Fire Alarm System

19
UCSB Fire Protection Division 16720-1 Fire Alarm System SECTION 16720 FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Provide a 24 VDC automatic addressable fire detection and alarm system per State of California standards and tie to the Campus Proprietary Alarm Panel via connection point indicated on the Drawings and as directed by the University’s Representative along with Life Safety Services (LSS). B. Equipment and materials furnished and installed in other Sections of the Specifications: 1. Fire sprinkler flow and tamper switches. 2. Elevators status annunciators. 3. Smoke/fire damper. 4. HVAC system. C. System Description and Function 1. The system shall consist of fire alarm control panel, annunciator panel(s), interface with University Police Dispatch, thermal detection, smoke detection manual pull stations, auxiliary equipment, audio and visual alarms, and accessories including wire and conduit. The entire system shall be equipped with an emergency battery back-up system. 2. The system shall be installed to be capable of being expanded at any time up to 25% of initial capacity. 3. The system shall be capable of operating both addressable and non-addressable ionization and photoelectric detecting devices, manual stations and waterflow switches. 4. The control panel shall provide power, annunciation, supervision and control for the fire detection and alarm system. The control panel shall be modular in construction, and contain all equipment necessary to operate according to the schedule in the following paragraphs of this Specification and the Drawings. The system shall be designed so that alarm indications override trouble conditions. The panel shall be capable of measuring the sensitivity of the addressable ionization and photoelectric detectors connected to it. The control panel shall allow 25% of growth as part of the system. 5. The system wiring shall be a Class "A" four wire system. Loss of any conductor shall not prohibit alarm initiation from any initiating device or alarm indication from any alarm device. Return wiring shall be in a separate conduit with a

description

Fire Alarm System

Transcript of Fire Alarm System

UCSB Fire Protection Division

16720-1 Fire Alarm System

SECTION 16720

FIRE ALARM SYSTEM

PART 1 - GENERAL

1.1 DESCRIPTION OF WORK

A. Provide a 24 VDC automatic addressable fire detection and alarm system per State of California standards and tie to the Campus Proprietary Alarm Panel via connection point indicated on the Drawings and as directed by the University’s Representative along with Life Safety Services (LSS).

B. Equipment and materials furnished and installed in other Sections of the Specifications:

1. Fire sprinkler flow and tamper switches.

2. Elevators status annunciators.

3. Smoke/fire damper.

4. HVAC system.

C. System Description and Function

1. The system shall consist of fire alarm control panel, annunciator panel(s), interface with University Police Dispatch, thermal detection, smoke detection manual pull stations, auxiliary equipment, audio and visual alarms, and accessories including wire and conduit. The entire system shall be equipped with an emergency battery back-up system.

2. The system shall be installed to be capable of being expanded at any time up to 25% of initial capacity.

3. The system shall be capable of operating both addressable and non-addressable ionization and photoelectric detecting devices, manual stations and waterflow switches.

4. The control panel shall provide power, annunciation, supervision and control for the fire detection and alarm system. The control panel shall be modular in construction, and contain all equipment necessary to operate according to the schedule in the following paragraphs of this Specification and the Drawings. The system shall be designed so that alarm indications override trouble conditions. The panel shall be capable of measuring the sensitivity of the addressable ionization and photoelectric detectors connected to it. The control panel shall allow 25% of growth as part of the system.

5. The system wiring shall be a Class "A" four wire system. Loss of any conductor shall not prohibit alarm initiation from any initiating device or alarm indication from any alarm device. Return wiring shall be in a separate conduit with a

UCSB Fire Protection Division

16720-2 Fire Alarm System

minimum of 6' separation between supply and return conduits. Class “B” wiring may be used if approved by the Designated Campus Fire Marshal (DCFM).

6. Alarm Sequence: The system alarm operation subsequent to the alarm activation of any area or duct detector, manual station or waterflow switch shall be as follows:

a. Cause audio and visual signals to alarm on all floors in the affected building.

b. Automatically notify the Campus Police.

c. Display individual detector number on annunciator with University defined message.

d. Print individual detector number with University defined message, date, and time on printer terminal.

e. Light an indicating lamp on the smoke detector initiating the alarm.

f. Activate elevator return sequence when elevator lobby or elevator machine room smoke detector initiating alarm.

g. Close all magnetically held fire doors unless programmed to close on affected floor only as determined by the Designated Campus Fire Marshal (DCFM).

h. Unlock security doors.

i. Individual HVAC units will automatically shut down upon activation of the duct detector serving that unit through the fire alarm system.

D. The alarm activation of any elevator lobby smoke detector shall, in addition to the operations listed above, cause the elevator cabs to be recalled according to the following sequence:

1. If the alarmed detector is on any floor other than the main level of egress, the elevator cabs shall be recalled to the main level of egress.

2. If the alarmed detector is on the main egress level, the elevator cabs shall be recalled to the predetermined alternate recall level as determined by the DCFM.

E. Activation of any fire sprinkler valve tamper switch shall cause a trouble signal.

F. There shall be no limit, other than maximum system capacity, as to the number of addressable devices which may be in alarm simultaneously.

G. Smoke/fire damper shall be controlled by fire alarm system area detection or through HVAC duct detector used for smoke shutdown (consult with DCFM).

