Replacement Guidelines for 2, 3, 4, 6 & 8 Cylinder S-Series (D2S, D3S, D4S, D6S, D8S) for 4 & 6 Cylinder Discus (D4D, D6D)

Transcript of Front page S Discus E 1013 - Emerson Climate · 2D and 3D Discus compressors exist in Star-delta...

Page 1: Front page S Discus E 1013 - Emerson Climate · 2D and 3D Discus compressors exist in Star-delta and Part-winding motor versions Motor code Power supply Nominal voltage Start connection

Replacement Guidelinesfor 2, 3, 4, 6 & 8 Cylinder S-Series (D2S, D3S, D4S, D6S, D8S)for 4 & 6 Cylinder Discus (D4D, D6D)

Page 2: Front page S Discus E 1013 - Emerson Climate · 2D and 3D Discus compressors exist in Star-delta and Part-winding motor versions Motor code Power supply Nominal voltage Start connection

D5.4.6/1113/E

1 Introduction ....................................................................................................... 1

2 Nomenclature .................................................................................................... 1

2.1 S-Series compressors ........................................................................................................ 1

2.2 Discus compressors ........................................................................................................... 1

2.3 Service 4/6 cylinder compressors ...................................................................................... 2

3 Replacement of D2S compressors .................................................................. 2

3.1 Performance – Cross reference tables .............................................................................. 2

3.1.1 Cross reference table ............................................................................................. 2

3.1.2 Capacity – R404A refrigerant ................................................................................. 2

3.1.3 Capacity – R134a refrigerant ................................................................................. 3

3.1.4 Capacity – R22 refrigerant ..................................................................................... 3

3.1.5 Electrical values (current) – R404A refrigerant ...................................................... 3

3.2 Dimensions ........................................................................................................................ 4

3.2.1 Dimensions, view from the oil pump side ............................................................... 4

3.2.2 Dimensions, side view ............................................................................................ 4

3.2.3 Comparison of compressor dimensions ................................................................. 5

3.2.4 Comparison of shut off valve position and diameter .............................................. 5

3.3 Motor .................................................................................................................................. 5

3.3.1 Motor current characteristics .................................................................................. 5

3.3.2 Motor codes ............................................................................................................ 6

3.4 Accessories ........................................................................................................................ 6

3.4.1 Common accessories ............................................................................................. 6

3.4.2 Specific accessories ............................................................................................... 6

4 Replacement of D3S compressors .................................................................. 7

4.1 Performance – Cross reference tables .............................................................................. 7

4.1.1 Cross reference table ............................................................................................. 7

4.1.2 Capacity – R404A refrigerant ................................................................................. 7

4.1.3 Capacity – R134a refrigerant ................................................................................. 7

4.1.4 Capacity – R22 refrigerant ..................................................................................... 7

4.1.5 Electrical values (current) – R404A refrigerant ...................................................... 8

4.2 Dimensions ........................................................................................................................ 8

4.3 Motor .................................................................................................................................. 9

4.3.1 Motor current characteristics .................................................................................. 9

4.3.2 Motor codes ............................................................................................................ 9

4.4 Accessories ........................................................................................................................ 9

4.4.1 Common accessories ............................................................................................. 9

4.4.2 Specific accessories ............................................................................................... 9

5 Replacement of D4 and D6 compressors ...................................................... 10

6 Replacement of D8S compressors ................................................................ 11

6.1 Performance – Cross reference tables ............................................................................ 11

Page 3: Front page S Discus E 1013 - Emerson Climate · 2D and 3D Discus compressors exist in Star-delta and Part-winding motor versions Motor code Power supply Nominal voltage Start connection

D5.4.6/1113/E

6.1.1 Cross reference table ........................................................................................... 11

6.1.2 Capacity – R404A refrigerant ............................................................................... 11

6.1.3 Capacity – R134a refrigerant ............................................................................... 11

6.1.4 Capacity – R407C refrigerant ............................................................................... 12

6.1.5 Capacity – R22 refrigerant ................................................................................... 12

6.1.6 Electrical values (current) ..................................................................................... 12

6.2 Dimensions ...................................................................................................................... 12

6.3 Motor ................................................................................................................................ 13

6.3.1 Motor current characteristics ................................................................................ 13

6.3.2 Motor codes .......................................................................................................... 13

6.4 Accessories ...................................................................................................................... 13

6.4.1 Common accessories ........................................................................................... 13

6.4.2 Specific accessories ............................................................................................. 14

7 Motor protection .............................................................................................. 14

8 Replacement for operation in parallel ............................................................ 15

8.1 Parallel operation with active oil management systems .................................................. 15

8.1.1 Replacement with same sight glass design and position ..................................... 15

8.1.2 Replacement with same sight glass design but different position........................ 15

8.1.3 Replacement with different sight glass design ..................................................... 15

8.2 Parallel operation with passive oil management systems ............................................... 15

Page 4: Front page S Discus E 1013 - Emerson Climate · 2D and 3D Discus compressors exist in Star-delta and Part-winding motor versions Motor code Power supply Nominal voltage Start connection

D5.4.6/1113/E 1

1 Introduction

With the recent and successful launch of Stream 4M and 6M compressors with CoreSense™ Diagnostics, Emerson has decided to consolidate product families over time in order to allow OEM’s and wholesalers to reduce complexity, product proliferation and therefore cost of operation.

The following changes will affect the semi-hermetic compressor range:

Conversion to black colour, similar to Stream compressors colour.

Conversion from to brand (cylinder head plates, compressor name plates, various labels).

