Firestop collar CFS-C P - Hilti · 63 mm 82 mm: 32 mm 1 pc: 435407 CFS-C P 90/3” 90 mm 117 mm: 42...

5
Scan this code to find out more: hilti.co.uk/ r4831 Firestop collar CFS-C P Technical data Base materials Aerated concrete, Concrete, Masonry, Drywall Approvals ETA-10/0404 Application temperature range -5 - 50 °C Temperature resistance range -20 - 100 °C Reaction to fire class (EN 13501-1) E Shelf life 1) Not relevant Can be painted No LEED VOC 7.6 g/l Minimum ceiling thickness 150 mm Minimum wall thickness 100 mm 1) at 77 °F / 25 °C and 50% relative humidity; from date of manufacture Applications Sealing flammable pipes from 50 mm to 250 mm in diameter in penetrations through fire compartment walls and floors Pipe materials: PVC, PVC-U, PE, PE-HD, PE-X, PP, ABS, Al-composite Suitable for use in openings in concrete, aerated concrete, masonry and drywall Different backfilling and sealing materials are covered Advantages Quick and easy closure without use of a tool Tab position is adjustable for simple fastening Sound decoupling strip based on PE (foam) can be used Low profile for installation where space is tight Ordering designation Nominal pipe diameter Outside diameter Height Sales pack quantity Item number CFS-C P 50/1.5” 50 mm 67 mm 22 mm 1 pc 435406 CFS-C P 63/2” 63 mm 82 mm 32 mm 1 pc 435407 CFS-C P 90/3” 90 mm 117 mm 42 mm 1 pc 435409 CFS-C P 110/4” 110 mm 146 mm 47 mm 1 pc 435410 CFS-C P 125/5” 125 mm 166 mm 48 mm 1 pc 435411 CFS-C P 160/6” 160 mm 236 mm 48 mm 1 pc 435412 CFS-C P 180/7” 180 mm 228 mm 153 mm 1 pc 435413 CFS-C P 200/8” 200 mm 257 mm 178 mm 1 pc 435414 CFS-C P 225/9” 225 mm 289 mm 203 mm 1 pc 435415 CFS-C P 250/10” 250 mm 319 mm 233 mm 1 pc 435416 1 Firestop bandage CFS-C P hilti.co.uk/r4831 | Issue 08/2016

Transcript of Firestop collar CFS-C P - Hilti · 63 mm 82 mm: 32 mm 1 pc: 435407 CFS-C P 90/3” 90 mm 117 mm: 42...

Scan this code to findout more:

hilti.co.uk/ r4831

Firestop collar CFS-C P

Technical dataBase materials Aerated concrete, Concrete,

Masonry, DrywallApprovals ETA-10/0404

Application temperature range -5 - 50 °C

Temperature resistance range -20 - 100 °C

Reaction to fire class (EN 13501-1)

E

Shelf life1) Not relevant

Can be painted No

LEED VOC 7.6 g/l

Minimum ceiling thickness 150 mm

Minimum wall thickness 100 mm1) at 77 °F / 25 °C and 50% relative humidity; from date of manufacture

Applications■ Sealing flammable pipes from 50 mm to 250 mm in diameter

in penetrations through fire compartment walls and floors■ Pipe materials: PVC, PVC-U, PE, PE-HD, PE-X, PP,

ABS, Al-composite■ Suitable for use in openings in concrete, aerated concrete,

masonry and drywall■ Different backfilling and sealing materials are covered

Advantages■ Quick and easy closure without use of a tool■ Tab position is adjustable for simple fastening■ Sound decoupling strip based on PE (foam) can be used■ Low profile for installation where space is tight

Ordering designation Nominal pipe diameter Outside diameter Height Sales pack quantity

