Fly_p20

104
User's Guide FLYPS 2.1 - English (FUS) P1 Copyright ã 1999 ITT Flygt AB All Rights Reserved ITT FLYGT AB MAKES NO WARRANTY, EITHER EXPRESSED OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE REGARDING THESE MATERIALS, AND MAKES SUCH MATERIALS AVAILABLE SOLELY ON AN “AS-IS” BASIS. IN NO EVENT SHALL ITT FLYGT AB BE LIABLE TO ANYONE FOR SPECIAL, COLLATERAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES IN CONNECTION WITH OR ARISING OUT OF PURCHASE OR USE OF THESE MATERIALS. THE SOLE AND EXCLUSIVE LIABILITY TO ITT FLYGT AB, REGARDLESS OF THE FORM OF ACTION, SHALL NOT EXCEED THE PURCHASE PRICE OF THE MATERIALS DESCRIBED HEREIN. ITT Flygt AB reserves the right to revise and improve its products as it sees fit. This publication describes the state of this product at the time of its publication, and may not reflect the product at all times in the future. Limitations of Remedies REGARDLESS OF WHETHER ANY REMEDY SET FORTH HEREIN FAILS IN ITS ESSENTIAL PURPOSE, IN NO EVENT WILL FLYGT BE LIABLE TO YOU FOR ANY SPECIAL, CONSEQUENTIAL, INDIRECT OR SIMILAR DAMAGES, INCLUDING ANY LOST PROFITS OR LOST DATA ARISING OUT OF THE USE OF INABILITY TO USE THE SOFTWARE OR ANY DATA SUPPLIED THEREWITH, EVEN IF FLYGT OR ANYONE ELSE HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES, OR FOR ANY CLAIM BY ANY OTHER PARTY. SOME STATES DO NOT ALLOW THE LIMITATION OF EXCLUSION OF LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TO YOU. IN NO CASE SHALL FLYGT'S LIABILITY EXCEED THE PURCHASE PRICE FOR THE SOFTWARE. Adobe Trademarks Adobe , the Adobe logo, Acrobat, the Acrobat logo, Distiller, Exchange, and Postscript are trademarks of Adobe Systems Incorporated. Microsoft Trademarks Windows, Windows NT, Windows 95, Windows 98, Windows2000, DOS is trademarks of Microsoft Corporation. Other product names mentioned in this manual may be trademarks or registered trademarks of their respective companies and are hereby acknowledged."

Transcript of Fly_p20

Page 1: Fly_p20

User's Guide FLYPS 2.1 - English (FUS) P1

Copyright ���� 1999 ITT Flygt AB

All Rights Reserved

ITT FLYGT AB MAKES NO WARRANTY, EITHER EXPRESSED OR IMPLIED, INCLUDING BUTNOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR APARTICULAR PURPOSE REGARDING THESE MATERIALS, AND MAKES SUCH MATERIALSAVAILABLE SOLELY ON AN “AS-IS” BASIS.

IN NO EVENT SHALL ITT FLYGT AB BE LIABLE TO ANYONE FOR SPECIAL, COLLATERAL,INCIDENTAL, OR CONSEQUENTIAL DAMAGES IN CONNECTION WITH OR ARISING OUT OFPURCHASE OR USE OF THESE MATERIALS. THE SOLE AND EXCLUSIVE LIABILITY TO ITTFLYGT AB, REGARDLESS OF THE FORM OF ACTION, SHALL NOT EXCEED THE PURCHASEPRICE OF THE MATERIALS DESCRIBED HEREIN.

ITT Flygt AB reserves the right to revise and improve its products as it sees fit. This publication describes the stateof this product at the time of its publication, and may not reflect the product at all times in the future.

Limitations of Remedies

REGARDLESS OF WHETHER ANY REMEDY SET FORTH HEREIN FAILS IN ITS ESSENTIAL PURPOSE,IN NO EVENT WILL FLYGT BE LIABLE TO YOU FOR ANY SPECIAL, CONSEQUENTIAL, INDIRECT ORSIMILAR DAMAGES, INCLUDING ANY LOST PROFITS OR LOST DATA ARISING OUT OF THE USE OFINABILITY TO USE THE SOFTWARE OR ANY DATA SUPPLIED THEREWITH, EVEN IF FLYGT ORANYONE ELSE HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES, OR FOR ANY CLAIMBY ANY OTHER PARTY.

SOME STATES DO NOT ALLOW THE LIMITATION OF EXCLUSION OF LIABILITY FOR INCIDENTALOR CONSEQUENTIAL DAMAGES SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TOYOU.

IN NO CASE SHALL FLYGT'S LIABILITY EXCEED THE PURCHASE PRICE FOR THE SOFTWARE.

Adobe Trademarks

Adobe , the Adobe logo, Acrobat, the Acrobat logo, Distiller, Exchange, and Postscript are trademarks of AdobeSystems Incorporated.

Microsoft Trademarks

Windows, Windows NT, Windows 95, Windows 98, Windows2000, DOS is trademarks of Microsoft Corporation.Other product names mentioned in this manual may be trademarks or registered trademarks of their respectivecompanies and are hereby acknowledged."

Page 2: Fly_p20

ii •••• Contents User's Guide FLYPS 2.1

Contents

FLYPS 2.1 - Introduction 1FLYPS 2.1 - A Pump System Design Tool................................1New features in Version 2.1 .......................................................2

Getting Started 3System Requirements .................................................................3Contents ......................................................................................3Installation ..................................................................................4

Standard Installation ........................................................4Minimum Installation (Client) .........................................4Customized Installation ...................................................5Installing FLYPS 2.1........................................................6Installing Acrobat Reader ................................................6Network usage..................................................................7

General Instructions 8Start FLYPS 2.1..........................................................................8Component Description..............................................................9

Main window....................................................................9Menu...............................................................................10Toolbar ...........................................................................10Case-Manager Toolbar...................................................10

Workflow..................................................................................11Help...........................................................................................12Tips & Explanations.................................................................12Internet shortcuts ......................................................................13

Product Selection 14Overview...................................................................................14Browse ......................................................................................15Search .......................................................................................16

Set Search Criteria..........................................................17Search based on required flow and head .......................18Search based on required flow and a specified pipesystem.............................................................................18Search based on alternative pipe systems......................19

Page 3: Fly_p20

User's Guide FLYPS 2.1 Contents •••• iii

Search based on slurry calculation ................................20Search based on energy consumption............................24Pump list - description ...................................................25

Product Data Presentation 27Display Product data ................................................................27

Display pump curve and duty points .............................29View Dimensional Drawings ...................................................30

Pump System Analysis 32Overview ..................................................................................32Pipe system design ...................................................................32Head loss calculations..............................................................33Duty Analysis ...........................................................................35

Performance curves........................................................36Duty conditions..............................................................37

Life cycle cost analysis ............................................................38VFD - Analysis.........................................................................43

Pump Performance.........................................................44Pump Perf. vs. Freq. (Performance versus Frequency) 46Power vs. Freq. (Power versus Frequency) ..................47Power vs. Flow (Power versus Flow)............................48Specific Energy..............................................................49

Pump Station Design 50Sump Volume Calculation .......................................................50

Printouts 52Print Pump Performance Curve ...............................................52Print Outline Dimensional Drawings.......................................54Print Rating data.......................................................................56Print System Analysis Reports.................................................56Export graphs to Windows Meta File ......................................56Create Project Report ...............................................................57

Project Management 59Overview ..................................................................................59Project Management.................................................................59

Create a new Project ......................................................59Open a Project................................................................60

Page 4: Fly_p20

iv •••• Contents User's Guide FLYPS 2.1

Delete a project...............................................................61

Settings 62Overview...................................................................................62Set default values......................................................................63

Set Dialog language .......................................................63Set Frequency.................................................................63Set Voltage .....................................................................63Set Units .........................................................................64Set Head loss calculation method and constants ...........64Set Life cycle cost calculation default values................64Set VFD type ..................................................................65Set program and library paths ........................................65

Create a User Profile ................................................................66

Tutorial 67Overview...................................................................................67Basic pump search ....................................................................67

Task description .............................................................67Solution ..........................................................................68

Pump search based on a pumping system ................................79Task description .............................................................79Solution ..........................................................................81

Appendix 88Description of Flygt pump types ..............................................88Description of Pump Installation types ....................................90Description of Toolbar icons....................................................91Head loss calculation methods .................................................92Pump search methodology .......................................................94

Glossary 95

Page 5: Fly_p20

User's Guide FLYPS 2.1 FLYPS 2.1 - Introduction •••• 1

FLYPS 2.1 - Introduction

FLYPS 2.1 - A Pump System Design ToolFLYPS 2.1 is a pump system design tool intended for allprofessionals in the pump system design and pump applicationfield.

The program features pump selection modules and a numberof pump system tools such as pipe system design, variablespeed analysis, pump performance analysis, flow durationprofile and life cycle cost analysis. Outline dimensionaldrawings and product data sheets can be viewed and printed.

The program can be described as a PC-based product catalogdesigned to support product selection.

FLYPS 2.1 is developed by ITT Flygt AB, Market and Salessystems.

Design: Magnus Ståhl

Flygt US - Manual 2.1, Trumbull, CT 10/1/98

Page 6: Fly_p20

2 •••• FLYPS 2.1 - Introduction User's Guide FLYPS 2.1

New features in Version 2.1The following new features have been added, as compared tothe previous 1.2 DOS version:

• Multiple pump search. The pump search can beperformed to find solutions with several identicalpumps connected in parallel or in series (see"Search" on page 16).

• Total energy usage. Calculation of total energyusage based on flow duration profile (see “Searchbased on energy consumption” on page 24).

• Life cycle cost (LCC) analysis. Life cycle costsbased on equipment cost, energy cost, operatingtime and interest rate can be calculated (see “Lifecycle cost analysis” on page 38).

• Performance analysis. Individual and combinedpump duty points in multiple pump systems can becalculated (see “Duty Analysis” on page 35).

• Pump station design. Support sump dimension-,sump volume- and stop level calculations (see“Sump Volume Calculation” on page 50).

• Project manager. Project work can be stored in adatabase (see “Project Management” on page 59).

• Dimensional drawings. Link to Acrobat Reader forviewing and printing dimensional drawings in PDF-format (see “View Dimensional Drawings” on page30 and “Print Outline Dimensional Drawings” onpage 54)

• VFD analysis. Analyze one or all pumps whenoperated as variable speed pumps in pump systemswith parallel as well as series pump connection (see“VFD - Analysis” on page 43.

Page 7: Fly_p20

User's Guide FLYPS 2.1 Getting Started •••• 3

Getting Started

System RequirementsThe minimum software and hardware requirements are:

• Windows 95, Windows NT, Windows 98,Windows2000

• CD-ROM drive, 2x speed

• Pentium 120 MHz

• 32 MB RAM

• 30 MB free disk space for a Client installation, or 30MB-150 MB for a Laptop installation without CD-ROM depending on the database contents.

