UL 9540A large-scale fire test results
Fire Detection and Suppression
© NEC Energy Solutions 20182
On-board Fire Protection System Overview
Fire suppression agent container
Strobe and horn (internal)
Battery Racks
Fire strobe location (external)
Fire suppression system control
panel
Fire strobe location
(external)Fire suppression agent container
Smoke detector
Smoke detector
Fire strobe location (external)
The GBS® is the DC energy storage component of the NEC Energy Solutions GSS®. Each GBS® is equipped with dedicated fire detection and suppression system.
• The system uses optical smoke sensors to detect presence of a fire.• The system has a centrally located internal strobe light/horn to provide indication of smoke and fire detection for personnel inside
the container, and external strobe light(s) to notify personnel outside the container.• The system uses a gaseous, clean firefighting agent to suppress fire supplemented by internal water spray system for first responders to operate• The system also has optional security cameras to provide remote video of conditions inside the container.
Water spray nozzles (not shown)
© NEC Energy Solutions 20183
Automatic release of fire suppression agent A single detection of smoke or fire in the GBS will cause Signal sent to fire suppression system
Strobe light operation, horn sound at 60BPM
High voltage contactors will open (switch to “Off” mode)
A second detection will cause Same as previous, but horn now sounds at 120BPM, plus
Time delay countdown (20 sec) begins and is displayed on the control panel
Upon expiration of time delay, horn sounds steadily, and the fire suppression agent will be discharged, flooding the GBS container
Manual release of fire suppression agent Horn and strobe operate continuously
Time delay countdown (only 10 sec for manual release) begins and is displayed
Upon expiration of time delay system will respond in the same manner as above
Abort switch can be operated at any time Manual release switch can be operated at any time and will override the Abort
Optional autodial notification to local fire and other authorities is available.
As first responders arrive, water spray system supplied with water to fully extinguish fire
How it Works
© NEC Energy Solutions 20184
Fire Suppression Agent
Novec 1230 clean agent Fluoroketone; non-ozone depleting; breaks down rapidly in the atmosphere
Colorless, odorless, non-toxic, electrically non-conductive vapor
Stored as a liquid
When discharged, the fluid quickly evaporates into a gaseous state.
Agent suppresses fire by removing heat from the fire
Agent suppresses flame rapidly, helps prevent re-ignition, leaves no residue and requires no cleanup after discharge.
Novec 1230 is a widely accepted clean fire suppression agent due to its benign, non-ozone depleting characteristics.
Typical fire suppression clean agent container
© NEC Energy Solutions 20185
cup
Cup Burner Method used to determine level of fire suppression agent required In accordance with NFPA 2001 Standard on Clean Agent Fire Extinguishing
Systems (2012 edition), Appendix B
Pure battery electrolyte used as fuel Most flammable component of battery; permanently sealed inside the cells
Heated to the point of combustion and fire
Agent is introduced at various concentrations Test determined concentration of agent in air required to
extinguish flame
This concentration is used in the design of the fire suppression system to determine how much clean agent is required
Fire Suppression Agent Determination Test
Cup Burner Method; test apparatus set up
© NEC Energy Solutions 20186
UL9540A Installation Level Large-Scale Fire Test
BEFORE AFTER
© NEC Energy Solutions 20187
GBS® battery container is designed with a dedicated fire detection and suppression system in case all other safety measures fail Uses multiple smoke detectors to identify presence of a fire
Indicates visual/audible smoke and fire detection both internal and external to GBS container
Fans and high voltage contactors automatically respond to fire detection to reduce hazard level
Clean agent + water effectively prevents propagation and extinguishes flames
Clean agent can be used to suppress incipient fires inside container, and followed up with water spray system, full extinguishing with no re-ignition was seen in third-party laboratory testing Clean agent concentrations are determined specifically to combat fires involving lithium-ion battery cells
Successfully tested at UL fire test laboratory in accordance with UL 9540A
Summary