UPRN Full Address Prepared by Karen Daykin On date 21 June 2014 For Responsible Person Bluezone Ltd Woodberry Close Canvey Island, SS8 9PP Telephone 01268 697815 Email Website Site Contact name Telephone Date of Review FIRE RISK ASSESSMENT The Fire Risk Assessment is kept at the Head Office of Bluezone Ltd. A duplicate should be available on each site. It should be available for audits undertaken by the appropriate enforcement authority. Woodberry Manor REGULATORY REFORM (FIRE SAFETY) 2005 Ray Woodberry 01268 697815 Type of Fire Risk Assessment Block Risk Assessment Sleeping Accommodation Full Fire Risk Assessment Medium - Renew FRA at least every three years 21 June 2017

Transcript of Fire Risk Assessment Master ( Flats)

Page 1: Fire Risk Assessment Master ( Flats)

UPRN

Full Address

Prepared by Karen Daykin

On date 21 June 2014

For Responsible

Person Bluezone Ltd

Woodberry CloseCanvey Island, SS8 9PP

Telephone 01268 697815EmailWebsite

Site Contact name      Telephone

Date of Review

FIRE RISK ASSESSMENT

The Fire Risk Assessment is kept at the Head Office of Bluezone Ltd. A duplicate should be available on each site. It should be available for

audits undertaken by the appropriate enforcement authority.

Woodberry Manor

REGULATORY REFORM (FIRE SAFETY) 2005

Ray Woodberry01268 697815

Type of Fire Risk Assessment

Block Risk Assessment

Sleeping AccommodationFull Fire Risk Assessment

Medium - Renew FRA at least every three years

21 June 2017

Page 2: Fire Risk Assessment Master ( Flats)

UPRNFull AddressDate 21 June 2014

Contents

1. Introduction

8. Photographs

The responsible person must take general fire precautions as will ensure so far as is reasonably practicable the safety of any employees and

also in relation to relevant persons who are not in their employ take such general fire precautions as may reasonably be required in the

circumstances of the case to ensure that the premises are safe.

Regulatory Reform (Fire Safety) Order 2005 Article 9 requires that every responsible person must make a suitable and sufficient assessment of

the risks to which relevant persons are exposed for the purpose of identifying the general fire precautions needed to take to comply with the

requirements and prohibitions imposed by or under the order.

The responsible person (or other person who has to any extent control of the property) must ensure that the duties imposed by the relevant

articles of the Regulatory Reform (Fire Safety) Order 2005 are complied with where the matters relate to items within their control.

The prescribed information is the significant findings of the assessment including the measures which have or will be taken by the responsible

person pursuant to the Regulatory Reform (Fire Safety) Order 2005 and any group of persons identified by the assessment as being especially

at risk.

This includes identification of all current significant fire hazards to which relevant persons and others in the area may be exposed.

The Risk Assessment will prioritise the level of risk associated with the property incorporating existing controlling measures to mitigate any risk

The Assessment will also advise upon additional control measures that may me implemented to manage the risk in accordance with Article 10

of the Order.

a. Measures to control sources of ignition

00

1. Introduction2. Scope and Methodology of Assessment3. Identification of Significant Fire Hazards and People at Risk 4. Existing Fire Safety Measures and Occupancy5. Assessment of Fire Risk

b. Measures to control sources of fuelc. Measures to control sources of oxygend. Measures to assist Fire Servicee. Measures to assist Fire Fighters

h. Measures for Signs and Noticesi. Installation, Testing & Maintenancej. Management of Procedures & Information

2. Scope and Methodology of AssessmentStatutory Requirement

6. Fire Risk Rating Matrix7. Fire Risk Assessment Action Schedule

This report has been prepared as the written record of the Fire Risk Assessment carried out to the communal areas of this building on behalf of

the Landlord, Bluezone Ltd, in accordance with the requirements of the Regulatory Reform (Fire Safety) Order 2005.

The objectives of the Fire Risk Assessment are to ensure that a suitable and sufficient assessment of the risks to which relevant persons are

exposed for the purpose of identifying the general fire precautions he needs to take to comply with the requirements and prohibitions of the

Regulatory Reform (Fire Safety) Order 2005.

f. Measures for Fire Detection and Warningg. Measures to assist Means of escape

A Bluezone Ltd Fire Risk Assessment is not a one off document and is part of a strategic Fire Safety Strategy and Policy implemented to identify,

manage and monitor the risks to Bluezone Ltd properties on a regular basis.