H. The activation of any system smoke detector shall initiate an Alarm Verification operation whereby the panel will reset the activated detector and wait for a second alarm activation. If, within 30 seconds of resetting, a second alarm is reported from the same or any other smoke detector, the system shall process the alarm as described previously. If no second alarm occurs within 30 seconds the system is to resume

UCSB Fire Protection Division

16720-3 Fire Alarm System

normal operation. The Alarm Verification shall operate only on smoke detector alarms. Other activated initiating devices shall be processed immediately.

1.2 QUALITY ASSURANCE

A. Codes and Standards: Comply with the codes and standards as indicated in Section 1.4 of this Section.

B. Tests: The Contractor shall provide all meters, smoke generating equipment and test equipment and test the system in the presence of the University’s Representative and the DCFM. The tests shall include the following:

1. Each resettable initiating device for alarm including smoke test of all smoke detectors with smoke generating equipment.

2. The audio/visual system for sound level and initiation.

3. Verify Class "A" operation of each initiating device and audio/visual system.

4. System supervisory reporting.

5. Operation of system under stand-by power conditions.

6. Door release system.

7. Control of mechanical system.

8. Reporting to the existing central alarm panel. Verify existing central alarm system and conduit routing, prior to bid.

C. Contractor qualifications: The Contractor shall hold a current California C-10 contractor's license.

D. Contractor shall demonstrate satisfactory installations of comparable systems within the preceding five years, including references.

E. Ability to provide emergency response to effect repair within 4 hours by factory certified personnel during the warranty period.

F. Contractor shall provide proof that the fire alarm contractor is Underwriters Laboratories, Inc. (UL) listed under the classification of "PROTECTIVE SIGNALING SERVICES-LOCAL, AUXILIARY, REMOTE STATION AND PROPRIETARY (UUJS).

G. Contractor shall provide a copy of the following (NICET) Certificates. Proof that the certificate holders are a part of the fire alarm contractor's local facility servicing this project and will be actively involved in this project.

1. Certified Technologist or Registered Fire Protection Engineer.

2. Technician Level 2.

3. Technician Level 4.

UCSB Fire Protection Division

16720-4 Fire Alarm System

H. Documentation that the fire alarm contractor has on staff personnel factory-trained and certified for the equipment proposed for this project. Also, a statement that personnel meeting these qualifications are in the local facility, and will be maintained at that facility throughout the project and the warranty period.

1.3 SUBMITTALS

A. Certified test report to verify that the system and all components functioned properly and as intended, signed by both the Contractor and equipment supplier. Provide written certification per NFPA 72 from the fire alarm system installer that the system is in compliance with all applicable code requirements.

B. The following list includes but does not limit the required shop drawing and product data information that shall be submitted:

1. Catalogue sheets of all components indicating technical data, size and capacities. Reference catalogue sheets to specification paragraphs.

2. Submit parts list of all equipment with manufacturer's data sheets, the location of each piece and device (i.e. elevation of alarm panels and cabinets), battery calculations, and proposed conduit layout diagram for both vertical and horizontal runs. Identify location and sizes of terminal cabinets.

3. Submittals shall include State Fire Marshal LISTING SHEETS, including LISTING NUMBER with ANNUAL UPDATE and EXPIRATION DATE, for ALL SYSTEM COMPONENTS. SUBMITTALS WILL BE AUTOMATICALLY REJECTED IF COMPLETE LISTING INFOMATION DOES NOT ACCOMPANY SUBMITTAL. Complete point-to-point wiring diagram of the entire system showing interconnection of identified devices, and controls shall be submitted to, and approved by, the DCFM before installation. Complete conduit layouts at each floor and conduit riser diagrams.

4. State of California Fire Marshal approval of all components.

5. UL listing of all components for their intended use. Data sheets are required for all system components. Including but not limited to, control panels, batteries. Battery chargers, signal initiating devices, audible alarms, visual alarms, annunciators, terminals, cabinets, wiring conductors and relays. All equipment drawing alarm or supervisory current shall have documentation of the current draw highlighted in the submittal information.

6. Enclosures indicating:

a. Metal and gage.

b. Finish.

7. Output rating of all alarm system components, point-to-point Ohm's law voltage drop calculations not to exceed 3% or the maximum the equipment manufacturer allows battery calculations.

8. An index and title sheet shall be put at the front of the product data submittal to organize and speed review.

UCSB Fire Protection Division

16720-5 Fire Alarm System

C. Operation and Maintenance Manuals: Submit shop drawings and operation and maintenance manuals. Submit manuals, each of which shall include all instructions necessary for proper operation and maintenance of the system, complete circuit diagrams, wiring and termination schedule for each circuit entering and or leaving each piece of equipment, schematic diagrams of each major component, including a replacement parts list with part numbers, name and telephone number of local supplier. Include any portions of the material list and shop drawings which are not included in the foregoing.

D. Fire Marshal's approval of the installed system. Submit fire alarm system plans to DCFM for approval prior to installation. Plan Submittal shall include all applicable information from submittal checklist attached to the end of this specification. Mounting details shall be shown for pull stations, audio/visual devices, annunciator panels, and fire alarm control panels.

E. Furnish a letter from the manufacturer stating that the manufacturer has a factory warehouse at which spare parts are stocked and where a field service engineer permanently resides, located within 50 miles of the Job Site, factory trained and one whose primary duty is field service.

