FML-E3/FSL-E3
Fiber Loop Modules
GAMEWELL-FCI12 Clintonville Road, Northford, CT 06472-1610 USA Tel: (203) 484-7161 Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.2013 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9021-60783 Rev. A page 1 of 1
Description
The Gamewell-FCI, FML-E3 (Fiber-Optic Multi-Mode) andFSL-E3 (Fiber-Optic Single-Mode) are plug-in fiber loopmodules. The two types of fiber option modules are usedas one channel to transmit or receive communications withthe Gamewell-FCI RPT-E3-UTP (Network Repeater),ARCNET communication circuit.The following describe the two types of fiber option modules. The FML-E3 is a fiber module that allows the multi-
mode fiber to network between nodes. It features ST-style connectors with a maximum attenuation of 8db with 62.5/125 micrometer cable.
The FSL-E3 is a fiber module that allows the single-mode fiber to network between nodes. It features LC-style connectors with a maximum attenuation of 30db with 9/125 micrometer cable.
Each fiber loop module can Transmit (TX) or Receive (RX)fiber-optic cable connecting to the RPT-E3-UTP. Up to twofiber loop cards can be added to the RPT-E3-UTP, andboth cards may be combined in the same configuration.InstallationThe FML-E3/FSL-E3 modules are designed to be plugged-into their designated spots on the RPT-E3-UTP.
SpecificationsFML-E3 FSL-E3
Connections: ST style LC styleCable type: 62.5/125
micrometers9/125 micrometers
Operating Current: 0.053 amp 0.079 ampAlarm Current: 0.053 amp 0.079 ampOperating Temperature: 32 to 120 F (0 to 49 C)Relative Humidity: 0 to 93%,non-condensing at 90 F
(32 C)
Ordering InformationPart Number DescriptionFML-E3 Fiber Loop Module - Multi-mode fiber,
single TX or RX channel for RPT-E3-UTPFSL-E3 Fiber Loop Module - Single-mode fiber,
single TX or RX channel for RPT-E3-UTPRPT-E3-UTP Network Repeater, unshielded twisted-pair
for E3 or S3,optional FML-E3 or FSL-E3 fiber modules
UL is a registered trademark of Underwriters Laboratories Inc.
Features
FML-E3 (Multi-Mode Fiber)
FSL-E3 (Single-Mode Fiber)
Listed per ANSI/UL Standard 864 9th edition.
FML-E3 features ST-style connectors with a maximum attenuation of 8 dB with 62.5/125 micrometer cable
FSL-E3 features LC-style connectors with a maximum attenuation of 30db with 9/125 micrometer cable.
Offers the option to combine single and multi-mode modules on the same network card.
Provides a simple, plug-in card installation.
S1869
SIGNALING
DescriptionSpecificationsUL is a registered trademark of Underwriters Laboratories Inc.Features