ContentsThe CD contains:

• SETUP.EXE, FLYPS 2.1 installation program

• FLYPS 2.1, Executable program

• FLYPS 2.1 Help, Windows help files forWindows95.

• FLYPS 2.1 Manual, The manual in PDF format

• Dimensional drawings, All dimensional drawingsand the drawing list in a PDF format.

• ACROBAT, Acrobat Reader from Adobe in severallanguages.

Page 8: Fly_p20

4 •••• Getting Started User's Guide FLYPS 2.1

InstallationFLYPS 2.1 must be installed using the installation programSETUP.EXE

The program can be installed in three ways. Choose the bestsuited depending on the environment that the program isintended to be used in.

Standard InstallationRecommended for most computers with a CD-ROM. Allprogram components excluding the dimensional drawings willbe installed to the target PC.

Note: This installation requires that the CD isinserted in the CD-ROM drive when viewing orprinting dimensional drawings.

Minimum Installation (Client)Recommended for most computers with limited available diskspace and working in a network or with a CD-ROM. Thisinstallation type will require 16MB of disk space on the targetPC and leave the main program product database and thedrawing libraries accessible on the CD-ROM.

Note: This installation requires that the CD isinserted in the CD-ROM drive during every FLYPS 2.1session.

Page 9: Fly_p20

User's Guide FLYPS 2.1 Getting Started •••• 5

Customized InstallationRecommended for portable or standalone PC. The requiredprogram files and drawing libraries can be installed on thetarget PC.

The installation can be customised by selecting whichcomponents you want to install. The components are markedby clicking the check boxes. Unselected components will beleft on the CD-ROM and the program will try to find themthere.

• FLYPS Application (the program).

• FLYPS Product Database, Product databasesthat the program uses Read-Only.

• Dimensional drawings, Dimensional drawings inAcrobat PDF format.

The installation requires 16-100 MB of free disk space.

Page 10: Fly_p20

6 •••• Getting Started User's Guide FLYPS 2.1

Installing FLYPS 2.11. Start Windows.

2. Insert the FLYPS 2.1 CD in the CD-ROM drive.

3. In the Start menu choose Run.

4. Type D:\Setup and click OK (this exampleassumes that the CD-ROM drive is named D:).

5. Follow the instructions in the program.

Installation

A Program Group and a number of Program Icons are createdduring installation:

• FLYPS 2.1. Main program, starts FLYPS 2.1

• Help FLYPS 2.1. Starts Windows Help and opensFLYPS 2.1 Help file

• UnInstall FLYPS 2.1. FLYPS 2.1 can beuninstalled under the “Add/Remove Programs” inthe Control Panel.

Installing Acrobat ReaderA freeware PDF-file viewer, Acrobat Reader from Adobe, isincluded on the CD and can be installed together withFLYPS 2.1. Acrobat Reader is used to view and print productdimensional drawings.

Page 11: Fly_p20

User's Guide FLYPS 2.1 Getting Started •••• 7

During installation, the set-up program searches for AcrobatReader. If the set-up program can’t find it or if it is incorrectlyinstalled, you will be asked if you want to install it now.

Acrobat Reader is required to utilize all functionalityin FLYPS 2.1.

Acrobat Reader is available in many languages. If you want toinstall Acrobat Reader in another language, the installationprogram is located on the FLYPS 2.1 CD-ROM:

If you install a new language to a new location on the disk,you will have to change the command line for Acrobat Readerin the FLYPS Setup.

Network usageFLYPS 2.1 can run as a multi-user application with a commonproduct database on a network . However, each user needs tomake some preparations.

1. Network operator: Copy the contents of the CD to asuitable location on the network server.

2. Each user: Start the Set-up program on the serverand choose Client Installation. A limited selection offiles is copied to the local PC. Paths and workingdirectory are set to the network server.

Page 12: Fly_p20

8 •••• General Instructions User's Guide FLYPS 2.1

General Instructions

Start FLYPS 2.1FLYPS 2.1 is started by clicking the icon created at theinstallation.

Note! FLYPS 2.1 should be started by clicking theicon.

Page 13: Fly_p20

User's Guide FLYPS 2.1 General Instructions •••• 9

Component DescriptionFLYPS 2.1 is a Windows application consisting of a number ofwindows, a menu and a toolbar. FLYPS 2.1 has a MultipleDocument Interface(MDI) which implies that several windowscan be open in one frame. This enables the user tosimultaneously work with several tasks or cases in differentwindows.

Main window

Main window

The user can search or browse products in the Main window.The user can simultaneously work with several tasks oralternative solutions to one task (Cases).

The open windows are managed (arranged, minimized etc.) ina standardized way under the Windows item in the menu.The windows can be arranged as Layered, Cascaded or Tiled.

Menu Toolbar

Main window

Case-Managertoolbar

Page 14: Fly_p20

10 •••• General Instructions User's Guide FLYPS 2.1

MenuAll pump system tools and printouts can be accessed from theMenu. The menu is activated by clicking on it or by pressingALT + the underlined letter in the menu item name.

ToolbarFrequently used menu items are also accessible in the Toolbar.The toolbar location and layout is flexible and can becustomized by pointing at the toolbar and clicking the rightmouse button. The toolbar can be located at the top, left, right,bottom or as a floating window. (See also “Description ofToolbar icons” on page 91 )

Case-Manager ToolbarA new Case can be opened and already opened cases can beaccessed by using the Case Manager Toolbar. Up to 15different cases can be open at the same time.

Create new project

Open existing project

Save

Create report

Setup

Project Information

Design Pipe system

Flow duration

Performance analysis

LCC- analysis

Product data

DimensionaldrawingsPump stationdesign

VFD analysis

Page 15: Fly_p20

User's Guide FLYPS 2.1 General Instructions •••• 11

WorkflowAll pump system engineering tools in FLYPS 2.1, includingproduct data presentation, system analysis and data printoutsbecome activated when a product is selected.

There are two alternative methods to select products InFLYPS 2.1:

• Browse. The user selects a product in the databaseby successive choices (see “Browse” on page 15).

• Search. The program assembles a collection ofpumps that best fulfills the specified requirement(see "Search" on page 16).

When a product is selected (highlighted), product data such asPerformance curves and Dimensional drawings can be viewedand printed.

System analysis such as Performance analysis and Economyanalysis are also based on a selected pump, and user input suchas pipe system characteristics is required. Systemcharacteristics can be defined by a system curve (two points)or by specifying a pipe system.

All work corresponding to a project, such as specified pipesystems, flow duration and pump stations can be stored as aproject in a project database (see “Project Management” onpage 59).

Page 16: Fly_p20

12 •••• General Instructions User's Guide FLYPS 2.1

HelpTo help the user fully understand and utilize all features in theprogram, and guide the user through the workflow, FLYPS 2.1provides an extensive help facility.

FLYPS Help uses Windows95-Help and includes descriptionsof how to proceed using the program features together with aTutorial and a Glossary list.

Help is accessed in all dialog windows by clicking the Helpbutton. Information about the topic and how to proceed ispresented. Links to other related topics are displayed in greentext and are accessible by a mouse click.

Help is accessible from the Help menu on the Main screen.The help contents with links to all topics are presented.

FLYPS 2.1 Help contents

Tips & ExplanationsFLYPS 2.1 provides a facility to display Tips.

1. Point at the desired object with the mouse cursorand click the right mouse button. A Windows-Helpwindow with information related to the desiredobject appears.

Page 17: Fly_p20

User's Guide FLYPS 2.1 General Instructions •••• 13

Internet shortcutsFLYPS 2.1 has built-in shortcuts to Flygt's Internet sites. Youcan easily get the latest news about the program, ask questionsat the forum or register as user by using these shortcuts.

The FLYPS 2.1 Site contains:

• News. A home page with latest news aboutFLYPS 2.1 including patches for updates, etc.

• Forum. A home page with the possibility of askingquestions and exchanging experience aboutFLYPS 2.1. The questions can be answered by anyother FLYPS user or by Flygt’s local FLYPScoordinator.

• Registration. A home page to register as a FLYPSuser. As a registered user, you will automatically getuseful information regarding new program versionsand updates.

1. Make sure that a proper command line is set to yourWeb Browser (See “Set program and library paths”on page 65).

2. Choose Internet on the Help menu. A drop-downmenu appears.

3. Choose the home page that you want to visit.

Page 18: Fly_p20

14 •••• Product Selection User's Guide FLYPS 2.1

Product Selection

OverviewAll pump system engineering tools in FLYPS 2.1, includingproduct data presentation, system analysis and data printoutsbecome activated when a product has been selected.

There are two alternative methods to select pumps inFLYPS 2.1:

• Browse. The user selects a product in the databaseby successive choices.

• Search. The program assembles a collection ofpumps that best fulfills the specified requirement.

See "Workflow" on page 11 for further information.

Page 19: Fly_p20

User's Guide FLYPS 2.1 Product Selection •••• 15

BrowseBrowse allows the user to select a product in the database bysuccessive choices based on the product and its configuration.

1. In the Main window, select the Browse Tab.

2. Select in order; Pump type, installation type andproduct model. A list of all available impellers isdisplayed. The list can be limited by selectingparticular options.

3. Select the preferred impeller(s) by clicking in thepump/impeller list.

Main screen - Browse

Page 20: Fly_p20

16 •••• Product Selection User's Guide FLYPS 2.1

SearchThe program searches for pumps that can meet a specifiedduty point within a specified interval. The search can belimited to one or several pump types, wet or dry pitinstallations and a number of other search criteria (see "SetSearch Criteria" on page 17)

A feature in version 2.1 is the ability to search for solutionswith multiple pumps. The program searches for a solution withone or several identical pumps running either in parallel or inseries that meet the required duty point.

The results from the search are presented in a list showing themost desirable pump choices based on the selected sortingcriteria. The list presents general product data together withduty conditions at the duty point. A description of the listcontents is found in: “Pump list - description” on page 25.

For further information regarding the search see Appendix"Pump search methodology" on page 94

Main Screen - Search

Page 21: Fly_p20

User's Guide FLYPS 2.1 Product Selection •••• 17

Set Search CriteriaThe search interval and the available product range, etc. can belimited by setting specific search criteria:

1. In the Main window, select the Search Tab.

2. Click the Criteria button

3. Select a suitable tab and enter the preferred criteria.

Selection Criteria dialog window

The search criteria includes:

General

• Search interval (in percentage of requested dutypoint).

• Minimum and maximum number of pumps formultiple pump searches.

• Max number of pump hits, based on active sortingcriteria, to be presented in the result list.

• Approval (Standard or FM approved product)

Electrical

• Number of poles in the induction motor (all, one orseveral).

• Number of phases (all, 1Ø or 3Ø).

Material

• Material (all, one or several)

Page 22: Fly_p20

18 •••• Product Selection User's Guide FLYPS 2.1

Note! When material or number of poles is unspecified,selecting every available option will slow down the search.Select the option All Material and All Poles instead.

