12 SWITCHBOARDS Front Connected Switchboards Type SB1, SB2 and SB3 General Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog 12-2 Maximum Flexibility Whether the design is for a 240V ac, 400 ampere system; a 600V ac, 6000 ampere system; or something in between, Siemens front connected switchboards should be considered. Every aspect of the equipment design has been targeted at improving layout convenience, reducing installation costs, and minimizing the impact and cost of system changes. These switchboards provide the rugged construction and service reliability required for industrial plants, hi-rise complexes, hospitals, and commercial buildings, and are built to UL 891 and NEMA PB-2 standards. Type SB1 For Limited Space Applications The Siemens type SB1 switchboard has been specifically designed for those applications where floor space is at a premium. The SB1 contains front-connected protective devices and bus ratings up to 2000 amperes at 600V ac. The rear of all sections align as standard. Type SB2 For Increased Service And More Load Cable Room Siemens SB2 switchboards can have extra depth behind the vertical bus in each distribution section, and contains protective devices and bus rated up to 4000 amperes at 600V ac. The rear of all sections align as a standard. Front and rear alignment is available as an option. Type SB3 For Custom Options The SB3 switchboard is available with protective devices and bus up to 6000 amperes at 600V ac. Options include, but are not limited to, incoming and outgoing busway, ACCESS communication, protective relaying, autothrowover schemes and transformer connections. Siemens SB Switchboards Available Features SB1 SB2 SB3 Maximum Bus Rating 2000A 4000A 6000A Main Devices MCCB, VB, HCP, BPS MCCB, VB, HCP, BPS, WL (Fixed) MCCB, VB, HCP, BPS, WL Feeder Devices MCCB, VB, HCP, BPS MCCB, VB, HCP, BPS, WL, (Fixed) MCCB, VB, HCP, BPS, WL Solid State MCCB No 100,000 AIC 200,000 AIC Customer Metering Yes Yes Yes Utility Metering Yes Yes Yes Density Rated Bussing No Yes Yes Accessible Front Front Front (up to 38" deep) Front/Rear (Above 38" deep) Alignment Rear Rear STD; Rear/Front Optional Rear STD; Rear/Front Optional For additional information on this product visit our website at www.sea.siemens.com. For application pricing information contact your local distributor or the closest Siemens sales office.

Transcript of Front Connected Switchboards

Page 1: Front Connected Switchboards

12SW

ITCH

BOAR

DS

Siemens / Speedfax Previous folio: 12-2

Front Connected SwitchboardsType SB1, SB2 and SB3 General

Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog12-2

Maximum FlexibilityWhether the design is for a 240V ac,400 ampere system; a 600V ac, 6000ampere system; or something inbetween, Siemens front connectedswitchboards should be considered.Every aspect of the equipment designhas been targeted at improving layoutconvenience, reducing installationcosts, and minimizing the impact and cost of system changes. Theseswitchboards provide the ruggedconstruction and service reliabilityrequired for industrial plants, hi-risecomplexes, hospitals, and commercialbuildings, and are built to UL 891 andNEMA PB-2 standards.

Type SB1 For LimitedSpace ApplicationsThe Siemens type SB1 switchboard has been specifically designed for those applications where floor space is at a premium. The SB1 containsfront-connected protective devices and bus ratings up to 2000 amperes at 600V ac. The rear of all sections align as standard.

Type SB2 For Increased ServiceAnd More Load Cable RoomSiemens SB2 switchboards can haveextra depth behind the vertical bus ineach distribution section, and containsprotective devices and bus rated up to4000 amperes at 600V ac. The rear ofall sections align as a standard. Frontand rear alignment is available as anoption.

Type SB3 For Custom OptionsThe SB3 switchboard is available withprotective devices and bus up to 6000amperes at 600V ac. Options include,but are not limited to, incoming andoutgoing busway, ACCESScommunication, protective relaying,autothrowover schemes andtransformer connections.

Siemens SB SwitchboardsAvailable Features SB1 SB2 SB3Maximum Bus Rating 2000A 4000A 6000A

Main Devices MCCB, VB, HCP, BPS MCCB, VB, HCP, BPS, WL (Fixed) MCCB, VB, HCP, BPS, WL

Feeder Devices MCCB, VB, HCP, BPS MCCB, VB, HCP, BPS, WL, (Fixed) MCCB, VB, HCP, BPS, WL

Solid State MCCB No 100,000 AIC 200,000 AIC

Customer Metering Yes Yes Yes

Utility Metering Yes Yes Yes

Density Rated Bussing No Yes Yes

Accessible Front Front Front (up to 38" deep)

Front/Rear (Above 38" deep)

Alignment Rear Rear STD; Rear/Front Optional Rear STD; Rear/Front Optional

For additional information on this product visit our website at www.sea.siemens.com.For application pricing information contact your local distributor or the closest Siemens sales office.

Sect_12_Speedfax2007 3/27/07 9:59 AM Page 12-2

Page 2: Front Connected Switchboards

12SW

ITCHBOARDS

Siemens / Speedfax Previous folio: 12-4

Integrated Power Systems Switchboards Type IPS General

� • Main Breaker or Switch

up to 4000 Amp

• MLO to 2000 Amp

� Transient Voltage

Surge Suppressor

� Digital Meter

• PLC

•• •

� •

� •

� •

•• •

� Service Section Distribution Sections

� �

Distribution Transformer

Lighting Control

Lighting Contactors, PLC, Time Clocks,

ATS, Telephone Cabinets

HVAC Control

Customer Supplied Components

Lighting Panelboards

• Feeder Breakers (up up 4000 Amp)

• Feeder Switches (up up 4000 Amp)

• Motor Starter Modules

(up to NEMA Size 4)

• Lighting Contactors (30 to 225 Amp)

• Time Clock Local Display Unit

(ACCESSTM Communication)

For additional information on this product visit our website at www.sea.siemens.com.For application pricing information contact your local distributor or the closest Siemens sales office.

The modular design of the Siemens lPSswitchboard allows the user to integrateelectrical distribution equipment, powermonitoring and environmental controlsthat typically mount in multipleenclosures into one switchboard line-up.Users have the freedom to configure anarrangement that best fits their individualneeds. Optional factory installedinterconnection wiring is available tofurther reduce installation time.

lPS Equipment Benefits include:

▪ Less product to handle and install

▪ Lower total installation cost

▪ Less time on the jobsite

▪ Less floor space used for electricalequipment

▪ Single source equipment supplier

▪ Simplified field setup and programming

lPS switchboards are built to UL 891 andNEMA PB-2 standards. Standard heightof lPS sections is 90 inches. Optionalheight of 70 inches is available. Minimumdepth of lPS switchboards is 13.75inches. Optional depths of 20, 28 and 38

inches are available. Some componentsdictate the use of optional depths.

Numerous components are availableto fit customer's individual needs.

▪ Lighting Panelboards (MLO and MainDevice)

▪ Power Monitoring

▪ Distribution Transformers

▪ ACCESS Communication

▪ Lighting Contactors

▪ Lighting Control

▪ HVAC Control

▪ Building Management

▪ PLC

▪ Automatic Transfer Switch

▪ Motor Starter Units

▪ Backup Generators

Typical lPS switchboards consist ofone service section and one or moredistribution sections that are cableconnected. However, lPS switchboards are alsoavailable with through bus and pullsections. lPS switchboards will

accommodate systems up to 4000amperes. 600V ac maximum in 1-phase 3-wire, 3-phase 3-wire, or 3-phase 4-wireconfigurations.

All components can be built into standard NEMA Type 1 indoorenclosures, or optional NEMA Type 3Routdoor construction.

