Final test - 0N323 Serial number 0N323 Model MWA 2x900 VSMTE/S Customer AXIMA REFRIGERATION FRANCE Language F Certified component SI_PED Supervisory PRED Wiring Diagram QE 0N323 MWA2X900VSMT_rev02.pdf QE model ARMADIO VFR32 +KIT Electrician MEGGEL Wiring Diagram QP - QP model - Electrician - legend Successful Test Failed Test Unnecessary Tests Page 1 of 23 0N323 03/08/2012 http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

Transcript of Final test - 0N323 - SCM FRIGO · 1=1 X CIRCUITO 0 0 Costruttore - C16 Type sondes pression...

Final test - 0N323

Serial number 0N323

Model MWA 2x900 VSMTE/S

Customer AXIMA REFRIGERATION FRANCE

Language F

Certified component SI_PED

Supervisory PRED

Wiring Diagram QE 0N323 MWA2X900VSMT_rev02.pdf

QE model ARMADIO VFR32 +KIT

Electrician MEGGEL

Wiring Diagram QP -

QP model -

Electrician -

legend

Successful Test

Failed Test

Unnecessary Tests

Page 1 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

Page 2 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

TEST

Note

Check electrical panel box free from waste processing

Verification of correspondence with the separate components of electric scheme

ELECTRICAL TEST

Note

Check continuity equipotential protection circuit (<1V) 058v

Isolation tests (>1000 MOhm) ovfl Mhom

Tension tests (>1000V) 1072v

TEST - Serial Card

Note

Present

TEST - Verification of compliance under the wiring diagram:

Note

Main terminals

Struments terminals

Thermical overload offset

TEST - Checking the voltage input and output transformers

Note

TV1 384v 229v

TV2A 387v 25v

TV3 229v 24v

TV4

Carter resistance 229v

TEST - Check operation

Note

Compressors contactors

Lamps lights

Carter resistance

Page 3 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

Relay

Main breaks

Selectors

Solenoids

Flow switch

Antifreeze

Float

TEST - Verification operation

Note

Thermical overload

HIGH/LOW PRESSURE SWITCH

TEST - Check safety devices

Note

Pressure switches

Safety valves

TEST - Check direction of rotation

Note

Screw or scroll compressors provati.

TEST

Note

Check correspondence diagram of the electronic equipment installed

Page 4 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

Software Chiller Vite SCM Frigo - rev. 07 -

Code Parameter Default Set Note

Setpoint - S02

Set-point chiller -7 8

Costruttore - C00

Configuration circuits 1 2

Costruttore - C00

Configuration Compres. 1 2

Costruttore - C01

Type Compresseur 0=SERIE HS53...HS64 1=SERIE HS74 2=SERIE HS85 3=SERIE CSH

0 3

Costruttore - C02

Intermittence partialisation 4 temps de ON 10 10

Costruttore - C02

Intermittence partialisation 4 temps de OFF 10 10

Costruttore - C02a

Economizer type 0=STANDARD 1=POWER STEP

0 0

Costruttore - C02a

Economizer start delay 1 5

Costruttore - C02b

Compressors inverter 0=NO INVERTER 1=INVERTER 1 COMP. 2=INVERTER 2 COMP.

0 2

Costruttore - C02c

Compressor inverter minimum limit 0 0

Costruttore - C03

Type evaporat. 0=1 PAR CIRC. 1=EVAP. SIMPLE

1 0

Costruttore - C03

Type condenseur 0=AIR 1=EAU

0 1

Costruttore - C03a

Enable condenser probes 0=NON 1=OUI

0 0

Costruttore - C04

Active deuxième pompe 0=NON 1=OUI

0 0

Costruttore - C05

Act. gestion Refroi. pLAN 0=NON 1=OUI

0 0

Costruttore - C05

Num. unitè pCO 1 1

Costruttore - C06

Retard alarme rès. pLAN 30 30

Costruttore - C07

Active gestion refroidiss. huile 0=NON 1=OUI

0 0

Costruttore - C08

Activat. gestion multi-condenseurs 0=NON 1=OUI

0 0

Costruttore - C09

Num. Ventilateurs condenseur 4 4

Costruttore - C10

Condenser modulating regulat. 0=NO REGULATION 1=SPEED FAN CONTROLLER 2=INVERTER CONTROLLER