Search based on required flow andhead

1. In the Main window, select the Search Tab.

2. Enter the required flow, total head and (if known)the static head. This specifies the System curve. Ifthe static head is unknown, set it to zero.

3. Select pump type(s) by clicking on the impellerpictures. (Right click the mouse for a detailedexplanation)

4. Select a Single, multiple Parallel- or multipleSeries connection.

5. Select a Wet or Dry Pit installation.

6. Select suitable search criteria (see "Set SearchCriteria" on page 17)

7. Start the search by clicking the Start searchbutton. A box showing the current search criteria isdisplayed during the search.

The pump alternatives meeting the requirements arepresented in a list. The list can be sorted accordingto different criteria by clicking the proper header. Adescription of the pump/impeller list contents isfound in the “Pump list - description” on page 25.

8. Highlight the desired pump(s) for product datapresentation or pump system analysis by clicking onthe products in the pump list.

Search based on required flow and aspecified pipe systemIf a pipe system is defined, the total required head includinglosses can be calculated and is used to search for pumpselections. The losses in the station piping will be taken intoconsideration when searching for parallel pumps.

Page 23: Fly_p20

User's Guide FLYPS 2.1 Product Selection •••• 19

1. In the Main window, select the Search Tab.

2. Design the pipe system (see “Pipe system design” onpage 32).

3. Select the option Use calculated head basedon system.

4. Enter the required flow and the static head if known.The total head is calculated based on the specifiedsystem.

5. Follow the instructions in steps 2 - 7 in section"Search based on required flow and head" on page18.

Search based on alternative pipesystemsSeveral different pipe systems can be specified to finddifferent pump solutions to the same task. The different pipesystems are referred to as Cases.

1. Follow the instructions in section “Search based onrequired flow and a specified pipe system” onpage 18 to specify the first pipe system and searchfor suitable pumps.

2. Click the # icon in the Case ManagerToolbar. A new Main window with a second caseis opened. This case will be a copy of the activecase.

3. Repeat the procedure to specify a second pipesystem and search for suitable pumps. The searchcriteria are common for all cases and do not have tobe specified again. Up to 15 different systems can bespecified.

4. Repeat steps 2 - 3 to specify several alternativesystems. Swap between open windows by using theCase Manager Toolbar. The open window canbe arranged as “Layered”, “Cascaded” or “Tiled” inthe Windows menu.

Page 24: Fly_p20

20 •••• Product Selection User's Guide FLYPS 2.1

Search based on slurry calculation

This function selects pumps for slurry applications. Itcalculates the reduction factors caused by the presence ofsolids for the head and flow from the pump.

Note! For homogeneous, viscous or non-settling slurries thisfunction is not an adequate tool. Also, this slurry function onlysupports the Colebrook-White method for the calculation offriction losses.

Only a small amount of input data from the consideredapplication is required to use this tool. The basic input data arethe slurry description, particle size distributions (d50 and d85),SG’s of the liquid, solids and mixture, solids concentration byweight and volume, mass fraction of particles < 75µm andparticle shape (sand or mica). These inputs are used tocalculate the intersection between the system and pumpcurves, both in terms of slurry, to give the new duty point.

1. On the main Flyps screen, select Search Tab.

2. From the Tool menu choose “Defineliquid/slurry” or click the icon.

Specify liquid

Page 25: Fly_p20

User's Guide FLYPS 2.1 Product Selection •••• 21

3. Select a slurry type from stored projects. Fourslurries are stored as standards; copper and ironores, mill scale and sand.

Browse liquid

4. You can define your own slurry by entering adescription, particle size distributions (d50 and d85),SG’s of the liquid, solids and mixture, solidsconcentration by weight and volume, mass fractionof particles < 75µm and particle shape (sand ormica). See “Specify liquid” overview

5. Click OK twice to return to Search.

6. In the Tool menu choose File and select Save orclick the icon. It is very important to save yournew slurry to be able to find it later under “Browse.”

7. Enter the flow and head for the specific project,select connection, installation, pump type and startsearch. (Note: If you define the piping system aswell, the slurry must be defined first.)

8. Mark one or several pumps.

Page 26: Fly_p20

22 •••• Product Selection User's Guide FLYPS 2.1

Main Screen - Search

9. In the Tool menu, choose Duty analysis or clickthe icon.

Duty Analysis

The following information can be viewed:

• Slurry performance curve

• Shaft power curve for slurry and clean water

Page 27: Fly_p20

User's Guide FLYPS 2.1 Product Selection •••• 23

• Hydraulic efficiency for slurry and clean water

• NPSHre

• System curve

• Clean water performance curve

For more detailed information concerning duty analysis, pleaselook into the respective chapter (see“Duty Analysis” on page35).

Explanations of the input parameters in the slurrycalculation

Description = Slurry name or description.

d50=The sieve size opening for which 50% of the particles arefiner, [mm].

d85 = The sieve size opening for which 85% of the particlesare finer, [mm].

SG Liquid = Specific gravity of the liquid (water is 1).

SG Solids = Specific gravity of the Solids. The density of thesolids divided by the density of water.

SG Mixture = Specific gravity of the mixture.

Conc. by weight = Solid concentration by weight, [%].

Conc. by volume = Solid concentration by volume, [%].

Mass fraction (part. < 75µm) = The fraction of the mass ofsolids of particle size smaller than 75 µm. This is valid up to0.5. Above this, the slurry will be considered homogeneous,viscous or non-settling.

Particle shape = Sand for spherical shapes or mica for flatshapes

Page 28: Fly_p20

24 •••• Product Selection User's Guide FLYPS 2.1

Search based on energyconsumptionThis function is used when the lowest total energyconsumption is the primary search criteria for a pumpingsolution. Most flow duration diagrams can be simplified andreduced to a format of max., average and min. values with veryaccurate results. This flow data is very useful when searchingfor a pump selection yielding the lowest energy consumption.It can be used to determine the optimum parallel pumpsolution. The energy consumption is based on a On-Offpumping system.

1. In the Main window, select the Search Tab.

2. In the Tool menu choose Flow duration or click

the icon. A window for specifying the flowduration data appears.

3. Enter maximum(peak)-, average- and minimum flowvalues and enter the duration in percentage for eachflow respectively. Click OK. The Flow durationwindow is closed.

Flow Duration Diagram dialog box

In the Main window:

1. Select the Use flow duration option.

Page 29: Fly_p20

User's Guide FLYPS 2.1 Product Selection •••• 25

2. Select the Parallel connection. Minimum andmaximum number of pumps allowed in the searchcan be set in the Search criteria (see "Set SearchCriteria" on page 17).

3. Select a Wet Pit or a Dry Pit installation.

4. Select suitable search criteria (see "Set SearchCriteria" on page 17).

5. Start the search by clicking the Start searchbutton. The pump alternatives meeting therequirements are presented in the pump/impeller list.

6. Sort the pump list by Total energy by clicking thecorresponding header. The total energy consumptiondisplayed is based on the entered flow duration data.

7. Mark the desired pump(s) for further product datapresentation or analysis by clicking in the pump list.

Pump list - descriptionThe solutions that meet the Search criteria requirements arepresented in the pump list. The list contains general productdata and duty conditions for each alternative.

The list can be sorted according to different criteria; Numberof pumps, Divergence from duty point, Specific energy andTotal energy consumption. Click on the corresponding headerto sort.

No of* Number of parallel or series pumps requiredto meet the requested duty point (if a multiplepumps search has been performed)

Product Flygt product code.

Curve Curve code

Diff.* Divergence between the requested and theactual duty point

Pwr. cons. Pump motor input power for the actual dutypoint.

Spec.energy*

Specific energy at the actual duty point (kwh/ million gallons) in US units.

Total Total energy consumption over a period of

Page 30: Fly_p20

26 •••• Product Selection User's Guide FLYPS 2.1

energy* time, based on a specified flow duration

NPSHre NPSH required at the actual duty point

Flow Flow at the actual duty point

Rtd. Power The motor's rated power in kW or HP

Poles Number of poles in the induction motor

Phases Number of phases of the electrical powersupply

Vanes Number of impeller vanes or blades

Throughlet Impeller throughlet size

Imp. Diam. Impeller diameter or propeller blade angle

Drive unit Drive unit designation

Version Flygt version codes such as:

.180, 181, 182…Cast Iron pump

.090, 091…FM approved pump

.170, 171, 172…Grinder pump

.980…PH pump

.280, 281…Stainless Steel pump

.410, 490…Low head propeller pumps

Install Available pump installation methods(variants)

Material Pump material

* The pump list can be sorted according to these criteria.

Page 31: Fly_p20

User's Guide FLYPS 2.1 Product Data Presentation •••• 27

Product Data Presentation

Display Product dataProduct data and performance curves for one selected pumpcan be presented on the screen. Product data includes a dataoverview and performance curves.

1. Select a pump either by browsing or searching (see“Browse” on page 15 or "Search" on page 16)

2. Double click the desired pump in the pump/impellerlist or mark it and choose Product data in the

Tool menu or click the icon in the toolbar. Awindow with product data and curves appears.

Product Data - Overview

Page 32: Fly_p20

28 •••• Product Data Presentation User's Guide FLYPS 2.1

Clicking the Print button in the Overview tab generates aPerformance Curve and Rating data printout.

Product data - Rating

Clicking the Print button in the Rating tab generates aPerformance Curve and Rating data printout.

If the current voltage setting does not correspond to the defaultvoltage in the database, a message like the following isdisplayed before the Product data windows appears.

Product data information message

Page 33: Fly_p20

User's Guide FLYPS 2.1 Product Data Presentation •••• 29

Display pump curve and duty pointsDuty points on the performance curve can be displayed byentering flow or head.

1. Display product data for a selected pump accordingto the instructions above.

2. Select the Curves tab.

3. Enter a desired flow or head or click the spincontrols. Data for the duty points are displayed. Thehelp lines indicate the location of the duty points.

Product data - Curves

Page 34: Fly_p20

30 •••• Product Data Presentation User's Guide FLYPS 2.1

View Dimensional DrawingsThe outline Dimensional drawing for a selected pump can beviewed on the screen. The drawings are stored in PDF-format.

1. Select pumps (See “Browse” on page 15 or "Search"on page 16)

2. Mark one or several pumps in the pump list andchoose Dimensional drawings in the Tool menu

or click the icon in the toolbar. A window with alist of the available outline dimensional drawings foreach marked pump appears (Many pumps are oftenavailable with different discharge connections indifferent sizes).

3. Double click on a drawing or highlight the drawingand click the View button. The outline dimensionaldrawing will be displayed on the screen.

Dimensional drawings dialog box

Page 35: Fly_p20

User's Guide FLYPS 2.1 Product Data Presentation •••• 31

Acrobat Reader

Page 36: Fly_p20

32 •••• Pump System Analysis User's Guide FLYPS 2.1

Pump System Analysis

OverviewFLYPS 2.1 provides a number of facilities to analyze a pumpsystem.

These tools are accessed from the Toolbar or the Menu andcan only be activated when a pump has been selected.