Change of product nomenclature to reflect the brand change. The leading character “D”

traditionally used for compressors will no longer be used in the black painted compressors that use the brand.

Replacement of D2S, D3S and D8S with equivalent Copeland Discus™ 2D, 3D and 8D compressors.

Replacement of D4S, D4D, D6S and D6D with Stream 4M and 6M models.

2 Nomenclature

2.1 S-Series compressors

2.2 Discus compressors

Page 5: Front page S Discus E 1013 - Emerson Climate · 2D and 3D Discus compressors exist in Star-delta and Part-winding motor versions Motor code Power supply Nominal voltage Start connection

2 D5.4.6/1113/E

2.3 Service 4/6 cylinder compressors

3 Replacement of D2S compressors

The D2S reed valve 2-cylinder S-Series will be phased out and replaced with the high efficiency Copeland Discus 2D series.

3.1 Performance – Cross reference tables

3.1.1 Cross reference table

D2S compressors and Discus 2D have different performances. The equivalent compressor can vary depending on the application and the refrigerant used.

D2S models Displacement

@ 50 Hz Copeland brand models

Displacement @ 50 Hz

Mineral oil Ester oil m3/h Mineral oil Ester oil m3/h

D2SA-450 D2SA-45X 22.40 LSG-401 LSG-40X 22.50

2DL-400 2DL-40X 23.70

D2SA-550 D2SA-55X 22.40 2DL-750 2DL-75X 23.70

D2SC-550 D2SC-55X 26.80 2DL-400 2DB-500

2DL-40X 2DB-50X

23.70 28.00

D2SC-650 D2SC-65X 26.80 2DL-750 2DB-750

2DL-75X 2DB-75X

23.70 28.00

D2SK-650 D2SK-65X 31.20 2DB-500 3DA-500

2DB-50X 3DA-50X

28.00 32.20

Table 1

The operating conditions and the refrigerant will have to be taken into consideration when replacing D2S compressors.

3.1.2 Capacity – R404A refrigerant

S-Series Copeland brand models

Compressor Capacity kW Power input kW Compressor Capacity kW Power input kW

D2SA-55X 11.15 5.46 2DL-75X 12.15 5.05

D2SC-65X 13.25 6.57 2DL-75X 2DB-75X

12.15 14.90

5.05 6.22

Table 2: Performance with R404A @ medium temperature: -10°C / 45°C / 20°C / 0K

S-Series Copeland brand models

Compressor Capacity kW Power input kW Compressor Capacity kW Power input kW

D2SA-45X 3.53 2.90 LSG-40X 2DL-40X

3.48 3.78

2.57 2.71

D2SC-55X 4.05 3.18 2DL-40X 2DB-50X

3.78 4.63

2.71 3.22

D2SK-65X 4.86 3.98 2DB-50X 4.63 3.22

Table 3: Performance with R404A @ low temperature: -35°C / 40°C / 20°C / 0K

Page 6: Front page S Discus E 1013 - Emerson Climate · 2D and 3D Discus compressors exist in Star-delta and Part-winding motor versions Motor code Power supply Nominal voltage Start connection

D5.4.6/1113/E 3

3.1.3 Capacity – R134a refrigerant

S-Series Copeland brand models

Compressor Capacity kW Power input kW Compressor Capacity kW Power input kW

D2SA-45X 6.52 3.16 2DL-40X 6.60 2.96

D2SC-55X 7.91 3.74 2DB-50X 8.37 3.45

D2SK-65X 8.84 4.30 3DA-50X 9.45 3.89

Table 4: Performance with R134a @ medium temperature: -10°C / 45°C / 20°C / 0K

3.1.4 Capacity – R22 refrigerant

S-Series Copeland brand models

Compressor Capacity kW Power input kW Compressor Capacity kW Power input kW

D2SA-550 D2SA-55X 10.15 4.72 2DL-750 2DL-75X 11.40 4.46

D2SC-650 D2SC-65X 13.25 6.57 2DB-750 2DB-75X 14.00 5.43

Table 5: Performance with R22 @ medium temperature: -10°C / 45°C / 20°C / 0K

S-Series Copeland brand models

Compressor * Capacity

kW

Power input

kW Compressor

Capacity

kW Power input kW

D2SA-450 D2SA-45X 3.31 2.52 2DL-400-DC LSG-401

LSG-40X 3.13 3.51

2.47 2.73

D2SC-550 D2SC-55X 4.00 3.09 2DB-500-DC 3.95 3.17 * Performance with suction valve below cylinder head for operation at low temp with R22

Table 6: Performance with R22 @ low temperature: -35°C / 40°C / 20°C / 0K

3.1.5 Electrical values (current) – R404A refrigerant

S-Series Copeland brand models

Compressor Current A MOC

A

LRA

A Compressor

Current A MOC

A

LRA

A ** * ** *

D2SA-45X 5.97 9.62 11.4 68.5 LSG-40X 2DL-40X

5.50 6.13

- 9.38

8.9 11.1

68.5 55

D2SA-55X - 9.84 13.1 67.3 2DL-75X 8.51 10.88 13.8 70

D2SC-55X 7.00 11.07 13.1 74.1 2DL-40X 2DB-50X

6.13 6.71

9.38 10.88

11.1 13.4

55 55

D2SC-65X - 12.05 16.2 85.3 2DL-75X 2DB-75X

8.54 9.06

10.88 12.32

13.8 16.1

70 70

D2SK-650 8.70 13.79 16.4 85.3 2DB-50X 6.71 10.88 13.4 55 * Medium temperature: -10°C / 45°C / 20°C / 0K ** Low temperature: -35°C / 40°C / 20°C / 0K