Bus bars are available in standard tin-finished aluminum or optional silver-finished copper. Standard bus issized on the basis of heat rise criteria, inaccordance with UL 891. All bus bars aresized to limit heat rise to 65ºC above amaximum ambient temperature of 40ºC.

As an option, conductor material can besized according to density limits, basedon bus material. The applicable limits are:

Copper — 1000 amperes sq. in.

Aluminum — 750 amperes sq. in.

Screw type mechanical connectors (lugs)are provided as standard equipment onall devices. However, compressionconnectors are available as an option.

Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog 12-3

Sect_12_Speedfax2007 3/27/07 9:59 AM Page 12-3

Page 3: Front Connected Switchboards

12SW

ITCH

BOAR

DS

Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog12-4

Siemens / Speedfax Previous folio: 12-11

Integrated Power Systems Switchboard (Type IPS)Individually Mounted Devices

Dimensions shown in inches and millimeters ( ).

5.00(127)2.50 (63.5)

5.00(127)

2.50 (63.5)

W

2.50 (63.5)

2.50 (63.5)

3.00 (76.2)

CONDUIT AREATOP & BOTTOM

Unit Space75.00(1905)

90.00(2286)

D

3.00 (76.2)

Sect_12_Speedfax2007 3/27/07 10:00 AM Page 12-4

Page 4: Front Connected Switchboards

12SW

ITCHBOARDS

Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog 12-5

Siemens / Speedfax Previous folio: 12-12

Integrated Power Systems Switchboard (Type IPS)Individually Mounted Devices

Component Dimensions in inches (mm)

Required Minimum MinimumUnit Space Section Width (W) Section Depth (D)

P3 Panels 25.00 (635)P1, P2 Panels

Time Clock � (Up to 6 in 20" and 25" wide, 37.50 (953) � 20.00 (508) � 13.75 (349)

9 in 32" wide)

LCP Lighting Control Panel 25.00 (635)

Distribution Transformer � (15 KVA)37.50 (953) � 20.00 (508)

20.00 (508)Distribution Transformer � (30 - 45 KVA) 25.00 (635)

Distribution Transformer � (75 - 112.5 KVA) 37.50 (953) 32.00 (813)

Distribution Transformer � (150 KVA)38.00 (965)

28.00 (711)

Distribution Transformer � (225 KVA) 75.00 (1905)

Distribution Transformer � (300 KVA) 46.00 (1168) 38.00 (965)

Lighting Contactor (Up to 4 in 20" and 25" wide,30 through 225 Amp � 6 in 32" wide)ASCO 920 or Siemens CLH �

37.50 (953) 20.00 (508) 13.75 (349)PLC (LOGO!) � (Up to 6 in 20" and 25" wide, 9 in 32" wide)

PLC (S7–200) � (Up to 4 in 20" and 25" wide, 6 in 32" wide)

Automatic Transfer Switch 75.00 (1905)

32.00 (813) 20.00 (508)(up to 400 Amp) � �

400-1200 Amp MCCB

1600-2000 Amp MCCB 37.50 (953)28.00 (711)

800-2000 Amp ICCB (WL Breaker)38.00 (965)2500-4000 Amp ICCB (WL Breaker) 75.00 (1905)

800-1200 Amp BPS 37.50 (953)38.00 (965)1600-2000 Amp BPS

75.00 (1905)2500-4000 Amp BPS 46.00 (1168)

Unit Space For Components

NOTE: For required unit space relative to HVAC control and custom specified components, contact Siemens sales.

� These components can be mixed in a 37.5" (953mm) high compartment.� 37.50" (half section) for panels that would fit in to panel cans <=44".

75" (full section) for panels that would fit into panel cans >44".� 20.00" for P1/P2 panel (note may be mounted 2 across in >=38" wide sections).

25" for P3 panels (note may be mounted 2 across in >=46" wide sections).� Distribution transformer minimum size requirements are based on 150 degree rise TP1

rated units - aluminum or copper bus. Consult Siemens for size requirements related to otherratings including K-Rated. Outdoor sections with transformers must also have rear dooradded to that section for ventilation. Stacked transformers in a section are limited to 45KVAat this time. Contact Siemens for updated information.

� For CLH contactor only, up to 6 in 20"and 25" wide section can be mounted and 9 in a 32" wide section.

� ATS includes generator controls. Contact Siemens sales for details.� Emergency power generators are available. Contact Siemens sales for details.

Sect_12_Speedfax2007 3/27/07 10:00 AM Page 12-5

Page 5: Front Connected Switchboards

12SW

ITCH

BOAR

DS

Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog12-6

Siemens / Speedfax Previous folio: 12-13

Integrated Power Systems SwitchboardTypical IPS Lineup

Dimensions shown in inches and millimeters ( ).

D

32.00 (813)

800 A MLO DP1 480Y/ 277 Vac

38.00 (965)

75 KVA XFMR

20.00 (508)

250 A MLO P1 LP3

28.00 (711)

13.75 (349)

250 A MLO P1 LP2

250 A MB P1 LP1 250 A

MLO P1

LPD

Sect_12_Speedfax2007 3/27/07 10:00 AM Page 12-6

Page 6: Front Connected Switchboards

12SW

ITCHBOARDS

Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog 12-7

Siemens / Speedfax Previous folio: 12-8

General Layout Information (Type SB1, SB2, SB3, IPS)Individually Mounted Service Mains

H1

W1

D

Main

9300Meter

H1

W1

D

Main

W2

9300Meter

H1

W1

D

Main

W3

9300Meter

H1

W1

D

Main

9300Meter

Top Entrance Cables Pull Box

Bottom Entrance withNon-Bussed Pull Section

Bottom Entrance withBussed Pull Section

Bottom Entrance

Dimensions in Inches (mm)Height Width

Pull Section

Max.Non- Bussed

Amp. Device Bussed UG �

Rating Type H1 W1 W2 W3

Molded Case Circuit Breakers

HJXD6, HHJD6,HHJXD6, JXD2, 14.00 400JXD6, JD6, HJD6, (356)SJD6, SHJD6 32.00 HLXD6, HHLD6, (813)HHLXD6, LXD6, 20.00600LD6, HLD6, (508)SLD6, SHLD6

MXD6, MD6, HMD6,20.00 20.00 �

LMXD6, LMD6,800 HLMD6, HLMXD6, (508) (508)

SMD6, SHMD6, 90.00NM, HM, LM (2286)

NXD6, ND6, HND6,1000 SND6, SHND6,

HNXD6, NN, HN, LN 38.00 32.00

NXD6, ND6, HND6, (965) (813)1200

SND6, SHND6, HNXD6, NN, HN, LN

1600PXD6, PD6, HPD6,SPD6, HPXD6,NP, HP, LP 32.00 28.00 �

2000RXD6, RD6, (813) (711)HRXD6, HRD6

800 20.00 1200 32.00 (508) 28.00 �

1600 (813) (711)2000 90.00 38.00

32.002500

(2286) (965)(813)

3000 38.00 38.0

4000(965) (965)

Insulated Case Circuit Breakers — Stationary Mounted

Type WLInsulatedCaseBreaker

400 14.00 (356)600

HCP20.00 (508) 20.00 �

800 (508)1200

800 20.001000 Vacu-Break 38.00 (508)1200 (965) 32.00

800 90.00 (813) 28.00 �

1000(2286) (711)

12001600 Bolted2000 Pressure2500 32.00

3000 46.00 38.00 (813) 38.00

4000(1168) (965) (965)

Switches

� For EUSERC UGPS dimensions, refer to Siemens Front Connected Switchboard Selection & Application Guide.� Optional depths are 28 and 38 inches.� Optional depth is 38 inches.