The Fire Risk Assessment will be reviewed under Article 9 (3) of the Order and in direct accordance with Bluezone Ltd review policy and

National guidance documentation; this includes but is not restricted to:-

(a)          there is reason to suspect that the Fire Risk Assessment is no longer valid;(b)          there has been a significant change to which it relates including when the premises, special, technical or organisational measures

undergo significant change, extension or conversion.

(c)          Identification of risk following an actual or near miss incident.The report is to provide and assessment of the risk to life from a fire within the building and to make recommendations to ensure compliance

with the Regulatory Reform (Fire Safety) Order 2005; it does not address the risk to the property or business continuity from fire.

Page 3: Fire Risk Assessment Master ( Flats)

Information contained within the report is based on observations at the time of inspection and details provided by on site personnel.

To identify the significant fire hazards within the premises checklists are used which consider the particular fire hazard associated with the

building and the nature of the occupancy.

The hazard will consider the items with regard to existing control measures which are either already inherent within the building or

implemented through the management procedures. The answers are either Yes / No or Not Applicable (N/A).

Each hazard is assessed in accordance with the fire risk rating system. This includes consideration of the hazard in terms of the potential to

harm (severity) and their likelihood (probability) of occurring.

In addition a specific risk rating is applied in consideration of the controlling measures in place and subsequently considers the timescales

within which the measures should be implemented.

The Action plan details the significant findings of both technical and procedural measures that should be considered necessary to address the

risk identified. It is a register of the remedial and advisory actions to be carried out in accordance with the priorities defined using the fire risk

rating system. To reduce the risk to an acceptable level all Action Plan items should be addressed.

The Fire Risk Assessment information is gathered using non invasive physical inspections of the property. Where floor plans are available these

have been used utilised and direct conversation or information has been gathered from on-site staff. Digital photographs have also been taken

and included for means of identification of locations and hazards

The new Regulatory Reform (Fire Safety) Order 2005 requires a fire risk assessment to be carried out and the significant findings recorded. The

process followed was as follows:

The building was inspected, hazards were identified and the fire risk categorised as high, medium or low. The existing measures were recorded

as well as any recommended action. Where actions have been recommended these are in line with British Standards.

Hazards included any sources of ignition (sparks, electrical equipment, heat sources etc), dangerous substances (flammable materials,

combustible materials, gases etc) and unsatisfactory structural features (absence of fire stopping, ducts and voids and compromised protected

routes). Any areas where evacuation of occupants could be compromised were also classed as hazards.

A high fire risk was categorised in areas where there is likely to be a large number of people or old, young or disabled people. Areas with

flammable processes or large quantities of heat or combustible materials were also categorised high risk as well as any areas where structural

features would allow the spread of smoke or fire from one part of the building to another.

A normal fire risk was categorised where a fire is likely to remain localised or to spread slowly enough to allow people to escape to a place of

safety or where there is an effective automatic means of detecting and giving warning of fire.

A low fire risk was categorised where there is minimal risk to life safety and the risk of fire occurring is negligible and the risk of fire, smoke or

fumes spreading is negligible.

Identification of Fire Hazards

Assessment of Fire Risk

The Fire Risk Assessment Action Plan

Information Source

Page 4: Fire Risk Assessment Master ( Flats)

UPRNFull AddressDate 21 June 2014

2

8

1

no

Staircase (element)

yesnoyes

yes

no

Sole Leaseholder or post

1991 converted or purpose

built property

Maximum number of occupants / residents 24

Maximum number of visitors 120

Maximum number of sleeping occupants at any one time 144

Maximum number of vulnerable occupants at any one time 24

Does the tenure include occupants who are:-“Disabled” incl mobility impairment, hearing or vision impairment unknown“Restricted” parents with children unknown“Sensory Impaired” due to alcohol, drugs or medication unknown

Maximum number of unaccompanied children at any one time unknown

Maximum occupation in remote areas at any one time n/a

Accessible by lift / s

Tenure of flats / units

General tenure / occupancy description

4. Identification of People at Risk

Number of Flats within block

Number of direct staircases from corridors

Is there a lobby approach from the staircases to the flats or within the flats?