The system curve characteristics must be defined before ananalysis can be performed. The system curve can be defined bytwo specified duty points or by specifying a pipe system.

To fully utilize these tools, good pumping knowledge isessential.

Pipe system designThe system curve is the base for all analysis in FLYPS 2.1. Apipe system with two individual pipes (suction piping and/orstation piping) per pump and up to three common pipes (forcemains) with different dimensions and properties can bespecified. A number of user-selectable point losses can beadded to each pipe section.

Branched systems cannot be analyzed.

1. In the Tool menu, choose Pipe system design or

click the icon in the toolbar. A window for pipesystem design appears.

2. Select any of the tabs Station Piping 1, StationPiping 2 or ForceMain1 - ForceMain3.

Page 37: Fly_p20

User's Guide FLYPS 2.1 Pump System Analysis •••• 33

3. Enter pipe section length and select Material,Pressure class and Dimension. Values for insidediameters for standard pipes are stored in a table.

It is also possible to specify a custom or special pipe byclicking the check box for Standard pipes andentering the inside diameter.

4. Click the spin controls to enter number of pipefittings for each pipe section.

5. Repeat steps 2 - 4 until the entire system has beendefined.

Pipe System Design dialog box

Head loss calculationsHead Loss calculations can be made to determine the requiredtotal discharge head (TDH.). FLYPS 2.1 supports two methodsof head loss calculations; the Colebrook-White and Hazen-Williams equations. Typical values used in these calculationssuch as roughness / C-factors for different materials and pointloss factors can be edited in Setup (See also “Set Head losscalculation method and constants” on page 64).

Single or parallel multi-pump systems can be analyzed. Thecalculations are based on clean water pumping.

Page 38: Fly_p20

34 •••• Pump System Analysis User's Guide FLYPS 2.1

1. Design the pipe system (see “Pipe system design” onpage 32).

2. Enter the design flow and the static head.

Head loss calculations

The following is calculated and presented:

• Total friction loss

• Total head, (static head and total losses)

• Liquid velocity for each pipe section (station pipingonly if the Single (pump) radio button is selected)

• If the Multi (multiple pump) radio button isselected, different values for the total losses arepresented (the flow rate in the station piping willvary depending upon the number of pumps requiredto meet the total flow).

The different values for total head can be used whensearching for multiple pump solutions when thenumber of requested pumps is unspecified.

Page 39: Fly_p20

User's Guide FLYPS 2.1 Pump System Analysis •••• 35

Duty AnalysisPerformance analysis is used to study pump performancecurves and duty conditions in a single or a multiple pumpsystem.

One or several flow/head-, power-, efficiency- and NPSHcurves can be displayed for comparing pump alternatives.

Duty conditions, combined and for each individual pump, canbe studied in a system with several identical pumps. The dutypoint is based on the system curve. The data is presented inboth diagram and table format.

The graphs presenting performance curves and duty conditionscan be printed or exported to a WMF-file (Windows MetaFile)

1. Specify a system by entering a flow, total head andstatic head or by designing a pipe system and givinga flow.

2. Select pumps by searching or browsing (See“Browse” on page 15 or "Search" on page 16)

3. Mark one or several pumps in the pump list andchoose Duty analysis in the Tool menu or click

the icon in the toolbar. A window forperformance analysis appears. The marked pumpsare ”transferred” into the analysis window.

The window is divided into two tabs; Performance curvesand Duty conditions.

Page 40: Fly_p20

36 •••• Pump System Analysis User's Guide FLYPS 2.1

Performance curves

Duty Analysis - Performance curves

Mark the desired pump(s) in the list and use the check boxesto select the desired curves. The curve plot can be printed byclicking the Print button. It can also be exported to a WMF-file by clicking the Export button.

The following information can be viewed:

• Performance curve(s). If a pipe system is specifiedand parallel pumps are used, the reduced pumpperformance curve will also be displayed.

• Input power curve(s)

• Shaft power curve(s)

• Pump efficiency curve(s)

• Overall efficiency curve(s)

• NPSH required curve(s)

Page 41: Fly_p20

User's Guide FLYPS 2.1 Pump System Analysis •••• 37

Duty conditions

Duty Analysis - Duty conditions

Mark the desired pump and use the spin controls to enternumber of pumps running in the system. The graph can beprinted by clicking the Print button. The graph can also beexported to a WMF-file by clicking the Export button.

The following information is presented:

Each pump:

• The pump curve for each individual pump.

• Flow, head, input power, shaft power, efficiency,pump efficiency and specific energy at the dutypoint for each individual pump when the number ofpumps entered is running.

• Help lines highlight the duty point.

Page 42: Fly_p20

38 •••• Pump System Analysis User's Guide FLYPS 2.1

All pumps

• The combined performance curve for the selectednumber of pumps. If a pipe system is specified, thiscurve will be reduced by the head loss in eachpump's station piping.

• Total values for flow, head (reduced by the stationpiping), input power, shaft power, overall efficiency,pump efficiency and specific energy for the systemwith all specified pumps running.

• Help lines highlight the duty point.

Life cycle cost analysisThe following is an excerpt from the Guide to Life Cycle CostAnalysis for Pumping Systems developed by the HydraulicInstitute and EUROPUMP.

“Pumping systems account for nearly 20% of the world’selectrical energy demand and range from 25-50 % of theenergy usage in certain industrial plant operations. Pumpingsystems are widespread; they provide domestic services,commercial and agricultural services, infrastructure services,and industrial services for food processing, chemical,petrochemical, pharmaceutical, and mechanical industries.Although pumps are offered to markets as individualmachines, they provide a service only when operating as partof a system. The energy and materials consumed inaccomplishing this task depend on the design of the pump, thedesign of the installation, and the way the system is operated.These factors are interdependent. What’s more, they must becarefully matched to each other, and remain so throughouttheir working lives to ensure the lowest energy consumptionand cost. The initial purchase price is a small part of the LCCfor high usage pumps. Operating requirements may sometimesoverride energy cost considerations, but an optimum solutionis still possible.

A greater understanding of all the components that make upthe total cost of ownership will provide an opportunity todramatically reduce energy, operational, and maintenancecost. Excessive waste and energy usage are important factors

Page 43: Fly_p20

User's Guide FLYPS 2.1 Pump System Analysis •••• 39

in global environmental pollution. Reducing energy andmaterial usage also benefits the user by reducing costs.

Life Cycle Cost (LCC) analysis is a management tool that canhelp companies minimize waste and maximize energyefficiency for many types of systems, including pumpingsystems”

Life cycle cost analysis is used when comparing life cyclecosts for different pumping solutions. Future energy costs andmiscellaneous annual costs are calculated into a capitalizedpresent day value based on the selected interest rate. Thecalculation is based on the summation of the cost elements thatmake up the LCC.

LCC = (Cic + Cin + Ce + Co + Cm + Cs + Cd + Cenv)

C = cost element

ic = initial cost, purchase price (pump, system, pipe, auxiliaryservices)

in = installation and commissioning cost (including training)

e = energy costs (predicted cost for system operation,including pump driver, controls, and any auxiliary services)

o = operation cost (labor cost of normal system supervision)

m = maintenance and repair cost (routine and predictedrepairs)

s = down time cost (loss of production)

d = decommissioning/disposal cost (including restoration ofthe local environment and disposal of auxiliary services).

env = environmental cost (contamination from pumped liquidand auxiliary equipment)

Pumping solutions selected in all open Cases can be compared

1. Select pumps by searching (See “Search” on page16)

2. Mark one or several pumps in the pump list andchoose life cycle cost in the Tool menu or click theicon in the toolbar. A window for economy analysis

Page 44: Fly_p20

40 •••• Pump System Analysis User's Guide FLYPS 2.1

appears. The marked pumps are ”transferred” intothe analysis window.

3. Enter values for interest rate, energy rate, economicproject life and annual operation time.

4. To include pumps selected in all open Cases, selectthe option Include all open cases. All marked pumpsin the inactive Cases are “imported” for the purposeof performing a life cycle cost analysis.

5. Select the LCC button.

Page 45: Fly_p20

User's Guide FLYPS 2.1 Pump System Analysis •••• 41

1. Select the Initial Investment and DecommissioningCost tab.

2. Enter the cost of the pumps, controls, accessories,piping and engineering and design in the appropriatetext boxes. This will encompass Cic TotalEquipment Cost. The pump cost should be perpump while the balance of the items should be totalcost. Costs that are not applicable should be left as”0.00”.

3. Continue with installation cost and commissioningcost (including any training), to make up Cin.

4. Enter any decommissioning cost.

5. Select the Annual Costs tab.

Page 46: Fly_p20

42 •••• Pump System Analysis User's Guide FLYPS 2.1

1. The annual pump energy cost is calculated anddisplayed in a grayed out text box.

2. Enter any other annual energy cost for the auxiliaryequipment. This will be added to, and displayed asthe Total Energy Cost.

3. The next two text boxes are for the pump operatingcost and any additional operating costs.

4. They give the Total Cost of Operation.

5. The next two boxes are for the pump maintenancecost and any other maintenance costs.

6. These two boxes are added together and displayedas Total Cost of Maintenance.

7. Next are inputs for down time cost andenvironmental cost. These are added to the threeabove totals to give the Total Annual Cost.

8. Select OK to view the bar graphs in the LCCWindow.

Page 47: Fly_p20

User's Guide FLYPS 2.1 Pump System Analysis •••• 43

VFD - AnalysisThe VFD analysis tool is used to examine the effects ofvariable speed pumping with a Variable Frequency Drive(VFD). Two ways of applying VFD controls can be analyzed:

• One-Pump, One pump is speed regulated and allothers run at full speed with On-Off control.

• All-Pumps, All pumps in the system are speedregulated in parallel.

A number of graphs can be displayed to show the effects ofVFD use in the specified system. Graphs can be printed orexported to a WMF-file (Windows Meta File)

1. Select pumps by browsing or searching (See“Browse” on page 15 or "Search" on page 16).

2. Mark one or several pumps in the pump list andchoose VFD analysis in the Tool menu or click

the icon in the toolbar. A window for VFDanalysis appears. The marked pumps are”transferred” into the analysis window.

3. Click on the pump list to select a pump.

4. Select the type of VFD control: One-pump VFDcontrol or All-pumps VFD control. The two VFDcontrol scenarios that are available are by far themost popular. The first, “One-Pump VFD” refers toa control scenario where one pump is speedregulated while all other pumps that are running areat full speed. This scheme starts with the speed-regulated pump coming on first and increasing inspeed until it reaches full speed. At this timeanother pump would be started and this pump wouldrun at full speed while the second would be speedregulated. This would continue until all pumps wererunning at full speed. The shut down sequencewould be in reverse. The second scenario, “All-Pumps VFD”, refers to a control system in which allpumps are speed regulated together. In such asystem all pumps would be run at the same time andthe same speed. They would be increased in speeduntil they all reach full speed.