MinimumRequiredDepth

Sect_12_Speedfax2007 4/6/07 12:46 PM Page 12-7

Page 7: Front Connected Switchboards

12SW

ITCH

BOAR

DS

Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog12-8

Siemens / Speedfax Previous folio: 12-5

General Layout Information (Type SB1, SB2, SB3, IPS)

Dimensions in inches (mm)

SuitableFor Use Unit Space � � �

Only As LugsMax. Service Av Max.Ampere Equipment AIC Height Standard Alternate Compression Width Minimum Conduit Area

Rating � � Rating (H) 500 kcmil 750 kcmil 600 kcmil Max. (W) � Depth (D) � K L

40062.50 60.00 (1588) (1524) 55.00

60060.00 56.25 (1397)

32 or 38(1524) (1429)(8.13 or

800 90.0058.75 52.50 965)

200,000 (2286)(1492) (1334) 53.75 13.75 2.50 3.00

1200 � 57.50 50.00 (1365) (349) (64) (76)(1461) (1270)

160045.00 38.75 45.00 38.00

2000(1143) (984) (1143) (965)

� 46 in. (1168) width available as an option.� See page 12-12 for unit space requirements for disconnect devices.� Optional 70" high is also available. Unit space is reduced by 20".� If load through bus is required, the available unit space is reduced by 7.50 inches for 400-1200 amp MLO sections.� Maximum of 6 disconnect devices only.� SUSE service disconnects 1000A or higher on solidly grounded wye systems of more than 150V to ground require ground fault protection. Ground fault uses 10 in.

(254 mm) of unit space. See NEC 230-95 for additional details. This applies to branch devices 1000A or larger on non-service equipment unless ground fault protection is provided upstream at the service. See NEC 240-13 for further information.

� Optional section depths are 20", 28" and 38."

Main Lug Only Unit Space

K

K

L L

H

W

D

M.L.O.

UnitSpace

Cond. AreaTop / Bottom

Top Entrance

K

K

L L

H

W

D

M.L.O.

UnitSpace

Cond. AreaTop / Bottom

Bottom Entrance

Main Lug Only — 400A through 2000A

Available as a userselectable option

Available branch circuit unit space variesdepending on amperage of incomingservice, lug type and if through bus is

required. If more unit space is requiredthan is shown in the table below, one ormore panel mount device distribution

sections must be added.

Sect_12_Speedfax2007 4/6/07 12:46 PM Page 12-8

Page 8: Front Connected Switchboards

12SW

ITCHBOARDS

Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog 12-9

Siemens / Speedfax Previous folio: 12-6

General Layout Information (Type SB1, SB2, SB3, IPS)

Main Breaker with or without Ground Fault Protection

Dimensions in inches (mm)

Max. Conduit Area ServiceAmpere Breaker Height Unit Space Width Minimum Main EntranceRating Type (H) � � � (W) Depth (D) � K L Location Label

JXD2, JXD6, JD6,

400HJD6, HJXD6,HHJD6, HHJXD6, SJD6, SHJD6 56.25 (1429)LXD6, LD6, HLD6, 32.00 (813)

600HLXD6, HHLD6,HHLXD6, SLD6, YesSHLD6LMD6, LMXD6, 90.00 13.75 2.50 3.00 Top orHLMD6, HLMXD6, (2286) 53.75 (1365) (349) (64) (76) BottomNM, HM, LM �

800 MXD6, MD6, HMD6, HMXD6

52.50 (1334)

SMD6, SHMD6 40.00 (1016)NXD6, ND6,

1000 HND6, HNXD6, 52.50 (1334)38.00 (965) �NN, HN, LN

SND6, SHND6 40.00 (1016)Yes

NXD6, ND6, 52.50 (1334)1200 HND6, HNXD6,

NN, HN, LNSND6, SHND6 40.00 (1016)

� Ground fault, if applied, uses 10 in. (254 mm) of unit space.� See page 12-12 for unit space requirements for disconnect devices.� Available unit space for 400 and 600 amp main breaker sections is reduced to

53.75 if load side through bus is required.

� Optional section depths are 20", 28" and 38".� Optional 70" high is also available. Unit space is reduced by 20".� 46 in. (1168 mm) wide if 750 kcmil or compression lugs required.

IPS service sections can house both a main service disconnect device andbranch disconnects. Switchboards can be furnished with “Suitable for Use Only as Service Equipment”

labels, but include no provisions for utility metering.

Branch circuit device unit space varies,depending on the rating and consequent

physical size of the main disconnectdevice. If more unit space is requiredthan is shown in the tables below, one or more additional panel mounted devicedistribution sections must be added.

W

D

M/B

L L

UnitSpace

GF H

K

K

Conduit AreaTop or Bottom

400 -1200A Main Breaker With GFP

Fig. 2 Bottom Entrance (Invert for top entrance)

W

D

H

K

K

L L

M C B

UnitSpace

Conduit AreaTop or Bottom

400-1200A Main Breaker Without GFP

Fig. 1 Top Entrance (Invert for bottom entrance)

Panel Mounted MCCB — 400A through 1200A

Sect_12_Speedfax2007 4/6/07 12:47 PM Page 12-9

Page 9: Front Connected Switchboards

12SW

ITCH

BOAR

DS

Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog12-10

Siemens / Speedfax Previous folio: 12-7

General Layout Information (Type SB1, SB2, SB3, IPS)

400 — 1200A HCP Switch Main

Dimensions in inches (mm)

Max. ServiceAmpere Height Unit Width Minimum Conduit Area Main EntranceRating (H) Space � (W) � Depth (D) � K L Location Label

400 Top600 90.00 � 46.25 38.00 13.75 2.50 3.00 or Yes

800 (2286) (1175) (965) (349) (64) (76) Bottom

1200

� 46 in. (1168 mm) width available as an option.� See page 12-12 for unit space requirements for disconnect devices.� Optional section depths are 20", 28" and 38".� Optional 70" high is also available. Unit space is reduced by 20".

400-1200AHCP

Main Switch

UnitSpace

W

D

H

K

K

L L

Conduit AreaTop or Bottom

400 -1200A HCP

Top Entrance (Invert for Bottom Entrance)

Panel Mounted HCP Switch Main — 400A through 1200A

Top Feed

BottomFeed

Sect_12_Speedfax2007 4/9/07 12:15 PM Page 12-10

Page 10: Front Connected Switchboards

12SW

ITCHBOARDS

Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog 12-11

Siemens / Speedfax Previous folio: 12-10

General Layout Information (Type SB1, SB2, SB3, IPS)Panel Mounted Devices Through-Bus Fed

K

K

L L

H1

W

D

BusBar

ThroughBus

UnitSpace

H2

Conduit AreaTop or Bottom

Through-Bus Fed Distribution Sections

Through-Bus Fed Dimensions

Dimensions in Inches (mm)

Height Width

WithMaximum Maximum Unit Minimum Conduit AreaRiser Through-Bus Space Section DepthAmperage Amperage H1� H2 � � W (D) � K L

20002000 2500 & 3000 65.00 (1651) 32.00 or 38.00 �

4000 90.00 (2286)(813) (965)

20.00 (508) 2.50 (64) 3.00 (76)

3000 4000 62.50 (1588)38.00 or 46.00(965) (1168)

� See page 12-12 for unit space requirements for disconnect devices.� Optional 70" high is available. Unit space is reduced by 20.� Optional section depths are 28" and 38".� 46 inches (118 mm) width optional.

