With restructuring of power sector in Pakistan and increase in economic, commercial & industrial activities, more power utilities and other customers demanded high value packaged solutions for their Distribution net work, transmission systems, Power generation and enterprise electrification requirements. To meet this demand FNP established an Engineering Procurement and Construction division. FNP’s EPC Division consists of human resource with high academic qualifications and experience of local as well as global market. The EPC division delivers custom designed and built solutions in following areas: 132kV and 220kV grid stations for power utility companies 132kV and 11kV substations for industrial and commercial customers Integration of private captive power generation plants into utility network for sale of their surplus power to utility companies Power delivery systems for Independent Power Producers (IPPs) Electrical Plant for, Thermal & Hydro Power Units Electrification of commercial, housing projects and industrial parks Security & surveillance system Our services include: Design & Engineering Project Management Project Execution Turnkey or customized projects Automations, Hi-tech Systems & Solution Field Services for Erection, Testing & Commissioning Maintenance of Plant/Equipment In this regards we have ISO certified manufactures / supplier around the world some are mention below;- Eurogulf Transformer FZC from U.A.E (Manufacturer of Distribution & Power Transformers with collaboration of MACE S.a.s Italy). HOBUT from England SEZ - Krompachy from Slovakia IME from Italy. Conta-Clip from Germany RTR Energia from Spain Conputronics Control from UK Algodue Elettronica S.R.L from Italy. Arteche from Spain Korps from Korea Nikdim from Bulgaria Schrack from Austria 1 1

description

 

Transcript of First National Pakistan

Page 1: First National Pakistan

With restructuring of power sector in Pakistan and increase in economic, commercial & industrial

activities, more power utilities and other customers demanded high value packaged solutions for their

Distribution net work, transmission systems, Power generation and enterprise electrification

requirements.

To meet this demand FNP established an Engineering Procurement and Construction division. FNP’s EPC

Division consists of human resource with high academic qualifications and experience of local as well as

global market. The EPC division delivers custom designed and built solutions in following areas:

132kV and 220kV grid stations for power utility companies

132kV and 11kV substations for industrial and commercial customers

Integration of private captive power generation plants into utility network for sale of their

surplus power to utility companies

Power delivery systems for Independent Power Producers (IPPs)

Electrical Plant for, Thermal & Hydro Power Units

Electrification of commercial, housing projects and industrial parks

Security & surveillance system

Our services include:

Design & Engineering

Project Management

Project Execution

Turnkey or customized projects

Automations, Hi-tech Systems & Solution

Field Services for Erection, Testing & Commissioning

Maintenance of Plant/Equipment

In this regards we have ISO certified manufactures / supplier around the world some are mention below;-

Eurogulf Transformer FZC from U.A.E (Manufacturer of Distribution & Power Transformers with collaboration of MACE S.a.s Italy).

HOBUT from England

SEZ - Krompachy from Slovakia

IME from Italy.

Conta-Clip from Germany

RTR Energia from Spain

Conputronics Control from UK

Algodue Elettronica S.R.L from Italy.

Arteche from Spain

Korps from Korea

Nikdim from Bulgaria

Schrack from Austria

1

1

Page 2: First National Pakistan

Helukabel GmbH from Germany

Eland from UK

Agro from Switzerland

Cember from Italy

TLA Electrical Distributors Ltd from UK

CAN OZAN PANO from Turkic

Cenit Solar from Spain.

DEIF from UK

Quantum Controls Ltd.

Detail of components & equipments are as under: -

Eurogulf Transformer FZC o Distribution Transformers up to 4000 KVA, up to operational Voltage is 36 KV. o Power Transformer up to 100 MVA, up to operational Voltages is 132 KV. o Multi Tap Transformers to suit from 35Hz to 80Hz frequency System for VSD

application. o Special application motor starting auto transformers with full or intermittent

ratings. o Dry type varnish impregnated transformers for special applications. o Cast resin Transformers up to 5000 KVA.

HOBUT from England

o Analogue/ Digital Ammeters & Volt Meters o Analogue/ Digital PF Meters o Analogue/ Digital Frequency Meters o Analogue/ Digital Mega Var Meters o Analogue/ Digital Mega Watt Meters o Power Transducers o Digital Multi Function Meter M850 o Digital Multi Function Meter M812 o Single Phase Current Transformers (CT’s) o Three Phase Current Transformers (CT’s) o Earth Leakage Relay + CBCT o Earth Fault Relay o Over Current Relay

SEZ - Krompachy from Slovakia

o AC MCB’s o DC MCB’s o Cam/Selector Switches

2

Page 3: First National Pakistan

o Rotary Switches o AC Contactor o DC Contactor o Auxiliary Contactor o Auxiliary contact

IME from Italy. o Multifunction Meter o Transducers single & multifunction o Digital Static energy Meters with & without GSM modem. o Differential Relays o Insulation Relays o Measuring Relays. o Current Transformers with built-in transducer.

Conta-Clip from Germany

o Terminal Blocks / Connectors o Earth Terminal Blocks o CT Short Link Terminals o Fuse Terminals o Stoppers & End Plates o Numbering

RTR Energia from Spain

o L.V Capacitors o M.V Capacitors o Power Factor Controllers

Conputronics Control from UK

o Battery Chargers Algodue Elettronica S.R.L from Italy.

o Energy control solutions o Intelligence systems developed for professional security operations and authorized

investigations. o GPS systems solutions for monitoring moving objects, property, people

Arteche from Spain

Korops from Korea

Nikdim from Bulgaria

Schrack from Austria

Helukabel GmbH from Germany

o Control cables copper shielded and unshielded.

o LV Power Cables.

Eland from UK

o Control Cables, Instrumentation Cables.

3

Page 4: First National Pakistan

o Power Cables.

Agro from Switzerland

o Cable glands.

Cember from Italy

o Cables lugs – bimetallic

o Cables Terminal Insulated & un-insulated

o Polyamide high temperature Cable ties.

o Steel Cable ties.

TLA Electrical Distributors Ltd from UK

o Eriflex – Low voltage Power Distribution such as Busbar support Flexibar –

insulated busbar up to 2300A.

o Eritech – Facility Electrical Protection

o CADWELD – Electrical Grounding and Bonding.

o CRITEC – Surge Protection devices.

o ERITECH – Grounding Products.

o ERITECH – Lightning Protection Products.

o CADDY – Electrical Fixings, Fasteners and supports.

o CADDY – Mechanical Fixing, Fasteners and supports.

o PULS – DIN Power Supply.

o Fulleon – Sounder & Beacon

o VACON – Inverter Drive.

CAN OZAN PANO from Turkic

o Power distribution panels as IP65, IP55 class.

o Control and automation enclosures as per IP65, IP55 class.

o Synchronization / Parallel gen. set control Panel as IP65, IP55.

o Test Benches as per IP65, IP55.

Cenit Solar from Spain.

o Off grid / On grid Solar system up to 2MWatt.

o Solar water pumping systems – deep well & dewatering.

o Solar Heating system.

DEIF from UK

o Gas engine control unit.

o Generator protection unit.

o Multiple parallel control units.

Quantum Controls Ltd From UK.

o ABB Variable Speed Drives.

o ABB Motors.

o Refurbished Variable Speed derives.

o ABB Motor Gear.

o ABB LV Control Panels (Distribution & Process Control Panels).

4

Page 5: First National Pakistan

CONTACTS

Head Office: 155-A, Sarfraz Rafiqui Road, Lahore Cantt, Lahore.

Tel: +92 42 36662054~5

Fax: +92 42 36662053

Name Designation Mobile E-mail

Liaqat Ali Chairman 0333-5898999 [email protected]

M. Amir Amen CEO - [email protected]

Akhtar Ali Malik

Executive / Technical

Director 0044-7821043649 [email protected]

Meshud ul Hassan Technical Director 0321-8491035 [email protected]

Engr.Ali Raza Syed Executive / Director 0333-5174770 [email protected]

Qaisar Raza Rana Sales Manager 0344-4451323 [email protected]

Sanaullah Khan Sales Executive 0344-4451320 [email protected]

M.Shahid Haroon Estimate Exactive Officer 0344-4451324 [email protected]

Miss Aneela Iftikhar Account Officer 042-36662054-55 [email protected]

Miss Farina Waheed Customer Care Officer 042-36662054-55 [email protected]

Miss Amber Khan Office Attendant Officer 042-36662054-55 [email protected]

5

Page 6: First National Pakistan

6

Page 7: First National Pakistan

Multifunction meters

The art of measuring.

It is the ability of organising and estimating thedata of our everyday experience that makes us toprogress. This estimation is carried out by means of an artwhich enables us to choose among things differentfrom one another by comparing some of theircharacteristics. It is the art of weighing, counting and measuring.

ISTRUMENTI MISURE ELETTRICHE SpA

ISTRUMENTI MISURE ELETTRICHE SpA

7

Page 8: First National Pakistan

ISTRUMENTI MISURE ELETTRICHE SpA

ISTRUMENTI MISURE ELETTRICHE SpA

I

Nemo 96 HD Nemo 96 HD

Twins, but differentAs with people, you need only one look to knowthat we are dealing with twins: same physicalstructure, same features, same colour of eyes andhair. But if we want to catch what makes them similarand what distinguishes them, then, as with people, asingle look is no longer enough: we need to knowthem more closely.

Why are different

What distinguishes the two products is definitely the use they are intended for: 96 HD is intended for low voltage applications, while 96 HD+ for both lowand medium voltage applications. This implies some important differences, that is to say, a proper insulation class for voltage and current inputs,

Complete compatibility for optional modules: one module can be installed on any of the two modelswithout limitation; both models can accept up to4 modules at the same time.Same possibility of network connection (single-phase,three-phase 3 or 4 wires).Same reading of measurements and parameterprogramming for the two models; same direct and derived electrical quantities, same energy and time count, same data storing.The software can be updated on field.

Nemo 96 HD+Nemo 96 HD Nemo 96 HD

Nemo 96 HD+

What do have in common

The structure and the mechanical dimensions, the flush mounting fixing system, the expandability of the functions by means of optional modules.The backlit display, characterised by high visibility and information content, and a 4-button keypad for the dialogue man-machine.

bt

and a more complete programming menu that allowsto define specific functioning conditions as, for example, in case of connection by means of current and voltage transformers, linked in medium voltage networks.

MT

8

Page 9: First National Pakistan

P•Q•SActive powerReactive powerApparent powerPhase and three-phase instantaneous valueAverage value and average value peak

ICurrentInstantaneous phase and neutral valueHarmonic distortion for phaseAverage value and average value peak

UVoltageInstantaneous valueMin and max valueHarmonic distortion

E•TEnergy counting Total and partial activePositive and negative activeTotal and partial reactivePositive and negative reactivePower factorPhase and three-phase instantaneous valueFrequencyInstantaneous valueHourmeterWorking hour counting

9

Page 10: First National Pakistan

Communication interfaceAccording to standard RS 232-C. Communication speed programmable up to 38,400 bit/s.

Communication interfaceAccording to standardPROFIBUS.Communication speedup to 3Mb.

Same modules for: Nemo 96 HD Nemo 96 HD

Communication interfaceAccording to standard RS 485. The protocol used is MODBUS RTU; on demand, implementation of proprietary protocols can be provided.Communication speed programmable up to 38,400 bit/s.

Analogue outputTwo independent andisolated channelswith output current0…20mA and/or 4…20 mA. The association betweenquantities measured and analogue outputs is definedat module’s installation.

Expansion modulesThe seven following expansion modules are available in the kit of Nemo 96 HD and 96 HD+. The modules can be used without limitation on bothmodels, which can accept up to 4 modules each.

Pulse emitter for energy countTwo isolated optorelaysprogrammable independently (time ON and weight of associated energy) foractive and reactive energy. Contacts: SPST-NO.

AlarmsTwo independent and isolated alarm relays with programmable functions.Contacts: SPST.

USCITA CON IMPULSI CONTEGGIO ENERGIA

BUS SPECIALI

USCITA CON ALLARME

COMUNICAZIONEUSCITA ANALOGICA

USCITA CON IMPULSI CONTEGGIO ENERGIA

BUS SPECIALI

USCITA CON ALLARME

COMUNICAZIONEUSCITA ANALOGICA

USCITA CON IMPULSI CONTEGGIO ENERGIA

BUS SPECIALI

USCITA CON ALLARME

COMUNICAZIONEUSCITA ANALOGICA

USCITA CON IMPULSI CONTEGGIO ENERGIA

BUS SPECIALI

USCITA CON ALLARME

COMUNICAZIONEUSCITA ANALOGICA

USCITA CON IMPULSI CONTEGGIO ENERGIA

BUS SPECIALI

USCITA CON ALLARME

COMUNICAZIONEUSCITA ANALOGICA

Neutral currentNeutral currentdirect measure. Programming ofneutral CT ratioindipendent frommeasuring CT’s.

COMUNICAZIONEMULTIMISURA CONTEGGIO ENERGIA CONTROLLO E GESTIOINE

PROTEZIONESENSORI DI CAMPO MISURE CONTROLLOMISURE GRANDEZZE SINGOLE

10

Page 11: First National Pakistan

Easy module connectionFixing of optional modules by means of a sliding shutter.The operation requires no screwing.

Mechanics:

Fast mountingPanel fixing system by means of clips.

8162

Reduced depthJust 61mm depth without modules and81mm with mounted modules.

IME is proud and pleased to put on the market

the two latest creations in the already large

family of network devices series Nemo.

Pleased because of the delight always felt

when something new is created, and proud

because of the awareness of creating

products that sum up, from the technical,

functional and esthetical point of view,

the whole experience gained through years

of dedication to the field of electric measurement.

These two products complete our range

proposing flush mounting models

characterised by: high precision, flexibility,

high visibility, clearness of reading

and attention for details.

11

Page 12: First National Pakistan

ISTRUMENTI MISURE ELETTRICHE SpA

ISTRUMENTI MISURE ELETTRICHE SpA

Codes

Auxiliary supply

Network

line

Input

voltage

current

frequency

Accuracy class

voltage

current

powers

frequency

active energy

reactive energy

Programmable parameters

connection

average value delay time

display

rated current

CT ratio

VT ratio

Housing

front frame dimensions

depth (without modules)

depth (with modules)

front frame protection degree

Technical Note

Optional modules

energy counting repetition

analogue output

alarm signalling

neutral current

RS485 communication interface

RS232 communication interface

Profibus communication interface

Model Nemo 96 HD+Nemo 96 HD

www.imeitaly.com Via Travaglia 7 20094 Corsico (Mi) Tel.02 44 878.1fax 02 45 03 448 +39 02 45 86 76 63 [email protected]

low voltage connection on dedicated CT ‘s low and medium voltage

80...265Vac / 110...300Vdc 11...60Vdc

MF96001 MF96002 MF96021 MF96022

single-phase, three-phase 3 or 4 wires

80...500V phase-phase 80...690V phase-phase

1 and 5A

47...63Hz

0,2

0,2

0,5

±0,15Hz

cl.0,5s according to EN62053-22

cl.2 according to EN62053-23

single-phase, three-phase 3 or 4 wires

5 - 8 - 10 - 15 - 20 - 30 - 60 min

contrast and brightness

1 or 5A

1...9999

1...10 1...3000

96 x 96 DIN 43700

62 mm

81 mm

IP54 according to EN60529

2 SPST-NO optorelay pulse outputs

2 indipendent channels 0...20mA and/or 4...20mA

2 indipendent alarms with SPST output

neutral current measure

speed up to 38,400 bit/s

speed up to 38,400 bit/s

speed up to 3 Mb

IME

S.p

.A.

rese

rves

the

rig

ht

tom

od

ify

the

tech

nic

alch

arac

teri

stic

sw

ith

ou

tn

oti

ce.

104/

07Ed

.A08

-W

80...265Vac / 110...300Vdc 11...60Vdc

Technical Note

NT677

NT678

NT679

NT683

NT675

NT676

NT682

Codes

IF96003

IF96004

IF96005

IF96006

IF96001

IF96002

IF96007

NT680 NT681

12

Page 13: First National Pakistan

~ NATIONAL TRANSMISSION ANn nESPATCH COMPANY LIMITED

No.CFlSPINTDCU J 666 -I 0

Chief Engineer (System Protection) NTDCLDATED /1,-1 ()c-anl<~

MIS First National Pakistan.28-A, Meera Khan Road, St. John Park1.0hore Cantt

SUDJECT:- APPROVAL OF TRANSDUCERS ]<OR CURRENT (TEMA 14),VOLTAGE ('1'1<:]\1A lJ4) AJI\D ACTIVE PO\VEI~, RRACTIVEPO'VER, APPARENT PO\VJ(J~! l'O\VER FACTOR, PHASEANGLI!: (TEMA fP) - (!\1AKE Jl\IE ITALY)

Rcfr- Your letter No.FNP071l3 dated 27·09·2013

The Transducers of current (TEMA 14), Voltage (TEMA U4) and Active Power,

Reactive Power, Apparent Power, Power Factor, Phase Angle (TEMA fP) - (MA.K.E

lME ITALy) for use in control panels arc hereby Approved for installation III Control

Panels in PEPCO I NTDCL Network. You will provide the necessary literature required

for installation of these transducers.

~~___'~/!.I"'\C.E. (System-Protection) NTDCi

CC re..

I. Chief Engineer (Design) NTDCL, Wapda HO\1~e, Lahore2. All ACE's of this office.

MlflileRlFile

J30·Wnpda House,Lahore,PakistanTF,:+92 42 99202655,Fux:+92 42 99202t84 r..MuiJ:[email protected].:\Tariq\arshad.doc

13

Page 14: First National Pakistan

1mA

1.5 I 2

200 400

0

kW

482

600

300

100 500

kW

Rapporto TA -TVCT -VT ratio

Potenza attivaActive power

Potenza reattivaReactive power

Potenza apparenteApparent power

Fattore di potenzaPower factor

Angolo di fasePhase angle

Potenza mediaMax. demand

FrequenzaFrequency

0...5mA

0...10mA

0...20mA

4...20mA

5...0...5mA

10...0...10mA

20...0...20mA

0...10V

10...0...10V

1...5V

Inserzione diretta fino a 500V Direct connection up to 500V

NT51

4 04

- 20

10 5

aEd

.pag

.1/6

Tema fPTrasduttoreprogrammabile

8 Moduli

Un solo apparecchio per tutte le inserzioni,linea monofase e trifase

Completamente configurabile in campoIngresso tensione trifase diretta fino a 500V

e su TV/100 e 115VIngresso corrente da TA/5A opp. /1A

Misura in vero valore efficace

Misure associabili all’uscita:Potenza attiva

Potenza reattivaPotenza apparenteFattore di potenza

Angolo di fasePotenza media

Frequenza

Uscita realizzabile con tutti i segnali standard

0...5/10/20mA - 4...20mA0...10V - 1...5V

Programmable transducer8 Module

Just one meter for single-phase and 3-phase connectionsWholly field programmableDirect three-phase voltage input up to 500V andthrough V.T. 100 and 115V Current input C.T/5A or /1ATrue R.M.S. measurements

Measured quantity: Active powerReactive powerApparent powerPower factorPhase anglePower demandFrequency

Output possible with all standard signals0...5/10/20mA - 4...20mA0...10V - 1...5V

TRASDUTTORITRANSDUCERS

Grandezza Quantity

Uscita Output

14

Page 15: First National Pakistan

MISUREMEASURE

LINEA MONOFASESINGLE PHASE LINE

S250/97

LINEA TRIFASE THREE PHASE

3 FILI EQUILIBRATABALANCED LOAD 3-WIRE

S250/93 S250/100

4 FILI EQUILIBRATABALANCED LOAD 4-WIRE

S250/95

3 FILI SQUILIBRATAUNBALANCED LOAD 3-WIRE

S250/94/96/98

4 FILI SQUILIBRATAUNBALANCED LOAD 4-WIRE

S250/99

Potenza attiva monofaseSingle phase active power •

Potenza attiva L1-NActive power L1-N N •

Potenza attiva L2-NActive power L2-N •

Potenza attiva L3-NActive power L3-N •

Potenza attiva trifaseThree phase active power • • • •Potenza reattiva monofase

Single phase reactive power •Potenza reattiva L1-NReactive power L1-N N •Potenza reattiva L2-NReactive power L2-N •Potenza reattiva L3-NReactive power L3-N •

Potenza reattiva trifaseThree phase reactive power • • • • •

Potenza apparente monofaseSingle phase apparent power •

Potenza apparente L1-NApparent power L1-N N •

Potenza apparente L2-NApparent power L2-N •

Potenza apparente L3-NApparent power L3-N •

Potenza apparente trifaseThree phase apparent power • • • •Fattore di potenza monofase