0 30

Costruttore - C11

Modbus config. Stop bit. 0=1 BIT 1=2 BIT

0 0

Costruttore Modbus config. Parity mode: 0=NONE

0 0

Page 5 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

- C11 1=EVEN 2=ODD

Costruttore - C12

Modbus config. Baud rate: 0=1200 1=2400 2=4800 3=9600 4=19200

4 4

Costruttore - C12

Modbus config. Timeout 2000 2000

Costruttore - C13

Règlage sur 0=TEMP. ENTRÉE 1=TEMP. SORTIE

0 1

Costruttore - C13

Type règlage 0=BANDE LATÉRALE 1=ZONE NEUTRE

0 1

Costruttore - C14

Active prèsence sonde tempèrature externe 0=NON 1=OUI

0 0

Costruttore - C14

Active prèsence sonde tempèrature out generale 0=NON 1=OUI

0 1

Costruttore - C15

Vanne ligne liquide 0=1 X COMPRESS. 1=1 X CIRCUITO

0 0

Costruttore - C16

Type sondes pression 0=4..20MA 1=0..5V

0 0

Costruttore - C17

Active gestion alarmes perte sondes 0=NON 1=OUI

1 1

Costruttore - C18

Active alarmes de perte sondes B1 0=NON 1=OUI

1 1

Costruttore - C18

Active alarmes de perte sondes B2 0=NON 1=OUI

1 1

Costruttore - C18

Active alarmes de perte sondes B3 0=NON 1=OUI

1 1

Costruttore - C18

Active alarmes de perte sondes B4 0=NON 1=OUI

1 1

Costruttore - C18

Active alarmes de perte sondes B5 0=NON 1=OUI

1 1

Costruttore - C19

Active alarmes de perte sondes B6 0=NON 1=OUI

1 1

Costruttore - C19

Active alarmes de perte sondes B7 0=NON 1=OUI

1 1

Costruttore - C19

Active alarmes de perte sondes B8 0=NON 1=OUI

1 1

Costruttore - C20

Active alarmes de perte sondes B9 0=NON 1=OUI

1 1

Costruttore - C20

Active alarmes de perte sondes B10 0=NON 1=OUI

1 1

Costruttore - C21

Retard alarme perte sondes 10 10

Costruttore - C22

Alarmes sonde expansion 1 0=NON 1=OUI

0 0

Costruttore Alarmes sonde expansion 3

Page 6 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

- C22 0=NON 1=OUI

0 0

Costruttore - C22

Alarmes sonde expansion 4 0=NON 1=OUI

0 0

Costruttore - C22

Retard sonde expansion 10 10

Costruttore - C22a

Alarmes sonde 1 expansion 2 0=NON 1=OUI

0 0

Costruttore - C22a

Alarmes sonde 2 expansion 2 0=NON 1=OUI

0 0

Costruttore - C22a

Retard sonde expansion 2 10 10

Costruttore - C23

Offset sondes B1 0 0

Costruttore - C23

Offset sondes B2 0 0

Costruttore - C23

Offset sondes B3 0 0

Costruttore - C24

Offset sondes B4 0 0

Costruttore - C24

Offset sondes B5 0 0

Costruttore - C25

Offset sondes B6 0 0

Costruttore - C25

Offset sondes B7 0 0

Costruttore - C25

Offset sondes B8 0 0

Costruttore - C26

Offset sondes B9 0 0

Costruttore - C26

Offset sondes B10 0 0

Costruttore - C27

Offset sonde expansion 1 0 0

Costruttore - C27a

Offset sonde 1 expansion 2 0 0

Costruttore - C27a

Offset sonde 2 expansion 2 0 0

Costruttore - C28

Champ sonde B1 limite inf. 0 0

Costruttore - C28

Champ sonde B1 limite sup. 30 30

Costruttore - C29

Champ sonde B2 limite inf. 0 0

Costruttore - C29

Champ sonde B2 limite sup. 30 30

Costruttore - C30

Champ sonde B3 limite inf. -1 -1

Costruttore - C30

Champ sonde B3 limite sup. 20 12

Costruttore - C31

Champ sonde B6 limite inf. -1 -1

Costruttore - C31

Champ sonde B6 limite sup. 20 12

Costruttore - C32

Champ sonde B7 limite inf. 0 0

Costruttore - C32

Champ sonde B7 limite sup. 30 30

Page 7 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

Costruttore - C34

Active prèsence vannes elect 0=NON 1=OUI

0 1

Costruttore - C34

DRIVER Carel 0=NON 1=OUI

0 0

Costruttore - C35

Active alarme haute press./therm. compresseur 0=NON 1=OUI

1 1

Costruttore - C36

Retard alarme haute press./therm. compresseur 0 0

Costruttore - C37

Alarme haute press.therm. compresseur rèp. aut./man. 0=AUTOMATIQUE 1=MANUEL

1 1

Costruttore - C38

Active alarme pression basse compresseur 0=NON 1=OUI

1 1

Costruttore - C39