Fully Enclosed / No Borrowed Light / windowsSemi Enclosed / some Borrowed Light / windowsFully Open / with Borrowed Light / windows

Fully Enclosed / No Borrowed Light / windowsSemi Enclosed / some Borrowed Light / windowsFully Open / with Borrowed Light / windows

Number of Storeys (incl basement)

Date of Construction

Areas not assessed      

Two storey tradditional build premise comprising eight residential flats accessed by two

doors front and rear and

0

3. Existing Fire Safety Measures and Occupancy (Static data)

Brief description of building and its construction

No communal Corridors (flats direct to staircases)

Corridors (from the staircases)

1986

Roof void area

0

Page 5: Fire Risk Assessment Master ( Flats)

UPRNFull AddressDate 21 June 2014

Risk Level

1 (Low)

2

3 (Medium)

4

5 (High)

Probability Level1 (Low)23 (Medium)45 (High)

Degree of Risk Risk Rating ScoreHigh 15 – 25Medium High 08 – 12Medium 02 – 06Low Risk 01

Continuous review 00

A Traffic light approach is made in respect of the degree and level of risk, which is also translated into the priority rating for remedial

work or recommendations. Timescales given include consideration for practicality and financial impact to Bluezone Ltd when

planning their implementation. In order to reduce the risk to an acceptable level it is recommended that all Action Plan items are

implemented

5. Risk Matrix

Building / Area should not be occupied until risk is reduced. Fatality or total loss of property

ExposureImprobable – no known instances of occurrence <10%

Essential that efforts are made to reduce the risk; measures to be implemented within set timescales. Serious damage to

propertyConsiderable resources may have to be allocated to reduce the risk; where a building is occupied urgent action should be

undertaken. Permanent injury; permanent damage to property.

The following risk matrix has been used to prioritise and quantify the individual fire safety deficiencies identified.

Action / Consequence

No Further Action is necessary, detailed records needed. No serious injuries, little or no damage to property.

No major additional controls needed consideration for improvements which have minor cost incurrence. Some injury,

remedial works needed to property

00

Unlikely – but still possible 10 -30% Likely to occur 30 - 50 % Will occur frequently 50 - 90% Will occur very frequently unless prevented >90%

Within three years of notification (programmed work)

Within five years of notification (programmed work)

Timescale for actionWithin 28 days of notification

Within six months of notificationWithin one year of notification

Page 6: Fire Risk Assessment Master ( Flats)

UPRNFull AddressDate 21 June 2014

some

no

yes

Zero – 1 fire

yes

some

7. Identification of significant Fire Hazards

Source & location of Ignition123456789

10

Other notes

Source & location of Fuel123456789

10

Other notes

Source and location of oxygen12345

Other notes

Are Estate Management issues being raised and managed effectively?

Is there automatic smoke or fire detection present to the building ?

Fixed lighting equipment

00

Have flat / unit own doors been upgraded to 30 min fire rated?

Is Emergency Lighting installed throughout?

6. Existing Fire Safety Measures and Occupancy (changeable data)

Is the Means of Escape kept clear at all times?

How Many fires have occurred within the block within the past five

Natural airflow

Page 7: Fire Risk Assessment Master ( Flats)

UPRNFull AddressDate 21 June 2014

Item Measures to control Source of

Ignition

N/A Yes No

Ris

k Le

vel

(1-5

)

Pro

bab

ilit

y Le

vel (

1-

Rat

ing

(RLx

P) Priority Comments Action

Point

Ref.

8.1.1 Are current arrangements for the

control of arson suitable and

sufficient?

r a r 0 1 0 Continuous

review

None

8.1.2 Is Smoking confined to

designated areas and “No

Smoking” signs displayed as

appropriate?

r a r 0 1 0 Continuous

review

None

8.1.3 Are suitable arrangements in

place for the disposal of

“smoking” materials

r r a 2 3 6 Medium

Risk

Evidence that residents dispose

of smoking materials at entrance

area.