Page 48: Fly_p20

44 •••• Pump System Analysis User's Guide FLYPS 2.1

5. Click the appropriate tab to display a diagram.

6. The graph shown can be printed by clicking thePrint button. The graph can also be exported to aWMF-file by clicking the Export button.

VFD Analysis - Frequency curves

Graphs showing the effects of VFD use in the specified systemare presented under five different tabs. A description of thediagrams and the presented data follows.

Pump Performance

Page 49: Fly_p20

User's Guide FLYPS 2.1 Pump System Analysis •••• 45

VFD Analysis - Pump Performance

The Number of pumps in operation and the operationalfrequency can be changed by clicking the spin controls.

The following data are presented:

• Blue curves: Combined performance for thespecified number of pumps operating and forfrequencies in 5 Hz increments.

• Gray curves: Combined performance for otherpossible numbers of pumps operating and forfrequencies in 5 Hz increments.

• Red curves:

1. Total performance for the specifiedfrequency and the specified number ofpumps in operation.

2. Pump performance for each VFD pump.

• Black curve: Performance for the const. speedpump(s) (only when using a one-pump VFDcontrol).

• Help lines highlighting the duty points at thespecified frequency - total, regulated and const.speed pumps.

• Tabulated performance data for a specifiedfrequency and a specified number of pumps inoperation.

Page 50: Fly_p20

46 •••• Pump System Analysis User's Guide FLYPS 2.1

Pump Perf. vs. Freq. (Performanceversus Frequency)

VFD Analysis - Performance vs. Frequency

The Number of pumps in operation can be changed by clickingthe spin controls.

The graph shows data plotted versus frequency.

• Flow - Total, regulated or const. speed pump

• Head - Total, regulated or const. speed pump

The three radio buttons in the pump region Total, Regulatedand Constant Speed Pump, are described below.

Selecting the Total button will illustrate the values for allpumps combined whether they are a regulated pump orconstant speed pump. Selecting the Regulated button willillustrate the values for a single regulated pump, whether One-Pump VFD or All-Pump VFD is selected. Selecting theConstant Speed Pump button will display the values for onepump running at full speed, the change in frequency refers tothe regulated pump, since the constant speed pump does notchange speed.

Page 51: Fly_p20

User's Guide FLYPS 2.1 Pump System Analysis •••• 47

Power vs. Freq. (Power versusFrequency)

VFD Analysis - Power vs .frequency

The graphs shows power data plotted versus frequency.

• Total input power (electrical)

• Input power (electrical)

• Shaft power

• Total efficiency

• Overall efficiency

• Pump efficiency

• VFD efficiency - VFD effects, only available when aRegulated pump is selected.

Page 52: Fly_p20

48 •••• Pump System Analysis User's Guide FLYPS 2.1

Power vs. Flow (Power versus Flow)

VFD Analysis - Power vs. Flow

The graphs shows data plotted versus flow.

• Total input power (electrical)

• Input power (electrical)

• Shaft power

• Total efficiency

• Overall efficiency

• Pump efficiency

Page 53: Fly_p20

User's Guide FLYPS 2.1 Pump System Analysis •••• 49

Specific Energy

VFD Analysis - Specific Energy

Specific energy is defined as the energy consumed by apumping system (pumps and piping system) for a givenvolume of pumped liquid. This is a measure of the system'senergy consumption per unit liquid, and is usually expressedin kWh/Mg (kilowatt hours/million gallons). Specific energyis useful when comparing different pump and piping systemsolutions from the operating cost point of view.

The graphs show data plotted versus flow.

• One-pump VFD control, Specific Energy whenone pump is VFD controlled and the others run atfull speed On-Off controlled.

• All-pumps VFD control, Specific Energy whenall pumps in the system are operated on VFD's.

• On-Off control, Specific Energy when all pumpsrun at full speed in an On-Off controlled mode.

Page 54: Fly_p20

50 •••• Pump Station Design User's Guide FLYPS 2.1

Pump Station Design

Sump Volume CalculationFLYPS 2.1 provides a module for pump station design. Theminimum active sump volume and stop levels are calculated todetermine the minimum station dimensions. The calculationshandle duplex pump stations with one pump in operation andone spare pump.

The sump volume calculation is based on pump capacity andthe maximum number of starts per hour. The stop level andstation dimensions are calculated together with the sumpgeometry and the specified start level.

1. Select pumps either by browsing or by searching(see “Browse” on page 15 or "Search" on page 16)

2. Mark one desired pump in the pump list and choosePump Station design in the Tool menu or click

the icon in the toolbar. A window to design apump station appears.

3. Enter pump design flow. If the pump is selected bysearching, the pump flow is transferred and cannotbe changed.

4. Select Station type.

5. Select Discharge flange size.

6. Enter grade elevation, use the spin controls to enterStart level and Number of start per hour. Theminimum active sump volume, stop level and levelfor station footings are calculated.

Page 55: Fly_p20

User's Guide FLYPS 2.1 Pump Station Design •••• 51

Pump station design - Minimum sump volume calculation

Page 56: Fly_p20

52 •••• Printouts User's Guide FLYPS 2.1

Printouts

Print Pump Performance CurveA pump performance curve for a selected pump can be printed.The printed document includes product data and diagrams withcurves including; head, input and shaft power, efficiency andNPSH-required.

The printout is handled through the Windows Print manager.The printer settings can be altered by choosing Printer Setupin the File menu.

1. Select pumps (see “Browse” on page 15 or "Search"on page 16)

2. Double click the desired pump in the pump list. Awindow with product data and curves appears. Youcan also mark the desired pump and choose

Product data in the Tool menu or click theicon in the toolbar.

3. Select the Overview tab and click the Print button.

Page 57: Fly_p20

User's Guide FLYPS 2.1 Printouts •••• 53

Performance curve printout

Page 58: Fly_p20

54 •••• Printouts User's Guide FLYPS 2.1

Print Outline Dimensional DrawingsAn outline dimensional drawing for a selected product can beprinted by using Acrobat Reader. The drawings are stored inPDF-format.

The printout is handled by Acrobat Reader through theWindows Print manager.

1. Select pumps (see “Browse” on page 15 or "Search"on page 16)

2. Mark one or several desired pumps in the pump listand choose Dimensional drawings in the Tool

menu or click the icon in the toolbar. A windowwith a list of all available dimensional drawings foreach marked pump appears.

3. Double click on the desired drawing or mark thedrawing and click the Print button. Acrobat Readerstarts and a window to select options for the printoutappears.

4. Select options and click OK.

Page 59: Fly_p20

User's Guide FLYPS 2.1 Printouts •••• 55

Outline Dimensional drawing

Page 60: Fly_p20

56 •••• Printouts User's Guide FLYPS 2.1

Print Rating dataRating data for a selected pump can be printed on paper. Theprinted document includes rated data based on the selectedvoltage.

The printout is handled through the Windows Print manager.The printer settings can be altered by choosing Printer Setupin the File menu.

1. Select pumps (see “Browse” on page 15 or "Search"on page 16)

2. Double click the desired pump in the pump/impellerlist . A window with product data and curvesappears. You can also mark the desired pump andchoose Product data in the Tool menu or click the

icon in the toolbar.

3. Select the Rating tab and click the Print button.

Print System Analysis ReportsA report of a performed system analysis can be printed. Allprintouts have a uniform layout and include projectinformation, user name and date.

The printouts are handled through the Windows Printmanager. The printer settings can be altered by choosingPrinter Setup in the File menu.

1. Follow the instructions for the preferredanalysis.

2. Click the Print button. If a project has notbeen specified a window to enter projectinformation appears. If required, enter projectname and click OK. A printout based on thepresent values is generated.

Export graphs to Windows Meta FileFLYPS 2.1 provides graphs from Duty analysis and VFD-analysis that can be exported to a Windows Meta File (.WMF).

Page 61: Fly_p20

User's Guide FLYPS 2.1 Printouts •••• 57

Graphs stored as WMF-files can easily be inserted as picturesin other documents such as Word documents.

1. Follow the instructions for the preferredanalysis.

2. Click the Export button. A standard dialogwindow to enter a filename appears.

3. Enter a path and a filename and click OK.

Create Project ReportA composite report consisting of several printouts can begenerated.

The report can be customized and consists of: PumpPerformance Curve, Rating data, Outline dimensionaldrawings, Sump volume calculations, Pipe system design, Lifecycle cost analysis, Duty analysis and a VFD analysis.

1. Select pumps either by browsing or by searching(see “Browse” on page 15 or "Search" on page 16)

2. Mark one or several desired pumps in the pump list

and choose Print in the File menu or click theicon in the toolbar. A window to specify reportcontents appears.

3. Select items to be included in the report and clickOK. If a project has not been specified, a window toenter the project information will appear. Enter theproject name and click OK. Windows to selectfurther options for each printout will appear oneafter the other.

4. Select options when applicable and click Print ineach window.

Page 62: Fly_p20

58 •••• Printouts User's Guide FLYPS 2.1

Create Project Report Dialog box

Page 63: Fly_p20

User's Guide FLYPS 2.1 Project Management •••• 59

Project Management

OverviewProject work, including several Cases, can be stored in aproject database.

The following data is stored:

• Project information, such as project name, end user,etc.

• Entered pipe system(s)

• Entered flow duration diagram

• Designed pump station

Project Management

Create a new Project1. Input data as applicable: pipe systems, flow duration

etc.

2. In the Tool menu, choose Project Information or

click the icon. A window to enter projectinformation appears.

3. Enter project name, end user and remarks and clickOK.

4. In the File menu choose Save. The active case inthe project is stored. Choose Save All to save allopen Cases.

Page 64: Fly_p20

60 •••• Project Management User's Guide FLYPS 2.1

Project Information Dialog box

Open a Project1. In the File menu, choose Open. A window with all

previously saved projects appears. The savedprojects can be sorted by clicking on the appropriateheading. It is possible to display projects created byall users or only projects created by the current user.

2. Mark the desired project.

3. Click OK. The selected project opens.

Open Project Dialog box

Page 65: Fly_p20

User's Guide FLYPS 2.1 Project Management •••• 61

Delete a project1. In the File menu choose Open. A window with all

previously stored projects appears. The sorting canbe changed by clicking the proper heading.

2. Mark the project to be deleted.

3. Click Delete. The marked project is deleted.

Page 66: Fly_p20

62 •••• Settings User's Guide FLYPS 2.1

Settings

OverviewSettings are user defined parameters that can be used tocustomize the program according to the user’s wishes. Allsettings are saved to a file with some of the search criteriawhen closing the program and are restored at the next session.

The settings include; dialog language, frequency, voltage,units, head loss calculation constants, economy calculationdefaults and also paths to your Internet browser, AcrobatReader and the outline dimensional drawing libraries.

Note that the database contents vary in different countries,therefore changing language, frequency, and voltage mighttherefore not be applicable to you.

A combination of settings can be saved as a User profile. Thisenables all custom settings to be changed in one operation(See “Create a User Profile” on page 66).

