Flammables Bulk Storage Standard Draft r9

29
Date: 22 Jan 2015 Page 1 of 29 Revision:Final Bulk Storage of Flammable and Combustible Liquids Standard PS-ST-001 Global Supply Chain PROCESS SAFETY WARNING – If Printed this document becomes an UNCONTROLLED Copy I. POLICY This standard outlines the Ecolab corporate requirements for the safe bulk storage of flammableand combustible liquids in bulk storage systems. The standard is based on NFPA 30 Flammable and Combustible Liquids Code. NFPA 30 provides greater detail and guidance and should be referred to for interpretation of this standard. 1. Requirements in this document are identified as follows: a. Mandatory requirements are identified by the bolded terms shall” or “must”; b. Recommendations, identified by the terms “recommended” or “should”, are not mandatory but preferred options. Each site is expected to follow recommendations where possible; and c. Guidance, identified with the terms “suggested” or “may”, is given where a specific approach cannot be defined or where multiple options are acceptable. 2. These requirements apply to all new construction and modifications to existing facilities. 3. These requirements do not apply retroactively to existing situations unless identified in the following manner: *** (Applies retroactively at all Ecolab sites)***. 4. It is recognized that standards cannot cover all possible situations and good engineering judgment may dictate alternative arrangements. Alternative arrangements for mandatory requirements must be approved, see PS-XX-NNN: Exception Process.

description

normas malla a tierra resintos peligrosos

Transcript of Flammables Bulk Storage Standard Draft r9

Page 1: Flammables Bulk Storage Standard Draft r9

Date: 22 Jan 2015 Page 1 of 18 Revision:Final

Bulk Storage of Flammable and Combustible Liquids Standard

PS-ST-001Global Supply Chain

PROCESS SAFETY WARNING – If Printed this document becomes an UNCONTROLLED Copy

I. POLICY

This standard outlines the Ecolab corporate requirements for the safe bulk storage of flammableand combustible liquids in bulk storage systems. The standard is based on NFPA 30 Flammable and Combustible Liquids Code. NFPA 30 provides greater detail and guidance and should be referred to for interpretation of this standard.

1. Requirements in this document are identified as follows:a. Mandatory requirements are identified by the bolded terms “shall” or “must”;b. Recommendations, identified by the terms “recommended” or “should”, are

not mandatory but preferred options. Each site is expected to follow recommendations where possible; and

c. Guidance, identified with the terms “suggested” or “may”, is given where a specific approach cannot be defined or where multiple options are acceptable.

2. These requirements apply to all new construction and modifications to existing facilities.

3. These requirements do not apply retroactively to existing situations unless identified in the following manner: *** (Applies retroactively at all Ecolab sites)***.

4. It is recognized that standards cannot cover all possible situations and good engineering judgment may dictate alternative arrangements. Alternative arrangements for mandatory requirements must be approved, see PS-XX-NNN: Exception Process.

5. In the event of a conflict with government or local standards, codes, or regulations, then the more stringent of the two (regulation or the Ecolab standard) must be followed.

6. In the event of a conflict with any legacy company standard, guidance document or commonly accepted practice, the requirements in this standard must be followed.

II. SCOPE

This standard applies to the bulk storage of flammable and combustibleliquids at all Ecolab and Nalco Champion manufacturing, processing, blending, and storage locations globally.

Storage, processing, handling and use of Class II and Class III liquids heated to within 17 degrees C of their flash point shall be treated as Class I liquids unless an

Page 2: Flammables Bulk Storage Standard Draft r9

Date: 22 Jan 2015 Page 2 of 18 Revision:Final

Bulk Storage of Flammable and Combustible Liquids Standard

PS-ST-001Global Supply Chain

PROCESS SAFETY WARNING – If Printed this document becomes an UNCONTROLLED Copy

engineering evaluation conducted in accordance with NFPA 30 justifies following the requirements for another liquid class.

III. DEFINITIONS

A. Flammable and Combustible Liquids Classification

1. Flammable liquids shall be classified as Class I liquids and further sub classified according to the following

a) Class IA Liquid- Any liquid that has a flash point below 22.8 deg C and a boiling point below 37.8 deg C

b) Class IB Liquid- Any liquid that has a flash point below 22.8 deg C and a boiling point above 37.8 deg C

c) Class1C Liquid- any liquid that has a flash point at or above 22.8 deg C but below 37.8 deg C

2. Combustible liquids shall be classified in accordance with the following

a) Class II liquids- Any liquid having a flash point at or above 37.8 deg C and below 60 deg C.

b) Class IIIA Liquids- any liquid having a flash point at or above 60 deg C but below 93 deg C

c) Class IIIB Liquid- Any liquid having a flash point at or above 93 deg C.