Table 7: Current values comparison in Ampere

Page 7: Front page S Discus E 1013 - Emerson Climate · 2D and 3D Discus compressors exist in Star-delta and Part-winding motor versions Motor code Power supply Nominal voltage Start connection

4 D5.4.6/1113/E

3.2 Dimensions

3.2.1 Dimensions, view from the oil pump side

DLSG 401/40X D2S 2D

3.2.2 Dimensions, side view

DLSG 401/40X D2S

2D

Page 8: Front page S Discus E 1013 - Emerson Climate · 2D and 3D Discus compressors exist in Star-delta and Part-winding motor versions Motor code Power supply Nominal voltage Start connection

D5.4.6/1113/E 5

3.2.3 Comparison of compressor dimensions

Replacement compressors have the same mounting positions, but the other dimensions can be different.

D2S Copeland brand models

Compressor Height Length Width Compressor Height Length Width

D2SA-450/45X

332 549

330

LSG-401/40X 350 470 330

2DL-400/40X

432 592 350 D2SA-550/55X 2DL-750/75X

D2SC-550/55X 2DB-500/50X

D2SC-650/65X 375 553 2DB-750/75X

D2SK-650/65X 332 549 3DA-500/50X 445 649 370

Table 8: Compressor dimensions in mm

3.2.4 Comparison of shut off valve position and diameter

D2S Copeland brand models

Compressor Suction valve Discharge valve

Compressor Suction valve Discharge valve

Ø I mm Ø Height Ø I mm Ø Height

D2SA-450/45X

1 1/8”

125

7/8” 251

LSG-401/40X 1 1/8” -- 5/8” 250

2DL-400/40X

1 3/8 161

7/8

387 D2SA-550/55X 2DL-750/75X 1 1/8”

D2SC-550/55X 2DB-500/50X 7/8

D2SC-650/65X 128 2DB-750/75X 1 1/8”

D2SK-650/65X 125 3DA-500/50X 135 7/8” 402

Table 9: Shut off valve dimensions and position

3.3 Motor

3.3.1 Motor current characteristics

For correct sizing of electrical protection devices and wires use the values shown below:

D2S Copeland brand models

Compressor Current

A

MOC

A

LRA

A Compressor

Current

A

MOC

A

LRA

A

D2SA-450/45X 5.97** 10.4 / 11.4 68.5 LSG-401/40X 5.50** 8.6 / 8.9 68.5

2DL-400/40X 6.13** 9.7 / 11.1 55

D2SA-550/55X 9.84* 12.9 / 13.1

67.3 2DL-750/75X 10.88* 13 / 13.8 70

D2SC-550/55X 7.00** 74.1 2DB-500/50X 6.71** 11.3 / 13.4 55

D2SC-650/65X 12.05* 18.6 / 16.2 85.3 2DB-750/75X 12.32* 15.6 / 16.1 70

D2SK-650/65X 8.70** 15.7 / 16.2 85.3 3DA-500/50X 7.77** 11.3 / 15.9 55 * Medium temperature: -10°C / 45°C / 20°C / 0K ** Low temperature: -35°C / 40°C / 20°C / 0K

Table 10: Motor current values in Ampere

Page 9: Front page S Discus E 1013 - Emerson Climate · 2D and 3D Discus compressors exist in Star-delta and Part-winding motor versions Motor code Power supply Nominal voltage Start connection

6 D5.4.6/1113/E

3.3.2 Motor codes

D2S and L compressors exist mainly in Star-delta motor version - (Y/∆)

2D and 3D Discus compressors exist in Star-delta and Part-winding motor versions

Motor code

Power supply Nominal voltage

Start connection DOL connection

EWL 220-240V/3~/50 Hz 380-420V/3~/50 Hz

230 400

Y/Δ --

Δ Y

D2S, L, 2D, 3D

AWM/D 380-420V/3~/50 Hz 440-480V/3~/60 Hz

400 460

YY/Y Y 2D, 3D

EWK 220-240V/3~/60 Hz 380-420V/3~/60 Hz

230 400

Y/Δ --

Δ Y

D2S, L, 2D, 3D

EWM/D 380-420V/3~/50 Hz 440-480V/3~/60 Hz

400 460

Y/Δ Y/Δ

Δ Δ

D2S, L, 2D, 3D

EWN 250-280V/3~/60 Hz 440-480V/3~/60 Hz

265 460

Y/Δ --

Δ Y

D2S, L

AWR 220-240V/3~/50 Hz 230 YY/Y Y 3D

Table 11: Available motors codes

3.4 Accessories

The standard delivery content of D2S and 2D compressors is the same.

3.4.1 Common accessories

D2S and 2D compressors use the same following accessories:

Shut off valves Mounting parts Crankcase heaters Oil pressure switches Additional fans

3.4.2 Specific accessories

3.4.2.1 Liquid injection

Liquid injection system (Demand Cooling) is required for applications of Discus compressors with R22 at low evaporating temperatures.

NOTE: R22 is no longer allowed for new refrigeration systems in Europe. Only recycled R22 is allowed for maintenance until 2015. From 1

st January 2015, R22 supply will be

forbidden.

Changing a compressor on an installation could be an opportunity to exchange R22 for a longer term refrigerant and at the same time to discard the liquid injection system.

3.4.2.2 Unloaded start

D2S and 2D compressors use the same principle for unloaded start. However the unloaded start kits are not interchangeable.

