Fire Pump System

12
Fire pump system  .1 Pump 2. Motor 3. Controller 4. Suction connections 5. Discharge connections 6. Test line

Transcript of Fire Pump System

Page 1: Fire Pump System

8/10/2019 Fire Pump System

http://slidepdf.com/reader/full/fire-pump-system 1/12

Fire pump system

 

.1Pump2. Motor

3. Controller

4. Suction connections5. Discharge connections

6. Test line

Page 2: Fire Pump System

8/10/2019 Fire Pump System

http://slidepdf.com/reader/full/fire-pump-system 2/12

PUMP TYPES

1-HORIZONTAL (AXIAL )

SPLIT CASE PUMP2- VERTICAL (RADIAL )

PUMPS

3-END SUCTION PUMP4-TURBINE PUMPS

We use centrifugal pumps

Page 3: Fire Pump System

8/10/2019 Fire Pump System

http://slidepdf.com/reader/full/fire-pump-system 3/12

HORIZONTAL SPLIT CASE

PUMP

* Single stage pump

* Multi stage pump

Advantages

•High flow rate

•Can used with electrical and diesel

motors

Disadvantages

•Hard maintenance

•High cost

•Takes a Big size

Page 4: Fire Pump System

8/10/2019 Fire Pump System

http://slidepdf.com/reader/full/fire-pump-system 4/12

VERTICAL PUMP

Vertical in-line is the most famous

 

Advantages

Effective

Good price

Disadvantages•Flow rate more than 1500 GPM

•Works on an electrical motor only

• Need a filter

Page 5: Fire Pump System

8/10/2019 Fire Pump System

http://slidepdf.com/reader/full/fire-pump-system 5/12

END SUCTION PUMP

Types

Flexible coupling pump•Long coupling pump

 

Advantages

•Works with electrical and diesel motors

•Easy installation

Disadvantages

Flow rare more than 150 GPM

 

Page 6: Fire Pump System

8/10/2019 Fire Pump System

http://slidepdf.com/reader/full/fire-pump-system 6/12

TURBINE PUMP

Advantages

•Works with electrical and diesel motors

•High flow rate

 

Disadvantages

•Hard installation and maintenance

•High price

Page 7: Fire Pump System

8/10/2019 Fire Pump System

http://slidepdf.com/reader/full/fire-pump-system 7/12

SYSTEM PUMP

We install on the main line 3 pumps

1-Electrical pump

Usually it is horizontal split case or end suction2-Electrical pump

Works when the power went off 

or when the main load more than electrical pump load

3- jockey pump

 it works to make up the friction losses

The flow 10 % from the total flow

Page 8: Fire Pump System

8/10/2019 Fire Pump System

http://slidepdf.com/reader/full/fire-pump-system 8/12

PUMP SELECTION

Requirements

1-it give the required flow rate and pressure .

2- it is preferred to be at the middle of the curve .

3-it give 150% of the flow rate at pressure higher than 65% of the real

 pressure.

4-the shut down pressure not more than 140% of the real pressure .

5-passed the UL&FM tests .6-NPSH not more than 20 Psi.

7- flow rate range from 25 to 5000 GPM.

 

Page 9: Fire Pump System

8/10/2019 Fire Pump System

http://slidepdf.com/reader/full/fire-pump-system 9/12

 

We can use Pump Affinity Laws to change the speed

*We use pumps with 2900 rpm

 

Page 10: Fire Pump System

8/10/2019 Fire Pump System

http://slidepdf.com/reader/full/fire-pump-system 10/12

INSTALLATION AND CONNECTING

PUMPS* INSTALL THE PUMPS CLOSE TO THE RISER TO

AVOID CAVITATIONS

*BEFORE THE PUMP WE INSTALL

  1-CHECK VALVE

2-GATE VALVE

  3-FLXIBLE CONNECTION

4-STRAINER 

  5-FLOW METER 

*WE PUT THE PUMP ON INSULATOR FROM RUBBER  

* TUBES LESS THAN 2’’ THREADED

MORE THAN THAN IS WELDED

Page 11: Fire Pump System

8/10/2019 Fire Pump System

http://slidepdf.com/reader/full/fire-pump-system 11/12

REQUIRED PUMP

PRESSUREPt= Pi + Pf + Ps

Pt: total pressure

Pi: system operating pressure

Pf: pressure friction losses

Ps: pressure losses due to elevation

According to NPFA

Not operating pressure doesn’t excess 120% therequired pressure and 140% for the end suctionpump

Page 12: Fire Pump System

8/10/2019 Fire Pump System

http://slidepdf.com/reader/full/fire-pump-system 12/12

PUMP SUMMARY