Item number

CFS-C P 50/1.5” 50 mm 67 mm 22 mm 1 pc 435406CFS-C P 63/2” 63 mm 82 mm 32 mm 1 pc 435407CFS-C P 90/3” 90 mm 117 mm 42 mm 1 pc 435409CFS-C P 110/4” 110 mm 146 mm 47 mm 1 pc 435410CFS-C P 125/5” 125 mm 166 mm 48 mm 1 pc 435411CFS-C P 160/6” 160 mm 236 mm 48 mm 1 pc 435412CFS-C P 180/7” 180 mm 228 mm 153 mm 1 pc 435413CFS-C P 200/8” 200 mm 257 mm 178 mm 1 pc 435414CFS-C P 225/9” 225 mm 289 mm 203 mm 1 pc 435415CFS-C P 250/10” 250 mm 319 mm 233 mm 1 pc 435416

1

Firestop bandage CFS-C P

hilti.co.uk/r4831 | Issue 08/2016

General information

Partition Flexible wall Rigid wall Rigid floorBase material thickness (tE) ≥ 100 mm ≥ 100 mm

≥ 450 g/m3≥ 150 mm

≥ 2400 g/m3

Minimum annular gap 25 mm 15 mm 10 mmFixing to wall M8 threaded rods and nuts HUS, DBZ, HSA

Ø ≥ 6 mm for collar up to 110 mm, Ø ≥ 10 mm larger collarsGap filler CFS-S ACR, gypsum, cementitious mortar CFS-S ACR with backfilling, gypsum,

cementitious mortarPenetration PVC, PVC-U, PE, PE-HD, PE-X, PP, ABS, Aluminium Composite

*e.g. Magnaplast “Skolan-dB”, “Phonex AS”, Pipelife “Master 3”, POLOPLAST “Polo Kal NG”, POLOPLAST “Polo Kal 3S”, Rehau “Raupiano Plus”, Wavin “AS” /KeKelit “Phonex AS”, Wavin “SiTech”, Cloes “Blue Power”, Cloes “PhoNoFire”, Valsire “Triplus”, Valsire “Silere”, Marley “Silent”, Geberit “Silent PP”

Excerpt of ETA document. Check the exact field of application for each pipe (type, diameter and pipe wall thickness) and which collar size to use in the ETA 10/0404 document.

Application Pipe material Pipe Ø mm ≥ 100 mm Rigid or flexible wall ≥ 150 mm Rigid wall Rigid floor

Waste water

PVC-U (EN ISO 1452, EN 1329-1, EN 1453-1) and PVC-C (EN 1566-1)

50 - 160 EI 120 U/UEI 120 U/U

180 - 250 - EI 180 U/U

PE (EN 1519, EN 12666-1)

50 - 160 EI 120 U/UEI 120 U/U

200 - 250 - EI 120 U/U

PP (EN 1451-1, DIN EN 12056)*

32 - 110 EI 120 U/U

EI 90 U/U125 - 160 -

200 - 250 - EI 120 C/U

IndustrialPVC-U (EN ISO 15493,

DIN 8061/8062)

50 - 160 EI 120 U/UEI 120 U/U

180 - 250 - EI 180 U/U

PE (EN ISO 15494, DIN 8074/8075)

50 - 160 EI 120 U/U EI 120 U/U

180 - 200 - EI 120 U/UEI 120 U/C

200 - 250 - EI 180 U/U

PP (DIN 8077/8078)

50 EI 90 U/U EI 120 U/U

63 EI 60 U/U

EI 180 U/U75 - 110 EI 120 U/U

110 - 125 -

Potable water

PP (EN ISO 15874, DIN 8077/8078)

50 EI 90 U/U EI 120 U/U

63 EI 60 U/U

EI 180 U/U75 - 110 EI 120 U/U

110 - 125 -

PE (EN 12201-2)50 - 160 EI 120 U/U

EI 120 U/U200 - 250 - EI 120 U/U

Main approved applications

2

Firestop bandage CFS-C P

hilti.co.uk/r4831 | Issue 08/2016

Other approved applications

Wide range of branded plastic pipes through walls and floors approved

View ETA 10/0404 for list of approved pipes (+GF+, Aquaterm, Geberit, KeKelit, Magnaplast, Pipelife, POLOPLAST, Rehau, Wavin)

Pre-insulated pipes through walls and floors PE-HD pipes (+GF+ Cool-Fit) with ABS/PUR insulation