8.1.3

8.1.4 Is there an adequate system

adopted for permitting and

monitoring hot works operations

by outside contractors?

a r r 0 0 0 Continuous

review

None

8.1.5 Are arrangements for managing

building work and alterations

suitable and sufficient?

r a r 0 1 0 Continuous

review

None

8.1.6 Are adequate measures in place

to guard against malicious

ignition?

r a r 0 2 0 Continuous

review

None

8.1.7 Are Access control / security

systems In place?

r a r 0 1 0 Continuous

review

door entry system not

operational

None

8. Assessment of Fire Risk

The following table details the approach that has been taken to assess the individual risk level for each identified hazard / fire safety deficiency. All

hazards have been considered with regard to the specific relevant people affected and the control measures necessary to contend with the risk.

00

Page 8: Fire Risk Assessment Master ( Flats)

UPRNFull AddressDate 21 June 2014

Measures to control Source of

Fuel

N/A Yes No

Ris

k Le

vel

(1-5

)

Pro

bab

ilit

y Le

vel (

1-

Rat

ing

(RLx

P) Priority Comments Action

Point

Ref.

8.2.1 Have all areas of flammable wall

and ceiling Linings been removed,

covered, or treated to reduce the

spread of flame across their

r a r 0 1 0 Continuous

review

None

8.2.2 Is the premises free from

accumulation of Rubbish, waste

paper, and other ignitable

materials?

r a r 0 1 0 Continuous

review

None

8.2.3 Are adequate arrangements

made for the Disposal of waste

and rubbish?

r a r 0 1 0 Continuous

review

None

8.2.4 Are suitable arrangements in

place for storing highly

flammable or readily

combustible materials not in

current use?

a r r 0 0 0 Continuous

review

None

8.2.5 Are storage areas for highly

flammable and explosive

materials identified by hazard

warning signs

a r r 0 0 0 Continuous

review

None

8.2.6 Are the housekeeping

arrangements for communal

areas sufficiently controlled?

r a r 0 1 0 Continuous

review

None

8.2.7 Are the arrangements for use of

equipment and machinery

suitable and sufficient?

a r r 0 0 0 Continuous

review

None

8.2.8 Is the existing building layout and

construction appropriate, suitable

and sufficient?

r a r 0 1 0 Continuous

review

None

8.2.9 Are areas of high fire risk and

loading provided with physical

separation from the remainder of

the premises?

r a r 0 2 0 Continuous

review

None

8.2.10 Is the provision of means for

restricting spread of fire and

smoke in common areas suitable

and sufficient?

r a r 0 1 0 Continuous

review

None

8.2.11 Is the provision of means for

restricting fire and smoke within

access duct /chutes etc. suitable

and sufficient?

a r r 0 0 0 Continuous

review

None

8.2.12 Is the provision of means for

restricting fire and smoke from

entering into individual flats /

units / areas / linked or attached

properties suitable and

sufficient?

r a r 0 1 0 Continuous

review

None

Measures to control Source of

Oxygen

N/A Yes No

Ris

k Le

vel

(1-5

)

Pro

bab

ilit

y Le

vel (

1-

Rat

ing

(RLx

P) Priority Comments Action

Point

Ref.

8.3.1 Are the communal opening

windows operational?

r a r 0 1 0 Continuous

review

None

8.3.2 Are there smoke vents present –

if they are not present are they

required / recommended ?

a r r 0 0 0 Continuous

review

None

8.3.3 Are air conditioning units present

– if they are not present are they

required / recommended ?

a r r 0 0 0 Continuous

review

None

00

Page 9: Fire Risk Assessment Master ( Flats)

UPRN

Full AddressDate 21 June 2014

Measures to assist fire service N/A Yes No

Ris

k Le

vel

(1-5

)

Pro

bab

ilit

y Le

vel (

1-

Rat

ing

(RLx

P) Priority Comments Action

Point

Ref.