Single phase power factor •Fattore di potenza L1-N

power factor L1-N N •Fattore di potenza L2-N

power factor L2-N •Fattore di potenza L3-N

power factor L3-N •Fattore di potenza trifaseThree phase power factor • • • •Angolo di fase monofasephase angle, single phase •

Angolo di fase trifasephase angle, three phase • •

Potenza mediapower demand • • • • • •

Valore massimo potenza mediapower max. demand N N N N N N

FrequenzaFrequency • • • • • •

CODICI DI ORDINAZIONEORDERING CODE

INGRESSOINPUT

AL. AUSILIARIA AUX. SUPPLY

TM8P02110 1A 80...500V 115V ca / ac

TM8P02120 5A 80...500V 115V ca / ac

TM8P03110 1A 80...500V 230 - 240V ca / ac

TM8P03120 5A 80...500V 230 - 240V ca / ac

TM8P0H110 1A 80...500V 20...150V cc / dc

TM8P0H120 5A 80...500V 20...150V cc / dc

TM8P0L110 1A 80...500V 150...250V cc / dc

TM8P0L120 5A 80...500V 150...250V cc / dc

NT51

4 04

- 20

10 5

aEd

.pag

.2/6

• Grandezze visualizzate che possono essere trasdotte (associabili all’uscita analogica) Display quantities which can be transduced (which can be associated to the analog output)

N Grandezze solamente visualizzate (non possono essere associabili all’uscita analogica) Quantities displayed only (which cannot be associated to the analog output)

15

Page 16: First National Pakistan

INGRESSO

Rete monofase, rete trifase 3 e 4 fili, carico equilibrato squilibratoInserzione: diretta o da TV e TA esterni (con rapporti programmabili)Rapporti TA e TV: programmabili, KTA x KTV ≤ 220.000 (In 5A) - ≤ 2.000.000 (In 1A)Tensione trifase nominale Un: 400V (fase - fase)Tensione monofase: 50...300VCorrente In: 5A oppure 1AFrequenza fn: 50HzEccedenza di breve durata (EN 60688): 2Un/1s - 20In/1sAutoconsumo (per ogni fase): tensione ≤ 0,5VA - corrente 0,5VA

CAMPI NOMINALI DI UTILIZZO (EN 60688)

Tensione trifase: 80...500V (fase - fase)Corrente: 0...120% InFrequenza: 45...65HzFattore di potenza: cosϕ 0,5...1...0,5 − senϕ 0,5...1...0,5Contenuto armonico: fino alla 16a armonica

IMPOSTAZIONE CAMPO DI USCITA

Programmabile: tramite tastieraPotenza corrispondente al fondo scala: 50...150% PnMinimo ∆ inizio - fondo scala: 25% Pndove:Pn (potenza nominale) = Un x In x √3Un (tensione nominale) = 400V (inserz. diretta) - 100V (inserz.su TV esterno)In (corrente nominale) = 5A oppure 1A

POTENZA MEDIA

Visualizzazione e misura: potenza media e valore massimo potenza mediaGrandezza: potenza attiva, reattiva o apparenteTempo di media: selezionabile 5/8/10/15/20/30/60 minutiCalcolo: media fissa sul periodo selezionatoAzzeramento valore massimo potenza media: manuale, da tastiera

VISUALIZZAZIONE

Tipo display: LCDVisualizzazione misure: suddivisa in differenti pagine, con scansione manualeUnità ingegneristica: visualizzazione automatica misure lato primario (TA-TV esterni)

PROGRAMMAZIONE

Programmazione parametri: tastiera frontale, 3 tastiConservazione parametri di configurazione: memoria permanente

PARAMETRI PROGRAMMABILI

Connessione: rete monofase - trifase (3 - 4fili), carico equilibrato - squilibratoTA -TV esterni: rapporto KTA x KTV ≤ 220.000 (In 5A) - ≤ 900.000 (In 1A)Uscita analogica: grandezza associata, inizio e fondo scala, valore nominale dicorrente (o tensione)Potenza media: grandezza, tempo di media, azzeramento

USCITA

Grandezze associabili: vedi tabellaTipo: uni e bidirezionale a zero reale e traslato, per carico d'uscita variabilePrecisione (EN 60688): cl.0,5 (potenza) - cl.1 (fattore di potenza) - ± 0,2Hz (frequenza)Ondulazione (EN 60688): ≤ 1%Tempo di risposta (EN 60688): ≤ 300msValori nominali di corrente: 0...5 - 5...0...5 - 0...10 - 10...0...10 -

0...20 - 20...0...20- 4...20mATensione disponibile: 16,5VCarico di uscita: ≤ 750Ω (20mA) - ≤ 1,5kΩ (10mA) - ≤ 3kΩ (5mA)

INPUT

Single phase, three phase network, 3 and 4 wire, balanced and unbalanced loadConnection: direct or by external VT and CT (with programmables ratios)VT and CT ratios: programmables, KVT x KCT ≤ 220.000 (In 5A) - ≤ 2.000.000 (In 1A)Three-phase voltage rating Un: 400V (phase – phase)Single-phase voltage: 50...300VCurrent rating In: 5A or 1AFrequency fn: 50HzExcessive input of short duration (EN 60688): 2Un/1s - 20In/1sRated burden (each phase): voltage ≤ 0,5VA - current ≤ 0,5VA

NOMINAL RANGE OF USE (EN 60688)

Voltage three-phase: 80...500V (phase – phase)Current: 0...120% InFrequency: 45...65HzPower factor: cosϕ 0,5...1...0,5- senϕ 0,5...1...0,5 Harmonic content: up to 16th harmonic

OUTPUT RANGE SETTING

Programmable: by keyPower corresponding to full scale: 50...150% pn∆ min. beginning - full scale: 25% pnwhere:Pn (nominal power) = Un x In x √3Un (nominal voltage) = 400V (direct connection) - 100V (external VT)In (nominal current) = 5A or 1A

POWER DEMAND

Measuring and display: power demand and power max. demandQuantity: active, reactive or apparent powerAveraging time period: selectable 5/8/10/15/20/30/60 minutesCalculation: Average on a selected time intervalMax. demand reset: manual, by keyboard

DISPLAY

Display type: LCDMeasurement display: subdivided on pages, with manual scrollEngineering units: automatic display according to the set VT and CT ratios

PROGRAMMING

Parameters programming: front keyboard, 3 keysHold of configuration parameters: non volatile memory

PROGRAMMABLE PARAMETERS

Connection: single phase - three phase network (3 - 4wire), balanced andunbalanced load External VT - CT: ratio KTA x KTV ≤ 220.000 (In 5A) - ≤ 900.000 (In 1A)Analog output: transduced quantity, beginning and full scale, standard outputPower demand: quantity, averaging time period, reset

OUTPUT

Associable quantities: see tableType: unidirectional and reversible, real or live zero for variable output loadAccuracy (EN 60688): cl.0,5 (power) - cl.1 (power factor) - ± 0,2Hz (frequency)Ripple content (EN 60688): ≤ 1%Response time (EN 60688): ≤ 300msCurrent rated values: 0...5 - 5...0...5 - 0...10 - 10...0...10 -

0...20 - 20...0...20- 4...20mACompliance voltage: 16,5VOutput load: ≤ 750Ω (20mA) - ≤ 1,5kΩ (10mA) - ≤ 3kΩ (5mA)

NT51

4 04

- 20

10 5

aEd

.pag

.3/6

16

Page 17: First National Pakistan

Valori nominali di tensione: 0...10V - 10...0...10 - 1...5VCarico di uscita: ≥ 5kΩ

ALIMENTAZIONE AUSILIARIA

Valore nominale Uaux ca: 115 – 230 e 240VVariazione ammessa: 0,85…1,1UauxFrequenza nominale faux: 50HzVariazione ammessa: 47…63HzAutoconsumo: ≤ 3VAValore nominale Uaux cc: 20…150Vcc -150...250VccAutoconsumo: ≤ 3WProtezione contro l’inversione di polarità

PROVE DI ISOLAMENTO (EN 60439-1)

Categoria di installazione: IIIGrado di inquinamento: 2Tensione di riferimento per l’isolamento: 500VProva di tensione a impulso 5kV 1,2/50μs 0,5JCircuiti considerati: ingresso, uscita, alimentazione ausiliariaProva di tensione alternata 2,5kV valore efficace 50Hz/1 minCircuiti considerati: ingr.tensione, ingr.corrente, uscita, alimentazione ausiliaria Prova di tensione alternata 4kV valore efficace 50Hz/1 minCircuiti considerati: alimentazione ausiliaria verso tutti gli altri circuitiProva di tensione alternata 4kV valore efficace 50Hz/1 minCircuiti considerati: tutti i circuiti e massa

COMPATIBILITA' ELETTROMAGNETICA

Prove di emissione in accordo con EN61000-6-3Prove di immunità in accordo con EN61000-6-2

CONDIZIONI AMBIENTALI (EN 60688)

Gruppo di utilizzo: IITemperatura di riferimento: 15...30°CTemperatura di impiego: 0...50°CCondizione limite di temperatura: -10...55°C Temperatura di immagazzinaggio: -25...70°CAdatto all’utilizzo in clima tropicaleMassima potenza dissipata 1: ≤ 4,8W1 Per il dimensionamento termico dei quadri

CUSTODIA

Dimensioni: 8 moduli DIN 43880Connessioni: morsetti a vite per conduttore fino a 4mm2 (amperometriche 8mm 2)Montaggio: a incastro su profilato 35mmTipo profilato: a cappello TH35-15 (EN60715)Materiale custodia: policarbonato autoestinguenteGrado di protezione (EN 60529): IP52 (frontale), IP20 (morsetti)Peso: 480 grammi

Voltage rated values: 0...10V - 10...0...10 - 1...5VOutput load: > 5kΩ

AUXILIARY SUPPLY

Rated value Uaux ac: 115 – 230 and 240VTolerance: 0,85…1,1UauxRated frequency faux: 50HzTolerance: 47…63HzRated burden: ≤ 3VARated value Uaux dc: 20…150Vdc -150...250VdcRated burden: ≤ 3WProtected against incorrect polarity

TESTS OF INSULATION PROPERTIES (EN 60439-1)

Installation category: IIIPollution degree: 2Insulation voltage rating: 500VImpulse voltage test 5kV 1,2/50μs 0,5JConsidered circuits: input, output, auxiliary supply A.C. voltage test 2,5kV r.m.s. 50Hz/1 minConsidered circuits: voltage input , current input, output, auxiliary supplyA.C. voltage test 4kV r.m.s. 50Hz/1minConsidered circuits: auxiliary supply toward all circuitsA.C. voltage test 4kV r.m.s. 50Hz/1minConsidered circuits: all circuits and earth

ELECTROMAGNETIC COMPATIBILITY

Emission test according to EN61000-6-3Immunity test according to EN61000-6-2

ENVIRONMENTAL CONDITIONS (EN 60688)

Usage group: IIReference temperature: 15...30°CNominal temperature range: 0...50°CLimit temperature range: -10...55°CLimit temperature range for storage: -25...70°CSuitable for tropical climatesMax. power dissipation 1: ≤ 4,8W1 For switchboard thermal calculation

HOUSING

Dimensions: 8 module DIN 43880Connections: screw terminals for cable up to 4mm 2 (ammetric 8mm 2)Mounting: snap-on 35mm rail Rail type: top hat TH35-15 (EN60715)Housing material: self-extinguishing policarbonateProtection degree (EN 60529): Ip52 (front frame); Ip20 (terminals)Weight: 480 grams

NT51

4 04

- 20

10 5

aEd

.pag

.4/6

17

Page 18: First National Pakistan

SCHEMI D’INSERZIONE WIRING DIAGRAMS

2 5 7 9

OUTPUTINPUT

8 4 61 3

X

S1

P1L

N

11

2 11

1214 1517

+ -mA- V

13 20

AUX.SUPPLY

2121+ –CURRENTVOLTAGE

NT51

4 04

- 20

10 5

aEd

.pag

.5/6

2 5 7 98 4 61 3

X

XX

2 5 8

S1

P1

a

AL1

L2

L3

11

2 5 8

OUTPUTINPUT

1214 1517

+ -mA- V

13 20

AUX.SUPPLY

2121+ –CURRENTVOLTAGE

OUTPUT

1214 15

OUTPUT

17 131214 1517

+ -mA- V

13

+ -mA- V

V mA

2 5 7 98 4 61 3

XXX

X

XX

2 5 8

S1

P1

a

AL1

L2

L3

N

11

11

OUTPUTINPUT

1214 1517

+ -mA- V

13 20

AUX.SUPPLY

2121+ –CURRENTVOLTAGE

USCITA ANALOGICA ANALOG OUTPUT

LINEA MONOFASE • SINGLE PHASE

LINEA TRIFASE 3 FILI, CARICO EQUILIBRATO

THREE PHASE 3 WIRE, BALANCED LOAD

LINEA TRIFASE 4 FILI, CARICO EQUILIBRATO

THREE PHASE 4 WIRE, BALANCED LOAD

2 5 7 98 4 61 3

X

XX

S1

P1L1

L3

11

5 8

L2

OUTPUTINPUT

1214 1517

+ -mA- V

13 20

AUX.SUPPLY

2121+ –CURRENTVOLTAGE

S 250/97

S 250/93

S 250/100

S 250/95

18

Page 19: First National Pakistan

La I.M

.E. S

.p.A.

si ris

erva

in qu

alsias

i mom

ento,

di m

odific

are l

e car

atter

istich

e tec

niche

senz

a dar

ne pr

eavv

iso. /

I.M.E

. S.p.

A. re

serve

s the

right,

to m

odify

the t

echn

ical c

hara

cteris

tics w

ithou

t noti

ce.

NT51

4 04

- 20

10 5

aEd

.pag

.6/6

2 5 7 98 4 61 3

X

XX

2 5 8

a

AL1

L2

L3

11

2 5 8

S1

P1

S1

P1

OUTPUTINPUT

1214 1517

+ -mA- V

13 20

AUX.SUPPLY

2121+ –CURRENTVOLTAGE

2 5 7 98 4 61 3

X

XX

2 5 8

S1

P1

a

AL1

L2

L3

11

2 5 8

S1

P1

OUTPUTINPUT

1214 1517

+ -mA- V

13 20

AUX.SUPPLY

2121+ –CURRENTVOLTAGE

2 5 7 98 4 61 3

X

XX

2 5 8

S1

P1

a

AL1

L2

L3

11

2 5 8

S1

P1

OUTPUTINPUT

1214 1517

+ -mA- V

13 20

AUX.SUPPLY

2121+ –CURRENTVOLTAGE

LINEA TRIFASE 3 FILI, CARICO SQUILIBRATO

THREE PHASE 3 WIRE, UNBALANCED LOAD

140

89,5

69

45

DIMENSIONI DIMENSIONS

2 5 7 98 4 61 3

XXX

X

XX

2 5 8

S1

P1 S1

P1 S1

P1

a

AL1

L2

L3

N

11

11

OUTPUTINPUT

1214 1517

+ -mA- V

13 20

AUX.SUPPLY

2121+ –CURRENTVOLTAGE

LINEA TRIFASE 4 FILI, CARICO SQUILIBRATO

THREE PHASE 4 WIRE, UNBALANCED LOAD

S 250/99

S 250/94

S 250/96

S 250/98

19

Page 20: First National Pakistan

1.5 I 2

200 400

0

V

482

600

300

100 500

V

0...5mA

0...10mA

0...20mA

4...20mA

0...5V

0...10V

2...10V

NT555 03 - 2011 8aEd.pag.1/3

Tema U4Trasduttore di tensione alternata

2 Moduli

Misura del valor medio, taratura rapportata al valore efficace

Ingresso diretto fino a 500VUscita selezionabile in campo (7 portate)

Valori selezionabili: 0…5/10/20mA - 4…20mA

0…5/10V - 2…10V

Alternating voltage transducer2 Module

To measure average value, calibration according RMS valueDirect input up to 500VOutput selectable on field (7 ranges)

Selectable values: 0…5/10/20mA - 4…20mA 0…5/10V - 2…10V

TRASDUTTORITRANSDUCERS

Inserzione diretta o su TV/100V o TV/110V

Direct connection or on VT/100V or VT/110V

Uscita Output

20

Page 21: First National Pakistan

INGRESSO

Tensione nominale Un: 100 - 110 - 120 - 250 - 400 - 500V

Altri valori a richiesta

Frequenza nominale fn: 50Hz

Eccedenza di breve durata (EN 60688): 2Un/1s (max 600V)

Autoconsumo: ≤ 0,5VA

CAMPI NOMINALI DI UTILIZZO (EN 60688)

Frequenza: 47…63Hz (fn 50Hz)

Forma d'onda: sinusoidale, fattore di forma 1,11

INTERVALLO DI MISURA

Tensione: 0...120% Un

USCITA

Tipo: unidirezionale a zero reale, per carico d'uscita variabile

Precisione (EN 60688): classe 0,5

Ondulazione (EN 60688): ≤ 1%Tempo di risposta (EN 60688): ≤ 300 msValore nominale: selezionabile tramite dip switch (7 portate)

Valori nominali di corrente: 0…5 - 0…10 - 0…20mA - 4...20mA

Tensione disponibile: 15V

Carico di uscita: ≤ 750Ω (20mA) - ≤ 1,5kΩ (10mA) - ≤ 3kΩ (5mA)Valori nominali di tensione: 0…5 - 0…10 - 2…10V

Carico di uscita: ≥ 5kΩ

INPUT

Voltage rating Un: 100 - 110 -120 - 250 - 400 - 500V

Other values on request

Frequency rating fn: 50Hz

Excessive input of short duration (EN 60688): 2Un/1s (max 600V)

Rated burden: ≤ 0,5VA

NOMINAL RANGE OF USE (EN 60688)

Frequency: 47…63Hz (fn 50Hz)

Waveform: sinusoidal, form factor 1,11

MEASURING RANGE

Voltage: 0...120% Un

OUTPUT

Type: unidirectional, real or live zero for variable output load

Accuracy (EN 60688): class 0,5

Ripple content (EN 60688): ≤ 1%

Response time (EN 60688): ≤ 300 ms

Rated value: selectable by dip switch (7 ranges)

Current rated values: 0…5 - 0…10 - 0…20mA - 4...20mA

Compliance voltage: 15V

Output load: ≤ 750Ω (20mA) - ≤ 1,5kΩ(10mA) - ≤ 3kΩ (5mA)

Voltage rated values: 0…5 - 0…10 - 2…10V

Output load: ≥ 5kΩ NT555 03 - 2011 8aEd.pag.2/3

CODICI DI ORDINAZIONEORDERING CODE

INGRESSOINPUT

AL. AUSILIARIA AUX. SUPPLY

TM3U210 100V 115V ca / ac

TM3U220 110V 115V ca / ac

TM3U230 120V 115V ca / ac

TM3U270 250V 115V ca / ac

TM3U290 400V 115V ca / ac

TM3U2A0 440V 115V ca / ac

TM3U2C0 500V 115V ca / ac

TM3U310 100V 230 - 240V ca / ac

TM3U320 110V 230 - 240V ca / ac

TM3U330 120V 230 - 240V ca / ac

TM3U370 250V 230 - 240V ca / ac

TM3U390 400V 230 - 240V ca / ac

TM3U3A0 440V 230 - 240V ca / ac

TM3U3C0 500V 230 - 240V ca / ac

TM3UH10 100V 20...150V cc / dc

TM3UH20 110V 20...150V cc / dc

TM3UH30 120V 20...150V cc / dc

TM3UH70 250V 20...150V cc / dc

TM3UH90 400V 20...150V cc / dc

TM3UHA0 440V 20...150V cc / dc

TM3UHC0 500V 20...150V cc / dc

TM3UL10 100V 150...250V cc / dc

TM3UL20 110V 150...250V cc / dc

TM3UL30 120V 150...250V cc / dc

TM3UL70 250V 150...250V cc / dc

TM3UL90 400V 150...250V cc / dc

TM3ULA0 440V 150...250V cc / dc

TM3ULC0 500V 150...250V cc / dc

TM3U2P0 da precisare / on request 115V ca / ac

TM3U3P0 da precisare / on request 230 - 240V ca / ac

TM3UHP0 da precisare / on request 20...150V cc / dc

TM3ULP0 da precisare / on request 150...250V cc / dc

21

Page 22: First National Pakistan

ALIMENTAZIONE AUSILIARIA

Valore nominale Uaux ca: 48 - 115 – 230 e 240V

Altri valori a richiesta

Variazione ammessa: 0,9…1,1Uaux – 40...60V (Uaux 48V)