Ret. al. basse démarrage 30 30

Costruttore - C39

Ret. al. basse régime 10 10

Costruttore - C40

Alarme pression basse Rèp. aut./man. 0=AUTOMATIQUE 1=MANUEL

0 0

Costruttore - C41

Réinitit. man. alarme basse pression après interv. heure 3 3

Costruttore - C42

Active alarme circuit huile compresseur 0=NON 1=OUI

1 1

Costruttore - C43

Ret. al. circ. huile compress. démarrage 30 90

Costruttore - C43

Ret. al. circ. huile compress. régime 5 90

Costruttore - C44

Alarme circuit huile compresseur rép. aut./man. 0=AUTOMATIQUE 1=MANUEL

1 1

Costruttore - C45

Active alarme fluxostat 0=NON 1=OUI

1 1

Costruttore - C46

Retard alarme fluxostat démarrage 10 10

Costruttore - C46

Retard alarme fluxostat régime 5 5

Costruttore - C47

Alarme fluxostat rèp. aut./man. 0=AUTOMATIQUE 1=MANUEL

1 1

Costruttore - C48

Active alarme therm. 0=NON 1=OUI

1 0

Costruttore - C49

Retard alarme therm. 0 0

Costruttore - C50

Alarme therm pompe rèp. aut./man. 0=AUTOMATIQUE 1=MANUEL

1 1

Costruttore - C50a

Heat alarm pump/s 0=UNIT OFF 1=SIGNALLING

0 0

Costruttore - C51

Active alerte al. therm. vent. condenseur 0=NON 1=OUI

1 1

Costruttore - C51a

Active alarme haute temperature glycol 0=NON 1=OUI

1 0

Costruttore - C51b

Retard alarme haute temperature glycol 120 120

Page 8 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

Costruttore - C51c

Alarme haute temperature gycol rép. aut./man. 0=AUTOMATIQUE 1=MANUEL

0 0

Costruttore - C52

Active alarme antigel 0=NON 1=OUI

1 1

Costruttore - C53

Retard alarme antigel 0 0

Costruttore - C54

Alarme antigel rép. aut./man. 0=AUTOMATIQUE 1=MANUEL

1 1

Costruttore - C54a

Enable low suction pressure warning 0=NON 1=OUI

1 0

Costruttore - C54b

Low suction pressure set-point 3 3

Costruttore - C54b

Low suction pressure differential 2 2

Costruttore - C54b

Low suction pressure warning delay 30 30

Costruttore - C54c

Active alarme haute pression 0=NON 1=OUI

1 0

Costruttore - C54d

Alarme haut. pres. set 24 24

Costruttore - C54d

Alarme haut. pres. diff. 4 4

Costruttore - C54d

Alarme haut. pres. rit. 30 30

Costruttore - C55

Active prevent haute pression 0=NON 1=OUI

0 0

Costruttore - C56

Prev. haut. pres. set 22 22

Costruttore - C56

Prev. haut. pres. diff. 2 2

Costruttore - C56

Prev. haut. pres. rit. 30 30

Costruttore - C57

Prévent haute pression 0=AUTOMATIQUE 1=MANUEL

0 0

Costruttore - C58

Active prévent économiseur 0=NON 1=OUI

0 0

Costruttore - C59

Prévent économiseur set. 50 50

Costruttore - C59

Prévent économiseur diff. 2 2

Costruttore - C60

Active antigel décharger 0=NON 1=OUI

0 0

Costruttore - C61

Antigel décharger set -11 -11

Costruttore - C61

Antigel décharger diff. 2 2

Costruttore - C62

Active alarme expans. off-line 0=NON 1=OUI

1 1

Costruttore - C63

Retard alarme expans. off-line 20 20

Costruttore - C63a

Alarm output type 0=GENERAL ALARM 1=PRIORITY ALARM

0 0

Costruttore

Page 9 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

- C64 Min. temps all. compresseur 5 10

Costruttore - C64

Min. temps éteint. compresseur 120 90

Costruttore - C65

Min. temps entre all. compress 10 10

Costruttore - C66

Min. temps entre allumages meme compresseur 360 240

Costruttore - C66a

Min. temps all. compresseur avec inverter 5 5

Costruttore - C66a

Min. temps éteint. compresseur avec inverter 120 120

Costruttore - C66b

Min. temps entre allumages compresseur avec inverter 360 360

Costruttore - C67

retard démar. partialisations 15 10

Costruttore - C68

Active rotation on/off compresseur 0=NON 1=OUI

1 1

Costruttore - C68

Active balancement 0=NON 1=OUI

0 0

Costruttore - C69b

Logique part. 1 0=NORM. OUVERT 1=NORM. FERME'

0 0

Costruttore - C69b

Logique part. 2 0=NORM. OUVERT 1=NORM. FERME'

