fsn018whycompressorsfailpart9
-
Upload
aheron-hizmo -
Category
Documents
-
view
215 -
download
0
Transcript of fsn018whycompressorsfailpart9
-
7/23/2019 fsn018whycompressorsfailpart9
1/4Field Service Note 018
1
Electrically testing Compressor motors and keeping
records of the motors winding resistances can some-
times help in preventing the early death of a compressor.
Prior to installing a new compressor the motor windings
resistance and their insulation value should be checked
to make sure the motor has suffered no damage duringits transportation to site.
Compressor manufacturers often list the motor resist-
ance data for their various compressor types and this
information is invaluable in testing if a machine is good
or damaged.
Single Phase Motors
Single phase motors have two windings, called the
START and RUN windings which are commoned through
a third pin. This connection sometimes has a Thermal
Klixon device at the common point to the Start winding,
so if the klixon /overload device trips, the Start windings
will be open circuited to try to prevent a burnout.
The compressor motor pins are
Termed as C= Common, S = Start , and
R = Run. The resistance of the Startwinding is normally of a higher ohmic
value than the Run Winding. This is
due to the Start winding being
wound in a lighter gauge wire than
the Run winding.
Measuring the Winding resistance is simply done using
an Ohmeter . The meter probes are connected to two
of the three motor pins in turn. And the measurements
noted.
Measuring the Start & Run winding resistance of a MTZ18-5
Why Compressors FailPart 9 Electrical Testing of Compressor Motors
MAKING MODERN LIVING POSSIBLE
-
7/23/2019 fsn018whycompressorsfailpart9
2/42
Using a Maneurop Compressor type MTZ28JE-5 (230v
1ph 50 Hz) as a reference, the design resistances for the
Run and Start windings are 1.16 Ohm (RUN) & 3.24 Ohm
(Start). When measuring the resistance between the Run
& Common Pins the resistance should read 1.16 Ohms
and between the Start & Common pins the resistance
should be 3.24 Ohms. When measuring between the
Run & Start pins the sum of the Run and Start winding
resistances should be measured ie 1.16 + 3.24 =4.4
Ohms.
These readings confirm that the motor windings are
good to run.
A further test of the compressor motor is the insulation
test . This test is to make sure that there is no earth leak-
age through the motor insulation.
This test is carried out using a Megger insulation tester,
a 500 volt dc megger is ideal. This involves simply put-
ting one of the meter probes onto the compressors earth
terminal or other part of its metallic shell, and the other
meter probe onto the motor pins, one at a time. The test
on all three pins should all show an insulation value of
at least 1 Meg ohm or higher, values showing infinity
are the desired value. Values lower than 1 Meg are acause for concern and usually mean the motor windings
are damaged and need further investigation.
Insulation test of a MTZ18-5 indicates there is no problemwith the motor windings.
NOTE :-
Care should be taken when carrying out Insulation test-
ing as the meter will generate 500 volts dc into the wind-
ings and compressor earth/shell . By touching the com-
pressor shell whilst under this test can cause the person
to receive a nasty electric shock.
Single phase compressor electrical components com-
prise of Potential Relays and Start and sometimes Run
capacitors.
here we have both PSC and CSR starting kits for single phasecompressors.
If there is any doubt as to the electrical components
integrity then they should be changed immediately.
Capacitors in general give good life time operation, but
capacitors are designed to store electricity and the Start
Capacitor is there to enhance the compressors starting
ability when pressure differences across the compressor,
during start up or quick re starts to the motor are
required. Pressure differences between the suction and
discharge of the compressor above 7 Bar should be
avoided, as even single phase machines designated asan HST ( HIGH START TORQUE) motor will only cleanly
start a machine where the pressure difference is less
than 7 Bar. Failing to ensure that the starting PD is less
than 7 Bar can cause the compressor to struggle to start,
and as such the potential relay will hold the START wind-
ing in circuit longer than desired and will eventually
cause the START winding to overheat and quickly burn.
( For every second that the START winding is in circuitits winding temperature will rise approx. 10C).
