.18 ), and then start and run the motor at the start frequency. It is suitable for small inertia loading which can cause reverse rotation at starting. 2: Running speed pick-up and then start: the inverter first calculates motor rotating speed and direction, and then start running to its set frequency from current speed, performing a smooth no-shock start to moving motor. This mode is applicable to momentary power-down start w hen the inertia loading is big.Function Cod e F0.15 F0.16 Setting Range 0.0010.00Hz 0.050.0s Default Value 0.50Hz 0.0 s

Beginning frequency of DC brake when stopping.During the Deceleration st op, when this frequency

Name Start frequency Hold time of start frequency

is rea ched, the DC brake is started. Waiting time of DC brake when stopping: Prior to the DC brake, the inverter blocks the output, and after this delay time, the DC braking is started. It is used to prevent over-current fault caused by DC braking at high speed. DC brake current when stopping: indicates the applied DC brake energy. The bigger the current, the stronger the DC brake e nergy should be. DC brake time when stopping: the durative time that the D C brake energy is applied. If the time is 0, DC brake is invalid, and the inverter stops the motor based on the set Deceleration time.

Setting proper starting frequency ca n increase the starting torque. Within the hold time of the starting frequency (F0.16), the inverter output frequency is the starting frequency, and then,from the starting frequency, running to the target frequency. If the target frequency (frequency command) is less than the

- 39-

- 40-

DZB Series

Chapter 6 Parameter Description

DZB Series

Chapter 6 Parameter Description

O u tp u t F r e q u e n c y f

0: Terminal command invalid when power on. Inverter will not run if it detect operating command terminal is valid. When the operat ing command terminal is invalid and enable this terminal again, inverter will run. 1: Terminal command valid when power on. Inverter will startup automatically a fter initialization is finished if it detect operation command terminal is valid.

Note: Customer shou ld be careful when you select this function, it may cause severe consequence.T im e t O u tp u t V o lta g e

F1 Motor ParametersD CBrak e when s ta r t in g D C B ra k e w h en s to p p in g

T im e t

Function Code F1.00

Name Inverter model

Setting Range 0B model 1P mod el

Default Value Set by model

Fig. 6-3 DC Bra ke Diagram

Functio n Cod e F0.2 4

Name Dead time between forward a nd reverse

Setting Range 0.0 36 00.0s

Default Value 0.0s

0: suit able for constant torque load of designated nominal parameter. 1: suit able for variable torque load (such as fan and pump). Constant torque(B model) inverter can drive larger variable torque(P model) load directly. For example, DZB300B0220L4 inverte r is set 22KW B model as default, if you want to drive 30KW fan, you should Set F1.00 as 1 Set F1 group motor parameter againFunction Code Default Value Set by model 50.00Hz Set by model Set by model Set by model

It is to set the transient time during w hich the output frequency is 0 in the FWD /REV transi ent process of inverter. It is shown as following figure:Output Frequency f

Name Motor rated power Motor rated frequency Motor rated speed Motor rated voltage Motor rated current

Setting Range 0.4 900.0kW 0.01Hz F0 .04 0360 00rpm 0460 V 0.1 1000.0 A

Forward

F1.0 1 F1.02 F1.03Time t Reverse

F1.04 F1.0 5

Dead Time

Note: please set th ese codes according to motor n ameplate parameters. The superior performances of vector control require precise motor parameters. DZB series invert er provides para meter self-learning function. A ccurate parameter self-learning comesDefault Value

Fig. 6-4 FWD/REV Dead Time Diagram

Functio n Cod e

from correct setting of motor nameplate parameters. In order to ensure the control performances, please do the motor setting based on the inverter standard adaptive motor. If the motor rated power has a too big difference to the standard adaptive motor, the inverter control performances will be deteriorated distinctly. Note: resetting of motor rated power (F1.01) can initialize motor parameter F1.02-F1.10.

Name Terminal command protection when power on

Setting Range 0 Te rmin al comma nd in va lid when power on 1 Te rmin al comma nd vali d whe n po wer on

F0.25

0 1

If operating command channel is set to terminal control, system will detect terminal status automatically during inverter power on.