The unloaded start can be ordered as an accessory (already assembled together with the compressor) or as a separate upgrade kit.

Page 10: Front page S Discus E 1013 - Emerson Climate · 2D and 3D Discus compressors exist in Star-delta and Part-winding motor versions Motor code Power supply Nominal voltage Start connection

D5.4.6/1113/E 7

4 Replacement of D3S compressors

The D3S reed valve 3-cylinder S-Series will be phased out and replaced with the high efficiency Copeland Discus 3D series.

4.1 Performance – Cross reference tables

4.1.1 Cross reference table

D3S models Discus equivalent models Displacement

@ 50 Hz

Mineral oil Ester oil Mineral oil Ester oil m3/h

D3SA-750 D3SA-75X 3DA-750 3DA-75X 32.2

D3SC-750 D3SC-75X 3DC-750 3DC-75X 38.0

D3SC-1000 D3SC-100X 3DC-1000 3DC-100X 38.0

D3SS-1000 D3SS-100X 3DS-1000 3DS-100X 49.9

D3SS-1500 D3SS-150X 3DS-1500 3DS-150X 49.9

Table 12: Equivalence table

D3S and 3D compressors are totally interchangeable in terms of dimensions.

4.1.2 Capacity – R404A refrigerant

S-Series Discus

Compressor Capacity

kW

Power input

kW Compressor

Capacity

kW

Power input

kW

D3SA-75X 15.55 7.21 3DA-75X 17.20 7.27

D3SC-100X 18.90 8.78 3DC-100X 20.60 8.57

D3SS-150X 25.90 12.35 3DS-150X 27.10 11.70

Table 13: Performance with R404A @ medium temperature: -10°C / 45°C / 20°C / 0K

S-Series Discus

Compressor Capacity

kW

Power input

kW Compressor

Capacity

kW

Power input

kW

D3SC-75X 5.50 4.32 3DC-75X 6.99 4.87

D3SS-100X 8.15 6.17 3DS-100X 9.59 6.53

Table 14: Performance with R404A @ low temperature: -35°C / 40°C / 20°C / 0K

4.1.3 Capacity – R134a refrigerant

S-Series Discus

Compressor Capacity

kW

Power input

kW Compressor

Capacity

kW

Power input

kW

D3SC-75X 10.45 4.95 3DC-75X 11.55 4.71

D3SS-100X 13.75 6.57 3DS-100X 15.15 6.19

Table 15: Performance with R134a @ medium temperature: -10°C / 45°C / 20°C / 0K

4.1.4 Capacity – R22 refrigerant

S-Series Discus

Compressor Capacity

kW

Power input

kW Compressor

Capacity

kW

Power input

kW

D3SA-75X D3SA-750 14.35 6.42 3DA-750 3DA-750 16.10 6.23

D3SC-100X D3SC-1000 17.35 7.83 3DC-1000 3DC-1000 19.20 7.37

D3SS-150X D3SS-1500 24.00 10.80 3DS-1500 3DS-1500 25.70 10.05

Table 16: Performance with R22 @ medium temperature: -10°C / 45°C / 20°C / 0K

Page 11: Front page S Discus E 1013 - Emerson Climate · 2D and 3D Discus compressors exist in Star-delta and Part-winding motor versions Motor code Power supply Nominal voltage Start connection

8 D5.4.6/1113/E

S-Series Discus

Compressor * Capacity

kW

Power input

kW Compressor **

Capacity

kW

Power input

kW

D3SC-750 D3SC-750 4.85 3.94 3DC-75X 3DC-750 5.44 4.04

D3SS-1000 D3SS-1000 6.70 5.56 3DS-100X 3DS-1000 7.50 5.73

* Performance with DTC injection for operation at low temp with R22 ** Performance with Demand Cooling injection for operation at low temp with R22

Table 17: Performance with R22@ low temperature: -35°C / 40°C / 20°C / 0K

4.1.5 Electrical values (current) – R404A refrigerant

S-Series Discus

Compressor Current

A

MOC

A

LRA

A Compressor

Current

A

MOC

A

LRA

A

D3SA-75X 13.7* 17.9 82 3DA-75X 13.38* 17.5 106

D3SC-75X 9.99** 18.7 82 3DC-75X 10.37** 18.3 70

D3SC-100X 16.13* 21.6 106 3DC-100X 15.53* 20.5 121

D3SS-100X 13.16** 26 109 3DS-100X 12.35** 244 121

D3SS-150X 21.77* 30.2 125 3DS-150X 20.53* 29 129 * Medium temperature: -10°C / 45°C / 20°C / 0K **Low temperature: -35°C / 40°C / 20°C / 0K

Table 18: Motor current values in Ampere

4.2 Dimensions

D3S and 3D compressors are totally interchangeable in terms of dimensions.