Frequenza nominale faux: 50Hz

Variazione ammessa: 47…63Hz

Autoconsumo: ≤ 3VAValore nominale Uaux cc: 20…150Vcc – 150…250Vcc

Autoconsumo: ≤ 1,5WProtezione contro l’inversione di polarità

ISOLAMENTO (EN 60439-1, EN61010-1)

Categoria di installazione: III

Grado di inquinamento: 2

Tensione di riferimento per l’isolamento: 600V

Prova di tensione a impulso 5kV 1,2/50µs 0,5J

Circuiti considerati: ingresso, uscita, al. ausiliaria

Prova a tensione alternata 2,5kV valore efficace 50Hz/1min

Circuiti considerati: ingresso, uscita, al. ausiliaria

Prova a tensione alternata 4kV valore efficace 50Hz/1min

Circuiti considerati: tutti i circuiti e massa

COMPATIBILITA' ELETTROMAGNETICA

Prove di emissione in accordo con EN 50081-1, EN 55011

Prove di immunità in accordo con EN 50082-2

Prova di disturbo ad alta frequenza, onda oscillatoria smorzata 1MHz (IEC255-4)

Tensione di prova: 2,5kV modo comune, 1kV modo serie

CONDIZIONI AMBIENTALI

Gruppo di utilizzo: II

Temperatura di riferimento: 15…30°C

Temperatura di impiego: 0…45°C

Condizione limite di temperatura: -10…55°C

Temperatura di magazzinaggio: -25…70°C

Umidità relativa: fino a 75%

Adatto all’utilizzo in clima tropicale

Massima potenza dissipata 1: ≤ 2,6W1Per il dimensionamento termico dei quadri

CUSTODIA

Dimensioni: 2 moduli DIN 43880

Connessioni: morsetti fissaggio a vite per conduttore fino a 4 mm2

Montaggio: a incastro su profilato 35mm

Tipo profilato: a cappello TH35-15 (EN60715)

Materiale custodia: makrolon autoestinguente

Grado di protezione (EN 60529): IP40 (frontale), IP20 (morsetti)

Peso: 200 grammi

AUXILIARY SUPPLY

Rated value Uaux ac: 48 - 115 – 230 and 240V

Other value on request

Tolerance: 0,9…1,1Uaux – 40...60V (Uaux 48V)

Rated frequency faux: 50Hz

Tolerance: 47…63Hz

Rated burden: ≤ 3VA

Rated value Uaux dc: 20…150Vdc – 150…250Vdc

Rated burden: ≤ 1,5W

Protected against incorrect polarity

INSULATION (EN 60439-1, EN61010-1)

Installation category: III

Pollution degree: 2

Insulation reference voltage: 600V

Impulse voltage test 5kV 1,2/50µs 0,5J

Considered circuits: input, output, aux. supply

A.C. voltage test 2,5kV r.m.s. 50Hz/1min

Considered circuits: input, output, aux. supply

A.C. voltage test 4kV r.m.s. 50Hz/1min

Considered circuits: all circuits and earth

ELECTROMAGNETIC COMPATIBILITY

Emission tests according to EN 50081-1, EN 55011

Immunity tests according to EN 50082-2

High frequency disturbance test, 1MHz damped oscillatory wave (IEC255-4)

Test voltage: 2,5kV common mode, 1kV series mode

ENVIRONMENTAL CONDITIONS

Usage group: II

Reference temperature: 15…30°C

Nominal temperature range: 0…45°C

Limit temperature range: -10…55°C

Limit temperature range for storage: -25…70°C

Relative humidity: up to 75%

Suitable for tropical climates

Max. power dissipation 1 : ≤ 2,6W1For switchboard thermal calculation

HOUSING

Dimensions: 2 module DIN 43880

Connections: screw terminals for cable up to 4 mm 2

Mounting: snap-on 35mm rail

Rail type: top hat TH35-15 (EN60715)

Housing material: self-extinguishing makrolon

Protection degree (EN 60529): IP40 (front frame), IP20 (terminals)

Weight: 200 gramsLa I.M.E. S.p.A. si riserva in qualsiasi mom

ento, di modificare le caratteristiche tecniche senza darne preavviso. / I.

M.E

. S.p

.A. r

eser

ves

the

right

, to

mod

ify th

e te

chni

cal

char

acte

ristic

s w

ithou

t not

ice.

SCHEMA D’INSERZIONE WIRING DIAGRAM DIMENSIONI DIMENSIONS

1 3

aA

bB

INPUT

mA V

1719

OUTPUT

– + –

1 3 20

AUX.SUPPLY

21(+) (–)

18

NT555 03 - 2011 8aEd.pag.3/3

S 306/24

22

Page 23: First National Pakistan

1mA

1.5 I2

200 400

0

A

482

600

300

100 500

A

0...5mA

0...10mA

0...20mA

4...20mA

0...5V

0...10V

2...10V

NT5

5402

-200

87a

Ed.

pag.

1/3

Tema I4Trasduttore di corrente alternata

2 Moduli

Misura del valor medio, taratura rapportata al valore efficace

Ingresso su TA/1A - TA/5AUscita selezionabile in campo (7 portate)

VVaalloorrii sseelleezziioonnaabbiillii:: 0…5/10/20mA - 4…20mA

0…5/10V - 2…10V

Alternating current transducer2 Module

To measure average value, calibration according RMS valueInput on CT/1A - CT/5AOutput selectable on field (7 ranges)

SSeelleeccttaabbllee vvaalluueess:: 0…5/10/20mA - 4…20mA 0…5/10V - 2…10V

TRASDUTTORITRANSDUCERS

Inserzione su TA/1A o TA/5A Connection up to CT/1A or CT/5A

Uscita Output

23

Page 24: First National Pakistan

INGRESSO

Corrente nominale In: 1 - 1,2 - 5 - 6A

Frequenza nominale fn: 50 - 400Hz

Eccedenza di breve durata (EN 60688): 20In/1s

Eccedenza continua: 3In

Autoconsumo: ≤ 0,2VA

CAMPI NOMINALI DI UTILIZZO (EN 60688)

Frequenza: 47…63Hz (fn 50Hz)

Forma d'onda: sinusoidale, fattore di forma 1,11

INTERVALLO DI MISURA

Corrente: 0…120%In

USCITA

Tipo: unidirezionale a zero reale o traslato, per carico d'uscita variabile

Precisione (EN 60688): classe 0,5

Ondulazione (EN 60688): ≤ 1%

Tempo di risposta (EN 60688): ≤ 300 ms

Valore nominale: selezionabile tramite dip switch (7 portate)

Valori nominali di corrente: 0…5 - 0…10 - 0…20mA - 4...20mA

Tensione disponibile: 15V

Carico di uscita: ≤ 750Ω (20mA) - ≤ 1,5kΩ (10mA) - ≤ 3kΩ (5mA)

Valori nominali di tensione: 0…5 - 0…10 - 2…10V

Carico di uscita: ≥ 5kΩ

ALIMENTAZIONE AUSILIARIA

Valore nominale Uaux ca: 48 - 115 – 230 e 240V

Altri valori a richiesta

Variazione ammessa: 0,9…1,1Uaux – 40...60V (Uaux 48V)

Frequenza nominale faux: 50Hz

Variazione ammessa: 47…63Hz

Autoconsumo: ≤ 3VA

Valore nominale Uaux cc: 20…150Vcc – 150…250Vcc

Autoconsumo: ≤ 1,5W

Protezione contro l’inversione di polarità

ISOLAMENTO (EN 60439-1)

Categoria di installazione: III

Grado di inquinamento: 2

Tensione di riferimento per l’isolamento: 450V

Prova di tensione a impulso 5kV 1,2/50µs 0,5J

Circuiti considerati: ingresso, uscita, al. ausiliaria

Prova a tensione alternata 2,5kV valore efficace 50Hz/1min

Circuiti considerati: ingresso, uscita, al. ausiliaria

Prova a tensione alternata 4kV valore efficace 50Hz/1min

Circuiti considerati: tutti i circuiti e massa

INPUT

Current rating In: 1 - 1,2 - 5 - 6A

Frequency rating fn: 50 - 400Hz

Excessive input of short duration (EN 60688): 20In/1s

Continuous excessive input: 3In

Rated burden: ≤ 0,2VA

NOMINAL RANGE OF USE (EN 60688)

Frequency: 47…63Hz (fn 50Hz)

Waveform: sinusoidal, form factor 1,11

MEASURING RANGE

Current: 0…120%In

OUTPUT

Type: unidirectional, real or live zero for variable output load

Accuracy (EN 60688): class 0,5

Ripple content (EN 60688): ≤ 1%

Response time (EN 60688): ≤ 300 ms

Rated value: selectable by dip switch (7 ranges)

Current rated values: 0…5 - 0…10 - 0…20mA - 4...20mA

Compliance voltage: 15V

Output load: ≤ 750Ω (20mA) - ≤ 1,5kΩ (10mA) - ≤ 3kΩ (5mA)

Voltage rated values: 0…5 - 0…10 - 2…10V

Output load: ≥ 5kΩ

AUXILIARY SUPPLY

Rated value Uaux ac: 48 - 115 – 230 and 240V

Other value on request

Tolerance: 0,9…1,1Uaux – 40...60V (Uaux 48V)

Rated frequency faux: 50Hz

Tolerance: 47…63Hz

Rated burden: ≤ 3VA

Rated value Uaux dc: 20…150Vdc – 150…250Vdc

Rated burden: ≤ 1,5W

Protected against incorrect polarity

INSULATION (EN 60439-1)

Installation category: III

Pollution degree: 2

Insulation reference voltage: 450V

Impulse voltage test 5kV 1,2/50µs 0,5J

Considered circuits: input, output, aux. supply

A.C. voltage test 2,5kV r.m.s. 50Hz/1min

Considered circuits: input, output, aux. supply

A.C. voltage test 4kV r.m.s. 50Hz/1min

Considered circuits: all circuits and earth NT5

54

02 -

2008

7a

Ed.

pag.

2/3

CODICI DI ORDINAZIONEORDERING CODE

INGRESSOINPUT

AL. AUSILIARIA AUX. SUPPLY

TM3I210 1A 115V ca / ac

TM3I230 5A 115V ca / ac

TM3I310 1A 230 - 240V ca / ac

TM3I330 5A 230 - 240V ca / ac

TM3IH10 1A 20...150V cc / dc

TM3IH30 5A 20...150V cc / dc

TM3IL10 1A 150...250V cc / dc

TM3IL30 5A 150...250V cc / dc

24

Page 25: First National Pakistan

ELECTROMAGNETIC COMPATIBILITY

Emission tests according to EN 50081-1, EN 55011

Immunity tests according to EN 50082-2

High frequency disturbance test, 1MHz damped oscillatory wave (IEC255-4)

Test voltage: 2,5kV common mode, 1kV series mode

ENVIRONMENTAL CONDITIONS

Usage group: II

Reference temperature: 15…30°C

Nominal temperature range: 0…45°C

Limit temperature range: -10…55°C

Limit temperature range for storage: -25…70°C

Relative humidity: up to 75%

Suitable for tropical climates

Max. power dissipation 1: ≤ 2,6W1For switchboard thermal calculation

HOUSING

Dimensions: 2 module DIN 43880

Connections: screw terminals for cable up to 4mm 2

Mounting: snap-on 35mm rail

Rail type: top hat TH35-15 (EN60715)

Housing material: self-extinguishing makrolon

Protection degree (EN 60529): IP40 (front frame), IP20 (terminals)

Weight: 200 grams

NT5

54

02 -

2008

7a

Ed.

pag.

3/3

La I.

M.E

. S.p

.A. s

i ris

erva

in q

uals

iasi

mom

ento

, di m

odifi

care

le c

arat

teris

tiche

tecn

iche

sen

za d

arne

pre

avvi

so. /

I.M

.E. S

.p.A

. res

erve

s th

e rig

ht, t

o m

odify

the

tech

nica

l ch

arac

teris

tics

with

out n

otic

e.

SCHEMA D’INSERZIONE WIRING DIAGRAM DIMENSIONI DIMENSIONS

mA V

L

N

S1

P1

1 3

INPUT

1719

OUTPUT

– + –

1 3 20

AUX.SUPPLY

2121(+) (–)

18

S 306/23

COMPATIBILITA' ELETTROMAGNETICA

Prove di emissione in accordo con EN 50081-1, EN 55011

Prove di immunità in accordo con EN 50082-2

Prova di disturbo ad alta frequenza, onda oscillatoria smorzata 1MHz (IEC255-4)

Tensione di prova: 2,5kV modo comune, 1kV modo serie

CONDIZIONI AMBIENTALI

Gruppo di utilizzo: II

Temperatura di riferimento: 15…30°C

Temperatura di impiego: 0…45°C

Condizione limite di temperatura: -10…55°C

Temperatura di magazzinaggio: -25…70°C

Umidità relativa: fino a 75%

Adatto all’utilizzo in clima tropicale

Massima potenza dissipata1: ≤ 2,6W1Per il dimensionamento termico dei quadri

CUSTODIA

Dimensioni: 2 moduli DIN 43880

Connessioni: morsetti fissaggio a vite per conduttore fino a 4mm2

Montaggio: a incastro su profilato 35mm

Tipo profilato: a cappello TH35-15 (EN60715)

Materiale custodia: makrolon autoestinguente

Grado di protezione (EN 60529): IP40 (frontale), IP20 (morsetti)

Peso: 200 grammi

25

Page 26: First National Pakistan

NT791 01 - 2013 0 Ed.

pag.1/4

ANIndicatori AnalogiciAQMrad

per tensione alternata48x48mm72x72mm96x96mm

Indicazione diretta della tensione di ingresso odella tensione primaria del TV esterno

Equipaggio a bobina mobile,con accessorio raddrizzatoreIngresso diretto da 10 a 600V

Ingresso da TV esterno /100V - /110VAmpiezza scala 240°

Precisione cl.1,5

AQMradAnalog Meters for alternating voltage48x48mm72x72mm96x96mm

Direct indication of input voltage or primaryvoltage of external VTMoving coil equipmentwith rectifier accessoryDirect connection 10...600VInput by external VT /100V - /110VScale lenght 240°Accuracy class 1,5

INDICATORI ANALOGICIANALOG METERS

Scala intercambiabileInterchange scales

AQ72Mrad - AQ96Mrad Coprimorsetto di serieStandard terminal cover

26

Page 27: First National Pakistan

Opzione / Option Suffisso / Suffix Esempio / Example

TropicalizzatoTropicalized

Aggiungere “1” al codice standardAdd “1” at the end of standard code AN65DDC300 ⇒ AN65DDC3001

Protezione frontale IP54IP54 Front protection

Aggiungere “3” al codice standardAdd “3” at the end of standard code AN65DDC300 ⇒ AN65DDC3003

Altre esecuzioni disponibili su tutti i modelli: Other executions available on all models:

NT791 01 - 2013 0 Ed.

pag.2/4

INSERZIONE SU TV

Dati da indicare oltre al codice di ordinazione

Scala e rapporto TV

Il valore della scala dovrà corrispondere al prodotto tra il valore di portata

scelto e il rapporto del TV

Es. portata 120V – rapporto TV 500/100V = valore scala = (120 x 500) : 100 = 600V

Solo per cod. AN54P11111 - AN64P11111 - AN74P11111: scala e rapporto TV

Es. scala 0...300V – rapporto TV 230/100V

VISUALIZZAZIONE

Scala: intercambiabile, con inserimento guidato a protezione dell’indice e cassettino

di chiusura

Colore scala: fondo bianco, divisioni e numerazione nere

A richiesta scale personalizzate

Opzioni: segno rosso di riferimento

Ampiezza scala: 240°

Tracciatura standard: 0...Un

Colore indice: nero

Opzione: indice rosso di riferimento (regolabile)

CONNECTION ON VT

Data to be shown in addition to ordering code

Scale and VT ratio

The scale value must correspond to the result between the chosen range

value and the VT ratio

Ex. range 120V – VT ratio 500/100V = scale value = (120 x 500) : 100 = 600V

Only for code AN54P11111 - AN64P11111 - AN74P11111: scale and VT ratio

Ex. scale 0...300V – VT ratio 230/100V

DISPLAY

Scale: interchangeable, easy-insertion to protect the pointer as wellas relevant

closing slip

Scale colour: white background, black divisions and numbering

Customized scales upon request

Option: reference red mark

Scale length: 240°

Standard scale marking: 0...Un

Pointer colour: black

Option: (adjustable) reference red pointer

InserzioneConnection 0...In - DIRETTA / DIRECT

ModelloModel AQ48Mrad AQ72Mrad AQ96Mrad

DimensioniDimensions 48 x 48 72 x 72 96 x 96

PortataRange CODICE DI ORDINAZIONE / ORDERING CODE

10V AN54DDB100 AN64DDB100 AN74DDB100

15V AN54DDB150 AN64DDB150 AN74DDB150

25V AN54DDB250 AN64DDB250 AN74DDB250

30V AN54DDB300 AN64DDB300 AN74DDB300

40V AN54DDB400 AN64DDB400 AN74DDB400

60V AN54DDB600 AN64DDB600 AN74DDB600

100V AN54DDC100 AN64DDC100 AN74DDC100

150V AN54DDC150 AN64DDC150 AN74DDC150

200V AN54DDC200 AN64DDC200 AN74DDC200

250V AN54DDC250 AN64DDC250 AN74DDC250

300V AN54DDC300 AN64DDC300 AN74DDC300

400V AN54DDC400 AN64DDC400 AN74DDC400

500V AN54DDC500 AN64DDC500 AN74DDC500

600V AN54DDC600 AN64DDC600 AN74DDC600

InserzioneConnection da TV / on VT

ModelloModel AQ48Mrad AQ72Mrad AQ96Mrad

DimensioniDimensions 48 x 48 72 x 72 96 x 96

PortataRange CODICE DI ORDINAZIONE / ORDERING CODE

100V AN54111111 AN64111111 AN74111111

120V AN54211111 AN64211111 AN74211111

125V AN54311111 AN64311111 AN74311111

131,58V AN54411111 AN64411111 AN74411111

133,33V AN54511111 AN64511111 AN74511111

136,36V AN54611111 AN64611111 AN74611111

150V AN54711111 AN64711111 AN74711111

altri valoriother values

AN54P11111 AN64P11111 AN74P11111

27

Page 28: First National Pakistan

NT791 01 - 2013 0 Ed.

pag.3/4

INGRESSO

Grandezza: tensione alternata monofase

Inserzione: diretta (S 250/124 - /141) o da TV esterno (S 250/125 - /142)

Misura: valor medio, rapportato al valore efficace, fattore di forma 1,11

Tensione nominale Un

Inserzione diretta: 10...600V

Inserzione da TV esterno: TV/100V - TV/110V

Sovraccarico permanente: 1,2Un

Sovraccarico istantaneo: 10Un/5s

Frequenza nominale fn: 50Hz

Frequenza di funzionamento: 45...65Hz

Precisione (EN/IEC 60051): cl.1,5

Autoconsumo: ≃1mA

ISOLAMENTO (EN/IEC 61010-1)

Categoria di installazione: III

Grado di inquinamento: 2

Tensione di riferimento per l’isolamento: 600V (Fase - Neutro)

Prova a tensione alternata 4kV valore efficace 50Hz/5s

Circuiti considerati: tutti i circuiti verso terra

CONDIZIONI AMBIENTALI

Temperatura di riferimento: 23°C

Campo nominale di utilizzo: 5...40°C

Campo di funzionamento: -25...50°C

Campo limite per l’immagazzinamento e trasporto: -40...80°C

Prova di vibrazioni: in accordo con EN/IEC 60051-1 paragrafo 7.6

Prova d’urto: in accordo con EN/IEC 60051-1 paragrafo 7.6

CUSTODIA

Fissaggio: incasso

Foratura pannello: vedi tabella

Frontale: vedi tabella

Profondità: vedi tabella

Connessioni: morsetti a vite / faston 6,3 x 0,8mm (AQ48Mrad solo faston)

Materiale custodia: policarbonato autoestinguente

Grado di protezione(EN/IEC 60529): IP52 frontale, IP20 morsetti (con coprimorsetto)

Opzione: protezione frontale IP54

Peso: vedi tabella

INPUT

Quantity: single-phase, alternating voltage

Connection: direct (S 250/124 - /141) or by external VT (S 250/125 - /142)

Measure: average value measurement, related to r.m.s value, form factor 1,11

Rating voltage Un

Direct connection: 10...600V

Connection by VT external: VT/100V - VT/110V

Continuous overload: 1,2Un

Istantaneous overload: 10Un/5s

Rating frequency fn: 50Hz

Working frequency: 45..65Hz

Accuracy (EN/IEC 60051): class 1,5

Rated burden: ≃1mA

INSULATION (EN/IEC 61010-1)

Installation category: III

Pollution degree: 2

Insulation rating voltage: 600V (Phase - Neutral)

A.C. voltage test 4kV r.m.s. 50Hz/5s

Considered circuits : all circuits and earth

ENVIRONMENTAL CONDITIONS

Reference temperature: 23°C

Nominal range of use: 5...40°C

Operating range: -25...50°C

Limit range for storage and transport: -40...80°C

Vibration test: according to EN/IEC 60051-1 paragraph 7.6

Shock test: according to EN/IEC 60051-1 paragraph 7.6

HOUSING

Mounting: flush mounting

Panel cutout: see table

Front frame: see table

Depth: see table

Connections: screw terminal / fast-on 6,3 x 0,8mm (AQ48Mrad only fast-on)

Housing material: self-extinguishing policarbonate

Protection degree (EN/IEC 60529): IP52 front frame, IP20 terminals (with protection)

Option: protection IP54 front frame

Weight: see table

28

Page 29: First National Pakistan

LOAD∼

V

Rad

S 250/141

a

A

b

B

LOAD∼

V

Rad

S 250/142

NT791 01 - 2013 0 Ed.

pag.4/4

La I.M.E. S.p.A. si riserva in qualsiasi mom

ento, di modificare le caratteristiche tecniche senza darne preavviso. / I.