3. Class II and Class III liquids heated to within 17 deg C of their flash point shall be treated as Class I liquids.

4. For further clarification refer to figure 1.

Page 3: Flammables Bulk Storage Standard Draft r9

Date: 22 Jan 2015 Page 3 of 18 Revision:Final

Bulk Storage of Flammable and Combustible Liquids Standard

PS-ST-001Global Supply Chain

PROCESS SAFETY WARNING – If Printed this document becomes an UNCONTROLLED Copy

Figure 1

B. Bulk Storage Systems-Bulk storage systems are defined as fixed tanks that exceed 230 L in capacity, portable tanks that exceed 2500 L in capacity or intermediate bulk containers that exceed 3000 L

C. Flash point- The minimum temperature of a liquid at which sufficient vapour is given off to form an ignitable mixture with air, near the surface of the liquid or within the vessel used.

D. Boiling point- the temperature at which the vapour pressure of the liquid equals the surrounding atmospheric pressure.

E. Unstable Liquid-Aliquid that, in the pure state oras commercially produced or transported, will vigorouslypolymerize, decompose, undergo condensation reaction or become self-reactive under conditions of shock, pressure or temperature.

F. Boil Over-An event in the burning of certain oils in anopen-top tank when, after a long period of quiescent burning,there is a sudden increase in fire intensity associated with expulsion of burning oil from the tank.

Page 4: Flammables Bulk Storage Standard Draft r9

Date: 22 Jan 2015 Page 4 of 18 Revision:Final

Bulk Storage of Flammable and Combustible Liquids Standard

PS-ST-001Global Supply Chain

PROCESS SAFETY WARNING – If Printed this document becomes an UNCONTROLLED Copy

G. Protection for Exposures-Fire protection for structureson property adjacent to liquid storage that is provided by(1) a public fire department or (2) a private fire brigade maintainedon the property adjacent to the liquid storage, either ofwhich is capable of providing cooling water streams to protectthe property adjacent to the liquid storage.

H. Stray Current- The portion of a total electric current that flows through paths other than the intended circuit.

IV. REQUIREMENTS

A. Location

1. Storage tanks storing Class I, Class II and Class IIIA stable liquids at pressures less than 2.5 psi (17.2 kPa) relative to property lines, public ways and important buildings must be sited

a) 10 ft. (3 m)from property line and 2.5 ft.(.76 m) from important structures for tanks less than 30,000 usg (113 m3)assuming that the structures are protected by either a local fire department or site fire protection systems and the tank has either an approved inerting system or a foam suppression system.

b) 20 ft.(6 m) from property line and 5 ft. (1.4 m) from important structures for tanks less than 30,000 usg(113 m3 )assuming that the structures are protected by either a local fire department or site fire protection systems and no fire protection systems exist for the tank.

c) 40 ft.(12 m) from property line and 10 ft.(3 m) from important structures for tanks less than 30,000 usg(113 m3) assuming that the structures are not protected by either a local fire department or site fire protection systems and no fire protection systems exist for the tank.

2. For stable liquid storage systems where the tank internal pressure exceeds 2.5 psi (17.2 kPa) or are equipped with emergency venting that will permit pressures to exceed 2.5psi (17.2 kPa), the separation distance for protected tanks increase to 30 ft (9.1 m) . from the property line including the opposite side of a public way and 25 ft (7.6 m) from the nearest side of any public way or the nearest important building on the same property. For unprotected exposures the distances increase to 50ft (15 m) from the

Page 5: Flammables Bulk Storage Standard Draft r9

Date: 22 Jan 2015 Page 5 of 18 Revision:Final

Bulk Storage of Flammable and Combustible Liquids Standard

PS-ST-001Global Supply Chain

PROCESS SAFETY WARNING – If Printed this document becomes an UNCONTROLLED Copy

property line and 25 ft (7.6 m) from the nearest side of any public way or the nearest important building on the same property

3. For tanks less than 30,000 USG (113 m3) storing Class IIIB liquids the minimum separation distances relative to property lines, public ways and important buildings must be 10 ft.(3 m) from property lines and 5 ft. (1.5 m)from important structures.

4. The minimum shell to shell spacing distances for above ground storage tanks must be 1/6 the sum of all adjacent tank diameters but not less than 3 ft.(.9 m)

5. For tanks larger than 30,000 USG (113 m3), tanks storing LP Gas, tanks storing boil over liquids, tanks storing unstable liquids and tanks storing Class IIIB liquids refer to NFPA 30 for specific separation distances and specific requirements.