Dimensions in mm Shut off valve

diameter

A B C L I H Suction Discharge

D3SA-750/X 3DA-750/X

305 381 356

680

370 445 1” 3/8

1” 1/8

D3SC-750/X 3DC-750/X 650

D3SC-1000/X 3DC-1000/X 680

D3SS-1000/X 3DS-1000/X 680

D3SS-1500/X 3DS-1500/X 710 1” 5/8

Table 19: Compressor dimensions

A B

l

H

L C

Page 12: Front page S Discus E 1013 - Emerson Climate · 2D and 3D Discus compressors exist in Star-delta and Part-winding motor versions Motor code Power supply Nominal voltage Start connection

D5.4.6/1113/E 9

4.3 Motor

4.3.1 Motor current characteristics

For correct sizing of electrical protection devices and wires use the values shown below:

S-Series Discus

Compressor Current

A MOC

A LRA

A Compressor

Current A

MOC A

LRA A

D3SA-750/X 13.7* 18.5 / 17.9 82 3DA-750/X 13.38* 18 / 17.5 106

D3SC-750/X 9.99** 17 / 18.7 82 3DC-750/X 10.37** 13.8 / 18.3 70

D3SC-1000/X 16.13* 22.8 / 21.6 106 3DC-1000/X 15.53* 21.3 / 20.5 121

D3SS-1000/X 13.16** 24.2 / 26,0 109 3DS-1000/X 12.35** 18.6 / 24.4 121

D3SS-1500/X 21.77* 31.1 / 30.2 125 3DS-1500/X 20.53* 28.8 / 29 129 * Medium temperature: -10°C / 45°C / 20°C / 0K **Low temperature: -35°C / 40°C / 20°C / 0K

Table 20: Motor current values in Ampere

4.3.2 Motor codes

The motor versions that are proposed are the same for D3S and 3D compressors.

4.4 Accessories

The standard delivery content of D3S and 3D compressors is the same.

4.4.1 Common accessories

D3S and 3D compressors use the same following accessories:

Shut off valves Mounting parts Crankcase heaters Oil pressure switches Additional fans

4.4.2 Specific accessories

4.4.2.1 Liquid injection

Liquid injection systems (DTC and Demand Cooling) were used for applications with R22 at low evaporating temperatures.

NOTE: R22 is no longer allowed for new refrigeration systems in Europe. Only recycled R22 is allowed for maintenance until 2015. From 1

st January 2015, R22 supply will be

forbidden.

Changing a compressor on an installation could be an opportunity to exchange R22 for a longer term refrigerant and at the same time to discard the liquid injection system.

DTC (Discharge Temperature Control): The DTC liquid Injection used on D3S compressors cannot be used on 3D compressors. The Demand Cooling system will be an alternative.

Demand Cooling: “Demand Cooling” as the term implies, means liquid refrigerant injection on demand. Demand Cooling is required for R22 operation of Discus compressors at low temperature.

4.4.2.2 Capacity control

Capacity control does not exist on D3S compressors.

Moduload and Digital are the two types of capacity modulation available for 3D compressors. If capacity modulation is required, either Moduload or Digital must be included in the original customer order for installation at the factory.

4.4.2.3 Unloaded start

Both models use the same principle for unloaded start. However the unloaded-start kits are not interchangeable (except the piping assembly with control valve). The unloaded start can be ordered as an accessory (already assembled with the compressor) or as a separate upgrade kit.

Page 13: Front page S Discus E 1013 - Emerson Climate · 2D and 3D Discus compressors exist in Star-delta and Part-winding motor versions Motor code Power supply Nominal voltage Start connection

10 D5.4.6/1113/E

5 Replacement of D4 and D6 compressors

A special Replacement Guideline is dedicated to the replacement of S-Series and Discus compressors with Service compressors. Performance/dimensions comparison tables and advice for replacement are provided in that document.

The cross reference tables given below do not take the various refrigerants into account. For more accurate equivalence it is advised to read the Replacement Guidelines “Service Compressors for 4 & 6 Cylinder S-Series and Discus (D4D, D4S, D6D, D6S)”, available on our website at www.emersonclimate.eu.