M.E

. S.p

.A. r

eser

ves

the

right

, to

mod

ify th

e te

chni

cal

char

acte

ristic

s w

ithou

t not

ice.

SCHEMI D’INSERZIONE WIRING DIAGRAMS

DIMENSIONI DIMENSIONS

B

AB

A

C

88 98 78

43 52

3,5

LOAD∼

V

S 250/124

a

A

b

B

LOAD∼

V

S 250/125

Accessorio raddrizzatoreper AQ48M/rad

Rectifier accessoryfor AQ48M/rad

Modello / Model Schemi / Diagrams A B C Peso / Weight

AQ48Mrad S 250 / 130 - 131 48x48 45x45 85,5 250 gr.

AQ72MradS 250 / 132 -133

72x72 68x68 84 300 gr.

AQ96Mrad 96x96 92x92 84 350 gr.

AQ48Mrad AQ48Mrad

AQ72/96Mrad AQ72/96Mrad

29

Page 30: First National Pakistan

NT790 12 - 2012 1aEd.pag.1/5

ANIndicatori AnalogiciAQMrad

per corrente alternata48x48mm72x72mm96x96mm

Indicazione diretta della corrente di ingresso odella corrente primaria del TA esterno

Equipaggio a bobina mobile, con accessorio raddrizzatore

Ingresso diretto 1...5AIngresso da TA esterno /5A oppure /1A

Versione per avviamento motore 2In opp. 5InAmpiezza scala 240°

Precisione cl.1,5

AQMradAnalog Meters for alternating current48x48mm72x72mm96x96mm

Direct indication of input current orprimary current of external CTMoving coil equipment,with rectifier accessoryDirect connection 1...5AInput by external CT /5A or /1AVersion for starting motor 2In or 5InScale length 240°Accuracy class 1,5

INDICATORI ANALOGICIANALOG METERS

2In

5In

In

Scala intercambiabileInterchange scales

AQ72M - AQ96M Coprimorsetto di serieStandard terminal cover

30

Page 31: First National Pakistan

NT790 12 - 2012 1aEd.pag.2/5

InserzioneConnection 0...In - DIRETTA / DIRECT

ModelloModel AQ48Mrad AQ72Mrad AQ96Mrad

DimensioniDimensions 48 x 48 72 x 72 96 x 96

PortataRange CODICE DI ORDINAZIONE / ORDERING CODE

1A AN51D1A100 AN61D1A100 AN71D1A100

2,5A AN51D1A250 AN61D1A250 AN71D1A250

5A AN51D1A500 AN61D1A500 AN71D1A500

Opzione / Option Suffisso / Suffix Esempio / Example

TropicalizzatoTropicalized

Aggiungere “1” al codice standardAdd “1” at the end of standard code AN6151C500 ⇒ AN6151C5001

Protezione frontale IP54IP54 Front protection

Aggiungere “3” al codice standardAdd “3” at the end of standard code AN6151C500 ⇒ AN6151C5003

Altre esecuzioni disponibili su tutti i modelli: Other executions available on all models:

InserzioneConnection da TA/ 5A on CT/5A da TA/ 1A on CT/1A

Scala / Scale 0...In 0...InModello / Model AQ48Mrad AQ72Mrad AQ96Mrad AQ48Mrad AQ72Mrad AQ96Mrad

DimensioniDimensions 48 x 48 72 x 72 96 x 96 48 x 48 72 x 72 96 x 96

Portata / Range CODICE DI ORDINAZIONE / ORDERING CODE

Senza scalaWithout scale AN51510000 AN61510000 AN71510000 AN51110000 AN61110000 AN7111000

5A AN51D1A500 AN61D1A500 AN71D1A500 AN5111A500 AN6111A500 AN7111A500

10A AN5151B100 AN6151B100 AN7151B100 AN5111B100 AN6111B100 AN7111B100

15A AN5151B150 AN6151B150 AN7151B150 AN5111B150 AN6111B150 AN7111B150

20A AN5151B200 AN6151B200 AN7151B200 AN5111B200 AN6111B200 AN7111B200

25A AN5151B250 AN6151B250 AN7151B250 AN5111B250 AN6111B250 AN7111B250

30A AN5151B300 AN6151B300 AN7151B300 AN5111B300 AN6111B300 AN7111B300

40A AN5151B400 AN6151B400 AN7151B400 AN5111B400 AN6111B400 AN7111B400

50A AN5151B500 AN6151B500 AN7151B500 AN5111B500 AN6111B500 AN7111B500

60A AN5151B600 AN6151B600 AN7151B600 AN5111B600 AN6111B600 AN7111B600

70A AN5151B700 AN6151B700 AN7151B700 AN5111B700 AN6111B700 AN7111B700

75A AN5151B750 AN6151B750 AN7151B750 AN5111B750 AN6111B750 AN7111B750

80A AN5151B800 AN6151B800 AN7151B800 AN5111B800 AN6111B800 AN7111B800

100A AN5151C100 AN6151C100 AN7151C100 AN5111C100 AN6111C100 AN7111C100

120A AN5151C120 AN6151C120 AN7151C120 AN5111C120 AN6111C120 AN7111C120

125A AN5151C125 AN6151C125 AN7151C125 AN5111C125 AN6111C125 AN7111C125

150A AN5151C150 AN6151C150 AN7151C150 AN5111C150 AN6111C150 AN7111C150

160A AN5151C160 AN6151C160 AN7151C160 AN5111C160 AN6111C160 AN7111C160

200A AN5151C200 AN6151C200 AN7151C200 AN5111C200 AN6111C200 AN7111C200

250A AN5151C250 AN6151C250 AN7151C250 AN5111C250 AN6111C250 AN7111C250

300A AN5151C300 AN6151C300 AN7151C300 AN5111C300 AN6111C300 AN7111C300

400A AN5151C400 AN6151C400 AN7151C400 AN5111C400 AN6111C400 AN7111C400

500A AN5151C500 AN6151C500 AN7151C500 AN5111C500 AN6111C500 AN7111C500

600A AN5151C600 AN6151C600 AN7151C600 AN5111C600 AN6111C600 AN7111C600

700A AN5151C700 AN6151C700 AN7151C700 AN5111C700 AN6111C700 AN7111C700

750A AN5151C750 AN6151C750 AN7151C750 AN5111C750 AN6111C750 AN7111C750

800A AN5151C800 AN6151C800 AN7151C800 AN5111C800 AN6111C800 AN7111C800

1.000A AN5151D100 AN6151D100 AN7151D100 AN5111D100 AN6111D100 AN7111D100

1.200A AN5151D120 AN6151D120 AN7151D120 AN5111D120 AN6111D120 AN7111D120

1.250A AN5151D125 AN6151D125 AN7151D125 AN5111D125 AN6111D125 AN7111D125

1.500A AN5151D150 AN6151D150 AN7151D150 AN5111D150 AN6111D150 AN7111D150

1.600A AN5151D160 AN6151D160 AN7151D160 AN5111D160 AN6111D160 AN7111D160

2.000A AN5151D200 AN6151D200 AN7151D200 AN5111D200 AN6111D200 AN7111D200

2.500A AN5151D250 AN6151D250 AN7151D250 AN5111D250 AN6111D250 AN7111D250

3.000A AN5151D300 AN6151D300 AN7151D300 AN5111D300 AN6111D300 AN7111D300

4.000A AN5151D400 AN6151D400 AN7151D400 AN5111D400 AN6111D400 AN7111D400

5.000A AN5151D500 AN6151D500 AN7151D500 AN5111D500 AN6111D500 AN7111D500

6.000A AN5151D600 AN6151D600 AN7151D600 AN5111D600 AN6111D600 AN7111D600

8.000A AN5151D800 AN6151D800 AN7151D800 AN5111D800 AN6111D800 AN7111D800

10.000A AN5151E100 AN6151E100 AN7151E100 AN5111E100 AN6111E100 AN7111E100

31

Page 32: First National Pakistan

NT790 12 - 2012 1aEd.pag.3/5

Modello Model

Scala per / Scale forAQ48Mrad

Scala per / Scale forAQ72Mrad

Scala per / Scale forAQ96Mrad

ScalaScale

0...In per amperometri su TA/5A / for CT/5A ammeters

Portata / Range CODICE DI ORDINAZIONE / ORDERING CODE

5/5A SC51D1A500 SC61D1A500 SC71D1A500

10/5A SC5151B100 SC6151B100 SC7151B100

15/5A SC5151B150 SC6151B150 SC7151B150

20/5A SC5151B200 SC6151B200 SC7151B200

25/5A SC5151B250 SC6151B250 SC7151B250

30/5A SC5151B300 SC6151B300 SC7151B300

40/5A SC5151B400 SC6151B400 SC7151B400

50/5A SC5151B500 SC6151B500 SC7151B500

60/5A SC5151B600 SC6151B600 SC7151B600

70/5A SC5151B700 SC6151B700 SC7151B700

75/5A SC5151B750 SC6151B750 SC7151B750

80/5A SC5151B800 SC6151B800 SC7151B800

100/5A SC5151C100 SC6151C100 SC7151C100

120/5A SC5151C120 SC6151C120 SC7151C120

125/5A SC5151C125 SC6151C125 SC7151C125

150/5A SC5151C150 SC6151C150 SC7151C150

160/5A SC5151C160 SC6151C160 SC7151C160

200/5A SC5151C200 SC6151C200 SC7151C200

250/5A SC5151C250 SC6151C250 SC7151C250

300/5A SC5151C300 SC6151C300 SC7151C300

400/5A SC5151C400 SC6151C400 SC7151C400

500/5A SC5151C500 SC6151C500 SC7151C500

600/5A SC5151C600 SC6151C600 SC7151C600

700/5A SC5151C700 SC6151C700 SC7151C700

750/5A SC5151C750 SC6151C750 SC7151C700

800/5A SC5151C800 SC6151C800 SC7151C800

1000/5A SC5151D100 SC6151D100 SC7151D100

1200/5A SC5151D120 SC6151D120 SC7151D120

1250/5A SC5151D125 SC6151D125 SC7151D125

1500/5A SC5151D150 SC6151D150 SC7151D150

1600/5A SC5151D160 SC6151D160 SC7151D160

2000/5A SC5151D200 SC6151D200 SC7151D160

2500/5A SC5151D250 SC6151D250 SC7151D250

3000/5A SC5151D300 SC6151D300 SC7151D300

4000/5A SC5151D400 SC6151D400 SC7151D400

5000/5A SC5151D500 SC6151D500 SC7151D500

6000/5A SC5151D600 SC6151D600 SC7151D600

8000/5A SC5151D800 SC6151D800 SC7151D800

10000/5A SC5151E100 SC6151E100 SC7151E100

Versione / Version Suffisso / Suffix Esempio / Example

Scala ristretta al fondo 2In2In overscale

Sostituire la 6a cifra del codice (1) con 2Replace the 6a digit of the code (1) with 2 SC5151C500 ⇒ SC5152C500

Scala ristretta al fondo 5In5In overscale

Sostituire la 6a cifra del codice (1) con 5Replace the 6a digit of the code (1) with 5 SC5151C500 ⇒ SC5155C500

Inserzione su TA/1ACT/1A connection

Sostituire la 5a cifra del codice (5) con 1Replace the 5a digit of the code (5) with 1 SC5151C500 ⇒ SC5111C500

Altre esecuzioni disponibili su tutti i modelli: Other executions available on all models:

32

Page 33: First National Pakistan

NT790 12 - 2012 1aEd.pag.4/5

VISUALIZZAZIONE

Scala: intercambiabile, con inserimento guidato a protezione dell’indice e cassettino

di chiusura

Colore scala: fondo bianco, divisioni e numerazione nere

A richiesta scale personalizzate

Opzioni: segno rosso di riferimento

Ampiezza scala: 240°

Tracciatura standard: 0...In

Tracciatura avviamento motore: 0...In...2In opp. 0...In...5In

Colore indice: nero

Opzione: indice rosso di riferimento (regolabile)

INGRESSO

Grandezza: corrente alternata monofase

Inserzione: diretta (S 250/130 - /132) o da TA esterno /5A opp. /1A (S 250/131 - /133)

Misura: valor medio, rapportato al valore efficace, fattore di forma 1,11

Corrente nominale In

Inserzione diretta: 1...5A (vedi tabella)

Inserzione da TA esterno: 5A oppure 1A

Sovraccarico permanente: 1,2In

Sovraccarico istantaneo: 10In/5s

Frequenza nominale fn: 50Hz

Frequenza di funzionamento: 45...65Hz

Precisione (EN/IEC 60051): cl.1,5

Autoconsumo: ≤ 1,1VA

ISOLAMENTO (EN/IEC 61010-1)

Categoria di installazione: III

Grado di inquinamento: 2

Tensione di riferimento per l’isolamento: 600V (Fase - Neutro)

Prova a tensione alternata 4kV valore efficace 50Hz/5s

Circuiti considerati: tutti i circuiti verso terra

CONDIZIONI AMBIENTALI

Temperatura di riferimento: 23°C

Campo nominale di utilizzo: 5...40°C

Campo di funzionamento: -25...50°C

Campo limite per l’immagazzinamento e trasporto: -40...80°C

Prova di vibrazioni: in accordo con EN/IEC 60051-1 paragrafo 7.6

Prova d’urto: in accordo con EN/IEC 60051-1 paragrafo 7.6

CUSTODIA

Fissaggio: incasso

Foratura pannello: vedi tabella

Frontale: vedi tabella

Profondità: vedi tabella

Connessioni: morsetti a vite / faston 6,3 x 0,8mm (AQ48Mrad solo faston)

Materiale custodia: policarbonato autoestinguente

Grado di protezione(EN/IEC 60529): IP52 frontale, IP20 morsetti (con coprimorsetto)

Opzione: protezione frontale IP54

Peso: vedi tabella

DISPLAY

Scale: interchangeable, easy-insertion to protect the pointer as well as relevant

closing slip

Scale colour: white background, black divisions and numbering

Customized scales upon request

Option: reference red mark

Scale length: 240°

Standard scale marking: 0...In

Motor startup marking scale: 0...In...2In or 0...In...5In

Pointer colour: black

Option: (adjustable) reference red pointer

INPUT

Quantity: single-phase, alternating current

Connection: direct (S 250/130 - /132) or by external CT /5A or /1A (S 250/131 - /133)

Measure: average value measurement, related to r.m.s value, form factor 1,11

Rating current In

Direct connection: 1...5A (see table)

Connection by CT external: 5A or 1A

Continuous overload: 1,2In

Instantaneous overload: 10In/5s

Rating frequency fn: 50Hz

Working frequency: 45..65Hz

Accuracy (EN/IEC 60051): class 1,5

Rated burden: ≤ 1,1VA

INSULATION (EN/IEC 61010-1)

Installation category: III

Pollution degree: 2

Insulation voltage rating: 600V (Phase - Neutral)

A.C. voltage test 4kV r.m.s. 50Hz/5s

Considered circuits : all circuits and earth

ENVIRONMENTAL CONDITIONS

Reference temperature: 23°C

Nominal range of use: 5...40°C

Operating range: -25...50°C

Limit range for storage and transport: -40...80°C

Vibration test: according to EN/IEC 60051-1 paragraph 7.6

Shock test: according to EN/IEC 60051-1 paragraph 7.6

HOUSING

Mounting: flush mounting

Panel cutout: see table

Front frame: see table

Depth: see table

Connections: screw terminal / fast-on 6,3 x 0,8mm (AQ48Mrad only fast-on)

Housing material: self-extinguishing policarbonate

Protection degree (EN/IEC 60529): IP52 front frame, IP20 terminals (with protection)

Option: protection IP54 front frame

Weight: see table

33

Page 34: First National Pakistan

NT790 12 - 2012 1aEd.pag.5/5

SCHEMI D’INSERZIONE WIRING DIAGRAMS

LOAD∼

A

Rad

S 250/130

S1

P1

S2

P2 LOAD∼

A

Rad

S 250/131

DIMENSIONI DIMENSIONS

B

AB

A

C

88 98 78

43 52

3,5

LOAD∼

A

S 250/132

S1

P1

S2

P2 LOAD∼

A

S 250/133

Accessorio raddrizzatoreper AQ48M/rad

Rectifier accessoryfor AQ48M/rad

La I.M.E. S.p.A. si riserva in qualsiasi mom

ento, di modificare le caratteristiche tecniche senza darne preavviso. / I.

M.E

. S.p

.A. r

eser

ves

the

right

, to

mod

ify th

e te

chni

cal

char

acte

ristic

s w

ithou

t not

ice.

Modello / Model Schemi / Diagrams A B C Peso / Weight

AQ48Mrad S 250 / 130 - 131 48x48 45x45 85,5 250 gr.

AQ72MradS 250 / 132 -133

72x72 68x68 84 300 gr.

AQ96Mrad 96x96 92x92 84 350 gr.

AQ48Mrad AQ48Mrad

AQ72/96Mrad AQ72/96Mrad

34

Page 35: First National Pakistan

35

Page 36: First National Pakistan

ENERGY MEASUREMENT AND CONTROL www.algodue.com

Technical Information

1SAUUPM3H157 May 2005

General Description

The UPM315 is a multifunction metering device with

advanced functionality features, suitable for electrical

parameters measurement and power quality analysis .

It provides accurate True RMS values on graphic LCD display,

or via communication port. Six or more parameters displayed

simultaneously give the complete situation of the electrical

line at first sight.

The UPM315 performs clear graphical functions such as:

waveforms of voltage and current, harmonic spectrum, phasor

diagrams and trends of measured values.

A simple menu structure makes the instrument easy-to-use

and allows a quick check of the instrument set-up and memory

status. Three languages can be selected easily: English,

German, Italian.

The backlighted LCD display is highly efficient therefore it

guarantees perfect visibility in all light conditions.

The UPM315 offers small size and a variety of mounting

combinations making it suitable for new installations as well

as retrofit applications. The power meter fits both in 4” round

and DIN96 square cutouts. The tranducer unit can be

mounted on opposite side of the display, on any flat surface

or onto a 35mm DIN rail.

n DIN 96 & ANSI 4” Cutout for New or Retrofit

Panels

n Highly Sofisticated Power Meter Providing

Advanced Functionality Features

n Large Graphic LCD Display with Excellent

Visibility

n UL Recognized Under UL61010B-1 and CAN/

CSA-C22.2 No.1010.1-92

n THD Even, Odd and Individual FFT Harmonic

Analysis up to 50th Order

n Power and Current Demand Calculation

n On-Board Memory up to 2MB

n Programmable Min/Max & Energy Data Logging

n Event and Alarm Recording, Waveform Capture,

Waveform Display, Phasor Diagrams, Historical

Trending, Time-of-Use and more....

UPM315DIN 96x96 and ANSI 4” Power Meter

Applications

••••• Switchboards, gensets, motor control centers, etc.

