FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC) Marking at 400 mm centres diamond or staggered pitch pattern Grinding at 400 mm centres diamond or staggered pitch pattern to remove existing paint at weld location of helical pins

Transcript of Fire Proofing On Steel Structure

Page 1: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

Marking at 400 mm centres diamond or staggered pitch pattern

Grinding at 400 mm centres diamond or staggered pitch pattern to remove existing paint at weld location of helical pins

Page 2: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

Helical pin held in the welding machine for welding on steel column.

Helical pin ready for welding on steel column.

Page 3: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

Helical pins welded on steel column

90 degree rotation test of welded helical pin on steel column. Ready for rotating clockwise downwards by 90 degree

Page 4: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

90 degree rotation test for helical pins welded on steel column

Rotated clockwise 90 degree downwards Rotated anticlockwise 90 degree reverse backward back to original position

Page 5: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

Applying primer PSK 101 coat of required WFT (100 to 150 microns) by brush on grinded area. Allowing primer PSK 101 coat for curing & drying for required time interval depending on temperature.

Page 6: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

Primer PSK 101 coat is ready to use item. Primer PSK 101 coat ready for application by roller.

Page 7: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

Application of primer PSK 101 coat by roller

Page 8: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

Primer PSK101 coat applied on the steel column of required WFT 100 to 150 micron

Page 9: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

Galvanised mesh & wood shuttering with wood blocks fixed on the steel column. Mesh to be positioned at 1/3rd distance from the surface of steel column.

Overlap of 50 mm to be ensured at mesh joints.

Page 10: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

• Following are the further logical sequential steps:1. Preparation of Fendolite MII & water mixture in

required proportions. Refer presentation Density Test (Spray Head)

2. Slump cone test. Refer presentation Slump Cone Test

3. Wet Density Test (Mixer).Refer presentation Wet Density Test (Mixer)

4. Density Test Spray HeadRefer presentation Density Test (Spray Head)

Page 11: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

After successful slump cone test, mixer & spray head density test, Fendolite MII & water mixture is sprayed on the steel column

Page 12: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

Spray application of Fendolite MII Finishing by trowel

Page 13: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

34 mm thickness check of applied Fendolite MII

Page 14: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

After trowel finish with wood shuttering in place Wood shuttering removed. Visible damage areas to be repaired

Page 15: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

Visible damaged areas repaired

Page 16: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

Ready for wrapping by polyethylene to retain moisture

Page 17: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

Wrapping by polyethylene to retain moisture in Fendolite MII & water mixture.Wrapping to be maintained for 3 days.

Page 18: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

Polyethylene removed. Sample left for 2 days of air drying

Page 19: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

Cafco Topcoat 200 ready to useRequired quantity being poured from container into bucket

Cafco Topcoat 200 required quantity poured into bucket.

Page 20: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

Roller being cleaned by cloth after dipping in water.

Page 21: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

Application 1st coat of Cafco Topcoat 200

Page 22: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

WFT check 150 to 200 microns of 1st coat of Cafco Topcoat 200 After complete application 1st coat of Cafco Topcoat 200

Page 23: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

Sealant ready for application at the junction of steel Sealant is filled at the junction of Steel & Cafco Fendolite MII

Page 24: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

After application of sealant at junction of steel, finger is dipped in water for sealant finishing

Finishing touch by water wet finger

Page 25: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

After sealant is filled all around the junction of Steel & Cafco Fendolite MII

Page 26: Fire Proofing On Steel Structure

FIRE PROOFING MOCK UP ON STEEL COLUMN (Y3DC)

After application of 2nd coat of Cafco Topcoat WFT 150 to 200 microns

FINAL FIREPROOFING PRODUCT