F. As-built Drawings on heavy-duty reproducible Mylar equal in size to the contract drawings. Submit sets of as-built documents for DCFM and engineer approvals, including: installation wiring, schematics, operation and maintenance manual, and complete replacement parts list. Drawings shall be reproducible type and shall be complete to facilitate troubleshooting and repair of the system.

G. Two full days (16 hours) of training shall be provided by a field engineer employed by the equipment manufacturer. Training shall be provided at the job site after completion of the Fire Alarm System installation.

H. NFPA 72 Record of Completion shall be completed by installing contractor at the end of the project and provided to the DCFM.

I. Written operating procedures shall be provided at a location approved by the DCFM.

1.4 REFERENCES

A. Fire alarm system, equipment, installation, and wiring materials and methods used shall comply with the following codes and standards:

1. California Electrical Code.

2. NFPA 72, including appendices.

3. Title 19, California Administrative Code.

4. Title 24, California Administrative Code.

5. California Building Code, current adopted edition.

6. California Mechanical Code, current adopted edition.

7. California Fire Code, current adopted edition.

UCSB Fire Protection Division

16720-6 Fire Alarm System

8. California State Fire Marshal's requirement.

9. DCFM.

10. UL 38, 217, 228, 268, 268A, 346, 464, 521, 864, 1481, 1638, 1730, 1971.

11. American Disabilities Act.

12. NFPA 90A

13. National Electrical Manufacturers Association (NEMA)

a. Guide for the proper use of Smoke Detectors.

b. Guide for the proper use of Duct Smoke Detectors.

B. Materials and/or installation shall meet or exceed the above referenced standards.

C. The system including all components shall be listed by the State Fire Marshal and Underwriters Laboratories Inc. for use as a fire protective signaling system.

D. The system must have proper listing and / or approval from the following nationally recognized agencies:

1. UL Underwriters Laboratories, Inc.

2. UL categories UUKL, PAZX, UDTZ, QVAX as well as the requirements of NFPA 90A, HVAC, and NFPA 92A & 92B, Smoke Control.

3. CSFM California State Fire Marshal

4. FM Factory Mutual

5. ISO International Standards Organization

PART 2 - PRODUCTS

2.1 MATERIALS AND EQUIPMENT

A. All materials, equipment, accessories, devices and other facilities and appurtenances covered by these specifications or noted on the Drawings shall be new, best suited for the intended use and shall conform to applicable and recognized standards for their use. The system shall be from one of the following acceptable manufacturers:

1. Fire Control Instruments

2. Notifier

3. Siemens – Cerberus Division

B. Manual, supplemental smoke detection and evacuation type fire alarm systems. This specification document provides the requirements for an analog addressable, multiprocessor-based fire ala rm control panel and combined fire alarm/voice evacuation/relocation system (non voice evacuation systems may be acceptable based

UCSB Fire Protection Division

16720-7 Fire Alarm System

on building type and size, consult with DCFM). This system shall include, but not be limited to, system cabinets, control and communication equipment, power amplifiers, Switching Power Supply Unit, System Control Unit, Analog Loop Unit with Keyboard Display Unit or Quad/Eight Zone Unit, audible and visual notification appliances, together with associated peripheral devices, programming, wiring and other relevant components to provide a complete and operable system.

2.2 CONTROL EQUIPMENT

A. The control panel shall provide power, annunciation, supervision and control for the detection and alarm system. The control panel shall be modular in construction, and contain all modules necessary to operate in compliance with the schedule in the "System Description and Function" paragraph of this Specification and applicable Drawings. The system shall be capable of reading and displaying at the control panel the sensitivity of remote addressable ionization and photoelectric detection devices. Individual, addressable detection device alarm threshold shall be adjustable from the control panel. The detection system shall remain 100 percent operational and capable of responding to an alarm condition while in the routine maintenance mode. Addressable detection devices shall be individually identified by the system, and any quantity of addressable detection devices shall be in alarm at any time up to the total number connected to the system.

B. The control panel shall be capable of supporting non-addressable as well as addressable detection devices.

C. The annunciator panel shall be a min. 80 character alpha-numeric display, which shall provide an optional University definable message associated with each detection device or zone as approved by LSS and DCFM. All annunciator panels shall be located on the exterior of the building in a location approved by the DCFM.

D. The Dynamic supervision of the system electronics, wiring, detection devices and software shall be provided by the control system. Failure of the system hardware or wiring shall be indicated by type and location on the alphanumeric annunciator. Software and processor operation shall be monitored by an independent hardware watchdog, which will indicate their failure. The system will provide failsafe operation, i.e. incoming alarms shall automatically override all other modes of operation, and the panel shall automatically return to normal operating mode from any operator initiated mode.

E. Ground fault detection shall be provided for all initiating and audible circuits. All system modules shall be capable of operation in any unused panel location. Lamp test capability shall be provided to test all visual panel indicators and associated software. Provisions shall be made for remote trouble and remote alarm silencing switches. The control panel shall be equipped with a silence before reset feature, designed to prevent accidental system reset during an alarm condition. The system alarm lamp shall flash upon receipt of any alarm condition. Acknowledgment of the alarm by operation of the silence switch shall silence the audible alarm and cause the alarm lamp to light steadily. Receipt of subsequent alarms shall cause the audible devices to resound and the alarm lamp to flash.