Page 67: Fly_p20

User's Guide FLYPS 2.1 Settings •••• 63

Set default values

Setup dialog window

Set Dialog language1. In the Setup menu choose Language. All

available dialog languages appear.

2. Select language.

Set FrequencyChanging frequency is only applicable if the pump databasecontains both 50Hz and 60Hz products.

1. In the Setup menu choose Setup or click theicon. A window to change settings appears.

2. Select the General tab.

3. Select preferred frequency and click OK.

Set VoltageChanging voltage is only applicable if the database containsdata for several voltages.

Note that product and performance data for some pumps isonly available in the default voltage.

Page 68: Fly_p20

64 •••• Settings User's Guide FLYPS 2.1

1. In the Setup menu choose Setup or click theicon. A window to change settings appears.

2. Select the General tab.

3. Select preferred voltage and click OK.

Set UnitsInput and output data can be entered and displayed in differentunits in any combination.

1. In the Setup menu choose Setup or click theicon. A window to change settings appears.

2. Select the Units tab.

3. Select preferred units and click OK.

Set Head loss calculation methodand constantsThe Head loss calculation method and constants used in losscalculations, such as roughness, C-factors and point lossfactors, can be set according to user wishes.

1. In the Setup menu choose Setup or click theicon. A window to change settings appears.

2. Select the Head loss tab.

3. Select the preferred head loss calculation method,enter the new constants and click OK.

Set Life cycle cost calculation defaultvaluesDefault values used in the Life cycle cost calculations, such asenergy cost and interest rate, can be set according to userpreference.

1. In the Setup menu choose Setup or click theicon. A window to change settings appears.

2. Select the Economy tab.

3. Enter proper default values and click OK.

Page 69: Fly_p20

User's Guide FLYPS 2.1 Settings •••• 65

Set VFD typeType of VFD properties used in the VFD analysis can be setaccording to the user’s preferences.

1. In the Setup menu choose Setup or click theicon. A window to change settings appears.

2. Select the VFD tab.

3. Select the proper VFD type and click OK.

The following refers to the three types of VFD’s. Flyps willuse this value to determine the efficiency of the VFD and inturn calculate the specific energy.

The Ideal button selects a typical PWM VFD, but it ignoresthe effect the VFD can have on a motor related to torque. Thiseffect is taken into account in the next two types. TheFrequency ~ Voltage option is the most common PWM VFDtype. Here, the voltage remains proportional to the frequencythroughout the reduced frequency range. This means thetorque capability of the motor remains constant as frequency isreduced, but the attached (centrifugal) load will be reducedmore quickly than the linear reduction in frequency. Thus therelative load on the motor becomes less and less as frequencyis reduced, and at lower loads the motor will tend to operateless efficiently. The Frequency ~ Voltage2 is therecommended PWM VFD type for centrifugal loads. In thiscase, as frequency is reduced the voltage is reduced by thesquare of the reduction in frequency. The motor torque isreduced more quickly than in the above case, roughly in thesame proportion as the attached centrifugal load. Thus, therelative load on the motor is almost constant so it operates atabout the same high efficiency at lower loads as it did at fullload.

Set program and library pathsTo be able to utilize the functions in FLYPS 2.1 using AcrobatReader to view outline dimensional drawings or the Internetshortcuts, proper paths need to be set.

If Acrobat Reader and the outline dimensional drawings wereinstalled together with FLYPS2.1, the paths to the viewer andto the drawing library were set during that procedure.

Page 70: Fly_p20

66 •••• Settings User's Guide FLYPS 2.1

1. In the Setup menu choose Setup or click theicon. A window to change settings appears.

2. Select the Program tab.

3. Set paths for Acrobat Reader, the outlinedimensional drawing library and your Web Browser.Click OK.

Create a User ProfileA combination of settings can be saved with a User profile.User profiles enable all the settings including language, unitsand calculation defaults etc. to be changed in one operation.

1. In the Setup menu, choose User profile. Awindow to select, add and edit User profiles appears.

2. Click the Add button. A window to enter settingsfor a new profile appears.

3. Select the preferred settings and click OK.

4. Enter a name for the new User profile and click OK.

5. Click OK to set the new profile as current and closethe window.

User Profile Dialog box

Page 71: Fly_p20

User's Guide FLYPS 2.1 Tutorial •••• 67

Tutorial

OverviewWe will explore, step by step, the procedures needed toperform your first pump search and basic system analysis inthis section.

This guided tour is divided into two parts.

The first part is basic and covers a pump search together with asimple system analysis and product data printout.

The second part is more advanced and covers different aspectsof pump searching together with an extensive system analysis.

It is assumed that you are comfortable with working in theWindows environment.

Basic pump search

Task descriptionFind a suitable pump for a duplex wastewater pump station.The pump should be in a wet pit installation. The design flowfor the station is 350 GPM and total head is 29 ft. Availablevoltage is 460 V with a frequency of 60 Hz.

The following parameters should be included in thespecification of the pump:

Product data

• Product code

• Curve code

Page 72: Fly_p20

68 •••• Tutorial User's Guide FLYPS 2.1

• Voltage [V]

• Rated power [HP]

• Rated current [A]

• Starting current [A]

• Weight [lbs]

• Available discharge connection sizes

• Height of pump [ft]

Performance

• Flow [GPM]

• Head [ft]

• Deviation from duty point [%]

• Input power [kW]

• Overall efficiency [%]

• Pump efficiency [%]

• NPSH required [ft]

Enclose printouts of a dimensional drawing and performancecurve for the specification after retrieving all the data.

If you have studied the manual for FLYPS 2.1, try to solve thistask by yourself. Otherwise, let the following pages guide youthrough the pump selection process, and learn how to retrieveperformance and product data and how to print outlinedimensional drawings and performance curves.

SolutionPump search

The first step in a search is to enter the duty point. Enter flowand head. Static head can be set to zero if it is unknown. Theentered value in the input box is total head, i.e. the sum ofstatic head and friction loss.

The C-type impeller is typical for wastewater applications (SeeAppendix “Description of Flygt pump types” on page 88 formore information). It has a high efficiency and excellent solidshandling properties. We are searching for a wet pit pumpinstallation, so be sure that the installation type is set to wet.

Page 73: Fly_p20

User's Guide FLYPS 2.1 Tutorial •••• 69

The specification stated that one pump should be able tohandle the duty point. This means that the connection shouldbe set to single.

Remember to always make sure that proper search criteria areused. Incorrect search criteria may result in an incorrect pumpselection.

A search interval of ± 10 % is adequate for low flows. Forlarger flows, use a narrower interval. The min. / max. value inthe multiple pump search section is not accounted for whenrunning a search with a single connection. FM approval is notnormally needed for standard wastewater applications. For therest of the parameters, use the default values. Search for allpoles, phases and materials.

1. Select the Search tab

2. Specify duty point.

• Enter flow. 250 GPM.

• Static head is unknown. Enter 0 ft.

• Enter head. 29 ft.

3. Click to choose impeller type C.

4. Set Connection to single.

5. Set Installation to wet-CP.

6. Click the Search criteria button. A window to setSearch criteria appears

• Set Search interval. - 10% and + 10%.

• Set Approval to Standard.

• Make sure that All poles, All phases andAll materials are selected. Click OK.

Page 74: Fly_p20

70 •••• Tutorial User's Guide FLYPS 2.1

1. Click the Start search button to perform a search.

After running the pump search, the pump list is displayed. Itshould look like the one below. Minor differences may benoted due to different product mixes in a later version of theprogram.

Page 75: Fly_p20

User's Guide FLYPS 2.1 Tutorial •••• 71

Main screen - Pump list

The pump list can be sorted according to different criteria.Sorting can be done with respect to no of pumps, deviationfrom duty point, specific energy and total energy.

The fact that we are searching for a single pump means that itis useless to sort by number of pumps. A duration diagram hasto be specified in order to sort on total energy. The relevantparameters left to sort on are deviation from duty point andspecific energy.

The following performance data can be obtained in the resultlist:

• Duty point flow

• Power consumption (input power)

• NPSH req.

The C 3102 is the least expensive one in the pump list. Let’sanalyze this pump to determine if the duty point is acceptable.Specifically, we want to determine if the duty point is withinthe preferred operational range on the pump curve, if NPSHreq. is acceptable, if the efficiency is sufficient, etc.

Page 76: Fly_p20

72 •••• Tutorial User's Guide FLYPS 2.1

Duty analysis

1. Select the C 3102 LT 63-441 by clicking on it in theresult list. Several pumps can be selected for theanalysis; click on all desired pumps in the list

2. In the Tool menu choose Duty analysis or click

the icon in the toolbar. A window for dutyanalysis appears.

3. Click the check boxes for Shaft power and Pumpefficiency to select those curves.

Performance curves for the C 3102-LT 63-441

This duty point is acceptable.

Now, when the pump is selected it is time to fill in thedata and performance tables. All performance datacan be found in the Duty analysis window. Some ofthe data can also be found directly in the pump list.

The following data can be obtained under thePerformance curves tab.

The values for:

• Shaft power

• Pump efficiency.

4. Click on the Duty condition tab.

Page 77: Fly_p20

User's Guide FLYPS 2.1 Tutorial •••• 73

Performance at the duty point for a C 3102-LT 63-441

The following data is obtained under the Dutycondition tab.

Duty point values for:

• Flow

• Head

• Input power

• Efficiency

• Specific energy.

5. Click Close to return to the Main window

Page 78: Fly_p20

74 •••• Tutorial User's Guide FLYPS 2.1

We have now found all of the data for the performance table inthe specification.

PerformanceFlow [GPM] 253Head [ft] 29.7Difference from duty point [%] 0.1Input power [kW] 4.2Shaft power [HP] 4.6Overall efficiency [%] 34.1Pump efficiency [%] 41.6Req. NPSH [ft] 12.9

Product data

1. Choose Product data in the Tool menu or click

the icon. It is also possible to double click on theselected pump in the pump list. A window for theProduct data presentation appears.

Note that the icon will be enabled only when onepump is selected.

2. A window with available installation types appears.Select installation type "P" and Click OK.

Page 79: Fly_p20

User's Guide FLYPS 2.1 Tutorial •••• 75

The product data window is divided into three sections;Overview, Rating, and Curves.

Product data overview

Overview - contains general product information such asvoltage, frequency, rated power, rated current, throughlet size,etc.

Rating - contains information about different ratings; forexample ratings for warm liquids. Please note that thisinformation is not available for all products.

Curves - Pump performance curves.

The following data can be obtained in the Product datawindow

• Rated power [HP]

• Rated current [A]

• Starting current [A]

• Weight [lbs]

3. Click Close to return to the Main window.

Page 80: Fly_p20

76 •••• Tutorial User's Guide FLYPS 2.1

Dimensional data

Now we have almost all of the information to fill in theproduct data sheet in the specification. The information aboutdischarge connections and the height of the pump is stillmissing. These can be obtained by viewing the outlinedimensional drawings.

1. In the Tool menu choose Outline Dimensionaldrawings or click the icon in the toolbar. Awindow with available installations and dischargeconnections appears.