B. Materials of Construction

1. For the storage of all flammable and combustible Class I, Class II and Class IIIA liquids, tanks shall be of steel or other approved noncombustible material .The materials of construction for tanks and theirappurtenances shall be compatible with the liquid to bestored. In case of doubt about the properties of the liquid tobe stored, the supplier, producer of the liquid, or other competent authority shall be consulted. *** (Applies retroactively at all Ecolab sites)***

2. Tanks shall be permitted to have combustible or noncombustible linings. The selection, specification, and type of lining material and its required thickness shall be based on the properties of the liquid to be stored. When there is a change in the characteristics of the liquid to be stored, thecompatibility of the lining and the liquid shall be verified.

3. Tanks shall be permitted to be constructed of combustiblematerials when approved. Tanks constructed of combustiblematerials shall be limited to any of the following:

a) Underground installationb) Use where required by the properties of the liquid stored*c) Aboveground storage of Class IIIB liquids in areas not exposed to a spill or leak of Class I or Class II liquid

Page 6: Flammables Bulk Storage Standard Draft r9

Date: 22 Jan 2015 Page 6 of 18 Revision:Final

Bulk Storage of Flammable and Combustible Liquids Standard

PS-ST-001Global Supply Chain

PROCESS SAFETY WARNING – If Printed this document becomes an UNCONTROLLED Copy

d) Storage of Class IIIB liquids inside a building protected byan approved automatic fire-extinguishing system.

*Note: OSHA 1910.106 prohibits the above ground storage of all flammable and combustible liquids (Class I, Class II and Class IIIA) in plastic tanks in the US.

C. Design Standards for Storage Tanks

1. Atmospheric tanks shall be designed and constructedin accordance with recognized engineering standards.Atmospheric tanks that meet any of the following standards shallbe deemed as meeting the requirements for the storage system design.

a) API Standard 650, Welded Steel Tanks for Oil Storageb) UL 58, Standard for Steel Underground Tanks for Flammable and Combustible Liquidsc) ANSI/UL 80, Standard for Steel Tanks for Oil-Burner Fuelsand Other Combustible Liquidsd) ANSI/UL 142, Standard for Steel Aboveground Tanks forFlammable and Combustible Liquidse) UL 1316, Standard for Glass-Fiber Reinforced Plastic UndergroundStorage Tanks for Petroleum Products, Alcohols, and Alcohol-Gasoline Mixturesf) ANSI/UL 1746, Standard for External Corrosion ProtectionSystems for Steel Underground Storage Tanksg) UL2080, Standard for Fire Resistant Tanks for Flammable andCombustible Liquidsh) ANSI/UL 2085, Standard for Protected Aboveground Tanksfor Flammable and Combustible Liquidsi) API Specification 12B, Bolted Tanks for Storage of Production Liquidsj) API Specification 12D, FieldWelded Tanks for Storage of Production Liquidsk) API Specification 12F, Shop Welded Tanks for Storage of Production Liquids*Note: API 12B,12D and 12F shall only be used for the storage of crude petroleum at oil producing sites.

2. Low-pressure tanks shall be designed and constructedin accordance with recognized engineering standards.Low-pressure tanks that meet either of

Page 7: Flammables Bulk Storage Standard Draft r9

Date: 22 Jan 2015 Page 7 of 18 Revision:Final

Bulk Storage of Flammable and Combustible Liquids Standard

PS-ST-001Global Supply Chain

PROCESS SAFETY WARNING – If Printed this document becomes an UNCONTROLLED Copy

the following standardsshall be deemed as meeting the requirements of this standard

a) API 620, Recommended Rules for the Design and Constructionof Large, Welded, Low-Pressure Storage Tanksb) ASME Code for Unfired Pressure Vessels, Section VIII, Division 1

3. Tanks with storage pressures above a gauge pressureof 15 psi (100 kPa) shall be designed and constructed inaccordance with recognized engineering standards. Pressurevessels that meet any of the following standards shall bedeemed as meeting the requirements of this standard

a) Fired pressure vessels shall be designed and constructedin accordance with Section I (Power Boilers), or SectionVIII, Division 1 or Division 2 (Pressure Vessels), as applicable,of the ASME Boiler and Pressure Vessel Code.b) Unfired pressure vessels shall be designed and constructedin accordance with Section VIII, Division 1 orDivision 2, of the ASME Boiler and Pressure Vessel Code.