Start winding burnout
-
7/23/2019 fsn018whycompressorsfailpart9
3/43
A weak Capacitor or a leaky capacitor will often com-
promise the compressors motor.
Capacitors can be checked with various CAPACITOR test-
ers on the market.
A quick test will tell if the capacitor is OK to be used or
thrown away and replaced. Capacitors have a lifetime
and deteriorate if not used for some time.
Capacitor tester, this model indicates the capacitors size
in f
Ohmeters and Meggers can be used for checking
capacitors, but it must be remembered that
Capacitors store electricity and after testing with a
Designated Capacitor checking device, the device will
automatically drain the charge making it safe to touch,
whereas if using a Megger, the charge that the Megger
puts into the capacitor will be stored in the capacitor if
its a good one. To remove the charge, simply touch the
two capacitor wires together being careful not to touch
the wires with your fingers as you will receive a nasty
electrical shock that is not at all pleasant. Capacitor
testers can be just simple indicator testers with a LED
indicator or a more sophisticated type that actually
tests the capacitor and can also measure the capacitors
size in f or microfarads. Capacitors can weaken over
time and should be checked during service visits.
Three Phase Motors
Three phase motors are wound
differently where all the three
windings have an equal resistance
value unlike their single phase
alternative. At the Star point of
the three phase windings is a KLIXON device which
is both current and temperature sensitive. If this trips
there will be no resistance measured between the
compressor motor terminal pins as the klixon breaks
the power circuit between the three phases creating
an open circuit.
Note:- On Maneurop Compressors if the Klixon open
circuits during an overload or temperature problem ,
it may take up to 8 hours to reset, depending on the
motors temperature.
Here we have a Klixon fitted to a 3-phase motor.The Klixon is the compressors last line of defence andshould not be used to cycle the compressor.
These machines are connected to the three phase
supply via a three phase contactor and sometimes a
close coupled overload is also fitted.
Testing a three phase machine is similar to the single
phase machine, only this time when resistance
measurements are taken across the 3 motor terminals
, two at a time, the results should be the same for
the three measurements. The three terminals are
designated T1, T2, T3.
If the measurements vary from winding to winding
then the motor has been damaged or burnt due to
over current/temperature, or has been running with a
loss of a phase voltage possibly a blown line fuse. This
causes only two phases to run the compressor motor,
but these two phases will draw extra current and run
in an overloaded condition. This situation often causes
the machine to cycle on the machines internal klixon
leading to eventual klixon failure or the motor burns
out.
-
7/23/2019 fsn018whycompressorsfailpart9
4/44
Using the same size compressor but a three phase
version, the resistance across the three windings is 7.11
ohms.
Resistance from T1-T2 =7.11ohm, T2-T3 = 7.11ohm, T3-
T1= 7.11 ohm. This motor is OK.
Insulation testing is the same as for the single phase
version.
If electrical Test records are kept as to the resistance of
the windings and also its Insulation value, then every
6 or 12 months the condition of the motor can be
checked against its previous condition. If for instance
the resistance values and especially the insulation
value, starts to drop, in a compressor motor this could
be a sign of moisture or oil degradation in the system.
A visual Indication of this can be seen in liquid
line moisture indicating sight glasses, and also
discolouration of the oil in the compressors oil sight
glass are easy visual checks to make during a service or
maintenance visit.
Sight glasses are quipped with sensitive indicators that re-flects a color, which depends on the moisture content ofthe refrigerant.
At this stage fitting a new drier and /or changing the
compressors oil charge, could potentially save the
compressor motor. As moisture, and weak acids plus
heat increase in the system due to age and poor
maintenance such as leaky systems, these acids will
start to attack the motors insulation. If left, further
deterioration to the insulation will occur and eventually
the insulation will break down at its weakest point,
causing a spot burn in the windings and then complete
failure of the motor will occur soon after.
Moisture along with week acids and heat can cause aspot burn in the windings.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without subsequent changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Field Service Notes are produced by Glenn K Moore
Field Support Manager, Danfoss Ltd. Danfoss Ltd 9-2013Field Service Note 018