F. The system trouble lamp shall flash and an integral trouble buzzer shall sound upon the occurrence of any trouble condition. Acknowledgment of the trouble condition

UCSB Fire Protection Division

16720-8 Fire Alarm System

by operation of the silence switch shall silence the audible alarm and cause the trouble alarm to light steadily. Receipt of subsequent troubles shall cause the trouble buzzer to resound and the trouble lamp to flash.

G. Individual input and output device addressability as well as remote sensitivity measurement shall all be performed on the same pair of wires. Wiring shall be Class "A" and no special wiring sequence shall be required on addressable device circuits. An unlimited number of writing branches shall be permitted with no loss of supervision. The system shall be capable of having all addressable devices in alarm simultaneously.

H. The service mode shall permit the arming and disarming of individual detection or output devices as well as manually operating output devices. Status of these devices shall be displayed upon command from the control panel. The panel shall automatically return to the normal mode in the event the panel remains unattended in the service mode.

I. The panel shall be capable of receiving and processing alarms even when in the service mode.

J. The control panel shall operate from a three wire 120 VAC power supply and internal 24V back-up battery. All power connections, both AC and DC, shall be separately fused within the control panel. Light emitting diodes (LED's) shall be included to indicate (green) system power, (yellow) trouble, and (red) alarm; trouble and alarm shall also be annunciated on an alpha-numeric display which will give device number and location plus diagnosis of trouble. An audible device shall sound within the control panel for alarm or trouble. This device shall have two distinct sounds and shall be silenceable by the acknowledge/silence switch. Alarms shall override any trouble condition.

K. The control power supply shall be capable of powering up to 500 addressable early warning detectors and at least thirty audible and visible signal circuits. All system expansion modules shall interconnect through a card edge connector and shall require no inter-module wiring.

L. The control panel shall be capable of measuring and adjusting the sensitivity of detectors. An alpha-numeric display shall be provided to display custom messages and give readings of the detector sensitivity, detector by detector. Each device on an addressable initiating circuit shall be checked continuously to include the following: sensitivity, response, opens, shorts, ground faults, functionality and status.

M. The control panel shall report the failure of a device's transmitting component(s) failure, open, or shorted, on an addressable initiating circuit. The device shall be recognized and identified by location within the circuit to the specific device, and all other devices on the circuit shall continue to function.

N. The control panel shall report, by specific device number, any device removed from an addressable initiating circuit and all other devices shall continue to function.

O. The control panel shall allow changing the status of configured circuits (arming and disarming and changing status of relays). If any change in status degrades system operation as configured, a trouble condition shall be reported and remain until system operation again meets configured status.

UCSB Fire Protection Division

16720-9 Fire Alarm System

P. The control panel shall have the ability to perform multiple operations at the same time. These operations shall include, but not be limited to, timed functions and multiple configured sequences.

Q. The control panel shall have the ability to support a printer terminal. This terminal shall be used for permanent records of the system's status and detector chamber voltages, and shall also be capable of system control as configured.

R. The control panel shall allow for expansion and shall also be configurable without system interwiring.

S. The system shall provide a hard copy written record of all alarms, troubles, and system activity by means of full carriage width terminal to print detection devices designations and location messages on a single line of up to 80 characters.

T. New unacknowledged alarms and troubles shall be distinctively displayed on both the visual display and the printer and differentiated from previous alarms and troubles.

U. The system shall automatically indicate the total quantity of alarms and of troubles which have occurred prior to reset at the control unit.

V. No alarm or trouble indication shall be resettable until it has been acknowledged. It shall not be possible to reset the system until all alarms have been acknowledged.

W. It shall be possible to display up to 127 alarm and up to 127 trouble indications, one at a time, on the digital annunciator and as a list on the printer. The printer shall be capable of listing, upon request:

1. Alarm with time, date and location.

2. Trouble with time, date, and location.

3. Status of output functions, "on" or "off."

4. Sensitivity of addressable smoke detectors.

5. Detection device number, type, and location.

6. Status of remote relays, "on" or "off."

7. Acknowledgment time and date.

8. Signal silence time and date.

9. Reset time and date.

X. The system shall be capable of:

1. Counting the number of addressable detectors within a "zone" which are in alarm.

2. Counting "zones" which are in alarm.

3. Counting the number of addressable detectors which are in alarm on the system.

UCSB Fire Protection Division

16720-10 Fire Alarm System

4. Differentiating among types of addressable detectors such as smoke detectors, manual stations, water-flow switches and thermal detectors.

5. Assigning priorities to types of detectors, zones or groups of detectors.

6. Cross-zoning.

Y. Control functions shall be assigned on the basis of system initiation patterns of detection devices such as "anding" zones, counting zones, counting devices, and "anding" groups, and "anding" types of detection devices.

Z. Control functions shall be assigned on the basis of time of day, day of week, and with a holiday schedule of up to thirty holidays per year. Each addressable detection device shall report its condition to the system control unit every four seconds in a manner such that failure of the connections to or internal electronics of the device will result in a trouble signal which identifies the specific device involved.

AA. Addressable photoelectric type smoke detector sensitivity shall be reported at the control panel when requested. The electronic readout of detector sensitivity shall be equivalent to sensitivity readings made with a meter for non-addressable detector, but shall be read at the control panel digital annunciator. It shall be possible to change the detector sensitivity from the control panel within maximum and minimum values as defined by the UL listing of the detectors.

