From the Desk of Managing Director Inside
-
Upload
nguyentuyen -
Category
Documents
-
view
225 -
download
5
Transcript of From the Desk of Managing Director Inside
From the Desk of Managing Director
FOR PRIVATE CIRCULATION ONLY SEPTEMBER 2016
Official News Letter of Amtech Electronics (India) Ltd., Gandhinagar, Gujarat (India)
AN ISO 9001 : 2008 COMPANYQM 003
Inside
Piyush Patel
IndustrialElectronics
Design & Developmentfor Customers in
Power Electronics
Power QualityActive Harmonic Filter,
Active Front End Converter
IndustrialAutomation
Controlling
Operating
Driving
Networking
Motion ControlAC Drive, MVD & Soft Starter
ACTIVE FRONT END CONVERTER
AXPERT-HIVERT MVD
TRACTION DRIVE WIND POWER CONVERTER SOLAR INVERTER HIGH VOLTAGE POWER SUPPLY
ACTIVE HARMONIC FILTER
PLC SCADA, HMI
AXPERT-EAZY AXPERT-VT 240S AXPERT-OPTI TORQUE
AN ISO 9001 : 2008 COMPANYQM 003
Page 4
Page 5
Page 8
Page 7
Appl. Case Study
Gandhinagar
Ahmedabad
Mumbai
Surat
Bangalore
Chennai
Bhilwara
Chandigarh
Delhi
VadodaraIndore
Jamnagar
Saurashtra
Udaipur
Kolkata
Nagpur
AurangabadPune
Hyderabad
Nasik
Vapi
Bhilai
Bhopal
Jamshedpur
Kota
Goa
Jaipur
Kanpur
Vizag
Page 3
PresenceAcross the Nation
Product Overview
AMTECH POWER
Techno-Talk
Techno-Talk
Customer’s Voice
Page 6
Page 2
“You question, we answer”
Editor : Atul Suthar
STATCON: MULTI-FUNCTIONAL ACTIVESTATIC VAR COMPENSATOR
AMTECH
Success dependsmore on
common sensethan on genius
How to ?DELEGATE
Define the task to be delegated
Empower the subordinate to execute the task
Level off subordinate’s weaknesses with your strengths
Enable timely interaction
Guide whenever and wherever required.
Avoid spoon-feeding
Take the responsibility of; and not the credit for, the results
Encourage the efforts taken
K-factor and itssignificance
-Amtech Family
touching lives... Aromatic Division
Energy Saving in Pump
CondenserAutomation System
Amtech Grid PowerFactor Controller
TECHNO-TALK
3
TITLE: K-FACTOR AND ITS SIGNIFICANCE
K-factor is one mathematical attribute of a distorted current, having harmonic distortion.
It is given as:
h = n
h (I /I )�2 2 2
h 1
h = 1
K =
h = n
(I /I )� h 1
2 2
h = 1
Where h is order of harmonic,I is the current of h harmonic and K is the K-factor.th
h
The eddy current losses in the transformer are proportional to the K-factor. Hence if thecurrent in the transformer is distorted the transformer design should be as per K-factordesign methodology.
For a pure sine-wave current with no harmonic distortion, the K-factor is 1.
If the current harmonic spectrum is as given in the below, the K-factor can betable-1calculated as per the above formula as 7.143
Harmonic spectrum of current
Order of Harmonic 1 3 5 7
Current in Amperes 100 5 50 20
Table-1
TECHNO-TALK
4
“You question, we answer”
Question:What are zero-phase sequence currents? How are they generated? What is theirimpact?
AnswerZero phase sequence currents are currents generated in three phases R, Y and B buthaving zero phase difference between them. Due to zero phase difference betweenthem, they get added in neutral unlike positive or negative phase sequence currentshaving 120 deg. phase shift between them, which makes the vector sum of thesecurrents equal to zero in neutral.
Zero phase sequence currents are generated by harmonics having frequencies whichare multiples of 3, i.e. 3 , 6 , 9 , 12 etc.
rd th th th
Zero phase sequence currents have changed the wiring philosophy from 3 and ½ corewiring for R-Y-B-N to 3 + 1 core wiring, as current in neutral can be as high as current in R-Y-B phases in presence of triplen harmonics of current.
To filter these currents 3-phase 4-wireActive Harmonic Filter is required.
Energy Conservation :Energy Conservation is the need of the day and today the rising energy consumption is ofgrowing concern due to adverse effect like climate change and global warming. A balancehas to be maintained between the worlds energy needs and the environment. Amtech helpsindustries in their efforts to reduce consumption without affecting productions through widerange of product and service.
WhyAmtech For Energy Conservation :1. In depth of knowledge of Industrial Systems.2. Wide Range of products.3. Accreditations from GEDA, Dy.CEI, MEDA, BEE, PCRA, MPUVNL, KES, CPRI,
CLL, NPC....4. Global Presence and wide installed based created through delivering trusted product an
solutions.
Amtech Offers :1. Complete EnergyAudit and Power QualityAudit.2. System Design, Optimization and Pay-back analysis.3. Demand side Management (DSM)4. Design, Supply, Installation and Commissioning of Harmonic Filters, VFD, MVD,
Automation System, Soft-Starters etc....5. Continuous post audit support for implementation.6. Training and Seminars on Power Quality and Energy Conservation.7. Guidance for financing of Energy Conservation Projects.
Total Solution for Power Quality Through Range of Products
AHF : Active Harmonic FilterAFC : Active Front End ConverterSHC : Static Harmonic ConverterSTATCON : Multi-Functional Active Static VAR Compensator
POWER QUALITY & ENERGY CONSERVATION
AMTECH: YOUR TRUE PARTNER FOR ENERGY CONSERVATION
APPLICATION CASE STUDY
5
TITLE : ENERGY SAVING IN PUMP
DOC.NO. : AMTCS-233
Industry : Steel
Application : Pump
Motor rating : AC Induction Motor, 3-phase
110kW :
415VOLT :
1482RPM :
50Hz :
186AMP :
Previous system : Motor was running on Star Delta starter.