D4S, D6S Displacement

@ 50 Hz Service

compressors Displacement

@ 50 Hz

Mineral oil Ester oil m3/h Ester oil m3/h

D4SF-1000 D4SF-100X 56.00 4MFS1-13X 61.72

D4SA-1000 D4SA-100X 56.00 4MFS1-13X 61.72

D4SA-2000 D4SA-200X 56.00 4MAS1-22X 61.72

D4SL-1500 D4SL-150X 70.80 4MLS1-15X 71.40

D4SH-1500 D4SH-150X 70.80 4MLS1-15X 71.40

D4SH-2500 D4SH-250X 70.80 4MHS1-25X 71.40

D4ST-2000 D4ST-200X 84.50 4MMS1-20X 78.25

D4SJ-2000 D4SJ-200X 84.50 4MMS1-20X 78.25

D4SJ-3000 D4SJ-300X 84.50 4MIS1-30X 78.25

D6SF-2000 D6SF-200X 84.00 4MMS1-20X 78.25

D6SA-3000 D6SA-300X 84.00 6MHS1-35X 104.48

D6SL-2500 D6SL-250X 106.00 6MLS1-27X 104.48

D6SH-2000 D6SH-200X 106.00 6MLS1-27X 104.48

D6SH-3500 D6SH-350X 106.00 6MHS1-35X 104.48

D6ST-3000 D6ST-300X 127.00 6MMS1-30X 120.51

D6ST-3200 D6ST-320X 127.00 6MMS1-30X 120.51

D6SJ-3000 D6SJ-300X 127.00 6MMS1-30X 120.51

D6SJ-4000 D6SJ-400X 127.00 6MIS1-40X 120.51

D6SU-4000 D6SU-400X 152.00 6MTS1-35X 135.09

D6SK-4000 D6SK-400X 152.00 6MTS1-35X 135.09

D6SK-5000 D6SK-500X 152.00 6MJS1-45X 135.09

Table 21: Cross reference between S-Series and Service compressors

D4D, D6D Displacement

@ 50 Hz Service

compressors Displacement

@ 50 Hz

Mineral oil Ester oil m3/h Ester oil m3/h

D4DF-1000 D4DF-100X 56.00 4MFS1-13X 61.72

D4DA-1000 D4DA-100X 56.00 4MFS1-13X 61.72

D4DA-2000 D4DA-200X 56.00 4MAS1-22X 61.72

D4DL-1500 D4DL-150X 70.80 4MLS1-15X 71.40

D4DH-1500 D4DH-150X 70.80 4MLS1-15X 71.40

D4DH-2500 D4DH-250X 70.80 4MHS1-25X 71.40

D4DT-2000 D4DT-200X 84.50 4MMS1-20X 78.25

D4DJ-2000 D4DJ-200X 84.50 4MMS1-20X 78.25

D4DJ-3000 D4DJ-300X 84.50 4MIS1-30X 78.25

D6DL-2500 D6DL-250X 106.00 6MLS1-27X 104.48

D6DH-2000 D6DH-200X 106.00 6MLS1-27X 104.48

D6DH-3500 D6DH-350X 106.00 6MHS1-35X 104.48

D6DT-3200 D6DT-320X 127.00 6MMS1-30X 120.51

D6DJ-3000 D6DJ-300X 127.00 6MMS1-30X 120.51

D6DJ-4000 D6DJ-400X 127.00 6MIS1-40X 120.51

Table 22: Cross reference between Discus and Service compressors

Page 14: Front page S Discus E 1013 - Emerson Climate · 2D and 3D Discus compressors exist in Star-delta and Part-winding motor versions Motor code Power supply Nominal voltage Start connection

D5.4.6/1113/E 11

6 Replacement of D8S compressors

The D8S reed valve 8-cylinder S-Series will be phased out and replaced with the high efficiency Copeland Discus 8D series.

6.1 Performance – Cross reference tables

6.1.1 Cross reference table

D8S models Discus equivalent models Displacement @ 50 Hz

Mineral oil Ester oil Mineral oil Ester oil m3/h

D8SH-3700 D8SH-370X 8DL-3700 8DL-370X

151

D8SH-400X 151

D8SH-5000 D8SH-500X 8DH-500X 151

D8SJ-4500 D8SJ-450X 8DT-4500 8DT-450X

181

D8SJ-500X 181

D8SJ-6000 D8SJ-600X 8DJ6000 8DJ-600X 181

D8SK-6000 D8SK-600X 210

D8SK-7000 D8SK-700X 210

Table 23: Equivalence table

6.1.2 Capacity – R404A refrigerant

S-Series Discus

Compressor Capacity

kW Power input kW Compressor

Capacity kW

Power input kW

D8SH-370X 74.00 35.20 8DL-370X 81.40 34.70

D8SH-500X 78.20 63.30 8DH-500X 81.70 34.70

D8SJ-450X 90.50 40.90 8DT-450X 96.00 42.60

D8SJ-600X 90.40 40.60 8DJ-600X 98.00 41.90

Table 24: Performance with R404A @ medium temperature: -10°C / 45°C / 20°C / 0K

S-Series Discus

Compressor Capacity

kW Power input kW Compressor

Capacity kW

Power input kW

D8SH-370X 24.60 17.55 6MT-35X 8DL-370X

25.60 28.00

17.45 19.45

D8SJ-450X 28.70 20.60 8DL-370X 28.00 19.45

Table 25: Performance with R404A @ low temperature: -35°C / 40°C / 20°C / 0K

6.1.3 Capacity – R134a refrigerant

S-Series Discus

Compressor Capacity

kW Power input kW Compressor

Capacity kW

Power input kW

D8SH-370X 44.40 19.40 6MT-35X 43.10 17.30

D8SH-400X 43.40 18.70

D8SJ-450X 53.00 22.30 8DL-370X 48.20 19.40

D8SJ-500X 50.10 22.90

D8SK-600X 57.50 25.50 8DT-450X 58.20 23.70

Table 26: Performance with R134a @ medium temperature: -10°C / 45°C / 20°C / 0K

S-Series Discus

Compressor Capacity

kW Power input kW Compressor

Capacity kW

Power input kW

D8SH-400X 77.20 25.80 8DL-370X 84.50 25.80

D8SH-370X 77.90 26.80

D8SJ-500X 89.60 31.50 8DL-370X 84.50 25.80

D8SJ-450X 95.30 30.90 8DT-450X 100.00 31.80

D8SK-600X 105.00 36.30 8DT-450X 100.00 31.80

Table 27: Performance with R134a @ high temperature: 5°C / 50°C / 20K

Page 15: Front page S Discus E 1013 - Emerson Climate · 2D and 3D Discus compressors exist in Star-delta and Part-winding motor versions Motor code Power supply Nominal voltage Start connection