8.4.1 Are there suitable access facilities

for Fire Service vehicles to access

the entire building?

r a r 0 1 0 Continuous

review

None

8.4.2 Are Fire Hydrants in suitable

proximity of building and clearly

visible?

r r a 4 4 16 High Risk No visual evidence of hydrants 8.4.2

8.4.3 Does the Emergency Action Plan

relate to the Fire & Rescue

Service response?

a r r 0 0 0 Continuous

review

None

8.4.4 Are the fire fighting lifts clearly

identified and appropriate

signage fitted?

a r r 0 0 0 Continuous

review

None

8.4.5 Are there Dry / Wet Risers

present – if they are not present

are they required /

recommended ?

a r r 0 0 0 Continuous

review

None

8.4.6 Are the fire fighting lifts clearly

identified and appropriate

signage fitted?

a r r 0 0 0 Continuous

review

None

8.4.7 Are there sprinklers / suppression

systems present – if they are not

present are they required /

recommended ?

a r r 0 0 0 Continuous

review

None

8.4.8 Are there hose reels present – if

they are not present are they

required / recommended ?

a r r 0 0 0 Continuous

review

None

8.4.9 Are fire blankets present – if they

are not present are they required

/ recommended ?

a r r 0 0 0 Continuous

review

None

8.4.10 Are there portable fire

extinguishers present – if they are

not present are they required /

recommended ?

a r r 0 0 0 Continuous

review

None

8.4.11 Are the portable fire

extinguishers clearly visible and

accessible with correct signage?

a r r 0 0 0 Continuous

review

None

8.4.14 Are the Portable Fire

Extinguishers suitable & sufficient

for purpose?

a r r 0 0 0 Continuous

review

None

8.4.15 Are the Portable Fire

Extinguishers clearly visible and

accessible?

a r r 0 0 0 Continuous

review

None

r

0

Page 10: Fire Risk Assessment Master ( Flats)

UPRNFull AddressDate 21 June 2014

Measures for fire detection and

warning

N/A Yes No

Ris

k Le

vel

(1-5

)

Pro

bab

ilit

y Le

vel (

1-

Rat

ing

(RLx

P) Priority Comments Action

Point

Ref.

8.4.12 Is an automatic fire warning

system present – or if it is not

present is it required or

recommended?

a r r 0 0 0 Continuous

review

None

8.4.13 Is the property classified as a

HMO (House of Multiple

Occupancy) within guidelines of

Lacors and Housing Act

a r r 0 0 0 Continuous

review

None

8.5.1 Does the fire warning system

have a named responsible

person, who has authority and

training to manage the system?

a r r 0 0 0 Continuous

review

None

8.5.2 Is the Automatic Fire Detection /

warning system suitable and

sufficient for the premises?

a r r 0 0 0 Continuous

review

None

8.5.3 Are manual call points suitable

and sufficiently located and

accessible?

a r r 0 0 0 Continuous

review

None

8.5.3 Are sounders/klaxons suitable

and sufficiently located?

a r r 0 0 0 Continuous

review

None

8.5.4 Does the Fire Warning system

have a guaranteed power supply?

a r r 0 0 0 Continuous

review

None

Measures for signs and notices N/A Yes No

Ris

k Le

vel

(1-5

)

Pro

bab

ilit

y Le

vel (

1-

Rat

ing

(RLx

P) Priority Comments Action

Point

Ref.

8.6.1 Are all Fire doors fitted with self

closing devices suitably and

correctly signed

a r r 0 0 0 Continuous

review

None

8.6.2 Are all Fire Doors to stores, and

cupboards suitably and correctly

signed

r a r 0 1 0 Continuous

review

None

8.6.3 Are all final exit doors suitably

and correctly signed

r a r 0 1 0 Continuous

review

None

8.6.4 Are all emergency exits suitably

and correctly signed

r a r 0 1 0 Continuous

review

None

8.6.5 Are all emergency escape routes

suitably and correctly signed?

r a r 0 1 0 Continuous

review

single means of escape from

building

None

8.6.6 Are Lifts ( in case of emergency)

suitably and correctly signed?

a r r 0 0 0 Continuous

review

None

8.6.7 Are Fire Action Notices clearly

displayed?

a r r 0 0 0 Continuous

review

None

8.6.8 Are electrical warnings clearly

displayed

a r r 0 0 0 Continuous

review

None

00

Page 11: Fire Risk Assessment Master ( Flats)

UPRNFull AddressDate 21 June 2014

Measures to assist means of

escape

N/A Yes No

Ris

k Le

vel

(1-5

)

Pro

bab

ilit

y Le

vel (

1-

Rat

ing

(RLx

P) Priority Comments Action

Point

Ref.