Problem observed : 1) High maintenance cost.
2) Energy losses due to flow control by Valve.
Present system : AMTECH 110 kWAxpert-Eazy VFD used in place of
Star Delta starter.
kW (Consumption) Valve Position
Previous system (Without drive): 98.9 kW 90% Open
Present system (With drive ) : 83.9 kW 100% Open
System block diagram :
Merits of new system : 1. Easy & smooth operation.
2. Energy saving due to flow control by VFD.
Economical analysis :
� Energy consumption without VFD - P1 = 98.9 kW� Energy consumption with VFD - P2 = 83.9 kW� Energy Saving Per Day ((P1-P2)*24) = 360 Units.� Saving Per Day @ Rs.5/-Unit = Rs.1800/-� Saving Per Year (Approx. 300 Days) = Rs.5,40,000/-� Payback periodApproximately = 6-8 Months.
110 kW, 3-PHASEINDUCTION MOTOR
AXPERT-EAZY
3-PHASE,
415 V,
AC SUPPLY
110 kW
PUMP
6
AMTECHPOWER LIMITED
B-9, GIDC Electronics Zone, Gandhinagar-382028, Gujarat, IndiaTel : 079 23289116 / 117, Fax: 079 23289110 / 111Email : [email protected] Visit : www.amtechpower.in
AMTECH GRID POWER FACTOR CONTROLLER
GEN
FIELD
AMTECHAVR
AMTECHVar / PF
CONTROLLER
AMTECHHMI
AMTECHVar / PF
SENSINGMODULE
PT
CT
GRIDBREAKER
PLANT LOAD
GRID
Advantages ofAmtech Grid Power factor controlling system
� Maintain PF during Power export to or Import from grid.
� Generate monthly reports through which we can analiseActive Power, Reactive Power and PF.
� There are two modes of operation: PF Mode or VAR Mode through which we can regulate gridPF.
� With installation of Grid Power control system customer has reduced PF penalty from electricityboard to almost zero.
The system is working satisfactorily till date and customer is delighted with it.
Functional Block Diagram of Grid Power Factor Control System
7
CONDENSER AUTOMATION SYSTEM
Bene�ts
� Energy consumption reduced by 20~25%
� Constant pressure control gives smooth operation ofplant processes.
� No manpower required as system start/stop pumps
� and fans as per pressure requirement automatically.
� Eliminates inrush currents.
� Smooth acceleration and deceleration by VFDreduces mechanical stress on machine, whichincreases life of mechanical parts compared to DOLor star/delta starter.
� Better reliability, more uptime.
� Refrigeration mimic in SCADAgives better monitoringof plant.
� Trend and Alarm gives historical analysis for plantperformance.
� Easy monitoring and controlling of delivery linepressure, make-up water tank level control, varioustemperature monitoring.
� Data logging and Report generation providesflexibility to evaluate performance.
� Appropriate displays are provided on the HMI unit toassist with pinpointing any faults.
� Short payback period with better productivity,reduced energy consumption.
� Improved process flow and excellent value for money.
� Quick and safe commissioning.
� Minimized maintenance costs.
� Qualified after-sales service byAmtech.
Features
� Accurate delivery line pressure control
� Auto control of multiple condensers as perrequirement of pressure
� Synchronized with compressor operation
� Flow control option for various distribution sections
� Factory-tested integration
� Simplified setup with standard solution based panel
� Smooth starting and operation of system
� User-friendly SCADA and HMI
� Full motor protection
� Efficient VFD
� SCADA and Intelligent Process Controller
The new generation of control system, developed by , integrates the operation ofAmtech Electronics (India) Ltd.Evaporative Condenser with respect to Refrigeration requirements.
Amtech offers an innovative & smart solution of Condenser control with Automation Package, based on itsvariable frequency drive, SCADA and intelligent process controller. This combination controls the multiplequantities of condensers along with compressor in Refrigeration section of Utility area.
This system provides total control of Refrigeration system in Utility area of Dairy plants or any other industries whereRefrigeration is required.
PRESENCE ACROSS THE GLOBE
Book - PostTo
Atlanta
8
Gandhinagar
Ahmedabad
Mumbai
Surat
Bangalore
Chennai
Bhilwara
Chandigarh
Delhi
VadodaraIndore
Jamnagar
Udaipur
Kolkata
Nagpur
AurangabadPune
Hyderabad
Nasik
Vapi
Bhilai
Bhopal
Jamshedpur
Kota
Goa
Jaipur
Lacknow
Vizag
Head Office
Branch Office
Dealer
System Integrater
Resident Engineer
Global Distribution
CoimbatorePondicherry
Raipur
Belgaum
From
Works & Regd. Office :
Amtech Electronics (India) Ltd.E-6, GIDC Electronics Zone,
+91 79 23289101, 23289102, 23289103+91 79 [email protected]
PhoneFaxE-MailWeb
::::
Gandhinagar-382 028, Gujarat (India)
M.D. Kamath
-
Regional Offices
Contact Person Phone No. (O) Mobile No. E-mail
022-28851603/28846083Vrajesh Yadav 09819900501
09449010977
09582888030
Mumbai
Bangalore
Chennai
Delhi
09449010977
011-25610211
T.S. Sridhar 044-26358919 09840618533.
Umesh Bhatia 09589344318Indore [email protected]
S. Senthil Kumar 044-26358919 09940229955 [email protected]