BB. The system shall be capable of listing detector chamber settings on the printer for permanent record.

CC. Water-flow switches, tamper switches, OS & Y valves, manual stations, and thermal detectors shall be equipped with an electronic address device which shall be supervised identically as addressable detectors.

DD. Water-flow switch alarm operation and automatic sprinkler system supervisory switches shall be wired and annunciated in conformance with the National Fire Codes.

EE. A trouble signal shall be initiated for each addressable device for which the automatic sensitivity measurement is too insensitive.

FF. The supervised and powered parallel output circuits shall be capable of use as audible signal circuits, fire extinguishing release circuits, municipal tie, remote station connection or general alarm release service. They shall be capable of providing 1.5 amp at 24 VDC.

GG. Provision for control relays in the firm alarm control unit shall be included for relays having dry contacts rated 120 VAC 3 amp inductive.

HH. Remote relays located on detector bases or double gang outlets throughout the building shall be controlled in the same manner as panel mounted relays.

II. "UPS": The system power supply shall be provided with an integral uninterruptible power source "UPS." This UPS shall provide continuous power to the system in the event of a commercial power failure. Transfer from commercial to standby power shall be instantaneous to insure proper processor operation, and indicated by flashing

UCSB Fire Protection Division

16720-11 Fire Alarm System

the system power LED. A dual rate battery charger shall be provided which is capable of recharging the batteries to 80 percent capacity in 12 hours. Loss of commercial power shall be annunciated as a system trouble. System trouble shall be indicated for over or under voltage conditions, blown fuse or disconnected batteries. The system shall automatically restart upon the return of power. No operator intervention shall be required.

JJ. The control panel enclosure shall be suitable for surface or semiflush mounting. A locked door shall be provided to limit access to individuals authorized access to the panel.

KK. All modules shall be plug-in, dynamically supervised and easily replaceable. Field wiring shall be connected to the panel with removable multi-conductor connectors to facilitate rapid removal and replacement of both the module and wiring for ease of servicing the panel.

LL. Visual indicators shall be long life LED's. Modules capable of initiating a system trouble shall display individual trouble indications on the alpha-numeric annunciator.

MM. Batteries

1. Battery shall be 12 volt, Sealed lead acid type.

2. Battery shall have sufficient capacity to power the fire alarm system for not less than 24 hours plus 15 minutes of alarm for voice evac and 5 minutes of alarm for non voice evac upon a normal AC power failure.

3. The batteries are to be completely maintenance free. No liquids are required. Fluid level checks refilling, spills and leakage shall not be required.

2.3 INITIATING CIRCUITS

A. Addressable/programmable initia ting circuits shall be provided by an Addressable Input Module. The module shall be system interconnected by a card edge connector, and shall be operable by the control unit.

B. Each initiating circuit shall consist of a four wire circuit, allowing multiple taps. Each initiating circuit shall accommodate up to 120 addressable/programmable initiating devices. Each circuit shall be Class "A" wiring.

C. Upon activation of any addressable/programmable device installed in the circuit, the system shall automatically report the status of the device and initiate the sequence of operations specified for that device, e.g., alarm, local, general, reporting, trouble reporting only, etc. Alarm shall have priority over trouble. Trouble conditions shall be reported to include the device number, location and type of trouble.

D. All initiating devices on all circuits may be in alarm at the same time and perform the sequences of operation prescribed by the system configuration. If there are more than 127 alarms, the message "more than 127" will appear and any alarm after 127 will still have all of its required functions performed.

E. The initiating circuits shall maintain complete reporting of device status while in trouble, due to any addressable device having its active transmitting component fail,

UCSB Fire Protection Division

16720-12 Fire Alarm System

open or shorted. The initiating circuits shall detect a line break and provide information to the control panel allowing the user to determine between which two devices the break has occurred.

2.4 OUTPUT CIRCUIT

A. An output circuit for operation of DC audible devices, leased line or city tie, or Halon release shall be provided by a Programmable Signal Module. This module shall be system interconnected by a card edge connector, and shall be operable by the control unit.

B. Upon command by the control unit, the output circuits shall power tie circuits, which shall be limited energy outputs.

C. The module shall be supervised by the control unit for open and shorted circuits. Open circuits shall respond in similar manner. Each output circuit shall be individually fused.

D. Output circuits may be user controlled. If such control degrades system configuration, a trouble condition shall be reported.

2.5 RELAY MODULE

A. A programmable supplementary relay module shall be provided for control of door holders.

B. The module shall be system interconnected by a card edge connector and shall be operable by the control unit or manually.

C. The module shall contain four independent relays, fitted with form "C" contacts, rated at 120 VAC 3 amps inductive. The module shall be Underwriters' Laboratories, Inc. and California State Fire Marshal listed.

2.6 ALARM INITIATING DEVICES

A. The addressable photoelectric smoke detector shall be listed by Underwriters Laboratories, Inc. and California State Fire Marshal. The detector shall contain a long life light-emitting diode (LED) as its light source, and a photo diode as a light receiver. An automatic gain control circuit shall be provided to maintain correct sensitivity by compensating for detector aging and dirt accumulation. The detector shall be a plug-in twist/lock unit which allows for each connection to its mounting base.

1. It shall be possible to adjust and/or electronically measure the sensitivity of each individual addressable detector from the control panel. Relative sensitivity or manual methods which check the detector at the maximum allowable obscuration will not be considered as being equivalent.