D. Normal Tank Venting

1. Storage tanks shall be vented to prevent the development of vacuum or pressure that can distort the tank or exceedthe rated design pressure of the tank when the tank isfilled or emptied or because of atmospheric temperaturechanges. Normal vents shall be located above the maximumnormal liquid level.*** (Applies retroactively at all Ecolab sites)***

2. Normal venting shall be provided for tanksand each primary compartment of a compartmented tank.*** (Applies retroactively at all Ecolab sites)***

3. Normal vents shall be sized in accordance with eitherAPI Standard 2000, Venting Atmospheric and Low-PressureStorage Tanks, or another approved standard. Alternatively, thenormal vent shall be at least as large as the largest filling orwithdrawal connection, but in no case shall it be less than1.25 in. (32 mm) nominal inside diameter.*** (Applies retroactively at all Ecolab sites)***

4. Atmospheric storage tanks shall be vented to preventthe development of vacuum or pressure above the 1.0 psi(6.9 kPa) maximum operating pressure.*** (Applies retroactively at all Ecolab sites)***

5. Low-pressure tanks and pressure vessels shall bevented to prevent the development of pressure or vacuum thatexceeds the rated design pressure of the tank or vessel. Meansshall also be provided to prevent overpressure

Page 8: Flammables Bulk Storage Standard Draft r9

Date: 22 Jan 2015 Page 8 of 18 Revision:Final

Bulk Storage of Flammable and Combustible Liquids Standard

PS-ST-001Global Supply Chain

PROCESS SAFETY WARNING – If Printed this document becomes an UNCONTROLLED Copy

from any pumpdischarging into the tank or vessel when the pump dischargepressure can exceed the design pressure of the tank or vessel.*** (Applies retroactively at all Ecolab sites)***

6. If any tank or pressure vessel has more than one fillor withdrawal connection and simultaneous filling or withdrawalcan be made, the vent size shall be based on the maximum possible simultaneous flow.*** (Applies retroactively at all Ecolab sites)***

7. For tanks equipped with vents that permit pressuresto exceed a gauge pressure of 2.5 psi (17 kPa) and for lowpressure tanks and pressure vessels, the outlet of all vents andvent drains shall be arranged to discharge in a manner thatprevents localized overheating of or flame impingement onany part of the tank, if vapors from the vents are ignited.*** (Applies retroactively at all Ecolab sites)***

8. Tanks and pressure vessels that store Class IA liquidsshall be equipped with venting devices that are closed, exceptwhen venting under pressure or vacuum conditions.*** (Applies retroactively at all Ecolab sites)***

9. Tanks and pressure vessels that store Class IB andClass IC liquids shall be equipped with venting devices or withlisted flame arresters. When used, vent devices shall be closed,except when venting under pressure or vacuum conditions.*** (Applies retroactively at all Ecolab sites)***

10. Tanks of 3000 barrels (bbl) [126,000 gal (475 m3)]capacity or less that store crude petroleum in crude-producingareas and outside aboveground atmospheric tanks of less than1000 gal (3785 L) capacity that contain other than Class IAliquids shall be permitted to have open vents.

11. Flame arresters or venting devices required in points 8 and 9 above shall be permitted to be omitted on tanksthat store Class IB or Class IC liquids where conditions aresuch that their use can, in case of obstruction, result in damageto the tank.

12. Piping for normal vents shall be designed in accordance with section I of this standard.

E. Emergency Relief Venting

1. Every aboveground storage tank shall have emergencyrelief venting in the form of construction or a device ordevices that will relieve excessive internal pressure caused byan exposure fire.*** (Applies retroactively at all Ecolab sites)***

Page 9: Flammables Bulk Storage Standard Draft r9

Date: 22 Jan 2015 Page 9 of 18 Revision:Final

Bulk Storage of Flammable and Combustible Liquids Standard

PS-ST-001Global Supply Chain

PROCESS SAFETY WARNING – If Printed this document becomes an UNCONTROLLED Copy

2. For vertical tanks, the emergency relief venting construction referred to in point 1 above shall be permitted to be afloating roof, a lifter roof, a weak roof-to-shell seam, or anotherapproved pressure-relieving construction.

3. If unstable liquids are stored, the effects of heat orgas resulting from polymerization, decomposition, condensation,or self-reactivity shall be taken into account.

4. If two-phase flow is anticipated during emergencyventing, an engineering evaluation shall be conducted in orderto size the pressure-relieving devices.

