Fire Standards & Regulations
• Regulatory Reform (Fire Safety) Order
• Local Licensing Requirements
• BS 5839-6: 2013
• Building Regulations Document B
• LACORS – Fire Safety Guidance
Are you confused?
![Page 2: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/2.jpg)
Fire Alarm Systems
There is no risk low enough to negate
the need for some form of system
• Single household up to 4 storey –
Grade D, Category LD3
• Shared House HMO up to 4 storey -
Grade D, LD3 + Kitchen, Lounge, cellar
• Shared House HMO 5 –6 storey -
Grade A, Category LD2 + all risk rooms
![Page 3: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/3.jpg)
Fire Alarm Systems
• Bedsit HMO up to 2 storey – mixed system
Grade D, Category LD2 in common areas
+ heat alarm in bedsits.
Grade D alarm in each bedsit
• Bedsit HMO 3 to 6 storey – mixed system
Grade A, Category LD2 in common areas
+ heat alarm in bedsits.
Grade D alarm in each bedsit
![Page 4: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/4.jpg)
Fire Alarm Systems• 2 storey house converted to flats, not to Building Regs – mixed system Grade D, Category LD2 in common areas + heat alarm in entrance to flat Grade D, Category LD3 in each flat
• 3 - 6 storey house converted to flats, not to Building Regs – mixed system Grade A, Category LD2 in common areas + heat alarm in entrance to flat. Grade D, Category LD3 in each flat
![Page 5: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/5.jpg)
BS 5839-6:2013 – What is it?
• Guidance for selection, siting & installation of fire alarm systems for dwellings
• The ‘Best Practice’ guide
• Building Regulations & other guidance based on this standard
![Page 6: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/6.jpg)
Grades & Category
• Grade of system - the type of system to
be installed...
Battery, Mains only, Mains with back-up etc
• Category of system - the extent of the
system...
The number of alarms installed & where
![Page 7: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/7.jpg)
Grades of system
• Grade A – similar to commercial
type fire alarm systems
Mains
power
supply
Sounder circuit
Detector circuit
Manual Call Point circuit
All circuits at 24VDC in fire
resistant cable
Central control panel
with zoning
![Page 8: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/8.jpg)
Grades of system
• Grade D - mains smoke/heat alarms
with an integral standby supply
Mains power
supply
Standard PVC
cable
Rechargeable cellsRechargeable cells PP3 BatteryPP3 BatteryOROR
![Page 9: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/9.jpg)
Categories of system
• LD3 – a system incorporating
detectors in all circulation spaces
that form part of the escape routes from the dwelling.
• Hallways, Landings
• Open Plan – Lounges, Sitting Room
![Page 10: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/10.jpg)
Hallway Landing
Category LD3
Optical or
Multi-Sensor
![Page 11: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/11.jpg)
Categories of system
• LD2 – a system incorporating
detectors in all circulation spaces
that form part of the escape routes from the dwelling, and in all
specified rooms and areas that
present a high fire risk to occupants.