Sect_12_Speedfax2007 4/6/07 12:47 PM Page 12-11

Page 11: Front Connected Switchboards

12SW

ITCH

BOAR

DS

Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog12-12

Siemens / Speedfax Previous folio: 12-9

General Layout Information (Type SB1, SB2, SB3, IPS)Unit Space for Panel Mount Disconnect and Miscellaneos Components

Unit Space Requirements — Molded Case Circuit Breakers (Mains and Branches)

Dimensions in inches (mm)

Max. Total Poles Unit Space Required EnclosureAmpere Device Available Twin Single MinimumRating Type 1P 2P 3P Mounted Mounted Width

100 BL, BLH, HBL, BQD, NGB, NEB, HEB6

2ED4, HHED6 2 3.75 (95)ED4, ED6, HED4, HHED6,NGB, NEB, HEBHED4, HHED6, ED4, NGB,

6.25 (159)125 ED6 with accessories

2CED6 3.75 (95) — 32.00 (813)CED6 with accessories

26.25 (159)

225 QJ2, QJH2, QJ2-H,HQJ2-HFXD6, FD6, HFD6, HFXD6, 5.00 (127)

250 HHFD6, HHFXD6CFD6 — 1 — 5.00 (127)JX2, JXD6, JD6, HJD6

—1 1 — 8.75 (222)

400 HJXD6, HHJD6, HHJXD6 2 2 8.75 (222) — 38.00 (965)SJD6, SHJD6 —LXD6, LD6, HLD6, HLXD6, 1

600 HHLD6, HHLXD6 8.75 (222) 32.00 (813)SLD6, SHLD6 —LMD6, LMXD6, HLMD6, HLMXD6 1 1 —

800MXD6, MD6, HMD6, HMXD6SMD6, SHMD6

10.00 (254) 38.00 (965) �

NM, HM, LM 8.75 (222) 38.00 (965)

1200 NXD6, ND6, HND6, HNXD6 1SND6, SHND6, NN, HN, LN —

10.00 (254) 38.00 (965) �

� 46 in. (1168mm) wide if 750 kcmil or compression lugs required.� The 2.5 in. (64) high unit is suitable for NEC Class H, K1 and K5 fuses only. Class R rejection type fuse holders

are not available.� Unit rated 600V, factory configured to accept 250V Class K or R fuses. Field convertible to accept Class J fuses.� Factory configure to accept Class J fuses only.

Component Unit Spacein inches (mm)

Local Display 10.00 (254)ADR 9000 (SRTU)Transient Voltage Surge 10.00 (254)Suppressor (TPS)9200A Digital Meter 10.00 (254)9200B Digital Meter 10.00 (254)9200C Digital Meter 10.00 (254)9300 Digital Meter 10.00 (254)9330 Digital Meter 10.00 (254)9350 Digital Meter 10.00 (254)Lighting Contactor30 to 225 Amp 10.00 (254)Siemens CLHLighting Contactor30 to 225 Amp ASCO 920 20.00 (508)Time ClockSangamo, Tork or Paragon 10.00 (254)PLC (LOGO!TM and S7) 10.00 (254)

Unit Space Requirements For Miscellaneous Components

Unit Space Requirements — Fusible Switches (Mains and Branches)

Dimensions in inches (mm)

Max Unit Space Required EnclosureAmp Switch 240V 600V MinimumRating Type Twin Single Twin Single Width

30-30 2.50 (64) � —30-3030-60 5.00 (127)60-60 — 7.50 (191) —

32.00 (813)60-100

7.50 (191)100-100 Vacu-Break200-200 10.00 (254) � 10.00 (254) �

100 7.50 (191) — 7.50 (191)200 10.00 (254) — 10.00 (254)400 —

15.00 (381)—

15.00 (381) 38.00 (965)600400 - 1200 HCP 16.25 (413) 16.25 (413)

Sect_12_Speedfax2007 4/6/07 12:48 PM Page 12-12

Page 12: Front Connected Switchboards

Siemens / Speedfax Previous folio: 12-3

Rear Connected SwitchboardsType RCS General

For additional information on this product visit our website at www.sea.siemens.com.For application pricing information contact your local distributor or the closest Siemens sales office.

Siemens RCS switchboards differ fromthe front connected (Type SB1, SB2,SB3) design primarily in the distributionsections. In the distribution section thebranch feeders are individually mounted.Because of this method of mounting,access to the outgoing cable terminalsmust be from the rear of the unit. Busbar extensions from the feeder devicesare run to the rear of the RCS sectionstopping before the conduit area foreasy access and cable connection. An optional cable management system

can be requested to secure the outgoingcables. The front and rear of all sectionsalign and are designed for mountingaway from the wall. RCS switchboardwill accommodate requirements up to6000 ampere and 600 volts. The mainbus can be specified for 400 to 6000ampere rating. Main, tie and branchdevices are available in amperage ratingsup to 6000 amps. RCS switchboards canbe indoor (NEMA 1) or outdoor (NEMA3R) construction.

RCS switch boards utilize Type WLinsulated case and/or low voltage powercircuit breakers with drawout mountings.Features and benefits include highbreaker density, 100kA standard shortcircuit bus bracing and three levels ofhorizontal bus. Options include insulated/isolated bus, Dynamic Arc Flash Sentry,ModBus Communication and intelligentpower monitoring.

WL Insulated Case WL LV PowerSwitchboard Circuit Breaker Circuit BreakerType RCS Mounting Drawout Mount Drawout Mount

Main Devices Individual 400-5000A 400-5000A

Branch Devices Individual 400-5000A 400-5000A

12SW

ITCHBOARDS

Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog 12-13

Sect_12_Speedfax2007 3/27/07 10:00 AM Page 12-13

Page 13: Front Connected Switchboards

12SW

ITCH

BOAR

DS

Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog12-14

Siemens / Speedfax Previous folio: 12-14

Multi-Metering Switchboards Type MMS GeneralIn today’s commercial and industrialenvironments, the electrical meteringrequirements vary according to thespecification of the development site.Siemens offers a solution with highquality multi-metering switchboards that meet the non-EUSERC arearequirements. The MMS switchboardmeets the requirements of memberutilities and municipalities with thesedependable commercial switchboards.

Features▪ Up to 4000A main service208Y/120V, three phase/four wire480Y/277V, 3-phase 4-wire

▪ 100A, 200A and 320A tenant mains are available

▪ UL listed and labeled

▪ NEMA “Non-EUSERC” Design

▪ Hot sequence metering is standard;cold sequence also available

▪ 50,000A symmetrical bus bracing isstandard; above 50,000A available uponrequest.

▪ All meter sockets are pre-wired for100A, 200A or 320A devices

▪ Copper or Aluminum bus available

▪ Units are front accessible.

▪ NEMA Type 1 and Type 3R constructionavailable

▪ Available with optional cable pullsections

▪ Sockets include lever type manual by-pass

▪ Load cable exit top or bottom

▪ Common depth for main and meteringsections upon request

▪ Ring-less type meter cover design

For additional information on this product visit our website at www.sea.siemens.com.For application pricing information contact your local distributor or the closest Siemens sales office.

Sect_12_Speedfax2007 5/10/07 2:09 PM Page 12-14

Page 14: Front Connected Switchboards

12SW

ITCHBOARDS

Siemens / Speedfax Previous folio: 12-14

Multi-Metering Switchboards Type SMM General

Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog 12-15

For additional information on this product visit our website at www.sea.siemens.com.For application pricing information contact your local distributor or the closest Siemens sales office.

Completely engineered and assembled,Siemens SMM commercial meteringswitchboards require minimal fieldassembly. They are UL listed and labeledand meet all EUSERC standards. SMMswitchboards are built to meet therugged requirements of the westernUnited States. These units can bemodified to meet any additionalrequirements of member utilities andmunicipalities. For a high qualitydependable commercial meteringswitchboard consider the West CoastSMM design.

