Technical DataTechnical Data
•Premium accuracy and measurement techniques:Guaranteedforallpowerqualityparameters,withIEC61000-4-30ClassAmeasurementsystems
•Quick and reliable configuration:PDAwire-less“frontpanelinterface”providesawindowintowhattheinstrumentisrecording,eveninawkwardtestlocations
•Threshold-free setup: ApplythresholdsafterdataiscollectedwithFlukePowerAnalyzeSoftware
•Captures everything: Cross-channelandcurrenttriggeringcaptureeverymeasurement,oneverychannel,everytime
•Intuitive PC software: Easilyanalyzedataandgeneratereports
Capture every measurement, every event, on every cycle, all the time with the Fluke 1750 Power Recorder. Unprecedented accuracy and resolution provide complete visibility into your distribution system.
Fluke 1750Three-Phase Power Recorder
Never miss capturing a disturbance - with the exclusive threshold-free measurement system, it’s automatic.
•Plug and play: Setupinminuteswithself-identifyingcurrentprobesandsingle-leadvoltageconnections
•No need to reconnect wires: SwapchannelsinternallywiththewirelessPDAorPCwhenconnectionsarenotcorrect
•Measure every parameter:voltageandcurrentonthreephases,neutral,andground
•5 MHz, 8000 Vpk waveform capture:Getadetailedpictureofeventheshortestevents
•Quickly retrieve data:WithincludedSDmemo-rycardorviathe100BaseThigh-speedEthernetconnection
�FlukeCorporationFluke1750Three-PhasePowerRecorder
Applications Long-term analysis:Uncoverhard-to-findorintermittentissuesPower quality surveys:Quantifypowerqualitythroughoutafacility,documentingresultswithprofessionalreportsQuality of service compliance:ValidateincomingpowerqualityattheserviceentranceSemi-permanent monitoring:Monitorcriticalequipment,capturingpowerqualityeventstocorrelatewithequipmentmalfunction
Easy to use Therecorderautomaticallydetects,scales,andpowerscurrentprobeswithoutneedingbatteries.Requiringonlysingle-leadvoltageconnectionsenablessafeandquicksetups.Oncepowerisappliedtheinstrumentautomaticallybeginsrecord-ingandLEDsgiveyouassurancethattherecorderispoweredupandsignalsarewithinrange–nomoreuncertaintythatdataisbeingrecorded.TheFluke1750hasanexclusivecapturealgorithmwhichmakescertainalleventsarecapturedwith-outthetedioussetupsandblindspotsassociatedwiththresholddrivenequipment.
ThePDAwirelesslyinterfaceswiththerecorder,allowingquicksetupandverificationwithwave-formdisplays,meterscreens,andphasordiagrams.Thebuilt-inwirelesstechnologyallowsyoutocontrolmultipleinstrumentsfromadistanceeasily,withouttheneedforalaptopcomputer(laptopscanalsobeusedwhendesired).
Viewmeasurementsreal-timewithwirelessPDAinterface.
Configurationsaresimplewithwiringdiagramstoguideyou.
Noneedtoreconnectwires—swapchan-nelsinternallyusingthePDAinterface.
3FlukeCorporationFluke1750Three-PhasePowerRecorder
Comprehensive power system data Everycycleoneverychannelissimultaneouslysampledprovidingcompleteanalysisofpowerquality,harmonics,powerandenergy.Cross-channelcurrentandvoltagetriggeringcaptureseventdataonallinputchannelssimultaneously,nomatterwhichchanneltriggeredtheevent.Whenperiodicanalysisofthewaveformmaybeneeded,theSnapshotmodecaptureswaveformsatuser-definedintervals.Evendcsignalscanberecorded!
Powerful data managementDataisautomaticallystoredontheinternalflashmemorythatcanstorerecordsforoveramonthwithoutcompressionoroverwriting.Dataisretrievedviaoneoftwoquickandeasyoptions:downloadthedataontotheincludedSDmemorycardwithoutusingyourlaptop,ortransferdirectlytoyourcomputerviaEthernet,usingTCP/IPprotocol.