• Power monitoring & control systems

• Individual machine load monitoring

• Power demand analysis and management

• Harmonics monitoring

• Remote metering and cost allocation

Benefits

••••• The UPM315 provides hundreds of accurate True RMS

metering values at low cost.

• It provides peak average current and power demand

information. This data is essential to work out proper

strategies aimed at avoiding uncontrolled power peaks

and consequent penalties.

• Being ultra-compact with flexible mounting, the UPM315

is suitable for replacing conventional meters. It fits in ANSI

4” and DIN 96 cutout allowing retrofit to existing

equipment.

• The UPM315 offers time and cost saving on mounting,

compared to many individual single-function

instruments.

• The recorded data allows to generate on a PC

consumption profiles, logged values trends, event and

alarm reporting, cost allocation and reports as well as

to identify critical values.

• Via communication port it is possible to read and log on

a PC all the readings and download the stored data.

CONFIGURATIONS

1) DIN 96x96 compact instrument

2) ANSI 4” instrument

3) ANSI 4” display + remote tranducer

4) Transducer without display

36

Page 37: First National Pakistan

ENERGY MEASUREMENT AND CONTROL www.algodue.com

UPM315 - DIN 96x96 and ANSI 4” Power Meter

Main Features

Measurements

••••• Three-phase 3-wire or 4-wire unbalanced load operation

• Direct measurement up to 600 (750)VAC

• Programmable 1A / 5A current full scale

••••• True RMS metering provides accurate measurement even

for distorted waveform

• Fully bi-directional, four-quadrant readings. 10 energy

counters are available, the apparent power/energy is

splitted in four counters: import lagging, import leading,

export lagging, export leading

• Volts, Amps, Power, PF, Frequency, Energy, Min/Max

values, Demand, Harmonics, etc. The full version

instrument provides more than 600 measured/calculated

parameters and shows on the LCD more than 35 graphical

pages

• Individual & total harmonic distortion for voltage and

current up to the 50th order. The harmonic content is

represented like even, odd and total

• Advanced waveform capture function. The instrument can

store, after a trigger, up to 200 waveforms with a resolution

from 16 to 128 samples (depending on the number of

waveforms).

The trigger can be programmed on a digital input or output

change, on a set point crossing or the capture can be

started from the keypad.

The stored waweform is downloadable through the

communication port.

Modularity

• Two slots for plug-in options boards

• The tranducers version, the ANSI 4” display unit and the

compact DIN 96 instrument allow various mounting

combinations to fit the requirements of new installations

as well as retrofit applications. The “Physical

Configurations” page shows the mounting combinations

Graphics

• The excellent graphical display performs clear graphical

representations allowing an immediate comprehension

of the measured parameters. Are displayed the voltage

and current waveforms, the harmonic spectrum and the

phasor diagrams.

• Moreover 6 measured values can be represented as a

graphical trend on the display. The scale of the trend can

be selected between 15 min, 1 hour, 1 day and 1 month.

On-Board Memory

• 128k or 2MBytes non-volatile memory for data storage

• Programmable start/stop time of recordings

• Wraparound or Fill (FIFO/Stack) selectable recording mode

• Min/Avg/Max logging every 1, 5, 10, 15, 30, 60 minutes,

programmable up to 8 selectable parameters

• Total and daily energy consumption recording. The

individual consumption of more than 300 days is

recorded.

• Time-of-Use (TOU) programmable data recording. The

TOU function stores the energy consumption in different

registers according the programmed time-scheme. A

group of 120 registers gives the situation of the previous

and current day, and of the previous and current month.

This feature is designed to fit different tariff structures.

It’s possible to program up to 10 daily tariff schedules

containing up to 3 tariffs and 8 tariff changes. Each

schedule can be assigned to the days of the week and

months as requested. Up to 20 holidays can be assigned

to the lowest tariff.

A diagnostic algorithm checks and notifies any setup

overlapping.

• Event, alarm and digital outputs ON/OFF recording. The

instrument records the status change of 8 programmable

set points, the digital outputs ON/OFF and the instrument

supply ON/OFF. All the events are integrated by date

and time reference

Communication

• Both RS232 and RS485 included in the basic unit. The

selection is made by dip-switches

• Modbus protocol or standard ASCII protocol

• Communication speed programmable up to 57,600 bps

• Optional 10/100 Ethernet, Profibus or Lonbus interfaces

• On-board HTML Web Page server or direct

communication through Ethernet / Internet network using

Modbus or standard ASCII protocol

Inputs & Outputs

• Up to 6 digital outputs for energy pulsing or for alarm

tripping. Two digital Optomos ML outputs are included in

the basic unit.

• Up to 4 analog outputs 0-20 or 4-20 mA

• Optional four digital inputs for pulse counting. A multiplier

is programmable for each input in order to store the real

quantities, as well different measurement units are

selectable (kWh, kVAh, kvarh, m3, etc.)

• One of the digital inputs can be programmed as demand

period syncronization input

Other

• Real Time Clock with battery backup

• Calculation of capacitor bank value for PF compensation

• No.1 programmable user page with 6 parameters

selected among measured values

• Five alpha-numeric characters password to avoid

unauthorized setup access

• Downloadable firmware via serial port

2

37

Page 38: First National Pakistan

ENERGY MEASUREMENT AND CONTROL www.algodue.com

INSTANTANEOUS MEASUREMENTS

PHASE VOLTAGE VL1-N

- VL2-N

- VL3-N

[V]

LINE VOLTAGE VL1-L2

- VL2-L3

- VL3-L1

[V]

SYSTEM VOLTAGE V [V]

LINE CURRENT IL1

- IL2

- IL3

- IN

[A]

SYSTEM CURRENT I [A]

POWER FACTOR PFL1

- PFL2

- PFL3

SYSTEM POWER FACTOR PF

COS Ø DPFL1

- DPFL2

- DPFL3

APPARENT POWER SL1

- SL2

- SL3

[VA]

SYSTEM APPARENT POWER S [VA]

ACTIVE POWER PL1

- PL2

- PL3

[W]

SYSTEM ACTIVE POWER P [W]

REACTIVE POWER QL1

- QL2

- QL3

[var]

SYSTEM REACTIVE POWER Q [var]

FREQUENCY f [Hz]

DEMAND (AVERAGE VALUES) PAV

- SAV

- QAV

- IAV

- ITHAV

( )

THERMAL CURRENT IL1

- IL2

- IL3

[A2s]

VOLTAGE & CURRENT THD (Total ) THDVL1,

L2,

L3

- THDIL1,

L2,

L3

[%]

VOLTAGE & CURRENT THD (Even, Odd) THDVL1,

L2,

L3

- THDIL1,

L2,

L3

[%]

FFT ANALYSIS 31ST VL1-N

- VL2-N

- VL3-N

- IL1

- IL2

- IL3

[%, V, A]

FFT ANALYSIS 50TH VL1-N

- VL2-N

- VL3-N

- IL1

- IL2

- IL3

[%, V, A]

UNBALANCE V,I [%]

PHASE REVERSAL 123 / 132

REAL TIME CLOCK Date, Time

UPM315 - DIN 96x96 and ANSI 4” Power Meter

STORED DATA

SYSTEM ACTIVE ENERGY [Wh]

SYSTEM APPARENT ENERGY (N.4 Counters - ) [VAh]

SYSTEM LAGGING REACTIVE ENERGY [varh ind]

SYSTEM LEADING REACTIVE ENERGY [varh cap]

MIN / MAX VALUES WITH TIME REFERENCE 7xV, 5xI, f, 4xPF, 6xTHD

PEAK VALUES PAV

- SAV

- QAV

- IAV

- ITHAV

( )

PROGRAMMABLE RECORDINGS

DAILY CONSUMPTION (More than 300 days) [Wh, VAh, varh]

ALARM / EVENT LOG 8 Set Points, Outputs ON/OFF, Instrument ON/OFF

MIN / AVG / MAX VALUES(1) [(1)]

ADVANCED FEATURES

GRAPHICAL TRENDS Max 6 parameters [15min/1hrs/1day/1month]

TIME OF USE (TARIFF REGISTERS) [Wh, VAh, varh]

WAVEFORM CAPTURE VL1-N

-VL2-N

-VL3-N

-IL1

-IL2

-IL3

[128 samples max]

CALCULATION OF PF COMPENSATION Capacitor bank [kvar]

DIGITAL INPUTS COUNTERS [Wh, VAh, varh, m3, litres, etc.]

= Standard = Bi-directional value = Optional = Enhanced Package

(1) Programmable every 1, 5, 10, 15, 30, 60 min - Maximum 8 measured parameters.

3

38

Page 39: First National Pakistan

ENERGY MEASUREMENT AND CONTROL www.algodue.com

UPM315 - DIN 96x96 and ANSI 4” Power Meter

Specifications

Power supply

Rated voltage: 65 - 250 Vac 50/60Hz or 90 - 250 Vdc

(19 - 60 Vdc - option)

Consumption: 5VA max

Voltage inputs

Maximum measurable voltage: 600 (750)VAC max L-L

Input impedance: >1.3 MOhm

Burden: max 0.15 VA per phase

Frequency: 45 - 65 Hz

Current inputs

Rated current (Ib): 1 / 5 ARMS programmable

Min / max measurable current: 20 mA / 7 ARMS

Maximum overload: 10ARMS continuous - 100 ARMS for 1 sec.

Input impedance: 0.02 Ohm approximately

Burden: max 0,5 VA per phase

Insulation voltage: 150 VAC max between phases

Typical accuracy

Voltage: ± 0.1% reading ± 0.03% full scale

Current: ± 0.1% reading ± 0.05% full scale

Active power: ± 0.5% reading ± 0.1% full scale (PF=1)

Power factor: 1% reading (0,5% optional) (0.5 ind - 0.8 cap)

Active energy: class 1 (class 0,5 optional)

Frequency: ± 0.05% reading ± 1 digits from 45 to 65 Hz

Display and operating controls

Display: Backlighted graphic LCD display

160 x 144 dots

Keypad: 5 push-buttons

Data memory

Type: On-Board non-volatile FLASH, 128kB or 2 MB

Communication port

Type: No.1 selectable RS232 or RS485, optoisolated

No.1 available for plug-in comm. boards

Baud Rate: 300 to 57600 bps

Real Time Clock

Type: with battery backup

Accuracy: ± 30 ppm

Digital outputs

Type: No.2 isolated Optomos (50V - 300mAAC-DC

)

Environmental conditions

Operating temperature: from -15 oC to +60 oC

Storage temperature: from -25 oC to +75 oC

Relative humidity: 80% max. without condensation

Mechanical characteristics

Material: Metal enclosure

Protection degree: IP54 (front panel); IP20 (terminals)

Terminals: Pluggable terminal blocks

(Barrier terminal strips - OPTION)

Size / Weight: 96 x 96 x 130 (mm) DIN version 750 gr

110 x 110 x 40 (mm) ANSI Display 390 gr

90 x 90 x 130 (mm) Transducer 800 gr

Standards compliance

Safety: UL recognized under UL61010B-1and CAN/

CSA-C22.2 No. 1010.1-92, 73/23/EEC,

93/68/EEC directives, EN61010.1

EMC: 89/366/EEC directive and following

modifications 93/31/EEC and 93/68/EEC,

EN50081-2, EN50082-2, EN61326/A1

Single-Phase up to 400V

TYPICAL WIRING DIAGRAMS

3-Phase 4-Wire up to 600V

3-Phase 3-Wire above 600V

L1 N

4

L1 L2 L3 NL1 L2 L3 N

L1 L2 L3

39

Page 40: First National Pakistan

ENERGY MEASUREMENT AND CONTROL www.algodue.com

UPM315 - DIN 96x96 and ANSI 4” Power Meter

PHYSICAL CONFIGURATION

Compact DIN 96x96 instrument

Compact version according DIN 96 standard (92 x 92 mm cutout)

Transducer

The transducer can be mounted, using the adapter, on a

flat surface or on a DIN Rail. It can be connected to the

display by a 3m (~10 feet) provided cable.

Rear connections - Barrier terminal strips (OPTION)

The RS232 / RS485 programmable port and the two

digital outputs are included in the basic configuration.

Two slots are available for option boards.

Rear connections - Standard pluggable terminals

The RS232 / RS485 programmable port and the two

digital outputs are included in the basic configuration.

Two slots are available for option boards.

ANSI 4” instrument (display + transducer)

The drawings below show the tranducer mounted on the

backside of the ANSI 4” display.

5

OUT1

OUT2

OUT1

OUT2

40

Page 41: First National Pakistan

ALGODUE ELETTRONICA s.r.l.

Via Passerina, 3/A

28010 FONTANETO D'AGOGNA

(NO) ITALY

Tel: +39 0322 89864 - 89307

Fax: +39 0322 89871

E-mail: [email protected]

Website: www.algodue.com

ENERGY MEASUREMENT

AND CONTROL

ALRALRALRALRALR AAAAA 55555 XXXXX

Subject to change without notice

UPM315 - DIN 96x96 and ANSI 4” Power Meter

ORDERING INFORMATION

UPM315

Series

User’s Manual Language

D = German

I = Italian

U = English

Communication Protocol

B = ASCII Standard

C = Modbus

E = Ethernet board

L = Lonbus board

P = Profibus board

Aux Power Supply

A = 65 ÷ 250VAC

/ 90 ÷ 250VDC

R = 19 ÷ 60VDC

Serial Port

5 = Selectable RS232/485 (1)

Memory

1 = 128 kBytes (1)

6 = 2MBytes + Enhanced package

Firmware Options

2 = Basic version (1)

3 = Harmonics to 31st+ DPF

4 = Enhanced package + Harmonics + DPF + 2MBytes

Special functions

X = None

5 = accuracy class 0,5 for energy counters

Physical Configuration

STANDARD PLUGGABLE TERMINALS (EU)

A = DIN 96x96 Instrument

B = ANSI Display + Transducer

C = ANSI Display + Transducer + Cable

+ mounting accessories

E = Transducer + mounting accessories

BARRIER TERMINAL STRIPS (USA)

G = DIN 96x96 Instrument

H = ANSI Display + Transducer

I = ANSI Display + Transducer + Cable

+ mounting accessories

K = Transducer + mounting accessories

Inputs (2)

X = None

4 = No.1 DI4-TR board - (No.4 digital inputs)

Analog Outputs (2)

X = None

A = No.1 AO2-0420 board - (No.2

programmable analog outputs)

R = No.2 AO2-0420 boards - (No.4

programmable analog outputs)

Digital Outputs (2)

2 = Basic version with No.2 built-in

optomos outputs (50V - 300mAAC-DC

) (1)

4 = No.1 DO2-ML board - (No.2 ML outputs)

6 = No.1 DO4-ML boards - (No.4 ML outputs)

R = No.1 DO2-R board - (No.2 relay outputs)

S = No.1 DO4-RML board - (No.2 relay

outputs + No.2 ML outputs)

V = No.1 DO2-MH board - (No.2 MH outputs)

W = No.1 DO4-MH boards - (No.4 MH outputs)

NOTES

1) The basic instrument configuration includes:

• Power Supply 65 ÷ 250VAC

/ 90 ÷ 250VDC

• No.2 Optomos Outputs (50V - 300mAAC-DC

)• RS232 / 485 selectable by dip-switches• 128 kBytes data recording memory• Real Time Clock with battery backup

2) The basic instrument can be equipped withmaximum 2 option boards.

DI4-TR No.4 Digital Inputs for Voltage-Free ContactsPROFI Profibus DP InterfaceLON Lonbus InterfaceETH 10/100 Ethernet Interface

PLUG-IN BOARDS

DO2-ML No.2 Optomos Outputs (50V - 300mAAC-DC

)DO2-MH No.2 Optomos Outputs (250V - 80mA

AC-DC)

DO2-R No.2 Relay Outputs (250V - 2AAC

resistive)DO4-ML No.4 Optomos Outputs (50V - 300mA

AC-DC)

DO4-MH No.4 Optomos Outputs (250V - 80mAAC-DC

)DO4-RML No.2 Relay + No.2 Optomos (ML) OutputsAO2-0420 No.2 0÷20 or 4÷20mA Analog Outputs

6

41

Page 42: First National Pakistan

42

Page 43: First National Pakistan

DIN RANGE PANEL METERSDESCRIPTIONAvailable with moving iron or moving coil movements for a.c. or d.c. use, these DIN panel metershave been supplied worldwide andare recognised for their quality and value. Standard scales or customised dials can be offered.

• Manufactured to:DIN 43700, IEC51 and BS89.

• 48mm, 72mm and 96mm sizes.• a.c. or d.c. use.• Interchangeable dials (72mm & 96mm).• Rugged pivot and jewel movement.• Ammeters, Voltmeters, Frequency

Meters, Power Factor Indicators,Wattmeters, Elapsed Time Indicatorsand Maximum Demand Indicators.

• Optional red secondary pointer andterminal cover.

• Special customised dials.

Howard Butler Limited is one of the largestindependent UK manufacturers of panel metersand associated products.

With over 80 years experience in the industryHOBUT products have built a reputation forhigh quality and modern design at competitive prices.

ANALOGUE PANEL METERS • D IGITAL PANEL METERS • HOURS COUNTERS • SELECTOR SWITCHES • PROTECTION RELAYS • TRANSDUCERSSHUNTS • CURRENT TRANSFORMERS • CHARGER METERS • THERMAL CUTOUTS • MULT I -FUNCTION METERS

11840

43

Page 44: First National Pakistan

DIN RANGE PANEL METERSMOVING IRON Types: D48SD, D72SD, D96SD.

Accuracy: Class 1.5 (Class 2.5-60A andabove).

AC ratings: 1A to 100A direct connected(D48SD - 40A max).1A or 5A CT operated.30V to 600V direct connected.

Burden: 0.7VA typical for 1A or 5A CToperated at 50Hz.1.2VA max up to 30A2.4VA max for 40A to 100A.6VA max for voltmeters up to 600V.

Frequency: Calibrated at 50Hz.Specify for frequencies 15Hz upto 400Hz

Scaling: Standard ammeter and voltmeterscales.(2x and 6x overload amme-ter scales available on request).

Damping: Heavily damped movements available.

MOVING COIL Types: D48MC, D72MC, D96MC.Accuracy: Class 1.5. DC ratings: 100µA to 50A direct connected

(D48MC - 40A max).4-20mA, 1mA or 20mAtransducer operated.50mV to 600V direct connected.50mV to 300mV shunt operated.

AC ratings: Rectifier types available for a.c.use (mean sensitivity).

DC burden: 80mV to 150mV volt drop fordirect connect ammeters 1mA(1000Ω/V) for voltmeters andshunt operated ammeters.

Non std.: Suppressed zero voltmeters andtrim potentiometer types available.

WATTMETER Type: D96WA.Accuracy: Class 1.5.AC ratings: 1A or 5A CT operated.

63.5V to 500V direct connected.Burden: Current<0.5VA

Voltage<2.0VA each circuit.

Working range: Current 0-120%

Voltage 75-125%.Frequency: Calibrated for 50Hz or 60Hz.Systems: WA1 Single phase.

WA2 3ph 3 wire balanced loadWA3 3ph 4 wire balanced loadWA4 3ph 3 wire unbalanced loadWA5 3ph 4 wire unbalanced load

Terminals: Screw clamps - connection diagram supplied.

CONNECTIONDIAGRAMS

All DIN range panel meters areavailable as Wattmeters using aseparate transducer.

Moving Iron panel meters can beused for D.C. operation atreduced accuracy.

L N

kK

L l

L1 L2 L3

K

L

k

l

L1 L2 L3 N

kK

L l

L1 L2 L3

K

L

k

l K

L

k

l

L1 L2 L3 N

K

L

k

l

K

L

k

l

K

L

k

l

SINGLE PHASE 3PH 3W BALANCED LOAD 3PH 4W BALANCED LOAD 3PH 3W UNBALANCED LOAD

3PH 4W UNBALANCED LOAD

VOLTMETER

AMMETER

L1

L2

(L)

(N)

Vv

Uu

L1

L2

(L)

(N)L

l

K

k

DIRECTCONNECTED

VOLTAGETRANSFORMER

OPERATED

DIRECTCONNECTED

CURRENTTRANSFORMER

OPERATED

VOLTMETER

AMMETER

-

+

+

-

+

+ +

DIRECTCONNECTED

SHUNTOPERATED

• • •

• • •

DIN96

DIN72

DIN48

••

•••

••

44

Page 45: First National Pakistan

DIN RANGE PANEL METERSPOWER FACTOR INDICATOR

Type: D96PF.Accuracy: Class 1.5 (±2 electrical degrees).AC ratings: 1A or 5A CT operated.

