PRESENTED BYSAMEER KUMAR SINGH (10M206)TARESH KUMAR MITTAL (10M207)NIKHIL KUSHWAHA (10M212)
First Swing Stabilty
![Page 2: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/2.jpg)
Stability
The stability of an interconnected power system is its ability to return to normal or stable operation after having been subjected to some form of disturbance.
![Page 3: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/3.jpg)
Machine Connected to Infinite Bus
Fault makes generator electric Power zero
Generator accelerates. Can generator get back to constant --synchronous speed?
Only if it can get rid of excess KE
Excess KE needs to go into the infinite bus through the line? Will it? What happens if it can’t?
Stability means returning to synchronous speed
KEBuilds up Excess KE
Needs to be removed
SPEED
Line Real Power P
PP
∞ ∞
![Page 4: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/4.jpg)
Instability
Instability means a condition denoting loss of synchronism or falling out of steps.
![Page 5: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/5.jpg)
Types of Power System Stability
![Page 6: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/6.jpg)
Pe = (EV/X) sinδPe = (VsVr/X)sinδ
Power-angle curve of the system
jXL+
E’/δ
Pe
jXd’
V/0
Fixed (Infinite Bus)
Pm
P
δ0°
180°
Pmax
![Page 7: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/7.jpg)
SWING EQUATION
Definition: The electromechanical equation describing the relative motion of the rotor load angle (δ) with respect to the stator field as a function of time is known as Swing equation.
M(d²δ/dt²) = Pm – PeM = Angular MomentumPm = Mechanical or shaft power inputPe = Electrical power outputδ = rotor angle with respect to a synchronously rotating reference
![Page 8: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/8.jpg)
For Stable Condition
Pmax
180°0°
Pm=PeP
δ
d2δ/dt2 =0 Pm = Pe
dδ /dt =0 ω = ωsyn
![Page 9: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/9.jpg)
Equal Area Criteria
![Page 10: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/10.jpg)
Equal Area Criteria
![Page 11: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/11.jpg)
First Swing Stability
Following a large disturbance, a power system can be considered as first swing stable if the angle of all machines in center of angle (COA) reference frame initially increases (decreases) until a peak (valley) is reached where the angle starts retuning to the stable equilibrium point
![Page 12: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/12.jpg)
First Swing Stability
![Page 13: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/13.jpg)
First Swing Stability
![Page 14: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/14.jpg)
Applications
1. Establish initial conditions2. Define sequence of events and network for
each event3. Develop Power angle curves4. Apply EAC
![Page 15: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/15.jpg)
![Page 16: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/16.jpg)
Applications Of FACTS Controller
1. Power transfer capability
2. Power oscillation Damping
3. Transient Stability
4. Prevent blackouts
![Page 17: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/17.jpg)
Fundamental of improving FSS
Pe = (EV/X) sinδPe = (VsVr/X)sinδPower systems
are normally designed to be transiently stable, with defined pre-fault contingency scenarios and post-fault system degradation when subjected to a major disturbance .
![Page 18: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/18.jpg)
Improvement of FSS using Shunt Devices
Pe = (V2/X)sinδ (for Uncompensated system)
Pe = 2(V2/X)sinδ/2 (for compensated system)
![Page 19: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/19.jpg)
P- δ curves for various operating conditions of SVC
areas when the angle increases areas when the angle decreases.
![Page 20: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/20.jpg)
System with a STATCOM
Equivalent circuitP- δ curve.
![Page 21: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/21.jpg)
Improvement of FSS using series Devices
P= V2sinδ (1-k)X
Q= 2V2. k . (1-cosδ) X (1-k)2
K= Xc ,o<k<1 X
![Page 22: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/22.jpg)
Improvement of FSS using Series compensator
Without compensation With compensation
![Page 23: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/23.jpg)
Using Phase Angle Regulator
P= V2sin(δ- ) X
Q= V2. {1-cos(δ - )} X
![Page 24: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/24.jpg)
Conclusion
When the fault is cleared (after roughly 0.1 s) the power system has to be restored to sufficiently small angle deviations between the generator rotors again. After the first swing we require damping of the oscillations.
In the first phase, the electrical properties are very quickly adjusting to the new situation.
In the second phase the unbalance between mechanical input and electrical output of each generator are causing a change of generator mechanical speed.
In the third phase protection and control are coming into play.
![Page 25: First Swing Stabilty](https://reader033.fdocuments.in/reader033/viewer/2022050816/55245b704a795968498b4690/html5/thumbnails/25.jpg)
References
[1] PAVELLA M., ERNST D., RUIZ-VEGA D.: ‘Transient stability of power systems: a unified approach to assessment and control’ (Klumer Academic Publishing, Boston, 2000)
[2] KUNDUR P., PASERBA J., AJJARAPU V., ET AL.: ‘Definition and classification of power system stability’, IEEE Trans. Power Syst., 2004, 19, (2), pp. 1381–1401 2003, 142, (2), pp. 59–67
[3] HAQUE M.H.: ‘Improvement of first swing stability limit by utilising full benefits of shunt FACTS devices’, IEEE Trans. Power Syst., 2004, 19, (4), pp. 1894–1902
[4] CHANG J., CHOW J.H.: ‘Time-optimal control of power systems requiring multiple switchings of series capacitors’, IEEE Trans. Power Syst. 1998, 13, (2), pp. 367–373.
[5]Narain G. Hingorani , Understanding FACTS