12 D5.4.6/1113/E

6.1.4 Capacity – R407C refrigerant

S-Series Discus

Compressor Capacity

kW Power input

kW Compressor

Capacity kW

Power input kW

D8SH-500X 63.20 27.70 8DH-500X 65.20 28.30

D8SJ-600X 79.90 34.00 8DJ-600X 78.20 33.70

D8SK-700X 89.80 39.50 -- -- --

Table 28: Performance with R407C @ medium temperature: -10°C / 45°C / 20°C / 0K

S-Series Discus

Compressor Capacity

kW Power input

kW Compressor

Capacity kW

Power input kW

D8SH-500X 114.00 38.10 8DH-500X 115.00 37.30

D8SJ-600X 136.50 46.40 8DJ-600X 137.50 45.40

D8SK-700X 161.00 55.00 -- -- --

Table 29: Performance with R407C @ high temperature: 5°C / 50°C / 20K

6.1.5 Capacity – R22 refrigerant

S-Series Discus

Compressor Capacity kW Power input kW Compressor Capacity kW Power input kW

D8SH-5000/500X 72.00 30.90 8DH-5000/500X 74.40 30.80

D8SJ-6000/600X 86.10 36.70 8DJ-6000/600X 89.20 36.90

D8SK-7000/700X 96.90 43.20 --

Table 30: Performance with R22 @ medium temperature: -10°C / 45°C / 20°C / 0K

6.1.6 Electrical values (current)

S-Series Discus

Compressor Current

A

MOC

A

LRA

A Compressor

Current

A

MOC

A

LRA

A

D8SH-370X 37.7*** 70.9 349 8DL-370X

40.3*** 74.3 349

D8SH-400X 43.5** 55 311 40.2**

D8SH-500X 58.30* 95.2 393 8DH-500X 59.3* 88.2 458

D8SJ-450X 46.9*** 90.8 441 8DT-450X

50.5*** 90.7 441

D8SJ-500X 52.9** 77 458 50.5**

D8SJ-600X 64.5* 106 476 8DJ-600X 70.8* 108 476

D8SK-600X 63.4** 88.2 476

D8SK-700X 81.7* 127 574 * Medium temperature: -10°C / 45°C / 20°C / 0K with R407C ** Medium temperature: -10°C / 45°C / 20°C / 0K with R134a ***Low temperature: -35°C / 40°C / 20°C / 0K with R404A

Table 31: Motor current values in Ampere

6.2 Dimensions

D8S and 8D compressors use the same body and consequently have many dimensions in common.

The cylinder heads have different heights, which has an impact on the width dimensions.

Dimensions in mm

Shut off valve diameter

A B C D E Suction Discharge

D8SH-3700X D8SH-400X D8SH-5000/X

835 700 240

467 227 2” 5/8

1” 5/8 8DL-3700/X 8DH-5000/X 475 235

D8SJ-4500/X D8SJ-500X D8SJ-6000/X 509 269

3” 1/8 8DT-4500/X 8DJ-6000/X 475 235

D8SK-600X 863 715 239 521 270 2” 1/8

D8SK-7000/X 907 756 280

Table 32: Compressor dimensions

Page 16: Front page S Discus E 1013 - Emerson Climate · 2D and 3D Discus compressors exist in Star-delta and Part-winding motor versions Motor code Power supply Nominal voltage Start connection

D5.4.6/1113/E 13

6.3 Motor

6.3.1 Motor current characteristics

For correct sizing of electrical protection devices and wires use the values shown below:

S-Series Discus

Compressor Current

A

MOC

A

LRA

A Compressor

Current

A

MOC

A

LRA

A

D8SH-3700/X 37.7*** 63.3 / 70.9

349 8DL-3700/X

40.30*** 74.3 349

D8SH-400X 43.5** 55 311 40.22**

D8SH-5000/X 58.3* 95.2 393 8DH-5000/X 59.35* 88.2 458

D8SJ-4500/X 46.9*** 77.9 / 90.8

441 8DT-4500/X

50.48*** 90.7 441

D8SJ-500X 52.9** 77 458 50.48**

D8SJ-6000/X 64.5* 106 476 8DJ-6000/X 70.81* 108 476

D8SK-600X 63.4** 88.2 476

D8SK-7000/X 81.7* 127 574 * Medium temperature: -10°C / 45°C / 20°C / 0K with R407C ** Medium temperature: -10°C / 45°C / 20°C / 0K with R134a *** Low temperature: -35°C / 40°C / 20°C / 0K with R404A

Table 33: Motor current values in Ampere

6.3.2 Motor codes

The motor versions that are proposed are the same for D8S and 8D compressors.

6.4 Accessories

The standard delivery content of D8S and 8D compressors is the same.

6.4.1 Common accessories

D8S and 8D compressors use the same following accessories:

Shut off valves Mounting parts Crankcase heaters Oil pressure switches

Page 17: Front page S Discus E 1013 - Emerson Climate · 2D and 3D Discus compressors exist in Star-delta and Part-winding motor versions Motor code Power supply Nominal voltage Start connection

14 D5.4.6/1113/E

6.4.2 Specific accessories

6.4.2.1 Additional fans

D8S and 8D compressors use the same additional fan, but the mounting parts are different and will have to be changed.

6.4.2.2 Capacity control

Both S-Series and Discus compressors can be used with capacity control, but they use specific capacity control components. Only the solenoid valve/coil/gasket kit is interchangeable.

The capacity control can be ordered as an accessory (already assembled together with the compressor) or as a separate upgrade kit.

6.4.2.3 Unloaded start

Both S-Series and Discus compressors can be used with unloaded start, but they use specific unloaded start components. Only the solenoid valve/coil/gasket kit is interchangeable.

The unloaded start can be ordered as an accessory (already assembled together with the compressor) or as a separate upgrade kit.

7 Motor protection

Copeland Brand compressors use a new generation of thermistor protection which has the same main features as the old one.

IMPORTANT

Different source for power supply and contacts 11 & 14! Module malfunction! Use same potential for power supply and the switch contact of the control loop (11-14).

Figure 1: Motor protection wiring diagram

Page 18: Front page S Discus E 1013 - Emerson Climate · 2D and 3D Discus compressors exist in Star-delta and Part-winding motor versions Motor code Power supply Nominal voltage Start connection

D5.4.6/1113/E 15

8 Replacement for operation in parallel

8.1 Parallel operation with active oil management systems

When replacing a compressor on an installation with oil management systems, having the same sight glasses at the same position is the easiest situation as no modification of the equalisation line is required.