- 41-

- 42-

DZB Series

Chapter 6 Parameter Description

DZB Series

Chapter 6 Parameter Description

Functio n Cod e F1.0 6 F1.0 7 F1.08 F1.0 9 F1.1 0

Name Motor sta tor resistance Motor rotor resistance Motor stator/rotor inductan ce Mutual ind uctance of motor stator/ro tor No-load current

Setting Range 0.0 01 65.535 0.00165.5 35 0.165 53.5 mH 0.165 53.5 mH 0.016 55.3 5A

Default Value Set by model Set by model Set by model Set by model Set by model

Function Code F1.12 F1.13 F1.14 F1.1 5 F1.16

Name Speed loop prop ortional gain1 Speed loop integral time1 Switching low point frequency Speed loop prop ortional gain 2 Speed loop integral time 2 Switching high point frequency 0100

Setting Range

Default Value 30 0.50s 5.0 0Hz 25 1.0 0s 10.00Hz

0.0110.00s 0.00HzF1.1 7 0100 0.0110.00s F1.14F0.04

After the motor self-learning is normally ended, F1.06-F1.10 setting values are automatically replaced. These parameters are the basis of high performance vector control and have direct effect on the control performance. Important: users DO NOT change this group parameters at will.Functio n Cod e Name Setting Range 0 NO operation F1.11 Self-learning of motor parameters 1 complete tu ning Self-le arning 2 static tunin g Self-lea rn ing 0 Default Value F1.1 7

Above parameters are valid only to vector control, but invalid to V/F control. When the frequency is less than the switching frequency point 1 (F1.14), the speed loop PI parameters are F1.12 and F1.13. When frequency is higher than the switching frequency point 2 (F1.17),the speed loop PI parameters are F1.15 and F1.16. Between the switching points, PI parameter is acquired according to the line type variation of the two group parameters, as shown in following figurePI Parameter (F1.12,F1.13)

Note:This function is invalid for DZB200Seriess. 0: NO operation, forbidding self-lea rning. 1: self-learning of parameters Prior to parameters self-learning, the motor must be disconnected with its load-ensuring the motor at no-load condition, and confirming the motor is at static state. Prior to parameters self-learning, it is a must to correctly input the motor nameplate para meters (F1.01~F1.05), otherwise what is se lf learned about motor parameters may be not correct. Prior to parameters self-learning, the Acceleration and Deceleration time (F0.08 and F0.09) should be set properly based on the motor inertia, otherwise over current fault may happen during motor parameters self-learning. When the self-learning of motor parameters is started by setting F1.11 as 1 and then pushing the button FUNC/DATA, LED displays -TUN- and flickering, then push the button RUN to begin the procedure of the motor parameters self-learning. At this time,T UN-0is displayed. After the motor is started, TUN-1is show n and RUN light is flickering. When the self-learning of parameters is finished, -END-is displayed, and finally back to the stop state interface. When -TUN -is blinking, the process of parame ters self-learning c an exit by pushing the button PRGM/RESET . During the process of parameters self-learning, it can be stopped by pressing the button STOP. Please note, the start and stop of the parameters self-learning can only be done through keypad. Once the parameter self-learning is finishe d, this function code automatically r estores to 0.F (F1.15,F 1. 16)

Fig. 6-5 PI Parameter D iagram By means of setti ng the proportion factor and integration time of t he speed regulator, the speed dynamic response of vector control can be regulated. Increasing the proportional gain,and reducing the integrat ion time, can equally qui cken the dynamic response of speed loop,but either the proportional gain being too much or the integration time being too short can easily cause system oscillation and too big overshoot. The proportional gain being too small als o can lead to system steady state oscillation and possibility of speed steady-state error oc curring S peed loop PI parameters have an intimate relation with the inertia of motor system, and therefore based on the default PI parameter the user needs to make adjustment for different loading character in order t o mee t different requirement.Function Code F1.1 8 Name VC slip compensating factor Setting Range 50%200% Default Value 100%

The slip compensating factor is used to adjust the slip frequency of vector control and improve the system s peed control accuracy. P roperly regulating this parameter can effectivel y restrain the speed steady-s tate error.