0 0

Costruttore - C70

Séq. allumag. compress. 0=CPPCPP 1=CCPPPP

1 0

Costruttore - C70

Séq. éteign compress. 0=PPCPP 1=PPPPCC

1 0

Costruttore - C71

Active gestion pump-down compresseur 0=NON 1=OUI

0 0

Costruttore - C72

Température de congélement -15 -15

Costruttore - C73

Temps maximum pump-down 10 10

Costruttore - C74

Logique gestion pompe 0=CONDITIONNEMENT 1=RÉFRIGÉRATION

0 0

Costruttore - C75

Retard all. éteign pompe 15 15

Costruttore - C76

Active anticip. condens. sur départ compress. 0=NON 1=OUI

0 0

Costruttore - C77

Temps anticip. ventilateurs condens. sur ON compresseurs 10 10

Costruttore - C78

Numéro niveaux de condensation actif si sonde KO 2 2

Costruttore - C79

Condensation modulant en cas de sonde KO 100 100

Costruttore - C80

Condensation modulant V Min 0,5 0,5

Costruttore - C80

Condensation modulant V Max 10 10

Costruttore - C81

Refroidisseur huile en cas de sonde KO 100 100

Costruttore - C82

Refroidisseur huile V Min 0 0

Costruttore

Page 10 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

- C82 Refroidisseur huile V Max 10 10

Costruttore - C83

Enable write parameter VFD condenser fan (for 10 min.)? 0 0

Costruttore - C84

Condens. fan VFD Require type: 0=BY AIN 1 1=BY AIN 2 2=BY KEY 3=BY MODBUS 4=MOTOPOTENTIOMETER 5= PID REG.

3 3

Costruttore - C85

Condens. fan VFD Rotation type: 0=CLOCKWISE 1=COUNTER-CLOCKWISE

0 0

Costruttore - C86

Condens. fan VFD Current limit: 0 0

Costruttore - C87

Condens. fan VFD Motor nominal voltage: 230 230

Costruttore - C88

Condens. fan VFD Motor nominal frequency: 50 50

Costruttore - C89

Condens. fan VFD Motor nominal speed 1440 1440

Costruttore - C90

Condens. fan VFD Motor nominal current 0 0

Costruttore - C91

Condens. fan VFD Motor cos-fi 85 85

Costruttore - C92

Condens. fan VFD 1 Control type 0=DIN 1=KEYPAD 2=MODBUS

3 3

Costruttore - C92

Condens. fan VFD 2 Control type 0=DIN 1=KEYPAD 2=MODBUS

3 3

Costruttore - C93

Condens. fan VFD Min. frequency 10 10

Costruttore - C94

Condens. fan VFD Max. frequency 50 50

Costruttore - C95

Condens. fan VFD Acceleration time 10 10

Costruttore - C96

Condens. fan VFD Deceleration time 10 10

Costruttore - C97

Condens. fan VFD Start function 0=RAMP 1=FLYING START

0 0

Costruttore - C98

Condens. fan VFD Stop function 0=COASTING 1=RAMP

0 0

Costruttore - C99

Condens. fan VFD V/F optimisation 0=NOT USED 1=AUTOMATIC BOOST

0 0

Costruttore - C0A

Condens. fan VFD Automatic restart 0=NOT USED 1=USED

0 0

Costruttore - C0B

Condens. fan VFD Motor control mode 0=FREQUENCY CONTROL 1=SPEED CONTROL

1 1

Costruttore - C0C

Condens. fan VFD V/F ratio selection: 0=LINEAR 1=SQUARED 2=PROGRAMMABLE 3=LINEAR WITH FLOW OPT

0 0

Costruttore - C0D

Condens. fan VFD V/F curve midpoint frequency 50 50

Costruttore - C0E

Condens. fan VFD V/F curve midpoint voltage: 50 50

Costruttore

Page 11 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

- C0F Condens. fan VFD Out voltage at 0 Hz 20 20

Costruttore - C0G

Condens. fan VFD Switching freq.: 15 15

Costruttore - C0H

Condens. fan VFD Advanced param. Address 0=READ 1=WRITE

0 0

Costruttore - C0H

Condens. fan VFD Advanced param. Address 0 0

Costruttore - C0H

Condens. fan VFD Advanced param. Address 0 0

Costruttore - C0I

Conversions press./temp. Gas 0=R22 1=R134A 2=R404A 3=R407C 4=R410A 5=R507 6=R290 7=R600 8=R600A 9=R717 10=R744