The specification stated that the pump should be installed in awet pit. The FLYGT denomination for a permanent submergedinstallation is P, and the pump denomination is therefore CP.(See Appendix "Description of Pump Installation types" onpage 90 for more information)

Outline Dimensional drawings for different installations and differentdischarge connections for the C 3102-LT 63-441.

The following requested data can be obtained from thedrawing:

Available discharge connections

• Available discharge connections for the selectedpump are ∅ 100/∅ 100 and ∅ 150/∅ 150.

Page 81: Fly_p20

User's Guide FLYPS 2.1 Tutorial •••• 77

1. Select CP 3102-LT DN100/DN100

2. Click View or double click on the row with therequested discharge connection to view thedimensional drawing. Acrobat Reader starts anddisplays the PDF file.

Dimensional drawing CP 3102 LT

The following data can be obtained from the drawing:

• Height of the pump

The drawing can be viewed and zoomed in and out by usingthe magnifying glass.

The dimensional drawings contain outline dimensions of thepump, guide bars and discharge connection size. Thedimensional drawing can be printed from within acrobat andfrom FLYPS 2.1.

3. Click Close to return to the Main window.

Page 82: Fly_p20

78 •••• Tutorial User's Guide FLYPS 2.1

The resulting product data table should look like this:

Product dataProduct code 3102.180Curve code 63-441Rated shaft power [HP] 5.0Voltage [V] 460Rated current [A] 6.5Starting current [A] 31.0Weight [lb] 258Available discharge connections ∅∅∅∅ 4”/∅∅∅∅ 4” and

∅∅∅∅ 6”/∅∅∅∅ 6”Height of pump [in] 24.3

PerformanceFlow [GPM] 253Head [ft] 29.7Difference from duty point [%] 1Input power [kW] 4.2Shaft power [HP] 4.6Overall efficiency [%] 34.1Pump efficiency [%] 41.6Req. NPSH [ft] 12.9

Page 83: Fly_p20

User's Guide FLYPS 2.1 Tutorial •••• 79

Printout of pump performance curve and outlinedimensional drawing.

1. In the File menu choose Print or click the iconto create a report. A window to specify a customreport appears.

2. Click the check boxes for Dimensional drawing andPerformance curve in the report dialog box.

3. Click OK to start the Printout.

Report dialog box.

Pump search based on a pumpingsystem

Task descriptionSelect suitable wastewater pumps for the system below. TheNumber of pumps is unspecified and has to be determined.One of the pumps shall be an installed spare. The systemshould be designed for minimum energy consumption.

Average flow during the day is 1500 GPM with peaks in themorning and evening. The peak flow is 2500 GPM. Minimumflow (night time) is 550 GPM. The flow is at minimum levelfor 35 % of the day, average flow is 60 % /day and the peakslast for 5 % of the day.

The force main and individual station pipes are made ofductile iron, Class 53. All pipes are considered to be new.

Page 84: Fly_p20

80 •••• Tutorial User's Guide FLYPS 2.1

Available voltage is 460 V and the frequency is 60Hz.

Pipe system illustration

Sump floor elevation + 200 ft.

W.L. in sump + 208 ft.

Outlet elevation + 230 ft.

W.L. at outlet + 219 ft.

Individual station pipe

Length 15 ft.

Diameter 10 "

Material Ductile iron, Class 53

1 Discharge con. k=0.3

1 Valve k=0.3

1 Check valve k=0.9

2, 90 degree bend. k=0.3

Force main #1

Length 5000 ft

Diameter 20 in

Material Ductile Iron

3 x 90 degree bend. k=0.3

1 x Outlet k=1.0

Page 85: Fly_p20

User's Guide FLYPS 2.1 Tutorial •••• 81

SolutionPipe system specification

The first step is to calculate the losses in the system. This isdone in the Design pipe system window. The pipe system isdivided into two different kinds of pipes, station piping andforce main pipe. The total flow runs through the force mainand the flow in the station piping is the flow from each pump.

You can specify one or two station pipes for each pump in thesystem and up to 3 force mains. Diameter, length, material/roughness and point losses must be specified for every pipesection.

If length is omitted for a pipe section, it will not be accountedfor in the loss calculation.

Five pipe sections are normally enough to model almost anypipe system, including complex ones.

Station piping

1. In the Tool menu, choose Design Pipe System

or click the icon in the toolbar. A window fordesigning a pipe system appears.

2. Enter flow. 2500 GPM

3. Enter static head 15 ft.

4. Select the first station piping tab.

5. Enter length. 15 ft.

6. Make sure Standard pipes are selected.

7. Choose ductile iron in the Material drop down listbox.

8. Choose CL 53 in the Pressure class drop down listbox.

9. Choose 10 in the Dimension drop down list box.

10.Specify point losses. Add 1 x Dischargeconnection, 2 x 90°°°° Bend, 1 x Valve and 1 xCheck valve by clicking on the spin control in theedit boxes.

Page 86: Fly_p20

82 •••• Tutorial User's Guide FLYPS 2.1

Loss calculation. Specification of station piping.

Note. The water velocity stated in the lower left corner iscalculated for single pump duty only. When running multiplepumps, the velocity in the station pipes will decrease due tochanging duty points. The loss factors can be edited in thesetup.

Force main

1. Specify losses in the force main. Select the Forcemain 1 tab or click on the pipe section in thepicture of the pipe system.

2. Enter length. .

3. Make sure Standard pipes are selected.

4. Choose ductile iron in the Material drop down listbox

5. Choose CL53 in the Pressure class drop down listbox

6. Choose 20 in the Dimension drop down list box

7. Specify point losses. Add 3 x 90°°°° Bend and 1 xOutlet by clicking on the spin control in the editboxes.

Page 87: Fly_p20

User's Guide FLYPS 2.1 Tutorial •••• 83

Loss calculation. Specification of force main.

If the option multi pumps is selected, the duty points for adifferent number of pumps are shown in a list. Both head lossand total head are shown. The min. and max. values for thenumber of pumps defined in Search criteria determines thenumber of duty points shown in the list.

The loss calculation method used in this case is Hazen-Williams. Calculation methods can be changed in the Setup.For more detailed information about the calculation methodssee Appendix “Head loss calculation methods” on page 92.

8. Click OK to return to the Main window.

When back at the main window, the edit boxes for static head,total head will be filled in and disabled.

Duration diagram specification

The flow variation throughout a 24 hour period is, in this case,substantial. This implies that we have to specify a durationdiagram in order to do an accurate energy consumptioncalculation.

1. In the Tool menu choose Duty analysis or click

the icon in the toolbar. A window for specifyinga duration diagram appears.

Page 88: Fly_p20

84 •••• Tutorial User's Guide FLYPS 2.1

2. Specify maximum flow (peak flow). Enter Max.flow. 2500 GPM. Enter duration. 5%.

3. Specify average flow. Enter Avg. flow. 1500 GPM.Enter duration. 60%.

4. Specify minimum flow. 550 GPM. Enter duration.35%

Duration diagram.

Graph plotting a can be switched off by clicking in the Graphcheckbox.

5. Click OK to return to the Main window.

Pump search based on a given system and with aspecified flow duration diagram

The basic details of a search were described in Tutorial 1, andwill not be discussed here.

The C-type impeller is typical for wastewater applications. Ithas a high efficiency and excellent solids handling properties.In this case, the number of pumps is not specified.

1. Make sure Calculate head based on system isselected.

2. Make sure Use duration diagram is selected.

3. Click to choose impeller type C.

Page 89: Fly_p20

User's Guide FLYPS 2.1 Tutorial •••• 85

4. Set Connection to Parallel.

5. Set Installation to Wet.

6. Check search criteria. To have same results as in thetutorial set search interval to -5% and +5%.

7. Click the Start search button to perform a search.A list of pump alternatives fulfilling therequirements will appear.

8. Sort the result list on total energy consumption.Click on the Total energy column heading.

Results from pump search. Sorted with respect to total energy.

The solution with the lowest specific energy at the maximumflow does not necessarily have to be the one with the lowesttotal energy consumption.

In systems with normal flow distribution and high losses,multiple pump solutions tend to have lower total energy thansolutions with few pumps. This is due to the fact that thelosses decrease when fewer pumps are running.

Page 90: Fly_p20

86 •••• Tutorial User's Guide FLYPS 2.1

Duty point analysis

Always remember to check if the duty point(s) are on thepreferred part of the curve, not power limited, NPSH requiredis OK, etc. When running with multiple parallel pumps it isimportant to check all duty points.

Normally when selecting a pump, alternatives with negativedifference are discarded.

1. Select the best pump (according to total energy) inthe result list. Click on the first pump in the resultlist.

2. In the Tool menu, choose Duty analysis or click

the icon in the toolbar. A window for dutyanalysis appears.

3. Select the Duty condition Tab.

4. Check single pump duty. Decrease No. of pumpsrunning by clicking on the spin control.

Duty analysis one pump running

Page 91: Fly_p20

User's Guide FLYPS 2.1 Tutorial •••• 87

Summary

The objective in this tutorial was to optimize for minimumenergy consumption. By sorting the pump list with respect tospecific energy, we will find a single CP 3201 which canhandle the specified duty point. How much energy is saved byselecting the optimum 2xCP 3127 solution instead of thesingle pump solution? Total energy during 1 year for the 2pump alternative is 61,600 kwh and for the single pumpalternative 74,500 kwh. The energy saved by using 2 pumpsinstead of one is 74,500 - 61,600 = 12,900 kwh. Whether ornot these savings are justifiable can be analyzed with the Lifecycle cost tool.

Page 92: Fly_p20

88 •••• Appendix User's Guide FLYPS 2.1

Appendix

Description of Flygt pump typesPump type Description

BOpen multi vane impeller for clear liquidsand liquids containing finer solids such assand, silt, sediment, etc.).

CClosed single and multi-vane impellers withlarge throughlets primarily designed forsolids bearing liquids of low and mediumabrasiveness.

DVortex impeller and with large throughletprimarily designed for solids bearing liquidsof low and medium abrasiveness.

FOpen screw type cutting impeller for liquidscontaining solids and fibers.

HOpen single and multi-vane high chromeimpellers with abrasion-resistant volute forextra tough applications and very abrasiveliquids.

LShrouded single or multi-channel mixedflow impellers with bowl type diffuser pumpcasing.

MOpen multi-vane impellers with integralgrinder cutter for liquids containing solidsand fibers.

Page 93: Fly_p20

User's Guide FLYPS 2.1 Appendix •••• 89

NWith volute (NP, NS, NT, NZ)Without volute (NL)State of the art, high efficiency, semi-open,self-cleaning, multi-vane impeller andvolute with a patented cleaning/cuttinggroove. Recommended for pumping alltypes of liquids ranging from clean water tohighly solids bearing liquids, such as rawsewage, sludge, fibrous liquids and liquidmanure.