5. If used, a weakroof-to-shell seam shall be constructed to fail preferential toany other seam and shall be designed in accordance withAPI Standard 650, Welded Steel Tanks for Oil Storage, orANSI/UL 142, Standard for Steel Aboveground Tanks for Flammableand Combustible Liquids.

6. Where entire dependence for emergency relief ventingis placed upon pressure-relieving devices, the total ventingcapacity of both normal and emergency vents shall be sufficientto prevent rupture of the shell or bottom of a verticaltank or of the shell or heads of a horizontal tank.*** (Applies retroactively at all Ecolab sites)***

7. Refer to NFPA 30 Section 22.7.3 for methods of determining the required emergency relief venting capacity.

F. Containment

1. Every tank that contains a Class I, Class II, or Class IIIA liquid shall be provided with means to prevent an accidental release of liquid from endangering important facilities and adjoining property or from reaching waterways.*** (Applies retroactively at all Ecolab sites)***

2. Tanksmust have a containment basin to meet local requirements or 110% of the largest tank volume in the containment area plus allowance for a 25 year 24 hour event rain fall whichever is more stringent. *** (Applies retroactively at all Ecolab sites)***

3. If drain valves are used to drain surface water, a system must be in place to control access via locks. Control of drainage should be accessible from outside the containment system in the event of fire. *** (Applies retroactively at all Ecolab sites)***

Page 10: Flammables Bulk Storage Standard Draft r9

Date: 22 Jan 2015 Page 10 of 18 Revision:Final

Bulk Storage of Flammable and Combustible Liquids Standard

PS-ST-001Global Supply Chain

PROCESS SAFETY WARNING – If Printed this document becomes an UNCONTROLLED Copy

4. Floor of bund or tank pad should be sloped to prevent the accumulation of spills under tanks.

G. Level Measurement

1. Facilities with aboveground tanks larger than 1320 gal (5000 L) storing Class I or Class II liquids shall establish procedures or shall provide equipment, or both, to prevent overfilling of tanks.*** (Applies retroactively at all Ecolab sites)***

2. While filling the following *** (Applies retroactively at all Ecolab sites)***a) tanks shall be gauged at intervals in accordance with established procedures by personnel continuously on thepremises during product receipt orb) tanksshall be equipped with a high-level detection device that is either independent of any gauging equipment or incorporates a gauging and alarm system that provideselectronic self-checking to indicate when the gauging andalarm system has failed.

3. Alarms shall be located whereEcolab personnel who are on duty throughout product transfercan arrange for flow stoppage or diversion in accordancewith established procedures or tanks shall be equipped with an independent high-leveldetection system that will automatically shut down or divertflow in accordance with established procedures.*** (Applies retroactively at all Ecolab sites)***

4. Liquid level gauges capable of giving local readings must be installed on all storage tanks*** (Applies retroactively at all Ecolab sites)***. However, gauges capable of giving both local and remote readings are recommended.

5. For Ecolab Class II and Class III materials stored in bulk storage vessels, additional level control measures must be in place as detailed below*** (Applies retroactively at all Ecolab sites)***.

a) In addition to a continuous liquid-level gauge, Class II and Class III material storage vessels must have a high-level alarm (Note: the high-level alarm and the liquid-level gauge may be the same device, however independent level and alarm devices are recommended) *** (Applies retroactively at all Ecolab sites)***. The alarm must not be used for normal operational control.b) The high-level alarm should be activated at 90% of the capacity of the storage vessel leaving a 10% void volume as protection against overflow. Note: If the material being stored in a given storage vessel may require

Page 11: Flammables Bulk Storage Standard Draft r9

Date: 22 Jan 2015 Page 11 of 18 Revision:Final

Bulk Storage of Flammable and Combustible Liquids Standard

PS-ST-001Global Supply Chain

PROCESS SAFETY WARNING – If Printed this document becomes an UNCONTROLLED Copy

the emergency addition of an inhibitor (per Ecolab or supplier recommendations), the high-level alarm must be set at a level that takes into account the maximum volume of inhibitor that may be required to be added (i.e. 90% minus the maximum volume of inhibitor) *** (Applies retroactively at all Ecolab sites)***.c) Audible alarms should sound at an attended location. If site conditions (manpower, site layout, etc.) will not permit timely intervention by an Operator to an audible alarm, a trip must also activate to stop flow when the alarm set-point is reached *** (Applies retroactively at all Ecolab sites).