8.7.1 Are there a sufficient number of

exits from the building, and are

they of adequate size for the

number of occupants?

r a r 0 1 0 Continuous

review

None

8.7.2 Can all emergency / final exit

doors be opened easily in single

action?

r a r 0 1 0 Continuous

review

None

8.7.3 Do means of escape lead directly

to a place of safety?

r a r 0 1 0 Continuous

review

None

8.7.4 Is the Escape route free from

obstructions, slip or trip hazards?

r a r 0 1 0 Continuous

review

None

8.7.5 Are the travel distances suitable

and sufficient ?

r a r 0 1 0 Continuous

review

None

8.7.6 Are the escape routes suitable

and sufficient for occupants with

impaired mobility ?

r r a 3 4 12 Medium

High Risk

No details provided about

private residents with disabilities

8.7.6

8.7.7 Are the escape routes widths and

capacities suitable and sufficient

?

r a r 0 1 0 Continuous

review

None

8.7.8 Are there alternative exits from

inner rooms or basements?

a r r 0 0 0 Continuous

review

None

8.7.9 Are the exits from external

stairways suitable and sufficient?

a r r 0 0 0 Continuous

review

None

8.7.10 Is the means of escape clear of

the need to use ladders, hatches

or windows?

r a r 0 1 0 Continuous

review

None

8.7.11 Is the Means of Escape suitable

and sufficient to provide 30

minutes fire resistance?

r a r 0 1 0 Continuous

review

None

8.7.12 Is the use of cavity barriers / fire

stopping and dampers evident

within ducts / suspended ceilings

/ floors?

a r r 0 0 0 Continuous

review

None

8.7.13 Is a suitable and sufficient place

of safety (refuge) provided?

a r r 0 0 0 Continuous

review

None

8.7.14 Are defined zones on external

emergency areas of fire resisting

nature, including doors, windows,

and walls?

a r r 0 0 0 Continuous

review

None

8.7.15 Where roof exits are designated

as means of escape is suitable

and sufficient access through the

door available?

a r r 0 0 0 Continuous

review

None

8.7.16 Where roof exits are designated

as means of escape is suitable

and sufficient lighting /

illumination available?

a r r 0 0 0 Continuous

review

None

8.7.17 Where roof exits are designated

as means of escape is the surface

non slip / guarded with a

protective barrier?

a r r 0 0 0 Continuous

review

None

8.7.18 Are all emergency escape routes

suitably illuminated with

emergency lighting?

r r a 3 4 12 Medium

High Risk

borrowed lighting available 8.7.18

8.7.19 Does the Emergency Lighting

system have a back up power

source?

a r r 0 0 0 Continuous

review

None

8.7.20 Do all final exit doors open in the

direction of escape?

r r a 3 4 12 Medium

High Risk

limited occupation less than 60

persons

8.7.20

00

Page 12: Fire Risk Assessment Master ( Flats)

UPRN

Full AddressDate 21 June 2014

Measures of maintenance for

fire safety facilities. Do you

regularly inspect, test, report

and record in a log book the

following?

N/A Yes No

Ris

k Le

vel (

1-5

)

Pro

bab

ility

Leve

l (1-

5)

Rat

ing

(RLx

P) Priority Comments Action

Point

Ref.