PAxial flow propeller pumps for high flow,low head pumping of clean or lightlycontaminated liquids

Page 94: Fly_p20

90 •••• Appendix User's Guide FLYPS 2.1

Description of Pump Installation types

Installation Description

FSemi permanent, free-standing for hoseor pipe connection.

HSemi permanent, quick connectionsuspended installation with an integralcheck valve.

J Semi permanent installation withswiveling guide bar to permit mixingand pumping.

LSemi permanent installation of pumpinside the vertical discharge column.

PSemi permanent wet pit installationwith pump guided by two guide barswith automatic connection to adischarge connection.

SPortable version with hose coupling orflange for connection to dischargepipeline.

TPermanent dry pit installation withflange connection to suction anddischarge piping (vertical installation).

ZPermanent dry pit installation withflange connection to suction anddischarge piping (horizontalinstallation).

Page 95: Fly_p20

User's Guide FLYPS 2.1 Appendix •••• 91

Description of Toolbar icons

Icon Description

Create Report. Opens a window tospecify the contents of a project report

Setup. Opens a window to change userdefined default values.

Project Information. Opens awindow to enter project information.

Pipe system design. Opens awindow for pipe system design and headloss calculations

Flow duration. Opens a window tospecify a flow duration diagram.

Duty analysis. Opens a window forcurve comparison and duty pointanalysis.

Life cycle cost analysis. Opens awindow for Life cycle cost analysis.

VFD-analysis. Opens a window forvariable speed pumping analysis.

Product data. Opens a window withproduct data for a selected product.

Outline dimensional drawings.Opens a window to view and printoutline dimensional drawings.

Pump station design. Opens awindow for pump station design andsump volume calculations.

Page 96: Fly_p20

92 •••• Appendix User's Guide FLYPS 2.1

Head loss calculation methodsThe loss calculations in FLYPS 2.1 are based on theassumption that the pipes are entirely filled with liquid andthat the liquid has the qualities of clean water.

Density: 62.4 lb/ft³ Kinematic viscosity: 1.2 x 10-5 ft²/s

Description of loss calculation:

Htot = Hs + Hf

Htot = Total head

Hs = Static head

Hf = Head losses

The head losses consist of two parts:

hf= hfl + hpl

where hfl = Friction losses, hpl = Point losses

In FLYPS the friction losses can be calculated with twodifferent methods:

Colebrook-White

h fL

D

V

gfl =2

2

λ is dependent upon the Reynolds number (Re) and theroughness of the pipe.

Re =V D⋅

ν

For turbulent flow (Re > 4000), Colebrook-White's formula is:

12

3 7

2 5

f D f= − ⋅ +

⋅�

��

��

���

���log10

ε.

.

Re

Page 97: Fly_p20

User's Guide FLYPS 2.1 Appendix •••• 93

where; f = Darcy-Weisbach friction factor, ε = absoluteroughness-ft, D = inside diameter of pipe-feet, ν = kinematic,viscosity-ft2/sec.

Hazen-Williams

h LC

gpm

dfl ==== ����

��������

����

��������.

. .

.002083

1001 85 1 85

4 8655

where L = pipe length, including equivalent length for lossthorugh fittings-ft., C = friction factor for Hazen-Williams,

gpm = flow of liquid, d = inside diameter of pipe-inches

Page 98: Fly_p20

94 •••• Appendix User's Guide FLYPS 2.1

Pump search methodologyDuring a duty point search for a pump, the program searchesfor the intersection between the system curve, which runsthrough the requested duty point, and the pump performancecurve. This intersection is the duty point for this pump curve.The distance between the requested and actual duty point iscalculated and compared with the distance to the requestedduty point (see graph below). If this relative distance fallswithin the given search interval, the curve is regarded as a hit.The search interval is given with both a positive and anegative limit. Performance curves where the requested flow isless than 15% of the curve's maximum flow are not included inthe search. This is done so that the program will not suggestpumps where the duty point would be close to the shutoffhead.

• C1 Pump curve

• C2 System curve

• P1 Requested duty point

• P2 Actual duty point (calculated intersection)

• D1 Distance to requested duty point

• D2 Distance between requested and actual dutypoint

Relative divergence between actual and requested duty pointsis calculated as follows:

Rel. div. = D2 / D1

Page 99: Fly_p20

User's Guide FLYPS 2.1 Glossary •••• 95

Glossary

Cd

Decommissioning/Disposal Cost (Cd)

Decommissioning cost includes the restoration of the localenvironment and the disposal of pumps piping and auxiliaryequipment. In the vast majority of cases, the cost of disposingof a pumping system will vary little with different designs.

Cenv

Environmental Cost, Including Disposal of Parts andContamination from Pumped Liquid (Cenv)

The cost of contaminant disposal during the lifetime of thepumping system varies significantly depending on the natureof the pumped product. Certain choices can significantlyreduce the amount of contamination, but usually at anincreased investment cost.

Examples of environmental contamination can include coolingwater and packing box leakage disposal, hazardous pumpedproduct flare-off, used lubricant disposal, contaminated usedparts, such as seals. Costs for environmental inspection shouldalso be included.

Cs

Downtime and Loss of Production Cost (Cs)

The cost of unexpected downtime and lost production is a verysignificant item in the total LCC and can rival the energy costsand replacement parts costs in its impact. The value of lostproduction can dwarf all other elements. Despite the design ortarget life of a pump and its components, there will beoccasions when an unexpected failure occurs. In those cases

Page 100: Fly_p20

96 •••• Glossary User's Guide FLYPS 2.1

where the cost of lost production is unacceptably high, a sparepump may be installed in parallel to reduce the risk. If a sparepump is used, the initial cost will be greater but the cost ofunscheduled maintenance will include only the cost of therepair.

Cm

Maintenance and Repair Cost (Cm)

Obtaining optimum working life from a pump requires regularand efficient servicing. The manufacturer will advise the userabout the frequency and the extent of this routine maintenance.Its cost depends on the time and frequency of service and thecost of materials. The design can influence these costs throughthe materials of construction and components chosen and theease of access to the parts to be serviced.

Co

Operation Cost(Co)

Operation costs are labor costs related to the operation of apumping system. These vary widely depending on thecomplexity and duty of the system. For example, a hazardousduty pump may require daily checks for hazardous emissions,operational reliability, and performance within acceptedparameters. On the other hand, a fully automated non-hazardous system may require very limited supervision.Regular observation of the functioning of a pumping systemcan alert operators to potential losses in system performance.Performance indicators include changes in vibration, shockpulse signature, temperature, noise, power consumption, flowrates, and pressure.

Ce

Energy Cost (Ce)

Energy consumption is often one of the larger cost elementsand may dominate the LCC especially if pumps run more than2000 hours per year. Energy consumption is calculated firstby gathering the data on the pattern of the system output. Ifoutput is steady, or essentially so, the calculation is simple. Ifoutput varies over time, then a time-based usage pattern needsto be established.

Page 101: Fly_p20

User's Guide FLYPS 2.1 Glossary •••• 97

Cin

Installation and Commissioning (Start-up) Cost (Cin)

Installation and commissioning costs include the following:

· Foundations - design, preparation, concrete and reinforcing,etc.

· Setting and grouting of equipment on foundation

· Connection of process piping

· Connection of electrical wiring and instrumentation

· Connection of auxiliary systems and other utilities

· Provisions for flushing or 'water runs'

· Performance evaluation at start-up.

· Training of users and owners.

Cic

Initial Investment Cost (Cic)

Although the initial investment cost will contain purchaseprice of pumps, piping and equipment, it can also include thefollowing items:

· Engineering, e.g. design and drawings, regulatory issues

· The bid process

· Purchase order administration

· Testing and inspection

· Inventory of spare parts

· Auxiliary equipment for cooling and sealing water

Acrobat reader

A program from Adobe used to view outline dimensionaldrawings and other PDF-files. Acrobat Reader is distributedtogether with FLYPS 2.1

Browse

A product is selected in the database by successive list choicesbased on user preferences.

Page 102: Fly_p20

98 •••• Glossary User's Guide FLYPS 2.1

Case

An alternative solution to a task. Can, for exaple, be used tostudy the impact of a different pipe system design. In theprogram, the cases appear as different sets of the Mainwindow. Navigation between Cases is handled by The CaseManager Toolbar.

Export graphs

Graphs showing various curves in the Performance analysisand VFD analysis functions can be saved in WMF-format(Windows Meta File). Graphs stored in WMF format caneasily be inserted as pictures into other document such asMicrosoft Word, Excel and Powerpoint, etc.

Force main

The portion of the piping system which is common to allpumps.

Input power

The electrical power used by the motor.

Internal losses

The frictional and point losses in the station piping in aspecified pipe system. This value is used to create the reducedpump curve.

Minimum active sump volume

The minimum effective volume in the sump between the startand stop level settings, necessary to prevent excessive startsper hour.

Motor efficiency

The ratio of shaft power to electric input power, expressed inpercent (%).

Overall efficiency

The ratio of the liquid power delivered by the pump to theinput power into the motor, expressed in percent.

Page 103: Fly_p20

User's Guide FLYPS 2.1 Glossary •••• 99

Performance curve

A printout of a complete pump curve with extensive productdata and various curves in a standardized layout. The curvesinclude: head, input and shaft power, efficiency and NPSH-required.

Point loss

A concentrated friction or shock loss, created by a pipe fitting,valve, or similar.

Present day value

The algebraic sum of the disocunted positive and negativefuture value of goods. Often referred to as present worth.

Pump efficiency

The ratio of the liquid power delivered by the pump to thepump shaft power, expressed in percent.

Pump search methodology

The program searches for pumps that fulfill the search criteria,and with a performance curve close to the requested dutypoint.

Radio button

Mutually exclusive “push button”; only one button can beselected at any given time.

Rated power

The maximum shaft power that an electric motor can sustainfor its designated duty conditions, when operated withnameplate voltage and frequency.

Search interval

Flow interval along the system curve, as a percentage of theduty point.

Shaft Power

The mechanical output power from an electric motor, usuallyexpressed in HP.

Page 104: Fly_p20

100 •••• Glossary User's Guide FLYPS 2.1

Specific Energy

The energy used to pump a unit volume for a given pump in agiven system, often expressed in kilowatt hours per milliongallons (kWh/Mg).

Spin controls

The up and down arrows shown to the right of a field of entry.By clicking the up arrow, the value in the field increases,consequently the down arrow decreases the value.

System curve

The system characteristics are described by the System curve.The system curve shows the total discharge head (T.D.H.) inthe pipe system as a function of the flow.

Throughlet size

The (clear) open circular, rectangular or elliptical internalpassage through the impeller, which indicates the largestdiameter solid that may be passed.

Total efficiency

The ratio of the liquid power delivered by the pump to theinput power into the VFD, expressed in percent. This term isonly applicable to pumps that are operated through a variablespeed drive.

Total input power

The electrical power into the VFD for the total number ofpump selected. This term is only applicable to pumps that areoperated through a variable speed drive.

User profile

A combination of user defined settings stored under a name.Enables the user to change all settings in one operation.