2 1

Costruttore - C0I

Conversions press./temp. Temp. 0=CONDEN 1=BULLE

0 0

Costruttore - C0J

Type protocole 0=--- 1=CAREL 2=MODBUS 3=LONWORKS 4=RS232 5=GSM

1 1

Costruttore - C0K

Vit. transmis. 0=1200 1=2400 2=4800 3=9600 4=19200

4 4

Costruttore - C0K

Adresse sérielle 1 1

Utente - P00

Language 0=ALLEMAN 1=ANGLAIS 2=FRANÇAIS 3=ITALIEN

0 2

Utente - P01 Lim. set-point refroid. minimum -12 0

Utente - P01 Lim. set-point refroid. maximum 0 15

Utente - P02 Reg. refroid bande 2 2

Utente - P02a

1 Compressor inverter regulation offset 0,2 0,2

Utente - P02a

1 Compressor inverter regulation hysteresis 0,2 0,2

Utente - P02a

1 Compressor inverter regulation differential 2 2

Utente - P02b

2 Compressors inverter regulation offset 0,2 0,2

Utente - P02b

2 Compressors inverter regulation hysteresis 0,2 0,2

Utente - P02b

2 Compressors inverter regulation differential 2 2

Utente - P02c

1 Compressor inverter minimum increase time 30 20

Utente - P02c

1 Compressor inverter maximum increase time 60 40

Utente - P02d

1 Compressor inverter minimum decrease time 30 20

Page 12 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

Utente - P02d

1 Compressor inverter maximum decrease time 60 40

Utente - P02e

2 Compressors inverter minimum increase time 30 20

Utente - P02e

2 Compressors inverter maximum increase time 60 40

Utente - P02f

2 Compressors inverter minimum decrease time 30 20

Utente - P02f

2 Compressors inverter maximum decrease time 60 40

Utente - P03 Regulation chiller compressors switch on zone 2 1,5

Utente - P03 Regulation chiller dead zone 2 2

Utente - P03 Regulation chiller compressors switch off zone 2 1,5

Utente - P04 Type de réglage compresseurs en bande latérale 0=PROPORTIONNEL. 1=PROP. + INT.

0 0

Utente - P05 Gest. compress. temps d'action intégrale 300 300

Utente - P05a

Type de réglage inverter 1 compresseur 0=PROPORTIONNEL. 1=PROP. + INT.

0 0

Utente - P05b

Gest. 1 inverter temps d'action intégrale 300 300

Utente - P05c

Type de réglage inverter 2 compresseurs 0=PROPORTIONNEL. 1=PROP. + INT.

0 0

Utente - P05d

Gest. 2 inverter temps d'action intégrale 300 300

Utente - P06 Minimum call time in dead zone startup time 10 10

Utente - P06 Maximum call time in dead zone startup time 20 20

Utente - P06a

Minimum call time in dead zone power off time 5 10

Utente - P06a

Maximum call time in dead zone power off time 10 20

Utente - P07 Alarme antigel refroid set -13 3

Utente - P07 Alarme antigel refroid diff 2 2

Utente - P07a

High glycol temperature alarm set-point 5 5

Utente - P07a

High glycol temperature alarm differential 2 2

Utente - P08 Gestion cond. set 14 14

Utente - P08 Gestion cond. diff. 4 4

Utente - P08 Condenser management offset 0 0

Utente - P09 Gest. condens. modulant set 10 10

Utente - P09 Gest. condens. modulant diff. 2 2

Utente - P10 Type de régl. condensation 0=PROPORTIONNEL. 1=PROP. + INT.

0 0

Utente - P11 Gestion conden. temps d'action integral 300 300

Utente - P12 Gestion refroidiss. huile set 80 80

Utente - P12a

Gestion refroidiss. huile ventilateurs diff 2 2

Utente - P12a

Gestion refroidiss. huile modulation diff 2 2

Utente - P13 Type de réglage refroidisseur huile 0=PROPORTIONNEL. 1=PROP. + INT.

0 0

Utente - P14 Gestion refr. huile temps d'action intégrale 300 300

Page 13 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

Utente - P15

Gestion Set 2 compresseur de 0=NON 1=ENTR. DIGITAL 2=BANDE HORAIRE 3=ENTR. ANALOGIQ 4= TEMP. EXTERNE.