Features▪ Up to 4000A main service120/240V 1-phase 3-wire240/120V 3-phase 4-wire208Y/120V 3-phase 4-wire480Y/277V 3-phase 4-wire

▪ 200 amp continuous duty metersockets

▪ Meets EUSERC requirements

▪ UL listed and labeled

▪ Hot sequence metering standard - cold sequence metering optional

▪ Test blocks are standard

▪ Copper or Aluminum bus

▪ 65,000A Sym bracing standard(higher bracing rating available ifrequired)

▪ Type NEMA Type 1 and Type 3Rconstruction available

▪ Meets UL891 and NEMA PB2standards

▪ Rear cable barriers available for topload cable exist

▪ Ring type meter cover design

Sect_12_Speedfax2007 3/27/07 10:00 AM Page 12-15

Page 15: Front Connected Switchboards

12SW

ITCH

BOAR

DS

Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog12-16

Siemens / Speedfax Previous folio: 12-15

Multi-Metering Switchboards Type SMM General

� SMM sections–Cross bus from 800–2500 ampere.Sections 20" deep.

� Price sockets with tenant mains from Table 7.4.6.25,7.4.6.26, 7.4.6.27. Price sockets only from Table 7.4.6.28.

� Cross bus is not included. Price from Table 7.4.6.29or 7.4.6.30.

� When load cables exit top of section, rear load barrier(RLB) must be priced. See Table 7.4.6.31.

� SMD sections required for cross bus exceeding2500 ampere. Sections 28" deep.

� Fuses not included. For Class J fuse provisions, changeR to J.

� 26" wide for Outdoor Type 3R. 38" wide for Outdoor Type 3R. 35" wide for Outdoor Type 3R.

NOTE: Component priced Meterboards allow for any combination of 100 and 200 ampere tenantmains or blank positions. Select the base structure, meter sockets and tenant mains accordingly.

Table 7.4.6.19 SMM� Sections With Space For CB Mains And Sockets� � �

Sockets Figure

3 A6 B

Table 7.4.6.20 SMD� Sections With Space For CB Mains And Sockets� � �

3 A6 B

Table 7.4.6.22 SMD� Sections With Space For T-Fuse Mains and Sockets� � �

3 A6 B

Table 7.4.6.21 SMM� Sections With Space For T-Fuse Mains And Sockets� � �

3 A6 B

Table 7.4.6.23 SMM� Sections With Space For VB Mains And Sockets � � � �

2 C6 D2 C6 D

Table 7.4.6.24 SMD� Sections With Space For VB Mains And Sockets � � �

2 C6 D2 C6 D

20" 32" 20" 32" 26"

Figure A� Figure B Figure C� Figure D

SMM/SMD Sections with Space for Tenant Mains/Meter Sockets

Sect_12_Speedfax2007 3/27/07 10:00 AM Page 12-16

Page 16: Front Connected Switchboards

12SW

ITCHBOARDS

Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog 12-17

Siemens / Speedfax Previous folio: 12-16

Multi-Metering Switchboards Type SMM GeneralComponents

� Order 100A and 200A tenant circuit breakers fromthe same option only. Do not mix breakers fromdifferent options.

� Meter socket with Test Block included. For socket only,without tenant disconnect, price from Table 7.4.6.28.

Table 7.4.6.25 — Tenant Circuit Breaker With Meter Socket�

240 Volt

No.Ampere Breaker of

Option� Rating Type Poles I.C.

100 BQ 2 110,0003 110,000

100 BQH 2 122,0003 122,000

100 HBQ 2 165,00001 3 165,000

200 QJ2 2 110,0003 110,000

200 QJH2 2 122,0003 122,000

200 QJ2-H 2 142,0003 142,000

100 ED4 2 165,0003 165,000

100 NGG 2 165,0003 165,000

100 HED4 2 100,000

023 100,000

100 HEG 2 100,0003 100,000

200 FD6 2 165,0003 165,000

200 HFD6 2 100,0003 100,000

480 Volt

100 ED4 2 118,0003 118,000

100 NGG 2 125,0003 125,000

100 HED4 2 142,0003 142,000

100 HHED6 2 165,00003 3 165,000

100 HEG 2 165,0003 165,000

200 FD6 2 135,0003 135,000

200 HFD6 2 165,0003 165,000

200 HFD6 2 165,0003 165,000

Sect_12_Speedfax2007 5/11/07 3:02 PM Page 12-17

Page 17: Front Connected Switchboards

12SW

ITCH

BOAR

DS

Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog12-18

Siemens / Speedfax Previous folio: 12-17

Super Blue Pennant SwitchboardsWarehouse Stock General

Ampere Ratings400–600–800 Ampere CircuitBreaker Main400–600 Ampere FusibleVacu-Break Main

Voltage Ratings120/240 Volts 1-Phase, 3-Wire240/120 Volts 3-Phase, 4-Wire Delta240 Volts 3-Phase, 3-Wire Delta208Y/120 Volts 3-Phase, 4-Wire480Y/277 Volts 3-Phase, 4-Wire480 Volts 3-Phase, 3-Wire Delta

I.C. RatingsThe short circuit current rating islimited to the lowest currentinterrupting rating, at the supplyvoltage, of any device installed. OnlySiemens breakers with short circuitinterrupting ratings equal to or greaterthan the marked short circuit currentrating shall be used for replacement or additions.

FeaturesThe Super Blue Pennant service entranceswitchboard is designed to meet theneeds of main over current protection with distribution devices for medium duty service applications. Main servicedisconnects can be either Siemens Vacu-Break fusible switch or Siemensmolded case circuit breakers. Either type of device provides dependableperformance with series ratedcombinations available. The switchboard islabeled as “suitable for use only as serviceequipment”. Super Blue Pennantswitchboards meet EUSERC utilityrequirements.

□A NEMA Type 1 indoor or Type 3Routdoor self-contained enclosures areconstructed of code gauge steel andpainted ANSI-61 light gray.

□B Rating label information is clearly visibleon the equipment front panel. Danger,short circuit rating labels and UL listinglabel present necessary information toconform with NEMA Standard PB-2.

□C Metering and test block provisionsmeet EUSERC utility specifications.

□D Incoming main lugs are mechanicalscrew-type mounted on studsaccepting a wide range of cable sizes.

□E Barriered hot sequence utility meteringand fully bussed power companycurrent transformer compartment meetEUSERC utility standards.

□F Service disconnect can be fusibleVacu-Break switch through 200,000 AICor circuit breaker with maximum ratingof 65,000 AIC at 240 volts and 50,000AIC at 480 volts.

□G Distribution panel kits are optional andfield addable with ratings of 400–800amperes. Up to 40 branch circuitprovisions available, 18 branch circuitminimum.

▪ High interrupting capacity subfeed kitswith molded case circuit breaker ratingsof 225 or 400 amperes.

▪ Series rated combinations are available.Consult sales office.

▪ Contact sales office for warehousestocking locations.

Sect_12_Speedfax2007 3/27/07 10:00 AM Page 12-18

Page 18: Front Connected Switchboards

12SW

ITCHBOARDS

Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog 12-19

Siemens / Speedfax Previous folio: 12-18

Super Blue Pennant SwitchboardsType 1 — Indoor, Type 3R — Outdoor Dimensions

2.875"

12.5"14.5" 14.5"8.75"

2.875"

2.875"

2.875"

26.25"

()

)(

Type 1 — Indoor

3.875" 5.875"

3.875"

15.625"

()

Type 3R — Outdoor Weatherproof

Dimensions (inches)Description A B C

Without Lug Landing 46 14 12

With Lug Landing 58 26 24

Dimensions (inches)Description A B C

Without Lug Landing 53 15 13

With Lug Landing 65 27 25

For inches / millimeters conversion, see conversion tablein Application Data section.