- 43-

- 44-

DZB Series

Chapter 6 Parameter Description

DZB SeriesOutput Voltage (V)

Chapter 6 Parameter Description

Func tio n Cod e F1.1 9

Name Upper torque l imit setting

Setting Range

Default Value

0.0200.0%(inverter rated current) 15 0.0%

Vb

The setting 100.0% is corresponding to the rated output current.The function code belowF1.20~F1.24 a re valid to V/F control ( 0.001 ), but invalid to vector F control.

Functio n Cod e F1.2 0

Name V/F curve setting

Setting Range 0 Linear V/F curve 1 square torque V/F curve

Default Value 0

V b o o st f c u t -o f f fOutput Frequency f b

Fig. 6-7 Manual torque boost diagram

0: Linear V/F c urve. It is applicable to constant torque load. 1: 2.0 exponential V/F curve. It is applicable to variable torque load, such as blower, pump e tc.

Function Code F1.23

N ame

Setting Range

Default Value 100%

V/F sli p compensation limit 0.0200.0%

Output Voltage (V)

VbLinear V/F curve

Setting this parameter can compensate the motor speed change produced because of undertaking loading while on V/F control, to increase the rigidity of motor mechanical performance. This value should be set as the motor rated slip frequency.

Function Code

Name Energy Conservation Sele ction

Setting Range 0:No Oper ati on

Default Value 0

2.0 exponential V/F curve

F1.24

1:Energy Conservation

1/3 fb

fbFig. 6-6 V/F curvediagram

Output Frequency f

When the motor is running in no-load or lower-load during,the inverter can adjust output voltage by automatically current kf the load Note:This function is especially valid for variable torque load (such as fan and pump).

Func tio n Cod e F1.21 F1.2 2

Name Torque boost Torque boost cut-off

Setting Range 0.0%(auto) 0.130.0

Default Value 0 20 .0%

0.0%50.0% (relative to motor rated frequency)

F2 Input and Output Terminal Function Parame tersFunction Code F2.00 N ame On-off signal filter times 110 Setting Range Default Value 5

Torque Boost is mainly applied to less than cut-off frequency (F1.22). The V/F curve after boost is shown in following figure. Torque booth can improve the low frequency torque performance of V/F control. Based on the load, a torque should be chosen properly. For heavy loa d, increase the tor que boost, but the torque boost should not be set too big, which will result in the motor operating at overexcitation and that it could be overheated, and also the inverter output current is big, reducing efficiency. When the torque boost is set as 0.0%, the inverter is at automatic torque boost. Torque boost cut-off frequency: below this frequency, torque boost is valid, and above this frequency setting, torque boost is invalid.

It sets up S1-S6, VI and CI terminal s sample filtering time. In big interference situation, this parame ter should be increased in order to prevent maloperation.

- 45-

- 46-

DZB Series

Chapter 6 Parameter Description

DZB Series

Chapter 6 Parameter Description

Func tio n Code F2.01 F2.02 F2.03 F2.04 F2.05 F2.06

Name S1 Terminal Function Selec tion S2 Terminal Function Selec tion S3 Terminal Function Selec tion S4 Terminal Function Selec tion S5 Terminal Function Selec tion S6 Terminal Function Selec tion

Setting Range 0~25 0~25 0~25 0~25 0~25 0~25

Defau lt Value 1 2 4 7 12 1311 Frequency up/down setting clear 10 Frequency down setting 9 Frequency up setting

When the frequency is set by external terminal, modify the freque ncy up and down command. When the frequency source is set as digital se tting, the set frequency can be regulated up and down.K1

UP terminalDZB300

K2

DOWN terminalK3

UP /D OWN c lear DCM termi nal

These parameters are used to set up the corresponding functions of digital multifunction input terminals.