0 0

Utente - P16 Set-point 2 0 0

Utente - P17 LUNDI set-point principal début à heure 7 7

Utente - P17 LUNDI set-point principal début à minute 30 30

Utente - P17 LUNDI set-point principal jusqu' a heure 22 22

Utente - P17 LUNDI set-point principal jusqu' a minute 30 30

Utente - P18 MARDI set-point principal début à heure 7 7

Utente - P18 MARDI set-point principal début à minute 30 30

Utente - P18 MARDI set-point principal jusqu' a heure 22 22

Utente - P18 MARDI set-point principal jusqu' a minute 30 30

Utente - P19 MERCREDI set-point principal début à heure 7 7

Utente - P19 MERCREDI set-point principal début à minute 30 30

Utente - P19 MERCREDI set-point principal jusqu' a heure 22 22

Utente - P19 MERCREDI set-point principal jusqu' a minute 30 30

Utente - P20 JEUDI set-point principal début à heure 7 7

Utente - P20 JEUDI set-point principal début à minute 30 30

Utente - P20 JEUDI set-point principal jusqu' a heure 22 22

Utente - P20 JEUDI set-point principal jusqu' a minute 30 30

Utente - P21 VENDREDI set-point principal début à heure 7 7

Utente - P21 VENDREDI set-point principal début à minute 30 30

Utente - P21 VENDREDI set-point principal jusqu' a heure 22 22

Utente - P21 VENDREDI set-point principal jusqu' a minute 30 30

Utente - P22 SAMEDI set-point principal début à heure 7 7

Utente - P22 SAMEDI set-point principal début à minute 30 30

Utente - P22 SAMEDI set-point principal jusqu' a heure 22 22

Utente - P22 SAMEDI set-point principal jusqu' a minute 30 30

Utente - P23 DIMANCHE set-point principal début à heure 7 7

Utente - P23 DIMANCHE set-point principal début à minute 30 30

Utente - P23 DIMANCHE set-point principal jusqu' a heure 22 22

Utente - P23 DIMANCHE set-point principal jusqu' a minute 30 30

Utente - P24 Type de sonde set-point à dist. 0=0..10V 1=4..20MA

1 1

Utente - P25 Limit. set-point distant (Set 1) -12 -12

Utente - P25 Limit. set-point distant (Set 2) 0 0

Utente - P26 Set compresseurs T. ext A -10 -10

Utente - P26 Set compresseurs set A -4 -4

Utente - P26 Set compresseurs T. ext B 0 0

Utente - P26 Set compresseurs set B -7 -7

Utente - P27

Gestion Set 2 condensat. de 0=NON 1=ENTR. DIGITAL 2=ENTR. ANALOGIQ 3= TEMP. EXTERNE.

0 0

Utente - P28 Set-point 2 condensat 12 12

Utente - P28 Set-point 2 condensat inverseur 9 9

Page 14 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

Utente - P28a

Limit. set-point distant cond. (Set 1) -12 10

Utente - P28a

Limit. set-point distant cond. (Set 2) 0 14

Utente - P29 Set cond. vent. T.ext A -5 -5

Utente - P29 Set cond. vent. Set A 8 8

Utente - P29 Set cond. vent. T.ext B 10 10

Utente - P29 Set cond. vent. Set B 14 14

Utente - P30 Set cond. modul. T.ext A -5 -5

Utente - P30 Set cond. modul. Set A 6 6

Utente - P30 Set cond. modul. T.ext B 10 10

Utente - P30 Set cond. modul. Set B 12 12

Utente - P31 Active entrée cons. distant 0=NON 1=OUI

1 1

Manutentore - A00

Active alarme pour limite franchi heures fonctionn. compresseurs 0=NON 1=OUI

1 1

Manutentore - A01

Seuil heures fonctionnem. compresseur 5 50

Manutentore - A02

Heures fonct. compresseur 1 heures réinit 0=NON 1=OUI

0 0

Manutentore - A03

Heures fonct. compresseur 2 heures réinit 0=NON 1=OUI

0 0

Manutentore - A04

Heures fonction. pompe 1 Heures Réinit 0=NON 1=OUI

0 0

Manutentore - A05

Heures fonction. pompe 2 Heures Réinit 0=NON 1=OUI

0 0

Manutentore - A06

Roue pompe tout 10 10

Manutentore - A07

Sorties digital de clavier 0=NON 1=OUI

0 0

Manutentore - A07

Sorties digital de clavier T. forçage 30 30

Manutentore -

Forzatura uscita digitale 1 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 2 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 3 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 4 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 5 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 6 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 7 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 8 0=NON 1=OUI

0 0

Page 15 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

Manutentore -

Forzatura uscita digitale 9 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 10 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 11 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 12 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 13 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 14 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 15 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 16 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 17 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 18 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 1 espansione 1 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 2 espansione 1 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 3 espansione 1 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 4 espansione 1 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 1 espansione 2 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 2 espansione 2 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 3 espansione 2 0=NON 1=OUI

0 0

Manutentore -

Forzatura uscita digitale 4 espansione 2 0=NON 1=OUI

0 0

Manutentore - A08

Sorties anal. de clavier 0=NON 1=OUI

0 0

Manutentore - A08

Sorties anal. de clavier T. forçage 30 30

Manutentore -

Forzatura uscita analogica 1 0 0

Manutentore -

Forzatura uscita analogica 2 0 0

Manutentore -

Forzatura uscita analogica 3 0 0

Manutentore Forzatura uscita analogica 4 0 0

Page 16 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

-

Manutentore -

Forzatura uscita analogica 5 0 0

Manutentore -

Forzatura uscita analogica 6 0 0

Manutentore -

Forzatura uscita analogica 1 espansione 1 0 0

Manutentore - A11

Activation Retard ON aprés blackout 0=NON 1=OUI

0 1

Manutentore - A11

Retard ON aprés blackout 60 30

Manutentore - A12

Date et heure: heure 0=NON 1=OUI

0 0

Manutentore - A12

Heure 0 10

Manutentore - A12

Date et heure: minute 0=NON 1=OUI

0 0

Manutentore - A12

Minute 0 0

Manutentore - A12

Date et heure: jour 0=NON 1=OUI

0 0

Manutentore - A12

Jour 1 3

Manutentore - A12

Date et heure: mois 0=NON 1=OUI

0 0

Manutentore - A12

Mois 1 8

Manutentore - A12

Date et heure: an 0=NON 1=OUI

0 0

Manutentore - A12

An 4 12

Manutentore - A12

Rég. Jour 0=NON 1=OUI

0 0

Manutentore - A12

Jour de semain 1=LUNDI, 2=MARDI 3=MERCREDI 4=JEUDI 5=VENDREDI 6=SAMEDI 7=DIMANCHE

4 5

Manutentore - A13

Active alarme 0=DESACTIVE' 1=ACTIVE POUR 60 S 2= ACTIVE CONTINU

2 2

Driver - Man - F1

EVD type 1=EVD400 PLAN 2=EVD400 TLAN

1 1

Driver - Man - F1

Battery enable 0=NON 1=OUI

0 0

Driver - Man - F2

EVD probes type 0=NOT SELECTED 1=SHEAT NTC-P(4-20)MA 2=SHEAT NTC-P(RAZ) 3=SHEAT NTC-NTC 4=SHEAT PT1000-P 5=SHEAT NTCHT-P(RAZ) 6=PID PRESS 7=PID NTC 8=PID NTC HT 9=PID PT1000

