Frontterminal VRLA batter y FTB12-100 12 V 100 · • BS 6290-4: 1997High recovery ability,...

2
Global Batterier AB • Nyckelvägen 5 • 142 50 Skogås • Sweden • T el: +46 (0)8-448 30 00 • Orderfax: +46 (0)8-448 30 02 • www.global.se 10 years design life at 77 °F(25°C); Rectangle structure container with 2×3 cell structure, good for heat dispersion; Plate pasting technology applying active materials with 4BS high temperature and moisture curing technique- resulting in long cyclic life performance; T erminals located in the front of cover for ease of installation, connection and maintenance; Front central gas collection vent system venting gas out of the battery room; Plug in isolation terminal protection cover forshort- circuit prevention with inspect hole on it, convenient for voltage inspection; - height; - pact resistant and vibration resistant; Patented multi-layer terminal sealing technology for safety and integrity; High recovery ability, time-saving and energy saving; IEC60896-21/22: 2004 BS 6290-4: 1997 YD/T799-2010 Complaint with ISO9001, ISO14001, Fro n tt ermin al VRLA batter y FTB 12-100 12 V 100 A h Working features: Rated voltage: 12V 6 cells Rated capacity at 25°C / 77°F: 10h rate (10.0A, 10.8V): 100Ah 5h rate (17.5A, 10.8V): 87,5Ah 1h rate (64.6A, 10.5V): 64,6Ah Internal resistance: 4.4mΩ when fully charged at 25°C / 77°F Average self discharge rate: ≤1.5% per month at 7°F/ 25°C Maximum discharge current: 873 A (3s) at 77°F/ 25°C Working temperature range: Discharge: -20~50°C Charge: -10~50°C Storage: -20~50°C Charging method: with constant voltage at 77°F / 25°C Maximum charge current: 20A Cycle use: 14.28-14.52V/piece Temperature compensation: -21mV/°C/piece Standby use: 13.50-13.74V/piece Dimension and weight Length: 395 mm Width: 110 mm Height: 288 mm TH: 288 mm Weight: 34,5 kg

Transcript of Frontterminal VRLA batter y FTB12-100 12 V 100 · • BS 6290-4: 1997High recovery ability,...

Page 1: Frontterminal VRLA batter y FTB12-100 12 V 100 · • BS 6290-4: 1997High recovery ability, time-saving and energy saving; • Complaint with ISO9001, ISO14001, IEC60896-21/22: 2004

Global Batterier AB • Nyckelvägen 5 • 142 50 Skogås • Sweden • Tel: +46 (0)8-448 30 00 • Orderfax: +46 (0)8-448 30 02 • www.global.se

• 10 years design life at 77 °F(25°C);

• Rectangle structure container with 2×3 cell structure, good for heat dispersion;

• Plate pasting technology applying active materials with 4BS high temperature and moisture curing technique-resulting in long cyclic life performance;

• Terminals located in the front of cover for ease of installation, connection and maintenance;

• Front central gas collection vent system venting gas out of the battery room;

• Plug in isolation terminal protection cover forshort-circuit prevention with inspect hole on it, convenient for voltage inspection;

• -

height;

• -pact resistant and vibration resistant;

• Patented multi-layer terminal sealing technology for safety and integrity;

• High recovery ability, time-saving and energy saving;

IEC60896-21/22: 2004BS 6290-4: 1997YD/T799-2010Complaint with ISO9001, ISO14001,

Frontterminal VRLA battery

FTB12-100 12 V 100 Ah

Working features: Rated voltage: 12V6 cells

Rated capacity at 25°C / 77°F: 10h rate (10.0A, 10.8V): 100Ah5h rate (17.5A, 10.8V): 87,5Ah1h rate (64.6A, 10.5V): 64,6Ah Internal resistance: 4.4mΩ when fully charged at 25°C / 77°F Average self discharge rate: ≤1.5% per month at 7°F/ 25°C Maximum discharge current: 873A (3s) at 77°F/ 25°C Working temperature range:Discharge: -20~50°CCharge: -10~50°CStorage: -20~50°C Charging method: with constant voltage at 77°F / 25°CMaximum charge current: 20ACycle use: 14.28-14.52V/pieceTemperature compensation: -21mV/°C/pieceStandby use: 13.50-13.74V/piece

Dimension and weight Length: 395 mmWidth: 110 mmHeight: 288 mmTH: 288 mmWeight: 34,5 kg

Page 2: Frontterminal VRLA batter y FTB12-100 12 V 100 · • BS 6290-4: 1997High recovery ability, time-saving and energy saving; • Complaint with ISO9001, ISO14001, IEC60896-21/22: 2004

Global Batterier AB • Nyckelvägen 5 • 142 50 Skogås • Sweden • Tel: +46 (0)8-448 30 00 • Orderfax: +46 (0)8-448 30 02 • www.global.se

End voltage (V/cell) 5min 10min 15min 30min 45min 1h 2h 3h 4h 5h 6h 8h 10h 20h

1.60 333 245 197 116 82.7 69.8 39.9 29.2 22.1 18.3 15.7 11.8 10.4 5.4 1.65 315 227 183 109 80 68.4 39.4 28.7 21.9 18.2 15.6 11.8 10.3 5.3 1.70 293 213 169 105 77.2 67.0 38.5 28.1 21.7 18.0 15.4 11.7 10.2 5.3 1.75 276 194 156 100 74.1 64.6 38.1 27.8 21.4 17.7 15.2 11.7 10.1 5.3 1.80 260 176 146 95 71.1 62.2 37.5 27.4 21.2 17.5 15.0 11.5 10.0 5.3

End voltage (V/cell) 5min 10min 15min 30min 45min 1h 2h 3h 4h 5h 6h 8h 10h 20h

1.60 543 410 345 215 156 132 75.5 55.5 42.3 35.0 30.2 22.7 20.0 10.341.65 530 390 325 205 151 130 74.9 54.8 42.0 34.9 30.0 22.7 20.0 10.341.70 510 376 308 198 147 128 73.9 54.0 41.8 34.7 29.7 22.7 20.0 10.341.75 496 352 293 189 142 124 73.5 53.5 41.5 34.4 29.5 22.7 19.9 10.341.80 482 331 276 181 137 120 72.6 53.1 41.2 34.1 29.3 22.4 19.7 10.34

Constant power discharge data (Watt/cell 25°C)

Constant power discharge data (Ampere/cell 25°C)

Discharge parameter

Performance Curve