8.8.1 All Flat Entrance doors a r r 0 0 0 Continuous

review

None

8.8.2 All Communal doors r a r 0 1 0 Continuous

review

Doors in poor condition and do

not lock securely

None

8.8.3 All Roof Access doors a r r 0 0 0 Continuous

review

None

8.8.4 All intake Cupboard doors r a r 0 1 0 Continuous

review

None

8.8.5 All Store Cupboard doors a r r 0 0 0 Continuous

review

None

8.8.6 Escape Routes r a r 0 1 0 Continuous

review

None

8.8.7 Housekeeping r a r 0 1 0 Continuous

review

None

8.8.8 Compartmentation a r r 0 0 0 Continuous

review

None

8.8.9 Fire Integrity common areas r a r 0 1 0 Continuous

review

None

8.8.10 Emergency Lighting a r r 0 0 0 Continuous

review

None

8.8.11 Fire fighting equipment a r r 0 0 0 Continuous

review

None

8.8.12 Portable Appliances a r r 0 0 0 Continuous

review

None

8.8.13 Electrical installations r r a 3 2 6 Medium

Risk

no evidence of recent Periodic

inspection to electrical system

8.8.13

8.8.14 Fire Alarm / Detection / warning

system

r a r 0 1 0 Continuous

review

None

8.8.15 Fire Extinguishers a r r 0 0 0 Continuous

review

None

8.8.16 Smoke Vents a r r 0 0 0 Continuous

review

None

8.8.17 Sprinklers / Suppression system a r r 0 0 0 Continuous

review

None

8.8.18 Signs & Notices r a r 0 1 0 Continuous

review

None

8.8.19 Dry / Wet Riser a r r 0 0 0 Continuous

review

None

8.8.20 Lightning Conductors a r r 0 0 0 Continuous

review

None

8.8.21 Access levels r a r 0 1 0 Continuous

review

None

8.8.22 Gas Appliances / systems a r r 0 0 0 Continuous

review

None

8.8.23 Air conditioning units a r r 0 0 0 Continuous

review

None

8.8.24 Hose Reels a r r 0 0 0 Continuous

review

None

8.8.25 Fire Blankets a r r 0 0 0 Continuous

review

None

8.8.26 Presence of a log book a r r 0 0 0 Continuous

review

None

0

0

Page 13: Fire Risk Assessment Master ( Flats)

UPRN

Full AddressDate 21 June 2014

Item Measures for management of

information and procedure

N/A Yes No

Ris

k Le

vel

(1-5

)

Pro

bab

ilit

y Le

vel (

1-

Rat

ing

(RLx

P) Priority Comments Action

Point

Ref.

8.9.1 Is a suitable emergency action

plan in place for the purpose of

safeguarding residents, occupants

and other persons present in the

event of a fire?

r r a 5 4 20 High Risk No emergency plans on site or

issued to occupants

8.9.1

8.9.2 Is the plan premise specific and

up to date?

a r r 0 0 0 Continuous

review

None

8.9.3 Is there a fully trained and

equipped warden nominated to

implement the emergency action

plan?

a r r 0 0 0 Continuous

review

None

8.9.4 Are emergency contacts with

external services arranged as

necessary with regards to rescue

work and fire fighting?

r r a 3 4 12 Medium

High Risk

contact is local fire brigade

service

8.9.4

8.9.5 Where two or more organisations

share/manage the premise do

they cooperate as far as

necessary to comply with the

RR(FS)O .

a r r 0 0 0 Continuous

review

None

8.9.6 Have appropriate procedures

been established to evacuate or

restrict access to confined spaces

or hazardous locations?

a r r 0 0 0 Continuous

review

None

8.9.7 Are others who may have caused

to visit or work within the

property provided with

comprehensive information on

the measures taken in

compliance with the RR(FS)O?

r a r 0 1 0 Continuous

review

None

8.9.8 Are occupants on the premise

provided with comprehensive

and relevant information on the

emergency action plan?

r r a 3 4 12 Medium

High Risk

No emergency plans on site or

issued to occupants

8.9.8

8.9.9 Do the occupants know the

identity of those persons

nominated to implement the

emergency action plan?

r r a 3 4 12 Medium

High Risk

No emergency plans on site or

issued to occupants

8.9.9

8.9.10 Is a record of fire or near misses

kept with full details of the

occurrence?

r a r 0 1 0 Continuous

review

None

8.9.11 Are others who may have caused

to visit or work within the

property provided with regular

fire safety training and details of

the training recorded?

r a r 0 1 0 Continuous

review

None

8.9.12 Are regular fire evacuation drills

undertaken and details of these

recorded?

r r a 3 4 12 Medium

High Risk

8.9.12

0

0

Page 14: Fire Risk Assessment Master ( Flats)

UPRNFull AddressDate 21 June 2014

Responsible Team Action to be taken Date

Completed

8.1.3

Are suitable arrangements in

place for the disposal of

“smoking” materials

Evidence that residents

dispose of smoking

materials at entrance

area.

Medium

Risk

1 year Landlord / managing

agent

consider installing

smokers bin

adjacent to the door

8.4.2

Are Fire Hydrants in suitable

proximity of building and

clearly visible?

No visual evidence of

hydrants

High Risk 28 days Landlord / managing

agent

identify and clearly

label the location of

local hydrants to the

site

8.7.6

Are the escape routes

suitable and sufficient for

occupants with impaired

mobility ?