63.5V to 500V direct connected.Burden: Current<0.5VA

Voltage<2.0VA each circuit.

Working Current 20-150%range: Voltage 75-125%.Scaling: Cos ø 0.5 CAP -|- 0.5 IND.Frequency: Calibrated for 50Hz or 60HzSystems: PF2 3 phase 3 or 4 wire balanced

load.Separate transducer required forsingle phase use.

Terminals: Screw clamps - connection diagram supplied.

MAXIMUM DEMAND INDICATORType: D96MD, conforming to ES50-2.Accuracy: Class 3.AC rating: 5A CT operated with

1.2 x overscaling to 6A.1A version available on request.

Burden: 5VA. Time lag: 15, 20 or 30 mins.Frequency: Calibrated at 50Hz

Specify for frequencies up to 400Hz.Scaling: Range of interchangeable scales

to suit 5A CT’s. For double ratioCT’s two interchangeable dials are fitted.

Mounting: Front of panel fixings are available.

Type: D96CMD.Accuracy: Class 3, moving iron Class 1.5.AC rating: 5A CT operated with

1.2 x overscaling to 6A.1A version available on request.

Burden: 5.6VA. Time lag: 15, 20 or 30 mins.Frequency: Calibrated at 50Hz

Specify for frequencies up to 400Hz.Scaling: Range of interchangeable scales

to suit 5A CT’s. For double ratioCT’s two interchangeable dials are fitted.

Mounting: Front of panel fixings are available.

Types: D48HZ, D72HZ, D96HZ.Accuracy: Class 0.5 (±0.5% of nominal

frequency).Class 1.0 for 45/65 Hz.Class 1.5 for D48HZ types.

Ranges: 45/55, 45/65, 55/65, 360/440Hz.Ranges incorporating RPM scalealso available.

Input volts: 110V±15%, 225V±15%380 to 440V±5%.

Burden: 6mA at nominal voltage.

Types: D48HR, D72HR, D96HR.AC Ratings: 110V or 240V.Frequency: 50Hz or 60Hz.

DC models also available.Range: Seven digits up to 99999.99hrs.Terminals: Connections to terminal block.

Note: D48HR has a special panel cut-out=45.5 mmsq

L1 L2 L3 N

k K

Ll

L1

L2

(L)

(N)L

l

K

k

CURRENTTRANSFORMER

OPERATED

L1

L2

(L)

(N)L

l

K

k

CURRENTTRANSFORMER

OPERATED

CONNECTIONDIAGRAMS

COMBINED MAXIMUM DEMAND INDICATOR

FREQUENCY METER

ELAPSED TIME METER

L1

L2

(L)

(N)

Vv

Uu

DIRECTCONNECTED

VOLTAGETRANSFORMER

OPERATED

L1

L2

(L)

(N)

+0.5–0.0

• • •

• • •

DIN96

DIN72

DIN48

All DIN panel meters are availableas Power Factor Indicators using aseparate transducer.

Bi-metallic movement with additional Moving Iron movement,for instantaneous reading

Bi-metallic movement indirectlyheated.

••

45

Page 46: First National Pakistan

DIN RANGE PANEL METERS

Our policy is one of continuous development and therefore specifications may change without notice.

HOWARD BUTLER LTDCROWN WORKS, LINCOLN ROAD

WALSALL WS1 2EB ENGLAND

Tel: 01922 640003 Fax: 01922 723626International Tel: +44 1922 640003 E-mail: [email protected]

Web: www.hobut.co.uk

TECHNICAL SPECIFICATION PANEL CUT-OUTS (All dimensions mm)

DIMENSIONS (All dimensions mm)

Standards IEC 51, BS 89.

Enclosure: DIN 43700.Flame retardant: base material UL94V1,case & terminal cover material UL94V0.Scale marking DIN 43802Protection IP52: IP54 can be supplied.

Overload: CURRENT - 1.2 x rating for 2hrs.- 10 x rating for 5 secs.

VOLTAGE - 1.2 x rating for 2hrs.- 2 x rating for 5 secs.

Insulation test: 2kV 50Hz for 1min.

Temperature: Calibrated at 23°c.Suitable for use at -25°c to +40°c.

Available extras: Adjustable red secondary pointer.Terminal cover.Special scale.Polycarbonate window.6.4mm “Faston” terminal tag(voltmeters & ammeters to 5A).

Other DIN products: Our illustrations and technical specifications apply to

meters with 90° scale arcs.Instruments with 240° scale arcs are also available.

dims+0.6–0.0

dims+0.7–0.0

dims+0.8–0.0

4568

6892

92

45

DIN 48 can be slot mounted using the standard fixing clip.DIN 72 & DIN 96 can be supplied with special fixing clips for slot mounting.Slot dimensions available on request.

• Digital panel meters.• Current Transformers.• Shunts.• Power transducers.• Protection relays.• Battery charger indicators.• Thermal cut-outs.

New HOBUT products include:• Pro-Din panel meters.• 240° panel meters.• kWh meters.• Multi-function meters.• Protective current transformers.

Data sheets on the following HOBUT product ranges are available onrequest:

E

F

D

CBA

A

A B C D E FDIN48 (M4 screw clamps) 48 5 43 44.8 10 –Ammeters up to 5A & Voltmeters

DIN48 (M6 stud terminals) 48 5 43 44.8 21 –Ammeters 6A to 40A

DIN72 (M4 screw clamps) 72 5.5 38.5 66 10 –Ammeters up to 5A & Voltmeters

DIN72 (M6 stud terminals) 72 5.5 38.5 66 19 –Ammeters 6A to 50A

DIN72 (M8 stud terminals) 72 5.5 38.5 66 22 –Ammeters 60A to 100A

DIN96 (M4 screw clamps) 96 5.5 38.5 90 10 20Ammeters up to 5A & Voltmeters

DIN96 (M6 stud terminals) 96 5.5 38.5 90 19 20Ammeters 6A to 50A

DIN96 (M8 stud terminals) 96 5.5 38.5 90 22 20Ammeters 60A to 100A

DIN96 Watt-meter 96 5.5 123 90 13 –DIN96 Power Factor Indicator 96 5.5 123 90 13 –DIN96 Max. Demand Indicator 96 5.5 58 90 10 20(M4 screw clamps)DIN96 Combined M.D.I. 96 5.5 58 90 10 20(M4 screw clamps)Note: If terminal covers are fitted as an optional extra, add 23mm to dimension ‘C’ for DIN72 & DIN96 meters, and 25mm to dimension ‘C’ for DIN48 meters.

DIN 96 DIN 72 DIN 48

46

Page 47: First National Pakistan

47

Page 48: First National Pakistan

PRODIN RANGE PANEL METERS

PD72SD MOVING IRON - AC

PD72HZ FREQUENCY RANGES

PD72MC MOVING COIL - DC

Dimensions (mm)Specifications

Options

DESCRIPTION 72 x 72mm DIN sized panelmeter with a horizontal scaleand a round barrel.Manufactured to IEC51.

APPLICATION Used widely in the panel building industry, where a DINproduct with a horizontal scaleis required. Round barrel allowsstraightforward installation withoutspecial tools.

Our policy is one of continuous development and therefore specifications may change without notice.

HOWARD BUTLER LTDCROWN WORKS, LINCOLN ROAD

WALSALL WS1 2EB ENGLAND

Tel: 01922 640003 Fax: 01922 723626International Tel: +44 1922 640003 E-mail: [email protected]

http://www.hobut.co.uk

Rating Burden Accuracy ClassScaled up to 40A direct connected 1.2VA max up to 30A, 2.4VA up to 40A 1.51A or 5A CT operated, scaled as necessary 0.7VA typically at 50Hz 1.5Scaled 30V to 600V, direct connected 6VA max 1.5

Rating Burden Accuracy Class45/65, 45/55 or 55/65 Hz for 110/230/380V direct connected 6mA at nominal voltage 1.5

Rating Burden Accuracy Class100µA to 40A direct connected up to 150mV 1.54/20mA, scaled as necessary up to 150mV 1.5Scaled up to 600V, direct connected 1mA (1000Ω/V) 1.550mV to 300mV shunt operated, scaled as necessary 1mA (1000Ω/V) 1.5

Flame retardant: Base - UL94V1, Case - UL94V0Protection: IP52 (front of panel)Scale marking: DIN 43802Overload (A): 1.2 x rating 2hrs / 10 x rating 5 secondsOverload (V): 1.2 x rating 2hrs / 2 x rating 5 secondsInsulation test: 2kV 50Hz for 1 minuteTemperature: Calibrated at 23°C, suitable for -25 to +40°CTerminals: M4 screw clamps supplied as standard

(above 5A, M6 studs are supplied)Panel mounting: U-clamp fixing or 2 pin fixing (57mm or 53mm)

• Special scales• M6 terminals, M3 studs • 6.4mm faston tags (up to 5A)• Terminal cover

Panel cut-out ø56

11840

48

Page 49: First National Pakistan

R68 RANGE PANEL METERS

R68SD MOVING IRON - AC

R68MC MOVING COIL - DC

Dimensions (mm)Specifications

Options

DESCRIPTION Rectangular fronted, round barrelled, moving iron and moving coil panel meters for AC or DC use. Manufactured to IEC51 / BS89.

APPLICATION Used widely in the panel building, welding, and batterycharger industry, where a roundbarrelled instrument is requiredto fit into a standard 64mmdiameter panel cut-out.

Our policy is one of continuous development and therefore specifications may change without notice.

HOWARD BUTLER LTDCROWN WORKS, LINCOLN ROAD

WALSALL WS1 2EB ENGLAND

Tel: 01922 640003 Fax: 01922 723626International Tel: +44 1922 640003 E-mail: [email protected]

http://www.hobut.co.uk

Rating Burden AccuracyScaled up to 100A direct connected 1.2VA max upto 30A, 2.4VA max 40-100A 2.5%1A or 5A CT operated, scaled as necessary 0.7VA typically at 50Hz 2.5%Scaled 30V to 600V, direct connected 6VA max 2.5%

Rating Burden AccuracyScaled 50µA to 50A direct connected 80mV to 150mV volt drop 1.5%50mV to 300mV shunt operated, scaled as necessary 1mA (1000Ω/V) 1.5%Scaled 50mV to 600V, direct connected 1mA (1000Ω/V) 1.5%

R68SD R68MCScale length 52mm 62mmMovement 90° 90°Fixing method U-clip U-clipFlame retardant Base UL94V1 Base UL94V1

Case UL94V0 Case UL94V0Protection(front of panel) IP52 IP52

82 29.5

58

10

68 63Dia

64

• Adjustable red secondary pointer• 6 x overload scale (R68SD) • Tropical finish• Special dials• Black or white dial mask• R68 available as power factor indicator, wattmeter,

frequency meter, details on request.

Panel cut-out

11840

49

Page 50: First National Pakistan

50

Page 51: First National Pakistan

51

Page 52: First National Pakistan

52

Page 53: First National Pakistan

53

Page 54: First National Pakistan

AC VOLTAGE

TECHNICAL SPECIFICATION

INPUT

Rated value Un 57.8 <100 / 110 <600 V

Power consumption <1.5 VA (VA1, VA3)

<1 VA (VL1, VL3, VR1)

Working range 15-125% Un (VA1, VA3)

0-125% Un (VL1, VL3, VR1)

Rated Frequency 50 / 60 / 400 Hz

Frequency influence 0.005 % / Hz

Overload continuous 1.5 x Un

Overload for 1 sec. 4 x Un (VL1 VL3 VR1 )

2 x Un (VA1 VA3)

OUTPUT

Rated value mA 0-1/5/10/20mA (VA1, VA3)

Rated value mA 1/5/10/20 & 4-20mA (VR1)

Rated value mA 4-20mA (VL1)

Rated Value volts 0-5 / 10 V (VA1, VA3)

Rated value volts 0-5 / 10 & 1-5 V (VR1)

Rated value volts 1-5 V (VL1 VL3)

ADJUSTMENT

Zero No adjustment (VA1,VA3)

Zero ± 2% (VR1,VL1)

Span ± 10% (VA1,VA3,VR1,VL1,VL3)

AUXILIARY

A.C. Voltage 115 / 230 / 400 V

(± 25% / 45-65Hz / <2 VA)

D.C. Voltage 24 / 48 / 110 V (± 20% /

galvanically isolated / < 3 W)

Note M100-VA1 & VA3 are self

powered.

WEIGHT & CASE SIZE

M100-VA1 Approx. 0.3 kg. 55mm case

M100-VL1,VR1 Approx. 0.4 kg. 55mm case

M100-VA3 Approx. 0.6 kg. 100mm case

M100-VL3 Approx. 0.7 kg. 100mm case

ORDERING INFORMATION

Product Code Input In Output Aux Freq. OptionsM100-AL1 5A 4-20mA 230V 50Hz

OPTIONS

1. Non standard inputs / outputs only as far as technically

acceptable.

2. A.C. Auxiliary in range 57.7 to 450 volts

3. Calibration at nominal Hz 35.....450Hz

4. Calibration at temperature other than 23°C

7

The M100 series voltage transducers are designed to measure

A.C. Voltage in single and 3 phase system. They convert the

A.C. Signal to a D.C. Output that is directly proportional to

the input signal.

The M100-VA1 VA3 are self powered (i.e. no auxiliary

required) average sensing RMS calibrated voltage

transducers, mA and voltage outputs are available.

The M100-VL1 VL3 are average sensing RMS calibrated, live

zero voltage transducers. Auxiliary is required to provide

power so that 4mA output signal is present when the input is

zero.

The M100-VR1 is true RMS sensing RMS calibrated allowing

measurement of distorted waveforms of up to 9th harmonic

with a crest factor of 5. The VR1 is typically used in voltage

measurement where distorted waveform is common such as

thyristor drives.

The above units are used to measure voltage in energy

management systems, switchboards, generator and telemetery

controls. Isolation of 4kV is provided between the input and

output signal, allowing the ouput to be fed to conventional

analogue meters, digital meters, PLC, and computer systems.

TYPICAL APPLICATIONS

SELECTION GUIDE

M100-VA1 1 ph. self powered ave. sensing RMS calibrated

M100-VL1 1 ph. aux powered ave. sensing RMS calibrated

M100-VR1 1 ph. aux powered true RMS sensing RMS cal.

M100-VA3 3 ph. self powered ave. sensing RMS calibrated

M100-VL3 3 ph. aux powered ave. sensing RMS calibrated

54

Page 55: First National Pakistan

AC VOLTAGE CONNECTION

DIAGRAMS

9

M100-VA1 / VS1 M100-VL1 / VR1 / VX1

M100-VA3 M100-VL3 / VX3

55

Page 56: First National Pakistan

56

Page 57: First National Pakistan

57

Page 58: First National Pakistan

58

Page 59: First National Pakistan

59

Page 60: First National Pakistan

M850 MULTIFUNCTIONMETERSDESCRIPTION The new range of Hobut multifunction panel metersfeature 96 x 96mm sizes complete with unique blueLED screen, which can be seen in direct sunlight. Therange is easy to use, features user-programmable CT &VT ratios, and can be used on any single or 3 phasesystem with any input voltage without re-programming.

APPLICATION The range is a cost effective replacement for traditionalpanel meters and is suitable for low, medium and highvoltage control panels, gensets, building managementsystems, power management and more.

STANDARD FUNCTIONS:

Phase Voltage (V)

Phase to Neutral Voltage (V)

Phase Current (I)

Frequency (Hz)

Active Power (W)

Active Energy (kWh)

Reactive Power (VAr)

Apparent Power (VA)

Reactive Energy (VArh)

Power Factor (PF)

Instantaneous Amp Demand

Instantaneous Watt Demand

Instantaneous VA Demand

Maximum Amp Demand

Maximum Watt Demand

Maximum VA Demand

Neutral Current Measurement

RANGE ORDERING INFORMATION

PLUG-IN OPTIONS

All models feature thefollowing user-programmablefunctions:

• Current Transformer Ratio• Voltage Transformer Ratio• Baud Rate, Parity, Stops

• AC or DC AUX• 1A or 5A CT• Single or 3 phase system• Input voltage range 28-570V• RS485 address, 1-247• Security code access for

programming

PROGRAMMABLE FUNCTIONS

Suitable for any 1 or 3 phasesystem, AC aux 100-440V or DC aux 100-420V

Input 28/330V L-N48/570V L-L5A

STANDARD PRODUCT OPTIONAL EXTRAS

Pulsed Output

RS 485 Output

1A input (instead of 5A)

330mV Input(instead of 1A or 5A CT)

Order example: a standard product with RS 485 output is partnumber M850-MP1-RS

M850-MP1 P RS 1 MV

Both pulsed output(for Wh or VArh) andRS 485 output(Modbus protocol)are plug in optionswhich can besupplied with themultifunction meter.If purchasedseparately please useordering codes onright.

RS 485 Outputwhen ordered separately

use part RS485-M850

Pulsed Outputwhen ordered separately

use part PULSE-M850

60

Page 61: First National Pakistan

L1

L2

L3

NL K

L3l k

L K

L2l k

L K

L1l k

L1L2L3NAUX UH

L+ N-

M850 MULTIFUNCTIONMETERS

ACCURACY Volts/Amps: 0.5% of readingFrequency: 0.1 HzActive Power: 1% of readingApparent Power:1% of readingPower Factor: 2% of rangeEnergy: IEC 1036 Class 1INPUT Rated Un: 28-330V LN, 48-570V L-LOverload: 800V continuousBurden: 0.5VA per phaseRated In: 0.5-6AOverload: 10 In for 1 secBurden: 0.5VA per phaseAuxiliary: 100-440V AC / 100-420V DC Frequency: 45/65HzDISPLAY Digits: 3 lines 9999Size: 14.2mm 7 segmentBrightness: user adjustableOUTPUT RELAY (Wh or VArh) Pulse output: SPST-NO (10 watt, 300VDC, 500mA)Pulse duration: programmable from 40msec-200msec

INSULATION Test Voltage: 3kV RMS 50Hz for 1 minute between case,

input and aux.1kV between case, input, aux, relay output & RS485 output.

Impulse test: EMC 5kV transient complies with IEC801/ EN55020 HF

Surge withstand: IEC801/EN55020 Ansi C37.90AInterference: EHF 2.5kV 1Mhz complying to IEC255-4Protection class II: Complying to IEC348 / BS4753 /

DIN57411 / VDESTANDARDS General: IEC688, BSEN60688, BS4889, IEC359EMC: BSEN61000-6-3:2007, BSEN61000-6-4:2007,Safety: IEC1010, BSEN601010ENVIRONMENT Working temp: 0-60ºCStorage temp: -40 to +85ºCRelative humidity: 0-95% non condensingShock: 30G in 2 planesMATERIAL Black polycarbonate case to UL94V0Weight: 0.35kg

SPECIFICATIONS

CONNECTION DIAGRAM

96

96

with plug inoption fitted

8219

61

92 (+0.8)

92 (+0.8)

Panel cut out

DIMENSIONS (mm)

Our policy is one of continuous development and therefore specifications may change without notice.

HOWARD BUTLER LTDCROWN WORKS, LINCOLN ROAD

WALSALL WS1 2EB ENGLAND

Tel: 01922 640003 Fax: 01922 723626International Tel: +44 1922 640003 E-mail: [email protected]

Web: www.hobut.co.uk

VOLTAGE CURRENT L1 L2 L3 N L1 L2 L3

1ph ! - - ! ! - -1ph 3W ! ! - ! ! ! -3ph 3W ! ! ! - ! - !

3ph 4W ! ! ! ! ! ! !