6. For Class I liquids stored in bulk storage vessels, additional control measures must be in place as detailed below

a) In addition to the requirements for Class II and III materials, the high-level alarm must trigger both an audible alarm AND a safety shut-off which will automatically interrupt filling operations. Activation of the safety shut-off must function without restricting or interfering with the proper functioning of the normal vent or the emergency vent*** (Applies retroactively at all Ecolab sites)***.b) The safety shut-off activated by the high-level condition should have contacts or limit switches to confirm shut-off has occurred. Failure of the safety shut-off device to operate as required should also activate an alarm. c) If the independent instrument is a second liquid-level device, a deviation alarm should be triggered if the two devices register a difference in the measured liquid-level of > 2%.

H. Loading and unloading systems

1. Bonding for the control of static electricity shall be required for loading and unloading Class I liquids.*** (Applies retroactively at all Ecolab sites)***

2. Loading and unloading facilities that are used to load liquids into tank vehicles through open domes shall beprovided with a means for electrically bonding to protectagainst static electricity hazards. All parts of the fill pipe assembly, including, but not limited to, the drop tube, rack structure and piping, shall form a continuous electrically conductive path that is directed to ground through the rack assembly or by conductive wiring.*** (Applies retroactively at all Ecolab sites)***

3. In areas where excessive stray currents are knownto exist, all pipelines entering the area where Class I liquids are loaded or unloaded shall be

Page 12: Flammables Bulk Storage Standard Draft r9

Date: 22 Jan 2015 Page 12 of 18 Revision:Final

Bulk Storage of Flammable and Combustible Liquids Standard

PS-ST-001Global Supply Chain

PROCESS SAFETY WARNING – If Printed this document becomes an UNCONTROLLED Copy

provided with insulating sections to electrically isolate them from the facility piping.*** (Applies retroactively at all Ecolab sites)***

4. Tank vehicle and tank car loading and unloading facilitiesshall be separated from aboveground tanks, warehouses,other plant buildings, or the nearest line of adjoiningproperty that can be built upon by a distance of at least 25 ft(7.6 m) for Class I liquids and for Class II and Class III liquidshandled at temperatures at or within 17 deg C of their flash points measured from the nearest fill spout or transfer connection. These distances shall be permitted to be reduced if there is suitable protection for exposures.

5. Tank vehicle and tank car loading and unloading facilitiesshall be separated from aboveground tanks, warehouses,other plant buildings, or the nearest line of adjoiningproperty that can be built upon by a distance of at least 15 ft (4.6 m) for Class II and Class III liquids handled at temperatures below their flash points, measured from the nearest fill spout or transfer connection. These distances shall be permitted to be reduced if there is suitable protection for exposures.

6. Before loading Class I liquids in tank vehicles through open domes,a bonding connection shall be made to the vehicle or tankbefore dome covers are raised and shall remain in place untilfilling is completed and all dome covers have been closed and secured.Filling through open domes into tank vehicles that contain vapor–air mixtures within the flammable range or where the liquid being filled can form such a mixture shall be by means of a downspout that extends to within 6 in. (150 mm) of the bottom of the tank.*** (Applies retroactively at all Ecolab sites)***

7. When transferring Class I liquids, or Class II andClass III liquids at temperatures within 17 deg C of their flash points, engines of tank vehicles or motors of auxiliary or portable pumps shall be shut down during the making and breaking of hose connections. If loading or unloading is done without requiring the use of the motor of the tank vehicle, the motor shall be shut down throughout any transfer operations involving Class I liquids.*** (Applies retroactively at all Ecolab sites)***

I. Pipework and Valves

1. The design, fabrication, assembly, test, and inspection of piping systems shall be suitable for the working pressures and structural stresses to be encountered by the piping system. Compliance with applicable sections

Page 13: Flammables Bulk Storage Standard Draft r9

Date: 22 Jan 2015 Page 13 of 18 Revision:Final

Bulk Storage of Flammable and Combustible Liquids Standard

PS-ST-001Global Supply Chain

PROCESS SAFETY WARNING – If Printed this document becomes an UNCONTROLLED Copy

ofASMEB31, Code for Pressure Piping is required..*** (Applies retroactively at all Ecolab sites)*** Piping, valves, and fittings shall be permitted to have combustible or noncombustible linings.

2. Fill pipes that enter the top of a tankshall terminate within 6 in. (150 mm) of the bottom of thetank. Fill pipes shall be installed or arranged so that vibrationis minimized..*** (Applies retroactively at all Ecolab sites)***

a) Exception No. 1: Fill pipes in tanks whose vapor space under theexpected range of operating conditions is not in the flammable range oris inerted need not meet this requirement.