Using terminal can clear UP/DOWN set frequency so that set freque ncy can be restored the frequency setting given by freque ncy command cha nnel. 8 stages speed can be set up via these 3 terminals digital state combination. Note: multi-speed 1 is the low position, and multi-spee d 3 is the high position. 2 kinds of ACCE/DCCE time can be chosen via these two terminals digital state combination.

setting value0

Function

DescriptionEven if there is a signal input, the inverter does not run. Terminals which a re not used can be set to be no function in order to prevent malfunction The inverters forward or reverse running can be cont rol by external terminals. By means of this terminal the inverters operation mode can be defined to be three-wire control mode. For details, please refer to the function code description of F2.07 three-wire control mode. At Jogging operation, the frequency and Jogging Acceleration/Deceleration time can be found in detail descriptions of F4.02,F4.03 and F4.04 function codes. The inverter turns off output, and the motor stop process is not controlled by the inverter. It is often applied when the inertia loading is big and there is no requirement on stop time. This mode has the same definition as F0.19 does. This is external failure reset. It has the same function as STOP button on the keyboard. Using this function can perform long-distance failure reset. When external fault signal is input, the inverter reports it and stops.

12 13 14

Multi-speed terminal 1 Multi-speed terminal 2 Multi-speed terminal 3

No Function

1 2

Forward Reverse three-w ire operation control

15

3

ACCE/ DCCE time selection terminal

Terminal AC C/DCC time selection OFF ON ACCE time 0 ACCE time 1

Parameter F0.08F0.09 F4.00 F4.01

4 5

Forward Jogging Reverse Jogging

16

PID control pause

PID is temporarily out of work, and the inverter keeps its current frequency output. The inverter pauses at its current output frequency. After this function is cancelled, continue to start its traverse operation at its current frequency. The inverter is back to its center frequency output. Ensure the inverter is not interfered by external signals (excluding stop command), maintaining its current output freque ncy. Reserved

17 6 Free-run stop

Traverse pause

18

Traverse reset Acceleration/ Deceleration forbid Reserved

19 7 Failure reset 2025

8

External fault input

Function Code

N ame

Setting Range 0two- wi re control 1

Default Value

F2.0 7

Terminal control mode

1two- wi re control 2 2three- wire c ontrol 1 3three- wire c ontrol 2 0

- 47-

- 48-

DZB Series

Chapter 6 Parameter Description

DZB Series

Chapter 6 Parameter Description

This parameter defines four different control modes which controls the inverter operation through external terminals. 0: Two-wire type control, integrate Enable with direction. This mode is the most often used two-wire control mode. The motor forward and reverse operations are determined by the defined FWD and REV terminal command.

3: Three-wire control, separate Enable from direction. At this mode EN is the Enable terminal, SW1 or SW2 define operating command and control direction at the same time. Stop command is defined by SW2.

SW1 FWD

K1

FWD

K1

K2 OFF OFF ON ON

Operation Command STOP FWD REV STOP

SW2 EN K REV

K2

REV

DZB Series

OFF ON OFF

DZB Series

DCM

ON

COM

Fig. 6-8 Two-wire operation mode 1 1: Two-wire control, separate Enable from direction. When this mode is used, the defined FWD is enable terminal. The direction is determined by the defined REV state.

Fig. 6-11 Three-wire operation mode 2 S W1FWD opera ting button SW2STOP button KREV operating button

EN is def ining the corresponding terminal function as Function 3 Three-wire operation control.

K1

FWD

K1

K2 OFF OFF ON ON

Operation Command STOP FWD STOP REV

Note: For two-wire operation mode, when FWD/REV terminal is enabled and the stop command produced by other sources stops the equipment, the inverter does not start to operate after the stop command disappears even if the control terminal FWD/REV is still valid. If the inverter needs to operate , it is required to trigger FWD/REV again.

K2 REV

DZB Series

OFF ON OFF

DCM

ON

Function Code F2.0 8

N ame UP/DOWN frequency increment variable rate

Setting Range 0.0 15 0.00 Hz /s

Default Value 0.50Hz /s

Fig. 6-9 Two-wire operation mode 2 2: Three-wire control 1, integrate Enable with direction. At this mode, EN is the Enable terminal with the direction controlled by the defined FWD. REV define the direction.

Terminal UP/DOWN regulates the change rate of frequency setting.

SW1 FWD SW2 EN K REV Operation C ommand FWD REV

Function Code F2.09 K F2.10 F2.11 F2.12 F2.13 DCMFig. 6-10 Three-wire operation mode 1

N ame VI lower limit VI lower limit corresponding setting VI upper limit VI upper limit corresponding setting VI input filtering time

Setting Range 0