3ph 3W BAL ! ! ! - ! - -3ph 4W BAL ! - - ! ! - -

Unused Voltage terminals are internally connected

61

Page 62: First National Pakistan

NEW

101L SERIESTYPE CTH101L

19 SERIESTYPE 196

NEW

H

W

Ø

D

H

W

Ø

D

PRIMARYCURRENT

PRODUCT SELECTION GUIDE

An easy to use product selector for the HOBUT range of standard current transformers.Many more current transformers can also be seen on our web site

www.currenttransformers.co.uk

STANDARD CURRENT TRANSFORMERSSELECTION GUIDE

DIN railmount and foot mount

Sealableterminalcovers

Inside Dia. (mm) Ø 21 15 24 – 20 28 40

Busbars (mm) – – 30 x 10 WOUND 20 x 20 40 x 10 50 x 1020 x 20 PRIMARY 30 x 10 40 x 30

Dimensions (mm) H 65 70 70 85 78 78 95

W 45 49 49 60 60 60 70

D 30 43 30 43 30 30 40

DIN Rail Mount l l l l l l –

Foot Mount l l l l l l l

Terminal Cover l l l l l l l

40A 25A 60A 1A 30A 100A 250A

300A 125A 600A 60A 75A 800A 1200A

17 SERIES16 SERIES14 SERIES13 SERIESSERIESTYPE 175TYPE 164TYPE 162TYPE 160TYPE 143TYPE 141TYPE 132

PRIMARYCURRENT

Inside Dia. (mm) Ø 45 – 60 60 85 –

Busbars (mm) 60 x 15 60 x 30 60 x 30 80 x 10 100 x 30 100 x 5550 x 30 50 x 50 60 x 30 80 x 50

Dimensions (mm) H 108 126 124 124 160 144

W 85 90 100 100 135 129

D 30 45 40 40 40 40

DIN Rail Mount – – – – – –

Foot Mount l l l l l l

Terminal Cover l l l l l l

400A 400A 400A 400A 400A 600A

1600A 1600A 2000A 2000A 4000A 4000A

21 SERIES20 SERIES18 SERIESSERIESTYPE 21TYPE 208TYPE 206TYPE 186

All current transformers are supplied as standard with 5A secondry. 1A secondry available by request.A range of accuracies are available from 0.2S to class 3, protection and class X.

62

Page 63: First National Pakistan

127 SERIESTYPE CTH127L

H

W

Ø

D

H

W

Ø

D

Our policy is one of continuous development and therefore specifications may change without notice.

HOWARD BUTLER LTDCROWN WORKS, LINCOLN ROAD

WALSALL WS1 2EB ENGLAND

Tel: 01922 640003 Fax: 01922 723626International Tel: +44 1922 640003 E-mail: [email protected]

http://www.hobut.co.uk

PRIMARYCURRENT

Inside Dia. (mm) Ø – – – – – – –

Busbars (mm) 127 x 38 127 x 54 65 x 32 84 x 34 105 x 38 127 x 38 127 x 54

Dimensions (mm) H 115 140 113 135 156 178 178

W 160 160 90 96 98 98 125

D 40 40 45 40 40 40 40

DIN Rail Mount – – – – – – –

Foot Mount l l l l l l l

Terminal Cover l l l l l l l

400A 400A 150A 150A 200A 400A 400A

4000A 6000A 2000A 2500A 4000A 4000A 6000A

RECTANGULAR MOULDED CASESERIESTYPE CTV127LTYPE CTV127MTYPE CTV105TYPE CTV84TYPE CTV65

PRIMARYCURRENT

Inside Dia. (mm) Ø 16 21 25 or 31

Busbars (mm) 16mm 21mm 25mm or 31mmAPERTURES APERTURES APERTURES

Dimensions (mm) H 80 79 90

W 75 105 140

D 60 38 38

DIN Rail Mount – OPTION OPTION – –

Foot Mount l l l – OPTION

Terminal Cover l l l – –

60A 100A 250A 100A 1A

160A 250A 600A 6000A 6000A

RING TYPECAST RESINSERIES

All current transformers are supplied as standard with 5Asecondry. 1A secondry available by request.

A range of accuracies are available from 0.2S to class 3,protection and class X.

MANUFACTUREDTO ORDER

ANY SIZEANY BUSBAR

MANUFACTUREDTO ORDER

ANY SIZEANY BUSBAR

QualityHOBUT products are manufactured to stringentQuality Control techniques and the company isapproved to ISO 9001 certification.

3 PHASETYPE CT140FTYPE CT105FTYPE CT75

TYPE CTH127M

NEW

CUSTOMPRODUCTSHoward Butler Ltd.manufacture special CTsfor various applicationsthroughout the world. We manufacture highaccuracy CTs such as 0.2S& 0.5S, protection CTssuch as 5P10 & 5P20,Class X CTs and more. We can provide a solutionfor every low voltage CT application.

63

Page 64: First National Pakistan

64

Page 65: First National Pakistan

65

Page 66: First National Pakistan

66

Page 67: First National Pakistan

67

Page 68: First National Pakistan

Circuit breakers PR 60 J

A 15

Technical data PR 60 J – DCStandards EN 60 898-1, EN 60 947-2Number of poles 1, 2Instantaneous tripping characteristics C - according to EN 60 898-1, M - according to EN 60 947-2Rated current In A 0,2 - 63Rated voltage Un V 220; 440Short-circuit breaking capacity kA 4,5Electrical endurance switching cycles 4 000Mechanical endurance switching cycles 100 000Cross sectional area of inlet conductors mm2 1,5 - 25 for Cu conductors

2,5 - 25 for Al conductorsMounting on rail DIN 35x7,5 EN 60 715

on boardDegree of protection IP 20

IP 40 from the front panelAmbient air temperature °C from -25 to +55Working positions optionalResistance against vibrations 3g(8-50Hz)Approved ESS, ESČAccesories auxiliary and signal contacts - PKJ, 2PKJ,PKJ+SKJ

shunt trip - VCcovers - KSP1, KSP3indications labels - ŠNlockable operating means - UP1sealing blind - PZmounting brackets - PP, PL, PPL

Charakteristic CRated cur-rent In, A

Type desig-nation

Ordering number

0,5 PR 61J-C 0,5 00995101 PR 61 J-C 1 00995112 PR 61 J-C 2 00995123 PR 61 J-C 3 00995134 PR 61 J-C 4 00995146 PR 61 J-C 6 00995158 PR 61 J-C 8 0099516

10 PR 61 J-C 10 009951713 PR 61 J-C 13 009951816 PR 61 J-C 16 009951920 PR 61 J-C 20 009952025 PR 61 J-C 25 009952132 PR 61 J-C 32 009952240 PR 61 J-C 40 009952350 PR 61 J-C 50 009952463 PR 61 J-C 63 00995250,5 PR 62 J-C 0,5 00995501 PR 62 J-C 1 00995512 PR 62 J-C 2 00995523 PR 62 J-C 3 00995534 PR 62 J-C 4 00995546 PR 62 J-C 6 00995558 PR 62 J-C 8 0099556

10 PR 62 J-C 10 009955713 PR 62 J-C 13 009955816 PR 62 J-C 16 009955920 PR 62 J-C 20 009956025 PR 62 J-C 25 009956132 PR 62 J-C 32 009956240 PR 62 J-C 40 009956350 PR 62 J-C 50 009956463 PR 62 J-C 63 0099565

Rated cur-rent In, A

Type desig-nation

Ordering number

0,8 PR 61J-M 0,8 00995301,2 PR 61J-M 1,2 00995312 PR 61 J-M 2 00995323 PR 61 J-M 3 0099533

4,2 PR 61 J-M 4,2 00995346 PR 61 J-M 6 00995358 PR 61 J-M 8 0099536

10 PR 61 J-M 10 009953712 PR 61 J-M 12 009953814 PR 61 J-M 14 009953917 PR 61 J-M 17 009954021 PR 61 J-M 21 009954125 PR 61 J-M 25 009954232 PR 61 J-M 32 009954340 PR 61 J-M 40 009954450 PR 61 J-M 50 009954563 PR 61 J-M 63 00995460,8 PR 62 J-M 0,8 00995701,2 PR 62 J-M 1,2 00995712 PR 62 J-M 2 00995723 PR 62 J-M 3 0099573

4,2 PR 62 J-M 4,2 00995746 PR 62 J-M 6 00995758 PR 62 J-M 8 0099576

10 PR 62 J-M 10 009957712 PR 62 J-M 12 009957814 PR 62 J-M 14 009957917 PR 62 J-M 17 009958021 PR 62 J-M 21 009958125 PR 62 J-M 25 009958232 PR 62 J-M 32 009958340 PR 62 J-M 40 009958450 PR 62 J-M 50 009958563 PR 62 J-M 63 0099586

1 - pole

Scheme Picture

2 - pole

Scheme Picture

Charakteristic M

1 - pole

2 - pole

68

Page 69: First National Pakistan

Circuit breakers PR 60 J

A 16

Protection of DC circuits

It is possible to use both PR 60 and PR 60 J miniature circuit breakers for protection of DC circuits depending on voltage.

For voltage Un up to:

• 40Vd.c.useminiaturecircuitbreakersPR60.Sourcepoles(+)and(-)canbeconnectedtothe circuit breaker terminals arbitrarily.• 220Vd.c.or440Vd.c.,useminiaturecircuitbreakersPR61JorPR62J.Astheseminiaturecircuit breakersareequippedwithpermanentmagnets,sourcepoles(+)and(-)mustbeconnectedto identicallymarkedterminalsofthecircuitbreakers(seeconnectionexample).

69

Page 70: First National Pakistan

70

Page 71: First National Pakistan

71

Page 72: First National Pakistan

72

Page 73: First National Pakistan

73

Page 74: First National Pakistan

74

Page 75: First National Pakistan

75

Page 76: First National Pakistan

76

Page 77: First National Pakistan

77

Page 78: First National Pakistan

78

Page 79: First National Pakistan

79

Page 80: First National Pakistan

80

Page 81: First National Pakistan

81

Page 82: First National Pakistan

82

Page 83: First National Pakistan

CONTA-CLIP

Product overview

Three-wire installation

terminals DLI|DLIS

Page 80

Screw connection system

SRK|SSL

Page 16

Screw connection system

RK|SL

Page 24

Double-level terminal blocks

RKD|RKDG

Page 46

Test-disconnect

terminals PTK

Page 68

Fuse-disconnect terminals

STK|SIK

Fused terminals SK

Page 72

Feed-through terminals for

direct no-rail mounting

Page 92

Tension-spring connection

system

ZRK|ZSL

Page 138

Double-level terminal blocks

ZRKD| Double-level PE

terminal ZSLD

Page 152

Triple-level terminal block

ZIKD

Page 158

Screw connectionsystem

Pressure-springconnection system

Pressure-spring connection

system

FRK|FSL

Page 106

Disconnect-blade terminals |

Disconnect terminals | Fused

terminals FTRK

Page 122

Double-level terminal blocks

FRKD | Double-level PE

terminal FSLD

Page 116

8

CONTA-CONNECT

Tension-springconnection system

83

Page 84: First National Pakistan

Triple-level terminal block

IKD|IK

Page 58

Triple-level terminal block

IKD|DLI

Page 56

Disconnect terminal

TRK|STK 2|TK

Page 62

Motor-connection terminal

VMAK

Page 57

Pluggable connection system

PK-TS

Page 100

Disconnect-blade terminals |

Disconnect terminals | Fused

terminals FTRK

Page 162

Three-wire installation

terminals FDLIS

Page 128

Motor-connection terminal

ZVMAK

Page 159

Compact terminal series for

direct mounting ZSRK | ZSLN

Page 178

9

84

Page 85: First National Pakistan

CONTA-CLIP

Product overview

End stops

Page 274

End support

Page 274

Cuttable terminal rails EKB

Page 224

Shield-connection clip SAB |

SSAB

Page 230

DIN rails TS

Page 268GENERALACCESSORIESCONTA-CONNECT

10

CONTA-CONNECT

Ceramic terminal blocks KKB

Page 228

Stud connection system HSK

Page 186

Transformer terminals

TKS|TK

Page 198

SPECIAL TERMINALS Feed-through terminals RK | Fused

terminals SIK/SK, in high-temp.

design

Page 206

Test adapters

Page 318

labelling adapters

Page 314

Test plugs

Page 317

Fuse holders

Page 322

85

Page 86: First National Pakistan

Shield-connection clip SAB |

SSAB

Page 230

EX terminal blocks ATEX

Page 242

Marker holders for terminal

blocks and end stops

Page 276

Cross-connections

(Potential distribution)

Page 282

11

Covers

Page 310

End plates | Visual separation

Page 278

Terminal blocks for temperature

measuring circuits TSK

Page 210

Screw-distributor blocks SVB

Page 218

Terminal blocks with spade

connection FF/SF

Page 212

Pressure-spring junction

terminals D

Page 222

Fuse cartridges

Page 324

Specific accessories

Page 326

CE electrical cabinet

socket outlet

Page 330

86

Page 87: First National Pakistan

87

Page 88: First National Pakistan

AUXILIARY RELAYS FOR TRIPPING APPLICATIONS

88

Page 89: First National Pakistan

Auxiliary relays | Tripping applications

ARTECHE offers a wide range of relays specially designed to be used in circuit breaker tripping applications.

› Interface between protection and control equipments and HV and/or MV circuit breakers, eliminating risks in case of internal failure of the circuit breaker.

› Trip contacts multiplication, to operate directly on the circuit breaker and transmit the corresponding alarms in a minimum time.

› Trip and lock-out, with electric or hand reset to avoid accidental closing of circuit breakers associated to power transformers, generators or machines.

› The surveillance of the trip circuit, guarantees it is in perfect conditions to allow the trip when it is needed.

ANSWER FOR ANY TRIPPING APPLICATION

In addition to the specific applicable standards, ARTECHE auxiliary relays are designed based on the fulfilment of the following standards:

› IEC 61810: Electromechanical all-or-nothing relays.

› IEC 60255: Electrical relays. Measuring relays and protection

equipment.

› IEC 61812: Specified time relays for industrial use.

› IEC 61812: Relés de tiempo especificado para aplicaciones

industriales.

› IEC 60947: Low-voltage switchgear and controlgear.

› IEC 61000: Electromagnetic compatibility.

TECHNICAL STANDARDS

GENERAL STANDARDS

89

Page 90: First National Pakistan

usAuxiliary relays | Tripping applications

Some of the general characteristics of the ARTECHE trip relays are:

In addition, the different number of alternatives that are offered when the equipment is selected, both technically (increase of the breaking capacity by serial contacts or by the magnetic blow out, high speed operation of the output contacts, possibility of adding different options to the relay) and in the assembly method (front, rear or flush mounted sockets, with screws or fastons) must be considered.

› High isolation level between input and output circuit, which guarantees that a problem in the circuit breaker will not cause irreparable damages on the protection system.

› Fast operating times, down to 3 ms, minimizing the impact on the total trip time.

› High breaking capacity, which allows direct operation on highly inductive circuits.

› Sturdy design, which ensures high reliability.

› Wide range of auxiliary voltage (Vdc and Vac).

› Self-cleaning of the contacts.

› Security contacts according to EN 50205.

› Easy installation (plug-in relays with diff erent installation possibilities).

› Designed to work in permanent service, even at high temperature for the whole voltage range.

› Possibility to work in environments with relative humidity of 100%.

› Seismic characteristics, allowing their use in installations which can be subject to vibrations, as for example in power stations or in regions with high risk of seism.

› High protection degree (IP40), with transparent cover, making them appropriate for tropical and saline environments.

› Fulfi lment of the most demanding standards: IEC, EN, IEEE, CE and UL mark.

› No maintenance needed.

GENERALCHARACTERISTICS

90

Page 91: First National Pakistan

Auxiliary relays | Tripping applications

RANGE OF PRODUCTS

Instantaneous trip relays, whose contacts change instantaneously from the rest position to the working position when the coil is energized. The contacts return to the rest position when the coil is no longer energized.

This range includes relays with 2, 4 and 8 contacts, with operating times from 3 ms to 8 ms, depending on the model.

All the relays include a diode in parallel with the coil (see auxiliary relays with overvoltage protection characteristic) and comply with the sock and vibration standards, related to the relays with seismic characteristics.

Trip relays with 2 stable positions for the output contacts. Depending on which coil is energized, the contacts will change from one position to the other. The design of the ARTECHE relays has no consumption in permanence, and prevents both coils from being energized simultaneously.

This range includes relays with 3, 4 and 8 contacts, with operating times below 10 ms, depending on the model, and possibility of manual reset. The position change is made with 2 sets of coils with separated entrances, in BF-3 and BJ-8, and with breaking-flame contacts for each set of coils.

For single phase or three phase circuit breakers. Through a small supervision current the whole circuit is supervised, in both positions of the circuit breaker (opened or closed).

The correct state of the circuit is showed with a green LED on the front plate of the relay. The output contacts change its position if the relay detects a failure in the continuity of the circuit.

Auxiliary relay with four changeover contacts, aimed to supervise the failure of trip supply. Connecting the relay across the trip circuit supply, the equipment is normally energized. Faults will occur when the trip voltage is lost, so the relay drops off in those cases, providing the related signs and alarms.In order to avoid faulty alarms due to instantaneous supply voltage dips, the drop off time of the relay is delayed over 100 ms so those non-permanent failures of trip supply would not be considered.

TRIP RELAYS

TRIP AND LOCKOUT RELAYS

TRIP CIRCUIT SUPERVISION RELAYS

AUXILIARY SUPPLY CIRCUIT SUPERVISION RELAYS

91

Page 92: First National Pakistan

c'i\lus (Auxiliary relays | Tripping applications

TRIP RELAYS (I)Model RD-2R RD-2XR RF-4R RF-4XR

Applications Intended for tripping applications where high demanding requirements in operating time (with tripping time from 8ms to 3 ms) and breaking capacity are needed,

that is the case of tripping HV and MV circuit breakers.

High burden confi guration not available See page 15 for technical details

Construction characteristics

Contacts no. 2 Changeover 4 Changeover

Connections

OptionsWith 0P options • LED included • Diode in parallel with the coil included

Weight (g) 125 250

Dimensions (mm) 22,5 x 50,4 x 72 42,5 x 50,4 x 72 (F short Type)

Coil characteristics

Standard voltages(1) 24, 48, 110, 125, 220,

250 (4) Vdc /110, 127,

230 Vac (50-60Hz)

24, 48, 110, 125, 220,

250 Vdc

24, 48, 110, 125, 220,

250 (4) Vdc / 110, 127,

230 Vac (50-60 Hz)

24, 48, 110, 125, 220,

250 (4) Vdc

Voltage range +10% -20% UN

Pick-up voltageSee pick-up/release voltage-temperature curves

Release voltage

ConsumptionsIn permanence (U

N)

Peak • ≤96 Vdc

Peak • >96 Vdc

0,95 W 1 W

0,8 A / 20 ms 2,5 A / 20 ms 0,8 A / 20 ms 2,5 A / 20 ms

0,3 A / 20 ms 0,8 A / 20 ms 0,3 A / 20 ms 0,8 A / 20 ms

Operating time

Pick-up time <8 ms (<10 ms Vac) <5,5 ms <8 ms (<10 ms Vac) <5,5 ms

Drop-out time Vdc: <40 msVac: <50 ms

Vdc: <40 ms Vdc: <40 msVac: <50 ms

Vdc: <40 ms

Contacts

Contact material AgNi

Contacts resistance(2) ≤30 mΩ

Distance between contacts 1,2 mm

Permanent current 10 A

Instantaneous current 30 A during 1 s / 80 A during 200 ms / 200 A during 10 ms

Max. making capacity 40 A / 0,5 s / 110 Vdc

Breaking capacity See breaking capacity curves (Contact confi guration type B)

Max. breaking capacity See value for 50.000 operations

Umax

opened contact 250 Vdc / 400 Vac

Perfomance data

Mechanical endurance 107 operations

Operating temperature -25ºC +70ºC

Storage temperature -30ºC +70ºC

Max. operating humidity 93% / +40ºC

Operating altitude(3) <2000 m

(1) Other voltage upon request (2) Guarantee data for relays just manufactured

(3) Ask for higher altitudes (4) Voltage not recognized by UL

1

2

( –)

( +)

711

12

13

14

10

5

3

4 8

9

6

2( +)

1( –) 7

53

4

8

6

92

Page 93: First National Pakistan

c'i\lus (,,-

.

Auxiliary relays | Tripping applications

3

1

a

d

( –)

( +)

2

4

5

6

7

8

1110

202130314041505160

70

80

61

71

81

Model RJ-8R RJ-8XR RJ-4XR4

ApplicationsIntended for tripping applications where high quality requirements in operating time (with

models even tripping in less than 3 ms) and breaking capacity are needed, that is the case of

tripping HV and MV circuit breakers.