2. The addressable photoelectric detector shall provide complete supervision of the detector optics. The detector shall be supervised for complete failure of the LED light source or a critical reduction in the light output of the automatic gain control circuit.

UCSB Fire Protection Division

16720-13 Fire Alarm System

3. The detector mounting base shall be of the twist/lock type with screw terminals for field wiring. Pig-tails or in line connectors will not be permitted.

4. For smoke detector the following wiring scheme shall be used.

WIRE COLOR FOUR WIRE DETECTORS TWO WIRE DETECTORS

Red Positive Power (+) + Loop Feed

Black Negative Power (-) - Loop Feed

Yellow Loop Feed (Zone) + Loop Return

Blue Loop Feed (Common) - Loop Return

B. The addressable thermal detectors shall be of the rate compensated/fixed temperature type and shall be listed by Underwriters' Laboratories, Inc. and California State Fire Marshal. The addressable thermal detector shall be individually annunciated on the control panel. The addressable thermal detectors shall contain an integral alarm lamp.

C. The addressable programmable interface module shall provide an interface for direct shorting contact devices to the Addressable Input. This unit is used with water-flow switch, tamper switch and OS & Y valves.

D. The air duct detector shall operate on a cross-sectional air sampling principle to overcome stratification and the skin effect. The air duct detector shall consist of an addressable ionization detector mounted in an air duct sampling assembly and sampling tube that protrudes across the duct of the ventilating system.

E. Manual stations, non-coded and double action, shall be of rugged construction designed for semi-flush mounting. The station shall mechanically latch upon operation and remain so until manually reset by opening with key common to the fire alarm control panel to which they are connected.

2.7 CONTROL MODULE

A. HVAC control module shall contain three-position center OFF-ON-AUTO switches for manual override of automatic fan control of the air conditioning systems. In the "AUTO" position, the ACS shall operate under normal temperature control. In the "OFF" position, the system shall shut down. In the "ON" position, the system shall run, overriding the temperature control and fire alarm signals in the programmed mode for smoke control. Provisions shall be made for visual indication of each fan status.

B. All system interlocks, damper motors, electro-pneumatic relays, etc., for an operation system will be supplied and installed under different sections of these Specifications. The Contractor shall connect and wire to these devices.

2.8 AUDIO AND VISUAL ALARM SYSTEM

A. Audio/visual alarm shall be synchronized per ADA requirements and have a minimum 15 candela intensity flashing light and alarm as an integral unit. Visual components shall operate from the 24V DC polarized indicating circuits. All devices

UCSB Fire Protection Division

16720-14 Fire Alarm System

shall mount on 4- x 4-inch electrical boxes. Light will flash at the rate of one flash per second, minimum and three flash per second maximum. The min imum sound level shall be 75 dB at ten feet but not less than 15 dB above ambient noise. Audio device shall be mechanical or electronic horns and be set to sound temporal code 3. Audio/visual alarm shall be semi-flush mounted and located not more than 80 inches to the bottom of the lens above finished floor.

2.9 DOOR HOLDER AND RELEASE UNITS

A. Provide semi-flush wall and door mounted door holders. The armature section shall be mounted on the door per the architectural plans. The electromagnetic section shall be semi-flush mounted in the wall. Coordinate device locations with the architectural plans prior to installation. Door holder units shall be released by the control panel.

2.10 TRANSMITTERS

A. Provide a digital alarm communications transmitter capable of communicating with UCSB via phone lines. Coordinate with LSS to insure compliance with UCSB reporting requirements and to insure compatibility with UCSB receiving equipment.

B. Provide a radio alarm transmitter capable of wireless communication with UCSB via radio. Coordinate with LSS to insure compliance with UCSB reporting requirements and to insure compatibility with UCSB receiving equipment.

2.11 CONDUCTORS

A. All conductors shall be solid copper with UL THHN 600 volt, insulation, minimum size #14 AWG or larger. The cable shall be plenum fire rated with red outer jacket. Two conductor cables shall be used with two wire devices and four conductor cables shall be used for four wire devices. Two conductor cables shall consist of one red and one black wire. Four conductor cables shall have an additional yellow and blue wire.

2.12 PRINTER

A. Printers shall be of the automatic type, printing code, time, date, location, category, and condition.

B. The Printer shall provide hard copy printout of all changes in status of the system and shall time stamp such printouts with the current time of day and date. The printer shall be standard carriage with 80 characters per line and shall use standard pin feed paper. The printer shall be enclosed in a separate cabinet suitable for placement on a desktop or table. The printer shall communicate with the control panel using an interface complying with Electrical Industries Association standard EIA-232D. Power to the printer shall be 120 VAC @ 60 Hz.

C. Thermal printers are not acceptable.

2.13 SPARES

A. Spares of all devices shall be provided to the University for Maintenance or expansion of the system. This shall include all initiating and indicating devices,

UCSB Fire Protection Division

16720-15 Fire Alarm System

control panel zone and signaling cards and any other equipment which may not be readily available to the University.

PART 3 - EXECUTION

3.1 GENERAL

A. Control and other panels shall be mounted with clearances for observation and testing. All fire alarm junction boxes shall be marked for identification. Flexible connectors shall be used for all devices mounted in suspended lay-in panels. All conduits, mounting boxes and panels shall be hung and fastened with fittings to insure positive grounding throughout the entire system.