No details provided

about private residents

with disabilities

Medium

High Risk

6 months Landlord / managing

agent

consider reviewing

occupancy types

and include within

emergency action

plan for the building

where necessary

8.7.18Are all emergency escape

routes suitably illuminated

with emergency lighting?

borrowed lighting

available

Medium

High Risk

6 months Landlord / managing

agent

consider installing

emergency lighting

to the building

8.7.20Do all final exit doors open

in the direction of escape?

limited occupation less

than 60 persons

Medium

High Risk

6 months Landlord / managing

agent

nor requried due to

the building

capacity

8.8.13

Electrical installations no evidence of recent

Periodic inspection to

electrical system

Medium

Risk

1 year Landlord / managing

agent

Arrange for a five

yearly inspection of

system to be carried

out

00

Photo

Ref. No.

Action PointAssessment

Guidance

Ref.

Description of Significant

Finding / Item Priority

Target

TimeComment

Significant Findings

Page 15: Fire Risk Assessment Master ( Flats)

Responsible Team Action to be taken Date

Completed

Photo

Ref. No.

Action PointAssessment

Guidance

Ref.

Description of Significant

Finding / Item Priority

Target

TimeComment

Significant Findings

8.9.1

Is a suitable emergency

action plan in place for the

purpose of safeguarding

residents, occupants and

other persons present in the

event of a fire?

No emergency plans on

site or issued to

occupants

High Risk 28 days Landlord / managing

agent

create and distibute

emergency plan for

premise

8.9.4

Are emergency contacts with

external services arranged

as necessary with regards to

rescue work and fire

fighting?

contact is local fire

brigade service

Medium

High Risk

6 months Landlord / managing

agent

no action needed

8.9.8

Are occupants on the

premise provided with

comprehensive and relevant

information on the

emergency action plan?

No emergency plans on

site or issued to

occupants

Medium

High Risk

6 months Landlord / managing

agent

create and distibute

emergency plan for

premise

8.9.9

Do the occupants know the

identity of those persons

nominated to implement the

emergency action plan?

No emergency plans on

site or issued to

occupants

Medium

High Risk

6 months Landlord / managing

agent

create and distibute

emergency plan for

premise

8.9.12

Are regular fire evacuation

drills undertaken and details

of these recorded?

0 Medium

High Risk

6 months Landlord / managing

agent

create and distibute

emergency plan for

premise

Page 16: Fire Risk Assessment Master ( Flats)

Block Fire Risk Assessment Sheet

The below scoring system will determine the overall fire risk profile and frequencyof Fire Risk Assessment review.

Description High Risk Medium Risk Low Risk

1.0 Number of Staircases within the buildingOne Two Three +

1 0 0

2.0Is there a lobby approach to the flat front

doors? No Yes1 0

3.0Have ALL doors to the block been

upgraded? No Some Yes0 1 0

4.0Is Emergency Lighting installed

throughout? No Some Yes1 0 0

5.0Is the Means of Escape kept clear at all

times? No Sometimes Yes0 0 0

6.0How Many fires have occurred within the

block within the past five years? More than 6 2 – 5 fires Zero – 1 fire0 0 1

7.0Are Estate Management issues raised and

managed effectively No Sometimes Yes0 0 1

8.0What is the general layout or nature of the

building and referring to tenancy SAS / Community

centre / caretaker area

General Needs / HMO

designed building

General Needs /

Leaseholder or

converted property0 0 1

9.0How Many Floors are in the block

including basement Over 7 Between 4 - 6 One - three0 0 1

10.0Is there automatic smoke or fire detection

present to the building None at all in building

Some in communal

areas

Full Fire detection

system0 1 0

Scoringpoints added from each column 3 2 4Multiplication factor 3 2 1Sub score 9 4 4

Total score of all columns 17

Findings guide Fire Risk Assessment renewal as follows:

* between 1 and 10 is classified as a low risk building and will have a full fire risk assessment undertaken every five years.

All buildings will have their fire risk assessment reviewed prior and post completion of any major works within the block.

This building has been identified with a block level risk assessment as a building of :

Medium - Renew FRA at least every three years

0021 June 2014

* between 20 and 30 is a high risk building and will have a full fire risk assessment undertaken each year.

* between 10 and 20 is classified as a medium risk building and will have a full fire risk assessment undertaken every three

years.