3. Anti-syphon holes or other mechanisms must be provided to prevent reverse flow from down pipes.*** (Applies retroactively at all Ecolab sites)***

4. Valves at storage tanks, as required by and their connectionsto the tank shall be of steel or ductile iron, except asprovided for below.

5. Valves at storage tanks shall be permitted to be other than steel or ductile iron where the chemical characteristics of the liquid stored are not compatible with steel or where the valves are installed internally to the tank. Valves installed externally to the tank shall be permitted to be other than steel or ductile iron if the material of construction has a ductility and melting point comparable to steel or ductile iron and is capable of withstanding the stresses and temperatures involved in fire exposure or the valves are otherwise protected from fire exposures, such as by materials having a fire resistance rating of not less than 2 hours.

6. For tanks inside buildings storing Class I, Class II and Class IIIA liquids with bottom discharge lines, one of the following must be provided.*** (Applies retroactively at all Ecolab sites)***.

a) A normally closed, remotely activated valve orb) An automatic closing heat activated

7. An approved system for fire detection which would trigger the automatic interruption of filling or discharge operations should be considered.

8. For tanks storing Class I liquids where bottom connections are present:a) Valves should be kept closed except when liquid is being transferred;b) For tanks exceeding 38 m3 (10,000 gal), valves should be provided that are manually controllable from a remote location; andc) For Class I liquid storage tanks on legs, the legs should be fireproofed unless sprinklers are provided under the tank.

Page 14: Flammables Bulk Storage Standard Draft r9

Date: 22 Jan 2015 Page 14 of 18 Revision:Final

Bulk Storage of Flammable and Combustible Liquids Standard

PS-ST-001Global Supply Chain

PROCESS SAFETY WARNING – If Printed this document becomes an UNCONTROLLED Copy

J. Fire and Explosion Prevention

1. Operations involving all Class I, Class II, or Class IIIA flammable and combustible liquids shall be reviewed to ensure that fire and explosion hazards are addressed by fire prevention, fire control and emergency action plans.*** (Applies retroactively at all Ecolab sites)***

2. Hazard analysis is required to assess changes. Refer to corporate Management of Change Policy.*** (Applies retroactively at all Ecolab sites)***

3. Precautions shall be taken to prevent the ignition of flammable vapours by sources such as open flames, lightning, hot surfaces, radiant heat, smoking, cutting and welding, spontaneous ignition, friction heat or sparks, static electricity, electrical sparks, stray currents, heating equipment. Refer to Life Critical procedure for controlling hot work.*** (Applies retroactively at all Ecolab sites)***

K. Electrical Systems

1. Electrical utilization equipment and wiring shall not constitute a source of ignition for any ignitable vapor that might be present under normal operation or because of a spill.

2. All electrical utilization equipment and wiring shall beof a type specified by and installed in accordance withNFPA 70, National Electrical Code or equivalent.*** (Applies retroactively at all Ecolab sites)***

3. Points 4 and 5 below shall be used to delineate and classify areas for the purpose of installation of electrical utilization equipment and wiring under normal operating conditions.*** (Applies retroactively at all Ecolab sites)***

4. For indoor storage systems containing Class I liquidsa) NEC Class 1 Div 1 Zone 0-The entire area associated with such equipment where flammable gases or vapors are present continuously or for long periods of timeb) NEC Class 1Div 1 Zone 1-Area within 5 ft of any edge of such equipment, extending in all directionsc) NEC Class1 Div 2 Zone 2-Area between 5 ft and 8 ft of any edge of such equipment, extending in all directions; also, space up to 3 ft above floor or grade level within 5 ft to 25 ft horizontally

Page 15: Flammables Bulk Storage Standard Draft r9

Date: 22 Jan 2015 Page 15 of 18 Revision:Final

Bulk Storage of Flammable and Combustible Liquids Standard

PS-ST-001Global Supply Chain

PROCESS SAFETY WARNING – If Printed this document becomes an UNCONTROLLED Copy

5. For outdoor storage systems containing Class I liquidsa) NEC Class 1 Div 1 Zone 0-The entire area associated with such equipment where flammable gases or vapors are present continuously or for long periods of timeb) NEC Class 1Div 1 Zone 1-Area within 3 ft of any edge of such equipment, extending in all directionsc) NEC Class1 Div 2 Zone 2-Area between 3 ft and 8 ft of any edge of such equipment, extending in all directions; also, space up to 3 ft above floor or grade level within 3 ft to 10 ft horizontally.