0 0

Page 17 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

Driver - Man - F3

D1 probes offset S1 0,2 0

Driver - Man - F3

D1 probes offset S2 0 0

Driver - Man - F3

D1 probes offset S3 0 0

Driver - Man - F4

D2 probes offset S1 3 0

Driver - Man - F4

D2 probes offset S2 0,7 0

Driver - Man - F4

D2 probes offset S3 0,1 0

Driver - Man - F5

Valve type 0=NOT SELECTED 1=ALCO EX5 2=ALCO EX6 3=ALCO EX7 4=ALCO EX8 330 PASSI/S 5=SPORLAN 0.5-20TONS 6=SPORLAN 25-30TONS 7=SPORLAN 50-250TONS 8=CAREL E2V**P 9=CAREL E2V 10=DANFOSS ETS-25/50 11=DANFOSS ETS-100 12=DANFOSS ETS-250/400 13=CUSTOM 14=ALCO EX8 500 PASSI/S

0 0

Driver - Man - F5

Refrigerant 0=--- 1=R22 2=R134A 3=R404A 4=R407C 5=R410A 6=R507C 7=R290 8=R600 9=R600A 10=R717 11=R744 12=R728 13=R1270

3 3

Driver - Man - F6

Custom valve minimum steps 7 0

Driver - Man - F6

Custom valve maximum steps 0 0

Driver - Man - F6

Custom valve closing steps 256 0

Driver - Man - F7

Custom valve opening extra 0=NON 1=OUI

0 0

Driver - Man - F7

Custom valve closing extra 0=NON 1=OUI

0 0

Driver - Man - F8

Custom valve phase current 0 0

Driver - Man - F8

Custom valve still current 0 0

Driver - Man - F9

Custom valve step rate 0 0

Driver - Man - F9

Custom valve duty-cycle 0 0

Driver - Man - FA

EEV1 stand-by steps EEV position with 0% power demand 0 0

Driver - Man - FB

EEV2 stand-by steps EEV position with 0% power demand 9 0

Driver - Man - FC

S1 probe limits pressure limits minimum value -1 -1

Page 18 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

Driver - Man - FC

S1 probe limits pressure limits maximum value 9,3 9,3

Driver - Man - FD

Driver 1 alarms delay Low Super Heat 120 120

Driver - Man - FD

Driver 1 alarms delay High Super Heat 20 20

Driver - Man - FE

Driver 2 alarms delay Low Super Heat 120 120

Driver - Man - FE

Driver 2 alarms delay High Super Heat 20 20

Driver - Man - FF

Driver 1 alarms delay LOP 120 120

Driver - Man - FF

Driver 1 alarms delay MOP 120 0

Driver - Man - FG

Driver 2 alarms delay LOP 120 120

Driver - Man - FG

Driver 2 alarms delay MOP 120 0

Driver - Man - FH

Driver EEV alarms delay - Delay probe error 10 10

Driver - Man - FI

PID direction driver 0= FORWARD 1= REVERSE

0 0

Driver - Auto - Q0

Warning re-install autosetup values 0=NON 1=OUI

0 0

Driver - Auto - Q1

Driver 1 circuit/EEV ratio for opening at startup 60 60

Driver - Auto - Q2

Driver 2 circuit/EEV ratio for opening at startup 60 60

Driver - Auto - Q3

Compressor type 0=NOT SELECTED 1=RECIPROCATING 2=SCREW 3=SCROLL 4=CABINET FLOADED 5=CABINET

1 0

Driver - Auto - Q3

Capacity control 0=NOT SELECTED 1=NONE OR IN STAGES 2=CONTINUOS SLOW 3=CONTINUOS FAST

-70 0

Driver - Auto - Q4

Evaporator type cool 0=NOT SELECTED 1=PLATES 2= SHELL AND TUBES 3=FINNED FAST 4=FINNED SLOW

-250 0

Driver - Auto - Q4

Evaporator type heat 0=NOT SELECTED 1=PLATES 2= SHELL AND TUBES 3=FINNED FAST 4=FINNED SLOW