8.1.1 Replacement with same sight glass design and position

Replacement of D3S with 3D compressors Replacement of D4S, D4D, D6S and D6D with Service compressors Replacement of D8S with 8D compressors

It is possible to keep the existing oil management systems when replacing a compressor in a rack.

Replacement compressor acceptable oil levels are the same as for the original compressors.

8.1.2 Replacement with same sight glass design but different position

Replacement of D2S with 2D Replacement of D2S with 3D

The oil level regulators will fit the replacement sight glasses, but the oil equalisation line will have to be modified.

8.1.3 Replacement with different sight glass design

Replacement of D2S with LSG:

o D2S use 3 screw sight glasses, and LSG uses a male type sight glass The sight glass adaptor will have to be changed

o The position of the sight glass is different The oil equalisation line will have to be modified

Replacement of D8S with 6M:

o Both compressors use 3 screw sight glasses, but the 6M sight glass is reversed The sight glass adaptor will have to be changed

o The position of the sight glass is different The oil equalisation line will have to be modified

8.2 Parallel operation with passive oil management systems

Parallel operation with passive oil management system will only be possible with compressors listed in section 8.1.1 above.

These Tandem combinations will ensure about the same behaviour of the replacement compressor in terms of oil distribution compared to the original models (Twin and parallel operation in rack), even if both compressors are equipped with blocked suction capacity control. Since the sight glasses are identical, it is possible to keep the existing adapters for connection to compressor body at sight glass position when replacing a compressor in a rack.

For trio applications, it is expected that the replacement compressor will perform like the original models in terms of gas and oil equalization. However, Emerson Climate Technologies cannot exclude that modifications of existing passive oil management systems are required or that an active oil management system is the only successful solution.

For applications with more than 3 compressors only active oil management systems are recommended.

Page 19: Front page S Discus E 1013 - Emerson Climate · 2D and 3D Discus compressors exist in Star-delta and Part-winding motor versions Motor code Power supply Nominal voltage Start connection

Emerson Climate Technologies - European Headquarters - Pascalstrasse 65 - 52076 Aachen, GermanyTel. +49 (0) 2408 929 0 - Fax: +49 (0) 2408 929 570 - Internet: www.emersonclimate.eu

For more details, see www.emersonclimate.euD5.

4.6/

1113

/E

The Emerson Climate Technologies logo is a trademark and service mark of Emerson Electric Co. Emerson Climate Technologies Inc. is a subsidiary of Emerson Electric Co.Copeland is a registered trademark and Copeland Scroll is a trademark of Emerson Climate Technologies Inc.. All other trademarks are property of their respective owners.Emerson Climate Technologies GmbH shall not be liable for errors in the stated capacities, dimensions, etc., as well as typographic errors. Products, specifications, designs and technical data contained in this document are subject to modification by us without prior notice. Illustrations are not binding.© 2013 Emerson Climate Technologies, Inc.

BENELUXDeltakade 7NL-5928 PX VenloTel. +31 77 324 02 34Fax +31 77 324 02 [email protected]

UK & IRELANDUnit 17, Theale Lakes Business ParkReading, Berks RG7 4GB Tel: +44 1189 83 80 00Fax: +44 1189 83 80 [email protected]

BALKANSelska cesta 93HR-10 000 ZagrebTel. +385 1 560 38 75Fax +385 1 560 38 [email protected]

GERMANY, AUSTRIA & SWITZERLANDSenefelder Str. 3DE-63477 MaintalTel. +49 6109 605 90Fax +49 6109 60 59 [email protected]

SWEDEN, DENMARK, NORWAY & FINLANDPascalstr. 65DE-52076 AachenTel. +49 2408 929 0Fax +49 2408 92 95 [email protected]

UKRAINETurgenevskaya Str. 15, office 33UA-01054, KievTel. +38 - 44 - 4 92 99 24Fax. +38 - 44 - 4 92 99 [email protected]

FRANCE, GREECE & MAGHREB8, Allée du Moulin BergerFR-69134 Ecully CédexTel. +33 4 78 66 85 70Fax +33 4 78 66 85 [email protected]

EASTERN EUROPE & TURKEYPascalstr. 65DE-52076 AachenTel. +49 2408 929 0Fax +49 2408 929 [email protected]

ROMANIA

Tel. +40 - 374 -13 23 50Fax +40 - 374 -13 28 [email protected]

ITALYVia Ramazzotti, 26IT-21047 Saronno (VA)Tel. +39 02 96 17 81Fax +39 02 96 17 88 [email protected]

POLANDSzturmowa 2PL-02678 WarsawTel. +48 22 458 92 05Fax +48 22 458 92 [email protected]

MIDDLE EAST & AFRICAPO Box 26382Jebel Ali Free Zone - South, Dubai - UAETel. +971 4 811 81 00Fax +971 4 886 54 [email protected]

SPAIN & PORTUGALC/ LLull, 321 (Edifici CINC)ES-08019 BarcelonaTel. +34 93 412 37 52Fax +34 93 412 42 [email protected]

RUSSIA & CISLetnikovskaya 10, Bld. 2, floor 5RU-115114 MoscowTel. +7 495 981 98 11Fax +7 495 981 98 [email protected]

CZECH REPUBLIC Hajkova 2747/22CZ-13000 Prague 3Tel +420 271 035 628Fax +420 271 035 [email protected]