B. No wiring other than that directly associated with fire alarm detection, alarm or auxiliary fire protection functions shall be permitted in fire alarm conduits. Wiring splices shall be avoided. If needed, they shall be made only in junction boxes. Transposing or changing color coding of wires will not be permitted. All conductors in conduit containing more than one wire shall be labeled on each end with "E-Z markers." Conductors in cabinets shall be formed and harnessed so that each drops off directly opposite to its terminal. Cabinet terminals shall be numbered and coded. All controls, function switches, etc., shall be labeled on all equipment panels. All wiring shall be checked and tested to insure that there are no grounds, opens or shorts.

C. Paint all Fire Alarm boxes red on exterior and all Fire Alarm conduits.

3.2 INSTALLATION

A. Locate and install equipment and accessories as shown on the Drawings.

B. Mount control panels and terminal cabinets such that terminals are located between 42 and 66 inches above the adjacent walking surface.

C. Minimum wire size shall be No- 12 AWG (No. 14 AWG permitted for circuits not exceeding 25 volts), type THHN, 600 volt, stranded copper, installed in metallic conduit. Wire size shall be increased appropriately to maintain voltage and current capacity. All wires shall be identified with substantial markers. All initiation and signaling loops shall be wired without parallel branches and are to start and return at the main terminal cabinet. Space conductors are to be provided on a ten percent (minimum two conductors) schedule per riser; annunciator panels shall be wired for full capacity. No splicing will be allowed in terminal or device boxes. All connections shall be made on terminals. There shall be no below-grade splicing.

D. Supervised wiring shall be continuous, paralle l branches ("T" taps) are not permitted regardless of the method of supervision employed.

E. Conduit shall be EMT above grade and in buildings; schedule 40 PVC to be used underground. All concealed fire alarm system conduit shall be externally identified at 20 foot intervals in each space, and at "J" box covers by permanent red paint suitable for the purpose. All fire alarm system wiring shall be installed in conduit independent of all other electrical circuits. Magnetic door holding circuits and other non-power limited circuits shall be in separate raceways-

UCSB Fire Protection Division

16720-16 Fire Alarm System

F. Exposed flexible conduit as used for attachment to water-flow and valve tamper switched or similar application shall be liquid-tight and shall be minimum length required for neat and secure installation. Flexible conduit lengths shall not exceed three feet. Flexible conduit shall not be buried nor located closer than 12 inches to grade.

G. In rooms where smoke detectors are shown, smoke detector quantity and spacing shall be as recommended by the manufacturer and NFPA.

H. All fire alarm system equipment shall be installed in NEMA 1 enclosures for interior locations. Equipment shall include proper mounting boxes, hardware, and fittings for the respective building surfaces and finishes.

I. All equipment and devices installed in exterior and in wet locations shall be installed in NEMA 4 enclosures or otherwise approved for weatherproof use.

J. Breaker panels shall be provided with lockdown clips for circuit breakers supplying fire protection circuits. Circuit breakers shall be permanently and clearly identified.

K. All Duct Mounted Smoke Detectors shall be mounted and weatherproofed to the ductwork, as required, by the Mechanical Contractor. They shall be furnished and wired by the Fire Alarm Contractor. Access panels shall be provided for all duct mounted detectors per NFPA 90A. Sampling tubes shall be accessible via access panels.

L. HVAC/Smoke Control System Operation

1. On/Auto/Off switches and status indicators (LEDs) shall be provided for monitoring and manual control of each fan, damper, HVAC control unit, stairwell pressurization fan, and smoke exhaust fan. To ensure compliance the units supplied shall meet the following UL categories: UUKL, PAZX, UDTZ, QVAX as well as the requirements of NFPA 90A, HVAC, and NFPA 92A and 92B, Smoke Control. The control system shall be field programmable for either 90A operation or 92A/B operation to allow for future use and system expansion.

2. The OFF LED shall be yellow, the ON LED shall be green, the Trouble/Fault LED shall be amber/orange for each switch. The Trouble/Fault indicator shall indicate a trouble in the control and/or monitor points associated with that switch. In addition, each group of eight switches shall have two LEDs and one momentary switch which allow the following functions: An amber LED to indicate an OFF-NORMAL switch position, in the ON or OFF position; a green LED to indicate ALL AUTO switch position; a Local Acknowledge/Lamp Test momentary switch.

3. Each switch shall have the capability to monitor and control two addressable inputs and two addressable outputs. In all modes, the ON and OFF indicators shall continuously follow the device status not the switch position. Positive feedback shall be employed to verify correct operation of the device being controlled. Systems that indicate on/off/auto by physical switch position only shall not be acceptable.

4. All HVAC switches (i.e., limit switches, vane switches, etc.) shall be provided and installed by the HVAC contractor.

UCSB Fire Protection Division

16720-17 Fire Alarm System

5. It shall be possible to meet the requirements mentioned above utilizing wall mounted custom graphic annunciators if the project requires such.

3.3 TESTS AND REPORTS

A. In addition to tests required in this Section, the Contractor shall perform all electrical and mechanical tests required by the equipment manufacturer, the University’s Representative and the DCFM. In addition, via the printer terminal, provide a printout of the sensitivity readings of each addressable ionization or photoelectric detector connected to the control panel. The sensitivity readings shall be for each detector at its operational location under environmental conditions.