15 0

Driver - Auto - Q5

Minimum satured temp. cool mode -2 -2

Driver - Auto - Q5

Maximum satured temp. cool mode 12 12

Driver - Auto - Q6

High SuperHeat alarm limit driver 1 0 0

Driver - Auto - Q7

High SuperHeat alarm limit driver 2 0 0

Valvola - Auto - N0

Driver 1 status 0=NON 1=OUI

0 0

Valvola - Driver 2 status

Page 19 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

Auto - N1 0=NON 1=OUI

0 0

Valvola - Auto - N2

CH-Percentage EEV opening driver 1 3 0

Valvola - Auto - N3

CH-Percentage EEV opening driver 2 0 0

Valvola - Auto - N4

CH-Proportional D1 0,1 0

Valvola - Auto - N4

CH-Integral time D1 0 0

Valvola - Auto - N5

CH-Proportional D2 196,9 0

Valvola - Auto - N5

CH-Integral time D2 0 0

Valvola - Auto - N6

CH-Set SHeat D1 123,4 0

Valvola - Auto - N6

CH-Low SHeat D1 123,4 0

Valvola - Auto - N7

CH-Set SHeat D2 80 0

Valvola - Auto - N7

CH-Low SHeat D2 12 0

Valvola - Auto - N8

Sheat dead zone D1 0,1 0

Valvola - Auto - N8

Derivative time D1 25,6 0

Valvola - Auto - N9

Sheat dead zone D2 0 0

Valvola - Auto - N9

Derivative time D2 0,4 0

Valvola - Auto - NA

Low SHeat int. time D1 0 0

Valvola - Auto - NA

LOP integral time D1 12 0

Valvola - Auto - NB

Low SHeat int. time D2 10 0

Valvola - Auto - NB

LOP integral time D2 3 0

Valvola - Auto - NC

MOP integral time D1 0 0

Valvola - Auto - NC

MOP delay D1 3 0

Valvola - Auto - ND

MOP integral time D2 2,2 0

Valvola - Auto - ND

MOP delay D2 257 0

Valvola - Auto - NE

Prop. gain dynamic D1 0=NON 1=OUI

1 0

Valvola - Auto - NE

Attent. Valve lock D1 22 0

Valvola - Auto - NF

Prop. gain dynamic D2 0=NON 1=OUI

0 0

Valvola - Auto - NF

Attent. Valve lock D2 60 0

Valvola - Auto - NG

Hi Tcond. prot. D1 2 0

Valvola - Auto - NG

High Tcond. int. time D1 0 0

Valvola -

Page 20 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

Auto - NH Hi Tcond. prot. D2 50 0

Valvola - Auto - NH

High Tcond. int. time D2 0 0

Password - Constructeur mot de passe 1234 1234

Password - Utilisateur mot de passe 1234 1234

Password - Maintenance mot de passe 1234 1234

Password - Password Debug 123 123

Password - Password Blocco tasti 22 22

Page 21 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

TIMERS

Rif. Model Brand Range Calibration Function

COMPRESSORS DATA

Rif. Model Brand Serial Note Voltage

MC1 CSH7593-90Y 40P Bitzer 1082700074 colleg. con inverter 400V

MC2 CSH7593-90Y 40P Bitzer 1082700075 colleg. con inverter 400V

PRESSURE SWITCH CALIBRATION

Rif. Model Brand High (bar) Diff. (vbar) Low (bar) Diff. (vbar) Note

SPH1-2 061F 9501 DANFOSS 20 6 * * PRESS. ALTA

SPHM1-2 KP7B DANFOSS 15 4 * * PRESS. ALTA MAN.

SPL1-2 KP1 DANFOSS * * 1 0,7 PRESS. BASSA

OTHER COMPONENTS

Rif. Model Brand Serial Note

EVV1+YTE.. POLYCOOL(MVL661.20-2.5) Siemens * Controllo termostatiche

N°1 PCO3 large Carel * CONTROLLO CHILLER

AIN1 FC302 DANFOSS 040110g282 Inverter (conto lavoro)

AIN2 FC302 danfoss 040210g282 inverter 2(conto lavoro)

FINAL CHECKS

Note

Test date 03/08/12

Test user Filippo Moressa

TEST FOR CLOSURE

Note

Checking plates / labels / schedules / manuals with language request

Check labels and compliance presence

Added instrumentation diagrams and manuals

END TEST

Note

Closing date

Officer packaging

Page 22 of 230N323

03/08/2012http://10.0.0.150:8080/scmfrigo/ufficiocollaudo/stampa_collaudo.php

PRESSURES TEST

Test Type: HP

Date:25/07/2012 18:01:21

Response: test OK Duration: 01:01

Lines Line alarm Press. start test Press. half test Press. end test

Suction Line 1 22,3 bar 22,3 bar 22,3 bar

Discharge Line 1 29,8 bar 29,8 bar 29,8 bar

Suction Line 2 22,1 bar 22,1 bar 22,1 bar

Discharge Line 2 29,4 bar 29,4 bar 29,4 bar

Suction Line 3 0 bar 0 bar 0 bar

Discharge Line 3 0 bar 0 bar 0 bar

Suction Line 4 0 bar 0 bar 0 bar

Discharge Line 4 0 bar 0 bar 0 bar

Page 23 of 230N323