• Same as LD3 plus high risk rooms e.g
Living Room & Kitchen
![Page 12: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/12.jpg)
Category LD2
Optical or
Multi-Sensor
Heat
Ionisation,
Optical or
Multi-Sensor
Hallway
Kitchen
Living Room
Landing
![Page 13: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/13.jpg)
Mixed System – Grade D
Flat 3
Flat 1 Flat 2
Flat 4Escape Route
Escape Route
Separate
System in each
flat
Heat alarms
connected to
escape route
system
Smoke alarms
in escape route
![Page 14: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/14.jpg)
Mixed System – Grade A & D
Separate Grade D alarm system in each dwelling
Grade A system –smoke detectors +
heat detector in each dwelling
![Page 15: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/15.jpg)
The problem with Hard-wiring
Smoke alarm on landing
Smoke alarm in hallway
Mains Power
Supply
![Page 16: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/16.jpg)
Smoke alarm in hallway
RF interconnect
Smoke alarm on landing
Ground floor light pendant
1st floor light pendant
No cables & trunking
Radio signal interconnects the system
![Page 17: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/17.jpg)
RadioLINK Alarm Controller
• Test, Locate & Silence
from one button
• Fire or CO indicator
to easily identify
source of alarm
• Memory feature
• Engineers Mode for
interrogation
![Page 18: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/18.jpg)
Other Applications
Relay to trigger other devices
• Warden Call Systems
• Strobe light
• Sounder
• Door closer/opener
• Panel system
• Smoke vent
![Page 19: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/19.jpg)
Switched Input Module to activate
alarms from a sprinkler system
![Page 20: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/20.jpg)
Europe’s Leader in Residential Fire + Gas Detection
Ei Electronics, Shannon, Ireland
Aico Ltd is a wholly owned subsidiary of Ei Electronics
Promoting professional fire alarm
system installation in dwellings with
Made in Ireland
The Aico Fire Products Trained
Installer Scheme
![Page 21: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/21.jpg)
All combustion processes generate CO
Natural Gas / LPGNatural Gas / LPG 20 20 –– 200 ppm200 ppm
Oil / LiquidOil / Liquid Up to 1,000ppmUp to 1,000ppm
Solid fuelSolid fuel Up to 20,000 ppmUp to 20,000 ppm
![Page 22: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/22.jpg)
Tragic Incident
• Boiler slow to fire-up resulting in a build up of gas in firebox.
• Boiler eventually ignited, a small explosion caused the flue
to become displaced.
• Exhaust gases escaped into the boiler room
• Fumes leaked into 2 bedrooms above
• 1 man died and there was also a near miss.
• A CO alarm would almost certainly have saved them.
Bedroom 1
1 man died due to
CO poisoning
Bedroom 2
1 woman poisoned
By CO
Boiler flue dislodged
in boiler room
![Page 23: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/23.jpg)
Tragic Incident
• A flue leading from a boiler had been fixed just below the
bathroom window of a seaside hotel bedroom.
• The window had been screwed down but was later
undone – fumes entered the bedroom
• 1 man died from CO poisoning
• Flue and terminal were installed in the wrong place and in
the wrong way.
• Two employees of the installer company were charged
with manslaughter and received fines.
• Statements from family included ...
"We hope everyone who reads this will buy a carbon
monoxide alarm and pass the message on."
![Page 24: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/24.jpg)
A near miss
• Lady was complaining of flu-like symptoms
• CO Alarm was fitted and it did respond.
• Gas engineer could not find a problem – claimed
CO Alarm was faulty
• New digital alarm showed high levels of CO
• Exhaust gases were coming from the flat below
• A Near miss showing the value of fitting CO alarms
![Page 25: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/25.jpg)
Flues in voids – existing installations
• Gas Safe Technical Bulletin 008
Edition 3 issued April 2013
• Inspection hatches must be
fitted, OR
• A void monitoring system should
be installed
• How many will be?
![Page 26: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/26.jpg)
Flues in voids – an alternative
• Install a CO alarm in all habitable
rooms that the flue passes through
![Page 27: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/27.jpg)
Gas Cookers
• Owned by the tenant –rarely serviced?
• Can emit significant amounts of CO – 400ppm
not uncommon!
• Low level CO poisoning can
cause long-term health
problems
• Can this be ignored as
being outside of your responsibility?
![Page 28: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/28.jpg)
Corgi Report 2009
• ‘Just over 72% of installers said they have discovered a CO leak on a customer’s appliance’
• ‘Nearly 50% of CORGI registered installers say they recommend that their customers install an audible CO alarm’
• ‘through increased awareness of CO, it is hoped that public knowledge about the importance of installing an audible CO alarm will increase’.