Sect_12_Speedfax2007 3/27/07 10:00 AM Page 12-19

Page 19: Front Connected Switchboards

12SW

ITCH

BOAR

DS

Discount Schedule SWBDSiemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog12-20

Siemens / Speedfax Previous folio: 12-19

Super Blue Pennant SwitchboardsMain Circuit Breaker SelectionMain Circuit Breaker

Main Device Meter Distribution Approximate

Ampere Service Catalog Number List Price $ �Socket Kits Weight (lbs.)

Rating Voltage Indoor Outdoor Indoor Outdoor Clips Available � Indoor Outdoor

120/240; 1-Phase, PQ26303-Wire PB224 WPB224 4005.00 7071.00 5�

PQ2612 320 1050

240/120; 3-Phase,4-Wire Delta240; 3-Phase, PQ46303-Wire

PB424 WPB424 5000.00 8008.00 15 PQ4612 335 1060

208Y/120; 3-Phase,4-Wire

480Y/277; 3-Phase,4-Wire PE4630480; 3-Phase, PB444 WPB444 6856.00 9889.00 15 PF4606 335 1060

3-Wire

120/240; 1-Phase, PQ26303-Wire PB226 WPB226 5125.00 8151.00 5

PQ2612 320 1050

240/120; 3-Phase,4-Wire Delta240; 3-Phase, PQ46303-Wire PB426 WPB426 6981.00 10015.00 15

PQ4612335 1060

208Y/120; 3-Phase,4-Wire

480Y/277; 3-Phase,4-Wire PE4630

480; 3-Phase,PB446 WPB446 10476.00 13542.00 15 PF4606 335 1060

3-Wire

120/240; 1-Phase, PQ28403-Wire PB228 WPB228 6612.00 9656.00 5

PQ2816 460 1090

240/120; 3-Phase,4-Wire Delta240; 3-Phase, PQ48403-Wire PB428 WPB428 9053.00 12104.00 15 PQ4818 475 1090208Y/120; 3-Phase,4-Wire

480Y/277; 3-Phase,4-Wire PE4840480; 3-Phase,

PB448 WPB448 13909.00 16930.00 15 PF4809 475 1090

3-Wire

400 AmpereLine Lugs (2)—3⁄0-500kcmil (Copperor Aluminum)Breaker Rated65,000A IRSymmetricalat 240 Volts35,000A IRSymmetricalat 480 Volts Type JD6

600 AmpereLine Lugs (2)—3⁄0-500kcmil (Copperor Aluminum)Breaker Rated65,000A IRSymmetricalat 240 Volts35,000A IRSymmetricalat 480 Volts Type LD6

800 AmpereLine Lugs (3)—3⁄0-500kcmil (Copperor Aluminum)Breaker Rated65,000A IRSymmetricalat 240 Volts50,000A IRSymmetricalat 480 Volts Type MD6

For inches / millimeters conversion, see conversion tablein Application Data section.

� Price does not include load side lugs, Distribution Panelor Subfeed Kits.

� For 6-jaw requirements, order 6th clip kitfrom accessories.

� Refer to Distribution Panel Kits for list prices.

= Warehouse Stock

Sect_12_Speedfax2007 3/27/07 10:01 AM Page 12-20

Page 20: Front Connected Switchboards

12SW

ITCHBOARDS

Discount Schedule SWBD Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog 12-21

Siemens / Speedfax Previous folio: 12-20

Super Blue Pennant SwitchboardsMain Fusible Switch SelectionMain Fusible Switch�

Main Device Meter Distribution Approximate

Ampere Service Catalog Number List Price $ �Socket Kits Weight (Lbs)

Rating Voltage Indoor Outdoor Indoor Outdoor Clips Available � Indoor Outdoor

120/240; 1-Phase, PQ26303-Wire

PF224 WPF224 4697.00 7549.00 5�

PQ2612 365 1094

240/120; 3-Phase,4-Wire Delta240; 3-Phase, PQ46303-Wire

PF424 WPF424 5726.00 8721.00 15 PQ4612 375 1110

208Y/120; 3-Phase,4-Wire

480Y/277; 3-Phase,4-Wire PE4630480; 3-Phase, PF444 WPF444 6714.00 9498.00 15 PF4606 375 1110

3-Wire

120/240; 1-Phase, PQ26303-Wire PF226 WPF226 5761.00 8927.00 5�

PQ2612 370 1100

240/120; 3-Phase,4-Wire Delta240; 3-Phase, PQ46303-Wire

PF426 WPF426 7942.00 10936.00 15 PQ4612 390 1110

208Y/120; 3-Phase,4-Wire

480Y/277; 3-Phase,4-Wire PE4630480; 3-Phase, PF446 WPF446 10225.00 13024.00 15 PF4606 390 1120

3-Wire

400 AmpereLine Lugs (2)—3⁄0-500kcmil (Copperor Aluminum)200,000 AICmaximum at600 Volts

600 AmpereLine Lugs (2)—3⁄0-500kcmil (Copperor Aluminum)200,000 AICmaximum at600 Volts

For inches / millimeters conversion, see conversion tablein Application Data section.

� Fuses not included.� Price does not include load side lugs, Distribution Panel

or Subfeed Kits.

� For 6-jaw requirements, order 6th clip kitfrom accessories.

� Refer to Distribution Panel Kits for list prices.

= Warehouse Stock

Sect_12_Speedfax2007 3/27/07 10:01 AM Page 12-21

Page 21: Front Connected Switchboards

12SW

ITCH

BOAR

DS

Discount Schedule SWBDSiemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog12-22

Siemens / Speedfax Previous folio: 12-21

Super Blue Pennant SwitchboardsComponents SelectionMain Device (Circuit Breaker or Fusible Switch)Load Side Lugs�— Discount Schedule SWBD

Ampere Rating Description Catalog Number Wire Range List Price $

400 For Fusible LKF4 (1)—3/0-750 kcmil (Cu or Al) 227.00600 Switch LKF6 (2)—3/0-500 kcmil (Cu or Al) 227.00

400 For Circuit LKB4 (1)—600-750 kcmil (Cu or Al) 227.00600 Breaker LKB6 (2)—3/0-350 kcmil (Cu or Al) 227.00800 LKB8 (2)—600-750 kcmil (Cu or Al) 451.00

Distribution Panel Kits — Discount Schedule SWBD

Ampere Number and Type of Breaker Poles CatalogRating Voltage QP or HQ � ED4 � QJ2 or QJH2 � FXD6 � � � Number List Price $ � Weight

120/240V; 1-Phase, 3-Wire30 — — — PQ2630

1105.00 3912 — 12 — PQ2612

400 240/120V; 3-Phase, 4-Wire Delta � �30 — — — PQ4630

and 240V; 3-Phase, 3-Wire � 1373.00 42600 208Y/120V; 3-Phase, 4-Wire 12 — 12 — PQ4612

480Y/277V; 3-Phase, 4-Wire — 30 — — PE4630 1163.00 42

480V; 3-Phase, 3-Wire — 12 — 6 PF4606 1163.00 65

120/240V; 1-Phase, 3-Wire40 — — — PQ2840

1806.00 6512 — 16 — PQ2816

240/120V; 3-Phase, 4-Wire Delta � �40 — — — PQ4840

800 240V; 3-Phase, 3-Wire 2283.00 70208Y/120V; 3-Phase, 4-Wire 12 — 18 — PQ4818

480V; 3-Phase, 3-Wire— 40 — — PE4840 1806.00 65

— 12 — 9 PF4809 2552.00 70

Circuit Breaker Subfeed Kits: (Breakers Not Included) — Discount Schedule SWBDDescription Catalog Number List Price $

For FXD6-225A 2 or 3-pole PSFFJ6 595.00

For JXD6, JD6, HJD6 400A 2 or 3-pole PSFJL6 913.00

For inches / millimeters conversion, see conversion tablein Application Data section.