Eventscanbedisplayedagainstavarietyoftolerancecurves.
Voice,data,andpictureannotationscanbemadeviathePDAtoflagimportantpointsinthedatastream.Imaginebeingabletoflaginyourrecordeddatawhenatransferswitchwasoperated,orloadchangesweremade.
FullFFToneachchanneltothe50thharmonic.
Displaymultipleparameterssimultaneouslyononegraph. Full-featuredpowermeterdisplayforeachchannelandtotals.
4FlukeCorporationFluke1750Three-PhasePowerRecorder
IEC61000-4-30ClassAmeasurementsystemsprovidetheconfidencethatallparametersaremeasuredandcalculatedconsistentlywithinternationalstandards.
Designedtohelpprotectyouandyourequipment,theFluke1750Three-PhasePowerRecorderandaccessoriesareallcertifiedtomeetthestringentsafetystandardsforusein600VCATIVand1000VCATIIIenvironments.TheyarethefirsttoolsoftheirkindtocarrytheCATIVratingand,therefore,canbeusedformostpowerconnectionsandforalloutletsinalow-voltagepowerdistributionsystem.
View data the way you want ThenewFlukePowerAnalyzesoftwarerevo-lutionizesyourabilitytoanalyzedata.Noneedtoworryaboutthresholds–withFlukePowerAnalyze,thresholdscanbemodifiedafterthedataisrecorded!Andtheeasy-to-useuserinterfacewilldisplayvoltageasaphase-to-phaseorphase-to-neutralreading.
Applythresholdstodataaftercollectionusingavarietyofstandardorcustomizedtemplates.
SimplifiedreportwriterfeatureincludedinFlukePowerAnalyze.
All the latest power quality standards are built-in
600 V CAT IV and 1000 V CAT III safety rating
5FlukeCorporationFluke1750Three-PhasePowerRecorder
Optional Accessories
FlukePowerQualityCurrentTransformersarespeciallyde-signedtoworkseamlesslywithFlukePowerQuality/RPMFullDisclosure™PowerMonitors.AllClamp-onandFlexi-CT’sarematchedtotakefulladvantageofyourinstrument’sabilitytosetscalefactorsforaccuratereadings.
Model No. CT Type Current Range AccuracyFrequency Response Jaw Opening
3005R Clamp-On 0.01Ato5A 1%RDG±0.5%FS 5kHz �cm(.78in)dia.3014 Clamp-On 0.1Ato40A 1%RDG±0.1%FS 5kHz �cm(.78in)dia.31�0R Clamp-On 0.5Ato�00A 1%RDG±0.3%FS 5kHz �cm(.78in)dia.3140R Clamp-On �Ato400A �%RDG±0.04A �0kHz 3.�cm(1.�5in)dia.3100R Clamp-On 1Ato1000A 1%RDG±0.05%FS 5kHz 5cm(�in)dia.3300 Clamp-On 10Ato3000A �%RDG±0.05%FS 5kHz 9x11cm(3.5x4.5in)
Model No. CT Type Current Range AccuracyFrequencyResponse Probe Length
3110/RPM Flexi-CT �Ato100A 1%RDG±0.5%FS 7kHz 60cm(�4in)311�/RPM Flexi-CT �Ato100A 1%RDG±0.5%FS 7kHz 1�0cm(48in)3�10/RPM Flexi-CT �0Ato1000A 1%RDG±0.15%FS 7kHz 60cm(�4in)3�1�/RPM Flexi-CT �0Ato1000A 1%RDG±0.15%FS 7kHz 1�0cm(48in)3310/RPM Flexi-CT 100Ato5000A 1%RDG±0.15%FS 7kHz 60cm(�4in)331�/RPM Flexi-CT 100Ato5000A 1%RDG±0.15%FS 7kHz 1�0cm(48in)
Model No. CT Type Current Range AccuracyFrequency Response Jaw Opening