6. For more detail please refer to NFPA 497 Recommended practices for the Classification of Flammable Liquids, Gases and Vapours and of Hazardous (Classified) Locations for Electrical Installations in Chemical Process Areas

L. Fire Protection

1. Where the need is indicated by the hazards of the liquid as determined through Hazard Analysis, fixed fire protection shall be provided to prevent or minimize the loss from fire and explosion according to NFPA 30 6.7*** (Applies retroactively at all Ecolab sites)***.

2. A written emergency action plan that is consistent withavailable equipment and personnel shall be established to respond to fires and related emergencies. The plan shall include the requirements of NFPA 30 6.8*** (Applies retroactively at all Ecolab sites)***.

3. Where fixed fire protection systems are provided, equipment must be properly maintained and inspected. Water based fire protection systems shall be inspected, tested and maintained according to NFPA 25

M. Management of Security

1. Operations involving all Class I, Class II, or Class IIIA flammable and combustible liquids shall be reviewed to ensure that security vulnerabilities identified during the security vulnerability analysis (SVA) are addressed in a facility security program, with corresponding fire prevention and emergency action plans and drills. Refer to NFPA 30 6.10.*** (Applies retroactively at all Ecolab sites)***

N. Inspection and Maintenance of Storage Tanks 1. Each storage tank constructed of steel must be inspected and maintained

in accordance with API Standard 653, Tank Inspection,Repair, Alteration,

Page 16: Flammables Bulk Storage Standard Draft r9

Date: 22 Jan 2015 Page 16 of 18 Revision:Final

Bulk Storage of Flammable and Combustible Liquids Standard

PS-ST-001Global Supply Chain

PROCESS SAFETY WARNING – If Printed this document becomes an UNCONTROLLED Copy

and Reconstruction, STI SP001, Standard for the Inspection of Aboveground Storage Tanks or EEMUA 159 Maintenance and Inspection of Above Ground Vertical Steel Cylindrical Storage Tankswhichever is applicable.*** (Applies retroactively at all Ecolab sites)***.

2. Each storage tank constructed of other materials must be inspected and maintained in accordance with the manufacturer’s instructions and applicable standards to ensure compliance with the requirements of this standard. *** (Applies retroactively at all Ecolab sites)***.

3. Each storage tank must be maintained liquidtight. Each storage tank that is leaking shall be emptied of liquid and repaired. *** (Applies retroactively at all Ecolab sites)***.

4. Storage tanks and their appurtenances, including normal vents, emergency vents, overfill prevention devices, and related devices, must be inspected and maintained to ensure that they function as intended in accordance with written procedures. *** (Applies retroactively at all Ecolab sites)***.

5. Facilities with aboveground storage tanks must establish and implement a procedure to check for and remove water from the bottom of storage tanks that contain non-miscible liquids.*** (Applies retroactively at all Ecolab sites)***.

V. PERMITS

VI. AUDITS

VII. TRAINING

A. Hazard Awareness

1. General flammable and combustible liquid hazard awareness and recognition training must be provided annually to all site employees.*** (Applies retroactively at all Ecolab sites)*** The training should include

a) Properties of flammable and combustible liquidsb) Site inventory of specific flammable and combustible liquidsc) Required response to hazardous event involving flammable and combustible liquidsd) Appropriate elements of the Site Emergency Response Plan dealing with spills and fire involving flammable and combustible liquids

Page 17: Flammables Bulk Storage Standard Draft r9

Date: 22 Jan 2015 Page 17 of 18 Revision:Final

Bulk Storage of Flammable and Combustible Liquids Standard

PS-ST-001Global Supply Chain

PROCESS SAFETY WARNING – If Printed this document becomes an UNCONTROLLED Copy

2. Training regarding specific response action to hazardous events involving the bulk storage of flammable and combustible liquids must be provided to all employee emergency response personnel annually. .*** (Applies retroactively at all Ecolab sites)***

3. Consideration should be given to conducting annual exercises for the response to emergencies involving fire with bulk flammable and combustible liquid storage systems.

VIII. DOCUMENTATION

IX. REFERENCES

A. NFPA 30 Flammable and Combustible Liquids Code

B. NFPA 77 Recommended Practice on Static Electricity

Page 18: Flammables Bulk Storage Standard Draft r9

Date: 22 Jan 2015 Page 18 of 18 Revision:Final

Bulk Storage of Flammable and Combustible Liquids Standard

PS-ST-001Global Supply Chain

PROCESS SAFETY WARNING – If Printed this document becomes an UNCONTROLLED Copy

X. REVIEWS AND UPDATES

Revision

Date Change Revised by

Reviewed by

Approved

0 1/22/15 New Ecolab Standard K.Hahn TRC B. Ballard