� Price includes phase and neutral load lugs and neutrallink assembly.

� 2-pole FXD6 requires 3-pole space.

� Price includes branch neutral and disconnectlink assembly.� 1-pole breakers must not be connectedto “B” phase.

� 1-pole breakers must not be connectedto “B” phase.� 2-pole breakers must be rated 240V.� FXD6 circuit breakers are limited to 225A maximum.� Price from Molded Case Circuit Breaker section.

= Warehouse Stock

Sect_12_Speedfax2007 3/27/07 10:01 AM Page 12-22

Page 22: Front Connected Switchboards

12SW

ITCHBOARDS

Discount Schedule SWBD Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog 12-23

Siemens / Speedfax Previous folio: 12-22

Super Blue Pennant SwitchboardsAccessories Selection

For inches / millimeters conversion, see conversion tablein Application Data section.

� A PUG26 or WPUG26 Underground pull section isrequired when using these lug landing kits.

= Warehouse Stock

Description Catalog Number List Price $

14.5" Deep 90" High14" Wide (12" opening) — indoor PUG14 1597.0015" Wide (12" opening) — outdoor WPUG14 3370.00

26" Wide (24" opening) — indoor PUG26 1866.0027" Wide (24" opening) — outdoor WPUG26 3879.00

10" Wide (load wiring) PLW10 853.00

Underground Pull Section or Full Height Section For Load Wiring — Discount Schedule SWBD

400A 1-Phase, 3-Wire or 3-Phase, 4-Wire PLL44 � 814.00

600A 1-Phase, 3-Wire or 3-Phase, 4-Wire PLL46 � 1221.00

800A 1-Phase, 3-Wire or 3-Phase, 4-Wire PLL48 � 1435.00

Lug Landing Kits — Discount Schedule SWBD (Requires Catalog Number PUG26 or WPUG26)

400A 250/600V SSRK35 137.00

600A 250/600V SSRK36 137.00

“R” Fuse Clip Adapter Kit (Set of 3) — Discount Schedule VBSS

400A 250V W49814 330.00

400A 600V W49816 395.00

600A 240V W49813 459.00

600A 600V W49815 330.00

“J” Fuse Clip Adapter Kit (Set of 3) — Discount Schedule VBSS

400A 240V TFAK52 102.00

400A 600V TFAK55 151.00

600A 240V TFAK62 120.00

600A 600V TFAK65 174.00

“T” Fuse Clip Adapter Kit (One Pole Kit) — Discount Schedule VBSS

Blocking (QP-HQP 1, 2 and 3-pole) QL1 8.30

Blocking (QJ2, QJ2-H, QJH2) QJHS1 13.40

Blocking (ED2, ED4, ED6) E2HBL 16.00

Padlock (QP-HQP) QLD3 8.40

Padlock (QJ2, QJ2-H, QJH2) HL9419 15.10

Padlock (ED2, ED4, ED6) ED2HPL 16.00

Handle Blocking and Padlock Devices — Discount Schedule MCCB

QP-HQP-QJ2-QJ2H-QJH2 QF3 2.80

Filler Plates — Discount Schedule MCCB

Meter Compartment Door (32" Wide x 15" High for “S” base socket withtest block cutout (order necessary meter base from items below) PSP32 510.00

Meter Compartment Door (32" Wide x 30" High) for 2 “S” basemeters with mounting provisions for test block and printingdemand meter (order meter base from table below)Left Hand Hinge or Right Hand Hinge PSDP32 577.00

Blank Meter Compartment Door (32" Wide x 15" High) PBP32 243.00

5 Clip Meter Socket with ring PMS5 260.00

6 Clip Meter Socket with ring PMS6 294.00

8 Clip Meter Socket with ring PMS8 317.00

13 Clip Meter Socket with ring PMS13 577.00

15 Clip Meter Socket with ring PMS15 612.00

Optional Meter Sockets and Doors — Discount Schedule SWBD

PEGB42 101.00

Equipment Ground Bus –– Discount Schedule SWBD

Sect_12_Speedfax2007 3/27/07 10:01 AM Page 12-23

Page 23: Front Connected Switchboards

12SW

ITCH

BOAR

DS

Discount Schedule SWBDSiemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog12-24

Siemens / Speedfax Previous folio: 12-23

Circuit Breaker, Fusible Application SwitchboardsCircuit Breaker — BCT Service Cubicle SelectionService Entrance Equipment With Provisions For Metering Current TransformersService Entrance Circuit Breaker

COLD SEQUENCE METERING STANDARDFor Hot Sequence Metering Invert Unit and Breaker

BCT Switchboard

Connectors (Per phase and neutral)Ampere Connectors SuitableRating for Cu or Al

400A (1)–4/0–500 kcmil or(2)–250 kcmil

600A (2)–4/0–500 kcmil

800A (3)–250–500 kcmil

1000–1200A (4)–250–500 kcmil

Symmetrical Amps Dimensions Available Configurations

Catalog List Interrupting Capacity Ampere (inches) Top Feed Top Feed Bottom FeedNumber Price $ 240V 480V 600V Rating System Voltage Height Width Depth Cold Seq. Hot Seq. Cold / Hot Seq.

BCT436JXD6 6805.00 65,000 35,000 25,000400

120/240V 1-Phase, 3-Wire � � �

BCT436HJD6 10922.00 100,000 65,000 35,000 208Y/120V 3-Phase, 4-Wire � �

BCT636LXD6 9720.00 65,000 35,000 25,000600

240V 3-Phase, 3-Wire70 32 13.75

� � �

BCT636HLD6 12467.00 100,000 65,000 35,000 480Y/277V 3-Phase, 4-Wire � �

BCT836MXD6 12752.00 65,000 50,000 25,000800

480 or 600V 3-Phase, 3-Wire � � �

BCT836HMD6 17194.00 100,000 65,000 50,000 �

BCT1036NXD6 15220.00 65,000 — —1000

� � �

BCT1036HND6 20066.00 100,000 — — 208Y/120V 3-Phase, 4-Wire90 32 13.75

BCT1236NXD6 20135.00 65,000 — —1200

240V 3-Phase, 3-Wire � � �

BCT1236HND6 25777.00 100,000 — — �

PTE 1439.00 Potential Transformer Enclosure — — 20 20 10

For inches / millimeters conversion, see conversion tablein Application Data section.

= Warehouse Stock

▪ Available with current transformerprovisions on load side and can beinverted for current transformerprovision on line side.

▪ Tamperproof enclosure with hinged door over current transformercompartment with latch for utilitycompany sealing.

▪ Current transformer provisions areadjustable for use with 12" or 14.5"primary bar type current transformer.

▪ Indoor construction for floor mounting only.

▪ All units supplied as top feed coldmetering only. Units may be fieldmodified as shown in the AvailableConfigurations listed in the table below.

▪ Listed by Underwriters Laboratories’as suitable for use as serviceequipment only.

Sect_12_Speedfax2007 3/27/07 10:01 AM Page 12-24

Page 24: Front Connected Switchboards

12SW

ITCHBOARDS

Discount Schedule SWBD Siemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog 12-25

Siemens / Speedfax Previous folio: 12-24

Service Entrance SwitchboardsFusible Switch — SCT Service Cubicle SelectionService Entrance Fusible Switch

▪ Quick-Make — Quick-Break Fusible deadfront switch.

▪ Interlocked door over fuses withprovisions for padlocking switch.

▪ Door over current transformer sectionwith latch arrangement for utilitycompany seal.