3583R Split-CoreCT 0.01Ato10A 1%RDG±0.5%FS 5kHz 1cm(.437in)3584R Split-CoreCT 0.1Ato40A 1%RDG±0.5%FS 5kHz 1cm(.437in)3585R Split-CoreCT 0.5Ato100A 1%RDG±0.5%FS 5kHz 1cm(.437in)
6FlukeCorporationFluke1750Three-PhasePowerRecorder
Voltage probes
3602/RPM Battery Clip Probe •Setof5batterycliptypeprobes•Gripsconductorsupto0.9cm
(.375in)wide•Insulated,nickel-platedprobe
3605/RPM Stud Type Probe •5syringe-actionvoltageprobes•Threadedcontactforstuds/
screwsupto0.9cm(.375in)wide
3606/RPM Screw on Probe •5screwontypevoltageprobes•Interchangeablethreadedcon-
tactsfor3/8inand1/�instudsandscrews
3607/RPM Bus Bar Probe •5syringe-actionF-typeprobes•Adjustablejawforconductors
upto0.9cm(.375in)wide
3608/RPM Plunger Type Probe •5syringe-actionvoltageprobes•Crocodilejawforconductorsup
to0.9cm(.375in)wide•Plungerstyle,safetygrip
operationwithinsulatedjaws
Cases
CS1750/1760 Carrying Bag •Ruggedcanvasbagwithheavy
dutyzipperandstraps•Waterresistantwithpockets
foraccessories
1750/CASE Transit Case •Ruggedwatertighttransitcase
withrollers
Miscellaneous
1750/MC •AdditionalSDMemoryCard
forFluke1750
1750/SEAT-L •FlukePowerAnalyze-
AdditionalSEATLICENSE•Oneadditionallicenseforin-
stallationononeadditionalPC
1750/SITE-L •FlukePowerAnalyze-
AdditionalSITELICENSE•Sitelicenseforinstallation
onunlimitedPCs
4006 Security Cable •1.8m(6ft)loopedlockable
steelcableforsecuringmonitor
3602
3605
3606
3607
3608
7FlukeCorporationFluke1750Three-PhasePowerRecorder
Specifications for the System: Recorder and Power Analyze Software
General
Power quality measurement standards Conformance IEC61999-1-4Class1,IEC61000-4-30ClassAorBdependingonmeasurementfunction,
IEEE519,IEEE1159,IEEE1459Clock/calendar Leapyears,�4-hourclockReal-time clock accuracy Notmorethan±1s/dayInternal memory capacity for data Atleast1GBMaximum recording period Atleast31daysMeasurement time control AutomaticMaximum number of events LimitedonlybythesizeoftheinternalmemoryPower requirements 100to�40Vrms±10%,47-63Hz,40WOperating time during interruptions(internalUPSoperation)
5minutesperinterruption,60minutestotaloperatingtimewithoutrecharging
Dimensions �15mmx310mmx35mm(8.5inx1�.�inx3.5in)Mass (weight) 6.3kg(14lb)
InputMeasurement types OnePhasePlusNeutral,OnePhaseITNoNeutral,OnePhaseSplitPhase,ThreePhaseWye,Three
PhaseDelta,ThreePhaseIT,ThreePhaseHighLeg,ThreePhaseOpenLeg,�ElementDelta,�1/�ElementWye
Input channels Voltage:4channels,ac/dcCurrent:5channels
Voltage channels Inputresistance:�MΩInputcapacitance:<�0pF
Current input characteristics �Vrms=fullscale,1MΩInputImpedanceforferroCTs,lowimpedanceforFlexi-CTsMeasuring method Simultaneousdigitalsamplingofvoltageandcurrent.DigitalPLLsynchronizedsampling,internal
frequencyreferenceusedduringvoltagedrops.