B. If non-addressable detectors are used in the system, they shall be measured and adjusted to the maximum stable setting. This shall be performed with the detector at its operational location and under normal environmental conditions in the area. Bench settings are not acceptable.

C. A checkout report shall be prepared by the Contractor. Submit six (6) copies to the University’s Representative and one (1) copy to the equipment manufacturer. The report shall include, but not be limited to:

1. A complete list of equipment installed and wired.

2. Certify that all equipment is properly installed and functions and conforms with these specifications.

3. A print out via the printer terminal of all devices connected to the system.

4. Sensitivity settings for each ionization and photoelectric detector as measured in place with the HVAC system operating.

5. Technician's name, certificate number and date.

D. After completion of all the tests and adjustments listed above, and review and approval by the University’s Representative of data and test report, the Contractor shall submit the following information to the University’s Representative.

1. "As-built" conduit layout diagrams including wire color code terminal number (on permanent reproducible mylar originals).

2. Complete "as-built" wiring diagrams (on permanent reproducible mylar originals).

3. Detailed catalog data on all installed systems components (six (6) copies).

4. A final copy of the test report described in paragraph 3.03 C.1 above (six (6) copies).

E. Prior to calling for final test, the contractor shall conduct a 100% pre-test of all system components to insure complete operation. Once the pre-test is complete, the contractor shall sign a verification sheet that states a 100% functional test of the fire alarm system has been conducted and provide it to the DCFM.

UCSB Fire Protection Division

16720-18 Fire Alarm System

F. Final tests and inspections shall be held in the presence of the DCFM and LSS. The Contractor shall supply personnel and required auxiliary equipment (smoke generator, decibel meter) for this test without additional cost to the University. The completed alarm and detection system shall be tested to ensure that it is operating properly. This test will consist of:

1. Activation of all detection devices on each loop or zone. All devices of each type, ionization detector, photoelectric detector, manual pull station, thermal detectors, water flow and tamper switches, shall be activated per loop or zone, and verified for proper function per the specification and custom message location at the control panel alpha-numeric display and the printer.

2. Smoke detectors shall be tested using a smoke generator or a SOLO 301 Smoke Detector Testing Tool. Magnets are not an acceptable means of testing.

3. Verification that all audible-visual devices operate and that the audibility of the devices is at the proper sound level (per manufacturer's specifications) throughout the building using decibel meter.

4. Transmit alarm and trouble signal to University Police Dispatch and confirm receipt of alarms with dispatcher.

G. If the system does not perform to the above criteria it will not be accepted and the Contractor shall correct all deficiencies and shall re-test the system at Contractor's expense in the presence of the DCFM and LSS using the same test criteria.

H. Before final acceptance of the work, the Contractor shall deliver to the University’s Representative seven (7) bond copies of a composite "Operating and Shop Maintenance Manual." Each manual shall contain the following:

1. A statement of guarantee including date of termination.

2. Name and twenty-four hour telephone number of the repair facility to call in the event of equipment failure.

3. Individual factory issued manuals containing all technical information on each specific piece of equipment installed ("typical" data sheets on manuals covering various items are not acceptable).

4. Copy of the system program.

5. Record drawings of the system installation.

I. It shall be the responsibility of the Contractor to obtain the above items, from factory, or elsewhere. Advertising brochures or operational instructions shall not be used in lieu of the required technical manuals. All information shall be for the specific installation for the current project.

3.4 IDENTIFICATION

A. Provide identification of equipment and materials.

UCSB Fire Protection Division

16720-19 Fire Alarm System

3.5 GROUNDING

A. All metallic conduit, cabinets, junction boxes, and exposed non-current-carrying metal parts shall be permanently grounded. A separate No. 10 AWG conductor shall connect a grounding bus bar located in each main terminal cabinet to building ground. The bus bar shall be provided with a minimum of five tubular, pressure type screw terminals sized for no. 18 AWG through no. 10 AWG wire. The ground wire for the fire alarm control panel and the main terminal cabinet shall be grounded via the bus bar.

3.6 DOCUMENTATION

A. Copies of complete as-built installation wiring documentation, internal fire alarm control panel schematics, NFPA 72 Record of Completion and maintenance manuals are to be submitted to DCFM prior to final acceptance.

B. A copy of the completed NFPA 72 Record of Completion and final acceptance test printout shall be put into the door of the main fire alarm control panel.

3.7 SYSTEM TESTING AND INSTRUCTION

A. The entire fire alarm system shall be tested and adjusted by the contractor under the supervision of a factory-trained representative of the manufacturer.

B. Contractor shall furnish necessary equipment and personnel to perform required tests for approval. Performance tests shall be made in the presence of the DCFM. Inspection and testing shall be at the direction of the DCFM. The test is to ensure that all equipment and devices are installed in an approved manner and are performing properly. The completion test report prepared by the contractor, shall be submitted for approval by the Engineer. Rectify any deficiencies found and retest.

3.8 INSTRUCTION

A. Contractor shall ensure that manufacturer’s representative instruct LSS for a minimum of eight (8) hours in the operation, maintenance, and testing of the system. Factory Maintenance Manuals shall be provided to LSS upon completion of testing.

3.9 WARRANTY

A. The Contractor shall provide a 1-year warranty for all equipment and wiring free from inherent mechanical and electrical defects. Refer to Division 1 for warranty format.

END OF SECTION