View ETA 10/0404 for list of approved pipe sizes from +GF+ Pipings Systems

Plastic and composite pipes with Armaflex AF insulation through walls and floors

View ETA 10/0404 for list of approved pipes and configurationsPE, PP, branded (Aqutherm, Wavin, Friatec, Rehau, +GF+, Geberit, Ke Kelit,…)

Composite pipe (Geberit Mepla PE-Xb/Al/PE-HD) approved through rigid floors ≥2400 kg/m3)

View ETA 10/0404 for list of approved pipes and configurations

Ø 40, 50, 63 and 75 mm

Approved configurations with 550 kg/m3 rigid floors. Insulated and non-insulated pipes

View ETA 10/0404 for list of approved pipes

Pre-insulated plastic pipes, PVC-U, PE, PP and various branded pipes

2 pipes in one collar configurations through rigid floors

View ETA 10/0404 for list of approved pipes and configurations

PE EN 15494 or DIN 8074/5 2x Ø20 mm

Zero distance between collars S1 = 0

View ETA 10/0404 for details of approved pipes and configurations

Sound decoupling strip (C1) to be used with gypsum or mortar as gap filler (A3) to improve acoustic performances

View ETA 10/0404 for more details

PE foam sound decoupling strips. Maximum allowed thickness ranges from 5 mm to 9 mm depending on the configuration

3

Firestop bandage CFS-C P

hilti.co.uk/r4831 | Issue 08/2016

Consumption guide

General instructions for use

Collar size Pipe nominal outside diameter (mm)

Recommended opening diameter (mm)

Required number of fastening hooks

CFS-C P 50/1.5″ 50 62 2

CFS-C P 63/2″ 63 77 2

CFS-C P 75/2.5″ 75 82 3

CFS-C P 90/3″ 90 112 3

CFS-C P 110/4″ 110 122 4

CFS-C P 160/6″ 125 142 4

CFS-C P 50/1.5″ 160 182 6

CFS-C P 180/7″ 180 210 8

CFS-C P 200/8″ 200 230 8

CFS-C P 225/9″ 227 260 10

CFS-C P 250/10″ 250 280 12

4

Firestop bandage CFS-C P

hilti.co.uk/r4831 | Issue 08/2016

Characteristics of CFS-C P

Characteristics Assessment of characteristics Norm, standard, testHealth and the environmentAir permeability (gas tightness)Water permeability

Air tightness / smoke tightness and water tightness for a single penetration of a plastic pipe firestopped with Hilti Firestop Collar CFS-C P can be achieved when the annular gap is sealed with Hilti Firestop Acrylic Sealant CFS-S ACR (10  mm thickness).q/A [m3/(h x m2)] at Δ p 50 Pa / Δ p 250 PaAir: 1.9 x 10-6 / 9.7 x 10-6Nitrogen: 1.1 x 10-6 / 5.5 x 10-6CO2: 6.4 x 10-5 / 3.2 x 10-4Methane: 4.3 x 10-5 / 2.1 x 10-4

Watertight to 1 m head of water or 9806 Pa.

EN 1026

ETAG 026-2Dangerous substances CFS-C P is in compliance concerning the

registration, evaluation, authorisation and restriction of Chemicals (REACH).The product does not contain any constituents contained in the list of dangerous substances of the European Commission above the acceptable limits.

Material safety data sheet

Protection against noiseAirborne sound insulation

The following airborne sound insulation for a single penetration of plastic pipe firestopped with Hilti Firestop Collar CFS-C can be achieved when the annular gap is sealed with

Hilti Firestop Acrylic Sealant CFS-S ACR:Flexible wall Rw = 53 dB Dn,w = 60 dB Rigid wall Rw = 51 dB Dn,w = 58 dB

Cementitious mortar: Rigid wall Rw = 52 dB Dn,w = 59 dB

EN ISO 140-3EN ISO 20140-10EN ISO 717-1

Durability and serviceability Category Z2 (suitable for penetration seals intended for use in dry indoor conditions excluding temperatures below 0 °C).

ETAG 026-2 and 3

Reaction to fire Class E EN 13501-1

5

Firestop bandage CFS-C P