Synchronization and samplingPLL-synchronization source ThePLLsynchronizestotheA-Nvoltageforwyepowertypes,andtotheA-Bvoltagefordelta
powertypes.Alllistedpowertypescanbecharacterizedaseitherwyeordelta.PLL lock range 4�.5to69HzSampling frequency Voltageandcurrent:�56samples/cycle
Inter-harmonicsperIEC61000-4-7:�560points/10cycles(50Hz),307�points/1�cycles(60Hz)TransientVoltage:5MHz
A/D resolution Voltageandcurrent:�4bitsTransientvoltage:14bits
Voltage and current measurementsVoltage measurement range ACvoltage:1000Vrms±10%overrange
DCvoltage:±1000V+10%overrangeVoltage crest factor 3orlessCurrent measurement range DependsoncurrentprobeusedCurrent crest factor 4orless
8FlukeCorporationFluke1750Three-PhasePowerRecorder
Voltage and current measurement accuracy
RMS voltageMeasurement type Truermscalculatedcontinuously:everycycle,every1/�cycle,and
every10or1�cyclesat50or60Hzrespectively,asrequiredbyIEC61000-4-30.Measurement uncertainty AC:±0.�%reading±0.1%fullscale,above50Vrms
DC:±0.5%reading±0.�%fullscale,above50VdcRMS currentMeasurement type Truermscalculatedcontinuously:everycycle,every1/�cycle,and
every10or1�cyclesat50or60Hzrespectively,asrequiredbystandardsMeasurement uncertainty Ferromagnetic Clamps:±(0.1%fullscale+0.�%reading+currentsensoraccuracy),
validfor5%to100%ofcurrentsensorrangeFlexible Current Probes:±(0.1%fullscale+0.5%reading+currentsensoraccuracy),validfor5%to100%ofcurrentsensorrange
Transient voltage (impulse)Measurement type WaveshapesamplingFull scale 8000VpkSample resolution �00nSMeasurement uncertainty ±5%reading±�0V(testparameters:1000Vdc,1000Vrms,100kHz)
Dip (Sag) and Swell Measurements
Voltage swell (rms swell)Measurement type Truerms(onecyclecalculationbyoverlappingeachhalfcycle-voltagebetweenlinesismeasured
for3P3Wlinesandphasevoltageismeasuredfor3P4Wlines)Displayed data AmplitudeanddurationofswellMeasurement uncertainty Sameasrmsvoltage
Voltage dip (rms sag)Measurement type Truerms(onecyclecalculationbyoverlappingeachhalfcycle-voltagebetweenlinesismeasured
for3P3Wlinesandphasevoltageismeasuredfor3P4Wlines)Displayed data AmplitudeanddurationofdiporinterruptionMeasurement uncertainty Sameasrmsvoltage
Voltage dropout (interruption)Measurement type Sameasvoltagedip
Power Measurements
Calculated per IEEE1459 for best performance when distortions existMeasurement type Truermscalculatedcontinuously:everycycle,andevery10or1�cyclesat50or60Hzrespectively,
asrequiredbystandardsMeasurement accuracy +/-(voltageuncertainty+currentuncertainty+currentprobeuncertainty)FrequencyMeasurement range 4�.5to69HzMeasurement source SameasPLLsynchronizationsourceMeasurement accuracy ±10mHz(10to110%ofrange,withsinewave)
Power factorMeasurement range 0.000to1.000Measurement accuracy ±1digitfromthecalculationofeachmeasuredvalue(±3digitsfortotal)
Displacement power factorMeasurement method CalculatedfromthephasedifferencebetweenvoltagefundamentalandcurrentfundamentalMeasurement range -1.000(leading)to+1.000(lagging)Measurement accuracy ±0.5%reading±�%fullscale±1digit