High burden confi guration See page 15 for technical

details

See page 15 for technical

detailsnot available

Construction characteristics

Contacts no. 8 Changeover4 Changeover +

4 Fast Singles-Inversors without break power

Connections

Options With 0P options • LED included • Diode in parallel with the coil included

Weight (g) 500 335

Dimensions (mm) 82,5 x 50,4 x 72 (J short type) 42,5 x 50,4 x 82,5 (F short Type)

Coil characteristics

Standard voltages(1) 24, 48, 110, 125, 220, 250 (4) Vdc/110, 127, 230 Vac (50-60 Hz)

24, 48, 110, 125, 220, 250(4) Vdc

110, 125, 220, 250 (4) Vdc

Voltage range +10% -20% UN

+15% -20% UN

Pick-up voltage / Release voltage See pick-up/release voltage-temperature curves

Consumptions In permanence (U

N)

Peak • ≤96 Vdc

Peak • >96 Vdc

1,4 W 6,5 W

0,8 A / 20 ms 2,5 A / 20 ms 25 W / 5 ms

0,3 A / 20 ms 0,8 A / 20 ms

Operating time

Pick-up time <8 ms Vdc (<10 ms Vac)(Range 24 Vdc <10 ms)

<6,5 ms Contacts 1-4: <3 msContacts 5-8: <20 ms

Drop-out time Vdc: <40 msVac: <50 ms

Vdc: <40 ms Contacts 1-4: <25 ms Contacts 5-8: <50 ms

Contacts

Contact material AgNi Contacts 1-4: AgNi 10 Contacts 5-8: Ag1000

Contacts resistance(2) ≤30 mΩ

Distance between contacts 1,2 mm Contacts 5-8: 1,2 mm

Distance between contacts 10 A Contacts 5-8: 15 A Contacts 1-4: 8 A

Instantaneous current 30 A during 1 s / 80 A during 200 ms / 200 A during 10 ms

Max. making capacity 40 A / 0,5 s / 110 Vdc

Breaking capacity See breaking capacity curves (Contact confi guration type B)

Max. breaking capacity See value for 50,000 operations

Umax

opened contact 250 Vdc / 400 Vac

Perfomance data

Mechanical endurance 107 operations

Operating temperature -25ºC +70ºC

Storage temperature -30ºC +70ºC

Max. operating humidity 93% / +40ºC

Operating altitude(3) <2000 m

5

7

d

a

( +)

( -)

6

4

3

2

1

88180

707160615051404130

20

10

31

21

11

Hig

h br

eaki

ng

capa

city

Trip

TRIP RELAYS (II)

(1) Other voltage upon request (2) Guarantee data for relays just manufactured

(3) Ask for higher altitudes (4) Voltage not recognized by UL

93

Page 94: First National Pakistan

Auxiliary relays | Tripping applications

(1) Other voltage upon request (2) Ask for higher altitudes

Model RXR-4

Applications Tripping applications with very high speed requirements

High burden confi guration not available

Construction characteristics

Contacts no. 4 Changeover

Connections

Options No options available

Weight (g) 126

Dimensions (mm) 53 x 90 x 58

Coil characteristics

Standard voltages(1) 110, 125, 250 Vdc

Voltage range +10% -20% UN

Pick-up voltage 40%

Release voltage 28%

Consumptions <3 W

Operating time

Pick-up time <3 ms

Drop-out time <3 ms

Contacts

Contact material AgNi

Permanent current 8 A

Max. making capacity 15 A during 4s

Breaking capacity See breaking capacity curves

Umax

opened contact 250 Vdc / 400 Vac

Performance data

Mechanical endurance 107 operations

Operating temperature -10ºC +55ºC

Storage temperature -30ºC +70ºC

Max. operating humidity 93% / +40ºC

Operating altitude(2) <2,000 m

TRIP RELAYS (III)

1

2

( –)

( +)

NO1

NC2

N02

N03

N04

NC3

NC4

NC1

C1

C2

C3

C4

94

Page 95: First National Pakistan

c'i\lus

=--r-=--r-=--r-=--r-=--r-=--r-=--r-=--r-

Auxiliary relays | Tripping applications

(1) Other voltage upon request (2) Ask for higher altitudes

TRIP AND LOCKOUT RELAYS (I)Model BF-3R BF-4R BJ-8R

Applications Intended for trip and lockout applications where high demanding requirements in operating time and breaking capacity are needed.

High burden confi gurationnot available

See page 15 for technical

details

See page 15 for

technical details

Construction characteristics

Contacts no. 3 Changeover 4 Changeover 8 Changeover

Connections

Options Options are not available

Weight (g) 300 600

Dimensions (mm) 45 x 45 x 96,5 (F short Type) 90 x 50 x 100,5(J short Type)

Coil characteristics

Standard voltages(1) 24, 48, 72, 110, 125, 220 Vdc / 63,5, 110, 127, 230 Vac (50-60 Hz)

Voltage range +10% -20% UN

Pick-up voltage See pick-up voltage / temperature curves for Latching relays

Consumptions only in the change-over 27 W 23 W 35,5 W

Operating time

Pick-up time <10 ms (Vdc) <20 ms (Vac) <10 ms (Vdc) <20 ms (Vac)

Contacts

Contact material AgNi

Distance between contacts 1,8 mm

Permanent current 10 A

Instantaneous current 880 A during 200 ms / 200 A during 10 ms

Max. making capacity 40 A / 0,5 s / 110 Vdc

Breaking capacity See breaking capacity curves (Contact confi guration type A)

Max. breaking capacity See value for 50.000 operations

Umax

opened contact 250 Vdc / 400 Vac

Performance data

Mechanical endurance 107 operations

Operating temperature -40ºC +70ºC

Storage temperature -40ºC +70ºC

Max. operating humidity 93% / +40ºC

Operating altitude(2) <2000 m

913812711

5

4

3

1410

21

+-

+-

Set

Reset

10149138

712

11

6

5

4

3

B1

12-

+

+

Set

Reset

11

51

21

61

20

60

31

71

41

81

30

70

40

80

1

5

2

6

3

7

4

8

a

c

b

d

+

+

-

-

Set

Reset50

10

95

Page 96: First National Pakistan

=-r=-r=-r

~ =-r-L2:r =-r

=-r=-r=---r-

c'i\lus (

Auxiliary relays | Tripping applications

(1) Other voltage upon request (2) Ask for higher altitudes

TRIP AND LOCKOUT RELAYS (II)Model BF-4RP BJ-8RP

Applications Intended for tripping and locking applications where high quality requirements in operating

time and breaking capacity are needed, with manual reset.

High burden confi guration See page 15 for technical details See page 15 for technical details

Construction characteristics

Contacts no. 4 Changeover 8 Changeover

Connections

Options Options are not available

Weight (g) 300 600

Dimensions (mm) 45 x 45 x 96,5 (F short Type) 90 x 50 x 100,5 (J short Type)

Coil characteristics

Standard voltages(1) 24, 48, 72, 110, 125, 220 Vdc63,5, 110, 127, 230 Vac (50-60 Hz)

Voltage range +10% -20% UN

Pick-up voltage (20ºC) See pick-up voltage / temperature curves for Latching relays

Consumptions only in the change-over 23 W 35,5 W

Operating time

Pick-up time <10 ms (Vdc) <13 ms (Vac) <10 ms (Vdc) <20 ms (Vac)

Contacts

Contact material AgNi

Distance between contacts 1,8 mm

Permanent current 10 A

Instantaneous current 80 A during 200 ms / 200 A during 10 ms

Max. making capacity 40 A / 0,5 s / 110 Vdc

Breaking capacity See breaking capacity curves (Contact confi guration type A)

Max. breaking capacity See value for 50,000 operations

Umax

opened contact 250 Vdc / 400 Vac

Performance data

Mechanical endurance 107 operations

Operating temperature -40ºC +70ºC

Storage temperature -40ºC +70ºC

Max. operating humidity 93% / +40ºC

Operating altitude(2) <2000 m

11

51

21

61

20

60

31

71

41

81

30

70

40

80

1

5

2

6

3

7

4

8

a

c

b

d

+

+

-

-

Set

Reset50

10

10149138

712

11

6

5

4

3

B1

12-

+

+

Set

Reset

96

Page 97: First National Pakistan

c'i\lus (EAuxiliary relays | Tripping applications

(1) Other voltage upon request (2) Ask for higher altitudes

Model VDF-10 VDJ-30

Applications Trip circuit supervision for single-phase circuit

breakersTrip circuit supervision for three-phase circuit

breakers

Construction characteristics

Timing Contacts no. 2 Changeover 2 Changeover

Connections

Options Options are not available

Weight (g) 100 163

Dimensions (mm) 42,5 x 50,4 x 96,6 (F short Type) 82,5 x 50,5 x 96,6 (J short Type)

Coil characteristics

Standard voltages(1) 24/30, 60, 110/125, 220 Vdc, 110/127, 230 Vac (50-60 Hz)

Voltage range +10% -25% UN

Pick-up voltage (23º C) 70% UN

Release voltage (23º C) 50% UN

Consumptions 3,1 W 3,63 W

Operating time

Drop-out time >200 ms

Contacts

Contact material AgNi

Permanent current 8 A

Instantaneous current 15 A

Max. making capacity 15 A during 4 s

Max. breaking capacity 0,3 A / 110 Vdc

Umax

opened contact 250 Vdc / 400 Vac

Performance data

Mechanical endurance 107 operations

Operating temperature -10ºC +55ºC

Storage temperature -30ºC +70ºC

Max. operating humidity 93% / +40ºC

Operating altitude(2) <2000 m

TRIP CIRCUIT SUPERVISION RELAYS

+

-

TRIP SUPPLY

TRIP SUPPLY

Trip contact

6 51 4

FU

FU

CB

CIRCUIT BREAKER

K1 K2

10 14 9 132 12 8

52a 52b

TRIP SUPPLY

+

-TRIP SUPPLY

1Trip contact

1 2

CB1

FU

FU

CB2 CB3

CIRCUIT BREAKER

a

h

K11

11 21 31 41 7110

52a

52a

52a

52b

52b

52b

20 30 40 70

K21

K12

K22

K13

K23

3 b 4 e 7

2

Trip contact

3

Trip contact

97

Page 98: First National Pakistan

Auxiliary relays | Tripping applications

(1) Other voltage upon request (2) Guarantee data for relays just manufactured (3) Ask for higher altitudes

Model RUT-4

Applications Supervise only the auxiliary supply circuit of the protection equipments,

avoiding false alarms due to short-time drop of supply

Construction characteristics

Timing Contacts no. 4 Changeover

Connections

Options Options are not available

Weight (g) 250

Dimensions (mm) 42,5 x 50,4 x 96,6 (F short Type)

Coil characteristics

Standard voltages (1) 24, 48, 72, 110, 125, 220 Vdc

Voltage range +10% -20% UN

Pick-up voltage See pick-up release voltage-temperature curves for standard relays

Release voltage

Consumptions in permanence 3,9 W

Operating time

Pick-up time <20 ms

Drop-out time To minimum voltage

Maximum>100 ms<400 ms

Contacts

Contact material AgNi

Contacts resistance (2) ≤30 mΩ

Distance between contacts 1,8 mm

Permanent current 10 A

Instantaneous current 80 A during 200 ms / 200 A during 10 ms

Max. making capacity 40 A / 0,5 s / 110 Vdc

Breaking capacity See breaking capacity curves (Contact Confi guration Type A)

Max. breaking capacity See value for 50.000 operations

Umax

opened contact 250 Vdc / 400 Vac

Performance data

Mechanical endurance 107 operations

Operating temperature -10ºC +55ºC

Storage temperature -30ºC +70ºC

Max. operating humidity 93% / +40ºC

Operating altitude(3) <2000 m

AUXILIARY SUPPLY SUPERVISION RELAYS

11

3

(-)(-) 1

(+)(+) 2

4

5

6

12

13

14

7

8

9

10

98

Page 99: First National Pakistan

Auxiliary relays | Tripping applications

HIGH / LOW BURDEN CONFIGURATION (HIGH SPEED TRIPPING RELAYS ONLY)

The standard high speed tripping relays are manufactured with a low burden configuration, considering that the initiating contact is placed close to the tripping relay.

However, and in order to avoid unwanted trip relay operation due to pickup or transients, particularly if the relay operating coil is connected to extensive wiring, ARTECHE tripping relays could be manufactured with a high burden configuration, complying with ESI 48-4 international standard, as EB2 class relays. These EB2 class relays are suitable for use in high security circuit breaker tripping circuits, increasing their immunity to capacitance discharge currents.

Instantaneous relays (self reset relays): same consumption as low burden configuration

Latching relays (electric and hand&electric reset): See table below

For relays with rated voltage up to and including the 125 V, the relays will withstand, without operating, a discharge into their operate circuits of a 10μF capacitor charged to 120% of the higher rated voltage for the relay.

For relays with rated voltage of 220 V, the relays will withstand, without operating a discharge into their operate circuits of a 10μF capacitor charged to 100% of the higher rated voltage for the relay, i.e 242 V.

Specifications:

ESI 48-4 EB1: 1983 Low BurdenESI 48-4 EB2: 1983 High Burden

HIGH BURDEN RELAYS CONSUMPTIONS

Electrical reset and hand and electrical reset relays

Standard Voltage 220 Vdc 125 Vdc 24 Vdc

Consumption (only in commutation) < 150 W (peak) < 100 W (peak) < 75 W (peak)

99

Page 100: First National Pakistan

OGIPRO

Company

First National Pakistan155-A Sarfraz Rafiqui RoadLahore Cantt.Pakistan

Our sign JE Peggau, 01st September 2013

Authorized Distribution Letter

Dear Sirs,

GIPRO GmbH in Peggau Austria hereby confirms that First National Pakistan, 155-ASarfraz Rafiqui Road, Lahore Cantt., Pakistan is authorized to represent and to sellGIPRO products in the area of PAKISTAN.

The products are:In- and Outdoor epoxy insulators for several different applicationsSurge arrestors for several needs

With kind regards,

L

Mana ing Director

AnschriftGIPROGmbHWilhelm-Jentsch-Strasse2A 8120 Peggau

BankverbindungBank Die SteiermiirkischeBLZ 20815Kto.Nr. 0000-958702IBAN AT642081500000958702SWIFT/BIC STSPAT2G

FirmendatenFN 144442sUID-Nr ATU40635906ARA-Lizenz 4622

Kommunikation

20130901 JE GIPRO Authorized distribution letter to First National Pakistan.doc

Tel +433127209400Fax +43 3127 20940 40Email [email protected]://www.gipro.com

100

Page 101: First National Pakistan

theperFectFit

101

Page 102: First National Pakistan

102

Page 103: First National Pakistan

Reference Adress for supply:

GIPRO GmbH

Wilhelm-Jentsch-Strasse 2

8120 Peggau

AUSTRIA - EUROPE

[email protected] | www.gipro.com

103

Page 104: First National Pakistan

104

Page 105: First National Pakistan

105

Page 106: First National Pakistan

;;

J

TYPE TEST REPORTS relating toVARISlLTMHE polymer housectsurge arresters & associated accessories

I

TYPE TESTS REFERENCE SAMPLES TEST REPORT ADDITIONALPERFORMED STANDARD TESTED Reference Dete ' Langutf!!1_6 INFORMATION

, Housings rated CESI12 kV, 24 kVAT-A1f025452 September 3, 2001 English

Insulation withstand tests. &.36kVon the housings lEG 600994- Housing rated CESI

,

& § 10..8.2 1B kV &. type S3 AT ·A1/025961 September 5, 2001 English ,

the insu'latin9 bracketI insulating bracket .I

,

Housing rated CESI August 10, 2006 English, 42 kV A6/02i821 I

Technical dooumentSteep, lightning TPF ST HE 041 e rev. 02 Iand switching lEG 60099-4 6 kV CBSI , (January 4, 2010, English)currenl impulse § 10.8.3 prorated sections AT-AOJ041526 January 25, 2001 English &. Voltage vs current characteristic curve :

residual voltage tests VI 8997 01 XX (E rev. 03II (January "I, 2010, Engllsh)

HE18S0 C.ESI June 7, 2001 EnglishLong duration current lEG 60099-4 surge arresters AT-A1J014923 I

I impulse withstand test §10.8..4 6 kV 81D2 CESI •'September 28,2005 English ,

, prorated sections A5f0465386 kV CESI

January 25, 2001 English I

_prorated sections AT-AO!041527High Gurrent impulse IEC 60099-4 HE 18 80 CBS'I I i

I June 7, 2001 EngUsh, operating duty test § 10.8.5 surge arresters AT -A 1/014924

6 kV S1D2 CESI December 14, 2005 English,

prorated sections A5/055428

Date: January g, g013 Page: 1 J 2Refer.ence : TPF ST HE 01/ E rev. 19,

106

Page 107: First National Pakistan

TYPE TESTS REFERENCE SAMPLES TEST REPORT ADDITIONAL IPERFORMED STANDARD TESTED Reference Date Language INFORMATION

Voltage vs time IEC 60099-4 HE range Curve UT 8997 01 XX I E rev. 02characteristic curve § 6.10 (January 4,2010, English)

lEG 60099-4 CESI September 14,2011 EnglishTest carried out

§ 8.6.2.1 8102744'9 in series with a 6 kV 53D2 section

Tests on lEG 60099-4 Type S3D2 CESI September 14,2011 English Test carried out

disconnector _§_ 8.6.2.2 disconnector 81027448 in series with a 6 kV S302 section

lEe 60099-4 CESICurrent vs time characteristic curve

September 13, 2011 English CT 8997 09 9X I E rev. 02§ 8.6.3 B1027905 J (September 14, 20·11, English)

Tests on lEG 60099-4 Type IF CESICurrent vs time characteristic curve

September 11, 1997 English CT 899509 04 I E rev. 08fault indicator § 8.6.4 fault indicator MP·97/026984 (January 4,2010, English)

Short circuit tests IEC 60099-4 HE 24 CESIJune 25, 2008 English§ 10.B.7 surge arresters A8018577

Partial discharge test lEG 60099-4 HE 36 CESI December 22,2000 Engllish§ 10.8.8 surge arresters AT·AOJ042489

Bending moment test lEG 60099-4 HE 36 TRIDELTA I seas November 15, 2012 English§ 10.8.13 surge arresters TR.e 12018BMIEC 60099-4

HE 36 CESI t§ 10.8.14.2.1 December 18, 2002 English(1000 h test) surge arrester AT ·A2J032924

Weather ageing testlEG 60099-4§ 10.8..14.2.2 HE 24 CESI March 27, 2003 English(5000 h test)_ surge arrester AT ·A3/007530

b :reference Is.m_ to the Iatast version of lEe 60099-4 standard, ~ edition 22 published in May 2009

107

Page 108: First National Pakistan

Type HE 12Rated voltage Ur in kV rms 12

Rated frequency Hz 50 / 60Continuous operating voltage Uc in kV rms 10,2

Nominal discharge current In in kA with 8/20 impulse 10Line discharge class Class 1

High current impulse withstand kA with 4/10 impulse (x 2) 100Maximum leakage current under Uc at 20 °C resistive component in mA peak 1,0

capacitive component in mA peak 0,5total current in mA rms 1,0

nergy absorption capability with 8/20 impulse kJ / kV of Ur 4,1kJ / kV of Uc 4,8

Long duration current impulse withstand A with 2000 µs impulse (x 18 + 1) 300ergy absorption capability with 2 ms impulse kJ / kV of Ur 2,0

kJ / kV of Uc 2,4kV peak at 2.5 kA 8/20 29,0

Maximum lightning residual voltage kV peak at 5 kA 8/20 30,8kV peak at 10 kA 8/20 32,8kV peak at 20 kA 8/20 36,2kV peak at 40 kA 8/20 41,2

Maximum switching residual voltage kV peak at 125 A 30/80 24,6kV peak at 500 A 30/80 26,1kV peak at 1 kA 30/80 27,1kV peak at 5 kA 1/2.5 32,3

mum steep current impulse residual voltage kV peak at 10 kA 1/2.5 35,4Temporary overvoltage capability in kV rms 1 s without prior duty 15,5

1 s with prior duty 14,01 s with maximum prior duty 13,5

10 s without prior duty 14,810 s with prior duty 13,3

10 s with maximum prior duty 12,9Minimum reference voltage at 20 °C Iref in mA peak AC 1

Uref in kV peak/V2 11,6Short circuit current withstand kA during 0.2 s 20

A during 1.0 s 600Axial partial discharge level pC under 1.05*Uc < 10

Mechanical strength specified short-term load SSL in N.m 125specified long-term load SLL in N.m 100

dynamic pull loading in N 750static pull loading in N 500

torsion in N.m 30Line terminal maximum conductor diameter in mm 18

permissible materials Cu / Al / SteelEarth terminal maximum conductor diameter in mm s/ option

permissible materials Cu / Al / SteelInsulation withstand power frequency 1 min dry in kV rms 42

power frequency 1 min wet in kV rms 381.2/50 lightning impulse dry in kV peak 95

Physical characteristics of the housing material siliconenb of weathersheds ( small / large ) 4 / 5

weathersheds diameter in mm 74 / 104Nominal creepage distance mm 480

mm / kV of Ur 40,0Nominal arc length mm 195

Option S3D21,7Approximate weight in kg