![Page 29: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/29.jpg)
Gas Safe Register recommends the use of audible carbon
monoxide alarms marked with British Standard EN 50291. It
should also have a British or European approval mark, such as
a Kitemark.
What the Regulatory bodies say
England & Wales Building Regulations requires a CO alarm to
be installed when a new solid fuel appliance is installed or
when an existing one is replaced
Northern Ireland Building Regulations requires the
installation of a CO alarm when any fuel burning
appliance is installed – new and existing installations
Scotland Building Regulations requires the installation of
a CO alarm when any fuel burning appliance is
installed – new and existing installations
![Page 30: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/30.jpg)
Quote from Baxi website
‘For you and your family's safety, it is advisable to fit a carbon
monoxide alarm in each room in your home that has a gas
appliance’.
Response to e-mail enquiry to Worcester Bosch
We don't have a specific company stance on it [installing CO
alarms] - we would always refer customers to Gas Safe
Register's guidelines.
Quote from COCAA section of Vaillant website
Fit an audible Carbon Monoxide alarm. CO alarms need to
meet European safety standards and must be audible.
What the Boiler Manufacturers say
![Page 31: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/31.jpg)
BS EN 50292: 2002
Code of Practice for siting and
installation
BS EN 50291-1: 2010
BS EN 50291-2: 2010
Product Standards for CO Alarms
Standards & Regulations
![Page 32: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/32.jpg)
Choosing a CO alarm
Battery powered alarm• Lower purchase cost
• Easier to install
• Easier to remove
• Battery may have to be
replaced with some products
• Alarm has to be replaced after 7 years
• No interconnect with most products
• No signalling option with most products
![Page 33: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/33.jpg)
Choosing a CO alarm
Mains powered alarm
• No batteries to replace
• Less likely to be removed
• No back-up if mains fails
• Higher purchase price
• Higher installation cost
• Alarm has to be replaced after 5/6 years
• No interconnect option
• No signalling option
![Page 34: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/34.jpg)
Choosing a CO alarm
Mains powered with back-up
• Rechargeable back-up cells
• No batteries to replace
• Less likely to be removed
• Replace sensor after 5/6 years
• Hard wire and RF interconnect option
• Can be interconnected with smoke alarms
• Signalling via a relay option available
• Higher purchase price
• Same installation cost as mains only
![Page 35: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/35.jpg)
Where to site CO alarms• In all rooms where there is an appliance
• 1st Priority – open-flued or flue-less appliances
• 2nd Priority – where people spend most time
• 3rd Priority – where appliance is most used
Open–flued
appliance
![Page 36: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/36.jpg)
Siting CO Alarms
• BS EN 50292 allows wall or ceiling mounting
• BRE GBG 30 recommendations based on trial results...
• Ideally, site on the ceiling at least 300mm from wall or
other obstruction - the easiest siting position
• Site 1 - 3m from the appliance
Ceiling mounted Recommended Siting position
![Page 37: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/37.jpg)
Wall Mounting
• If it must be on the wall:
a). High as possible – 150mm from ceiling
b). Higher than doors or windows
• Between 1 – 3m from source of CO.
• Not easy to meet these restrictions
![Page 38: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/38.jpg)
Siting CO Alarms
• Where the appliance is in a confined
space e.g a boiler room
![Page 39: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/39.jpg)
Interconnecting alarms
• If only one CO alarm is installed audibility
could be a problem
• Interconnection with smoke alarms can
overcome this
Alarms not
interconnectedAlarms
interconnected
![Page 40: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/40.jpg)
Interconnecting CO & Smoke Alarms
Only with a
switch
Hard-wired
RadioLINK
![Page 41: Fire Standards & Regulations Are you confused? · 2013-11-13 · Fire Alarm Systems There is no risk low enough to negate the need for some form of system •Single household up to](https://reader034.fdocuments.in/reader034/viewer/2022050403/5f80e25d789b2777f344eabd/html5/thumbnails/41.jpg)
Thank you