Voltage unbalance and phase sequenceMeasurement method Positivesequencevoltagedividedbynegativesequencevoltage,perIEC61000-4-30
Harmonic voltage and currentAnalysis window rectangular
9FlukeCorporationFluke1750Three-PhasePowerRecorder
Analysis order 1stto50thorderMeasurement accuracy Voltage/Current:1stto�0thorders:±0.5%reading±0.�%fullscale,�1stto50thorders:±1%
reading±0.3%fullscale(currentsensoraccuracymustbeincludedforcurrentandpower)Measurement method IEC61000-4-7
Inter-harmonic voltage and current (intermediate harmonics)Analysis window rectangularAnalysis orders 1.5to49.5thorderMeasurement method IEC61000-4-7
External Interface Specifications
LAN interfaceConnector RJ-45Speed and type 10/100Base-T,autoMDIXCommunications protocol TCP/IPoverEthernet
Wireless controller interfaceConnection wireless(�.4GHzradio)Speed upto700kbit/secondCommunications protocol BluetoothSPP
Environmental and safety specificationsOperating environment Indoorsorincoveredareaoutdoors,upto�000maltitudeStorage temperature and humidity -�0°Cto50°C,80%RHmax,non-condensingOperating temperature and humidity 0°Cto40°C,80%RHmax,non-condensing
Maximum rated working voltageVoltage terminals 1100VrmsVoltage durability 5550Vrmsacfor1minute,betweenvoltageinputterminals,voltageinputterminalsandcurrent
probes,andvoltageinputterminalsandcase(50/60Hz,1mAsensecurrent)Enclosure protection IP30(perEN605�9)
Standards conformanceEMC EN613�6-1:1997+A1:1998ClassA
EN61000-3-�:1995+A1:1998+A�:1998EN61000-3-3:1995
Safety EN61010-1�ndEdition;�000Voltageinputunit: ContaminationLevel�,OvervoltageCategory1000VCATIII,600VCATIV(anticipatedovervoltage:8000V)
10FlukeCorporationFluke1750Three-PhasePowerRecorder
Fluke CorporationPOBox9090,Everett,WAUSA98�06
FlukeEuropeB.V.POBox1186,560�BDEindhoven,TheNetherlands
Formoreinformationcall:IntheU.S.A.(800)443-5853orFax(4�5)446-5116InEurope/M-East/Africa+31(0)40�675�00orFax+31(0)40�675���InCanada(800)36-FLUKEorFax(905)890-6866Fromothercountries+1(4�5)446-5500orFax+1(4�5)446-5116Webaccess:http://www.fluke.com
©�006FlukeCorporation.Allrightsreserved.Windows®isaregisteredtrademarkofMicrosoftCorporation.Specificationssubjecttochangewithoutnotice.PrintedinU.S.A.1/�007�4�8�01D-EN-NRevD
Fluke. Keeping your world up and running.™
Ordering information
Fluke-1750 Three-Phase Power Recorder
Includes: •1750acquisitionunit•PDAwireless“frontpanelinterface”andchargerpower
plugadapters•4-400Acurrentprobes(3140)•5testleadsandclips•SDmemorycard•FlukePowerViewandFlukePowerAnalyzesoftware•Powercordwithinternationalplugset•Ethernetcable•Colorlocalizationset•PrintedGettingStartedmanual•ProductCDwithsoftwareandusersmanualPDF
Flukeoffersafullsuiteofpowerqualitytesttoolstolocate,predict,preventandtroubleshootpowerproblems.•Handheldtroubleshootersforinstantanalysis•Ready-to-usepowerloggers•Comprehensivepowerqualityrecorders•PowercalibratorsandstandardsbackedbyFluke
metrologyexpertise
TheFlukepowerqualitysetofproductsoffersthehighestlevelofperformanceandmaintainstheFlukepromiseofruggedandreliabletesttools.
Tolearnmore,contactPowerQualitycustomersupport,inSeattle,WA,[email protected].