▪ Current transformer provisions areadjustable for use with 12" or 14.5"primary bar type current transformer.

▪ Indoor construction for floor mounting only.

▪ Compact tamperproof enclosure withhinged door over current transformercompartment with latch for utilitycompany sealing.

▪ Listed by Underwriters Laboratories’as suitable for use as serviceequipment only.

SCT Switchboard

DimensionsCatalog Number List Ampere (inches)

Cold Sequence Hot Sequence Price $ Rating System Voltage Height Width Depth

SCT432 LSCT432 7314.00 400 120/240V 1-Phase, 3-Wire

SCT632 LSCT632 9161.00 600208Y/120V 3-Phase, 4-Wire240V 3-Phase, 3-Wire

SCT436 LSCT436 8516.00 400 480Y/277V 3-Phase, 4-Wire90 32 20

SCT636 LSCT636 9755.00 600 480 or 600V 3-Phase, 3-Wire

SCT836 LSCT836 14244.00 800 All —

SCT1236 LSCT1236 17695.00 1200208Y/120V 3-Phase, 4-Wire240V 3-Phase, 3-Wire

Ampere Symmetrical AmperesRating Fuse Clip Interrupting Capacity

400–600 R 200,000

800–1200 L 100,000

Connectors (Per phase and neutral)Ampere Connectors SuitableRating for Cu or Al

400A (1)–4/0–500 kcmil or(2)–250 kcmil

600A (2)–4/0–500 kcmil

800A (3)–250–500 kcmil

1000–1200A (4)–250–500 kcmil

For inches / millimeters conversion, see conversion tablein Application Data section.

= Warehouse Stock

Sect_12_Speedfax2007 3/27/07 10:01 AM Page 12-25

Page 25: Front Connected Switchboards

12SW

ITCH

BOAR

DS

Discount Schedule SWBDSiemens Power Distribution & Control, SPEEDFAX™ 2007-2008 Product Catalog12-26

Siemens / Speedfax Previous folio: 12-25

Switchboard Replacement and Modification KitsReplacement Data, Accessories, Modifications SelectionConnecting Strap Kits� — Circuit BreakerDiscount Schedule SWBDFor use with Series 5 or 6 CDP Circuit Breaker Panelboards orFC20, FCI, FCII, CDP-6, VB-6, SB1, SB2, and SB3 Switchboards —includes copper straps, cover plates and necessary hardware forswitchboards manufactured since 1974. Replacement strap kitsfor RCIII switchboards contact your local sales office.

Filler Plates — Discount Schedule SWBDFor use with Series 5 or 6 CDP Circuit Breaker Panelboards, FC-20, Class II, FCI, FCII, SB1, SB2, and SB3 Switchboards.

Strap KitCatalog � List Height

Breaker Type Number Price $ (inches) Mounting

BL, BLH, HBL, BQD SBLBD 902.00 3.75 D

NEB, HEB SEBD 902.00 3.75 D

NGB SNBD 902.00 3.75 D

ED2, ED4, ED6, HED4, 6E62 1074.00 3.75 DHED6, HHED6

CED6 6CLE2 1074.00 3.75 D

QJ2, QJH2, QH2-H 6QJ2 1942.00 5. D

FD6, FXD6, HFD6, HFXD6, 6F62 1942.00 5. DHHFD6, HHFXD6

CFD6 6CLF1 1973.00 5. S

JXD2, JD6, JXD6, HJD6,HJXD6, HHJD6, HHJXD6 6JJ61 2695.00 8.75 SSingle Branch

JXD2, JD6, JXD6, HJD6,HJXD6, HHJD6, HHJXD6 6JJ62 2983.00 8.75 DDouble Branch

CJD6 6CLJ1 2695.00 8.75 S

SJD6, SHJD6 6SJL1 2695.00 8.75 S

SCJD6 6SCJ1 2695.00 8.75 S

LD6, LXD6, HLD6, HLXD6 6LL61 3207.00 8.75 S

CLD6 6CLL1 3207.00 8.75 S

SLD6, SHLD6 6SLL1 3207.00 8.75 S

SCLD6 6SCL1 3207.00 8.75 S

LMD6, LMXD6, HLMD6, SLM1D 3240.00 8.75 SHLMXD6

MD6, MXD6, HMD6, SMND 3847.00 10. SHMXD6, CMD6

SMD6, SHMD6, SCMD6 SSMND 4097.00 10. S

NM, HM, LM, MG1D 3317.00 8.75 S(VL Breaker)

ND6, NXD6, HND6, SMND 3847.00 10. SHNXD6, CND6

SND6, SHND6, SCND6 SSMND 4097.00 10. S

NN, HN, LN, NG1D 3939.00 10 S(VL Breaker)

Connecting KitsFor use with SMM and SMD metering switchboards.� �

Disconnect Strap Kit ListDevice Catalog Number Price $

NGB SMMNGMK 135.00

HEG SMMHEMK 135.00

BQ, BQH, HBQ SMMBQMK 135.00

QJ2, QJH2, QJ2-H SMMQJMK 135.00

ED4, HED4 SMMEDMK 135.00

FD6, HFD6 SMMFDMK 135.00

CED6 SMMCEMK 135.00

T-Fuse Pullout SMMTFMK 135.00

Replacement Meter Socket Kits� �

For use with SMM and SMD metering switchboards.

Strap Kit ListType Catalog Number Price $

1-Phase MSK2001 281.00

3-Phase MSK2003 385.00

Filler PlateCatalog

Breaker Frame Number List Price $ Notes

BQ, BQH, HBQ, E2,E4, E6, HE4, HE6,E2-A, E4-A, E6-A, QF3 2.80 Per PoleHE4-A or HE6-A andED2, ED4, ED6,HED4, HED6

Connecting Strap Kits Vacu-Break� and HCPDiscount Schedule SWBDFor use with VB-5, VB-6, FC-20, FC-I, FC-II, SB1, SB2 and SB3Switchboards. Includes copper straps and necessary hardware forSwitchboards manufactured since 1974.

Blank Plates — Circuit Breaker and Vacu-Break�

Discount Schedule SWBDFor use with Series 5 or 6 VB and CDP Panelboards, FC20, Class II,FCI, FCII, SB1, SB2, and SB3 Switchboards.

Note: When a front filler plate is not completely filled withbreakers, the openings in the unused space must beclosed with 1-pole filler plates from table.

Note: Price breakers from circuit breaker section of this catalog.

Ampere Unit Height Catalog ListRating (inches) Number Price $

30-30 5, 71⁄230-60 5, 71⁄260-60 5, 71⁄2 VB657 302.0060-100 71⁄2100-100 71⁄2

100 71⁄2

200 71⁄2, 10 VB671 471.00

200-200 10 VB610 511.00

400-600 15 VB6150 211.00

800-1200 � 161⁄4 F6162D 1366.00

Height Catalog Number

(inches) Series 6 List Price $

11⁄4 6FPB01 196.00

21⁄2 6FPB02 224.00

33⁄4 6FPB03 224.00

5 6FPB05 224.00

10 6FPB10 302.00

For inches / millimeters conversion, see conversion tablein Application Data section.

� Consult sales office for availability.� Connecting strap kit includes front filler plate.

� 10" plate accommodates 18 BQ or HBQ 1-pole breakers. Kits consist of all necessary mounting hardware, less

disconnect device and cable.� Siemens meter sockets used in SMM switchboards built

after 1/91.

�Siemens Type WMS263 Meter Sockets are rated 200AContinuous Duty.

� Type HCP.� Special order component supplied by apparatus factory.

Contact Sales for availability.

Note: D = Denotes double branch or twin mountingS = Denotes single mount

Sect_12_Speedfax2007 3/27/07 10:01 AM Page 12-26